IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report. Duquesne University Rockwell Hall. Duquesne University smba
|
|
- Scott Holland
- 6 years ago
- Views:
Transcription
1 IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report Duquesne University Rockwell Hall For: By: Duquesne University smba Craig E. Stevenson James Construction Date: December 15, 2014 Page 1 of 13
2 Table of Contents 1 Location, Site & Climate data Building Form, Layout & Zoning Materials & Constructions Space use classification and schedules Lighting HVAC Systems Results Page 2 of 13
3 1 Location, Site & Climate data City Country Latitude Longitude Altitude Time Zone (+GMT) Daylight saving time adjustment 1 From: To: Ground Reflectance 0.2 Terrain Type Wind Exposure Annual hourly climate data file 1.1 Climate Pittsburgh United States of America N W 1,204.1 feet -5.0 hours March October City Normal USA_PA_Pittsburgh.Intl.AP _TMY3.epw Table 1: Summary Location and Site Data ASHRAE Climate Zone 5A Annual percentile for Heating loads design weather 99.60% Annual percentile for Cooling loads design weather 0.40% Heating Loads Weather data: Outdoor winter design temperature Cooling loads weather data: Max. Dry-Bulb Max. Wet-Bulb Table 2: Climate Data Summary F 85.08ºF 66.51ºF Figure 1: Dry Bulb / Wet Bulb Summary Page 3 of 13
4 Figure 2: Climate metrics chart Figure 3: Temperature distribution chart (in Hrs.) Page 4 of 13
5 2 Building Form, Layout & Zoning 2.1 Summary Architectural floor plans have been used to develop the 3D Virtual Environment model. The drawing names are Building Record Drawings and the digital format is Adobe PDF. The document set includes; A1 Sub-Ground Floor Plan dated 12/13/10, A2 Concourse Level Floor Plan dated 12/13/10, A3 Basement Floor Plan dated 12/13/10, A4 Fifth Floor Plan dated 12/7/10, A5 Second Floor Plan dated 12/7/10, A6 Third Floor Plan dated 12/9/10, A7 Fourth Floor Plan dated 12/9/10, A8 Fifth Floor Plan dated 12/9/10, A9 Sixth Floor Plan dated 12/9/10, A10 Seventh Floor Plan dated 12/9/10, A11 Eighth Floor Plan dated 12/9/10, A12 Ninth Floor Plan dated 12/9/10, A13 Tenth Floor Plan dated 12/9/10, and A14 Roof Plan dated 12/9/10. Model geometry is represented as internal volumes. 2.2 Model View (no surroundings) Figure 4: Model view Perspective (no surroundings) 2.3 North Elevation Model View Figure 5: Model view North elevation Page 5 of 13
6 2.4 South Elevation Model View Figure 6: Model view South elevation 2.5 East Elevation Model view Figure 7: Model View East elevation Page 6 of 13
7 2.6 West Elevation Model View Figure 8: Model view West elevation 2.7 Floor / Room / Zone Summary Floor Floor Area (ft²) Deck to Deck (ft) Exterior Walls (ft²) Volume (ft³) Sub-Ground 12, , , Concourse 16, , , Basement 20, , , First 12, , , Second 10, , , Third 10, , , Fourth 10, , , Fifth 10, , , Sixth 10, , , Seventh 10, , , Eighth 10, , , Ninth 10, , , Tenth 10, , , Total: 156, , ,047, Table 3: Model Area Summary Functional Area analysis is incomplete. Rockwell Hall consists of functional areas for Classroom, Office, and Core functions. Occupant interviews are required to assess Functional Areas. Functional Area Floor Area (ft²) Classroom: Unknown Sf Office: Unknown Sf Core Unknown Sf Total 156, Sf Table 3A: Energy Star Portfolio Manager, Gross Square Feet Page 7 of 13
8 3 Materials & Constructions 3.1 External Constructions Figure 9: External Constructions Chart ID Category Description Data source U value (Btu/h ft² F) Thickness (in) STD_CEI L Internal Ceiling/Floor 2013 Internal Ceiling/Floor Generic STD_DO OR Door 2013 Door Generic STD_EXT W External Window 2013 External Window Generic STD_FLO 1 Ground/Exposed Floor 2013 Exposed Floor Generic STD_INT W Internal Window 2013 Internal Window Generic STD_PA R2 Internal Partition Internal Partition RH Internal Gyp Wall Generic STD_PA RT Internal Partition Internal Partition RH Internal Masonry Generic STD_RO OF Roof 2013 Roof Generic WALL External Wall External Wall RH Ground Wall Generic WALL1 External Wall External Wall RH Above Ground Wall Generic Figure 10: Constructions Thermal Values Page 8 of 13
