NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: TUBELITE, INC.

Similar documents
NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. (Revised) Rendered to: TUBELITE, INC.

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: GAMCO CORPORATION

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. (Revised) Rendered to: CUSTOM VINYL PRODUCTS, LLC

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: MGM INDUSTRIES. SERIES/MODEL: 4600 Picture Window

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: SPECIALTY WHOLESALE SUPPLY

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: MGM INDUSTRIES. SERIES/MODEL: 4600 Double Hung

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.

U-Factor, Solar Heat Gain Coefficient, Visible Transmittance and Condensation Resistance Calculation Report

Simulation Performance, Solar Heat Gain Coefficient, Visible Transmittance and Condensation Resistance Calculation Report

U-Factor, Solar Heat Gain Coefficient, Visible Transmittance and Condensation Resistance Calculation Report

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built)

Simulation Performance, Solar Heat Gain Coefficient, Visible Transmittance and Condensation Resistance Calculation Report REPORT NO: DRAFT

All Seasons Door and Window, Inc. SIMULATION PERFORMANCE & SOLAR HEAT GAIN REPORT. V700 Vertical Slider Double Hung NCTL

MGM Industries SIMULATION PERFORMANCE & SOLAR HEAT GAIN REPORT. Series 8005 Sliding Glass Door NCTL

MGM Industries SIMULATION PERFORMANCE & SOLAR HEAT GAIN REPORT. Series 8010 Picture Window NCTL

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: COASTAL INNOVATIVE PRODUCTS

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: W250C Awning TYPE: Projecting (Awning)

MGM Industries SIMULATION PERFORMANCE & SOLAR HEAT GAIN REPORT. Series 4006 Fixed NCTL

MGM Industries Inc. SIMULATION PERFORMANCE & SOLAR HEAT GAIN REPORT. Series 5600 Single Hung NCTL

Summary NFRC U-Factor Simulation Report Architectural Testing, Inc., 130 Derry Court, York PA Fascimile Telephone

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX AMERICA INC. SERIES/MODEL: CAP-1 PRODUCT TYPE: Fixed Acrylic Glazed Skylight

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America Inc. SERIES/MODEL: VCM/VCE B PRODUCT TYPE: Venting Curb Mounted Skylight

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

TEST REPORT. Report No.: A Rendered to: TUBELITE, INC. Walker, Michigan

TEST REPORT. Report No.: F Rendered to: VELUX America LLC Greenwood, South Carolina

ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: WIRE-BOND. SERIES/MODEL: Masonry Tie Thermal Evaluations (2x6 Steel Stud Wall)

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

TEST REPORT. Report No.: G Rendered to: CR LAURENCE CO., INC. Vernon, California

Structural Performance Certification Authorization Report

TEST REPORT. Report No.: F Rendered to: MI WINDOWS AND DOORS, LLC Gratz, Pennsylvania

TEST REPORT. Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California. SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11

MOCK-UP TEST REPORT. Rendered to: TUBELITE INC. PROJECT: 300 ES Interior Glazed Curtain Wall

Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT. Report Number: C Rendered to: Tubelite Inc.

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: ALUMIL US. SERIES/MODEL: M300 Falcon PRODUCT TYPE: Aluminum Horizontal Sliding Window (XO)

Structural Performance Certification Authorization Report

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: S80 Monterey. TYPE: Bi-fold Door

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

Architectural Testing

TEST REPORT. Report No.: B Rendered to: MI WINDOWS AND DOORS, INC. Gratz, Pennsylvania

ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC.

Structural Performance Certification Authorization Report

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: GAMCO CORPORATION. Series/Model: CW250

AAMA 506 TEST REPORT. Report No.: G Rendered to: VEKA INC. Fombell, Pennsylvania

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass

Architectural Testing TEST REPORT. Rendered to: COEUR D'ALENE WINDOW Spokane Valley, Washington. PRODUCT TYPE: PVC Fixed Window SERIES/MODEL: 3310

TEST REPORT. Rendered to: EARTHWISE GROUP, LLC Liberty Township, Ohio

PERFORMANCE TEST REPORT. Report No.: H Rendered to: VELUX America LLC Greenwood, South Carolina

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut

OSHA FALL PROTECTION TEST REPORT. Rendered to: SERIES/MODEL: FS S PRODUCT TYPE: Fixed Deck Mounted Skylight

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.

