Modelling the influence of building types on the building response to railway vibration

Size: px
Start display at page:

Download "Modelling the influence of building types on the building response to railway vibration"

Transcription

1 Modelling the influence of building types on the building response to railway vibration M. Villot 1, P.Ropars 1, P.Jean 1, E.Bongini 2, F.Poisson 2 1 CSTB, 24 Rue Joseph Fourier, Saint Martin d Hères, France { michel.villot@cstb.fr, pierre.ropars@cstb.fr, philippe.jean@cstb.fr } 2 SNCF, I&R/PFC, 45 Rue de Londres, Paris cedex 08, France { estelle.bongini@sncf.fr, franck.poisson@sncf.fr } Abstract A 2D BEM / FEM ground structure vibration interaction model is used to estimate the influence of building types on the building response to railway vibration. The results are expressed in terms of transfer function between free field ground vibration and building floor vibration. The ground / structure model is first experimentally validated from field measurements of ground and building vibration performed near railway and then used in a parametric study to evaluate the influence of floor thickness and span, as well as the thickness of buried walls and façades. Real railway ground signals are finally used to compare the results in terms of currently used vibration exposure indicators. Keywords: ground borne vibration from railways, building vibrational response. 1 Introduction A vibration measurement campaign has recently been carried out in France in order to compare freight trains and passenger trains (Vibsolfret project). Ground vibration measurements have been performed in free field at different distances from the tracks as well as vibration measurements in a building close to the train tracks. A dozen of passages for each train type were measured so that statistical data could be calculated. Having all these data for one ground-building configuration, a decision was made to try to extend the measured results to other building types by calculation, using a 2D ground structure vibration interaction model (MEFISSTO software) developed at CSTB. In the first part (section 2) of this paper, the model is described, the main parameters given and the model experimentally 1

2 validated. A parametric study is then performed in section 3 in order to extend the measured results to other building types by calculation and evaluate the influence of floor thickness and span, as well as the thickness of buried walls and façades. In the last part (section 4), real railway ground signals are used to express the results of the parametric study in terms of currently used vibration exposure indicators and to show the influence of building structures on people s perception and annoyance. 2 Model used; experimental validation 2.1 Model used A BEM FEM ground structure interaction model either 2D or 2D ½ has been developed at CSTB (MEFISSTO software, see [1,2]) in order to estimate the effect of environmental ground vibrations on buildings. The usual configuration tested consists of a half space ground (BEM approach) and a simplified building (FEM) with building elements either underground or above ground (see example in section 2.2). Three typical ground types are often used at CSTB, with the parameters shown in table 1 below. Table 1 Typical ground parameters Young modulus MPa Density kg/m3 Shear velocity m/s Softer ground Standard ground Harder ground Experimental validation Ground propagation MEFISSTO has been used here in a 2D ½ configuration composed of a free half space ground (no structures) and an infinite uncorrelated line source (1N/m force). The vibration acceleration levels at different distances from the line source were calculated; then the free field ground vibration level (narrow band spectrum) measured at 6m from the track during the measuring campaign were used to calibrate the calculated results. The 1/3 octave band acceleration spectra measured and calculated at different distances from the tracks (3, 6, 9, 12, 17 et 20m) are given in figure 1, showing that the attenuation with distance is well modeled with MEFISSTO using the standard ground parameters (see table 1) over a 1/3 octave Hz frequency range Transfer function between free field ground and building MEFISSTO has been used here in a 2D configuration composed of a half space ground and the building structure (given in figure 2), simplified compared to the real building but with elements having the right length and thickness: all the elements are made of 20cm thick reinforced concrete, except the façade (embedded part and part above ground), which was particularly thick (40 cm) in the (old) building measured. The building is located at 6m from the tracks (excitation force shown in figure 2). The transfer function between free field ground vibration level at the same distance as the building (configuration with no structures) and first floor vibration level in the building (location close to the center of the floor) was calculated 2

3 and compared to the transfer function obtained from measured spectra (free field ground at 6m and first floor in the building). Figure 1 Attenuation with distance calculated using MEFISSTO (continuous line) and measured (dotted line). Figure 2 Simplified 2D geometry of the measurement site The results given in figure 3 show that (i) the orders of magnitude are acceptable, (ii) the best calculated results are obtained using the standard ground parameters (which confirms the results of section 2.2.1) and (iii) the calculated transfer function frequency spectra are much rougher than the measured one. These rather acceptable results justify the use of a 2D model in the parametric study presented in the next section. 3

4 Figure 3 Transfer function between free field ground vibration (at the same distance from the tracks as the building) and first floor vibration in the building 3 Parametric study 3.1 Method In this section, a parametric study is performed in order to evaluate the influence on the floor vibration (at a location close to the center of the floor), of floor thickness and span, thickness of buried walls and façades as well as distance of the building from the tracks. The results are expressed here in terms of floor vibration velocity levels estimated from the calculated transfer functions obtained with MEFISSTO and real (measured) ground vibration spectra. 3.2 Parametric study Distance from the tracks The building originally at 6m from the track is virtually moved away at 20m. Assuming the transfer function between free field ground at the same distance and building is the same at 20m, the floor velocity level at 20m is estimated from the transfer function measured at 6m and the ground vibration measured at 20m. Ground and floor vibration levels are given in figures 4 and 5 respectively. The results show that there is an attenuation of more 20 db at 20m from the tracks. The frequency shift (of about 20 Hz toward the low frequencies) observed in Figure 4 between the 2 ground vibration spectra disappears in figure 5, showing a spectrum shape imposed by the floor modal response. 4

5 Figure 4 Free field ground levels measured at 6 and 20m from the tracks Figure 5 floor levels in the building measured at 6m and estimated at 20m from the tracks Floor thickness The floor thickness originally of 20cm is virtually either decreased (15cm) or increased (25cm). The floor vibration levels obtained are given in figure 6, showing that (i) the calculated floor velocity levels are close to the measured ones and (ii) the floor modal response (20 cm) is frequency shifted compared to the measured one (result expected with the 2D model used) and this shift varies with the floor thickness Façade thickness The façade (embedded part and part above ground) was particularly thick (40 cm) in the (old) building measured. Its thickness is now virtually decreased to a more current one (20cm). The floor vibration levels obtained are given in figure 7, showing that (i) the floor response is 5

6 frequency shifted (because of the change in its boundary conditions) and (ii) the vibration levels are more than 10 db higher. Figure 6 Floor velocity levels in the building either measured or estimated for different floor thicknesses Figure 7 Floor velocity levels in the building either measured or estimated for different façade thicknesses Floor span The floor span, originally of 3.4m is virtually doubled (6.8m), with the same floor thickness. The floor vibration levels obtained are given in figure 8, showing that the floor response is 6