9 4 Space use classification and schedules 4.1 Building Schedules Building Schedules analysis is incomplete. Rockwell Hall IES VE Model consists of ASHRAE 90.1 data for gains and profiles. Occupant interviews are required to assess Building Schedules. Functional Area Lighting & Plug Load / Occupancy Daily Profile Weekly Profile Classroom: Day 07:00-22:00 week 07:00-22:00 Office: Day 07:00-22:00 week 07:00-22:00 Core: Day 07:00-22:00 week 07:00-22:00 With Modulating Value With Modulating Value Lighting & Plug Load Profile Weekday Saturday Occupancy Profile Weekday Saturday Table 4: Lighting & Plug Load / Occupancy Profiles Page 9 of 13
10 5 Lighting The model is using the Space by space lighting power calculation method. Lighting power densities have been calculated using ASHRE 90.1 maximum sensible gain of watts per square foot values Power (kbtu/h) Sun Mon Tue Wed Thu Fri Sat Sun Date: Sun 08/Jun to Sat 14/Jun Total lights energy: (rockwell.aps) Figure 11: Typ. Weekly Lighting Loads 6 HVAC Systems 6.1 Proposed Systems HVAC Systems analysis is incomplete. Rockwell Hall IES VE Model consists of ASHRAE 90.1 data for systems. Systems survey is required to complete proposed systems setup. James Construction created a simple systems network for the building to complete the baseline simulation analysis, including the following Heating and Cooling information. Figure 12: Heating System Configuration in IES <VE> Systems Analysis Tool APHVAC Page 10 of 13
11 Figure 13: Cooling System Configuration in IES <VE> Systems Analysis Tool APHVAC 6.2 Service Hot Water Service Hot Water Systems analysis is incomplete. Rockwell Hall IES VE Model consists of ASHRAE 90.1 data for systems. Systems survey is required to complete proposed systems setup. James Construction created a simple systems network for the building to complete the baseline simulation analysis, including the following Domestic Hot Water information. Figure 14: Domestic Hot Water System Configuration in IES <VE> Systems Analysis Tool APHVAC Page 11 of 13
12 7 Results 7.1 Total Building Energy Usage Inputs (5 Yr. Avg.) Building Energy Usage analysis is incomplete. 7.2 Total Building Energy Usage- Model Outputs (1 Calendar Yr.) Figure 15: Gas/Electric Consumption (Model) Figure 16: Electric Consumption Detail (Model) Page 12 of 13
13 EUI Figure 17: Total Energy Detail (Model) Page 13 of 13
Oklahoma University Children s Medical Office Building
Oklahoma University Children s Medical Office Building Oklahoma City, O.K., BAE Advisor: Laura Miller Presentation Outline VRF System Dedicated Outdoor Air System Evaluation VRF Indoor Units Design Criteria
More informationThe Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma
LEED Green Building Certification The purpose of the LEED Green Building Rating is to provide a national standard that aims to improve environmental, health and economic performance of buildings using
More informationBullitt Center s Energy Performance
Bullitt Center s Energy Performance Introduction In 2007 Congress created a Zero Net Energy Commercial Buildings Initiative with a goal of achieving a market transition to Zero Net Energy for new commercial
More informationTEA Facility Data Survey
TEA Facility Data Survey Date: Facility Setup Printed Version 1. *Facility Name Click here type in name. Contact: Click here to enter text. 2. CRM Click here to enter CRM. Phone: Click here to enter text.
