Solar Ejector Refrigerating And Air-Conditioning System (SERAS) For Tower Buildings

Similar documents
Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis

Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy

The Benefit of Variable-Speed Turbine Operation for Low Temperature Thermal Energy Power Recovery

Computational Analysis Of Ejector With Oscillating Nozzle

Experimental investigation of solar-driven double ejector refrigeration system

Solar Cooling for Mediterranean Region as a Crop Storage Technology

Experimental Study of a CO2 Thermal Battery for Simultaneous Cooling and Heating Applications

Energy and Buildings

Parametric Study of a Vapor Compression Refrigeration Cycle Using a Two-Phase Constant Area Ejector

Investigations Of Low Pressure Two-Phase Steam- Water Injector

Analysis of Ejector Cooling Flow. Butovskyi Iegor, Kogut Volodimyr, Khmelniuk Mykhailo. Odessa National Academy of Food Technologies, Odessa, Ukraine

Heating Performance with a Volume Ratio on 2-Stage Compressor

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions

Compound ejectors with improved off-design performance

Performance Mapping for Variable Ductless Heat Pump Systems in Heating, Cooling and Defrost Operation

Application Of Oil Flooded Compression With Regeneration To A Packaged Heat Pump System

DESIGN ANALYSIS OF A REFRIGERATED WAREHOUSE USING LNG COLD ENERGY

COMPARATIVE ANALYSES OF TWO IMPROVED CO 2 COMBINED COOLING, HEATING, AND POWER SYSTEMS DRIVEN BY SOLAR ENERGY

Department of Mechanical Engineering. MSc/PGDip/PGCert in Energy Systems and the Environment. Specialist Modules

Parameters of the Atmospheric Air in the Dimensioning of Industrial Cooling Tower

Solar Air-Conditioning Systems in small - medium scale applications

Mathematical Modeling of Basic Parts of Heating Systems with Alternative Power Sources

SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS

A Scroll Expander with Heating Structure and Their Systems

Volume 2, Issue 2 (2014) ISSN International Journal of Advance Research and Innovation

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

Low-Grade Waste Heat Recovery for Power Production using an Absorption-Rankine Cycle

Buoyancy Driven Solar Engine

Numerical Investigation of the Flow Dynamics of a Supersonic Fluid Ejector

Performance Evaluation Of Thermally Activated Glass Fibre Reinforced Gypsum Building Equipped With Desiccant System

Using Simulation Model to Reduce System Design Time and Cost

The efficiency of the heat pump water heater, during DHW tapping cycle

Heat Pump Assisted Solar Thermal System

Compressor Performance Comparison When Using R134 and R1234YF as Working Fluids

Study of Unsteady State Thermal Characteristics of Homogeneous and Composite Walls of Building and Insulating Materials for Passive Cooling

Performance Characteristics and Mapping for a Variable-Speed Ductless Heat Pump

A review on Present development in refrigeration jet ejector system

Surface of Flow and Force Effective Areas Applied to Development of Reciprocating Compressors

COEFFICIENT OF PERFORMANCE OF TWO PHASE CONDENSING EJECTOR REFRIGERATION SYSTEM WITH R-22

Void Fraction of CO2 and Ammonia in Multiport Aluminum Microchannel Tubes

A Simplified Thermal Model for a CO2 Compressor

- 2 - SME Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency:

Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System

Fundamental Investigation Of Whole-Life Power Plant Performance For Enhanced Geothermal Systems

COOLING TOWER DESIGN FOR CENTRAL GENERATORS OF CUET, BANGLADESH. Mohammad Sharif Khan, Golam Mainuddin, Abu Sadat Mohammad Sayem, Nadeem Nafis

LCCP Analysis of Energy-Saving Effect of Defaulting to Recirculated Cabin Air in EV Mobile Air Conditioning System

DESIGN OF VAPOUR ABSORPTION REFRIGERATION SYSTEM OF 1.5TR CAPACITY BY WASTE HEAT RECOVERY PROCESS

Experimental Results on a New Prototype Packaged Heat Pump System Retrofitted with Oil Flooded Compression and Regeneration Technology

