FUNDAMENTALS OF CHILLED BEAMS ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

Similar documents
Milwaukee, WI. Darron Rempel

Chilled Beams. The new system of choice?

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

DISPLACEMENT VENTILATION

Chilled Beams Selection BY DAN INT-HOUT, FELLOW ASHRAE; AND LILLI WILBAR

2-Pipe fan coil terminal units were selected as the parallel system to handle the remaining sensible cooling load.

The pros and cons of chilled beams

Planning for Biomed Facility Puts Energy Efficiency Under Microscope

YORK BULKHEAD MOUNTED CHILLED BEAMS ENGINEERING GUIDE

Ceiling Radiant Cooling Panels

ACBC Floor Mounted Active Beam

Demonstration of modeling of radiant cooling system in design builder. Prashant Bhanware & Bharath Reddy

Underf loor For Schools

Walter Reed National Military Medical Center Bethesda, MD

EnergyPro Building Energy Analysis. Single-story School Building

EADQUARTERS. Thesis Revised Proposal. Stephanie Kunkel Mechanical Option

COMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST

ACBC Floor Mounted Active Beam

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1

Radiant Slab Cooling for Retail

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

Hourly Analysis Program v.4.1 Page 1 of 1

Large University Central Chiller Plant Design Considerations

Energy modeling in IDA ICE according to ASHRAE , app. G

Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619

Evaluation of Underfloor Air Distribution

Field Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE

Redland Tech Center Rockville, MD. Shawn Pepple Construction Management April 14, 2009

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Thermo Active Building Systems Using Building Mass To Heat and Cool

ARE YOUR VARIABLE SPEED PUMPING APPLICATIONS DELIVERING THE PREDICTED SAVINGS? IMPROVING CONTROL TO MAXIMIZE RESULTS

How to Reduce Energy Use in Your Labs by Up to 50%

ABSTRACT I. INTRODUCTION II. METHODS AND MATERIAL

Italcementi Center for Research and Innovation

Acutherm was spec d here. Building Automation Guide for Therma-Fuser Systems

Development of New Self-Comparison Test Suites for EnergyPlus

Energy Modeling of Dedicated Outdoor Air Systems for a Small Commercial Pilot Project

Sustainable Chilled Beam Design

Attaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016

LEED Commissioning and Actual Energy Use. John Kokko, P.Eng. LEED A.P. Vice President Enermodal Engineering

Gaige. Thesis Project Proposal. The. December 13 th, 2013 Matthew Neal, Mechanical Option Stephan Treado, Advisor. Proposed System Changes

David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option. Proposal

Application of Advanced Energy Technologies

Changes to the Minnesota Commercial Energy Code. Presented by: Andy Thielen, PE

Chilled Water Plant Redesign

Coppin State University Physical Education Complex - Technical Report 2

FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF

IECC Commercial Significant Changes Summary Tier I

McCarran International Airport Terminal 3

Doubling Down on Not Balancing Variable Flow Hydronic Systems BY STEVEN T. TAYLOR, P.E., FELLOW ASHRAE

2016 ASHRAE 90.1 Summary of Important Changes

Energy Modeling Applications for Existing Buildings

35% reduction in water use below code maximum 83% 88% 49% reduction in lighting power density 12%

VANZELM E N G I N E E R S

AHU Models Using Whole Building Cooling and Heating Energy Consumption Data

COMFORT-PRODUCTIVITY Building costs COMFORT-PERFORMANCE. Radiant Heating and Cooling Systems for Better Comfort and Energy Efficiency INDOOR - OUTDOOR

Senior Design Project for UNO. Design of the International Studies Building: An Environmental Analysis

Achieving acoustical standards in the classroom Study of HVAC systems and classroom acoustics

Ventilation. Demand-controlled ventilation (DCV) Demand-Controlled. With ASHRAE Standard Based

Energy Conservation and Mold Prevention at Ft. Polk Barracks 10 top items 1. Building air tightness

Next Generation: High Efficiency Energy Recovery Ventilator (ERV) 11/14/11 Dais Analytic Corporation

CONSTRUCTION REQUIREMENTS

Persistence Tracking in a Retro-commissioning Program

UC Berkeley Indoor Environmental Quality (IEQ)

Beam? previous. 50% over our. to our. the competition. reducing. first cost of the. project. shown at same. water flow

Potential Energy Savings from Optimized Schedule & Economizer Cycles in the Moody Library Building at UTMB

Teague Research Center

NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.40

Element Z General Design Requirements Existing Facilities Information

YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM

SGM Engineering, Inc.

