TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

Similar documents
TEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey

TEST REPORT. Report No.: G Rendered to: CR LAURENCE CO., INC. Vernon, California

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

PERFORMANCE TEST REPORT. Report No.: H Rendered to: VELUX America LLC Greenwood, South Carolina

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

TEST REPORT. Rendered to: ALL WEATHER INSULATED PANELS Vacaville, California. PRODUCT TYPE: Wall Panels SERIES/MODEL: DM45 Series

PERFORMANCE TEST REPORT. Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly

TEST REPORT. Report No.: B Rendered to: MI WINDOWS AND DOORS, INC. Gratz, Pennsylvania

TEST REPORT. Report No.: A Rendered to: TUBELITE, INC. Walker, Michigan

TEST REPORT. ASSOCIATED MATERIALS, INCORPORATED Cuyahoga Falls, Ohio. Rendered to: PRODUCT TYPE: Fixed Window SERIES/MODEL: A780 SPECIFICATIONS:

TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. Rendered to: All Weather Insulated Panels Vacaville, California. PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series

TEST REPORT. Report No.: F Rendered to: MI WINDOWS AND DOORS, LLC Gratz, Pennsylvania

TEST REPORT. Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California. SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window

Architectural Testing TEST REPORT. Rendered to: COEUR D'ALENE WINDOW Spokane Valley, Washington. PRODUCT TYPE: PVC Fixed Window SERIES/MODEL: 3310

TEST REPORT. Report No.: A Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina

TEST REPORT. Rendered to: UNIVERSAL PULTRUSIONS, LLC Marshall, Arkansas. Cycles 2,000,000. Summary of Results

Structural Performance Certification Authorization Report

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: ALUMIL US. SERIES/MODEL: M300 Falcon PRODUCT TYPE: Aluminum Horizontal Sliding Window (XO)

Structural Performance Certification Authorization Report

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: MGM WINDOW COMPANY Hendersonville, Tennessee

TEST REPORT. Report No.: F Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT ASTM E331. Report No.: E Rendered to: IMISON USA Houston, Texas

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: ALL-WEATHER INSULATED PANELS. SERIES/MODEL: SM40 PRODUCT TYPE: Insulated Sandwich Wall Panel

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

Structural Performance Certification Authorization Report

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

MOCK-UP TEST REPORT. Rendered to: TUBELITE INC. PROJECT: 300 ES Interior Glazed Curtain Wall

TEST REPORT. Rendered to: EARTHWISE GROUP, LLC Liberty Township, Ohio

AAMA 506 TEST REPORT. Report No.: G Rendered to: VEKA INC. Fombell, Pennsylvania

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: BRICK-IT. SERIES/MODEL: Brick Veneer Panel Systems PRODUCT TYPE: Wall Panel Systems

Carter Fabricating Inc. 326 Deerhurst Drive Brampton, Ontario L6T 5H9. Mr. Mike Libreiro

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

Structural Performance Certification Authorization Report

Carter Architectural Panels Inc. 221 E. Willis Road A Unit 18 Chandler, AZ Mr. Bruce Bourne

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT. Report Number: C Rendered to: Tubelite Inc.

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A AAMA TEST REPORT SUMMARY

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: BUILDERS ACCESSORIES, INC.

INTERNATIONAL WINDOW TEST REPORT

REPORT NUMBER: COQ-003 ORIGINAL ISSUE DATE: July 19, 2013

PERFORMANCE EVALUATION OF THE RIVETLESS PANEL SYSTEM IN ACCORDANCE WITH AAMA FOR PRESSURE EQUALIZATION BEHAVIOR & WATER PENETRATION RESISTANCE

Construction Consulting Laboratory, International

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: FLEETWOOD WINDOWS & DOORS. SERIES/MODEL: Norwood 3070HI OOX PRODUCT TYPE: Sliding Glass Door

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America LLC. SERIES/MODEL: FCM B PRODUCT TYPE: Fixed Glass Glazed Curb Mount Skylight

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built)

TEST REPORT. Report No.: F Rendered to: VELUX America LLC Greenwood, South Carolina

Dennis Fassnacht Jr :59:35-04'00'

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT SUMMARY. Rendered to:

MOCK-UP TEST REPORT. Report No: NCTL Test Dates:06/22, 07/23-27/10 Test Dates: 08/23-25/10 Report Date: 08/26/10

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America Inc. SERIES/MODEL: VCM/VCE B PRODUCT TYPE: Venting Curb Mounted Skylight

TEST REPORT. Rendered to: AD SKYLIGHTS, INC. Algonquin, Illinois. AD Skylight without Guard

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.

ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC.

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX AMERICA INC. SERIES/MODEL: CAP-1 PRODUCT TYPE: Fixed Acrylic Glazed Skylight

OSHA FALL PROTECTION TEST REPORT. Rendered to: SERIES/MODEL: FS S PRODUCT TYPE: Fixed Deck Mounted Skylight

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina

KNOTWOOD, A DIVISION OF OMNIMAX INTERNATIONAL MIAMI-DADE TEST REPORT

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: W250C Awning TYPE: Projecting (Awning)

SECTION STAINLESS STEEL WALL PANELS

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: COASTAL INNOVATIVE PRODUCTS

TEST REPORT. Rendered to: SENTINEL FENCE AND RAIL. For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post

TEST REPORT AAMA 501.5

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT

TEST REPORT. Report No.: H Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia

MOCK-UP TEST REPORT NCTL ACURLITE STRUCTURAL SKYLIGHTS MOCKUP TEST UNIT TEST DATES 03/13/17, 03/21/17 03/23/17 REPORT DATE 04/03/17

TEST REPORT. Rendered to: ENDURIS EXTRUSIONS INC. For: 6' high by 8' wide Dog Ear Picket Shadow Box Privacy Fence Systems

Field Testing and Forensic Analysis for Manufacturers

TEST REPORT. Rendered to: FAIRWAY BUILDING PRODUCTS, LP. For: Solutions Aluminum Guardrail System with Glass Balustrades

ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: WIRE-BOND. SERIES/MODEL: Masonry Tie Thermal Evaluations (2x6 Steel Stud Wall)

STRUCTURAL PERFORMANCE TEST REPORT. Series Casement (Rep/Impact/AAMA) C-C70 940mm x 1930mm (37 x 76 )

PERFORMANCE TEST REPORT. Rendered to: HILTI CORPORATION. PRODUCT: Extreme Weather Window & Door Insulating Foam Sealant

TEST REPORT. Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania. PRODUCT TYPE: Drywall Clip

TEST REPORT. Report No.: G Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390. TYPE: Sliding Glass Door

TEST REPORT. Report No.: G Rendered to: CR LAURENCE CO., INC. Vernon, California

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass

AAMA / ASTM E1996 / ASTM E1886 HURRICANE IMPACT AND PRESSURE CYCLE TEST REPORT

TEST REPORT. Rendered to: KEYLINK FENCING & RAILING, INC. For: PRODUCT: Lancaster Series. TYPE: Aluminum Level Guardrail System

SECTION ALUMINUM WINDOWS

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440. TYPE: Sliding Glass Door

MILLENNIUM METALS, INC TEST REPORT

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door

TEST REPORT. Rendered to: AFCO INDUSTRIES, INC. For: PRODUCT: Redi-Rail. TYPE: Aluminum Level Guardrail System

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door

SECTION ALUMINUM WINDOWS

PERFORMANCE TEST REPORT. Rendered to: SIMTEK FENCE. TYPE: SimTek Privacy Fence System

Transcription:

Architectural Testing TEST REPORT Report No.: D0162.01-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite Panel System AAMA 508-07, Voluntary Test Method and Specification for Pressure Equalized Rain Screen Wall Cladding Systems. Test Dates: 08/14/13 Through: 08/16/13 Test Record Retention Date: 08/29/17

Page 1 of 6 1.0 Report Issued To: TFC A Division of Centurion Industries, Inc. 1107 North Taylor Road Garrett, Indiana 46738 2.0 Test Laboratory: Architectural Testing, Inc. 849 Western Ave. North St. Paul, Minnesota 55117 651-636-3835 3.0 Project Summary: 3.1 Product Type: Pressure Equalized Rainscreen 3.2 Series/Model: 4 mm Composite Panel System 3.3 Compliance Statement: Results obtained are tested values and were secured by using the designated test methods. Test specimen description and results are reported herein. 3.4 Test Dates: 08/14/2013-08/16/2013 3.5 Test Record Retention End Date: All test records for this report will be retained until August 29, 2017. 3.6 Test Location: Architectural Testing, Inc. test facility in St. Paul, Minnesota. 3.7 Test Sample Source: The test specimen was provided by the client Representative samples of the test specimens will be retained by Architectural Testing for a minimum of four years from the test completion date. 3.8 Drawing Reference: The test specimen drawings have been reviewed by Architectural Testing and are representative of the test specimens reported herein. Test specimen construction was verified by Architectural Testing per the drawings located in Appendix B. Any deviations are documented herein or on the drawings. 3.9 List of Official Observers: Name Karl Lips-Eakins Company Architectural Testing, Inc.

