Emissions level: EPA NSPS Stationary Emergency Tier 2 2g TA Luft

Similar documents
1540 Prime 1250 Continuous Emissions level: EPA NSPS Stationary Emergency Tier 2 2g TA Luft

Standby rating. Turbocharged and low temperature after-cooled

1400 Prime 1125 Continuous Emissions level: EPA NSPS Stationary Emergency Tier 2 2g TA Luft

Emissions level: EPA NSPS Stationary Emergency Tier 2

135 Prime Emissions level: EPA NSPS Stationary Emergency Tier 3

180 Prime Emissions level: EPA NSPS Stationary Emergency Tier 3

Generator set data sheet. 80 Prime Emissions level: EPA Nonroad Tier 1. Fuel consumption. Engine Standby rating Prime rating Continuous rating

Generator set data sheet. 410 Prime Emissions level: EPA Nonroad Tier 1. Fuel consumption. Engine Standby rating Prime rating Continuous rating

aftertreatment operating costs Designed for maximum performance on FULL RANGE OF ATTACHMENTS low pressure gaseous fuel supply

3363 en / e

LSA 47.2 Low Voltage Alternators - 4 pole

INdoor MGM 200 Natural Gas - emissions NOx < 500 5%O2. Type Specifications Co-generation Unit with MAN Gas Engine

LSA 51.2 Low Voltage Alternators - 4 pole

Low Voltage Alternators - 4 pole LSA 46.2

Low Voltage Alternators - 4 pole LSA 46.3

LSA Rating Table Low Voltage Alternators - 4 pole

Lubricated Rotary Screw Air Compressors. Constant Speed Drives and Variable Speed Drives kw hp

3867 en / f. Alternators. LSA Pole Electrical and mechanical data

LSA 53.2 Low Voltage Alternator - 4 pole

Alternators single phase dedicated - 4 Pole LSA 43.2 / LSA 44.2

3867 en / a

3820 en / c

MECHANICAL ENGINEERING DEPARTMENT, OITM

ELECTRICITY OUTPUT THERMAL OUTPUT ELECTRIC EFFICIENCY THERMAL EFFICIENCY TOTAL EFFICIENCY

Equipment Design. Detailed Plant Conceptual Design. Version 9.0

TECHNICAL DETAILS INDOP220MB

Air Cooler Industry AC-MS Modular Systems

UFL Micro Biogas CHPs

Low Voltage alternators - 4 pole LSA 42.3

Equipment Design. Detailed Plant Conceptual Design. Version 7.0

Technical Specification Industrial Series - IS2 to IS48 Systems. CapDI Benefits. Feed Water Quality. Design and Scope of Supply.

NATIONAL CERTIFICATION EXAMINATION 2004 FOR ENERGY MANAGERS

Heat Recovery. Integrated CHP Systems Corp.

LSA 42.3 Low Voltage Alternators - 4 pole

Case 7 Reciprocating Compressor

ELECTRICITY OUTPUT THERMAL OUTPUT ELECTRIC EFFICIENCY THERMAL EFFICIENCY TOTAL EFFICIENCY

ELECTRICITY OUTPUT THERMAL OUTPUT ELECTRIC EFFICIENCY THERMAL EFFICIENCY TOTAL EFFICIENCY

HW-1: Due Tuesday 13 Jun 2017 by 2:00:00 pm EDT to Your Division s GradeScope Site

UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING FINAL EXAMINATION, DECEMBER 2008 MIE 411H1 F - THERMAL ENERGY CONVERSION

AALSO Summary of Formulas needed for Levels I, II and III.