7 frequency shifted (toward the low frequencies) and its vibration levels increased (the floor becomes more supple); these two results were expected. Figure 8 Floor velocity levels in the building either measured or estimated for different floor spans 4 Results expressed in terms of vibration exposure indicators 4.1 Method Without any proper standards / regulation on vibration from railways and its effects on people in France, the Norwegian standard NS 8176.E [3], in accordance with ISO and very well documented, was used to express the results of the parametric study in terms of vibration exposure indicators and corresponding annoyance. The procedure for calculating the Norwegian vibration exposure indicators is the following: (i) either the acceleration time signal or the velocity time signal is used (ii) the signal is filtered in 1/3 octave band in order to get N filtered time signals s i corresponding to the N 1/3 octave band considered (iii) the time dependant rms value (with time window τ =1s) of each signal s i is calculated according to 1 / 2 t 1 2 si,rms( t ) = si ( t ) dt (1) τ t τ (iv) at each instant t, the N 1/3 octave signals s i,rms (t) are then weighted using the w m weighting (expressed in 1/3 octave values w i ) defined in standard ISO ; the weighted signal s w,rms (t) is calculated according to s w,rms 1 / 2 2 ( t ) = si,rms( t ). wi (2) i 7

8 An example of weighted signal s w,rms (t) is given in figure 9, calculated from a measured ground acceleration signal generated by a passenger train at 6m from the tracks. Figure 9 Weighted signal s w,rms (t) calculated from a measured ground acceleration signal generated by a passenger train at 6m from the tracks For each train passage (index i), the above procedure was first applied to the floor velocity signal measured in the real building; then, the variations in the 1/3 octave floor vibration spectra calculated using MEFFISTO in the parametric study were added to the 1/3 octave w m weighting (step (iv) in the procedure) in order to get the modified weighted signal v w,rms,i (t) (which would be obtained in the modified building configuration).finally and according to standard NS 8176, the maximum value v w,max,i during the train passage was calculated. In a second step, the same procedure was applied to all the floor signals measured for all the freight trains (a dozen) and the mean value as well as the standard deviation σ calculated in order to get the 95% confidence value used in the Norwegian standard. 4.2 Results From the real building measured (located at 6m from the track, with a façade 40cm thick and a first floor 20cm thick and 3.40m long), the 4 configurations presented in the parametric study were considered: (i) same building at 20m from the tracks, (ii) building at 6m with modified façade thickness (20cm), (iii) building at 6m with modified floor thickness (15 and 25cm), (iv) building at 6m with modified floor span (6.80m). The exposure indicator obtained for all the building configurations are given in table 2. Table 2 Indicator obtained for all the building configurations calculated Real building measured Same building at 20m Façade thickness of 20cm Floor thickness of 15cm Floor thickness of 25cm Floor span of 6.80m mm/s

9 Following the Norwegian regulation, the results given in Table 2 show that: (i) the building at 20m from the tracks corresponds to a very good vibration environment (Class A of the Norwegian standard) where residents should normally not notice the presence of vibration, (ii) the real building and the building with floor thickness increased correspond to a relatively good vibration environment (Class B) where a low percentage (less than 10%) of the residents are expected to be annoyed, (iii) the building with reduced floor thickness corresponds to recommended values for a new building (Class C) where already about 15% of the residents are expected to be annoyed, (iv) the building with long floor span corresponds to recommended values for an existing building (Class D) when the cost for improvement is prohibitive; about 25% of the residents are expected to be annoyed, and (v) the building at 6m with smaller (but common) façade (20cm) corresponds to values higher than the recommended ones; the building must therefore be treated to at least reach Class D because more that ¼ of the residents are expected to be annoyed. 5 Conclusions From a whole set of railway vibration data, measured for one ground / building configuration, the results were extended to other ground /building configurations by calculation using a 2D BEM/FEM ground structure interaction model. The modified floor vibration was estimated for each configuration and expressed first in terms of 1/3 octave vibration velocity spectra and then in terms of vibration exposure indicator and corresponding annoyance; the example of the Norwegian standard NS 8176, in accordance with ISO and well documented, was used but other standards such as the similar German standard DIN or the British standard BS based on vibration dose could have also been used. The data presented were obtained from freight train passages; passenger trains usually faster than freight trains would have given very similar results. Acknowledgments The authors gratefully acknowledge the support of this work by the French Agency ADEME (Agency for Environment and Energy Management) References [1] Jean P., Boundary and finite elements for 2D soil-structure interaction problems, Acta Acustica 87, 56-66, (2001) [2] Jean P., Guigou-Carter C., Villot M. A 2.5D BEM model for ground structure interaction. Building Acoustics 11(3), (2004) [3] Norwegian Standard NS 8176.E: Vibration and shock Measurement of vibration in buildings from land based transport and guidance to evaluation of its effects on human beings, Norway,

VIBSOLFRET: ground vibrations induced by freight traffic, from the track to the building

VIBSOLFRET: ground vibrations induced by freight traffic, from the track to the building VIBSOLFRET: ground vibrations induced by freight traffic, from the track to the building Titre de la présentation 28/10/2010 DEUFRAKO seminary, Munich the 27th october 2010 OUTLINE Context Measurement

More information

Prediction of the acoustic performance of floor coverings on lightweight floors

Prediction of the acoustic performance of floor coverings on lightweight floors Prediction of the acoustic performance of floor coverings on lightweight floors Catherine Guigou-Carter a CSTB, Center for Building Science and Technology 24 Rue Joseph Fourier 38 Saint Martin d Hères,

More information

COMPARISON OF MEASURED AND PREDICTED SOUND INSULATION FOR A THERMAL RETROFITTED BUILDING

COMPARISON OF MEASURED AND PREDICTED SOUND INSULATION FOR A THERMAL RETROFITTED BUILDING Invited Paper COMPARISON OF MEASURED AND PREDICTED SOUND INSULATION FOR A THERMAL RETROFITTED BUILDING C. Guigou-Carter 1, R. Foret 2, R. Wetta 1, P. Ducruet 1, M. Villot 1 Affiliation: { 1 CSTB, 24 Rue

More information

DETAILED ANALYSIS OF MEASUREMENT RESULTS OF FLANKING TRANSMISSION ACROSS A JUNCTION COM- POSED OF DOUBLE WALLS CARRIED OUT ON A HALF SCALED TEST BENCH

DETAILED ANALYSIS OF MEASUREMENT RESULTS OF FLANKING TRANSMISSION ACROSS A JUNCTION COM- POSED OF DOUBLE WALLS CARRIED OUT ON A HALF SCALED TEST BENCH DETAILED ANALYSIS OF MEASUREMENT RESULTS OF FLANKING TRANSMISSION ACROSS A JUNCTION COM- POSED OF DOUBLE WALLS CARRIED OUT ON A HALF SCALED TEST BENCH. Charlotte Crispin, Christian Mertens and Arne Dijckmans

More information

A NEW EMPIRICAL PREDICTION APPROACH FOR GROUNDBORNE VIBRATION IN BUILDINGS

A NEW EMPIRICAL PREDICTION APPROACH FOR GROUNDBORNE VIBRATION IN BUILDINGS A NEW EMPIRICAL PREDICTION APPROACH FOR GROUNDBORNE VIBRATION IN BUILDINGS Daniel Lurcock and David Thompson University of Southampton, Institute of Sound and Vibration Research, Highfield, Southampton,