More informationIES <Virtual Environment> Live e-training. Trainee notes. VE-Gaia. SI Units. Version 6.4
IES Live e-training Trainee notes VE-Gaia SI Units Version 6.4 Introduction These training notes are to be used in conjunction with your VE-Gaia training. In this training session
More informationCOMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program
COMMERCIAL LOAD ESTIMATING Load Estimating Level 3: Block and Zone Loads Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design,
More informationLevel II - Whole Building Interval Electric Data with Tenant Plug Load System
Level II - Whole Building Interval Electric Data with Tenant Plug Load System 1. Overview and Scope This specification describes the capabilities and data requirements for equipment or service providers
More informationIII. Economics. A. General Page III-2 B. Initial Capital Costs Page III-3 C. Life Cycle Costs Page III-4
III. Economics Use of AERCON resulted in 3-month schedule reduction on this $23 million, 245,000-sq. ft. Residence Hall Complex. A. General Page III-2 B. Initial Capital Costs Page III-3 C. Life Cycle
More informationBuilding Energy Efficiency Analysis for a High School
Building Energy Efficiency Analysis for a High School (LG Multi V III VRF System) School Building Air-Conditioning Engineering Study VRF-ES-BH-002-US 013A30 Executive Summary Contents Executive Summary...2
More informationBuilding Performance Evaluation Guide
Building Performance Evaluation Guide Version 1.6 April 2012 1. Schematic Design & Design Development Phase Requirements Whole building energy simulation shall be used to determine the basis for the designed
More informationActivity 2.2.3A Heat Loss and Gain (Revised)
Activity 2.2.3A Heat Loss and Gain (Revised) Introduction When the winter design temperature is below 60ºF, the International Residential Code requires a dwelling to have heating facilities capable of
More informationEnergy Savings Audit
Energy Savings Audit PREPARED FOR Steve Bennett Eileen Horn City of Lawrence ASSESSMENT SITE City of Lawrence Arts Center 940 new Hampshire St. Lawrence, KS 66044 ASSESSMENT PERFORMED BY P1 Group Inc 16210
More informationCreation of a Prototype Building Model of College and University Building
Creation of a Prototype Building Model of College and University Building Y. Ye, G. Wang and W. Zuo Department of Civil, Architectural, and Environmental Engineering University of Miami, Coral Gables,
More informationBuilding Energy Efficiency Analysis for a High School
Building Energy Efficiency Analysis for a High School (LG Multi V Water II VRF System) School Building Air-Conditioning Engineering Study VRF-ES-BF-002-US 013A16 Contents Executive Summary...3 Introduction...4
More informationENERGY ANALYSIS AND ENERGY CONSERVATION OPTION FOR THE WAREHOUSE FACILITY AT THE HUMAN SERVICES CENTER COMPLEX DRAFT REPORT.
ESL-TR-86/09-03 ENERGY ANALYSIS AND ENERGY CONSERVATION OPTION FOR THE WAREHOUSE FACILITY AT THE HUMAN SERVICES CENTER COMPLEX DRAFT REPORT Submitted by Mohsen Farzad Dennis O'Neal Prepared For Energy
More informationhow to read an energy model
how to read an energy model Kohler Ronan, LLC is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported
More informationAnalysis of the Energy Savings Potential in K-5 Schools in Hot and Humid Climates. Jeff S. Haberl, Ph.D., P.E.
Analysis of the Energy Savings Potential in K-5 Schools in Hot and Humid Climates Piljae Im Graduate Student Jeff S. Haberl, Ph.D., P.E. Professor Energy Systems Laboratory Texas Engineering Experiment
More informationANNUAL STAKEHOLDER MEETING
ANNUAL STAKEHOLDER MEETING 2015 Technical Reference Manual High Impact C&I Measure Updates July 11, 2014 Presented by the Statewide Evaluation Team: MEETING AGENDA MEETING AGENDA Weather Mapping Lighting
More informationCOMPARISION OF FIVE WINDOW SHADE STRATEGIES
COMPARISION OF FIVE WINDOW SHADE STRATEGIES Yue Liu Karen Kensek USC, School of Architecture Watt Hall #204 Los Angeles, CA, 90089-0291 liuyue@usc.edu kensek@usc.edu ABSTRACT Exterior window shades are
More informationLoad Estimation. Ir. Dr. Sam C. M. Hui Faculty of Science and Technology
SPD4121 HVAC Technology for Plumbing Engineers http://ibse.hk/spd4121/ Load Estimation Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Jul 2016 Contents Basic Concepts
