Rainscreen Cladding Compliance Guide When specifying Celotex RS5000 in buildings above 18 metres

Similar documents
PRODUCT SUSPENDED. Rainscreen Cladding Compliance Guide When specifying Celotex RS5000 in buildings above 18 metres

BRE Global Classification Report

BRE Global Classification Report

Fire performance of curtain walls and rainscreens

BRE Global Classification Report

BS :2005 test on a Kingspan Benchmark External Wall Insulation System

6/16/2016. A FORENSIC EXAMINATION OF TALL BUILDING FACADE FIRES l Building Envelope Fires in Dubai Skyscrapers. Martin Edwards. The Address (Atkins)

BRE Global Test Report

BRE Global Assessment Report

Light steel frame walls

BRE Global Client Report

Insulation for Ventilated Rainscreen Cladding Systems

This was followed by a Part 2 experimental scoping study focusing on the issue of external fire spread, to be covered in next month s issue.

BRE Global Classification Report

8414-1: A1:2017

Certificate No: EWWS165

VENTILATED FIRE BARRIERS

VENTILATED FIRE BARRIERS

RH & RV CAVITY BARRIERS

BRE Global Test Report

Carbon Reduction. The next phase. We know insulation inside and out

BRE Global Test Report

BRE Global Test Report

BS8414 Part 1: 2002 Test on a Phenolic Insulated Rainscreen system. Prepared for: Kingspan Insulation Ltd Pembridge Leominster Herefordshire HR6 9LA

Annex C Cavity Closures

CELOTEX INSULATION CELOTEX CW4000 AND CG4000 PIR INSULATION FOR CAVITY WALLS

K15 Rainscreen Board. Insulation INSULATION FOR USE BEHIND RAINSCREEN CLADDING SYSTEMS

PRODUCT SUSPENDED. Concrete Soffit Liner Specification Guide

Loft Conversions - Attic Walls

Garage Conversion - Between and Under Joist Applications

CELOTEX INSULATION CELOTEX RANGE OF PIR INSULATION BOARDS FOR TIMBER-FRAME DWELLINGS

PARTITIONS & EXTERNAL WALLS 5

The experimental programme for this stage of the project has been undertaken in three phases:

Classification of fire performance in accordance with BR 135: Annex B: Prepared for: Alsecco (U.K) Ltd Whitebridge Way Stone Staffs.

Between and Under Rafter Applications

High Rise Buildings with a Floor Level Above 18m. Meeting the guidance within the Requirements of Approved Document B Volume 2

BRE Global Ltd Watford, Herts WD25 9XX. d+b facades (UK) Ltd. The Packway, Larkhill, Salisbury, SP4 8PY. Customer Services

Title: WF Report No: Prepared for: International Petroleum Products Ltd Bradwell Hall Bradwell-On-Sea Essex CMO 7HX. Date: 24 th August 2015

SOUTH AFRICAN NATIONAL STANDARD

Rainscreen Ventilated Fire Barrier

KINGSPAN INSULATION KOOLTHERM K15 RAINSCREEN INSULATION BOARD

Between and Under Rafter Applications

Engineering Analysis of NFPA 285 Tested Assemblies

Agrément Certificate 16/5343 website: Product Sheet 2

Agrément Certificate 16/5357 website: Product Sheet 2

SP FIRESTOP SYSTEMS The purpose-made solution for cavity fire stopping

combustibility behaviour of insulation products

Cavity Barriers: Final Factual Report of the Experimental Programme

ISO INTERNATIONAL STANDARD. Fire-resistance tests Elements of building construction Part 1: General requirements

XTRATHERM XTROLINER (XO) XTRATHERM XTROLINER RAINSCREEN BOARD (XO/RS)

K15 Cladding Board. Insulation INSULATION FOR USE BEHIND CLADDING SYSTEMS. Low Energy Low Carbon Buildings. Third Issue July 2017

SP FIRESTOP VRB Open-state cavity fire barrier for use within building facades

Agrément Certificate 17/5405 website: Product Sheet 1

Solutions. Main Headings Third Issue July Insulation DON T COMPROMISE ON THERMAL PERFORMANCE, FIRE PERFORMANCE AND ENVIRONMENTAL RESPONSIBILITY

Fire Rated Cladding Seals

SEPTEMBER construction type cavity barriers. SP Firestop Systems. The purpose-made solution for cavity fire stopping

Copyright 2016 UL LLC.

