1 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 492 AND ASTM E 2179 Rendered to REGUPOL AMERICA Series/Model: Regupol 6 mm SonusWave Impact Sound Underlayment Specimen Type: Concrete Slab mm Overall Size: 3023 mm by 3632 mm IIC 54 ΔIIC 25 Test Specimen Identification: Floor Topping: 12.7 mm Mannington Lexington Hickory Engineered Wood Floor Underlayment: 6 mm Regupol SonusWave Impact Sound Underlayment Floor Slab: 152 mm Concrete Slab Reference should be made to Intertek-ATI Report E for complete test specimen description. This page alone is not a complete report. 130 Derry Courtaa York, PA 17406aa p f

2 Page 1 of 4 Acoustical Performance Test Report REGUPOL AMERICA 33 Keystone Drive Lebanon, Pennsylvania Report E Test Date 06/18/15 Report Date 07/06/15 Project Scope Architectural Testing, Inc., a subsidiary of Intertek (Intertek-ATI), was contracted to conduct impact sound transmission and delta impact sound transmission tests. The complete test data is included as attachments to this report. The client provided the test specimen. The specimen was constructed on the date of testing. Test Methods The acoustical tests were conducted in accordance with the following standards. The equipment listed in the attachments meets the requirements of the following standards. ASTM E , Standard Test Method for Laboratory Measurement of Impact Sound Transmission Through Floor-Ceiling Assemblies Using the Tapping Machine ASTM E (2009), Standard Test Method for Laboratory Measurement of the Effectiveness of Floor Coverings in Reducing Impact Sound Transmission Through Concrete ASTM E (2012), Classification for Determination of Impact Insulation Class (IIC) ASTM E (2012) Standard Test Method for Determination of Decay Rates for Use in Sound Insulation Test Methods Test Procedure All testing was conducted in the VT test chambers at Intertek-ATI located in York, Pennsylvania. The microphones were calibrated before conducting the tests. The impact sound transmission test was conducted in accordance with the ASTM E 492 test method. Two background noise sound pressure level, two sound pressure level measurements with the tapping machine operating at each position specified by ASTM E 492, and five sound absorption measurements were conducted at each of five microphone positions. 130 Derry Courtaa York, PA 17406aa p f

3 Page 2 of 4 Test Procedure (Continued) The delta impact insulation test was conducted in accordance with ASTM E 2179 test method. In addition to the impact sound transmission test, two sound pressure level measurements with the tapping machine operating at each position specified by ASTM E 492 with only the concrete slab installed. The air temperature and relative humidity conditions were monitored and recorded during all measurements. Test Conditions Source Room Receive Room Average Temperature 22.1 C Average Temperature 22.6 C Average Relative Humidity 76% Average Relative Humidity 70% Test Calculations The IIC (Impact Insulation Class) and ΔIIC (Delta Impact Insulation Class) ratings were calculated in accordance with ASTM E 989 and ASTM E 2179, respectively. Test Specimen Materials and Installation Details Material Dimensions (mm) Thickness (mm) Manufacturer and Series Quantity Average Weight Engineered Wood by 127 Note: Loose laid Mannington Lexington Hickory m² 6.59 kg/m² SonusWave Impact Sound Underlayment Concrete Slab by Regupol m² Note: Loose laid by N/A m² Note: The concrete slab was installed in a test frame flush to the source room kg/m² kg/m² Comments The total weight of the floor/ceiling assembly was kg. Intertek-ATI will store samples of the test specimen for four years. Photographs of the test specimen are included in the attachments. A drawing of the test specimen is included in the attachments.

4 Page 3 of 4 Intertek-ATI will service this report for the entire test record retention period. Test records, such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation, will be retained by Intertek-ATI for the entire test record retention period. The test record retention period ends four years after the test date. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen tested. This report is intended to help in the client s quality assurance program, but it does not represent a continuous or exhaustive evaluation of the specimen tested or of other products or materials that were not evaluated. The statements and data provided herein do not constitute approval, disapproval, certification, or acceptance of performance or materials. This report may not be reproduced, except in full, without the written approval of Intertek-ATI. FOR INTERTEK-ATI: Daniel B. Mohler Technician II - Acoustical Testing Bradlay D. Hunt Project Manager - Acoustical Testing Attachments (7 Pages): This report is complete only when all attachments are included. * Stated by Client/Manufacturer N/A - Non Applicable

5 Page 4 of 4 Revision Log Revision Date Page(s) Description R0 07/06/15 N/A Original Report Issue This report produced from controlled document template ATI 00629(d), Revised 02/09/15.