Page 2 of 6 4.0 Test Methods: AAMA 508-07, Voluntary Test Method and Specification for Pressure Equalized Rain Screen Wall Cladding Systems. ASTM E 283-04, Standard Test Method for Determining Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen. Testing was conducted at 75 Pa (1.57 psf) positive static air pressure difference. ASTM E 1233-06 (Modified), Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylights, and Curtain Walls by Cyclic Static Air Pressure Differential. Testing was conducted for 100, three-second cycles from 240 Pa (5.0 psf) to 1200 Pa (25.0 psf) to 240 Pa (5.0 psf). ASTM E 331-00, Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls, by Uniform Static Air Pressure Difference. Testing was conducted at 300 Pa (6.24 psf) positive static air pressure difference for a 15 minute duration. Water was applied to the mock-up at a minimum rate of 5 gal/hr/ft 2. AAMA 501.1-05, Standard Test Method for Water Penetration of Windows, Curtain Walls, and Doors Using Dynamic Pressure. Testing was conducted with a dynamic pressure equivalent of 300 Pa (6.24 psf) for a 15 minute duration. Water was applied to the mock-up at a minimum rate of 5 gal/hr/ft 2. ASTM E 330-02, Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylights, and Curtain Walls by Uniform Static Air Pressure Difference. 5.0 Test Specimen Description: 5.1 Product Sizes: Overall Area: Width Height 6.1 m² (66.2 ft 2 ) millimeters inches millimeters inches Overall size 2470 97-1/4 2489 98 Panel size (x4) 1225 48-1/4 1212 47-3/4

Page 3 of 6 5.0 Test Specimen Description: (Continued) 5.2 Panel Construction: The wall system consisted of four composite panels that measured 4 mm (0.158") thick. The panels were constructed with a 0.118" thick plastic core and 0.020" thick aluminum interior and exterior skins, adhered to the plastic core. One 90 bend was utilized on all four sides of the panel with a 3/4" return leg. An aluminum extrusion was secured to the interior perimeter of the panel and secured with #6 x 1" screws. Extrusion corners were mitered and joined with a 4" x 4" piece of composite material. Horizontal joints, in the mid-field of the wall system, utilized a bent aluminum flashing to divert water towards the panel. The panels had 1/8" dia. weep holes along the bottom return leg spaced 6" from corners and mid-span. 3" long "F" shaped aluminum extrusions were utilized to secure the panels to the base wall, 2 per side, by fitting into the panel edge and screwed onto studs/sheathing with a #12 x 2" hex head screw. The perimeter of the wall system utilized an "L" shaped aluminum flashing. The intermediate joints of the wall panel system utilized an aluminum composite filler strip that slid into the panel backer extrusion. 5.3 Test Wall Construction: The test wall was constructed of 16 gauge, 6" galvanized steel studs. The steel studs were spaced 16" on center inside a 2x10 wood buck. The stud wall was covered with 1/8" thick clear lexan, sealed and secured to the exterior of the wall to simulate an air/water barrier. The wall panel system was then installed onto the clear polycarbonate in a manner consistent with normal construction procedures for the system. The clear lexan was calibrated to a predetermined air leakage rate by drilling 1/8" diameter holes on the backside in a uniform pattern, making sure to create an even pressure drop and leakage rate across the wall and in each quadrant. The exterior of the test unit was sealed to the wood buck with silicone. 5.4 Reinforcement: No panel reinforcement was utilized. 5.5 Installation: Installation of the tested product was performed by the client. The panels were installed in a bottom to top and left to right order. The perimeter of the wall assembly was sealed with silicone. 5.6 Cavity Depth: 38 mm (1-1/2 in.) 5.7 Air Cavity Volume to Vent Area Ratio: 1.6 m 3 /m 2 (55.8 ft 3 /ft 2 )