Component-Based Vapor Compression Simulation Tool With Integrated Multi-Objective Optimization Routines

CHARACTERISTICS OF PRESSURE RECOVERY IN TWO-PHASE EJECTOR APPLIED TO CARBON DIOXIDE HEAT PUMP CYCLE

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies

Deformation Control of Scroll Compressor for CO2 Refrigerant

Innovative Process for Comprehensive Treatment of Liquid Radioactive Waste

Figure 1: Uncovered and covered PVT collectors

Energy Simulation And Optimized Retrofit Practices Applied To A Real Dwelling

BEEP Guidelines for Energy Efficient Design of Multi-Storey Residential Buildings

ENERGY EFFICIENT TECHNIQUES AND SIMULATION OF ENERGY CONSUMPTION FOR THE SHANGHAI ECOLOGICAL BUILDING

Utilizing Heat Dump Capacity of a Small Pond Attached to Infloor Slab of a Net-Zero Energy House

Modelling of Phase Change Material Implemented Into Cold Storage Application

carbon-neutral architectural design Pablo La Roche CRC Press Taylor & Francis Croup Boca Raton London NewYork CRC Press is an imprint of the

Solar cooling design: a case study

Simulation of Solar Air-Conditioning System with Salinity Gradient Solar Pond

proposal for a mini solar chimney with venturi to multiply air flow velocity and to generate electricity from solar energy with high efficiency

Conversion Factors for Comparing the Performance of Variable Refrigerant Flow Systems

Geothermal Heat Pump Systems Efficiency in Russia

Optimisation and Cost Analysis of a Lithium Bromide Absorption Solar Cooling System

Thermal Comfort Evaluation of a Heat Pump System using Induced-air Supply Unit

Experimental Study on Thermal Performance Improvement of Envelop Integrated with Phase Change Material in Air-conditioned Room

Development of an Innovative 2.5 kw Water- Silica Gel Adsorption Chiller

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

Endless Possibilities Use of Heat Pipe for Global Warming Reduction

S O L A R C O OL I N G F O R A S U S T A I N A B L E EN E R G Y F U T U R E MARA MORBIN ITALY

Energy towers A renewable energy technology for producing electricity and desalinated water in arid climates

Investigation on A Ground Source Heat Pump System Integrated With Renewable Sources

SOLAR COOLING WITH SMALL SIZE CHILLER: STATE OF THE ART

Practice Final Exam (A) Six problems. (Open-book, HW solutions, and notes) (Plus /minus 10 % error acceptable for all numerical answers)

Solar Passive Techniques: Earth Air Tunnel

CHAPTER 1 INTRODUCTION

A Trans-critical CO2 Heat Pump System for Waste Heat Utilization in Warm Weather Condition Applied to a Milk Refrigeration Plant

COP Improvement Of A CO2 Refrigeration System With An Expander-Compressor-Unit (ECU) In Subcritical And Transcritical Operation

Department of Mechanical and Materials Engineering. Solar Energy Research Institute Faculty of Engineering and Built environment.

Performance Evaluation under the Actual Operation Condition of a Ground Source Multiheat Pump System

A Method for On-Going Commissioning of VRV Package Systems Using a. Simulation Model

IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS

Experimental investigation of a Scroll unit used as a compressor and as an expander in a Heat Pump/ ORC reversible unit

Analysis of Solar Thermal Cooling System Using TRANSOL

Heat Pump With a Condenser Including Solid- Liquid Phase Change Material

Thermal Performance Analysis to Assess Inhabitant Comfort inside LIG houses in Chhattisgarh

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

Solar Thermal Energy

Simulation Studies on Performance of Solar Cooling System in UAE Conditions

Stefan Elbel Pega Hrnjak University of Illinois at Urbana-Champaign

Experimental Studies on a Solar Assisted Heat Pump Working with R22: An Exergy Point of View

Control strategies study of a complete solar assisted air conditioning system in an office building using TRNSYS.