ELECTRICITY OUTPUT THERMAL OUTPUT ELECTRIC EFFICIENCY THERMAL EFFICIENCY TOTAL EFFICIENCY

Microturbine CHP for Microgrids Microgrid2017

ELECTRICITY OUTPUT THERMAL OUTPUT ELECTRIC EFFICIENCY THERMAL EFFICIENCY TOTAL EFFICIENCY

ELECTRICITY OUTPUT THERMAL OUTPUT ELECTRIC EFFICIENCY THERMAL EFFICIENCY TOTAL EFFICIENCY

automatic regulation of mixture richness way to emission decrease is in standard equipment of CHP unit

Code No: R31034 R10 Set No: 1

AQUAPROF BASIC AQUAPROF TOP ACTIVE SWITCH

Practice Final Exam (A) Six problems. (Open-book, HW solutions, and notes) (Plus /minus 10 % error acceptable for all numerical answers)

PAHT C pumps ATEX PAHT C pump

Technical Overview of Mitsubishi LNG Marine Auxiliary Solutions

OIL-INJECTED ROTARY SCREW COMPRESSORS. G ( kw / hp) / G VSD ( kw / hp)

Chapter 1 Basic Concepts

7 th NATIONAL CERTIFICATION EXAMINATION Nov FOR ENERGY MANAGERS & ENERGY AUDITORS

CAT CG132. Series Gas Generator Sets

Senior Thesis Report Spring Appendix - A. HAP Calculations without Enthalpy Wheel Excel Graphs

Autogas Series. Regenerative Turbine Coro-Flo Pumps For High Differential Pressure Applications Using LPG and Other Liquefied Gases.

SAF Filters. The automatic self-cleaning filter - suitable for more applications than ever.

ABB MEASUREMENT & ANALYTICS DATA SHEET. SCK Sampling system for dry gas sampling at rotary cement kiln gas exit and calciner gas exit

ELECTRICITY OUTPUT THERMAL OUTPUT ELECTRIC EFFICIENCY THERMAL EFFICIENCY TOTAL EFFICIENCY

MICROTUNNELING SYSTEMS DRIVEN FOR CUSTOMER SUCCESS

EBS Filters. The largest automatic self-cleaning filter for fine filtration. features: up to 7200 m³/h (32000 US gpm) less than 1% of the total flow

How to cool a D E S Y?

a. The power required to drive the compressor; b. The inlet and output pipe cross-sectional area. [Ans: kw, m 2 ] [3.34, R. K.

TGG, TBG, TEG, TUG, 3.9 TBS, Gene-Link series

GAS ENGINE GENERATORS

Siemens gas engine portfolio siemens.com/engines

Page of ENGINEERING DATA - HOT WATER CAPACITIES, CALCULATIONS AND CORRECTION FACTORS Use the following two tables to determine

NITROGEN SERIES COMPRESSOR SYSTEMS

Combustion Laboratory Unit C492

ELECTRICITY OUTPUT THERMAL OUTPUT ELECTRIC EFFICIENCY THERMAL EFFICIENCY TOTAL EFFICIENCY

NITROGEN SERIES COMPRESSOR SYSTEMS

Advanced Testing for Innovative Design

Alex Alexandrovich, P.E.

KX Series. 727 kva kva, 50 Hz 636 kw kw, 60 Hz

Index. Hydraulic Data Chapter 1. Formulas & Conversions Chapter 2. Friction Loss Chapter 3. Viscous Fluids & Slurries Chapter 4

Cummins power ensures uninterrupted patient care

flow rates filtration degrees water for cleaning minimum operating pressure micron less than 1% of the total flow

PET Compressed Air Solutions 470-4,000 cfm (800-6,800 m 3 /hr)

Introduction of Commercial CO 2 Heat Pump applications in Switzerland and Japan

Pressure Booster System. Hya-Eco VP. Type Series Booklet

AALSO Proficiency Program Level I, II & III

GOULDS PUMPS. Commercial Water. e-sv General Market Specifications. Applications. Specifications

Optimal use of energy

ProMinent Evolution Series

Organic Rankine Cycle Waste Heat Solutions And Opportunities In Natural Gas Compression > The renewable energy source