More information

TUNNEL BORING MACHINE VIBRATION IMPACT PREDICTION METHOD BASED ON SURFACE VIBRATION MEASUREMENTS AND TUNNEL TO SURFACE TRANSFER FUNCTION CALCULATION

TUNNEL BORING MACHINE VIBRATION IMPACT PREDICTION METHOD BASED ON SURFACE VIBRATION MEASUREMENTS AND TUNNEL TO SURFACE TRANSFER FUNCTION CALCULATION TUNNEL BORING MACHINE VIBRATION IMPACT PREDICTION METHOD BASED ON SURFACE VIBRATION MEASUREMENTS AND TUNNEL TO SURFACE TRANSFER FUNCTION CALCULATION Alexis Bigot SOLDATA ACOUSTIC, 92000 Nanterre, France

More information

Façade insulation at low frequencies influence of window design

Façade insulation at low frequencies influence of window design PROCEEDINGS of the 22 nd International Congress on Acoustics Challenges and Solutions in Acoustics Measurement and Design: Paper ICA2016-809 Façade insulation at low frequencies influence of window design

More information

The Influence of the Shape of Slab on Heavyweight Impact Sound Reduction for an Apartment Building

The Influence of the Shape of Slab on Heavyweight Impact Sound Reduction for an Apartment Building The Influence of the Shape of Slab on Heavyweight Impact Sound Reduction for an Apartment Building Young-Soo Chun 1 ; Bum-Sik Lee 2 ; Seong-Bok Lee 3 123 Land and Housing Institute, Korea Land and Housing

More information

Comparison of measured and predicted sound insulation for a thermal retrofitted building

Comparison of measured and predicted sound insulation for a thermal retrofitted building Comparison of measured and predicted sound insulation for a thermal retrofitted building C. Guigou-Carter, R. Foret, R. Wetta,P. Ducruet, M. Villot CSTB Inter-Noise 2010 Lisbon, Portugal PAGE 1 Introduction

More information

A parametric study on the isolation of ground-borne noise and vibrations in a building using a coupled numerical model

A parametric study on the isolation of ground-borne noise and vibrations in a building using a coupled numerical model A parametric study on the isolation of ground-borne noise and vibrations in a building using a coupled numerical model P. Fiala a, S. Gupta b, G. Degrande b and F. Augusztinovicz a a Budapest University

More information

Measurements of junction vibration level differences of timber framed constructions

Measurements of junction vibration level differences of timber framed constructions Measurements of junction vibration level differences of timber framed constructions Anders HOMB 1 1 NTNU Trondheim. Norwegian University of Science and Technology ABSTRACT Flanking transmission of supporting

More information

Aging and temperature dependency of acoustic PVC floor covering under French certification NF UPEC.A+

Aging and temperature dependency of acoustic PVC floor covering under French certification NF UPEC.A+ Edinburgh, Scotland EURONOISE 2009 October 26-28 Aging and temperature dependency of acoustic PVC floor covering under French certification NF UPEC.A+ Jean-Baptiste Chéné a Rémy Foret b Paris-Est University,

More information

Simulation of Ground-borne Vibration and Noise Due to High -speed. Trains through Changsha Railway Station

Simulation of Ground-borne Vibration and Noise Due to High -speed. Trains through Changsha Railway Station 5th International Conference on Civil Engineering and Transportation (ICCET 2015) Simulation of Ground-borne Vibration and Noise Due to High -speed Trains through Changsha Railway Station SHEN Daoming1,a*,

More information

Modal analysis and flanking sound insulation in connected panels of cross-laminated-timber at low frequencies

Modal analysis and flanking sound insulation in connected panels of cross-laminated-timber at low frequencies Modal analysis and flanking sound insulation in connected panels of cross-laminated-timber at low frequencies Blasius Buchegger Laboratory for Building Science, University of Technology, Graz, Austria.

More information

Control of variable frequency vibration in large span composite construction floor in a high rise building

Control of variable frequency vibration in large span composite construction floor in a high rise building Control of variable frequency vibration in large span composite construction floor in a high rise building ABSTRACT Tim Marks (1), Dr Len Koss (2) and Michael Plumb (3) (1) Associate Director, Marshall

More information

Flanking sound transmission in an innovative lightweight clay block building system with an integrated insulation used at multifamily houses

Flanking sound transmission in an innovative lightweight clay block building system with an integrated insulation used at multifamily houses Flanking sound transmission in an innovative lightweight clay block building system with an integrated insulation used at multifamily houses Blasius BUCHEGGER 1 ; Heinz FERK 2 ; Marlon MEISSNITZER 3 1,2,3

More information

THE EFFECTS OF LOCAL MODES ON VIBRATION REDUCTION OF BUILDING ISOLATION. Hong Kong SAR. Hong Kong SAR.

THE EFFECTS OF LOCAL MODES ON VIBRATION REDUCTION OF BUILDING ISOLATION. Hong Kong SAR. Hong Kong SAR. ICSV14 Cairns Australia 9-12 July, 07 THE EFFECTS OF LOCAL MODES ON VIBRATION REDUCTION OF BUILDING ISOLATION C. K. Hui 1, Y. Y. Lee 2 and C. F. Ng 1 1 Department of Civil and Structural Engineering, The

More information

A combined approach for base isolation design

A combined approach for base isolation design Acoustics 8 Paris A combined approach for base isolation design A. Neves E Sousa, L. Guerreiro and R. Gomes IST, Department of Civil Engineering and Architecture, Av. Rovisco Pais, 1, 49-1 Lisbon, Portugal

More information

Comparison Between Measurement Techniques to Estimate Flanking Sound Transmission

Comparison Between Measurement Techniques to Estimate Flanking Sound Transmission paper ID: 054 /p.1 Comparison Between Measurement Techniques to Estimate Flanking Sound Transmission Andrade, C.A.R a., Barbaresi, L. b, Fausti, P. c & Semprini, G. b a Universidad de Valladolid, E.T.S.I.I.

More information

The Numerical Prediction and Features Analysis of Cylindrical Shell Acoustic Radiation Noise

The Numerical Prediction and Features Analysis of Cylindrical Shell Acoustic Radiation Noise The Numerical Prediction and Features Analysis of Cylindrical Shell Acoustic Radiation Noise Hongli CAO 1 ; Shiliang FANG 2 ; Liang AN 3 Key Laboratory of Underwater Acoustic Signal Processing of Ministry

More information

European Round Robin Test for sound insulation Measurements of lightweight partition.