6 Attachments Instrumentation Instrument Manufacturer Model ATI Number Data Acquisition Unit National Instruments PXI /14 Microphone Calibrator Norsonic 1251 Y /14 Receive Room Microphone PCB Piezotronics 378B /15 Date of Calibration * Receive Room Microphone PCB Piezotronics 378B /15 Receive Room Microphone PCB Piezotronics 378B /15 Receive Room Microphone PCB Piezotronics 378B /15 Receive Room Microphone PCB Piezotronics 378B /15 Receive Room Environmental Indicator Comet T /14 Source Room Microphone PCB Piezotronics 378B /15 Source Room Microphone Source Room Microphone Source Room Microphone PCB Piezotronics 378B /15 PCB Piezotronics 378B /15 PCB Piezotronics 378B /15 Source Room Microphone PCB Piezotronics 378B /15 Source Room Environmental Indicator * The calibration frequency for this equipment is every two years per the manufacturer's recommendation. Test Chambers VT Receive Room Volume m³ Comet T /14 Tapping Machine Look Line s.r.l. EM50 (TM50) VT Source Room Volume 190 m³ /14 Page 1 of 7

7 IMPACT SOUND TRANSMISSION ASTM E 492 Test Date 06/18/15 Data File No. E Client Regupol America Description 12.7 mm Mannington Lexington Hickory Engineered Wood, 6 mm Regupol SonusWave Impact Sound Underlayment, 152 mm Concrete Slab Specimen Area m² Technician Daniel B. Mohler Freq Background SPL Absorption Normalized Impact SPL 95% Number Confidence (Hz) (db) (m²) (db) Limit Deficiencies of IIC Rating Deficiencies (Impact Insulation Class) (Sum of Deficiencies) Note: Receive Room levels less than 5 db above the Background levels are highlighted in yellow. ATI Revised 02/09/15 Page 2 of 7

8 IMPACT SOUND TRANSMISSION ASTM E 492 Test Date 06/18/15 Data File No. E Client Regupol America Description 12.7 mm Mannington Lexington Hickory Engineered Wood, 6 mm Regupol SonusWave Impact Sound Underlayment, 152 mm Concrete Slab Specimen Area m² Technician Daniel B. Mohler 100 Impact Sound Transmission Sound Pressure Level (db) Impact Insulation Class (IIC) Normalized Impact SPL Contour Curve Frequency (Hz) ATI Revised 02/09/15 Page 3 of 7

9 DELTA IMPACT INSULATION ASTM E 2179 Test Date 06/18/15 Data File No. E Client Regupol America Description 12.7 mm Mannington Lexington Hickory Engineered Wood, 6 mm Regupol SonusWave Impact Sound Underlayment, 152 mm Concrete Slab Specimen Area m² Technician Daniel B. Mohler Freq (Hz) Bkgrd SPL (db) Absorption (Square Meters) Normalized Impact SPL BARE (db) % Conf Limit 0.7 Normalized Impact SPL SPEC (db) % Conf Array L ref,c Limit No. of Deficiencies Resulting ΔIIC Rating Deficiencies (Delta Impact Insulation Class) (Sum of Deficiencies) Note: Receive Room levels less than 5 db above the Background levels are highlighted in yellow. ATI Revised 02/09/15 Page 4 of 7

10 DELTA IMPACT INSULATION ASTM E 2179 Test Date 06/18/15 Data File No. E Client Regupol America Description 12.7 mm Mannington Lexington Hickory Engineered Wood, 6 mm Regupol SonusWave Impact Sound Underlayment, 152 mm Concrete Slab Specimen Area m² Technician Daniel B. Mohler 100 Delta Impact Insulation Sound Pressure Level (db) Impact Insulation Class (IIC) Resulting Array Contour Curve Frequency (Hz) ATI Revised 02/09/15 Page 5 of 7

11 Photographs Source Room View of Test Specimen Installation Receive Room View of Test Specimen Installation Page 6 of 7

12 Drawing 1-Floor Topping 2-Underlayment 3-Concrete Slab Page 7 of 7

D R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA

D R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to REGUPOL AMERICA Regupol Sonus HS300 3 mm Underlayment Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632

More information

D R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA

D R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to REGUPOL AMERICA Series/Model: Regupol Sonus LV200 2mm Underlayment Specimen Type: Floor/Ceiling Assembly Overall Size:

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to REGUPOL AMERICA Series/Model: 3 mm Regupol Sonus Rubber Underlayment Specimen Type: Floor/Ceiling Assembly Overall Size:

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to REGUPOL AMERICA Series/Model: 5 mm Regupol Sonus Rubber Underlayment Specimen Type: Floor/Ceiling Assembly Overall Size:

More information

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to PROFLEX PRODUCTS, INC.