CAE 331/513 Building Science Fall 2017

THEORETICAL RESEARCH REGARDING HEAT TRANSFER BETWEEN GREENHOUSES AND ENVIRONMENT

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

Investigating two configurations of a heat exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System (IHICSSWHS)

Cold Plane Innovative Method for Humidity Condition Control

Transcription:

Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2010 Solar Ejector Refrigerating And Air-Conditioning System (SERAS) For Tower Buildings Dmytro Buyadgie Wilson Ltd Sergii Nichenko Wilson Ltd Vitaliy Sechenyh Wilson Ltd Follow this and additional works at: http://docs.lib.purdue.edu/ihpbc Buyadgie, Dmytro; Nichenko, Sergii; and Sechenyh, Vitaliy, "Solar Ejector Refrigerating And Air-Conditioning System (SERAS) For Tower Buildings" (2010). International High Performance Buildings Conference. Paper 13. http://docs.lib.purdue.edu/ihpbc/13 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

3240, Page 1 Solar ejector refrigerating and air-conditioning system (SERAS) for tower buildings Dmytro BUYADGIE 1, Sergii NICHENKO 1,2 *, Vitaliy SECHENYH *1,2 1 Wilson Ltd, Odessa, Ukraine tel.: +380 48 7343010, fax: +380 48 7342010, e-mail: nichenko@wilson-ukraine.com 2 Odessa State Academy of Refrigeration, Odessa, Ukraine tel.: +380 48 7232220, fax: +380 48 7231145 * Corresponding Author ABSTRACT Construction of "green buildings" become more and more demanded both for one-storey houses and for tower buildings. Application of "green buildings" technologies significantly reduces the cost of heating and air conditioning. Recent researches have shown that solar ejector refrigerating and air-conditioning systems (SERAS) can be successfully applied both for air-conditioning and for simultaneous generation of lower temperature cold CFD-modelling enabled to design flow part of ejector resulted in increase of entrainment ratio by 20-30%. In tower buildings hydrostatic pressure can "pump" liquid refrigerant to vapor-generator, instead of mechanical pumps, though minimal altitude for different refrigerants varies from 25 to 450 meters. The minimal altitude can be significantly reduced with application of steam injector, which uses the disposed hydrostatic pressure as a preliminary step or subcooler. This system allows to safely feed the liquid into the generator with a small additional expense of the working vapor, approximately 3-8% of the working vapor total consumption. Injector possesses all benefits of jet apparatus, works quietly and smoothly in stationary conditions. 1. INTRODUCTION Housing and communal services each year increase power consumption, first of all, due to living standards improvement, especially in developing countries. While the heating and hot water supply are remained more or less stable, and sometimes, in the context of global warming, heating costs are even reducing, energy consumption on air conditioning and cold supply for the past 5 years has almost doubled. This leads not only the necessity of additional energy production, but also increases emission of greenhouse gases into the atmosphere, that has contributed to global warming. Naturally, this model does not initially lead to catastrophic consequences. Though each year trends are worsening, as evidenced by the power overloads in several countries in the hottest days. This leads to disasters at national level. For example, in France on 11 August 2003, a threat of simultaneous stop of 58 nuclear reactors appeared because of the unprecedented heat, that led to system overload, because conditioners worked around the clock and throughout. The temperature of cooling water in the tanks reached the otherworldly magnitude of 50 C, resulting in consumers blackouts, and this has led to heat strokes and deaths of about 1000 people. Subsequently, a similar situation occurred in Chile, Brazil, Nigeria, Moscow and other regions. The way out at the same time is found in preventive disconnection a number of enterprises and other non-critical users from the power. 2. HEAT SEALING AND SCREENING OF COLD ROOMS These facts are pressing to reduce energy consumption on air conditioning by replacing traditional energy with solar energy and other renewable energy sources, as well as minimization of heat leakages in cooling rooms and selection of optimum conditioning scheme. As a result, compliance of complex arrangements can lead to significant savings. It is generally accepted that at the start of air-conditioning system design, first of all caloric estimation of cooling room should be done, and choose the best insulation. However, practice shows, in sunny and hot days the greatest heat leakage is caused not by the convective component of heat but by solar radiation through the walls and roof, and especially through the window openings. Therefore, following the principles of passive isolation gain the

