3 STORY STUCCO BUILDING HEIGHT ELEVATION=313.97' APARTMENTS SEPARATE APPLICATION AND PERMIT(S) IS/ARE REQUIRED FOR: ELECTRICAL WORK PLUMBING WORK SHORING FIRE SPRINKLER SIGNS ELEVATOR RETAINING WALLS MECHANICAL WORK GRADING DEMOLITION FIRE ALARM SWIMMING POOL BLOCK WALLS>3'6" LEGEND: AFCO Design, Inc. 2 STORY STUCCO APARTMENTS BUILDING HEIGHT ELEVATION=310.95' EXIT EXIT SIGN W/ EMERGENCY LIGHT CO SD HARD WIRED SMOKE DETECTORS WITH BATTERY BACK-UP AND LOW BATTERY SIGNAL DWELLING UNITS WITHIN WHICH FUEL-BURNING APPLIANCES ARE INSTALLED SHALL HAVE AN APPROVED CARBON MONOXIDE ALARM IN THE FOLLOWING LOCATIONS: 1. OUTSIDE OF EACH SEPARATE DWELLING UNIT SLEEPING AREA IN THE IMMEDIATE VICINITY OF BEDROOM(S) 2. ON EVERY LEVEL OF A DWELLING UNIT INCLUDING BASEMENTS 5 AIR EXCHANGE PER MINUTE MIN. EXHAUST FAN AND FLORESCENT LIGHT FANS SHALL BE ENERGY STAR COMPLIANT AND BE DUCTED TO TERMINATE TO THE OUTSIDE OF THE BUILDING. FANS NOT FUNCTIONING AS A COMPONENT OF A WHOLE HOUSE VENTILATION SYSTEM, MUST BE CONTROLLED BY A HUMIDITY CONTROL. FS WATER CURTAIN INSTALLED IN ACCORDANCE WITH SEC. 903.3.1.1 1 DOOR TYPE A F.E. FIRE EXTINGUISHER, RECESSED INTO WALL. 1 4 2 INTERIOR ELEVATION MARKER 3 00.00 EXISTING GRADE ELEVATION T.W. WINDOW TYPE TOP OF WALL F.F. FINISHED FLOOR BERENDO STREET E.F.G. T.D. A.D. EXISTING FINISH GRADE TOP OF DRAIN AREA DRAIN 2-HR 50 STC WALL SEE DETAIL 3/A-27 FIRE BARRIER 2-HR 50 STC WALL SEE DETAIL 3/A-27 FIRE BARRIER (PLB'S WALL) 1-HR 50 STC WALL SEE DETAIL 2/A-27 FIRE BARRIER 1-HR 50 STC WALL SEE DETAIL 2/A-27 FIRE BARRIER (PLB'S WALL) SOLID GROUTED CONCRETE BLOCK WALL CONCRETE WALL 1-HR RATED WOOD FRAMING. PROVIDE X6 MIN. WOOD FRAMING FOR ALL PLUMBING WALLS 11/A-26. 14" DROP SOFFIT. VERIFY SIZE PRIOR TO CONSTRUCTION VOID SOFFITS SHALL BE FILLED WITH INSULATION AND SOFFITS WITH AIR-CONDITIONING DUCTS SHALL BE PRE- LIMED WITH 5/8" THICK GYP BD TAPED AND INSPECTED PRIOR TO INSTALLATION OF THE DUCTS. AREAS REQUIRING INSULATION ABOVE AND THE SIDE OF THE SOFFITS SHALL BE INSULATED AND INSPECTED PRIOR TO THE PRELIM DRYWALL SEE DETAIL 6&7/A-27 AND 12/A-29 8'-2" HEADROOM CLERANCE SECURITY CAMERA AREA DRAIN AND FLOW DIRECTION 2 STORY STUCCO RESIDENCE EVS SEE NOTES FENCE WALL SITE PLAN NOTES: PROVIDE SUPERVISED AUTOMATIC FIRE SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1 NFPA13 THROUGH OUT THE BUILDING PROVIDE FIRE ALARM SYSTEM APPROVED BY THE FIRE DEPARTMENT PRIOR TO INSTALLATION THROUGHOUT THE BUILDING SHEET NO. A-01