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to PROFLEX PRODUCTS, INC. ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to PROFLEX PRODUCTS, INC. Series/Model: 4 mm Luxury Vinyl Plank over LV200 Specimen Type: Concrete Slab - 152 mm Overall Size:

More information

G R1 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to PROTECTO WRAP COMPANY

G R1 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to PROTECTO WRAP COMPANY ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to PROTECTO WRAP COMPANY Series/Model: Protecto Wrap Whispermat LVT Specimen Type: Concrete Slab - 152 mm Overall Size: 3023

More information

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to URBAN SURFACES

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to URBAN SURFACES ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to URBAN SURFACES Series/Model: Urban Surfaces Soundtec Specimen Type: Concrete Slab - 152 mm Overall Size: 3048 mm by 3658

More information

F R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP COMPANY

F R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP COMPANY ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to PROTECTO WRAP COMPANY Series/Model: Whisper Mat Underlayment with Everbond Adhesive Specimen Type: Concrete Slab - 152 mm Overall

More information

F R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to

F R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 9, ASTM E 492, ASTM E 2179 Rendered to EXPANKO, DIVISION OF THE STONCOR GROUP INCORPORATED Series/Model: Expanko CorkCore LVT Specimen Type: 152 mm Concrete Slab

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to REGUPOL AMERICA

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to REGUPOL AMERICA Series/Model: Regupol 7210C Screed Isolation Specimen Type: 203 mm Concrete Slab with Drop Ceiling Overall Size:

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to REGUPOL AMERICA

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to REGUPOL AMERICA Series/Model: Regupol 8 mm SonusWave Impact Sound Underlayment Specimen Type: Open Web Truss - 406 mm Overall Size:

More information

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to VENEKLASEN ASSOCIATES

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to VENEKLASEN ASSOCIATES ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to VENEKLASEN ASSOCIATES Series/Model: Urban Luxury Vinyl 9553 Gold Line Vinyl Plank Flooring Specimen Type: 152 mm (6") Concrete Slab

More information

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to VENEKLASEN ASSOCIATES

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to VENEKLASEN ASSOCIATES ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to VENEKLASEN ASSOCIATES Series/Model: Urban Luxury Vinyl 9230 Silver Line Vinyl Plank Flooring Specimen Type: 152 mm (6") Concrete

More information

RSIC ACOUSTIC ASSEMBLY

RSIC ACOUSTIC ASSEMBLY RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO WOOD I JOIST F4543.05 STC 62 IIC 61 CONSTRUCTION Mannington Hometown Lexington Hickory Hardwood Hacker Industries, Inc. Firm-Fill Gypsum Concrete

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to SENECA RADIANT TECHNOLOGIES

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to SENECA RADIANT TECHNOLOGIES ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to SENECA RADIANT TECHNOLOGIES Series/Model: Floor/Ceiling Assembly Specimen Type: Dimensional Lumber - 2x10 Overall Size: 3023 mm by

More information

D R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP COMPANY. Series/Model: Whisper Mat CS

D R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP COMPANY. Series/Model: Whisper Mat CS ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to PROTECTO WRAP COMPANY Series/Model: Whisper Mat CS Specimen Type: Sound Control & Crack Suppression Membrane Overall Size: 3023 mm

More information

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to US ARCHITECTURAL PRODUCTS, INC.

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to US ARCHITECTURAL PRODUCTS, INC. ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to US ARCHITECTURAL PRODUCTS, INC. Series/Model: Plycem CemDeck - No Floor Topping Specimen Type: 8J16 Steel Joist Assembly Overall

More information

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to US ARCHITECTURAL PRODUCTS, INC.

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to US ARCHITECTURAL PRODUCTS, INC. ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to US ARCHITECTURAL PRODUCTS, INC. Series/Model: Plycem CemDeck with Double Layer Ceiling - No Floor Topping Specimen Type: 8J16 Steel

More information

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9, ASTM E492, AND ASTM E2179 TESTING ON 4X SOUNDPANEL WITH AKUSTIPRO 8 RUBBER TILE SPECIMEN TYPE Concrete Slab - 152 mm REPORT NUMBER

More information

FLOOR CEILING ASSEMBLY

FLOOR CEILING ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO I JOIST FCW-ATI-E6968.08 CONSTRUCTION Sheet Vinyl Ecore Forest FX Plywood 5/8" Waterproof Membrane (15lb Felt) Plywood 5/8" I Joist 12" Deep @ 24" OC Insulation Nominal