April Section Cladded Walls

ARCHITECTURAL WALL PANELS APPLIED OVER A SHEATHED STUDWALL BY MEANS OF A FIELD ASSEMBLED TEN66 SUB-FRAME SYSTEM

SP FIRESTOP OSCB 60 & 120 Open-state cavity barrier only for use with RAINSCREEN DUO SLAB

CELOTEX INSULATION CELOTEX PIR PLASTERBOARD THERMAL LAMINATES

EUROPEAN ORGANISATION FOR TECHNICAL APPROVALS

Fire damper frequently asked questions for ASFP

Fire Engineering, the BCA (NCC) & Bushfire Calculator. Keith Nicholls - Manager Product Testing and Assessments (Australia) Exova Group Limited

CELOTEX INSULATION CELOTEX CF5000 PIR INSULATION FOR FULL FILL CAVITY WALLS

Contents. Timber framing to be installed in accordance with AS:1684 Metal framing to be installed in accordance with BCA Volume: 2

Agrément Certificate 16/5352 website: Product Sheet 2

Fire Testing Laboratory

Fire Test Report. Test Number 1243 Dated 22 September Prepared for:

REQUESTED BY : Atlas Roofing and Flooring PO Box Queenswood CONTRACT No : FTC12/088. AUTHOR(S) : K. van Dyk. DATE : 13 September 2012

Deer Ridge Consulting, Inc.

Superior Performance Phenolic Insulation. SR/RS Insulation for Ventilated Rainscreen Cladding. Walls 10/4803

NATIONAL ANNEX TO STANDARD. SFS-EN EUROCODE 1: ACTIONS ON STRUCTURES Part 1-7: General actions Accidental actions

RAINSCREEN DUO SLAB. Non-combustible thermal insulation

Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade)

Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade)

Multi-storey timber construction in the UK IRCC workshop, Vienna 7 June 2013 Dr Julie Bregulla Dipl-Ing, PhD, CEng, FICE

A handbook of thermal bridging details incorporating Porotherm blocks

PASSIVE FIRE PROTECTION SYSTEMS Application & Technical Manual: Cavity & Smoke Barriers, Parapet & Spandrel Walls

WOOD USE IN NONCOMBUSTIBLE BUILDINGS

Agrément Certificate 16/5343 website: Product Sheet 3

Executive summary. Fire Hazards of Exterior Wall Assemblies Containing Combustible Components v

Loss Prevention Standard

Title: The Fire Resistance Performance of EI60, Side and Centre-Opening Lift Landing Doorsets. WF Assessment Report No: /A.

european fire standards and national legislation

Fire detailing. for non-combustible masonry structures. DRAFT 30th March Cover image, branding and accreditation to be developed

KINGSPAN INSULATION KINGSPAN TW55 THERMAWALL FRAMING BOARD INSULATION

Fire safety issues with balconies

Multi-layer Insulation Blanket for Walls

CALL TO TALK TO THE SAS TEAM

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:

An introduction to Part L U-values

Part E robustdetails. robustdetails. January 2018 Update Pack

FIRE STOP & SMOKE SEAL

NVELOPE RAINSCREEN SYSTEMS NVELOPE RAINSCREEN CLADDING SUPPORT SYSTEMS

FIRE MITIGATION IN FACADE DESIGN & MATERIAL CHOICE

Title: ETICS Fire Performance Test. Authors: Ivana Banjad Pečur 1) Dubravka Bjegović 1) Lars Boström 2) Bojan Milovanović 1) Milan Hajduković 3)

NRC Research Update on Mid-Rise Wood Construction. Joseph Su Principal Research Officer, Fire Safety

Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD.

WHITE PAPER. External Wall Insulation (EWI) systems for high-rise steel framed buildings

Transcription:

01473 820850 celotex.co.uk Rainscreen Cladding Compliance Guide When specifying Celotex RS5000 in buildings above 18 metres 1 Rainscreen Cladding Compliance Guide

Compliance Guide This document provides guidance on complying with Approved Document B2 (AD B2) for external wall cladding systems fixed to steel frame or masonry constructions. It provides a step by step guide to an alternative route to compliance for AD B2 through meeting the performance criteria set out in BR 135 through testing to BS 8414-1:2002 or BS 8414-2:2005. Typical construction method Approved Document B2 Buildings with a storey height greater than 18 metres have additional requirements under the national Building Regulations. Section 12.5 (External Wall Construction) of Approved Document B2 states the following routes to compliance: External walls should meet the guidance given in paragraphs 12.6 or 12.9 or meet the performance criteria given in the BRE report Fire performance of external thermal insulation for walls of multi storey buildings (BR 135) for cladding systems using full scale data from BS 8414-1:2002 or BS 8414-2:2005 2 Rainscreen Cladding Compliance Guide