LEGEND: AFCO Design, Inc. EXIT EXIT SIGN W/ EMERGENCY LIGHT CO SD HARD WIRED SMOKE DETECTORS WITH BATTERY BACK-UP AND LOW BATTERY SIGNAL DWELLING UNITS WITHIN WHICH FUEL-BURNING APPLIANCES ARE INSTALLED SHALL HAVE AN APPROVED CARBON MONOXIDE ALARM IN THE FOLLOWING LOCATIONS: 1. OUTSIDE OF EACH SEPARATE DWELLING UNIT SLEEPING AREA IN THE IMMEDIATE VICINITY OF BEDROOM(S) 2. ON EVERY LEVEL OF A DWELLING UNIT INCLUDING BASEMENTS 5 AIR EXCHANGE PER MINUTE MIN. EXHAUST FAN AND FLORESCENT LIGHT FANS SHALL BE ENERGY STAR COMPLIANT AND BE DUCTED TO TERMINATE TO THE OUTSIDE OF THE BUILDING. FANS NOT FUNCTIONING AS A COMPONENT OF A WHOLE HOUSE VENTILATION SYSTEM, MUST BE CONTROLLED BY A HUMIDITY CONTROL. FS WATER CURTAIN INSTALLED IN ACCORDANCE WITH SEC. 903.3.1.1 1 DOOR TYPE A F.E. FIRE EXTINGUISHER, RECESSED INTO WALL. 1 4 2 INTERIOR ELEVATION MARKER 3 00.00 EXISTING GRADE ELEVATION T.W. F.F. E.F.G. T.D. A.D. WINDOW TYPE TOP OF WALL FINISHED FLOOR EXISTING FINISH GRADE TOP OF DRAIN AREA DRAIN 2-HR 50 STC WALL SEE DETAIL 3/A-27 FIRE BARRIER 2-HR 50 STC WALL SEE DETAIL 3/A-27 FIRE BARRIER (PLB'S WALL) 1-HR 50 STC WALL SEE DETAIL 2/A-27 FIRE BARRIER 1-HR 50 STC WALL SEE DETAIL 2/A-27 FIRE BARRIER (PLB'S WALL) SOLID GROUTED CONCRETE BLOCK WALL CONCRETE WALL 1-HR RATED WOOD FRAMING. PROVIDE X6 MIN. WOOD FRAMING FOR ALL PLUMBING WALLS 11/A-26. 14" DROP SOFFIT. VERIFY SIZE PRIOR TO CONSTRUCTION VOID SOFFITS SHALL BE FILLED WITH INSULATION AND SOFFITS WITH AIR-CONDITIONING DUCTS SHALL BE PRE- LIMED WITH 5/8" THICK GYP BD TAPED AND INSPECTED PRIOR TO INSTALLATION OF THE DUCTS. AREAS REQUIRING INSULATION ABOVE AND THE SIDE OF THE SOFFITS SHALL BE INSULATED AND INSPECTED PRIOR TO THE PRELIM DRYWALL SEE DETAIL 6&7/A-27 AND 12/A-29 8'-2" HEADROOM CLERANCE SECURITY CAMERA AREA DRAIN AND FLOW DIRECTION EVS SEE NOTES FENCE WALL GARAGE PLAN 31'-7" 12'-0" OCCUPANT LOAD: TABLE 1004.1.1 6,832 SQ. FT./200=35<50 2 EXITS REQUIRED REQUIRED EXIT AND STAIR WIDTH 36" (SEC. 1009.4) EXIT ACCESS TRAVEL DISTANCE: TABLE 1016.1 S2 OCCUPANCY 400' 1. SEE LOCATION(S) AND TYPE OF EVSE, RACEWAY METHOD(S). ONLY UNDERGROUND RACEWAYS AND RELATED UNDERGROUND EQUIPMENT ARE REQUIRED TO BE INSTALLED AT THE TIME OF CONSTRUCTION. ELECTRICAL CALCULATIONS SHALL VERIFY THAT SYSTEM HAS SUFFICIENT CAPACITY TO SIMULTANEOUSLY CHARGE ALL DESIGNATED EV SPACES AT FULL RATED AMPERAGE BASED ON LEVEL 2 EVSE. 2. THE ELECTRICAL SYSTEM SHALL HAVE SUFFICIENT CAPACITY TO SIMULTANEOUSLY CHARGE ALL DESIGNATED EV SPACES AT FULL RATED AMPERAGE BASED ON LEVEL 2 EVSE. A SEPARATE ELECTRICAL PERMIT IS REQUIRED. 