A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein.

Similar documents
SECTION SECONDARY UNIT SUBSTATIONS

Houston First Corporation Package 1 SECTION MEDIUM VOLTAGE FUSED SWITCH INTERRUPTER

SECTION OUTLET, PULL, AND JUNCTION BOXES

CONTENTS. B. System Design and Performance Requirements

SECTION ENCLOSED BUS ASSEMBLIES

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

A. Section includes busway and fittings including plug-in units.

SECTION GROUNDING

SECTION MOTOR CONTROL CENTER

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

SPECIFICATION FOR SIMPLEX SWITCHBOARDS

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

SECTION to 5000 AMPERE PLUG-IN AND FEEDER BUSWAYS - SPECTRA. A. Low-Voltage Plug-in Busway to 5000 ampere, 600 VAC

ADDENDUM NO. 1 BID AND CONTRACT DOCUMENTS FOR. BID No. 2019PW299

SECTION ENCLOSED BUS ASSEMBLIES

W-P-115C March 14, 1990 SUPERSEDING W-P-115B June 8, 1984 FEDERAL SPECIFICATION PANEL, POWER DISTRIBUTION

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding.

SECTION BUSWAYS

SPECIAL SPECIFICATION 6499 Environmentally controlled Communications Building

DIVISION 16. Electrical Specifications

SECTION PATIENT BED SERVICE WALLS

August 2011 DSC DeLand Campus COOP # SECTION INTERIOR DISTRIBUTION SYSTEM

31-SDMS-03 REV. 01 SPECIFICATIONS FOR

Technical Specifications

SECTION LOW-VOLTAGE SWITCHGEAR

OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE).

NOVADYNE 365 Lansdowne St. E., Unit 1, Peterborough, ON K9L 2A3

B. Scope of work includes replacement of all existing panels or panel interiors, reconnection of existing loads, electric services, etc.

ELECTRIC METERING GENERAL

SECTION CONDUITS AND BOXES PART 1- GENERAL. A. Work covered by this section includes the furnishing and installation of conduits and boxes.

OVERHEAD SERVICES - SECONDARY

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

METERING INSTALLATION

SECTION AUTOMATIC TRANSFER SWITCH

SUGGESTED SPECIFICATION for Low Voltage (600V) Generator Paralleling Switchboard

SECTION GENERAL ELECTRICAL REQUIREMENTS PART 1- GENERAL

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails.

HOTEL SPECIFICATION SECTION 08100

HOLLOW METAL DOORS AND FRAMES SECTION HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL

INDEX. Page SECTION 1.0: SCOPE Toronto Hydro Requirements Ontario Electrical Safety Code 1 SECTION 2.0: PURPOSE 1

37-SDMS-01 REV. 03 SPECIFICATIONS FOR

DIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION EARTHING AND EARTH FAULT PROTECTION

SERIES 800 / 810 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTER ASSEMBLIES

SECTION LOW-VOLTAGE TRANSFORMERS

Kaf-Tech Product Specification

SECTION ELECTRICAL MATERIALS AND METHODS

COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100

SECTION FACILITY LIGHTNING PROTECTION

SECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

A. American Society for Testing and Materials (ASTM): Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft.

SECTION A. ASTM B3 - Standard Specification for Soft or Annealed Copper Wire; 2013.

The fire resistance required for doors in this building is 1 (one) hour resistance in compliance with the below general specifications:

LOW-VOLTAGE SERVICE ENTRANCE SWITCHBOARDS SECTION D

a) Line and load compartments must be separated by a stable barrier.

UNDERGROUND SERVICES SECONDARY

(Condensed from National Electric Code)

UNIFIED FACILITIES GUIDE SPECIFICATIONS. Use for Southeast projects only **************************************************************************

SECTION FIELD PANELS

SECTION WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring.

SECTION BASIC ELECTRICAL REQUIREMENTS

Point Eight Power, Inc. Switchgear Specification Low Voltage UL 1558 Metal-Enclosed Switchgear

WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring.

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

OPERATING PROCEDURE NO. 310

SECTION GROUNDING AND BONDING

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

56-SDMS-01 REV. 01 SPECIFICATIONS FOR

E001 TERRACE VIEW APARTMENTS ELECTRICAL LEGEND, NOTES, AND ABBREVIATIONS 02/13/18 HUNT CLUB ROAD BLACKSBURG, VA KEY PLAN

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

SECTION (16071) - VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

SECTION LIGHTNING PROTECTION SYSTEM

SECTION GROUNDING AND BONDING

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC Van Dam Street Long Island City, NY ELECTRIC METER SHOP DEPARTMENT

ELECTRICAL SECTION 2

Power Electronics, Inc. Packaged Equipment Center Standard Construction and Design Features

SECTION LIGHTING. A. Section Basic Electrical Materials and Methods

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC).

