Lighting. Document Information. Approval. Document History. Document Name Roche Energy Efficiency Standard: Lighting. Document Owner Thomas Wolf, LSE

Similar documents
General Lighting Recommendations

Light levels should be appropriate for the task and per the following guide in Part 1 - General.

Light levels should be appropriate for the task and per the following guide in Part 1 - General.

Units. Lighting quantity is primarily expressed in three types of units.

Units. Lighting quantity is primarily expressed in three types of units.

Bulbs and Ballast. Regular Product : Bulbs and Ballast

KEITH DAVIS, LC, IESNA LIGHTING SPECIALIST

COMPLIANCE OVERVIEW. Module 2: Compliance Overview 4/6/2017 COMPLIANCE AND ENFORCEMENT

B. Prismatic acrylic diffusers for fluorescent fixtures shall be A12 pattern and at least 1/8 thick. Do not use styrene lenses.

Lighting Energy Management

Building Operator Certification Level I

Chapter 4.10: Lighting Systems

m nlighting Compliance Documentation Page 1

SECTION LIGHTING

MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2)

MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2)

Chapter XXX. Outdoor Lighting Standards.

A Cover. lighting ENERGY EFFICIENT

INTERIOR & EXTERIOR LIGHTING DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 LUMINAIRES

MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2)

Units. Lighting quantity is primarily expressed in three types of units.

NATIONAL TECHNICAL UNIVERSITY OF ATHENS School of Electrical and Computer Engineering. Lighting Controls. Lambros T. Doulos.

MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2)

Solano Community College District Lighting Standards

This document is provided as a reference for the design team and should not be used directly as written project specifications.

We see that the BD+C category is made up of two kinds of construction: New Construction, and Core and Shell

Spiral T2 10,000 & 8,000 hours

Guide to new, energy-efficient lighting applications for your business and properties

2009 IECC Commercial Lighting Requirements

Transitioning to LED Lighting Technology Helps Facilities Reduce Lighting Energy Consumption and Costs

Verification Methods For New Zealand Building Code Clause G8 Artificial Light

Energy Efficient Lighting Opportunities. Paul Vrabel, LC, PMP Principal ICF International

2015 WSEC: Electrical and Lighting Systems

Energy efficient lighting

2D Watt-Miser. Integral. Compact Fluorescent Lamp 18W. GE Lighting DATA SHEET. Product information. Features. Application areas.

B. Verify that electrical installation may be made in complete accordance with all pertinent codes and regulations and the original design.

Introduction to LED Lighting

8. LIGHTING SYSTEM. Syllabus Lighting System: Light source, Choice of lighting, Luminance requirements, and Energy conservation avenues

Smart Lighting An Overview

E3T Energy. Task/Vertical/Ambient Lighting. Emerging Technologies Showcase

2015 WSEC: Electrical and Lighting Systems

GE Lighting. raise the bar. Albeo LED Luminaires for high and low-bay environments

PRIMES. product group street lighting. Presented by

NONRESIDENTIAL LIGHTING Key Changes to mandatory and prescriptive lighting requirements in California s 2016 Building Energy Efficiency Standards

ARCHIVED. Compliance Document for New Zealand Building Code Clause G8 Artificial Light. Prepared by the Department of Building and Housing

center for the arts towson university Architectural Engineering Lighting/Electrical Benjamin Mitten Spring 2005

A. This Section includes lighting design criteria, interior and exterior luminaires, lamps and ballasts, as well as related installation guidelines.