Pressure Booster System. Hya-Eco VP. Type Series Booklet

Rotary Vane Vacuum Pumps

Séon TRO Seawolf. Séon TRO Seawolf Data Sheet. Model - WSTRO12000 Reverse Osmosis Seawater Desalination System Trailer Mounted

Combustion Laboratory Unit C492

Gas vs. Diesel Generator Sets Performance Cost & Application Differences

Diesel Engine Powered Cogeneration for a Dairy Farm. Jennifer Fan. A thesis submitted in partial fulfillment of the requirements for the degree of

Nessie Pumps type PAH 2/4/6.3, PAH 10/12.5, PAH 20/25/32 and PAH 50/63/70/80/100

Job Sheet 2. The Ground Loop OBJECTIVE PROCEDURE. Introduction

Installation plan. Washer-extractor PW 6107 EL. en - GB M.-Nr / 01

Gas Turbine Inlet Air Cooling System

Hitachi H-25 & H-80 Gas Turbine. Bucharest, Apr.23, 2013

Onsite Labor: $7, (30 hours /2 technicians) (Rate- $129.00/Hr.)

Architect s Project Number of 5 Decentralized HVAC Equipment District Master Specs 2013 Edition

CHAPTER 1 BASIC CONCEPTS

SERVO-HYDRAULIC UNIVERSAL TESTING MACHINE SERIES A

Transcription:

Generator set data sheet Model: DQKAJ Frequency: 50 Hz Fuel type: Diesel kva rating: 2500 Standby 2000 Prime Emissions level: EPA NSPS Stationary Emergency Tier 2 2g TA Luft Exhaust emission data sheet: Exhaust emission compliance sheet: Sound performance data sheet: Cooling performance data sheet: Prototype test summary data sheet: Standard set-mounted radiator cooling outline: Optional set-mounted radiator cooling outline: Optional heat exchanger cooling outline: Optional remote radiator cooling outline: EDS-1147 EPA-1205 MSP-1137 MCP-233 PTS-309 A034H896 A034T734 A042V096 A034U921 Fuel consumption Standby Prime kva (kw) kva (kw) Ratings 2500 (2000) 2000 (1600) Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full US gph 37 68 99 138 31 55 80 105 L/hr 140 256 375 523 117 210 302 399 Engine Standby rating Prime rating Engine manufacturer Cummins Inc. Engine model Configuration Aspiration QSK60-G18 NR2 Cast iron, V 16 cylinder Turbocharged and low temperature after-cooled Gross engine power output, kw m (bhp) 2164 (2901) 1727 (2315) BMEP at set rated load, kpa (psi) 2868 (416) 2289 (332) Bore, mm (in.) 159 (6.25) Stroke, mm (in.) 190 (7.48) Rated speed, rpm 1500 Piston speed, m/s (ft/min) 9.5 (1869) Compression ratio 14.5:1 Lube oil capacity, L (qt) 261 (276) 378 (399) Overspeed limit, rpm 1725 Regenerative power, kw 277