University of Rochester October 17, 2008 Brooks Landing Business Center

Inspection Guide for PV Systems in One- and Two- Family Dwellings (For Rooftop Photovoltaic Systems meeting the Standard Plan)

HUMBOLDT COUNTY BUILDING & SAFETY DEPARTMENT CITY OF WINNEMUCCA BUILDING DEPARTMENT

APPLICATION FOR FINISHED BASEMENT PERMIT

SECTION CONVECTORS

SECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION PART 1 GENERAL

UNDERGROUND SERVICES (RESIDENTIAL) SINGLE FAMILY RESIDENTIAL, DUPLEXES, OR TOWNHOUSES

SECTION STEEL DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS

Transcription:

16470 PANELBOARDS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 16 An optional keynote to the Drawings follows major product titles, for A/Es using National CAD Standard. ************************************************************************************************************* PART 1 GENERAL 1.1 SUMMARY A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein. B. All materials shall be listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL). C. Related Sections: 1. 09900 - Painting. 2. 16120 - Wire and Cable. 3. 16475 - Overcurrent Protective Devices. 1.2 SYSTEM DESCRIPTION A. Panelboards used as service entrance equipment shall be NRTL labeled as service entrance equipment. 1.3 SUBMITTALS A. Submit shop drawings, manufacturer's literature, and technical data before starting work. B. All switchboards and panelboards submitted shall be designed and manufactured according to the latest revisions of the following specifications: 1. UL 50, UL 67, UL 89, Ul489, Ul 891, UL 1283, UL 1449 2. Nema AB-1, PB1, PB1.1, PB2, PB2.1 PB 2.2 3. NFPA 70 4. Federal Specifications: W-C-375B, W-P-115C PART 2 PRODUCTS 2.1 MANUFACTURERS A. Panelboards: 1. General Electric. 2. Siemens. 3. Square D. Project No. SPECIFICATION GUIDELINES 16470-1

4. Eaton Corp. 2.2 EQUIPMENT A. Distribution and Power Panelboards: 1. Interior: Provide fully rated plated copper bus. Plating shall run the entire length of the bus bar. Solid neutral and ground bar shall be copper. Maximum rating: 1200 amp. 2. Main breaker shall be horizontally mounted. Main breakers shall have conspicuous marking labels. 3. Trims shall have door with keyed lock. All locks shall be keyed the same. 4. Provide directory holder and typed directory for all circuits. 5. Enclosure shall be galvanized galvaneal steel constructed in accordance with UL50 and NEMA 250. Box end walls shall be blank. 6. Short circuit current ratings shall be equal to or greater than available fault current at point of application. NRTL listed series ratings may be utilized, where not in violation of NEC 240.86. Provide documentation of NRTL listed series rating used. 7. Surge Protective Devices (SPD) shall be provided when specified in the design and associated electrical plans, with optional peak surge current of 260kA. 8. Distribution panels for use at 120/208 volts shall ne NRTL listed with minimum integrated assembly rating of 22K AIC. 9. Distribution panelboards, 400 amperes and over, shall be provided with molded case circuit breakers tested and labeled according to UL 489. B. Lighting, Receptacle and Power Panelboards 1. Interior: Provide fully rated plated copper bus. Plating shall run the entire length of the bus bar. Solid neutral and ground bar to be copper. Maximum rating: 600amp. 2. Main breaker shall be vertically or horizontally located and have conspicuous marking labels. 3. Trims shall have door with keyed lock. All locks to be keyed the same. Provide trims with concealed door hinges and trim screws for panels 600 amps or less. 4. Provide directory holder and typed directory for all circuits. 5. Enclosure shall be galvanized steel constructed in accordance with UL50. Box endwalls shall be blank. 6. Short circuit current ratings shall be equal to or greater than available fault current at point of application. NRTL listed series ratings may be utilized, where not in violation of NEC 240.86. Provide documentation of NRTL listed series rating used. 7. Provide SPD s when specified in the design and associated electrical plans, with optional peak surge current of 100kA. 8. Minimum rating of breakers shall be as follows: a. Lighting and power panels for use at 120/208 volts: 225 amp maximum with circuit breakers rated at 10K AIC symmetrical at 240 volts. b. Lighting and power panels for use at 480/277 volts: 225 amp maximum with circuit breakers rated at 14K AIC symmetrical at 480 volts. 9. Interiors shall be factory assembled and designed to allow switching and protective devices to be replaced without disturbing adjacent units, without removing the main bus connectors, and allowing circuits to change without machining, drilling or tapping. Project No. SPECIFICATION GUIDELINES 16470-2