HONG KONG GREEN BUILDING COUNCIL

Commercial Lighting Renovation Guide

new equipment & construction

Suggested Environmental Considerations for Lighting Equipment

2019 Lighting Retrofit Rebate Instructions. City of Winthrop

Daylighting Used With Task Lighting PHOTO: NJ AGRICULTURAL EXPERIMENT STATION

Guide to Lighting Control in Buildings

2019 Lighting Retrofit Rebate Instructions. City of Le Sueur

Lighting and Daylighting for The 21 st Century School

2019 Lighting Retrofit Rebate Instructions. City of Brownton

ENERGY EFFICIENT LIGHTING CONTROLLING THE COST OF ENERGY FOR OFFICE, EDUCATIONAL, RETAIL AND INDUSTRIAL ENVIRONMENTS

lighting control in schools k-12

WIRELESS CONTROLS WHAT, WHY, WHERE AND WHEN SHOULD THEY BE CONSIDERED?

The baseline building system for compliance with Senate Bill 668 is defined by Appendix G,

IV ENGINEERING OF ENVIRONMENTAL ENERGY ANALYSIS OF GHG REDUCTION POSSIBILITIES IN LATVIA BY IMPLEMENTING LED STREET LIGHTING TECHNOLOGIES

Next Generation Lighting Systems Page 1 of INDOOR Competition Two Entrant Guide

OWNERS: EASTSIDE 2008 EQUITIES INC. DEVELOPED, MANAGED AND LEASED: EAST PORT PROPERTIES LIMITED

SECTION LIGHTING

Building Operator Certification Level I

New Jersey: K-12 Schools Energy Efficiency / PCB Training Webinar. U.S. Environmental Protection Agency (EPA) Region 2 December 15, 2011

LIGHTING TECHNICAL SHEET

LIGHTING SOLUTIONS for Commercial Property Management

Why ENELTEC LED Tubes?

Challenges When Deploying LED Lighting Retrofits

Newsletter. Siemens EngineeringAdvantage. Introduction. Issue In This Issue:

UC Irvine s Student Center Interior Lighting Upgrade Vicky Do Energy Analyst Joseph Fleshman, P.E. Project Manager

Technical Requirements Table, V3.1 Technical Requirements: Luminaires

FAQ on LED Lighting. Part 1: General Questions

LiDe 3 Berlin October 8, 2015

FLUORESCENT HIGH BAY ENERGY-SAVING LIGHTING SYSTEMS

COLUMBIA LIGHTING ENERGY SOLUTIONS. VersaBay. Fluorescent High Bay

Lighting and sensors: Reducing energy costs in commercial buildings

TABLE Lighting Power Densities Using the Building Area Method

LED lighting solutions based on Light Engines technology. Hervé Barcelo October 2011

LED RESALE & WIRELESS CONTROLS BY MAGNUM INNOVATIONS

Rhode Island Commercial Codes FAQs

TDS-NAVFAC EXWC-PW-1601 Sep Interior LED Lighting Technology Navy Energy Technology Validation (Techval) Program

Solid State Lighting Annex: Performance Tiers for Non-Directional Lamps ANNEX ADOPTED TIER LEVELS

PRESCRIPTIVE APPROACH. 1. Actual and Allowed LPD 2. Complete Building Method 3. Area Category Method 4. Tailored Method

Compliance to the IgCC. September 29, 2011

Forum M: Top 10 Cost Reduction Strategies for Science Facility Operations and Maintenance

Technical Report 1. Dan MacRitchie. Lighting/Electrical 9/17/12. University of California, Riverside Student Recreation Center.

2010 CA Higher Education Sustainability Conference

Lighting Commercial Spaces 101. An Introduction to LED and Lighting Controls

Business Energy Rebates Application

Eco Engineering and Energy Solutions

Project 2 : Integration with Design Studio 5 Lighting Analysis

Decisions, Decisions: Inform Your Lighting Choices

Title 24 Part 6 and Part 11 Building Code Triggers

EarthTronics products. About us. Where Efficiency Meets Innovation T5 & T8 Linear. Founded in 2007, EarthTronics, Inc. is a Michigan based

LED & CONVENTIONAL LIGHTING SYSTEMS COMPARISON STUDY

Association of Energy Engineers. A Practical Guide to LED Product Selection & Applications