Thesis Proposal. Park. Findlay 12/10/2010. Connor Blood

Final Thesis Report Mechanical System Alternatives Analysis

NASA Langley Research Center Administration Office Building One Hampton, VA. Project Proposal. Introduction to Proposed Design Alternatives Revision 1

While underfloor air. Learning objectives

Valent Packaged Rooftop Units A Fresh Choice for High-Percentage Outdoor Air Designs. Valent is a business of Unison Comfort Technologies.

Walter Reed National Military Medical Center Bethesda, MD

Retro-Commissioning in Hospitals

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

The ASHRAE Energy Code: How it Will Affect Your Projects

Proceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28

Mechanical Technical Assignment One ASHRAE Standard Compliance Evaluation

Product Catalog. Variable Refrigerant Flow (VRF) System VRF-PRC008C-EN. Air Source Heat Pump and Heat Recovery Outdoor Units.

Texas Hospital. Central Plant Redesign. Central Utility Plant SECOND PLACE HEALTH CARE FACILITIES, EXISTING 2013 ASHRAE TECHNOLOGY AWARD CASE STUDIES

Sensitivity of energy and exergy performances of heating and cooling systems to auxiliary components

WEST VIRGINIA UNIVERSITY ALUMNI CENTER Morgantown, West Virginia

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE

Sub Wet-Bulb Evaporative Chiller

Trane Engineers Newsletter Live. Specifying Quality Sound Presenters: Dave Guckelberger, Brian Reynolds, Art Hallstrom

Asset Energy Calculator Guidance

Model Based Building Chilled Water Loop Delta-T Fault Diagnosis

Recommissioning Energy Savings Persistence

CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH

Canada Published online: 28 Feb 2011.

City of Fort Collins Building Automation Systems Enhances Savings and Commissioning Efficiency Works Training

Live Transportation Research and Improvement Initiatives

Principles of Ventilation and Air Conditioning Design & Installation

Transcription:

FUNDAMENTALS OF CHILLED BEAMS ANSI/ASHRAE STANDARD 200-2015, METHODS OF TESTING CHILLED BEAMS NEMIC 2017

Hello! I am Davor Novosel I am here because I love to share what I know about chilled beams with you. You can find me at: dnovosel@nemiconline.org 703.499.3869 2 NEMIC 2017

Today 08:00 10:00 Fundamentals of Chilled Beams 10:00 10:15 Break 10:15 11:15 ANSI/ASHRAE Standard 200-2015, Methods of Testing Chilled Beams 11:15 noon Panel Discussion: TAB of Chilled Beams 3 NEMIC 2017

FUNDAMENTALS OF CHILLED BEAMS NEMIC 2017

Agenda 1. Concept 2. Passive Chilled Beam 3. Active Chilled Beam 4. Applications 5. System Design 6. Passive Beam Selection 7. Active Beam Selection 8. Commissioning 9. Example 5 NEMIC 2017

References Alexander, D. 2008. Design Considerations for Active Chilled Beams. ASHRAE Journal 50 (11): 50-58 Brzezenski, SP. 2012. Chilled Beams in Historic Buildings. ASHRAE Journal 54 (11): 48-55 Danfoss Application Guide - Hydronic balancing solutions Price Industries. 2017. Active & Passive Beams Engineering Guide REHVA_ASHRAE. 2014. Active and Passive Beam Application Design Guide Schurk, D. 2012. Chilled Beams Application and Control SEMCO. 2017. NEUTON TM Brochure. Controlled Chilled Beam Pump Module Setty, BS. 2011. Application Issues for Chilled Beam Technologies. ASHRAE Transactions, 117 (1) Trane. 2011. Understanding Chilled Beams Systems. Engineers newsletter 38-4 Trox. 2009. Chilled Beams Design Guide Vastyan, J. 2011. Chilled Beams Basics. HPAC Engineering (July): 26-28, 42 6 NEMIC 2017