3240, Page 2 particular importance, i.e. minimization of heat leakages and infiltration of outdoor air in both directions, interception of heat for useful application or a reflection in the surrounding space (Chel and Tiwari, 2009, Makakaa, Meyerb and McPherson, 2008). These arrangements can be set to optimize the insulation, sealing and shielding. Qualitative solution of this problem leads to serious energy savings and help reduce CO2 emissions. To ensure the best results solar collectors and gardening of outdoor surfaces are good, application of modern harmless sealants. Gardening is also serves to partial absorption of CO2 and water vapor from the waste removed from the rooms recirculating air, that is replaced by supplied outside air. This problem is well solved in the so-called passive houses. Application of the passive houses technologies allows a 90% reduction in the heat leakages in the building. In such systems, almost no heat leakage from the outside and thus air-conditioning system should remove the heat released only by the internal heat source, i.e. appliances and people. 3. AIR-CONDITIONING IN DIFFERENT CLIMATIC ZONES In hot climate countries consumption of artificial cold in the housing and communal sphere is growing fast and does not depend on the season. In torrid zone, where there are two seasons, dry and moist, necessity in air-conditioning is virtually the same over the year and during the day. In a continental climate conditions, where relative humidity is between 12-20%, night time temperatures can drop to 3-7 C, while the day time temperatures can reach 35-40 C. Therefore, the concepts of air-conditioning in these regions are fundamentally different. In desert areas (Sahara Desert, The Karakum Desert, Kalahari Desert, etc.) it is reasonable in the winter period to accumulate the natural cold of the environment during the night and consume it during the day. This leads to significant energy saving in comparison with all means of artificial cold obtaining. During the summer, application of evaporation cooling of air is sufficient at a given relative humidity and to a certain ambient temperature. In the rest period artificial mechanical cooling must be applied in combination with the evaporation cooling and the use of solar energy, i.e. solar thermotransformers, such as ejector refrigerating systems (ERS). In humid tropical climates (Amazonia, Southeast Asia, equatorial Africa), air-conditioning that consists of preliminary air drying by mean of solar energy, and further air cooling with the solar ejector refrigeration system (SERS) is the most acceptable in comparison with existing systems of air-conditioning, where the moisture removal is carried from the cooling surfaces. Fig. 1. Diagram of cold coverage at various solar collectors surface area/refrigerated area rates

3240, Page 3 The power capacities of air-conditioning systems in both these cases are significantly differ (see Fig. 1), but both systems require solar refrigeration system. It can be seen from the diagram (fig. 1) that depending on insolation in the region and day temperature cold coverage can be done with the application of solar ejector refrigerating system. Degree of cold coverage depends on relative solar collectors surface, i.e. ratio of solar collectors surface area to area of cooled room Ssc / S fa. It can be seen from the diagram that, for example, at environmental temperature of 30 C and insolation of 5 kwh/(m 2 day) it is possible to cover necessity in cold for 100% with the application of solar ejector refrigerating system under condition that solar collectors surface is 50% of cooled room surface. However, this diagram is constructed for buildings with an average heat leakages. Application of passive houses technologies will significantly increase the degree of cold coverage in the ceteris paribus, and allow to use solar ejector refrigerating system as the main air conditioning system in buildings of various types. 3.1 The scheme of two-stage solar air-conditioning for different climatic zones In temperate climate, when parameters of air outside insignificantly differ from the parameters of air inside aircooling is performed without moisture fall. When temperature of cooling surface is lower than dew point moisture fall is observed. This, from one side, decrease heat-exchange surface of air-cooler, but, from the other side, leads to electric energy overconsumption for production of lower temperature cold and overconsumption of cold for moisture condensation. Especially a lot of moisture falls in tropical climate conditions, when outdoor air parameters significantly differ from the indoor air parameters. In this case infiltration of hot and moist air from the outside is increased that demands intensive moist removal. Application of two-stage air-conditioning can be the way out of this situation, that lies in preliminary dehumidification of moist air before cooling at the expense of solar energy. Preliminary solar drying in the tropics makes it possible to reduce the necessity in produced cold for nearly twice at equal conditions, that along with the appropriate preparation of the building insulation minimizes operational costs for air-conditioning (Fig. 2) Fig.2 Processes of two-stage cooling of moist air Q 1 heat, removed in a cooler without preliminary cooling; Q 2 heat, removed in a cooler with preliminary cooling; Q m heat that is removed along with the moisture removal. Moistening of the air in a dry hot climate leads to similar results, and for certain combinations of temperature and relative humidity of outside air artificial refrigeration may not be necessary. (Ris3) 4. TRANSITION TO SOLAR COLD GENERATOR Comparative analysis of cold sources, which can operate at the expense of solar heat and produce bithermal cold (cold of two temperature levels), have shown that the most rational in this case is a two-stage or cascade twocomponent variant of ejector refrigeration system (ERS). Here, the priority factor is the lack of moving parts, size and reliability of jet devices at high values of COP. 4.1 Identifying the basic characteristics of the ejector