Transcription:

Document Information Document Name Roche Energy Efficiency Standard: Document Owner Thomas Wolf, LSE Approval 18 Feb 2015 John Parodi, CESA 20 Feb 2015 Peter Schnurrenberger, LS Document History Version Changes Effective Date 1.0 First Edition 31 st March 2009 2.0 Second Edition 1 st March 2015 Roche Energy Efficiency Standard Rev 2.0 Page 1 of 7

1 Scope This Roche Energy Efficiency Standard is binding on all Roche companies. This standard applies to all new installations or when modifying, refurbishing, or expanding existing systems, regardless of ownership or rental/ lease arrangement. It defines minimum criteria for designing energy-efficient lighting. These requirements are intended to maintain a certain degree of design flexibility. They may be outperformed where appropriate and when yielding higher energy efficiencies or better economics (i.e. higher NPVs). The Standard takes precedence over locally applicable laws, regulations and standards whenever it exceeds the requirements therein. Deviation from this standard is acceptable - if alternative designs giving lower energy consumption or higher efficiency are implemented - if overruled by non-financial stipulations (e.g. health protection, statutory requirements, security, video quality, etc.), in which case deviation must be confined exclusively to the conflicting feature(s) of a design - if alternative designs yielding a higher net present value (NPV) - calculated as described in Group Directive K18, section 4.2 (Full-cost lifecycle analysis) - are implemented Any deviation must be documented in-house for potential internal and external review. For identical design situations, generic evaluation is appropriate. Not covered by this standard are lights that are integral to packaged equipment and emergency lighting. These may be covered by other standards. Roche Energy Efficiency Standard Rev 2.0 Page 2 of 7

2 Target The design of lighting systems must comply with the following design criteria: 2.1 design target values The following tables list illuminance levels and lighting power density (LPD) for typical areas and spaces 1. The first table provides the target values in Lux and Watts/m 2, and the second table provides the same targets in units of Footcandles and Watts/ft 2. Illuminance levels These illuminance levels should be used as guidance for each of the spaces listed, unless otherwise required by statutory requirement, health, safety or other limitations. In any case, lighting levels must not be higher than stipulated by local norms and standards 2. The values listed indicate the illuminance levels for the actual task area 3, on the working plane. The illuminance levels are to be met in real conditions, accounting for degradation due to age and upkeep 4. Power Density (LPD) LPD s must not exceed the maximum permissible values and should meet the target values for each space type 5. The LPD values refer to the net illuminated floor area. The values listed comprise all lighting within a specific space including plug-in lights, accent and architectural lighting. Roche Energy Efficiency Standard Rev 2.0 Page 3 of 7

INDOOR Traffic Zones Private Open OUTDOOR SPACE TYPE Lux Watts/m 2 max target Entrance Lobby 8 Elevator Lobby 6 Corridors 4 100 Staircases 4 1 Elevators 4 Pass-Through Areas in Office 5 work area 500 surrounding area 300 9 6 work area 500 surrounding area 300 8 5 Storage Areas in 100 4 2 Conference & Meeting Rooms 300 11 8 Auditoriums (House ) 300 10 6 Auditoriums (Podium ) 750 15 8 Classrooms 400 8 5 Manufacturing Areas (non-precision work) 6 300 8 3 Manufacturing Areas (precision work) 7 750 13 8 Laboratories 8 500 10 5 Mail Rooms 500 10 5 High-Bay warehouse 9,10 100 4 1 Low-Bay Warehouse 9,10 100 3 1 Cold Store 10 100 4 1 Interior Storage 10 100 3 1 Archive 10 200 6 2 Food Preparation 500 12 5 Dining Areas 150 8 2 Restrooms 150 6 5 Locker Rooms/Showers 100 5 2 Fitness Center/Gym 300 7 3 Medical Rooms 500 12 5 Mechanical/Electrical Spaces 10 150 5 2 Server Rooms / Data Centers 10 500 10 5 Parking Lots 5 1 0.5 Exterior Walkways 50 1.5 0.5 Building Entrances 40 7 0.5 Internal Roadways 10 1 0.5 Parking Garages 20 1.5 1 Exterior Storage 10 100 4 1 Roche Energy Efficiency Standard Rev 2.0 Page 4 of 7

