Outline Chilled Water T Study AHU Coil Overview Cooling Overview Test Setup Data Analysis Findings Summary

Similar documents
Chilled Water Energy Savings Study

Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY AHR Expo Innovation Award Winner in the Category of Building Automation

Optimizing Central Chilled Water Systems

Knowledge is Power. Belimo Energy Valve

Pressure Independent Valve Systems. ASHRAE Seminar College of the North Atlantic, Doha, Qatar 20 th April 2013

WHITE PAPER. Chiller Plant Optimization - A Practitioner s Perspective. Abstract

IMPROVING CAMPUS CHILLED WATER SYSTEMS WITH INTELLIGENT CONTROL VALVES: A FIELD STUDY

Agenda. Understanding the three basic piping systems. Low DeltaT Syndrome causes, effects, and solutions Design & Control Considerations (VPF)

Intelligent. Powerful. Proven. usa.siemens.com/demandflow

Optimizing Chilled Water Systems for Energy Efficiency and Occupant Comfort

Management Committee December 3, Johnson County Community College Retrocommissioning Report

The Milton S. Hershey Medical Center Academic Support Building. AE Senior Thesis Kari Anne Donovan Mechanical Option

Teague Research Center

ENERGY AS SERVICES COMPANY ESCO. Jamal E. Alostaz. Projects Engineer Al-Salem Johnson Controls

EBCx of the Connecticut Convention Center Complex

Existing Building Cx: Processes & Results A Cultural Journey. Barry Abramson Senior Vice President Servidyne

UCSF Mission Bay Campus Arthur and Toni Rembe Rock Hall th Street San Francisco, California

Central Chiller Plants

CHLLED WATER SYSTEMS OPTIMIZATION AN OVERVIEW

North Grounds Boiler and Chiller Plant Replacement

DCP Capacity Upgrade By Adding Thermal Ice Storage. Jelle Wagelmans Sales Manager EVAPCO Middle East DMCC

SGM Engineering, Inc.

Xavier University of Louisiana

Central Plant Retro-Commissioning at Boston Logan International Airport IDEA 2015 Annual Conference Session 3C June 30, 2015

Palm District Cooling 19XR Chiller Energy Optimization Kwh saving test

Building Control Strategies That Work to Improve Your Energy Bottom Line

NEXT GENERATION ENERGY EFFICIENT TECHNOLOGIES: A CASE STUDY DEMONSTRATING TOP OPERATIONAL PERFORMANCE. The Aventine Chiller Plant Optimization

Seacrest & Kalkowski, PC, LLO

CONTRA COSTA COMMUNITY COLLEGE DISTRICT

THE GREAT CHILLED WATER DEBATE. Michael Dagher

Retrocommissioning Investigation Study of the Sheraton Chicago Hotel

05/14/2012 THE CRIME OF IMPROPER ENERGY MANAGEMENT AGENDA

Variable Frequency Drive Retrofit Opportunities. Michael Kuk CERx Solutions LLC

A STUDY OF ABSORPTION CHILLER/HEATER APPLICATION IN MARINE ENGINEERING

Use of Building Automation Systems for (Retro)Commissioning

Managing. Delta T in Buildings

Persistence Tracking in a Retro-commissioning Program

CHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM

Utilities Infrastructure Cooling Distribution. Purpose of Today s Presentation. Agenda. GLHN Architects & Engineers, Inc.

District Cooling Sustainable Design. Presented by George Berbari CEO of DC PRO Engineering

Central Chilled Water Plant Sustainable Design. By : George Berbari, CEO DC PRO Engineering

Characteristics of Energy Consumption by building type of a U.S. Navy Installation in Hot and Humid Climate

Rowan University Energy Management Optimization of our Central Chilled Water System

Empire State Building PY 2 M&V Report. Empire State Building. Performance Year 2 M&V Report March 1, 2013 Rev.1 (August 15, 2013)

Empire State Building Performance Year 4 M&V Report April 2, 2015

Small Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants

Energy Reduction Strategy Through 2020

Monitoring-Based Commissioning Best Practices Award Welch Hall

Air-Water Systems. Chilled Ceilings and Beams TROX USA. Principle of Operation. Radiant Effect on Occupants. Early 1980 s. Chilled Ceiling Panels

Final Report for National Grid USA Service Company. Evaluation of 2003 Custom HVAC Installations Part II. September 27, 2005.

Retro-Commissioning in Hospitals

Retrocommissioning Investigation Report

Digital FM The New Era (Case Study: Burj Khalifa) Bashar Kassab, Director HFM, Emaar Properties

An Alternative Approach to Chilled Water Optimization: Operator Advisory and On-going Training A 10,000 ton Central Chilled Water Plant Case Study

ARE YOUR VARIABLE SPEED PUMPING APPLICATIONS DELIVERING THE PREDICTED SAVINGS? IMPROVING CONTROL TO MAXIMIZE RESULTS

NEWMOA June 30, Fran Boucher LEED AP, Certified Energy Manager Senior Energy Engineer

(For ASllRAE Staff Use Only)

Project Information. Measure Description

ACCOMPLISHMENTS IN ENERGY REDUCTION EFFORTS AT THE ARCHITECT OF THE CAPITOL IDEA CAMPUS ENERGY CONFERENCE MARCH 8, 2018

December 13, 2012 Energy Efficient Cooling Information Service Webinar Series Christine Brinker and Gearoid Foley CHP with Absorption Chilling

Energy Reduction Programs: Understanding, Implementing & Delivering. PL Energy Services

D DAVID PUBLISHING. Optimizing Thermal Energy Storage Systems in the Hospitality Industry. 1. Introduction

A Case Study of Control Problems and Resolutions in a High rise

Chilled Water Plant Design American Standard Inc.