Fuel flow Maximum fuel flow, L/hr (US gph) 939 (248) Maximum fuel inlet restriction, kpa (in Hg) 30 (9.0) Maximum fuel inlet temperature, C ( F) 71 (160) Air Standby rating Prime rating Combustion air, m 3 /min (scfm) 154 (5450) 130 (4578) Maximum air cleaner restriction, kpa (in H 2O) 6.2 (25) Alternator cooling air, m 3 /min (cfm) 192 (6780) Exhaust Exhaust flow at set rated load, m 3 /min (cfm) 378 (13330) 360 (12715) Exhaust temperature, C ( F) 507 (944) 450 (841) Maximum back pressure, kpa (in H 2O) 6.7 (27) Standard set-mounted radiator cooling Ambient design, C ( F) 40 (104) Fan load, kw m (HP) 40 (53) Coolant capacity (with radiator), L (US gal) 537 (142) Cooling system air flow, m 3 /min (scfm) 2094 (73937) Total heat rejection, MJ/min (Btu/min) 97 (92368) 73 (69465) Maximum cooling air flow static restriction, kpa (in H 2O) 0.12 (0.5) Maximum fuel return line restriction kpa (in Hg) Optional set-mounted radiator cooling Ambient design, C ( F) 50 (122) Fan load, kw m (HP) 64 (86) Coolant capacity (with radiator), L (US gal) 606 (160) Cooling system air flow, m 3 /min (scfm) 2347 (82891) Total heat rejection, MJ/min (Btu/min) 97 (92368) 73 (69465) Maximum cooling air flow static restriction, kpa (in H 2O) 0.12 (0.5) Maximum fuel return line restriction kpa (in Hg) Optional heat exchanger cooling Set coolant capacity, L (US gal) Heat rejected, jacket water circuit, MJ/min (Btu/min) Heat rejected, aftercooler circuit, MJ/min (Btu/min) Heat rejected, fuel circuit, MJ/min (Btu/min) Total heat radiated to room, MJ/min (Btu/min) Maximum raw water pressure, jacket water circuit, kpa (psi) Maximum raw water pressure, aftercooler circuit, kpa (psi) Maximum raw water pressure, fuel circuit, kpa (psi) Maximum raw water flow, jacket water circuit, L/min (US gal/min) Maximum raw water flow, aftercooler circuit, L/min (US gal/min) Maximum raw water flow, fuel circuit, L/min (US gal/min) Minimum raw water flow at 27 C (80 F) inlet temp, jacket water circuit, L/min (US gal/min)

Optional heat exchanger cooling (continued) Minimum raw water flow at 27 C (80 F) inlet temp, aftercooler circuit, L/min (US gal/min) Minimum raw water flow at 27 C (80 F) inlet temp, fuel circuit, L/min (US gal/min) Raw water delta P at min flow, jacket water circuit, kpa (psi) Raw water delta P at min flow, aftercooler circuit, kpa (psi) Raw water delta P at min flow, fuel circuit, kpa (psi) Maximum jacket water outlet temp, C ( F) Maximum aftercooler inlet temp, C ( F) Maximum aftercooler inlet temp at 25 C (77 F) ambient, C ( F) Maximum fuel return line restriction, kpa (in Hg) Optional remote radiator cooling 1 Standby rating Prime rating Set coolant capacity, L (US gal) Max flow rate at max friction head, jacket water circuit, L/min (US gal/min) 1590 (420) Max flow rate at max friction head, aftercooler circuit, L/min (US gal/min) 503 (133) Heat rejected, jacket water circuit, MJ/min (Btu/min) 50 (46957) 40 (37512) Heat rejected, aftercooler circuit, MJ/min (Btu/min) 35 (33332) 24 (22739) Heat rejected, fuel circuit, MJ/min (Btu/min) Total heat radiated to room, MJ/min (Btu/min) 13 (11969) 10 (9132) Maximum friction head, jacket water circuit, kpa (psi) 48 (7) Maximum friction head, aftercooler circuit, kpa (psi) 35 (5) Maximum static head, jacket water circuit, m (ft) 18 (60) Maximum static head, aftercooler circuit, m (ft) 18 (60) Maximum jacket water outlet temp, C ( F) 104 (220) 100 (212) Maximum aftercooler inlet temp at 25 C (77 F) ambient, C ( F) 49 (120) Maximum aftercooler inlet temp, C ( F) 71 (160) 66 (150) Maximum fuel flow, L/hr (US gph) Maximum fuel return line restriction, kpa (in Hg) Weights 2 Unit dry weight kgs (lbs) 17837 (39323) Unit wet weight kgs (lbs) 18537 (40867) Notes: 1 For non-standard remote installations contact your local Cummins representative. 2 Weights represent a set with standard features. See outline drawing for weights of other configurations.