More informationChapter 4. Analysis of Building Energy Performance
Chapter 4 Analysis of Building Energy Performance 128 4.1 Introduction This chapter deals with energy modeling and simulation of the baseline models for the buildings to assess energy performance of the
More informationOcean Discovery Institute: Designing for Zero Net Energy
CASE STUDY Ocean Discovery Institute: Designing for Zero Net Energy How one client used targeted energy analysis to navigate a limited budget and a tight schedule to join the ranks of San Diego s Zero
More informationEnergy Analysis: The Impacts of the Curtain Wall System
Energy Analysis: The Impacts of the Curtain Wall System Executive Summary of Analysis Minor components of a building can have major impacts on the buildings costs to the owner. While initial costs can
More informationSURNA Grow Facility: Systems Comparison - IEA
SURNA Grow Facility: Systems Comparison - IEA May 2016 SURNA Grow Facility This analysis provides the projected energy and associated cost comparison between the Surna proposed facility in comparison to
More informationEnergy Auditing of a Building using Green BIM
Volume 1, Issue 1, July-September, 2013, pp. 07-15, IASTER 2013 www.iaster.com, Online: 2347-2855, Print: 2347-8284 Energy Auditing of a Building using Green BIM 1 Gokulavasan.M, 2 Ramesh Kannan.M 1 PG
More informationPractitioner Modeling Competition
Practitioner Modeling Competition Design and Simulation of a Laboratory Building Building Simulation 2017 Briefing Document IBPSA-USA San Francisco Bay Area Chapter http://www.ibpsa.us/chapter/san-francisco
More informationSample Reports. for. HAP v4.80 Example Problem
Sample Reports for HAP v4.80 Example Problem October, 2013 Carrier Software Systems Copyright 2013 Carrier Corporation, All Rights Reserved Introduction This document contains reports generated using the
More informationN/A. ENERGY STAR Data Verification Checklist. Circle Star Plaza. 1. Review of Whole Property Characteristics. Property & Contact Information
ENERGY STAR Data Verification Checklist N/A ENERGY STAR Score 1 Circle Star Plaza Primary Function: Office Gross Floor Area (ft²): 207,896 Built: 2000 For Year Ending: 03/31/2014 Date Generated: 05/12/2014
More informationEngineering Building No W. 32 nd St. Chicago, IL 60616
CAE 524: Building Enclosure Design Engineering Building No. 1 10 W. 32 nd St. Chicago, IL 60616 November 13, 2013 Performed By: Jay Shetty Firas Putros Gilberto Osornio Table of Contents I) Building and
More informationTHERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE
S447 THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE by Bojan V. ANDJELKOVIĆ *,a, Branislav V. STOJANOVIĆ b, Mladen M. STOJILJKOVIĆ b, Jelena N. JANEVSKI
More informationand LEED Energy and Atmosphere Credits Jean Ascoli, LEED AP BD+C Architect, Energy Specialist
ASHRAE University of Illinois Student Chapter April 20, 2011 Building Energy Efficiency and LEED Energy and Atmosphere Credits Jean Ascoli, LEED AP BD+C Architect, Energy Specialist Building Research Council,
More informationPractitioner Modeling Competition
Practitioner Modeling Competition Design and Simulation of a Laboratory Building Building Simulation 2017 Briefing Document Updated: Feb. 04, 2017 IBPSA-USA San Francisco Bay Area Chapter http://www.ibpsa.us/chapter/san-francisco
More informationARCH-MEDES (I) CONSULTANTS PVT. LTD. Green Park Delhi
Passive & Energy Efficient Design Assistance Report for Proposed Hospital Complex Manipal Health System at Pitampura, New Delhi ARCH-MEDES (I) CONSULTANTS PVT. LTD. Green Park Delhi Prepared By (Low Carbon
More informationTHERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE
Andjelković, V., B.et. al.: Thermal Mass Impact on Energy Performance of A Low, Medium and Heavy S507 THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE by Bojan
More informationFOR DUQUESNE UNIVERSITY, ROCKWELL HALL AN EXISTING BUILDING
FOR DUQUESNE UNIVERSITY, ROCKWELL HALL AN EXISTING BUILDING OVERVIEW Building: Rockwell Hall, Constructed 1958 Building Owner: Duquesne University Location: Pittsburgh, Pennsylvania Building Size: 165,945
More informationMatt Gudorf UCI Energy Manager
Matt Gudorf UCI Energy Manager UNIVERSITY OF CALIFORNIA, IRVINE Comprehensive research university 22,216 Undergraduate Students $330 million sponsored research 27 lab buildings operating 24/7 ~7.5 Million
