Cost optimal levels for envelope components in residential building renovation Rainha Dona Leonor neighbourhood case study

Similar documents
Cost optimality and nzeb target in the renovation of Portuguese building stock. Rainha Dona Leonor neighborhood case study

Cost Optimality and nzeb target in building renovation of Portuguese residential buildings

Cost Effective Energy and CO2 Emissions Optimization in Building Renovation Annex 56 methodology and its application to a case study

Refurbishment challenges of nzeb

Thermal rehabilitation of buildings facades with exterior insulation systems

Portuguese Thermal Building Legislation and Strategies for the Future

CALCULATIONS OF COST-OPTIMAL LEVELS OF ENERGY PERFORMANCE REQUIREMENTS FOR RENOVATED BUILDINGS AND BUILDING ELEMENTS: A LATVIAN CASE

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Dynamic Simulation of Thermal Behaviour of Sheraton Lisboa Hotel & SPA

Towards nzeb buildings: a historical building case study

ANALYSIS OF ENVELOPE THERMAL BEHAVIOUR THROUGH PARAMETRIC STUDIES. Civil Engineer, PhD, Assistant Professor, Civil Engineering Department (3)

Achieving the nearly zero energy building concept - A study based on practical experience

Energy consumption and thermal comfort in a passive house built in Romania

A study on the energy efficency of libraries of the west and tejo valley region in portugal

Analysis of different shading strategies on energy demand and operating cost of office building

THE ROAD TO NEARLY ZERO-ENERGY BUILDINGS

METHODOLOGY TO ENHANCE THE PORTUGUESE THERMAL REGULATION ACCURACY FOR EXISTING BUILDINGS

ZEMedS: Implementation

447 - Thermal Performance of Residential Buildings in Lisbon with Large Glazing Areas

School Tito Maccio Plauto Cesena (IT)

Upgrading the energy performance of residential buildings in Cyprus

Thermal performance of single family residential building according to the methodology of RCCTE calculation

Energy efficiency of buildings from Europe to Slovakia

PASSIVE HOUSE OBJECT DOCUMENTATION

Retrofit of an historical building toward NZEB

THERMAL AND ACOUSTIC COMFORT IN BUILDINGS

IMPACT ANALYSIS OF WINDOWS IN BUILDING THERMAL PERFORMANCE Jorge Filipe da Cruz Sirgado Lisbon, October 2010

Danish national plans for Nearly Zero Energy Buildings

Koniklecová 4, Brno-Nový Lískovec

Energy Consumption Prediction Model of the Residential Sector. Abstract. 1. Introduction

Facades Modules for Eco-Efficient Refurbishment of Buildings: An Overview

ZEMedS: Case studies

Large Valorisation on Sustainability of Steel Structures CASE STUDIES

ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE

Adaption of the passive house concept in northern Sweden - a case study of performance

EXECUTIVE SUMMARY: Best practices and lists of technologies to refurbish buildings & Proposed packages of measures

Características do. 1. Introduction In the. that led the. other. were the. Energy-related Nevertheless, the concerns of many.

Kindergarten Vejtoften, Høje-Taastrup, Denmark

Imp ementation Case:

Optimization of building envelope components based on life cycle environmental impacts and costs

2000 Antwerp, terraced house

The Nottingham Ecohome. Part L1 (2002) in existing dwellings

SOLAR XXI: A Portuguese Office Building towards Net Zero-Energy Building

Update of the Residential and Non-residential Building Stock Renovation Strategy, Slovak Republic

OPTIMIZATION OF THE REFURBISHMENT OF THE ENVELOPE THROUGHOUT ITS LIFE CYCLE

REPORT FROM THE COMMISSION TO THE EUROPEAN PARLIAMENT AND THE COUNCIL

Thermal insulation of buildings and cooling demand

Low energy buildings

Cost optimal energy efficiency in multifamily houses

SOLAR PHOTOVOLTAIC ENERGY

Modeling and Simulation of Energy Use and Indoor Thermal Environment of Highly-Insulated Buildings

Thermal performance characterization of a modular system for facade CARDOSO, C., a, JALALI, S.,b

THE INFLUENCE OF ENVELOPING ON ENERGETIC AND ECOLOGICAL EFFICIENCY OF PASSIVE HOUSES

Energy Audit of two Apartment Buildings in Cagliari using Energy Simulation

Single family low energy house, Herselt, Belgium

ENERGY SAVING INNOVATION IN CHINESE TRADITIONAL BUILDINGS. L. Zhu Nanjing University of Technology China