LAP/CAP Workshop Kevin Louder NFRC September 26, 2017

TEST REPORT. Rendered to: UNIVERSAL PULTRUSIONS, LLC Marshall, Arkansas. Cycles 2,000,000. Summary of Results

TEST REPORT ASTM E331. Report No.: E Rendered to: IMISON USA Houston, Texas

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500. TYPE: Double Hung Window

TEST REPORT. Report No.: A Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440. TYPE: Sliding Glass Door

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390. TYPE: Sliding Glass Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 900 Series. TYPE: Out-swing Double Terrace Door

Structural Performance Certification Authorization Report

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: SHA4. TYPE: Single Hung Window

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window

PERFORMANCE TEST REPORT. Rendered to: DOW CORNING CORPORATION. PRODUCTS: Dow Corning 790 Silicone

PERFORMANCE TEST REPORT. Rendered to: HILTI CORPORATION. PRODUCT: Extreme Weather Window & Door Insulating Foam Sealant

NFRC SOLAR HEAT GAIN COEFFICIENT TEST REPORT. Rendered to: CLEAR FOCUS IMAGING

TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.

PERFORMANCE TEST REPORT. Rendered to: ALL-WEATHER INSULATED PANELS. SERIES/MODEL: SM40 PRODUCT TYPE: Insulated Sandwich Wall Panel

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: BUILDERS ACCESSORIES, INC.

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: FabriSpan. TYPE: Ceiling System. Summary of Test Results

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. ASSOCIATED MATERIALS, INCORPORATED Cuyahoga Falls, Ohio. Rendered to: PRODUCT TYPE: Fixed Window SERIES/MODEL: A780 SPECIFICATIONS:

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NOVAWALL SYSTEMS, INC. SERIES/MODEL: 3/4" Weltless. TYPE: Stretch Fabric Wall System

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America LLC. SERIES/MODEL: FCM B PRODUCT TYPE: Fixed Glass Glazed Curb Mount Skylight

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: Fabri Trak System. TYPE: Upholstered Panel

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: MI WINDOWS AND DOORS, LLC. SERIES/MODEL: 1650 Vinyl

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, LLC. SERIES/MODEL: 1650 Polyvinyl Chloride (PVC)

TEST REPORT. Rendered to: THE NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS Glen Ellyn, Illinois

2000 Skylight. For specific product applications, Consult your Kawneer representative. JANUARY, 2017 EC FEATURES ADMF020EN

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: MGM WINDOW COMPANY Hendersonville, Tennessee

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 2200 Glazed Wall System

TEST REPORT. Rendered to: ALL WEATHER INSULATED PANELS Vacaville, California. PRODUCT TYPE: Wall Panels SERIES/MODEL: DM45 Series

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

TEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

SUBMITTAL PACKAGE. SH46 Picture Window. Thermal Report Page 2-4 Structural Report Page 5-15

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1-1/4" Fabri Trak

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

Transcription:

Architectural Testing NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: 400 Series Curtain Wall (6" Standard Tube Backmember) - Fiberglass Pressure Plate Report Number: Report Date: 07/09/13 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com

Architectural Testing NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT Rendered to: TUBELITE, INC. 4878 Mackinaw Trail Reed City, Michigan 49677 Report Number: Simulation Date: Report Date: 06/11/12 07/09/13 Project Summary: Architectural Testing, Inc. was contracted to perform U-Factor, Solar Heat Gain Coefficient, Visible Transmittance, and Condensation Resistance* computer simulations in accordance with the National Fenestration Rating Council (NFRC). The products were evaluated in full compliance with NFRC requirements to the standards listed below. *NFRC's Condensation Resistance rating is NOT equivalent to a Condensation Resistance Factor (CRF) determined in accordance with AAMA 1503. Standards: NFRC 100-2010: Procedure for Determining Fenestration Product U-Factors NFRC 200-2010: Procedure for Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at Normal Incidence NFRC 500-2010: Procedure for Determining Fenestration Product Condensation Resistance Values Software: Frame and Edge Modeling: THERM 6.3.46 Center-of-Glass Modeling: WINDOW 6.3.74 Total Product Calculations: WINDOW 6.3.74 Spectral Data Library: IGDB 30.0 Simulations Specimen Description: Series/Model: 400 Series Curtain Wall (6" Standard Tube Backmember) - Fiberglass Pressure Plate Type: Glazed Wall System, Curtain Wall Frame Material: AT Aluminum w/ Thermal Breaks - All Members Sash Material: NA Not Applicable Standard Size: 2000mm x 2000mm 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com