CHILLED WATER DISTRIBUTION SYSTEM

Central Utilities at UNL: NU Corp & Development of Thermal Energy Storage (TES) at UNL East Campus

PRESENTED BY: BRAD SWEARINGEN JIM NONNENMANN, PE

OPERATIONAL EXCELLENCE

Campus-Wide Cooling Plant Load Analysis & Thermal Energy Storage (TES) System Concept Engineering Study

Chilled Beams. The new system of choice?

High Impact Hotel Projects

Georgetown University New Science Center

AE 481W Thesis Proposal

Large University Central Chiller Plant Design Considerations

Energy Auditing for Schools. Maryland Energy Administration Eric Oliver, EMO Energy Solutions, LLC May 10, 2007

Geothermal Heat Pump Technology. What s new in the business of capturing the. Energy We Already OWN

Chilled Water Distribution Systems. APPA Institute for Facilities Management New Orleans, LA January 19, 2016

Technical Report Three Mechanical Systems Existing Conditions Evaluation

Intelligent System Design

AN INNOVATIVE DEDICATED OUTDOOR AIR APPLICATION FOR A GOVERNMENT OFFICE TOWER. MICHAEL HALLENBECK, PE, CEM Southland Industries

BCM00 Introduction to Building Controls and HVAC (available on request) One day course BCIA Members VAT Non-members VAT

IDEA Synopsis Submission

Chilled Water Plant Statement of Capabilities

ASHRAE s LowDown Showdown

DISTRICT COOLING HEAT REJECTION. Dubai 09/04/2018

Energy Reduction in Hospitals

University of Southern California Main Campus Plant Energy use reduction of 49% compared to previous plants and control strategies.

HVAC Variable Speed Pump Control System Diversity

Mechanical Project Proposal

Effective Energy Modeling WGBA Leadership Conference October 19, 2005

UC Irvine Energy Efficiency Energy Storage Energy Optimization. Matt Gudorf CEM, LEED AP Assistant Director Energy, Engineering, and Inspection

Mount Sinai Main Hospital Energy Conservation and Demand Management Plan

9/13/2011. Mark Hanicits, Director of Facilities and Safety, MetroSouth Medical Center. Terry Malloy P.E., Cxa, Project Manager, Teng & Associates

Reducing Hospital Energy Use and Maintaining Savings. Glen Anderson, PE

Model Based Building Chilled Water Loop Delta-T Fault Diagnosis

National Grid USA Service Company. Impact Evaluation Of 2006 Design2000plus Custom Comprehensive Projects. Final Report

ISPE CASA Energy Management Forum - Energy Management of Capital Projects at Novartis

Implementing Low-Cost Energy Savings Projects & Conducting Energy Audits

Existing Building Commissioning (or Retro-Commissioning)

Submitted to. Texas A&M University - Kingsville The Texas A&M University System. Submitted by. Yeqiao Zhu John Bryant Dan Turner David Claridge

Transcription:

Improved Chilled Water Plant Performance with New Energy Valve (EV) Outline Chilled Water T Study AHU Coil Overview Cooling Overview Test Setup Data Analysis Findings Summary 6 December 2012 Boston Hotels Conference 1

The Energy Valve, (EV) The EV is an intelligent/smart valve that corrects Low Delta T Syndrome in Chilled Water systems. Low Delta T Syndrome occurs when the temperature difference between Supply and Return chilled water temperatures across an Air Handling Unit, (AHU), heat exchanger is lower than the Chiller s Design Chilled Water Delta T. This causes additional chillers to come on line even though the cooling load has not increased, thus wasting energy. 6 December 2012 Boston Hotels Conference 2

Hayden Library Case Study 6 December 2012 Boston Hotels Conference 3

MIT Savings goal by eliminating causes of low Delta T (30,000 Ton Plant) Component Recommend implementing chilled water delta T improvement projects across the campus. Annual Energy Savings Annual Cost Savings Chiller Steam 10,887 Mlbs $181,000.00 Chiller Electric 2,576,000 kwh $412,000.00 CHW Pump Electric 2,334,000 kwh $373,000.00 CW Pump Electric 2,417,000 kwh $387,000.00 CT Fan Electric 740,000 kwh $118,000.00 TOTAL SAVINGS $1,471,000.00 25% 100% 6 December 2012 Boston Hotels Conference 4