1. CONCEPT 7 NEMIC 2017

A Brief History Willis Carrier induction unit First radiant ceiling system by Norwegian engineer Gunnar Frenger The first radiant ceiling installed in Gothenburg, Sweden The first radiant cooling device installed in Gothenburg, Sweden The first passive chilled beam installed in Stockholm, Sweden Rapid spread in Europe Introduced in USA by Trox 1920s 1940s 1960s 1972 1986 1990s 2000s 8 NEMIC 2017

Chilled beam = Linear induction unit 9 NEMIC 2017

Early 20 th century perimeter induction unit 10 NEMIC 2017

Tuttle & Bailey Induction air terminal unit Titus Fan-powered induction unit 11 NEMIC 2017

Types of chilled beams Passive chilled beam 12 NEMIC 2017

13 NEMIC 2017

Types of chilled beams Active chilled beam 14 NEMIC 2017

15 NEMIC 2017

Types of chilled beams Multi service chilled beam 16 NEMIC 2017

17 NEMIC 2017

Why beams? Physics! Water carries significantly more energy than air. Approximate comparison between water and air transporting equivalent energy 18 NEMIC 2017

Why beams? results in more efficient HVAC system with lower operating costs (?!) Virginia Commonwealth University new school of medicine; energy modeling by Sera Engineering 19 NEMIC 2017

2. PASSIVE CHILLED BEAM 20 NEMIC 2017

2. Passive Chilled Beam Passive beams provide sensible cooling from the water coil. Heating and ventilation must be handled by complementing systems. 21 NEMIC 2017

2. Passive Chilled Beam Heat transfer is mainly via natural convection. Warm air cooled by the heat exchanger flows downward into the space. 22 NEMIC 2017

2. Passive Chilled Beam Room air flow pattern of a passive beam in cooling 23 NEMIC 2017

2. Passive Chilled Beam Components of a typical passive chilled beam 24 NEMIC 2017

2. Passive Chilled Beam Exposed Passive CB Critical issues: wdistance between soffit and CB wdistance between side wall and CB wdistance of CB above floor Recessed Passive CB Critical issues: wdistance between soffit and CB wreturn air path wnet free area of return air path 25 NEMIC 2017

2. Passive Chilled Beam Roof / Ceiling Z > 0.25 B Z > 0.5 B B Exposed Passive CB < 14 ft Floor 26 NEMIC 2017

2. Passive Chilled Beam Roof / Ceiling Z > 0.25 B B Recessed Passive CB Z 0.5 B Z 0.5 B suspended ceiling 27 NEMIC 2017

3. ACTIVE CHILLED BEAM 28 NEMIC 2017

3. Active Chilled Beam Active beams are connected to both the primary air as well as the chilled- and heatedwater systems Constant volume supply air system Chilled water temperature > space dew point Requires dedicated outdoor air system to remove all (external + internal) latent loads 29 NEMIC 2017

3. Active Chilled Beam Active beams heat or cool a space through induction and forced convection. 30 NEMIC 2017

3. Active Chilled Beam Room air flow pattern of a typical linear active beam in cooling 31 NEMIC 2017

3. Active Chilled Beam ACTIVE BEAM TYPES Ceiling mounted wone-way and two-way discharge units wfour-way discharge units Bulkhead chilled beam Other type of active beams are Floor mounted Perimeter wall 32 NEMIC 2017

3. Active Chilled Beam Frenger Systems Halo - Active Chilled Beam Trox 2-way CB 33 NEMIC 2017

3. Active Chilled Beam Trox Type DID-R active chilled diffuser with radial air discharge 34 NEMIC 2017

3. Active Chilled Beam Price ACBV Vertical Active Beam/Induction Unit 35 NEMIC 2017

4. APPLICATIONS 36 NEMIC 2017

4. Applications Active beams are a good choice for the following applications: Spaces with typical heating and sensible cooling requirements Buildings with moderate internal latent loads Spaces with limited floor-to-ceiling heights Spaces where low noise levels are desired 37 NEMIC 2017