More information

RSIC ACOUSTIC ASSEMBLY

RSIC ACOUSTIC ASSEMBLY RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY World Leader in Noise Control Solutions DIRECT FIX TO WOOD OPEN WEB TRUSS F4545.07 STC 61 IIC 54 CONSTRUCTION Hacker Industries, Inc. Firm-Fill Gypsum Concrete

More information

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Base 10

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Base 10 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to Series/Model: Base 10 Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results Data File Result

More information

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to AMORIM CORK COMPOSITES

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to AMORIM CORK COMPOSITES ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to AMORIM CORK COMPOSITES Series/Model: AcoustiCORK ECOx2 Sound Reduction Underlayment for LVT Plank Flooring Specimen Type: 152 mm

More information

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to URBAN SURFACES. Series/Model: Urban Surfaces Soundtec

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to URBAN SURFACES. Series/Model: Urban Surfaces Soundtec ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to URBAN SURFACES Series/Model: Urban Surfaces Soundtec Specimen Type: 152 mm Concrete Slab with Drop Ceiling Overall Size: 3048 mm

More information

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to KOLAY FLOORING INTERNATIONAL, LLC

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to KOLAY FLOORING INTERNATIONAL, LLC ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to KOLAY FLOORING INTERNATIONAL, LLC Series/Model: Kolay KW 110 Specimen Type: Open Web Truss - 457 mm Overall Size: 3048 mm by 3658

More information

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to AMORIM CORK COMPOSITES

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to AMORIM CORK COMPOSITES ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to AMORIM CORK COMPOSITES Series/Model: AcoustiCORK ECOx2 Sound Reduction Underlayment for LVT Plank Flooring Specimen Type: Open Web

More information

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP. Series/Model: Protecto Wrap Whisper Mat CS

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP. Series/Model: Protecto Wrap Whisper Mat CS ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to PROTECTO WRAP Series/Model: Protecto Wrap Whisper Mat CS Specimen Type: Open Web Truss - 457 mm Overall Size: 3048 mm by 3658 mm

More information

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON 1MM REGUPOL SONUS SOUND CONTROL UNDERLAYMENT UNDER CERAMIC TILE SPECIMEN TYPE Concrete Slab - 23 mm REPORT

More information

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON 18" OPEN WEB TRUSS WITH 3MM SONUS, HARDWOOD FLOOR AND SONUSCLIP CEILING SPECIMEN TYPE Open Web Truss -

More information

ACOUSTICAL PERFORMANCE TEST REPORT

ACOUSTICAL PERFORMANCE TEST REPORT REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON 1MM REGUPOL SONUS SOUND CONTROL UNDERLAYMENT UNDER CERAMIC TILE SPECIMEN TYPE 23 mm Concrete Slab with

More information

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Forest rx

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Forest rx ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to Series/Model: Forest rx Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results Data File

More information

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Base 10

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Base 10 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to Series/Model: Base 10 Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results Data File Result

More information

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to NEW ENGLAND SOUNDPROOFING SERIES/MODEL: REVRB TRADITIONAL SERIES

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to NEW ENGLAND SOUNDPROOFING SERIES/MODEL: REVRB TRADITIONAL SERIES ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423 Rendered to NEW ENGLAND SOUNDPROOFING SERIES/MODEL: REVRB TRADITIONAL SERIES TYPE: Acoustic Panels Summary of Test Results Data File No. 1/3 Octave Sound Absorption

More information

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Expona

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Expona ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to ECORE International Series/Model: Expona Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results

More information

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: QT4005

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: QT4005 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to Series/Model: QT4005 Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results Data File Result

More information

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: QT4002

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: QT4002 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to Series/Model: QT4002 Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results Data File Result

More information

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to FABRITRAK SYSTEMS, INC. SERIES/MODEL: Fabri Flex Fabric with 6#

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to FABRITRAK SYSTEMS, INC. SERIES/MODEL: Fabri Flex Fabric with 6# G9534.02-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423 Rendered to FABRITRAK SYSTEMS, INC. SERIES/MODEL: Fabri Flex Fabric with 6# TYPE: 1" (25.4 mm) Thick Acoustical Fiberglass Summary of Test

More information

H R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR. Type: Office Partition

H R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR. Type: Office Partition H0258.01-303-11-R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR Type: Office Partition Glazing: 1/4" Tempered Interior, 3-1/2" Air Space, 1/4" Tempered

More information

URBAN SURFACES TEST REPORT

URBAN SURFACES TEST REPORT URBAN SURFACES TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON URBAN SURFACES SOUNDTEC REPORT NUMBER H4383.13311R TEST DATE 8/1/17 ISSUE DATE 8/16/17 RECORD RETENTION END 8/1/21 PAGES 13 DOCUMENT