European Round Robin Test for sound insulation Measurements of lightweight partition. European Round Robin Test for sound insulation Measurements of lightweight partition. Cyrille Demanet, Maria Jose De Rozas 2, Jean Baptiste Chene and Remy Foret 4 Lafarge gypsum, Avignon FRANCE 2 Tecnalia

More information

GARAGE STRUCTURE VIBRATION TRANSMISSION TO HUMAN OCCUPIED SPACES

GARAGE STRUCTURE VIBRATION TRANSMISSION TO HUMAN OCCUPIED SPACES GARAGE STRUCTURE VIBRATION TRANSMISSION TO HUMAN OCCUPIED SPACES Jack B. Evans* 1 1 JEAcoustics / Engineered Vibration Acoustic & Noise Solutions 175 West Koenig Lane, Austin, Texas 78756, USA Evans(at)JEAcoustics.com

More information

NODALIZATION OF ISOLATOR FOR FLOATING FLOOR DESIGN. C.K. Hui and C. F. Ng

NODALIZATION OF ISOLATOR FOR FLOATING FLOOR DESIGN. C.K. Hui and C. F. Ng ICSV14 Cairns Australia 9-12 July, 07 NODALIZATION OF ISOLATOR FOR FLOATING FLOOR DESIGN C.K. Hui and C. F. Ng Department of Civil and Structural Engineering, The Hong Kong Polytechnic University, Kowloon,

More information

Propagation of Structure-borne Sound in Lightweight Gypsum Board Walls

Propagation of Structure-borne Sound in Lightweight Gypsum Board Walls Propagation of Structure-borne Sound in Lightweight Gypsum Board Walls Stefan Schoenwald, Eddy Gerretsen, Heiko J. Martin Eindhoven University of Technology, NL-56 MB Eindhoven, Den Dolech 2, The Netherlands,

More information

Full-Scale Shaking Table Tests of XLam Panel Systems - Correlation With Cyclic Quasi-Static Tests

Full-Scale Shaking Table Tests of XLam Panel Systems - Correlation With Cyclic Quasi-Static Tests Full-Scale Shaking Table Tests of XLam Panel Systems - Correlation With Cyclic Quasi-Static Tests V. Hristovski, M. Stojmanovska Institute of Earthquake Engineering and Engineering Seismology (IZIIS),Skopje,

More information

Introduction. Engineering, Universiti Tun Hussein Onn Malaysia, Johor, MALAYSIA. Universiti Tun Hussein Onn Malaysia, Johor, MALAYSIA

Introduction. Engineering, Universiti Tun Hussein Onn Malaysia, Johor, MALAYSIA. Universiti Tun Hussein Onn Malaysia, Johor, MALAYSIA Floor Dynamic Assessment on Laboratory due to Ground Borne Vibrations using ModalV Analysis from Passing Vehicles Tuan Norhayati Tuan Chik 1, a, Shurl Yabi 2,b, Nor Azizi Yusoff 3,c, Mohd Hanif Mohamed

More information

Comparative Impact Performances of Lightweight Gym Floors

Comparative Impact Performances of Lightweight Gym Floors Comparative Impact Performances of Lightweight Gym Floors Lloyd Cosstick, Evan Hong and Tim Murray Embelton Noise and Vibration, Melbourne VIC 3058, Australia ABSTRACT Gyms are a common source of complaints

More information

CANDU 6 Nuclear Power Plant: Reactor building floor response spectra considering seismic wave incoherency

CANDU 6 Nuclear Power Plant: Reactor building floor response spectra considering seismic wave incoherency CANDU 6 Nuclear Power Plant: Reactor building floor response spectra considering seismic wave incoherency A. Nour 1,2, A. Cherfaoui 1, V. Gocevski 1 & P. Léger 2 1 Hydro Québec, Montréal, Québec, H2L4P5,

More information

Field investigation of the effects of vegetation on the performance of roadside noise barriers

Field investigation of the effects of vegetation on the performance of roadside noise barriers Proceedings of the Acoustics 2012 Nantes Conference 23-27 April 2012, Nantes, France Field investigation of the effects of vegetation on the performance of roadside noise barriers M. Hodgson and S. Daltrop

More information

B Page 1 of 21-

B Page 1 of 21- Airborne and impact sound transmission measurements were performed on three floor assemblies which comprised the NRC 150 mm reference concrete slab and a 102 mm floating concrete slab. For report purposes,

More information

Vibrational Response of Structures Exposed to Human-induced Loads

Vibrational Response of Structures Exposed to Human-induced Loads Vibrational Response of Structures Exposed to Human-induced Loads Jonas Syders Knudsen, M.Sc., Nikolaj Grathwol, M.Sc. and Svend Ole Hansen, Ph.D.,2 Svend Ole Hansen ApS, Sankt Jørgens Allé 5C, 65 Copenhagen,

More information

Vibration Serviceability Design and Field Tests of Long-Span Ultra- Slim Composite Floor System for Super Tall Residential Buildings

Vibration Serviceability Design and Field Tests of Long-Span Ultra- Slim Composite Floor System for Super Tall Residential Buildings Vibration Serviceability Design and Field Tests of Long-Span Ultra- Slim Composite Floor System for Super Tall Residential Buildings *Guo Ding 1), Jun Chen 2), Rong He 3) and Liwei Ye 4) 1), 3) Tongji

More information

Measurement of room-to-room airborne sound insulation with an access floor in a dwelling unit of condominium

Measurement of room-to-room airborne sound insulation with an access floor in a dwelling unit of condominium Measurement of room-to-room airborne sound insulation with an access floor in a dwelling unit of condominium T. Koga Kajima Technical Research Institute, 2-19-1 Tobitakyu, Chofu, 182-0036 Tokyo, Japan

More information

Measurement of room-to-room airborne sound insulation with an access floor in a dwelling unit of condominium

Measurement of room-to-room airborne sound insulation with an access floor in a dwelling unit of condominium Measurement of room-to-room airborne sound insulation with an access floor in a dwelling unit of condominium Takashi Koga Kajima Technical Research Institute, 2-19-1 Tobitakyu, Chofu, 182-0036 Tokyo, Japan

More information

An empirical model for the equivalent translational compliance of steel studs a. John L. Davy bc

An empirical model for the equivalent translational compliance of steel studs a. John L. Davy bc An empirical model for the equivalent translational compliance of steel studs a John L. Davy bc School of Applied Sciences, RMIT University, GPO Box 2476V Melbourne, Victoria 3001, Australia Catherine

More information

The specimen B W was identified by the client as a Skyfold Classic operable partition, with panels, seals, and clearances in configuration 4E.