4. Applications Suitable building types for active CBs: Commercial office buildings Schools Hospital patient rooms Laboratories with high internal loads Hotels, dormitories 38 NEMIC 2017

4. Applications Applications NOT suitable for CBs: Building areas where humidity can be difficult to control (lobbies, atria, egress routes) Spaces with high latent loads (pools, etc.) Applications with high airflow/ventilation requirements, such as an exhaust driven lab Kitchens Data centers Spaces with high ceilings ( > 14ft.) 39 NEMIC 2017

4. Applications Passive beams are ideally suited to aisle ways or perimeters of large spaces, such as Offices Lobbies Conference centers Libraries Any other space that requires perimeter or additional cooling 40 NEMIC 2017

4. Applications Humidity control at all times is paramount to proper operation of chilled beam systems Dew point controller No weekend shutdowns Building pressurized at all times 41 NEMIC 2017

4. Applications When humidity controls fails 42 NEMIC 2017

4. Applications of chilled beams by climate zones Easy Medium: hot, humid summers Difficult: humid to tropical climate 43 NEMIC 2017

4. Applications Condensation risks Near entry points At perimeter, mixed-mode ventilation Building retrofits with leaky envelope Spaces with high variable latent loads: wlunch, coffee rooms wmeeting rooms 44 NEMIC 2017

4. Applications Condensation prevention System meets 100% latent load at peak dew point design Limit overcooling Chilled water shut-off or reset Reset air temperature VAV for variable occupancy 45 NEMIC 2017

4. Applications Condensation prevention Chilled water reset in response to space dew point 46 NEMIC 2017

5. SYSTEM DESIGN 47 NEMIC 2017

5. System Design Chilled beam systems require Source of chilled water at two different temperatures Source of hot water (4 pipe system) Supply of primary air 48 NEMIC 2017

5. Chilled Water System Design DOAS 54 F By-pass 42 F Active CB Dedicated Chillers Two independent chilled water loops Allows for smaller chiller servicing ACB loop Allows for high chiller efficiency of the ACB loop Higher first cost ACB Loop By-pass 62 F 56 F 49 NEMIC 2017

5. Chilled Water System Design DOAS 56 F ACB Loop 42 F 54 F 62 F Common chiller Chiller downsizing not possible Lower EER compared to separate loops Higher supply water temperature not feasible DOAS load significantly higher the ACB loop one 50 NEMIC 2017

5. Chilled Water System Design DOAS Control valve 56 F By-pass ACB Loop 54 F 42 F 62 F Common chiller with heat exchanger Chiller downsizing not possible Lower EER compared to separate loops Higher supply water temperature not feasible DOAS load significantly higher the ACB loop one Requirement for isolated chilled water loops 51 NEMIC 2017

5. Chilled Water System Design Packaged DOAS Active CB ACB Loop By-pass 62 F 56 F Chiller / Decouples DOAS Allows for smaller chiller servicing ACB loop Allows for high chiller efficiency of the ACB loop 52 NEMIC 2017

5. Chilled Water System Design Source: SEMCO A Fläkt Woods Company. 5504ASCENDANT Health Care Brochure - SEMCO 2016-02 53 NEMIC 2017

5. Chilled Water System Design Primary airflow (PA) is based on largest of: Minimum outdoor airflow required (ASHRAE 62.1) Airflow required to offset space latent load (depends on dew point of PA) Airflow needed to induce sufficient room air (RA) to offset the space sensible cooling load PA RA SA 54 NEMIC 2017

5. System Design-Controls Beam system controls typically include the following: Zone control Beam water temperature control Primary air-conditioning control Condensation prevention 55 NEMIC 2017

5. System Design-Controls Airside Control Primary air w Use fully self-contained volume flow limiter (VFL) w VFL s are recommended when an AHU also supplies VAV terminals. Monitor space dew point w Use small quantity of high quality sensors w Do not use rel. humidity sensors w Locate sensors in room not in ceiling Reduce primary moisture content to control space rel. humidity w DOAS 56 NEMIC 2017