MIT Chilled Water System 2011 Peak Load 26,000 tons * From 2008 Chilled Water Delta T Study 6 December 2012 Boston Hotels Conference 5

Cooling Energy GPM= Tons 24 T Flow & T T are inversely proportional; for a given load, as flow increases, T T drops Flow T 6 December 2012 Boston Hotels Conference 6

The Coil Causes of Low T Overflowing the coil Control valves oversized Improper balancing Non-dynamic balancing Dirty or fouled coils etc. 6 December 2012 Boston Hotels Conference 7

Typical Chilled Water System System Data Chiller #1 Load = 90% Chiller #2 Load = 0% Loop Flow = 360 GPM Chiller T = 12 F 42 CHWS 180 Ton Load (45%) CHWR 54 Increase flow by 15% VFD Pump Chiller 200 tons 90% Load Design: 400 Ton CHW System @ 12 T VFD Pump Chiller 200 tons 360 GPM Loop Flow 6 December 2012 Boston Hotels Conference 8

Typical Chilled Water System System Data Chiller #1 Load = 45% Chiller #2 Load = 45% Loop Flow = 414 GPM Chiller T = 10.4 F 42 CHWS 180 Ton Load (45%) CHWR 52.4 Increase flow by 15% An additional pump and chiller were started to meet the flow demand, not cooling demand! Design: 400 Ton CHW System @ 12 T VFD Pump VFD Pump Chiller 200 tons 45% Load Chiller 200 tons 45% Load 414 GPM Loop Flow 6 December 2012 Boston Hotels Conference 9

Cooling Energy Tons 24 GPM= T Flow & T T are inversely proportional; for a given load, as flow increases, T T drops You have to run your central plant to supply the building s need for water, not it s need for cooling! If flow is increased by 15%, Delta T is lowered by 13%! 6 December 2012 Boston Hotels Conference 10

Charles Hayden Library Case Study Issues Coil T reported as 6 Degree F Over pumping Low DeltaT Syndrome at Chiller Plant 6 AHU units, 153,000 sq-ft 6 December 2012 Boston Hotels Conference 11

Case Study Setup Data Internet Ethernet AI DDC 54F T Rw 42F T Sw Chilled Water is designed to run through a coil at a designed temperature drop to supply air conditioned cooling air and to de-humidify. i.e. Water Delta T=12 degrees F. 6 December 2012 Boston Hotels Conference 12

Belimo Energy Valve The Energy Valve is a pressure independent control valve that optimizes, documents and proves water coil performance. Actuator Magnetic Flow sensor Valve Temperature Sensors (for supply & return water) 6 December 2012 Boston Hotels Conference 13

AHU-6 Cooling Power Curve: July 4, 2011 6 December 2012 Boston Hotels Conference 14

AHU-6 Chilled Water T Curve: July 4, 2011 6 December 2012 Boston Hotels Conference 15

AHU-6 Power & T Curve: July 4, 2011 6 December 2012 Boston Hotels Conference 16

Definitions Power Saturation Point Point beyond which coil cannot yield additional heat transfer regardless of increased flow. Waste Zone Range beyond the Power Saturation Point. 6 December 2012 Boston Hotels Conference 17

Power Saturation & Waste Zone 6 December 2012 Boston Hotels Conference 18

Energy Valve Delta-T Manager Waste Zone 6 December 2012 Boston Hotels Conference 19

Pump Savings Example 24% flow savings = 56% energy savings 35.00 35.00 30.00 25.00 Pump flow Savings = (56.6-43.09)/56.6 = 24% Mechanical Energy Savings =1-((1-.24) power 3) =56% 30.00 25.00 20.00 20.00 15.00 10.00 5.00 T Curve 12.57, 43.09 10.27, 56.60 15.00 10.00 5.00 T 0.00 0.00 0.00 10.00 20.00 30.00 40.00 50.00 60.00 70.00 80.00 90.00 Flow [GPM ] 6 December 2012 Boston Hotels Conference 20

Hours Delta T Manager Active (Summer 2011) New right-sized Coil @14F T 6 December 2012 Boston Hotels Conference 21

Hayden Whole Building Results 2011 vs. 2010 Flow 8/9-10/9 2010 6.15 F T 8/9-10/9 2011 12.14 F T 6 AHU units, 153,000 sq-ft From whole building meters, Metering data PI archive Tonsx24/GPM= Weighted Average Delta T 6 December 2012 Boston Hotels Conference 22

Hayden Library Case Study Findings 1. The Delta-T limiting is especially effective on coils that display power saturation 2. Overall reduction of chilled water flow 3. Significant energy savings are realized in mechanical pumping energy with Delta-T Manger Estimated annual pump energy savings of $12,529 Total estimated annual overall savings of $50,116 Two year payback NSTAR and National Grid are conducting EV evaluations to determine incentives 6 December 2012 Boston Hotels Conference 23

Belimo Energy Valve Technical Summary Maximize coil performance Monitor savings at the coil level Documented commissioning of coil 13 month data archive 6 December 2012 Boston Hotels Conference 24

Thank You dick.hubbell@us.belimo.com 6 December 2012 Boston Hotels Conference 25