More information

H R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR. Type: Office Partition

H R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR. Type: Office Partition H0258.04-303-11-R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR Type: Office Partition Glazing: 1/4" Laminate Interior, 3-1/2" Air Space, 3/8" Laminate

More information

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON CERAMIC TILE OVER 5 MM ECOSILENCE UNDERLAYMENT SPECIMEN TYPE Vulcraft 2 Gage Dove Tail 3.5 Steel Deck

More information

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON FUSION HYBRID OVER 2 MM ECOSILENCE UNDERLAYMENT SPECIMEN TYPE Vulcraft 2 Gage Dove Tail 3.5 Steel

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: GAMCO CORPORATION. Series/Model: CW250

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: GAMCO CORPORATION. Series/Model: CW250 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: GAMCO CORPORATION Series/Model: CW250 Type: Two-Lite Curtain Wall System Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC

More information

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E90 AND ASTM E492 TESTING ON ATTAIN LVT OVER 2 MM ECOSILENCE UNDERLAYMENT

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E90 AND ASTM E492 TESTING ON ATTAIN LVT OVER 2 MM ECOSILENCE UNDERLAYMENT VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON ATTAIN LVT OVER 2 MM ECOSILENCE UNDERLAYMENT SPECIMEN TYPE Vulcraft 2 Gage Dove 2. Tail Steel Deck

More information

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: SHA4. TYPE: Single Hung Window

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: SHA4. TYPE: Single Hung Window ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: SHA4 TYPE: Single Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to DFB SALES. Series/Model: DFB Artform Panel Wrapped in Carnegie Xorel

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to DFB SALES. Series/Model: DFB Artform Panel Wrapped in Carnegie Xorel E7002.01-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423 Rendered to DFB SALES Series/Model: DFB Artform Panel Wrapped in Carnegie Xorel Type: Absorption Panel Summary of Test Results Data File

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: THERMA-TRU CORPORATION Series/Model: 3/0 x 6/8 Fiber-Classic/Smooth-Star, Full Lite Flush Glazed Type: Side-Hinged Single Door System Summary of

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: PAC INTERNATIONAL, LLC

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: PAC INTERNATIONAL, LLC ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: PAC INTERNATIONAL, LLC TYPE: Wall, Steel (0.018" / 25 ga), RSIC-V, STC 67 DATA FILE NO: E4748.01A STC 67 OITC 56 Test Specimen Identification: (Source

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: THERMA-TRU CORPORATION Series/Model: 3/0 x 6/8 Fiber-Classic/Smooth-Star, Full Lite 1" IG Impact Glass with BTS Lite Frame Type: Side-Hinged Single

More information

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: MI WINDOWS AND DOORS, LLC. SERIES/MODEL: 1650 Vinyl

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: MI WINDOWS AND DOORS, LLC. SERIES/MODEL: 1650 Vinyl ACOUSTICAL PERFORMANCE TEST REPORT ASTM E9 Rendered to: MI WINDOWS AND DOORS, LLC SERIES/MODEL: 165 Vinyl TYPE: Double Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC

More information

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON CERAMIC TILE OVER 5 MM ECOSILENCE UNDERLAYMENT SPECIMEN TYPE Vulcraft 2 Gage Dove Tail 3.5 Steel Deck

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: S80 Monterey. TYPE: Bi-fold Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: S80 Monterey. TYPE: Bi-fold Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: S80 Monterey TYPE: Bi-fold Door Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC

More information

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NOVAWALL SYSTEMS, INC. SERIES/MODEL: 3/4" Weltless. TYPE: Stretch Fabric Wall System

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NOVAWALL SYSTEMS, INC. SERIES/MODEL: 3/4 Weltless. TYPE: Stretch Fabric Wall System ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: NOVAWALL SYSTEMS, INC. SERIES/MODEL: 3/4" Weltless TYPE: Stretch Fabric Wall System Summary of Test Results Sample ID Number & Sample Description 1/3

More information

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E90 SOUND TRANSMISSION LOSS TESTING ON A STEEL STUD WALL ASSEMBLY WITH SONUSCLIP REPORT NUMBER H7677.03-113-11-R0 TEST DATE 11/20/17

More information

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB. TYPE: Acoustic Baffles

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB. TYPE: Acoustic Baffles ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB TYPE: Acoustic Baffles Sample ID Number & Sample Description D9015.01 Series/Model 9100AB REVRB,