Architectural Testing Page 2 of 7 Modeling Assumptions/Technical Interpretations: 1) To prevent air infiltration, tape was applied to all interior sash crack locations. 2) This product is available in either a painted or anodized finish. These two finish types were grouped for simulation purposes in accordance with NFRC 100-2010, Section 4.2.1.L. The painted finish was simulated since it is worst case (highest emissivity). The test sample was painted aluminum. 3) The center-line modeling approach was conducted using the horizontal intermediate for the head and sill models, and the vertical intermediate for the jambs. This procedure is outline in the NFRC Simulation Manual Section 8.10. Specialty Products Table: The specialty products method allow the manufacturer to determine the overall product SHGC and VT for any glazing option. The center of glass SHGC and/or VT must be determined using WINDOW 6.3.74. The method gives overall product SHGC and VT indexed on center of glass properties. All values used in the calculations are truncated to six decimal place precision. No Dividers Dividers < 1 Dividers > 1 SHGC0 0.011651 0.015100 0.018335 SHGC1 0.915905 0.813914 0.718241 VT0 0.000000 0.000000 0.000000 VT1 0.904254 0.798814 0.699906 SHGC = SHGC0 + SHGCc (SHGC1 - SHGC0) VT = VT0 + VTc (VT1 - VT0) Validation Matrix: The following products are part of a validation matrix. Only one is required for validation testing. Product Line Report Number None -

Architectural Testing Page 3 of 7 Spacer Option Description Sealant Spacer Type Primary Secondary Code Aluminum Spacer Butyl Rubber Butyl Rubber A1-D Grid Option Description Grid Size Grid Type Grid Pattern None - - Reinforcement Option Description Location Material None - Gas Filling Technique Description Fill Type Method 84.48% Xenon Single Probe Timed 76.14% Argon Single Probe Timed 88.47% Argon Single Probe Timed 78.56% Argon Single Probe Timed 78.10% Krypton Single Probe Timed 87.41% Argon Single Probe Timed 64.98% Argon Single Probe Timed 74.70% Argon Single Probe Timed 60.78% Argon Single Probe Timed 62.43% Argon Single Probe Timed 86.02% Argon Single Probe Timed 81.60% Xenon Single Probe Timed 94.54% Xenon Evacuated Chamber 76.90% Krypton Single Probe Timed 71.54% Xenon Single Probe Timed 76.45% Krypton Single Probe Timed 66.67% Xenon Single Probe Timed 82.16% Xenon Single Probe Timed Edge-of-Glass Construction Interior Condition EPDM Gasket Between Aluminum Frame and Glass Exterior Condition EPDM Gasket Between Fiberglass Pressure Plate and Glass Weatherstripping Type Quantity Location None - - Frame/Sash Materials Finish Interior Painted Aluminum Exterior Painted Aluminum

Architectural Testing Page 4 of 7 NFRC 100/200/500 Summary Sheet 400 Series Curtain Wall (6" Standard Tube Backmember) - Fiberglass Pressure Plate ID Pane Thickness 1 Gap Width 1 Pane Thickness 2 Gap Width 2 Pane Thickness 3 Gap Width 3 Pane Thickness 4 Solar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation U-Factor Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance 1 COG=0.4400 0.222 0.500 0.225 XEN84 CL A1-D N U-Factor 0.54 SHGC (N) 0.63 VT (N) 0.67 CR 46 2 COG=0.4200 0.236 0.500 0.225 ARG76 0.654(#2) RC A1-D N U-Factor 0.52 SHGC (N) 0.32 VT (N) 0.29 CR 46 3 COG=0.4000 0.223 0.500 0.225 ARG88 0.571(#2) CL A1-D N U-Factor 0.50 SHGC (N) 0.22 VT (N) 0.15 CR 47 4 COG=0.3800 0.236 0.500 0.225 ARG79 0.465(#2) RC A1-D N U-Factor 0.49 SHGC (N) 0.20 VT (N) 0.13 CR 48 5 COG=0.3600 0.221 0.500 0.225 KRY78 0.406(#2) SR A1-D N U-Factor 0.47 SHGC (N) 0.20 VT (N) 0.16 CR 49 6 COG=0.3400 0.232 0.500 0.225 ARG87 0.318(#2) CL A1-D N U-Factor 0.45 SHGC (N) 0.43 VT (N) 0.51 CR 49 7 COG=0.3200 0.223 0.500 0.225 ARG65 0.215(#2) CL A1-D N U-Factor 0.44 SHGC (N) 0.57 VT (N) 0.66 CR 50 8 COG=0.3000 0.233 0.500 0.225 ARG75 0.166(#2) CL A1-D N U-Factor 0.42 SHGC (N) 0.41 VT (N) 0.48 CR 51 9 COG=0.2800 0.223 0.500 0.225 ARG61 0.087(#2) CL A1-D N U-Factor 0.40 SHGC (N) 0.50 VT (N) 0.69 CR 52 10 COG=0.2600 0.223 0.500 0.225 ARG62 0.035(#2) CL A1-D N U-Factor 0.39 SHGC (N) 0.35 VT (N) 0.63 CR 53 Gap Fill Low-e (Surface#) Tint Spacer Grid Type