The specimen B W was identified by the client as a Skyfold Classic operable partition, with panels, seals, and clearances in configuration 4E. TestingLaboratory: Client: Specimen: SpecimenID: Manufacturer: ConstructionDates: Testspecimenmountedby: NationalResearchCouncilCanada InstituteforResearchinConstruction 1200MontrealRoad Ottawa,OntarioK1A0R6

More information

A study on the prediction of the noise reduction performance according to applying the rail web-damper in curved track section

A study on the prediction of the noise reduction performance according to applying the rail web-damper in curved track section A study on the prediction of the noise reduction performance according to applying the rail web-damper in curved track section Jinho KIM 1 1 Korea Railroad Research Institute, Korea ABSTRACT This research

More information

ENGLISH SUMMARY. Rakenteiden Mekaniikka, Vol. 24 No 1, 1991 ON THE EFFECT OF NOISE AND VIBRATION TO MAN. Antero Honkasalo

ENGLISH SUMMARY. Rakenteiden Mekaniikka, Vol. 24 No 1, 1991 ON THE EFFECT OF NOISE AND VIBRATION TO MAN. Antero Honkasalo ENGLISH SUMMARY Rakenteiden Mekaniikka, Vol. 24 No 1, 1991 ON THE EFFECT OF NOISE AND VIBRATION TO MAN Antero Honkasalo The development of technology, urbanization and increase of traffic has lead us to

More information

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE Copyright SFA - InterNoise 2000 1 inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering 27-30 August 2000, Nice, FRANCE I-INCE Classification: 5.1 INCLUSION OF DAMPING

More information

TONAL NOISE MITIGATION ON WIND TURBINES

TONAL NOISE MITIGATION ON WIND TURBINES TONAL NOISE MITIGATION ON WIND TURBINES Jutta M. Stauber, Brett A. Marmo and Donald Black Xi Engineering Consultants Ltd, Edinburgh, UK email: juttastauber@xiengineering.com Free layer damping tiles were

More information

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE Copyright SFA - InterNoise 2000 1 inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering 27-30 August 2000, Nice, FRANCE I-INCE Classification: 1.0 NOISE REDUCTION

More information

COMPARISON AMONG METHODS TO MEASURE THE SOUND INSULATION OF BUILDING FAÇADES

COMPARISON AMONG METHODS TO MEASURE THE SOUND INSULATION OF BUILDING FAÇADES PACS: 43.55.Rg, 43..X. U. Berardi DAU Politecnico di Bari, Via Orabona 4, 70 Bari, Italy Tel-Fax (+39) 05 9 1 E-mail: u.berardi@poliba.it COMPARISON AMONG METHODS TO MEASURE THE SOUND INSULATION OF BUILDING

More information

FLANKING TRANSMISSION IN STEEL-CONCRETE COMPOSITE FLOORS

FLANKING TRANSMISSION IN STEEL-CONCRETE COMPOSITE FLOORS FLANKING TRANSMISSION IN STEEL-CONCRETE COMPOSITE FLOORS Beth Paxton and Jack Harvie-Clark Apex Acoustics, Design Works, William Street, Gateshead, UK email: jack.harvie-clark@apexacoustics.co.uk This

More information

Holistic optimisation of noise reducing devices

Holistic optimisation of noise reducing devices Holistic optimisation of noise reducing devices T. Leissing a, F. Grannec a, J. Defrance a, P. Jean a, D. Lutgendorf b, C. Heinkele c and J.-P. Clairbois d a CSTB, 24 rue Joseph Fourier, 38400 Saint Martin

More information

Static and dynamic analysis of high-rise building with consideration of two different values of subsoil stiffness coefficients

Static and dynamic analysis of high-rise building with consideration of two different values of subsoil stiffness coefficients Static and dynamic analysis of high-rise building with consideration of two different values of subsoil stiffness coefficients Olga Ivankova 1,*, Janka Kovacikova 1 and Lenka Konecna 1 1 Slovak University

More information

Footfall vibration analysis of a high precision manufacturing facility

Footfall vibration analysis of a high precision manufacturing facility Footfall vibration analysis of a high precision manufacturing facility Jason GAEKWAD 1 ; Yong Keat LEE 1 ; Neil MACKENZIE 1 1 Aurecon Pty Ltd, Australia ABSTRACT High tech manufacturing facilities often

More information

On the use of scaled models in building acoustics

On the use of scaled models in building acoustics On the use of scaled models in building acoustics V. Wittstock a, M. Schmelzer b and C. Kling b a Physikalisch-Technische Bundesanstalt, Bundesallee 100, 38116 Braunschweig, Germany b Physikalisch-Technische

More information

Façade sound insulation of residential houses within Hz

Façade sound insulation of residential houses within Hz Façade sound insulation of residential houses within 5 00 Hz Jukka Keränen, Jarkko Hakala, Valtteri Hongisto Turku University of Applied Sciences, Indoor Environment, Finland. Summary Health-based regulations

More information

Seismic Evaluation of a 1930 Steel Bridge with Lightly Reinforced Concrete Piers

Seismic Evaluation of a 1930 Steel Bridge with Lightly Reinforced Concrete Piers Seismic Evaluation of a 1930 Steel Bridge with Lightly Reinforced Concrete Piers R. Tinawi & M. Leclerc École Polytechnique de Montréal, Canada D. Mitchell McGill University, Canada A. Massad Hydro-Québec,

More information

RESEARCH ON ASSESSMENT OF FOURTH POWER VIBRATION DOSE VALUE IN ENVIRONMENTAL VIBRA- TION CAUSED BY METRO

RESEARCH ON ASSESSMENT OF FOURTH POWER VIBRATION DOSE VALUE IN ENVIRONMENTAL VIBRA- TION CAUSED BY METRO The 2 st International Congress on Sound and Vibration 3-7 July, 204, Beijing/China RESEARCH ON ASSESSMENT OF FOURTH POWER VIBRATION DOSE VALUE IN ENVIRONMENTAL VIBRA- TION CAUSED BY METRO Yiqian Yang,

More information

The Effects of Building Parameters on the Modal Displacement Shapes of Tall Buildings

The Effects of Building Parameters on the Modal Displacement Shapes of Tall Buildings The Effects of Building Parameters on the Shapes of Tall Buildings Massoud Sofi, James Helal, Elisa Lumantarna, Colin Duffield, Priyan A. Mendis ) Department of Infrastructure Engineering, The University

More information

KINETICS NOISE CONTROL TEST REPORT #AT001021B

KINETICS NOISE CONTROL TEST REPORT #AT001021B KINETICS NOISE CONTROL TEST REPORT #AT001021B KINETICS NOISE CONTROL PRODUCTS: o ICW ACOUSTICAL RATINGS: o STC 76 o IIC 62 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B3463.13 KINETICS DRAWING NUMBER:

More information

Vibro-acoustic performance of different steel studs in doubleleaf walls by Finite Element analysis

Vibro-acoustic performance of different steel studs in doubleleaf walls by Finite Element analysis Vibro-acoustic performance of different steel studs in doubleleaf walls by Finite Element analysis Item type Authors Citation Publisher Journal Article Nguyen, Van Bac; Morgan, Tertia; English, Martin;

More information

ENGINEERING MECHANICS 2012 pp Svratka, Czech Republic, May 14 17, 2012 Paper #141 SHORT-SPAN RAILWAY COMPOSITE BRIDGES:TEST AND RATING

ENGINEERING MECHANICS 2012 pp Svratka, Czech Republic, May 14 17, 2012 Paper #141 SHORT-SPAN RAILWAY COMPOSITE BRIDGES:TEST AND RATING . 18 m 2012 th International Conference ENGINEERING MECHANICS 2012 pp. 109 116 Svratka, Czech Republic, May 14 17, 2012 Paper #141 SHORT-SPAN RAILWAY COMPOSITE BRIDGES:TEST AND RATING J. Benčat * Abstract:

More information

KINETICS NOISE CONTROL TEST REPORT #AT001067

KINETICS NOISE CONTROL TEST REPORT #AT001067 KINETICS NOISE CONTROL TEST REPORT #AT001067 KINETICS NOISE CONTROL PRODUCTS: o FLM- NEOPRENE PAD ACOUSTICAL RATINGS: o STC 69 o IIC 61 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA

More information

Use of ISO measurement uncertainty guidelines to determine uncertainties in noise & vibration predictions and design risks

Use of ISO measurement uncertainty guidelines to determine uncertainties in noise & vibration predictions and design risks Use of ISO measurement uncertainty guidelines to determine uncertainties in noise & vibration predictions and design risks P. Karantonis, C. Weber Renzo Tonin & Associates, Surry Hills, NSW, Australia

More information

Jib Crane Analysis Using FEM

Jib Crane Analysis Using FEM ISSN 295-1621 Jib Crane Analysis Using FEM #1 S. S. Kiranalli, #2 N.U. Patil #1Department of Mechanical Engineering, Trinity Polytechnic, Pune ABSTRACT In this paper the analysis of Free Standing Jib Crane

More information

Evidence of Performance Joint sound reduction of filling material

Evidence of Performance Joint sound reduction of filling material Evidence of Performance Test Report No. 13-002455-PR01 (PB Z6-K02-04-en-01) ift Rosenheim 13.09.2013 Client Soudal N. V. Everdongenlaan 18-20 2300 Turnhout Belgium Product Designation Thickness of sealant

More information

NOISE REDUCTION METHODS FOR WALL GAS BOILERS SUMMARY INTRODUCTION

NOISE REDUCTION METHODS FOR WALL GAS BOILERS SUMMARY INTRODUCTION NOISE REDUCTION METHODS FOR WALL GAS BOILERS Andrea NICOLINI Università degli Studi di Perugia, Dipartimento di Ingegneria Industriale, Via G. Duranti 67, 06125 Perugia, ITALY SUMMARY Noise emissions reduction

More information

Research Group VISIBLE. Axis 1. Interaction between vehicle and infrastructure

Research Group VISIBLE. Axis 1. Interaction between vehicle and infrastructure Research Group VISIBLE Axis 1 Interaction between vehicle and infrastructure Contents Topics addressed in Axis 1 French entities involved Activities Topics addressed in Axis 1 Vehicle / Infrastructure

More information

Fatigue cracks induced by traffic loading on steel bridges' slender orthotropic decks

Fatigue cracks induced by traffic loading on steel bridges' slender orthotropic decks Fatigue cracks induced by traffic loading on steel bridges' slender orthotropic decks R.C. Battista&M.S. Pfeil., C.f. Abstract Both static and dynamic problems of contact pressures and interaction between

More information

Measurement of Airborne & Impact Sound Insulation. University of Durham, Pavilion H, Howlands Farm, Durham.

Measurement of Airborne & Impact Sound Insulation. University of Durham, Pavilion H, Howlands Farm, Durham. FAO: CARL SUTCLIFFE noise.co.uk noise.co.uk Ltd Report No U20 Measurement of Airborne & Impact Sound Insulation University of Durham, Pavilion H, Howlands Farm, Durham. For: The Concrete Centre 9/9/2005

More information

STRUCTURE-BORNE SOUND PROPAGATION ACROSS A DOUBLE LEAF TIMBER-FRAME WALL

STRUCTURE-BORNE SOUND PROPAGATION ACROSS A DOUBLE LEAF TIMBER-FRAME WALL STRUCTURE-BORNE SOUND PROPAGATION ACROSS A DOUBLE LEAF TIMBER-FRAME WALL Fabian Schöpfer, Andreas R. Mayr, Ulrich Schanda Laboratory for Sound Measurement LaSM, University of Applied Sciences Rosenheim,

More information

ASSESSMENT OF INWARD TRAFFIC NOISE IMPACT AT RESIDENTIAL DEVELOPMENT, WONDERFUL BARN, LEIXLIP, CO. KILDARE

ASSESSMENT OF INWARD TRAFFIC NOISE IMPACT AT RESIDENTIAL DEVELOPMENT, WONDERFUL BARN, LEIXLIP, CO. KILDARE ASSESSMENT OF INWARD TRAFFIC NOISE IMPACT AT RESIDENTIAL DEVELOPMENT, WONDERFUL BARN, LEIXLIP, CO. KILDARE Technical Report Prepared For Ardstone Capital Ltd. 48 Fitzwilliam Square Dublin Technical Report

More information

Hive Acoustic Report.

Hive Acoustic Report. Hive Acoustic Report www.connection.uk.com Introduction An acoustic report of the equivalent sound absorption area of selected Connection products carried out by AIRO Acoustics Laboratory. The original

More information

Guide to evaluation of human exposure to vibration in buildings

Guide to evaluation of human exposure to vibration in buildings BRITISH STANDARD Guide to evaluation of human exposure to vibration in buildings Part 1: Vibration sources other than blasting ICS 13.160 NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT

More information

CONSIDERATIONS REGARDING IMPACT SOUND INSULATION PERFORMANCES OF DIFFERENT FLOOR MATERIALS

CONSIDERATIONS REGARDING IMPACT SOUND INSULATION PERFORMANCES OF DIFFERENT FLOOR MATERIALS JAES_1(14)_1_2011 TAMAS-GAVREA D.R. et all, pp.111-116 SECTION Civil Engineering and Installations CONSIDERATIONS REGARDING IMPACT SOUND INSULATION PERFORMANCES OF DIFFERENT FLOOR MATERIALS TĂMAŞ-GAVREA

More information

The Concrete Centre Hospital Floor Vibration Study Comparison of Possible Hospital Floor Structures With Respect To NHS Vibration Criteria Black

The Concrete Centre Hospital Floor Vibration Study Comparison of Possible Hospital Floor Structures With Respect To NHS Vibration Criteria Black Hospital Floor Vibration Study Comparison of Possible Hospital Floor Structures With Respect To NHS Vibration Criteria Black Comparison of Possible Hospital Floor Structures With Respect To NHS Vibration

More information

VIBRATION FROM LIVE TRAINS. Tuesday, 10 June 2014

VIBRATION FROM LIVE TRAINS. Tuesday, 10 June 2014 VIBRATION FROM LIVE TRAINS Tuesday, 10 June 2014 1 QUALITY CONTROL PROCESS 2 TWAO VIBRATION OBLIGATIONS QUALITY CONTROL PROCESS Network Rail Local Planning Authority Network Rail appoint specialist designer

More information

CHAPTER 3 IMPROVEMENT OF DYNAMIC CHARACTERISTICS OF CUTTING TOOL SYSTEM USING VISCOELASTIC DAMPER

CHAPTER 3 IMPROVEMENT OF DYNAMIC CHARACTERISTICS OF CUTTING TOOL SYSTEM USING VISCOELASTIC DAMPER 44 CHAPTER 3 IMPROVEMENT OF DYNAMIC CHARACTERISTICS OF CUTTING TOOL SYSTEM USING VISCOELASTIC DAMPER This chapter introduces a novel design for turning tool holder assembly with enhanced damping capability.