5. System Design-Controls Volume flow limiter (VFL) 57 NEMIC 2017

5. System Design-Controls Monitor space dew point 58 NEMIC 2017

5. System Design-Controls Waterside Control Variable water flow w Pressure independent control Two position valves or modulating valves 6-way valves can be used on 4 pipe into 2 pipe chilled beams Reschedule or shut off chilled beam water supply only if primary moisture content cannot reduced 59 NEMIC 2017

5. System Design-Controls Beam zone temperature control using constant-volume primary airflow. 60 NEMIC 2017

5. System Design-Controls Beam zone temperature control using variable volume primary airflow. 61 NEMIC 2017

5. System Design-Controls Variable flow system, typical application in FCU heating-cooling systems and any kind of terminal unit (e.g. AHU) 62 NEMIC 2017

5. System Design-Controls Constant flow system, typical application in FCU heating-cooling systems and in AHU 63 NEMIC 2017

5. System Design-Controls 64 NEMIC 2017

5. System Design-Controls Heating with active chilled beams 65 NEMIC 2017

5. System Design-Controls Heating with active chilled beams Active CB available in 2-pipe or 4-pipe configuration Application limited by output capacity: w Zones < 300 Btu/h/ft² w Zones 300 400 Btu/h/ft² Air discharge towards window at 75fpm w Zones > 400 Btu/h/ft² 66 NEMIC 2017

5. System Design-Controls 6-way ball valve is a combination valve for connecting heating and cooling 4 pipe system into a single coil 67 NEMIC 2017

5. System Design-Controls 68 NEMIC 2017

5. System Design-Controls 69 NEMIC 2017

6. PASSIVE BEAM SELECTION 70 NEMIC 2017

6. Passive Beam Selection The performance of a passive beam is dependent on several factors: Water flow rate Mean water temperature and surrounding air temperature Shroud height Free area of the air paths (internal and external to the beam) Location and application 71 NEMIC 2017

6. Passive Beam Selection General Application Parameters Room Temperature Water Temperatures Design Sound Levels Cooling Capacity Ventilation Requirement, 74 F to 78 F in summer, 68 F to 72 F in winter Cooling 55 F to 58 F EWT, 5 F to 8 F T < 40 NC 500 Btu/h ft CB 0.1 to 0.5 cfm/ft 2 floor area 72 NEMIC 2017

6. Passive Beam Selection The difference between the mean water temperature, t w, defined as: t w = t supply +t return 2 and the surrounding (coil inlet) air temperature is one of the primary drivers of the beam performance 73 NEMIC 2017

6. Passive Beam Selection Passive beam capacity vs. vs. difference between mean water and room air temperature 74 NEMIC 2017

6. Passive Beam Selection Passive beam capacity vs. water flow 75 NEMIC 2017

6. Passive Beam Selection Re = u d h v where Re = Reynolds Number (non dimensional) u = velocity (ft/s) d h = hydraulic diameter (ft) ν = kinematic viscosity (ft 2 /s) Below are two links to online Reynolds Number Calculators. Reynolds Number Calculator Reynolds Number Calculator Temperature ( o F) Kinematic Viscosity - ν - (10-5 ft 2 /s) 32 1.924 40 1.664 50 1.407 60 1.210 70 1.052 80 0.926 90 0.823 100 0.738 120 0.607 140 0.511 160 0.439 180 0.383 200 0.339 212 0.317 76 NEMIC 2017

6. Passive Beam Selection Factors that affect performance of passive beams A passive beam installed above a perforated ceiling 77 NEMIC 2017

6. Passive Beam Selection The impact on the capacity of the gap between a passive beam and building structure 78 NEMIC 2017

6. Passive Beam Selection Expected velocities below an 18 in. wide passive beam 79 NEMIC 2017

7. ACTIVE BEAM SELECTION 80 NEMIC 2017

7. Active Beam Selection The performance of an active beam is dependent on several factors: Active beam configuration Coil circuitry Primary air flow (plenum pressure) Water flow 81 NEMIC 2017