Page 4 of 6 6.0 Test Results: The temperature during testing was 26 C (79 F). The results are tabulated as follows: Air Leakage (Infiltration per ASTM E 283) Pressure Results Allowed Note 0.6 L/s/m 75 Pa (1.57 psf) 2 0.6 L/s/m 2 (0.11 cfm/ft 2 ) min. (0.12 cfm/ft 2 ) 0.7 L/s/m 2 (0.13 cfm/ft 2 1 ) max. Pressure Cycling (per ASTM E 1233) 100 cycles from 240 Pa (5 psf) to 1200 Pa (25 psf) to 240 Pa (5 psf) Compartment #1 Results Allowed Note Cycle Time Lag 0.01 sec. 0.08 sec. max. Cycle Pressure Difference 4.8 Pa (0.10 psf) 600 Pa (12.5 psf) max. 2, 3 PASS / FAIL PASS -- Static Water Penetration (per ASTM E 331) Pressure Results Allowed Note 300 Pa (6.24 psf) <0.01 m 2 (<0.01 ft 2 ) 0.30 m 2 (3.20 ft 2 ) 4, 5 PASS Dynamic Water Penetration (per AAMA 501.1) Pressure Results Allowed Note 300 Pa (6.24 psf) <0.01 m 2 (<0.01 ft 2 ) 0.30 m 2 (3.20 ft 2 ) 4, 5 PASS

Page 5 of 6 7.0 Test Results: Optional Performance Uniform Load Deflection (per ASTM E 330) Pressure Results Allowed Note taken on panel edge +2880 Pa (+60.0 psf) -2880 Pa (-60.0 psf) 3.8 mm (0.15") 0.3 mm (0.01") Report Only 6, 7 Uniform Load Structural (per ASTM E 330) Pressure Results Allowed Note taken on panel edge +2880 Pa (+60.0 psf) -2880 Pa (-60.0 psf) <0.3 mm (<0.01") <0.3 mm (<0.01") Report Only Note #1: The calibrated leakage was achieved with twelve, 1/8" diameter holes drilled through the polycarbonate. All holes were evenly distributed in each stud cavity and located 6" above the bottom and the midspan of the wall. Note #2: Pressure tap was attached through the air barrier at center of wall. Note #3: Reference Pressure Cycling graph in Appendix A. Note #4: Water percolated at the bottom of the panel at the weeps. Water was visibly present on the polycarbonate. Note #5: Water on the polycarbonate air/water barrier surface was in the form of mist or droplets. Note #6: Loads were held for 10 seconds. Note #7: Tape and film were not used to seal against air leakage during structural testing. General Note: All testing was performed in accordance with the referenced standards. This report is not intended as a comprehensive evaluation of the system regarding performance and application to specific buildings. 6, 7

Page 6 of 6 8.0 Test Equipment: Computerized control panel to run positive pressures, cyclic pressures, and measure air leakage rates. Structural test chamber to mount the test wall, as to evaluate the performance of the wall panel system for static and cyclic pressures, as well as water penetration. The wall was situated such that the interior side of the test wall was accessible to observe air and water leakage. Dynamic wind generator to create a wind pressure to test the wall panel system for dynamic water penetration. Computerized data management equipment to read, log, and graph differential pressures. The service life of this report will expire on the stated Test Record Retention End Date, at which time such materials as drawings, data sheets, samples of test specimens, copies of this report, and any other pertinent project documentation, shall be discarded without notice. If test specimen contains glazing, no conclusions of any kind regarding the adequacy or inadequacy of the glass in any glazed test specimens can be made. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimens tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, Inc. Karl A. Lips-Eakins Senior Technician Daniel A. Johnson Director, Regional Operations KLE/jb Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Graph (1) Appendix-B: Drawings (2) This report produced from controlled document template ATI 00521, issued 03/4/11.

Appendix A Graph

Test Report No.: C8510.01-109-44 Report Date: 06/26/13 ASTM E 1233 Pressure Equalization Testing 30 Exterior Pressure Cavity Pressure 25 0.01 second lead time 0.10 psf 20 Pressure (psf) 15 10 5 0 200 201 202 203 204 205 206 207 208 209 210 Time (seconds)

Appendix B Drawings

R 1107 NORTH TAYLOR ROAD GARRETT, IN 46738 PH. (260) 357-6665 FAX (260) 357-6533 509 TEST PANEL'S WALL ELEVATION 509 TEST PANELS 7-24-13 1" = 1' DF A2.0

R 1107 NORTH TAYLOR ROAD GARRETT, IN 46738 PH. (260) 357-6665 FAX (260) 357-6533 509 TEST PANEL'S WALL DETAILS 509 TEST PANELS 7-24-13 6" = 1' DF A4.0