3240, Page 4 The main expenditure and energy characteristics of the ejector is the entrainment ratio, that is, in fact, the ratio of the available work of expansion of a working vapor to the required work of compression of ejected and the working vapor with all the energy losses that appear in the flow part of the ejector. Data obtained in a result of CFD simulations is used at the designing of ejector flow part (Fig. 4, 5). The calculation of the maximum entrainment ratio, that can be achieved on a working fluid was carried out in two stages. The first stage is the theoretical estimation of the entrainment ratio by the method described in (Sokolov and Zinger, 1989, He, Li and Wang, 2009). As a result of this calculation, preliminary assessment of the entrainment ratio and its main geometric characteristics, such as area ratio were obtained. Area ratio is the ratio of cross-section areas of ejectors major parts, such as the ratio of cross-sectional areas of nozzle exit to the nozzle throat, the ratio of cross-sectional areas of a mixing chamber to the nozzle throat. Fig.3 Processes of two-stage cooling of dry air Q m - heat, removed in the process of evaporative cooling; Q - heat, removed from dry air in the cooling process; m - the amount of water supplied in the process of evaporative cooling. However, the proposed method of calculation is imperfect, and results may significantly differ from the true values of the entrainment ratios (He, Li and Wang, 2009). Therefore, the second stage of entrainment ratio estimation is the CFD simulation of processes in an ejector for each of the selected working fluids. Theoretical results obtained in the first stage are used as a first approximation to the next stage. Such approach significantly reduces the time required to perform CFD simulations and significantly improve the accuracy of the obtained data. Illustration of CFD models of the ejector flow part for air conditioning, working on isobutane, are shown on Figures 4 and 5. The results of this calculation for all of the selected fluids are presented in Table 1. In terms of energy efficiency COP is a more important characteristic than entrainment ratio. Figure 4. Velocity profile in flow part of ejector of ERS first stage ( T ev =12 C, T con =35 C, T gen =85 C) working with R600a refrigerant, obtained at CFD modelling.

3240, Page 5 COP of ejector heat-utilizing air-conditioner is determined by the equation: COP = ω q / q (1) ej ev gen where ω - entrainment ratio, kg/kg; q ev - specific cooling capacity, kj/kg; generator, kj/kg. q gen - specific heat load on the Figure 5. Velocity profile in flow part of ejector of ERS second stage ( T ev =-15 C, T con =35 C, T gen =85 C) working with R600a refrigerant, obtained at CFD modelling. Table 1: Results of CFD modelling of ejectors flow part of two-stage solar ejector refrigerating system (ERS) ( T ev =12 C, T con =35 C, T gen =85 C) Working fluid qev / q gen ω COP R290/RE170 0.937 0.64 0.60 R600/RE170 0.743 0.66 0.49 R600 0.67 0.51 0.34 RE170 0.767 0.54 0.41 R13T1 0.765 0.44 0.34 R601b 0.615 0.5 0.31 RC318 0.545 0.42 0.23 To test the work of an ejector refrigeration system and verify the simulation results experimental setup was designed and created. The experimental setup is shown in Figure 6.

