Electrical Isolation

Similar documents
SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

Changes for the. TOHOPEKALIGA WATER AUTHORITY Standards, Specifications and Details

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

Arms Group Drainage System. 1. Swivel Joint Type 2. Pivot Joint Type 3. Flexible Hose Type 4. Swing Master Joint Type 5. Floating Check Valve

SECTION HANGERS AND SUPPORTS FOR PLUMBING

This section includes materials and installation of ductile-iron pipe and fittings for potable and recycled water systems.

Construction Standard No: 8.3.3

Wide-Range Restraint Solutions

STANDARD SPECIFICATIONS SECTION JACKED CASING

SECTION (15150) - SANITARY WASTE AND VENT PIPING

VSS-2 ½ D HIGH HEAD SUMP PUMP FREE STANDING

San Antonio Water System Standard Specifications for Construction ITEM NO. 812 WATER MAIN INSTALLATION

MPR MODULAR WALL AND CASING SEAL


t y p e V S A S E W A G E P U M P

SECTION NATURAL GAS DISTRIBUTION

Meter Connection Products: Overview

is Central. Gas Water & Waste Water Energy Industrial Your One-Stop Source State-of-the art manufacturing

Isolation Gaskets 101

SECTION LAYING AND JOINTING BURIED PIPELINES

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION HVAC PIPES AND TUBES

8000 PIVOT EXPORT 6-5/8" PIPE 90" COUPLER SPACING

TRICON DOUBLE-CON PLUS

GASKET ASME Standards

SECTION FACILITY STORM DRAINAGE PIPING

THOMAS. Buffalo Saddles. Tap In Products PIPE PRODUCTS. Universal Live Tap In Saddles for All Rigid Pipe Materials.

INSTALLATION MANUAL. B-710/760 H20 SERIES MODULAR UST to AST TRANSITION SUMP

San Antonio Water System Standard Specifications for Construction ITEM NO. 813 WATER SERVICE FOR FIRELINES

Preventing or controlling corrosion by contact can be achieved by insulating the two metals with VR Insulation KIT (Flange Insulation Kit).

SECTION 13. A. Extent of Work: The requirements of this section apply to the piping systems specified elsewhere in these specifications.

192GasCatalog.

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT

UNIVERSITY OF MISSOURI Hydronic Energy Distribution 2016 Q1

SECTION VIBRATION CONTROLS FOR PLUMBING PIPING AND EQUIPMENT

Pipeline Accessories. PSI Wall Sleeves. General Information Selection Guide Technical Data Installation Instruction

.1 ANSI/ASME B31.1, Power Piping, (SI Edition)..2 American Society for Testing and Materials (ASTM)

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING. A. This Section includes the following storm drainage piping inside the building.

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC).

SECTION FACILITY LIGHTNING PROTECTION

Effective Date: Revision #: 1. Section K: Miscellaneous. Casing Insulators/ Stainless Steel. Polyethylene Encasement.

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

Water & Industrial Products Catalog

WATER UTILITY WORKER, 3912 WATER UTILITY SUPERVISOR, 3976

1.2 ACTION AND INFORMATIONAL SUBMITTALS.1 Provide submittals in accordance with Section Submittal Procedures.

CITY OF WARRENVILLE STANDARD SPECIFICATIONS WATER MAIN, SANITARY SEWER AND STORM SEWER

Model AT Modular Linear Anode

Stanford University Facilities Design Guidelines SECTION CATHODIC PROTECTION. B. Section : Site Restoration and Rehabilitation

PSI Compakt Seals and Wall Sleeves with Fixed / Loose Flange

195LiquidsCatalog.