Technical control activities in waterproofing systems of flat roofs

CASE STUDIES - CENTRE FOR SUSTAINABLE BUILDING (ZUB) KASSEL, GERMANY

Computer-aided decision supporting tool for nearly Zero Energy Building renovation

5 social row houses (Wachtebeke)

Results from the Application of the Maltese Energy Performance Rating of Dwellings in Malta EPRDM Software to a New Block of Apartments

Polyurethane spray insulation

Materials & Energy Efficiency

Economic Feasibility Analysis of Sustainable Construction Measures

(Notices) EUROPEAN COMMISSION

Single family house in Herselt BE

CCHVAC REHVA Workshop in CLIMA nzeb experiences in South Europe and Mediterranean Climate

STATUS IN DECEMBER Current status of Implementation of the EPBD I. ENERGY PERFORMANCE REQUIREMENTS

ENVIRONMENTAL ANALYSIS OF BUILDING MATERIALS OF HOMES IN SLOVAK REPUBLIC A CASE STUDY

United Nations Economic and Social Commission for Asia and the Pacific (ESCAP) United Nations Economic Commission for Europe (UNECE)

Semi-detached house in De Pinte, Belgium

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies

A STUDY OF WALL SURFACE TEMPERATURE VARIATIONS FOR HOUSING IN MODERATE CLIMATES

Functional Adaptive Nano-Materials and. Impact of External Insulation

Methodology, Calculations and Results

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Upgrade your Home Insulation

The requirement system of the Hungarian directive on the energy performance of buildings

BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE

ZEMedS ds: Case studies

D3.9_Overall Refurbishment Plan DRAFT CS03. Hotel Restaurant Valcanover

Conforto Ambiental em Edifícios. Efficient walls

Built examples and project certification. Zeno Bastian, Passive House Institute

Module 3: Simulation and Data Analysis

Portuguese Passive House case study: a comparison between monthly and seasonal energy performance methods

Facades Modules for Eco-Efficient Refurbishment of Buildings: Glazing Thermal Performance Analyses to Coimbra and Faro

Comparison of measured and predicted sound insulation for a thermal retrofitted building

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

BVSC BVSC. Midwest Technical Inspections Survey Worksheet. Account / Account Code: Insured: Policy #: Building Data - Section 1

WP3 Impact, compliance and control of legislation - the Czech Republic. Jan Pejter ENVIROS, s.r.o. Prague

Investigations of thermal self-sufficient Residential Buildings with Solar Energy Systems

171: An urban office designed for the southern Brazilian climate

INCREASE THE VALUE AND COMFORT OF YOUR HOME. Saving Energy, Saves Money. and lower monthly costs with energy efficiency features.

CONSTRUCTIVE STUDY OF A DANISH SINGLE FAMILY SECOND HOUSE IN VILAFAMÉS. RENEWABLE ENERGIES, MATERIALS, CONSTRUCTIVE SOLUTIONS AND INSTALLATIONS.

ZEMedS ds: Case studies

EXPERIMENTAL AND NUMERICAL SIMULATION OF THE THERMAL PERFORMANCE OF LIGHT STEEL RESIDENTIAL BUILDINGS

Imp ementation Case:

ADAPTING TO PART L REGULATION CHANGES

RECOMMENDATIONS FOR CALCULATING REAL ENERGY CONSUMPTION

ZEMedS: Implementation

Transcription:

Cost optimal levels for envelope components in residential building renovation Rainha Dona Leonor neighbourhood case study Space for a portrait of the presenting author If you do not wish to provide a photograph, then leave this space empty. Manuela Almeida Associate Professor. University of Minho Portugal malmeida@civil.umin ho.pt Such texts should be aligned left (as above) Space for a portrait of the co-author. If there is no coauthor please delete this text. Pedro Civil Engineer. University of Minho Portugal a51324@uminho.pt Researcher Ana Rodrigues, University do Minho, Portugal, anarocha32846@yahoo.co.uk Researcher Marco Ferreira, University of Minho, Portugal, marcoferreira@civil.uminho.pt Short Summary Energy Efficiency in Buildings has been gaining increasing relevance in the past decades due to the raise of the energy consumption in the building sector as a consequence of the modern way of living with higher comfort patterns. In Europe, buildings are responsible for 40% of the energy consumption, which turns them into an important target for carbon emissions reduction [1]. Energy efficiency should be a main concern not only in new buildings, but also in the existing ones, which have poor energy performances. In Portugal most of the building stock was built before 1990, date of entrance into force of the first thermal regulation. Therefore, most of these buildings need intervention to improve not only the living environment, but also their energy performances. To evaluate the best measures, that fulfil the minimum requirements established for the energy needs with the lowest costs, the European Commission released the Commission Delegated Regulation (EU) Nº 244/2012 that establishes a comparative methodology framework for calculating the costoptimal level for minimum energy performance. In order to verify the renovation potential of these buildings, based on the Delegated Regulation methodology and taking advantage of a renovation process in course, a social housing neighbourhood called Rainha Dona Leonor was analysed. This analysis allowed obtaining the optimal levels for different renovations measures. The results show that it is not possible to establish a direct connection between the optimal level for the building envelope and the building as a whole, without considering the influence of the building systems. Keywords: Buildings renovation, cost-optimal, energy savings, renovation measures 1. Introduction Changes in the comfort patterns required by the buildings occupants and the buildings poor energy performance, led to excessive energy consumption in this sector, especially electricity [2]. In order to stop the increase in energy consumption and help the member states to keep up with their commitment towards the 2020 targets, the European Commission released the Directive 2010/31/EU (EPBD recast) to replace the previous one, dating from 16 December 2002. The new Directive states that after 2020 every new EU building must be a nearly zero energy building (nzeb). Besides this, every member state should create a methodology to establish minimum recommended requirements for buildings and building components to be integrated into the national legislation. The minimum recommended requirements should be established to the buildings cost-optimal levels and also to their components [3].The cost-optimal level is the balance between the best energy performance achieved with the lowest cost during the buildings life cycle [4]. The costs