More information

VIBRATION OF BUILDINGS LOCATED IN RAILWAY STATION AREA

VIBRATION OF BUILDINGS LOCATED IN RAILWAY STATION AREA 3 rd International Conference on Experiments/Process/System Modeling/Simulation & Optimization 3 rd IC-EpsMsO Athens, 8-11 July, 2009 IC-EpsMsO VIBRATION OF BUILDINGS LOCATED IN RAILWAY STATION AREA Jan

More information

Application of experimental modal testing for estimating dynamic properties of structural components

Application of experimental modal testing for estimating dynamic properties of structural components University of Wollongong Research Online Faculty of Engineering - Papers (Archive) Faculty of Engineering and Information Sciences 2005 Application of experimental modal testing for estimating dynamic

More information

Noise measurement and mitigation for urban building foundation excavation

Noise measurement and mitigation for urban building foundation excavation PROCEEDINGS of the 22 nd International Congress on Acoustics Challenges and Solutions in Acoustical Measurement and Design: Paper ICA2016-552 Noise measurement and mitigation for urban building foundation

More information

Rating of Sound Insulation of Wall Impact Sounds in Buildings. Shih-Pin Huang and Rong-Ping Lai. Reprinted from JOURNAL OF BUILDING ACOUSTICS

Rating of Sound Insulation of Wall Impact Sounds in Buildings. Shih-Pin Huang and Rong-Ping Lai. Reprinted from JOURNAL OF BUILDING ACOUSTICS Rating of Sound Insulation of Wall Impact Sounds in Buildings by Shih-Pin Huang and Rong-Ping Lai Reprinted from JOURNAL OF BUILDING ACOUSTICS Volume 13 Number 2 06 MULTI-SCIENCE PUBLISHING CO. LTD. 5

More information

SEISMIC SOIL-STRUCTURE INTERACTION (SSI) EFFECTS FOR A DIFFERENT TYPE OF BUILDINGS IN DENSE URBAN AREA

SEISMIC SOIL-STRUCTURE INTERACTION (SSI) EFFECTS FOR A DIFFERENT TYPE OF BUILDINGS IN DENSE URBAN AREA SEISMIC SOIL-STRUCTURE INTERACTION (SSI) EFFECTS FOR A DIFFERENT TYPE OF BUILDINGS IN DENSE URBAN AREA Ovidiu BOGDAN 1, Dan M. GHIOCEL 2 and Dan CRETU 3 ABSTRACT The paper presents the results of a project

More information

KINETICS NOISE CONTROL TEST REPORT #AT001049

KINETICS NOISE CONTROL TEST REPORT #AT001049 KINETICS NOISE CONTROL TEST REPORT #AT001049 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o STC 53 o IIC 27 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA o B-3463.1

More information

Open Access Seismic Resistance and Damping Model Test and Numerical Simulation of Highway Tunnel

Open Access Seismic Resistance and Damping Model Test and Numerical Simulation of Highway Tunnel Send Orders for Reprints to reprints@benthamscience.ae The Open Civil Engineering Journal, 2015, 9, 673-681 673 Open Access Seismic Resistance and Damping Model Test and Numerical Simulation of Highway

More information

Low-frequency noise incl. infrasound from wind turbines and other sources

Low-frequency noise incl. infrasound from wind turbines and other sources Low-frequency noise incl. infrasound from wind turbines and other sources Lorenz HERRMANN 1 ; Ulrich RATZEL 2 ; Otto BAYER 3, Klaus-Georg KRAPF 1, Martin HOFFMANN 3, Janosch BLAUL 1, Clemens MEHNERT 3

More information

STATISTICAL ENERGY ANALYSIS OF A HIGH SPEED ELEVATOR CAB AND FRAME

STATISTICAL ENERGY ANALYSIS OF A HIGH SPEED ELEVATOR CAB AND FRAME FIFTH INTERNATIONAL CONGRESS ON SOUND w DECEMBER 15-18, 1997 ADELAIDE, SOUTH AUSTRALIA AND VIBRATION STATISTICAL ENERGY ANALYSIS OF A HIGH SPEED ELEVATOR CAB AND FRAME Charles Coffen Dr. Larry Hardin United

More information

CAN THE IMPACT SOUND IMPROVEMENT OF FLOOR COVERINGS BE MEASURED ON A WOODEN MOCK UP INSTEAD OF A TIMBER JOIST FLOOR?

CAN THE IMPACT SOUND IMPROVEMENT OF FLOOR COVERINGS BE MEASURED ON A WOODEN MOCK UP INSTEAD OF A TIMBER JOIST FLOOR? CAN THE IMPACT SOUND IMPROVEMENT OF FLOOR COVERINGS BE MEASURED ON A WOODEN MOCK UP INSTEAD OF A TIMBER JOIST FLOOR? Pacs reference: IP, RBA-CIB Scholl, Werner Physikalisch-Technische Bundesanstalt Fachlabor

More information

Spatial variability effects of the seismic action in Cable-Stayed Bridges and modelling techniques

Spatial variability effects of the seismic action in Cable-Stayed Bridges and modelling techniques Spatial variability effects of the seismic action in Cable-Stayed Bridges and modelling techniques Eleftheria Efthymiou, Alfredo Camara City University London, London, UK11 Abstract This paper presents

More information

Evidence of Performance Airborne sound insulation of building components

Evidence of Performance Airborne sound insulation of building components Evidence of Performance Airborne sound insulation of building components Test Report No. 14-000251-PR01 (PB Z09-H01-04-en-02) Client Product Designation PRESS GLASS SA Nowa Wies Kopalniana 9 42-262 Poczesna

More information

The Optimization of a Wooden Floor Design Based on Validated Finite Element Models

The Optimization of a Wooden Floor Design Based on Validated Finite Element Models The Optimization of a Wooden Floor Design Based on Validated Finite Element Models Jeffrey MAHN 1 ; Carl HOPKINS 2 ; Marios FILIPPOUPOLITIS 2 ; Ulrich SCHANDA 3 ; Raphael VÖLTL 3 ; Luboš KRAJČI 4 1 National

More information

KINETICS NOISE CONTROL TEST REPORT #AT001052

KINETICS NOISE CONTROL TEST REPORT #AT001052 KINETICS NOISE CONTROL TEST REPORT #AT001052 KINETICS NOISE CONTROL PRODUCTS: o ISOMAX CLIPS ACOUSTICAL RATINGS: o STC 66 o IIC 44 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA

More information

Application of Isolation Technology in High-voltage Electrical Equipments

Application of Isolation Technology in High-voltage Electrical Equipments Application of Isolation Technology in High-voltage Electrical Equipments WEN Bo 1 AND ZHANG Jun-fa 2, NIU Di-tao 3 1 Doctoral Candidate, Dept. of Civil Engineering, Xi an University of Architecture &

More information

Int. Journal for Housing Science, Vol.34, No.2 pp , 2010 Published in the United States