3240, Page 6 Fig. 6. Solar Ejector Refrigeration and Air-conditioning System (SERAS). In this installation measurement of entrainment ratio by two independent methods is provided: thermal balance of apparatus and volumetric flow meter. Deviations of pressure and flow rate measurements are between 1.5-2.5%, and of temperature measurements is about 0.2 C, which is acceptable for engineering experiments. At this stage the experimental verification of obtained CFD simulation result is performed. 4.2 Pumpless ejector refrigeration system (PERS) Because the report focuses on tower buildings, it is interesting to solve problem of liquid refrigerant supply to steam generator. All heat-utilizing refrigerating systems have a pump as indispensable element for the implementation of the direct cycle, which uses mechanical work or heat. For large altitudes, when the hydrostatic pressure exceeds the difference of pressures in the generator and condenser, spontaneous flow of liquid from the condenser to the generator is possible, which further simplifies the installation scheme. (Fig.7) We refused from application of mechanical pumps for liquid refrigerant supplying from the condenser to the steam generator, pumpless systems of batch operation, and, in some cases from thermopumps. For example, in tower buildings liquid refrigerant can be supplied to steam generator at the expense of hydrostatic pressure, at that a minimum altitude for different substances varies between 25-450 m. Such difference of altitude is conditioned by the difference of pressures between generator, P gen, and condenser, P con, and density of liquid refrigerant, ρ liq Pgen Pcon Δ H req = (2) ρliq g A number of fluids, that works well in cooling cycles, but requires high altitudes, can be successfully applied at much lower altitudes, if steam injector will be included into the scheme, which uses the disposed hydrostatic pressure as a preliminary step or subcooler. This system allows to safely feed the liquid into the generator with a small additional expense of the working vapor, approximately 3-8% of the working vapor total consumption. Injector possesses all benefits of jet apparatus, works quietly and smoothly in stationary conditions. Individual levels of generator and condenser placement should be adjusted, that limits application of some refrigerants in PERS systems because high vertical level difference is required for their circulation. Refrigerants cyclopropane (S3H6) and Methylacetylene (CH3CCH) may be used only for buildings with height of 300 meters (see Table. 2). Refrigerant R290 can be used in buildings of 475 meters height. The application of injectors allows to increase fluid pressure in the inlet line of steam generator (output line of condenser), that reduces the necessary level difference by 25-65% (see Table. 2).

3240, Page 7 Fluids Fig. 7. Principal chart of PERS. Table 2: Results of injector calculation with application of multi-stage scheme tot Δ Hreq 1 2 3 4 5 6 7 Δ H 100 % tot Cyclopropane 311.3 24.48 27.85 29.90 30.76 113.0 36.3 RE170 266.8 20.00 25.89 31.26 33.50 30.61 22.32 163.6 61.3 R600a 193.9 20.08 27.33 32.02 31.08 110.5 57.0 R290 475.1 26.81 33.91 41.15 48.97 51.59 49.08 38.44 289.9 61.1 Propyne 294.4 18.40 22.32 26.19 28.88 29.33 26.96 21.46 173.5 58.9 R124 95.70 9.85 13.40 16.12 14.99 54.36 56.8 R134a 178.1 12.81 16.14 20.82 23.49 23.02 17.8 114.1 64.1 R152a 210.8 15.08 19.00 23.35 26.15 25.55 20.85 130.0 61.7 R227ea 110.6 9.20 12.65 16.68 19.39 16.71 74.63 67.5 R13T1 68.98 6.63 6.80 4.18 17.61 25.5 The most promising refrigerant of considered for application in PERS type systems is refrigerant R13T1. For the circulation of the refrigerant along the contour of PERS a small vertical level difference is required (from 69 m) and req