10. Branch circuits shall be arranged using double row construction unless narrow column panels are indicated. A nameplate shall be provided listing panel type and ratings. Circuit breakers shall be bolt-on type. 11. Unless otherwise noted, full size insulated neutral bars shall be included. Bus bar taps for panels with single pole branches shall be arranged for sequence phasing of the branch circuit devices. Neutral bussing shall have a suitable lug for each outgoing feeder requiring a neutral connection. A ground bus shall be provided in all panels. C. Boxes and Trims shall meet the following criteria: 1. Boxes shall be at least 20 inches wide made from code gage galvanized sheet steel. a. Provide minimum gutter space according to NEC requirements. b. Where feeder cables supplying the mains of a panel are carried through its box to supply other electrical equipment, the box shall be sized to include the additional required wiring space. c. At least 4 interior mounting studs with adjustable nuts shall be provided. 2. Switching device handles shall be accessible. a. Doors and panelboard trims shall not uncover any live parts. b. Doors shall have flush chrome plated handle with cylinder lock and catch, except doors over 48 inches in height shall have auxiliary fasteners top and bottom of door in addition to the flush type cylinder lock and catch. c. Panelboard switching devices with individual dead front doors shall be acceptable instead of standard door in trim design. d. Panelboard trim clamps shall be of the indicating type. 3. Exterior and interior steel surfaces of the trim shall be properly cleaned, primed with rust inhibiting phosphatic coating, and finished with manufacturer's standard gray paint. a. Trims for flush panels shall overlap the box for at least 3/4" all around. b. Surface trims shall have the same width and height as the box. c. Trims shall be mountable by a screwdriver without the need for special tools. d. After installation, trim clamps shall not be accessible when the panel door is closed and locked. 4. Panelboards exposed to the weather shall have NEMA type 3R raintight enclosure or NEMA 4X in corrosive environments. D. Electrical Components: 1. Main bus bars shall be fully rated copper bus bars, with plating shall running the entire length of the bus bar, and shall be sized according to NRTL standards to limit the temperature rise on any current carrying part to a maximum of 50 degrees C. above an ambient of 40 degrees C. maximum. Provide main circuit breakers, main lugs, or sub-feed lugs as required. 2. Each panelboard shall incorporate breakers as shown with AIC or higher, at the application voltage, than the available fault at its location along the electrical Project No. SPECIFICATION GUIDELINES 16470-3

distribution system, as determined by the short circuit study. Minimum rating of breakers shall be: a. Lighting and power panels for use at 120/208 volts: 225 amp maximum with circuit breakers rated at 10K AIC symmetrical at 240 volts. b. Lighting and power panels for use at 480/277 volts: 225 amp maximum with circuit breakers rated at 14K AIC symmetrical at 480 volts. c. Distribution panels for use at 120/208 volts: UL listed with minimum integrated assembly rating of 22K AIC. 3. Panels tested and listed according to UL 67 and bearing an integrated short circuit rating shall be determined by the short circuit study on the electrical system with 10,000 AIC minimum. 4. Any 2 single pole circuit breakers shall be replaceable by 1 two-pole circuit breaker and any 3 single-pole breakers shall be replaceable by 1 three-pole circuit breaker. 5. Where new circuit breakers are specified to be installed within existing panelboards, they shall be compatible in terms of manufacture, type, and AIC. 6. Breakers 100 ampere through 400 ampere frame sizes shall be thermal-magnetic trip with inverse time current characteristics, unless otherwise noted. 7. Provide ground fault circuit interrupter circuit breakers where indicated. 8. Emergency Panelboards Identification: Paint door red and stencil in 1 inch high yellow letters "EMERGENCY PANEL" in addition to appropriate individual panel identification as shown on drawings. PART 3 EXECUTION 3.1 INSPECTION A. Do not proceed with the work of this section until conditions detrimental to the proper and timely completion of the work have been corrected in an acceptable manner. 3.2 INSTALLATION A. Panelboards shall be installed where indicated and with top of cabinet 6'-6" above floor, and shall be rigidly and securely attached to building construction and shall not depend upon conduit for support. Allow at least 1/2" air space behind wall mounted panelboards. B. Install panelboards according to manufacturer's recommended data. Maintain clearances required by the National Electrical Code, with particular attention to working space around panelboards. Maintain clear space above panelboards, coordinate with other trades to avoid placement of panelboards below piping, ductwork, or other foreign appurtenances. Relocate panels at no additional cost should such interferences occur. C. Supply panelboards with phenolic nameplate 1 inch x 3 inch on exterior of panels and engraved with panel designation and voltage rating. Lighting and power panelboards shall be provided with a clear plastic enclosed typewritten directory inside. Circuit identification shall include load type (lighting, receptacles, etc.) and rooms served. D. Where flush type panelboards are indicated, provide one 3/4" empty conduit terminated in accessible ceiling above for each 3 spare circuit breakers provided in the panelboard. Project No. SPECIFICATION GUIDELINES 16470-4

E. Install circuit breakers in existing panelboards according to manufacturer's recommendation. Verify tightness of connections including mains. Identify new circuits on the panel directory. If none exists, provide one. F. Clean and touch up panelboard as required at completion of the project. G. Support surface mounted panelboards for other than masonry walls, from floor slab secured "Kindorf" or "Unistrut" channels. Mount those installed on masonry walls to back boards secured to walls, and according to manufacturer s recommendations and applicable codes and regulations. Contractor shall coordinate manufacturer s actual panelboard dimensions with room clearances to conform with NEC requirements. END OF SECTION Project No. SPECIFICATION GUIDELINES 16470-5