BR 135 The first edition of BR 135 published in 1988, was developed in response to the increasing use of thermal insulation in external wall constructions of multi-storey buildings. Its primary purpose is to analyse the key stages associated with fire spread on the outside of a building envelope. These are classified as: Initiation of the fire Fire breakout Interaction with the external envelope Fire re-entry Fire service intervention Performance Criteria Annex B of BR 135 establishes the performance criteria and classification for testing to BS 8414-2: 2005. Performance criteria and classification method: The performance criteria and classification method are based on the latest edition of the BS 8414-2:2005 test method. In order for a classification to be undertaken the system must have been tested to the full test-duration requirements of BS 8414-2 without any early termination of the full fire-load exposure peroid. As explained in Annex A, the primary concerns when setting the performance criteria for these systems are fire spread away from the initial fire source, and the rate of fire spread. If fire spread away from the initial fire source occurs, the rate of progress of fire spread or tendency for collapse should not unduly hinder intervention by the emergency services. The performance of the system under investigation is evaluated against three criteria: External fire spread Internal fire spread Mechanical performance The classification applies only to the system as tested and detailed in the classification report. The classification report can only cover the details of the system as tested. It cannot state what is not covered. When specifying or checking a system it is important to check that the classification documents cover the end-use application. Copyright IHS, reproduced by permission Rapid Fire Spread Cladding system contributes to flame spread resulting in risk of multiple simultaneous secondary fires Restricted Fire Spread Cladding system does not contribute to flame spread. Risk of secondary fires limited If the external cladding contributes to the flame spread there is a risk of secondary fire spread to all levels If a secondary fire is allowed to develop then process is repeated Flames break out and attack adjacant windows Initial fire is allowed to develop and flashes over Flames break out and attack adjacant windows External fire incident Secondary external fires arising from falling burning debris Figure 3 BR 135 Copyright IHS, reproduced by permission 3 Rainscreen Cladding Compliance Guide

Thermocouple measurements are recorded at different levels on the tested system to establish the performance against the set criteria. Failure to meet the performance criteria set out in BR 135 is deemed to occur if the system: Records temperatures exceeding 600 C for a period of at least 30 seconds within 15 minutes of the start time at level two external thermocouples Records temperatures exceeding 600 C for a period of at least 30 seconds within 15 minutes of the start time at level two internal thermocouples. Mechanical performance of the system is observed and details of ongoing system combustion following extinguishing of the ignition source, system collapse etc are included in the classification report. Celotex RS5000 Celotex RS5000 is a premium performance solution and is the first PIR board to successfully test to BS 8414-2:2005 for rainscreen cladding systems meeting the performance criteria set out in BR 135. The system tested was as follows: 12mm Fibre Cement Panels Supporting aluminium brackets and vertical rails 100mm Celotex RS5000 12mm Non-combustible sheathing board 100mm SFS System 2 x 12.5mm plasterboard Fire stopping was provided by ventilated horizontal fire breaks positioned at each floor slab edge and above the hearth opening. Vertical non-ventilated fire breaks were provided at the edges of both the main face and the return wing and around the hearth opening. The fire performance and classification report issued only relates to the components detailed and constructed in figure 4. Any changes to the components listed and construction method set out in figure 4 will need to be considered by the building designer. Ventilated fire barriers comprised of stonewool insulation with Class O aluminium foil facings and a continuous bonded intumescent strip. Non-ventilated fire barriers comprised of stonewool insulation with Class O aluminium foil facings specifically intended to fully fill the void. BR140mm Helping Hand bracket 12mm Marley Eternit Natura panel 12mm Magnesium Oxide board 100mm LSF system Aluminium 60x40x2mm Continuous rail 100mm Celotex RS5000 Insulation Figure 4 Bibliography Approved Document B Fire safety: volume 2: buildings other than dwellinghouses BS 8414-2:2005 - Fire performance of external cladding systems: test method for non-loadbearing external cladding systems fixed to & supported by a structural steel frame BR 135 Third Edition 2013 - Fire performance of external thermal insulation for walls of multi-storey buildings 4 Rainscreen Cladding Compliance Guide

Find out more at celotex.co.uk Follow us on @celotex Team up with us on Like us on Celotex, Lady Lane Industrial Estate, Hadleigh, Ipswich, Suffolk, IP7 6BA T: 01473 820850 E: technical@celotex.co.uk Date of publication: February 2015 5 Rainscreen Cladding Compliance Guide