Derating factors Standby Prime Standard cooling system: Full rated power available up to 1497m (4917 ft) at 40 C. Above these conditions, derates by 10% per 1000m (3281 ft) and 13.5% per 10 C. Enhanced cooling system: Full rated power available up to 149m (489 ft) at 50 C. Above these conditions, derates by 10% per 1000m (3281 ft). Standard cooling system: Full rated power available up to 1325m (4346 ft) at 40 C. Above these conditions, derates by 12% per 1000m (3281 ft) and 12.5% per 10 C. Enhanced cooling system: Derates by 10% at sea level at 50 C. Above these conditions, derates by 11% per 1000m (3281 ft). Continuous Ratings definitions Emergency Standby Power (ESP): Limited-Time Running Power (LTP): Prime Power (PRP): Base Load (Continuous) Power (COP): power to varying electrical load for the duration of power interruption of a reliable utility source. Emergency Standby Power (ESP) is in accordance with ISO 8528. Fuel stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514. power to a constant electrical load for limited hours. Limited-Time Running Power (LTP) is in accordance with ISO 8528. power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten percent overload capability is available in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514. power continuously to a constant electrical load for unlimited hours. Continuous Power (COP) is in accordance with ISO 8528, ISO 3046, AS 2789, DIN 6271 and BS 5514. No sustained overload capability is available at this rating. Alternator data Voltage Connection 1 Temp rise degrees C Duty 2 Single phase factor 3 Max surge kva 4 Winding No. Alternator data sheet Feature code 380-440 Wye, 3-phase 125 P 5000 312 ADS-334 BA07-2 400-440 Wye, 3-phase 105 P 5280 312 ADS-335 BA03-2 380 Wye, 3-phase 163/105 S/P 5971 312 ADS-515 BA23-2 380&440 Wye, 3-phase 125/80 S/P 6758 312 ADS-516 BA15-2 400-415 Wye, 3-phase 105/80 S/P 6758 312 ADS-516 BA08-2 380&440 Wye, 3-phase 105/80 S/P 7354 312 ADS-517 BA08-2 400-415 Wye, 3-phase 80 P 7354 312 ADS-517 BA05-2 400-415 Wye, 3-phase 150/105 S/P 5971 312 ADS-515 BA18-2 3300 Wye, 3-phase 125/80 S/P 5477 51 ADS-518 BA33-2 3300 Wye, 3-phase 105/80 S/P 6316 51 ADS-519 BA31-2 3300 Wye, 3-phase 80/80 S/P 7040 51 ADS-520 BA34-2 6300-6600 Wye, 3-phase 105 P 5250 61 ADS-521 BA37-2 6300 Wye, 3-phase 125/80 S/P 6076 61 ADS-522 BA44-2 6600 Wye, 3-phase 105/80 S/P 6076 61 ADS-522 BA39-2 11000 Wye, 3-phase 105/80 S/P 5896 51 ADS-522 BA40-2 11000 Wye, 3-phase 80 P 5196 51 ADS-521 BA36-2 11000 Wye, 3-phase 80/80 S/P 6784 51 ADS-523 BA45-2 Notes: 1 Limited single phase capability is available from some three phase rated configurations. To obtain single phase rating, multiply the three phase kw rating by the Single Phase Factor 3. All single phase ratings are at unity power factor. 2 Standby (S), Prime (P) and Continuous ratings (C). 3 Factor for the Single phase output from Three phase alternator formula listed below. 4 Maximum rated starting kva that results in a minimum of 90% of rated sustained voltage during starting.

Formulas for calculating full load currents: Three phase output Single phase output kw x 1000 kw x SinglePhaseFactor x 1000 Voltage x 1.73 x 0.8 Voltage Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building s electrical system except through an approved device or after building main switch is open. For more information contact your local Cummins distributor or visit 2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and Our energy working for you. are trademarks of Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice. D-3531 (09/17)