Architectural Testing Page 5 of 7 NFRC 100/200/500 Summary Sheet 400 Series Curtain Wall (6" Standard Tube Backmember) - Fiberglass Pressure Plate ID Pane Thickness 1 Gap Width 1 Pane Thickness 2 Gap Width 2 Pane Thickness 3 Gap Width 3 Pane Thickness 4 Gap Fill Low-e (Surface#) Tint Spacer Grid Type Solar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation U-Factor Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance 11 COG=0.2400 0.223 0.500 0.223 ARG86 0.035(#2) / 0.035(#3) CL A1-D N U-Factor 0.37 SHGC (N) 0.33 VT (N) 0.57 CR 54 12 COG=0.2200 0.223 0.500 0.223 XEN82 0.018(#2) / 0.018(#3) CL A1-D N U-Factor 0.35 SHGC (N) 0.24 VT (N) 0.47 CR 57 13 COG=0.2000 0.223 0.500 0.223 XEN95 0.018(#2) / 0.018(#3) CL A1-D N U-Factor 0.34 SHGC (N) 0.24 VT (N) 0.47 CR 55 14 COG=0.1800 0.223 0.250 0.003 0.250 0.221 KRY77/AIR 0.018(#2)/0.755(#3)/0.122(#4)/0.028(#5) CL A1-D N U-Factor 0.31 SHGC (N) 0.23 VT (N) 0.40 CR 62 15 COG=0.1600 0.223 0.250 0.003 0.250 0.223 XEN72/AIR 0.018(#2, #5) / 0.755(#3) / 0.122(#4) CL A1-D N U-Factor 0.30 SHGC (N) 0.23 VT (N) 0.42 CR 63 16 COG=0.1400 0.223 0.250 0.003 0.250 0.223 KRY76 0.018(#2, #5) / 0.755(#3) / 0.122(#4) CL A1-D N U-Factor 0.28 SHGC (N) 0.22 VT (N) 0.42 CR 64 17 COG=0.1200 0.223 0.250 0.003 0.250 0.223 XEN67 0.018(#2, #5) / 0.755(#3) / 0.122(#4) CL A1-D N U-Factor 0.26 SHGC (N) 0.22 VT (N) 0.42 CR 65 18 COG=0.1000 0.223 0.250 0.003 0.250 0.223 XEN82 0.018(#2, #5) / 0.755(#3) / 0.122(#4) CL A1-D N U-Factor 0.25 SHGC (N) 0.22 VT (N) 0.42 CR 66

Architectural Testing Page 6 of 7 The Condensation Resistance results obtained from this procedure are for controlled laboratory conditions and do not include the effects of air movement through the specimen, solar radiation, and the thermal bridging that may occur due to the specific design and construction of the fenestration system opening. Ratings values included in this report are for submittals to an NFRC-licensed IA and are not meant to be used directly for labeling purposes. Only those values identified on a valid Certification Authorization Report (CAR) by an NFRC accredited Inspection Agency (IA) are to be used for labeling purposes. The ratings values were rounded in accordance to NFRC 601, NFRC Unit and Measurement Policy. Architectural Testing, Inc. is an NFRC accredited simulation laboratory and all simulations were conducted in full compliance with NFRC approved procedures and specifications. The NFRC procedure requires that the computational results be verified through actual test results. Architectural Testing will service this report for the entire test record retention period. Test records that are retained such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation will be retained by Architectural Testing, Inc. for the entire test record retention period. The test record retention end date for this report is June 11, 2016. Results obtained are simulated values and were secured by using the designated test methods. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the product simulated. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC.: SIMULATED BY: REVIEWED BY: Kristen L. Livelsberger Senior Simulation Technician NFRC Certified Simulator Michael J. Thoman Director - Simulations and Thermal Testing Simulator-In-Responsible-Charge KLL:kll Attachments (pages): This report is complete only when all attachments listed are included. Appendix A: Drawings and Bills of Material (9)

Architectural Testing Page 7 of 7 Revision Log Rev. # Date Page(s) Revision(s).06R0 07/09/13 All Original Report Issued to Tubelite, Inc. This report produced from controlled document template ATI 00037, Revised 10/2/2012.

All drawings and Bills of Material used to simulate this product are enclosed in this Appendix Appendix A