INDOOR Traffic Zones Private Open OUTDOOR SPACE TYPE Footcandles Watts/ft 2 max target Entrance Lobby 0.8 Elevator Lobby 0.6 Corridors 0.4 10 Staircases 0.4 0.1 Elevators 0.4 Pass-Through Areas in Office 0.5 work area 50 surrounding area 30 0.9 0.6 work area 50 surrounding area 30 0.8 0.5 Storage Areas in 10 0.4 0.2 Conference & Meeting Rooms 30 1.1 0.8 Auditoriums (House ) 30 1.0 0.6 Auditoriums (Podium ) 75 1.5 0.8 Classrooms 40 0.8 0.5 Manufacturing Areas (non-precision work) 6 30 0.8 0.3 Manufacturing Areas (precision work) 7 75 1.3 0.8 Laboratories 8 50 1.0 0.5 Mail Rooms 50 1.0 0.5 High-Bay warehouse9,10 10 0.4 0.1 Low-Bay Warehouse 9,10 10 0.3 0.1 Cold Store 10 10 0.4 0.1 Interior Storage 10 10 0.3 0.1 Archive 10 20 0.6 0.2 Food Preparation 50 1.2 0.5 Dining Areas 15 0.8 0.2 Restrooms 15 0.6 0.5 Locker Rooms/Showers 10 0.5 0.2 Fitness Center/Gym 30 0.7 0.3 Medical Rooms 50 1.2 0.5 Mechanical/Electrical Spaces 10 15 0.5 0.2 Server Rooms / Data Centers 10 50 1.0 0.5 Parking Lots 0.5 0.1 0.05 Exterior Walkways 5 0.15 0.05 Building Entrances 4 0.7 0.05 Internal Roadways 1 0.1 0.05 Parking Garages 2 0.15 0.1 Exterior Storage 10 10 0.4 0.1 Roche Energy Efficiency Standard Rev 2.0 Page 5 of 7

2.2 Design Rules and Guidelines 11 In addition to compliance with the above-stated targets for illuminance and LPDs the following rules and guidelines must be followed: 2.2.1 Design Criteria Overall lighting quality should be considered, including o Overall light distribution o Integration with architectural design o Availability of daylighting o Type of light o Deterioration of light levels o Glare o Surface brightness o Flexibility for varying activities o Light density variation o Color rendering The use of incandescent bulbs is not permitted. LED technology is the prescribed standard for all areas. For applications where LED technology is not currently practical or the most efficient, alternate lighting technology may be considered with the provision to facilitate LED technology in the future. The indoor use of HID (high intensity discharge) systems is not permitted. In areas with high ceilings, the use of high bay LED fixtures is preferred. Outdoor and architectural lighting must be designed to minimize light pollution. Exit signs must not be more than 5 W each. fixtures, drivers, ballasts, transformers, circuit boards and other associated components should be designed and located in such a way as to allow for easy access for cleaning, maintenance, repair and replacement, as well as for heat dissipation and moisture protection. In case fluorescent systems are exceptionally used they must utilize T5. utilize electronic ballasts with the lowest sound rating available, no PCBs, minimum ballast factor (BF) of 0.95 (except where lower BF is needed to meet LPD targets), total harmonic distortion (THD) less than 10% (electromagnetic ballasts are not permitted). be selected with mercury content lower than levels limited by applicable laws and regulations 12 but not more than 5 mg for each linear fluorescent lamp or more than 3 mg for each compact fluorescent lamp. be recycled or disposed of properly and in accordance with local jurisdictional requirements. Roche Energy Efficiency Standard Rev 2.0 Page 6 of 7