include initial investment, maintenance costs and energy costs. Based on primary energy consumption and on the investment in each renovation solution, this methodology allows analysing different solutions. Usually the analysis starts with a basic solution and evolves to more efficient ones. When the analysis includes packages, instead of individual measures, it is possible to observe not only one cost-optimal level but a group of similar packages that form a range of cost-optimal solutions [5]. The combination of several measures can create a synergy that leads to better results compared to individual ones. Therefore, it is possible that despite the increase of the initial investment, the global cost may decrease because there is less energy costs associated to a certain measure or package. However, after a certain point, the increase in the initial investment will not be compensated by the reduction in energy costs [5]. This is an iterative process and the biggest challenge is to assure that the analysis doesn t become unbearable due to the numerous possibilities. Therefore, the analysis should be targeted to the lowest energy consumptions and lowest carbon emissions [5]. The cost-optimal analysis can follow two different perspectives: private perspective (microeconomic) and social perspective (macroeconomic). The social perspective considers the cost of the carbon emissions and excludes investment rates and discounts. The private perspective considers the discount rates and excludes the carbon emissions costs [5]. The methodology also advices choosing a reference building that can be either real or virtual. This building must be representative of the major part of the national building stock in order to have results that do not depend much on the buildings specific characteristics. In countries where the building stock has not been renovated, the age criteria may be very useful [5]. In Portugal the building sector is the second biggest energy consumer [6] after transports. Despite this fact, there aren t yet many studies in accordance with these recommendations, so it is important to develop knowledge by applying the methodology to case studies. Therefore, the present work aimed at studying a real building in which this methodology has been applied. The chosen building is part of the social housing Rainha Dona Leonor neighbourhood and it is located in Oporto city, Norwest of Portugal. 2. Methodology The analysis followed the recommendations of the Delegated Regulation and the selected building is representative of the Portuguese building stock and is currently under a renovation intervention. The analysis started with the energy characterization of the building. The determination of the energy needs followed the Portuguese regulation for thermal behaviour of the buildings (RCCTE, Decree-Law 80/2006) in accordance with ISO 13790 [7]. The comfort temperatures considered were 20ºC for winter and 25º for summer. After this characterization it was necessary to establish renovation measures able to promote energy efficiency in the building. The measures should affect the elements of the building with higher losses in winter and excessive gains in summer. For this case study, the renovation measures intended to improve the insulation level in walls, roof, floor and windows. There were also some calculations related to the heating/cooling systems. The analysed systems (one for heating and another for cooling) were divided into three groups: first, electric heater and electric cooler; second, gas boiler with radiators for heating and electric air conditioned for cooling, third, a heat pump for both heating and cooling. To evaluate the impact of the renovation measures it is necessary to calculate the heating and cooling needs and then the energy needs for all other usages. After that it is necessary to calculate the primary energy usage. After calculating the energy needs for each measure or package it is necessary to calculate the global cost. The solution with the lowest global cost is the cost optimal solution. This global cost depends on the initial investment and on all the costs related to the measure during the life cycle of the building that was considered of 30 years. The costs were calculated according to the private perspective, so the carbon emissions costs weren t considered. The discount rate applied was 6% and it was considered an increase of the energy cost of 3% per year. The initial investment and maintenance costs were based on the Cype software for generating prices. With the primary energy consumption and the global cost of each renovation measure, it was