More information

NOVAWALL SYSTEMS, INC. ACOUSTICAL PERFORMANCE TEST REPORT

NOVAWALL SYSTEMS, INC. ACOUSTICAL PERFORMANCE TEST REPORT NOVAWALL SYSTEMS, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM C423 SOUND ABSORPTION TESTING ON A 2" NOVAWALL SQUARE EDGE SYSTEM REPORT NUMBER H8708.02-113-11-R0 TEST DATE 12/28/17 ISSUE

More information

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9000AP REVRB. TYPE: Acoustical Wall Panel

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9000AP REVRB. TYPE: Acoustical Wall Panel ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9000AP REVRB TYPE: Acoustical Wall Panel Summary of Test Results Sample ID Number & Sample Description D9013.01

More information

ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT

ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM C423 SOUND ABSORPTION TESTING ON OMNIASCREEN, ROLLER SHADE FABRIC REPORT NUMBER I7377.01-113-11-R0 TEST DATE 08/14/18 ISSUE DATE 09/04/18

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500. TYPE: Double Hung Window

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500. TYPE: Double Hung Window ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500 TYPE: Double Hung Window Data File No. 97455.01 Summary of Test Results Glazing (Nominal Dimensions)

More information

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP TYPE: Picture Window ATI Data File No. 71965.01A 71965.01B Summary of Test Results Glazing

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390. TYPE: Sliding Glass Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390. TYPE: Sliding Glass Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390 TYPE: Sliding Glass Door Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 6/8 Sliding Patio Door ATI Data File No. 74387.01 74387.01A* Summary of Test Results Glazing (Nominal

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, LLC. SERIES/MODEL: 1650 Polyvinyl Chloride (PVC)

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, LLC. SERIES/MODEL: 1650 Polyvinyl Chloride (PVC) ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, LLC SERIES/MODEL: 1650 Polyvinyl Chloride (PVC) This product also is labeled under the following Series/Model names: 1555,

More information

9WOOD, INC. ACOUSTICAL PERFORMANCE TEST REPORT

9WOOD, INC. ACOUSTICAL PERFORMANCE TEST REPORT 9WOOD, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM C423 SOUND ABSORPTION TESTING ON 1000 SERIES SKU 1113-6 CROSS PIECE WOOD GRILLES WITH FIBERGLASS DUCT LINER REPORT NUMBER H5145.04-303-11

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 8/0 Sliding Patio Door with Impact Glass ATI Data File No. 74391.01 74391.01A* Summary of Test Results

More information

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: FabriSpan. TYPE: Ceiling System. Summary of Test Results

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: FabriSpan. TYPE: Ceiling System. Summary of Test Results ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: FabriSpan TYPE: Ceiling System Summary of Test Results Sample ID Number & Sample Description C8714.01 Series/Model

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star TYPE: 3/8 Impact Rated Side Hinged Door ATI Data File No. 74385.01A*

More information

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1-1/4" Fabri Trak

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1-1/4 Fabri Trak ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1-1/4" Fabri Trak TYPE: Upholstered Panel System with 1-1/4" Fabri Tack Summary of Test Results Sample ID Number

More information

BENETTI HOME ACOUSTICAL PERFORMANCE TEST REPORT

BENETTI HOME ACOUSTICAL PERFORMANCE TEST REPORT BENETTI HOME ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM C423 SOUND ABSORPTION TESTING ON BENETTIMOSS WALL PANELS REPORT NUMBER H6047.01-303-11 R0 TEST DATE 10/20/17 ISSUE DATE 11/13/17 RECORD

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 8/0 Sliding Patio Door Summary of Test Results ATI Data File No. Glazing (Nominal Dimensions) STC

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1 ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1 TYPE: Standard 8" Hollow Block Wall With Single Stud Wall Construction SOUND ISOLATION MATERIAL: Acoustiblok

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 900 Series. TYPE: Out-swing Double Terrace Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 900 Series. TYPE: Out-swing Double Terrace Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: UNITED STATES ALUMINUM SERIES/MODEL: 900 Series TYPE: Out-swing Double Terrace Door ATI Data File No. 63136.01 Summary of Test Results Glazing

More information

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1" FABRI TACK

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1 FABRI TACK ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1" FABRI TACK TYPE: Tackable Acoustic Core Material with Guilford of Maine FR 701 Fabric Sample ID Number & Sample

More information

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: Fabri Trak System. TYPE: Upholstered Panel

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: Fabri Trak System. TYPE: Upholstered Panel ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: Fabri Trak System TYPE: Upholstered Panel Summary of Test Results Sample ID Number & Sample Description 1/3 Octave

More information

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK AAMA 1801 TESTING ON IT451, STOREFRONT WINDOW REPORT NUMBER H7645.03-303-11 R0 TEST DATE 11/03/17 ISSUE DATE 11/17/17 RECORD RETENTION