2.2.2 Control Concept An overall lighting design and control concept must be developed to assure energy-efficient, high quality lighting resulting in the best life cycle cost. Such a concept should be based on consideration of economic efficiency according to the rules contained in Group Directive K18, section 4.2. At a minimum, the following control strategies must be evaluated: The use of photo-sensors to adjust and reduce artificial light levels to supplement daylighting as needed. The use of occupancy sensors in particular in areas typically not or seldom occupied or requiring intermittent lighting during normal working hours. Large, open areas should be divided into smaller areas of control to allow for independent and local lighting control of each area. Scheduled, automated lighting controls to turn off lights during unoccupied times and non-working hours. Local over-rides should be provided to allow for lighting in a limited area after normal working hours. Overrides should be for a limited time and require repeated activation if needed. monitoring systems to verify proper lighting control. Automated control of outdoor lighting to prevent lighting during daytime periods with sufficient natural lighting and for limited duration use of architectural and landscaping lighting. LED lighting output gradually decreases over a lamp s life, and maintenance factors are typically applied to maintain required light levels accounting for degradation. This will result in higher installed light levels and energy uptake. To prevent overlighting and excessive energy use, control the fixture via dimmable driver to provide constant output. Ensure that light levels do not exceed the design illuminance levels for the space. Use of low voltage control for ease of maintenance and improved safety. 2.2.3 Maintenance Plan A comprehensive lighting maintenance plan should be developed and implemented to ensure sufficient illuminance and lighting quality, continuing energy-efficient operation, and minimized life cycle costs. The maintenance plan should, at a minimum, include the following: Appropriate maintenance procedures to keep lighting installations clean and in good working condition. Periodic monitoring of light output, to gauge lamp lumen depreciation. Re-lamping procedures should include cleaning of the fixtures. Where appropriate, relamp to longer life lamps. The economics and feasibility of group relamping should be considered and, where applicable, implemented. 3 Measures All group companies are required to develop and implement measures that ensure fulfillment of the defined criteria and specifications. Existing design, engineering and maintenance standards and procurement standards must be revised to include and account for these. In accordance with Section 4.3 (Optimizing Existing Assets) of Group Directive K18, existing lighting assets should be reviewed and analyzed and, as appropriate, a replacement/upgrade plan should be developed and implemented. 1 For spaces not listed here, use values of those spaces that house activities that match closest the actual activity. 2 For example, in EU the EN 12464 norm and in US the IES (Illuminating Engineering Society) Handbook. 3 Partial area in the work place in which the visual task is carried out. For places where the size and/or location of the task area is unknown, the area where the task may occur shall be taken as the task area. 4 Many factors, including fixture age, moisture, temperature, and dirt accumulation have negative effects on the light yield. The lighting design needs to take these into account. In calculations, the maintenance factor should account for these negative effects. 5 In order to ensure compliance, the architecture and interior must be designed appropriately (e.g. layout, surface reflectance, etc.). Furthermore, compliance may be achieved by adjusting the installation height of lighting fixture. 6 These levels are representative of a variety of manufacturing spaces. Actual targets may vary based on anticipated activity. 7 Manufacturing tasks which may require an exacting view of detail (e.g. certain assembly or inspection tasks) could require higher illuminance. 8 Laboratory benchtop tasks could require up to 1,000 lux. 9 Certain materials handling tasks, such as wrapping, packing, and labeling, require up to 300 Lux. 10 During unoccupied and inactive times lights must be switched off. 11 See the SHE Good Practice Wiki http://rochenet.roche.com/cse/good_she_practices_at_roche.htm for further design information. 12 For example, in Europe the Restriction of Hazardous Substances Directive (RoHS). Roche Energy Efficiency Standard Rev 2.0 Page 7 of 7