possible to determinee the cost optimal measure. For this case, the primary energy included only the heating and cooling needs. For an easier reading, the resultss were presented in graphics with the primary energy consumptionn on the x-axis and the global cost in the y-axis, for every tested measure. This way of presentationn usually allows drawing a curve where the lowest point shows the optimal level for the selected building. 3. Case study characterization The analysed building is part of a social housing neighbourhood built in 1953. It has two apartments with threee bedrooms each with a total area of 110.54m² (55.27m² each apartment), divided in two floors. The building no longer comply with the current living patterns, therefore it willl be transformed in two apartments, one in each floor and, instead of three small bedrooms, theree will be only one bedroom with a bigger area, in each apartment. Besides these changes, the project also includes improvements in the building envelope. Figure 1 shows the building final horizontal plan and figure 2 shows how it looks like after renovation. The building has single brick walls, light weight slabs, a wooden roof structure covered with fibre cement tiles and wooden windows frames with single glass. There is no insulation and the domestic hot water (DHW) is provided by an electricc heater with a storage tank. The building doesn t have any heating or cooling system installed. Fig. 1 Building horizontal plan after renovation Fig. 2 Building front view, after renovation 3.1 Renovation measures The intervention on the living space is a good opportunity to improve the energy performance of the building without ncreasing excessively the initial investment. However, it is important to study its impact before the final decision. Table 1 summarisess the studied measures for this case study.

Table 1: Summary of the analysed renovation measures by building component Element Renovation Measure *ETICS Ventilated Façade Wall Roof Floor Window Heating and cooling Systems Insulation in the inside Insulation above the slab Insulation above the roof' wooden structure Insulation above the existing fibrocement sheets Insulation between the wooden beams Insulation above the floor slab Insulation above the regularization concrete layer Insulation under the slab New windows with PVC, Wood or Metal frames Electric heater and cooler Gas boiler Analysed Insulation type *RW (thicknesses of 80, 100,120 and 140mm) *EPS, *XPS and *MW (thicknesses of 60 and 80mm) *EPS and *RW (thicknesses of 40, 60, 80, 100, 120 and 150mm) *EPS, *XPS and *RW (thicknesses of 60, 80, 100, and 120mm) Sandwich panel with MW or XPS (thicknesses of 60, 80 and 100mm) *GW and *RW (thicknesses of 80, 100, 120 and 140mm) *MW (thicknesses of 50 and 60mm) *XPS (thicknesses of 40, 60, 80 and 100mm) *RW (thickness of 20mm) *RW and *XPS (thicknesses of 40, 60, 80 and 100mm) Glass: 4+6+6 Low ε; 100% árgon Glass: 4+10+6 Low ε; 100% árgon Glass: 4+12+6 Low ε; 100% árgon Glass: 4+16+6 Low ε; 100% árgon Glass: 4+18+6 Low ε; 100% árgon Heat pump *ETICS External Thermal Insulation Composite System; XPS Extruded polystyrene; EPS Expanded polystyrene; MW Mineral wool

4. Results This section presents the cost optimal results obtained for the walls, roof, floor and windows considering the referred three heating and cooling systems for the analysed renovation measures. The purpose of the analysis was to find the cost-optimal solutions for each one of the building elements. Building renovation packages were not analysed. The reference solution (the starting point) included 60mm of EPS on the walls, 60mm of XPS on the roof and windows with wooden frames and double glass. 4.1 Wall For the walls, the best solution consists in placing the insulation on the inside. This is due to the low investment needed to implement this solution. Figure 3 shows the results for different thicknesses of wall insulation and for the three heating/cooling systems analysed. The lowest point in each cloud of points is the cost optimal solution for that specific system. Table 2 shows a summary of the best solutions per each one of the systems analysed. The best performance corresponds to 80mm of insulation on the wall when using heat pump for heating and cooling. This equipment may have a high initial cost but the energy savings along the building life cycle compensate the initial investment resulting in a lower global cost. For the other equipments the cost optimal solution was obtained with higher insulation thicknesses. Fig. 3 Cost Optimal curves for the external walls for each of the three tested systems Table 2: Cost optimal solutions for exterior walls per type of heating/cooling system Equipment Cost optimal U-value (W/m². C) Primary energy (kgep/m 2.year) Costs ( ) Investment Energy Global Electric heater and cooler 120mm *EPS 0,27 32,70 5593 33726 39320 Gas boiler 120mm *EPS 0,27 10,71 5593 16012 21605 Heat Pump 80mm *EPS 0,36 8,95 5108 9234 14342 *EPS Expanded polystyrene 4.2 Roof Among the measures analysed for the roof, the best solution corresponds to keeping the existing roof solution and applying insulation above it, placing asphalt shingle on top. Figure 4 shows the