Iron Check Valves & Y-Strainers Illustrated Index

SECTION 7 SEPARATION OF WATER MAINS AND SANITARY SEWERS

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION

PIP PNSC0011 Installation of ASME B31.3 Metallic Piping

SECTION CATHODIC PROTECTION

SECTION STORM UTILITY DRAINAGE PIPING PART 1 - GENERAL 1.1 SUMMARY 1.2 SUBMITTALS 1.3 PROJECT CONDITIONS

CVO/169897A OCTOBER 29, CONVEYANCE PIPING GENERAL

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS

SAMPLE SPECIFICATIONS FOR PREFABRICATED FRP LIFT STATIONS

SECTION FACILITY STORM DRAINAGE PIPING

1. Cast-in-place concrete is specified in Section

DARTMOUTH COLLEGE DESIGN September 15, 2004 &CONSTRUCTION GUIDELINES

40'-0" PIPE SUPPORT (TYP.) (SEE DWG. NO. SK-2 OR DWG. NO. SK-4)

MSME Testing Centre, 65/1, G. S. T. Road, Guindy, Chennai, Tamil Nadu. Discipline Electrical Testing Issue Date

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE)

DIAGRAM FOR CALCULATING PIPE SIZES, DISCHARGE VELOCITIES AND LOSS OF HEAD IN STANDARD STEEL PIPE PIPE FRICTION LOSS CHART

Installation Guidelines for Flygt Pumps Pump Anchoring Recommendations

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING

A. This Section includes gravity-flow, nonpressure storm drainage outside the building, with the following components:

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION PAGE 1 SECTION SUPPORTING DEVICES

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

2 5 0 P. S. I. G. AMERICAN DARLING 5 1 /4" B-84-B FIRE HYDRANT

Ø mm. SYSTEM KAN-therm. High quality for reasonable price TECHNOLOGY OF SUCCESS ISO 9001

SECTION SANITARY SEWERAGE PART 1 GENERAL 1.01 RELATED DOCUMENTS

1 Revised: 2019 Edition

SECTION DUCTILE IRON FITTINGS. A. This section includes materials, installation, and testing of ductile iron fittings 48 inches and smaller.

sites under the deposit become anode and the lead to pitting. Hence, a good design should not allow the built up of impurities on surface

TABLE OF CONTENTS

CITY OF FARGO SPECIFICATIONS SEWER AND WATER SERVICE CONNECTIONS

CONTENTS. B. System Design and Performance Requirements

A. Gravity-Flow, Nonpressure, Drainage-Piping Pressure Rating: 10-foot head of water (30 kpa).

PVC PRESSURE FITTINGS

General Rules for Underground Polyethylene Pipe in Propane Applications:

Copper-Type K soft Drawn 40, 50 HDPE 100 and larger

Foundation Specifications for 3.6-/3.7-Meter Earth Station Antennas

PART 5 WATER SYSTEMS

Diffused Aeration Piping Equipment

DIVISION 15-MECHANICAL SECTION SUPPORTS AND ANCHORS PN PART 1 - GENERAL 1.01 SECTION INCLUDES. A. Pipe and equipment support systems.

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SERVICE LINES, METERS AND APPURTENANCES

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping

MATERIAL/MANUFACTURER SPECIFICATIONS FOR DISTRIBUTION WATER MAINS AND APPURTENANCES

H. Underground Transmission System Design

SECTION GROUNDING AND BONDING

DUCTILE IRON PIPES AND FITTINGS DETAILED PRODUCTS SPECIFICATIONS

AVK Couplings and Adaptors

Operating Instructions

Facility Sanitary Sewers

Youngstown State University

CHINO VALLEY FIRE DISTRICT FIRE PROTECTION STANDARD

Transcription:

Electrical Isolation Period 6 Practical Applications 2017 February 21-23, 2017 Mark E. Anderson M.T.S 1

Introduction Common isolating fittings & their installation Uses & locations of isolating fittings February 21-23, 2017 Mark E. Anderson M.T.S 2

COMMON ISOLATING FITTINGS AND THEIR INSTALLATION Unions Flanges Compression Couplings Monolithic Joints Meter Swivels and Meter Bars February 21-23, 2017 Mark E. Anderson M.T.S 3

Unions (example on next slide) Frequently used in small diameter pipe, 2 to 3-inch Generally confined to above ground applications most gas codes prohibit their use underground. common location for isolating unions is on service risers just before the meter Do not over tighten the nut Over-tightening can crack the sleeve and squash the gasket, causing a short and rendering the union useless February 21-23, 2017 Mark E. Anderson M.T.S 4