7. Active Beam Selection General Application Parameters Room Temperature Water Temperatures Design Sound Levels Cooling Capacity, 74 F to 78 F in summer, 68 F to 72 F in winter Cooling 55 F to 58 F EWT, 5 F to 8 F T < 40 NC 1,000 Btu/h ft CB Water Temperature Heating 110 F to 130 F EWT, 10 F to 20 F T Heating Capacity Ventilation Requirement Ventilation Capability 1,500 Btu/h ftcb 0.1 to 0.5 cfm/ft 2 floor area 5 to 30 cfm/ft Primary Air Supply Temp. 50 F to 65 F Inlet Static Pressure 0.2 in. w.g. to 1.0 in. w.g. external 82 NEMIC 2017

7. Active Beam Selection Transfer efficiency = measure for the overall performance of an active beam This is the ratio of total heat transferred by the coil per unit volume of primary air: The higher the efficiency, the higher the energy savings The transfer efficiency is largely dependent on the airside load fraction and the sensible heat ratio. 83 NEMIC 2017

7. Active Beam Selection The higher the sensible load fraction is, the smaller the beam nozzle can be, resulting in a higher induction ratio, defined as the ratio of the induced mass air flow to that of the primary air: Smaller nozzles result in higher plenum pressures for a fixed primary air flow rate. Larger nozzles will have a lower induction ratio but allow more primary air to be supplied, though at a lower transfer efficiency 84 NEMIC 2017

7. Active Beam Selection Transfer efficiency is reduced by increasing nozzle size 85 NEMIC 2017

7. Active Beam Selection Increased nozzle size Capacity of a typical active beam vs. primary air flow 86 NEMIC 2017

7. Active Beam Selection Capacity vs. air volume 87 NEMIC 2017

7. Active Beam Selection Active beam capacity vs. water flow 88 NEMIC 2017

7. Active Beam Selection Active beam capacity vs. difference between the mean water and room air temperatures 89 NEMIC 2017

8. COMMISSIONING 90 NEMIC 2017

8. Commissioning Initial steps should ensure that the coil is free of dust and debris by visual inspection the beam is free of all transportation packaging. the primary air supply rate and temperature is within tolerance. the supply water flow rate(s) and temperature(s) are within tolerance 91 NEMIC 2017

8. Commissioning Control Components Testing of the typical sensors associated with the beam as appropriate: Breathing on dew-point or humidity sensors. This local increase of humidity from breath should be sufficient to develop moisture on the device. Dripping water on condensation sensors Opening the window to trip the contact 92 NEMIC 2017

9. EXAMPLE Active Beams in a Computer Lab 93 NEMIC 2017

9. Example - Active Beams in a Computer Lab This space is a school computer lab designed for 26 occupants, 26 computers with one LCD monitor each, a projector, three printers, and T8 florescent lighting Temperature set-point is 75 F at 50% RH in the summer The room is 50 ft long, 50 ft wide, and has a floor-to-ceiling height of 9 ft. The ceiling is exposed, with possible duct connections in the interior of the space. 94 NEMIC 2017

9. Example - Active Beams in a Computer Lab Assumptions Infiltration is minimal, and is neglected for the purposes of this example. The specific heat and density of the air for this example will be 0.24 Btu/lb F and 0.075 lb/ft2 respectively. The air handling system utilizes energy recovery to provide 65 F at 50 F dew point. 95 NEMIC 2017

9. Example - Active Beams in a Computer Lab Selected Active CB Specifications Total Capacity 33044 Btu/h Quantity 6 Length 96 in. Width 24 in. Airflow 780 cfm Throw 17 ft. Air Pressure Drop 0.76 in. Transfer Efficiency 42.4 Btu/h cfm Water Flow Rate 6.48 gpm Water Pressure Drop 4.6 ft hd NC 30 Required System Performance 32902 Btu/h 632 cfm Supply Air Temperature : 65 F 96 NEMIC 2017

9. Example - Active Beams in a Computer Lab 97 NEMIC 2017

Thanks! Any questions? You can find me at: dnovosel@nemiconline.org 703-499-3869 98 NEMIC 2017

Next ANSI/ASHRAE Standard 200-2015, Methods of Testing Chilled Beams 99 NEMIC 2017