3. A LABEL STATING 'EV CAPABLE' SHALL BE POSTED IN A CONSPICUOUS PLACE AT THE SERVICE PANEL OR SUB-PANEL AND THE EV CHARGING SPACE. 4. WHERE ONLY A SINGLE CHARGING SPACE IS REQUIRED: INSTALL A MINIMUM 1-INCH (INSIDE DIAMETER) RACEWAY TO ACCOMMODATE A DEDICATED 208/240 VOLT BRANCH CIRCUIT. RACEWAY SHALL ORIGINATE AT THE MAIN SERVICE OR SUB-PANEL AND TERMINATE IN CLOSE PROXIMITY TO THE PROPOSED LOCATION OF THE CHARGING SYSTEM INTO A LISTED CABINET, BOX OR ENCLOSURE. 20'-0" 12'-0" 31'-7" CIRCULATION DRIVEWAY DETAIL NOTES: PROVIDE SUPERVISED AUTOMATIC FIRE SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1 NFPA13 THROUGH OUT THE BUILDING PROVIDE FIRE ALARM SYSTEM APPROVED BY THE FIRE DEPARTMENT PRIOR TO INSTALLATION THROUGHOUT THE BUILDING PROVIDE MECHANICAL VENTILATION FOR THE GARAGE SECTION 406.4.2 CAR CHARGER CALCULATIONS: TOTAL REQUIRED CARS: 17 NO OF CHARGERS REQUIRED@5%= 1 NO. OF CHARGERS PROVIDED" 1 SHEET NO. A-02
D/W FIRST FLOOR PLAN SCALE: 1/4"=1'-0" SHEET NO. A-03
SECOND FLOOR PLAN SCALE: 1/4"=1'-0" SHEET NO. A-04
3RD &4TH FLOOR PLAN SCALE: 1/4"=1'-0" SHEET NO. A-05
WEST ELEVATION EXTERIOR WALL OPENING SOUTH WALL: (SEC. 705.8.1) TOTAL OPENING: 139 SQ. FT. (1ST FLOOR) WALL OPENING RATIO 139/ 1,025=13.58% < 25% ALLOWED TOTAL OPENING: 181 SQ. FT. (2ND & 3RD FLOOR) WALL OPENING RATIO 181/ 1,025=17.66% < 25% ALLOWED TOTAL OPENING: 218 SQ. FT. (4TH FLOOR) WALL OPENING RATIO 218/ 1,025=21.27% < 25% ALLOWED SOUTH ELEVATION SHEET NO. A-06
EXTERIOR WALL OPENING SOUTH WALL: (SEC. 705.8.1) TOTAL OPENING: 139 SQ. FT. (1ST FLOOR) WALL OPENING RATIO 139/ 1,025=13.58% < 25% ALLOWED TOTAL OPENING: 181 SQ. FT. (2ND & 3RD FLOOR) WALL OPENING RATIO 181/ 1,025=17.66% < 25% ALLOWED TOTAL OPENING: 218 SQ. FT. (4TH FLOOR) WALL OPENING RATIO 218/ 1,025=21.27% < 25% ALLOWED ELEVATION EXTERIOR WALL OPENING SOUTH WALL: (SEC. 705.8.1) TOTAL OPENING: 139 SQ. FT. (1ST FLOOR) WALL OPENING RATIO 139/ 1,025=13.58% < 25% ALLOWED TOTAL OPENING: 181 SQ. FT. (2ND & 3RD FLOOR) WALL OPENING RATIO 181/ 1,025=17.66% < 25% ALLOWED TOTAL OPENING: 218 SQ. FT. (4TH FLOOR) WALL OPENING RATIO 218/ 1,025=21.27% < 25% ALLOWED EAST ELEVATION SHEET NO. A-07