Isolating Union February 21-23, 2017 Mark E. Anderson M.T.S 5

Isolating Flanges (continued on next slide) Used wherever isolation is desired in a flanged connection Can also be added in piping system where otherwise there would be no break Flange isolating kit consists of four components: Isolating gasket - small gasket that just fits over the mating faces of the flange, or a full circle gasket that extends to the outside diameter of the flange and has holes in it for the bolts Fiber or other non-metallic isolating washers; these go against the flange face Steel bearing washers; these go outside of the fiber washers Non metallic isolating sleeves that go over the bolts Some standard gaskets will also function as isolating gaskets so long as the gaskets contain no metallic particles or components Many high-pressure gaskets do contain metal and cannot be used in an isolating flange February 21-23, 2017 Mark E. Anderson M.T.S 6

Isolating Flanges (continued on next slide) Installation Cautions fiber isolating and the steel bearing washers are put on in the right order and that they are put on every bolt fiber washers go against the flange face and the steel ones go under the bolt head or nut Flange bolts may be isolated on both sides of the flange or on only one side Sleeve goes over the bolt Do not jam a bolt through the sleeve; bolt threads will cut thorough the sleeve and cause a short If bolts do not fit smoothly, use smaller diameter bolts of the same strength as the original ones February 21-23, 2017 Mark E. Anderson M.T.S 7

Isolating Flanges (continued from previous slide) Installation (continued) Flange faces must line up Forcing them into line will put a stain on the sleeves that will very likely crack them Can protect flange from corrosion by filling the space with an inhibited grease or similar material to protect Wrap outer edge with pipeline tape to prevent the entrance of water into the flange Do not over tighten the bolts; can deform the isolating washers and cause shorts (Isolating flange shown on next slide) February 21-23, 2017 Mark E. Anderson M.T.S 8

Isolating Flange February 21-23, 2017 Mark E. Anderson M.T.S 9

Compression Couplings Plastic cap that fits over one end of the coupled pipe ends and extends an inch or so beyond the compression ring cap separates the two pipe ends, thus proving isolation between them don t jam the two pipe ends together; a cracked plastic cap can cause a short Plastic separator placed between the pipe ends Compression coupling shown on next slide February 21-23, 2017 Mark E. Anderson M.T.S 10

Compression Coupling February 21-23, 2017 Mark E. Anderson M.T.S 11

Monolithic Joints Self-contained units isolating mechanism sealed within a steel container entire fitting is welded into the pipeline generally more expensive less prone to damage or failure than other isolating fittings Monolithic Joint shown on next slide February 21-23, 2017 Mark E. Anderson M.T.S 12

Monolithic Joints February 21-23, 2017 Mark E. Anderson M.T.S 13

Meter Swivels and Meter Bars Installed at a residential gas meter Swivels are equipped with an isolating washer and sleeve very similar to the those in an isolating union do not over-tighten the swivel; may crack the isolation and cause a short Meter bar contains a built in isolating assembly The larger of the two nuts contains the isolation Meter bar shown on next slide February 21-23, 2017 Mark E. Anderson M.T.S 14

Typical Meter Bar Isolated Union February 21-23, 2017 Mark E. Anderson M.T.S 15

USES AND LOCATIONS OF ISOLATING 2017 Underground Corrosion Short Course FITTINGS Above Grade Installation Cathodic Protection Sectionalizing Distribution Cathodic Protection Dissimilar Metal Separation Metering, Compressor and Town Border Stations Regulator Sites Casing Isolation Short Circuits February 21-23, 2017 Mark E. Anderson M.T.S 16

Above Grade Installation Best to isolate above grade can be easily tested can be easily repaired in the event of a failure Underground installation subjects the fitting to soil stress and the possibility of wet, low resistance soil reducing the isolating quality of the fitting February 21-23, 2017 Mark E. Anderson M.T.S 17

Cathodic Protection Isolated from other structures that are not part of the protection system Confines cathodic protection current to the piping to be protected, making smaller, less expensive cathodic protection systems possible Important when protecting coated structures with galvanic anodes, as anodes may not produce sufficient current to overcome the short February 21-23, 2017 Mark E. Anderson M.T.S 18

Sectionalizing Isolating fittings used to separate, or sectionalize Gas distribution systems may be broken up into families of piping, each family isolated from the others Shorts or other malfunction in one family does not affect the other families Facilitates troubleshooting in the family where the trouble occurred See next slide for sectionalizing February 21-23, 2017 Mark E. Anderson M.T.S 19