Int. Journal for Housing Science, Vol.34, No.2 pp , 2010 Published in the United States Int. Journal for Housing Science, Vol.34, No. pp. 117-16, 010 Published in the United States SOUND TRANSMISSION PERFORMANCE OF COCONUT FIBER IMPREGNATED FERRO-CEMENT AND WOOD WOOL PANELS ON THE LOSS FACTOR

More information

REPORT ON VIBRATION MONITORING GRANGEGORMAN CAMPUS CENTRAL & EAST QUAD, DUBLIN 7

REPORT ON VIBRATION MONITORING GRANGEGORMAN CAMPUS CENTRAL & EAST QUAD, DUBLIN 7 Glenside Environmental Unit 18 Great Island Industrial Estate Ballincollig, Cork T: 021-4810016 F: 021-4875183 e: info@glenenv.ie W: www.glenenv.ie REPORT ON VIBRATION MONITORING AT GRANGEGORMAN CAMPUS

More information

Study on human reactions to vibration from blasting activities nearby dwellings

Study on human reactions to vibration from blasting activities nearby dwellings 12 th ICBEN Congress on Noise as a Public Health Problem Study on human reactions to vibration from blasting activities nearby dwellings Iiris Turunen-Rindel 1, Ronny Klæboe 2, Karin Norén-Cosgriff 3 1

More information

Proceedings of the ASME nd International Conference on Ocean, Offshore and Arctic Engineering OMAE2013 June 9-14, 2013, Nantes, France

Proceedings of the ASME nd International Conference on Ocean, Offshore and Arctic Engineering OMAE2013 June 9-14, 2013, Nantes, France Proceedings of the ASME 2013 32nd International Conference on Ocean, Offshore and Arctic Engineering OMAE2013 June 9-14, 2013, Nantes, France OMAE2013-10684 A COMPARISON STUDY OF PRESSURE VESSEL DESIGN

More information

Acoustics Management Predictions Measurements Analysis. Rail vehicle acoustics. Know-how and experience in vibro-acoustics.

Acoustics Management Predictions Measurements Analysis. Rail vehicle acoustics. Know-how and experience in vibro-acoustics. Acoustics Management Predictions Measurements Analysis Rail vehicle acoustics Know-how and experience in vibro-acoustics www.muellerbbm.com Our competence The engineering company Müller-BBM is active in

More information

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE Copyright SFA - InterNoise 2000 1 inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering 27-30 August 2000, Nice, FRANCE I-INCE Classification: 8.6 SOUND INSULATION

More information

OPERATIONAL MODAL ANALYSIS FOR DAMAGE DETECTION OF A MASONRY CONSTRUCTION

OPERATIONAL MODAL ANALYSIS FOR DAMAGE DETECTION OF A MASONRY CONSTRUCTION OPRATIONAL MODAL ANALYSIS FOR DAMAG DTCTION OF A MASONRY CONSTRUCTION Luís F. Ramos, Dep. Civil ngineering, University of Minho, Portugal Alfredo Campos Costa, LNC, Portugal Paulo B. Lourenço, Dep. Civil

More information

LASD Coatings Optimized for Damping of Aluminum Intensive Vehicle Bodies

LASD Coatings Optimized for Damping of Aluminum Intensive Vehicle Bodies Global Automotive Lightweight Materials August 18-20, 2015 LASD Coatings Optimized for Damping of Aluminum Intensive Vehicle Bodies Ion Pelinescu, Ph.D. NVH-Acoustics Engineering Associate Coatings Innovation

More information

SELWYN PRIMARY SCHOOL, LONDON ENVIRONMENTAL NOISE SURVEY

SELWYN PRIMARY SCHOOL, LONDON ENVIRONMENTAL NOISE SURVEY 202 Uxbridge Road London W12 7JP Tel: +44(0)203 475 2280 Fax: +44(0)203 475 2281 info@clementacoustics.co.uk www.clementacoustics.co.uk SELWYN PRIMARY SCHOOL, LONDON ENVIRONMENTAL NOISE SURVEY Report 8991-ENS-03

More information

Comparison of the effect of different sleeper typologies and track layout on railway vibrations

Comparison of the effect of different sleeper typologies and track layout on railway vibrations 2241 Comparison of the effect of different sleeper typologies and track layout on railway vibrations Abstract The last years, ground vibrations have become an important study field due to the increase

More information

Evidence of Performance Joint sound reduction of filling material

Evidence of Performance Joint sound reduction of filling material Evidence of Performance Test Report No. 13-002455-PR02 (PB-K05-04-en-01) ift Rosenheim 10.09.2013 Client Soudal N. V. Everdongenlaan 18-20 2300 Turnhout Belgium Product Designation Density Special features

More information

DYNAMIC CHARACTERISTICS OF A R/C BUILDING OF FIVE STORIES BASED ON MICROTREMOR MEASUREMENTS AND EARTHQUAKE OBSERVATIONS

DYNAMIC CHARACTERISTICS OF A R/C BUILDING OF FIVE STORIES BASED ON MICROTREMOR MEASUREMENTS AND EARTHQUAKE OBSERVATIONS DYNAMIC CHARACTERISTICS OF A R/C BUILDING OF FIVE STORIES BASED ON MICROTREMOR MEASUREMENTS AND EARTHQUAKE OBSERVATIO 5 Yasutaka IRIE And Kazuya NAKAMURA SUMMARY This paper describes the dynamic characteristics

More information

FEM UPDATING OF THE HERITAGE COURT BUILDING STRUCTURE

FEM UPDATING OF THE HERITAGE COURT BUILDING STRUCTURE FEM UPDATING OF THE HERITAGE COURT BUILDING STRUCTURE Carlos E. Ventura Rune Brincker Eddy Dascotte Palle Andersen Dept. of Civil Engineering Dept. of Building Technology and Dynamic Design Solutions n.v.

More information

DETERMINING THE STATIC STIFFNESS OF STRUCTURES: A COMPARISON OF METHODS INVOLVING MEASUREMENT OF DISPLACEMENT AND MEASUREMENT OF ACCELERATION RESPONSE

DETERMINING THE STATIC STIFFNESS OF STRUCTURES: A COMPARISON OF METHODS INVOLVING MEASUREMENT OF DISPLACEMENT AND MEASUREMENT OF ACCELERATION RESPONSE DETERMINING THE STATIC STIFFNESS OF STRUCTURES: A COMPARISON OF METHODS INVOLVING MEASUREMENT OF DISPLACEMENT AND MEASUREMENT OF ACCELERATION RESPONSE Abstract Aaron Miller 1 and Dominik Duschlbauer 1

More information

Some Structural Design Issues of the 14-Storey Timber Framed Building Treet in Norway

Some Structural Design Issues of the 14-Storey Timber Framed Building Treet in Norway COST Action FP1004 Final Meeting 15 April 17 April 2015 Lisbon, Portugal Some Structural Design Issues of the 14-Storey Timber Framed Building Treet in Norway Kjell A. Malo, NTNU Norwegian Univ. Science

More information