3240, Page 8 with the use of injectors this level difference may be reduced by more 17.6 m. Thus, the refrigerant R13T1 can be successfully applied in buildings of 15 storeys and above. 5. ECONOMIC ASPECTS Calculation of economic indexes was performed for PERS in comparison with traditional system of heating, individual air-conditioning units and household refrigerators. Capital expenditures for traditional system are n K1 = Ci (3). i= 1 It consists of costs of air-conditioners, household refrigerators and heating system. Capital expenditures for similar PERS system depends on cost of collectors per square meter of surface and defined as K2 = SscCsc sm + Ceq (4) where S sc surface area of collectors required for PERS, m 2 ; C sc sm a cost of square meter of collector, $/m 2 ; C eq a cost of other PERS equipment. It is assumed that average efficiency of evacuated tube collectors varies from 0.5 to 0.8. Average cost of collector s square meter varies from $400 to $1000 (Purohit, Kumar and Kandpal, 2006). Electricity and heat prices are considered as sole variable costs. For a standard system expenditures on electricity are N1 = W1 24 365 C pr (5) where W 1 consumed power, kwh; C PR a power rate. Power rate varies from $0.04 to $0.29 per kw h [11], [12]. Heating and hot water costs for traditional system are calculated as H1 = Vhw Chw I (6) where V hw hot water consumption per one person, m 3 ; I a number of persons using the system; C hw a price of hot water. Cold water costs for PERS are defined by: H2 = Vcw Ccw I (7) where V cold water consumption, m 3 ; I a number of persons using the system; cw Amortization costs A are inversely proportional to operation life time. For traditional system reduced expenditures are: E = K Am+ C C cw cold water cost. 1 1 1 (8) where C1 = N1+ H1 (8) For PERS reduced expenditures are: E2 = K2 A+ C2 (8) where C2 = H2 (9) Annual income as a result of PERS installation is: A1 = E1 E2 (10) Additional capital expenditures are: ACE = K2 K1 (11) Payback of investments for PERS is defined by: K K PyP = 2 1 (11) A 1

3240, Page 9 Payback period vs. power rate of PERS application in different regions are shown on Figure 5. Fig. 8. Diagram of payback period vs. power rate. 6. CONCLUSIONS As the Figure 5 shows, at different values of power rate in various regions of the world, PERS payback period ranges from 3 to 10 years. In countries of hydrocarbons-in-place and cheap power rates, the payback period for PERS will be over 10 years. In Europe, where average power rate is about $0.18, PERS payback period is about 3 years. United Nations Climate Change Conference (COP15) in Copenhagen held in December, 2009 has concluded that energy prices upward trends and advanced control for CO 2 emissions, shall lead to expansion of renewable sources utilization in the near future. This message primarily concerned territories with maximal access to renewable energy sources. Therefore, in the next 10 years, necessity in such facilities as PERS, will increase in the Middle East countries as well as in the other parts of the world. NOMENCLATURE S surface (m 2 ) Subscripts Q total heat load (kw) sc solar collector q specific heat load (kw) fa cooled room T temperature (K) m moisture mass ω entrainment ratio (kg/kg) ev evaporator COP coefficient of performance (-) con condenser P pressure (kpa) gen generator ρ density (kg/m 3 ) req required g acceleration due to gravity (m/s 2 ) tot total Δ H level difference (m) sm square meter K capital expenditures ($) eq equipment C cost ($) pr power rate W power (kwh) hw hot water N expenditures ($) cw cold water V water consumption (m 3 ) E reduced expenditures ($) Am amortization cost ($) A annual income ($) ACE additional capital expenditures ($)

3240, Page 10 Py payback of investments () REFERENCES Chel, A., Tiwari, G.N., 2009, Thermal performance and embodied energy analysis of a passive house Case study of vault roof mud-house in India, Applied Energy, vol. 86, no. 10: p. 1956-1969. Golden Makakaa,,, Edson L. Meyerb and Michael McPherson, 2008, Thermal behaviour and ventilation efficiency of a low-cost passive solar energy efficient house, Renewable Energy, vol. 33, no. 9: p. 1959-1973. He, S., Li, Y., Wang, R.Z., 2009, Progress of mathematical modeling on ejectors, Renewable and Sustainable Energy Reviews, vol. 13, no. 8: p. 1760-1780. Solokov, E. R., Zinger, N. M., 1989, Jet devices, Energiya, Moscow, pp. 352 (in Russian) Purohit, P., Kumar, A., Kandpal, T. C., 2006, Solar drying vs. open sun drying: A framework for financial evaluation, Solar Energy vol. 80, no, 12: p. 1568-1579.