Sectionalizing February 21-23, 2017 Mark E. Anderson M.T.S 20

Distribution Cathodic Protection Gas distribution piping electrically connected to steel service lines, is isolated at the meter this isolation confines the cathodic protection to the gas piping, with no loss to water piping, telephone cable and the like Residential services can usually be isolated at the meter with meter swivels, meter bars or unions Commercial services, which usually have large meters, generally require flange or coupling isolation February 21-23, 2017 Mark E. Anderson M.T.S 21

Dissimilar Metal Separation Isolation is often used to separate dissimilar metals In effect disconnecting the anode from the cathode copper service line, for example, may be isolated from a steel or ductile iron main Past practices - pipe was replaced with coated and cathodically protected pipe old, bare services were left in place and electrically isolated at the main Note; services isolated at the main cannot be used as test points for the main February 21-23, 2017 Mark E. Anderson M.T.S 22

Metering, Compressor and Town Border Stations Transmission lines are nearly always isolated from metering and town border stations usually represent points of ownership change separates cathodic protection systems Compressor stations are complex systems and usually cathodically protected separately isolation is used to prevent any problems in the compressor station from affecting the transmission line protection. Some may prefer not to isolate compressor stations from the transmission line to avoid the maintenance that may be associated with isolating fittings sufficient cathodic protection is used to overcome any undesirable effect on the transmission line February 21-23, 2017 Mark E. Anderson M.T.S 23

Regulator Sites Points where pressures change Most companies isolate the higher-pressure piping from the lower pressure piping Especially valuable where galvanic anodes are used on both systems, as the isolation acts like sectionalizing and separates the two systems electrically Telemetering and motor operated valves can cause shorts Next slide shows typical regulator site isolation Notice the places where shorts can occur February 21-23, 2017 Mark E. Anderson M.T.S 24

Distribution Regulator Setting February 21-23, 2017 Mark E. Anderson M.T.S 25

Casing Isolation (continued on next slide) Casings must be isolated from carrier pipes Many casings are bare Protective current will flow to the casing and then to the pipe through the metallic contact, leaving the pipe within the casing unprotected Casing isolation consists of three major components casing spacers centering cradles end seals February 21-23, 2017 Mark E. Anderson M.T.S 26

Casing Isolation (continued on next slide) Spacers are non-metallic runners that are bolted around the carrier pipe Spacers serve three purposes electrically separate the carrier pipe from the casing support the pipe within the casing pipe pulled through the casing rests on the spacers; this prevents coating damage while the carrier pipe is being installed February 21-23, 2017 Mark E. Anderson M.T.S 27

Casing Isolation Centering cradle Partial spacer that fits under the end of the carrier pipe and prevents it from bending down and contacting the casing Most casing shorts occur at the ends End seals Boot type is essentially a sealed rubber boot Modular type secures the carrier pipe in place and seals the casing against intrusion of water and debris Carrier pipe must be well supported for several feet beyond the end of the casing Sand bags or well-tamped earth can be used Pipe should come out of the casing at exactly the elevation of the bottom of the ditch See casing on next slide February 21-23, 2017 Mark E. Anderson M.T.S 28

Casing February 21-23, 2017 Mark E. Anderson M.T.S 29

Short Circuits Electrical isolation fittings can inadvertently be by-passed, or shorted Any metallic path, such as a kick brace, regulator equalizing line or pipe supports attached to aluminum siding that goes around an isolator will render the isolator ineffective Above ground fittings such as block valves may have kick braces or other reinforcements that will provide a short circuit across the valve braces need to be isolated in such a way that no short is created February 21-23, 2017 Mark E. Anderson M.T.S 30

Lab 8 Flange Isolation Test 1. Hook leads up to meter set 2. Coated Steel (represents gas distribution system or other protected system) 3. Copper Pipe (represents water distribution system or other non-protected system) 4. Connect magnesium anode to the coated pipe 5. Take P/S reading of the coated pipe 6. Short the isolation flange 7. Take P/S reading of the coated pipe February 21-23, 2017 Mark E. Anderson M.T.S 31

Summary Common isolating fittings & their installation Uses & locations of isolating fittings February 21-23, 2017 Mark E. Anderson M.T.S 32

Questions???? February 21-23, 2017 Mark E. Anderson M.T.S 33