results for different thicknesses of roof insulation and for the three heating/cooling systems analysed. Per each system, the lowest point represents the optimal solution, which corresponds to placing rock wool with 80 to 120mm, depending on the heating/cooling system adopted, above the existing roof and cover it with shingle. Fig. 4 Cost optimal solutions for the renovation measures in the roof per each of the tested systems Table 3 summarises the results for the cost-optimal solutions with different heating/cooling systems. The heat pump is the equipment that combined with this solution requires the lowest roof insulation level. Table 3: Cost optimal solutions for the Roof per type of heating/cooling system Equipment Cost optimal U-value (W/m². C) Ntc (kgep/m 2.year) Costs ( ) Investment Energy Global Electric heater and cooler 120mm *RW 0,17 33,16 5974 34205 40178 Gas boiler 100mm *RW 0,18 10,68 5927 16107 22034 Heat pump 80mm *GW 0,20 8,55 5871 8816 14687 * RW Rock wool; GW Glass wool

4.3 Windows For the window frame type, PVC is the most cost effective. The changes come especially from the glass type. Figure 5 shows the results for the windows with PVC frames with different glass types. The best glass type is the 4+16+6 with argon or air inside the air gap.table 4 summarises the costoptimal solution for the windows with PVC frames, for the three systems analysed. Fig. 5 Cost optimal solutions for the window renovation measures, for each one of the three analysed systems Table 4: Cost optimal solutions for Windows with PVC frames with different systems Equipment Electric heater Cost optimal PVC + 4+16+6 100% Árgon U glass -U frame. (W/m². C) Primary energy (kgep/m 2.year) Costs ( ) Investment Energy Global 2,60-1,70 34,65 3052 35746 38798 Gas boiler PVC + 4+16+6 100% Árgon 2,60-1,70 11,21 3052 16856 19908 Heat pump PVC + 4+16+6 2,70-1,70 9,00 2993 9287 12280

4.4 Floor For the floor, every solution was tested considering the creation of an air space underneath the floor slab. Taking this into account, the best solution was the application of rock wool under the slab. Figure 6 shows the results of different thicknesses combined with each one of the analysed systems. Table 5 has the compilation of the cost optimal results. The best result comes with the heat pump and with 40mm of rock wool insulation under the slab. Fig. 6 Cost optimal solutions for the floor renovation measures, for each one of the three analysed systems Table 5: Cost Optimal solution for the Floor per type of heating/cooling system Equipment Electric heater and cooler Cost Optimal U-value (W/m². C) Primary energy (kgep/m 2.year) Costs ( ) Investment Energy Global 140mm *RW 0,21 21,48 3180 22158 25338 Gas boiler 60mm *RW 0,42 7,21 2880 10764 13643 Heat pump 40mm *RW 0,55 5,90 2780 6087 8867 *RW Rock wool 5. Conclusions For each building component, the cost optimal solution depends on the efficiency of the heating/cooling equipment used. The more efficient the system the lower the level of insulation of the envelope needed. In this case, the heat pump allowed using a thinner layer of insulation to maintain the same comfort levels as the other systems. In this particular case, the reference solution was already a good solution, considering the Portuguese patterns, unless for the floor. Therefore, the only renovation measures with significant impact on the building energy performance were those related to this building element. However, this conclusion cannot be generalized since this is not the common situation of the Portuguese existing buildings. 6. References

[1] EPBD Concerted Action Energy Performance of Buildings Implementing the Energy Performance of Buildings Directive Featuring country reports of 2010 concerted Action Comunication, 2011; [2] Parlamento Europeu. Directiva 2010/31/UE Parlamento Europeu e do Conselho, de 19 de Maio de 2010 sobre o desempenho energético dos edifícios /reformulação ; [3] EUROPEAN PARLIAMENT AND THE COUNCIL OF THE EUROPEAN UNION, Directive 2010/31/EU. Official Journal of the European Union, 2010; [4] European Commission Guidelines accompanying Commission Delegated Regulation (EU) No 244/2012 of 16 January 2012 ; Official Journal of the European Union; page 2012/C 115/01; 2012; [5] European Commission Commission Delegated Regulation (EU) No 244/2012 of 16 January 2012. Official Journal of the European Union, page 81/18; 2012; [6] WORLD ENERGY COUNCIL Energy Efficiency A global review, 2004; [7] Ministério da Economia e da Inovação Regulamento das Características do Comportamento Térmico dos Edifícios (RCCTE), 2007