More information

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK AAMA 1801 TESTING ON IT451, STOREFRONT WINDOW REPORT NUMBER H7645.02-303-11 R0 TEST DATE 11/03/17 ISSUE DATE 11/17/17 RECORD RETENTION

More information

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440. TYPE: Sliding Glass Door

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440. TYPE: Sliding Glass Door Architectural Testing AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440 TYPE: Sliding Glass Door ATI Data File No. 71967.01 Summary of Test

More information

PERFORMANCE TEST REPORT. Rendered to: DOW CORNING CORPORATION. PRODUCTS: Dow Corning 790 Silicone

PERFORMANCE TEST REPORT. Rendered to: DOW CORNING CORPORATION. PRODUCTS: Dow Corning 790 Silicone PERFORMANCE TEST REPORT Rendered to: DOW CORNING CORPORATION PRODUCTS: Dow Corning 790 Silicone Report No.: F6923.03-106-31 Report Date: 09/19/16 Test Record Retention Date: 09/07/21 130 Derry Court York,

More information

PERFORMANCE TEST REPORT. Rendered to: HILTI CORPORATION. PRODUCT: Extreme Weather Window & Door Insulating Foam Sealant

PERFORMANCE TEST REPORT. Rendered to: HILTI CORPORATION. PRODUCT: Extreme Weather Window & Door Insulating Foam Sealant PERFORMANCE TEST REPORT Rendered to: HILTI CORPORATION PRODUCT: Extreme Weather Window & Door Insulating Foam Sealant Report No.: G1169.02-106-31 Report Date: 11/16/16 Test Record Retention Date: 10/25/20

More information

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only. ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 492: Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using

More information

The purpose of the testing on the mock up specimen was to document the acoustical performance of four underlayments installed under ¾ thick marble.

The purpose of the testing on the mock up specimen was to document the acoustical performance of four underlayments installed under ¾ thick marble. February 24, 12 Daniel Tormo Green Sound Control 6956 SW 47 th Street Miami, FL 33155 Re: Field Impact Insulation Class Testing Report Paramount Bay, Miami Florida Dear Daniel, This letter presents the

More information

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK Order No Date: May 24, 2008 REPORT NO CRT-001

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK Order No Date: May 24, 2008 REPORT NO CRT-001 REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045 Order No. 3151742 Date: May 24, 2008 REPORT NO 3151742CRT-001 IMPACT SOUND TRANSMISSION TEST AND CLASSIFICATION OF LM FLOORING ½ INCH ENGINEERED HARDWOOD

More information

A L I O N Technical Center. Test Report

A L I O N Technical Center. Test Report FOR: Lebanon, PA Impact Sound Transmission CONDUCTED: 2017-07-12 Page 1 of 8 ON: Quarry Floor Tiles and Regupol SonusPlus (underlayment) over 8 inch Concrete Slab (no Ceiling) TEST METHOD Riverbank Acoustical

More information

TEST REPORT. Report No.: H Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia

TEST REPORT. Report No.: H Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia TEST REPORT Report No.: H3615.01-550-44 Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia PRODUCT TYPE: EIFS Panel Systems SERIES/MODEL: GP ForceField Air & Water Barrier Sheathing with

More information

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK Order No October 15, REPORT NO CRT-002d3

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK Order No October 15, REPORT NO CRT-002d3 REPORT ACCREDITATION UNDER NVLAP 3933 US ROUTE 11 CORTLAND, NEW YORK 13045 Order No. 3166866 October 15, 2013 REPORT NO. 3166866CRT-002d3 IMPACT SOUND TRANSMISSION TEST AND CLASSIFICATION OF LAMINATE FLOORING

More information

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio TEST REPORT Report No.: E9792.01-501-47 Rendered to: TREMCO, INCORPORATED Beachwood, Ohio PRODUCT TYPE: Wall Panel System SERIES/MODEL: ExoAir 230, Dymonic 100 SPECIFICATION: ASTM E 331, Standard Test

More information

KINETICS NOISE CONTROL TEST REPORT #AT001049

KINETICS NOISE CONTROL TEST REPORT #AT001049 KINETICS NOISE CONTROL TEST REPORT #AT001049 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o STC 53 o IIC 27 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA o B-3463.1

More information

KINETICS NOISE CONTROL TEST REPORT #AT001110

KINETICS NOISE CONTROL TEST REPORT #AT001110 KINETICS NOISE CONTROL TEST REPORT #AT001110 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o STC 53 o IIC 29 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o REPORT NO. A1-010601.1 o DATED:

More information

KINETICS NOISE CONTROL TEST REPORT #AT001035

KINETICS NOISE CONTROL TEST REPORT #AT001035 KINETICS NOISE CONTROL TEST REPORT #AT001035 KINETICS NOISE CONTROL PRODUCTS: o RIM I-2-16 ACOUSTICAL RATINGS: o STC 66 o IIC 63 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B-3140.1 KINETICS DRAWING

More information

B Page 1 of 21-

B Page 1 of 21- Airborne and impact sound transmission measurements were performed on three floor assemblies which comprised the NRC 150 mm reference concrete slab and a 102 mm floating concrete slab. For report purposes,

More information

KINETICS NOISE CONTROL TEST REPORT #AT001052

KINETICS NOISE CONTROL TEST REPORT #AT001052 KINETICS NOISE CONTROL TEST REPORT #AT001052 KINETICS NOISE CONTROL PRODUCTS: o ISOMAX CLIPS ACOUSTICAL RATINGS: o STC 66 o IIC 44 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA

More information

KINETICS NOISE CONTROL TEST REPORT #AT001067

KINETICS NOISE CONTROL TEST REPORT #AT001067 KINETICS NOISE CONTROL TEST REPORT #AT001067 KINETICS NOISE CONTROL PRODUCTS: o FLM- NEOPRENE PAD ACOUSTICAL RATINGS: o STC 69 o IIC 61 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA

More information

KINETICS NOISE CONTROL TEST REPORT #AT001021B

KINETICS NOISE CONTROL TEST REPORT #AT001021B KINETICS NOISE CONTROL TEST REPORT #AT001021B KINETICS NOISE CONTROL PRODUCTS: o ICW ACOUSTICAL RATINGS: o STC 76 o IIC 62 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B3463.13 KINETICS DRAWING NUMBER:

More information

ASTM D 4541 ADHESION STRENGTH PERFORMANCE TEST REPORT. Rendered to: BAUTEX SYSTEMS. PRODUCT: AMB 20-WN Liquid Applied Membrane

ASTM D 4541 ADHESION STRENGTH PERFORMANCE TEST REPORT. Rendered to: BAUTEX SYSTEMS. PRODUCT: AMB 20-WN Liquid Applied Membrane ASTM D 4541 ADHESION STRENGTH PERFORMANCE TEST REPORT Rendered to: BAUTEX SYSTEMS PRODUCT: AMB 20-WN Liquid Applied Membrane Report No: Report Date: 08/30/13 Report Retention Date: 07/23/14 130 Derry Court

More information

ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: WIRE-BOND. SERIES/MODEL: Masonry Tie Thermal Evaluations (2x6 Steel Stud Wall)

ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: WIRE-BOND. SERIES/MODEL: Masonry Tie Thermal Evaluations (2x6 Steel Stud Wall) ASTM C 1363-11 THERMAL PERFORMANCE TEST REPORT Rendered to: WIRE-BOND SERIES/MODEL: Masonry Tie Thermal Evaluations (2x6 Steel Stud Wall) TYPE: Masonry Wall Assembly Summary of Results Test Unit R-Value

More information

FIELD IMPACT INSULATION TESTS 133 SCARBOROUGH STREET, SOUTHPORT TEST REPORT

FIELD IMPACT INSULATION TESTS 133 SCARBOROUGH STREET, SOUTHPORT TEST REPORT Commissioned by: National Flooring Distributors Pty Ltd Date: 26 June 2015 Project number: 3872 Version: V.0 Author: Eric Huang 24 Mexicanus Drive, PO Box 790, Park Ridge Queensland 4125 Australia p. +61

More information

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 7 TEST : Acoustical Surfaces, Inc. Report Date: May 25, 2011 Test Date: September 28, 2010 Test

More information

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only. ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 492: Laboratory Measurement of Impact Sound Transmission through Floor- Ceiling Assemblies Using

More information

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 7 TEST : Acoustical Surfaces, Inc. Report Date: May 25, 2011 Test Date: September 28, 2010 Test

More information

Ceramic Tile, LATICRETE 253 Gold Mortar and LATICRETE 170 Sound & Crack Isolation Mat on 6 Inch Concrete Slabs. Page 1 of 5. CONDUCTED: 1 May 2008

Ceramic Tile, LATICRETE 253 Gold Mortar and LATICRETE 170 Sound & Crack Isolation Mat on 6 Inch Concrete Slabs. Page 1 of 5. CONDUCTED: 1 May 2008 FOR: LATICRETE International, Inc. Bethany, CT Floor Covering Impact Reduction Test ON: Ceramic Tile, LATICRETE 253 Gold Mortar and LATICRETE 170 Sound & Crack Isolation Mat on 6 Inch Concrete Slabs Page

More information