More informationMODELLING THE IMPACTS OF NEW UK FUTURE WEATHER DATA ON A SCHOOL BUILDING
MODELLING THE IMPACTS OF NEW UK FUTURE WEATHER DATA ON A SCHOOL BUILDING Hu Du, Jerry Edge, Chris Underwood School of Built and Natural Environment, Northumbria University, Newcastle upon Tyne, United
More informationIESVE Compliance for ASHRAE IES Virtual Environment
IESVE Compliance for ASHRAE 90.1 - IES Virtual Environment July 2018 IES Virtual Environment and Compliance with ASHRAE 90.1-2004, 2007, 2010 & 2013; Appendix G, Performance Rating Method and Chapter 11,
More informationCOMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING
COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING ABSTRACT F. Bagheri 1, M. Fakoor 1, B. Young 1, C. Cranswick 1 1 BC Building Science Ltd. 611 Bent
More informationEnergy Assessment Report Clayville Elementary School DRAFT October George Washington Highway, Clayville, RI DRAFT
Report Clayville Elementary School October 2016 3 George Washington Highway, Clayville, RI 02815 Clayville Elementary School Summary of Findings On behalf of the School Building Authority at Rhode Island
More informationStudent Modeling Competition
Student Modeling Competition Design and Simulation of a Laboratory Building Building Simulation 2017 Briefing Document Zahraa Saiyed Ben Brannon Anna Brannon Christina Hopfe Gerhard Zweifel Student Modeling
More informationDemonstration of Load Shifting and Peak Load Reduction with Control of Building Thermal Mass
Demonstration of Load Shifting and Peak Load Reduction with Control of Building Thermal Mass J. E. Braun and T. M. Lawrence, Ray W. Herrick Laboratories, Purdue University C. J. Klaassen and John M. House,
More informationASHRAE Standard 90.1 App G, PHI and PHIUS+
ASHRAE Standard 90.1 App G, PHI and PHIUS+ A NYSERDA Comparative Evaluation Study June 16, 2017 Governor Cuomo s strategy to build a clean, resilient and affordable energy system for all New Yorkers 2
More informationCHIANG MAI HEALTH CARE CENTER Energy Efficiency Study, Chiang Mai, January 19, 2017
CHIANG MAI HEALTH CARE CENTER Energy Efficiency Study, Chiang Mai, January 19, 2017 Unexpected Co., Ltd. EGS-plan (Bangkok) Co.,Ltd. Project location, 18 45'47.2"N / 99 00'40.9 E Chiang Mai Old City Ban
More informationLEED Energy Performance Summary Report
Section 1.1 - General Information Simulation Program: Principle Source: Energy Code Used: Weather File: Climate Zone: New Construction Percent: Existing Renovation Percent: Quantity of Floors: Proposed:
More informationLOGO. Trivium Level II Energy Audit
LOGO Trivium Level II Energy Audit Submission Date: 9/16/2016 Table of Contents 1.0 EXECUTIVE SUMMARY 3 2.0 SITE ENERGY CONSUMPTION 5 3.0 BACKGROUND INFORMATION 6 3.1 Description of the Client 6 3.2 Description
More informationCAE 331/513 Building Science Fall 2017
CAE 331/513 Building Science Fall 2017 November 14, 2017 Heating load calculations Advancing energy, environmental, and sustainability research within the built environment www.built-envi.com Twitter:
More informationBuilding Energy Modeling Professional (BEMP)
ASHRAE beq Program Amanda Bogner President, Energy Studio KU Architectural Engineering Licensed Mechanical Engineer LEED AP BD + C, Certified LEED Reviewer Vice-chair USGBC s EA Technical Advisor Group
More informationImpacts of Increased Outdoor Air Flow Rates on Annual HVAC Energy Costs
Impacts of Increased Outdoor Air Flow Rates on Annual HVAC Energy Costs David Mudarri, U.S. EPA, Indoor Environments Division John D. Hall, ICF Kaiser Consulting Group Eric Werling, ICF Kaiser Consulting
More informationThermal Performance of Toplighting Systems in a Hot and Humid Climate: Thailand
Thermal Performance of Toplighting Systems in a Hot and Humid Climate: Thailand S. Harntaweewongsa, L.O. Beltrán, Ph.D., Texas A&M University Keywords: Abstract: Toplighting, architecture, sustainability,
More informationEnergy Strategies That Work Case Studies
Energy Strategies That Work Case Studies Jean Ascoli, Architect, CEM, Program Director for New Construction Smart Energy Design Assistance Center University of Illinois, Urbana Champaign of Homeland Security
More informationBall State Architecture ENVIRONMENTAL SYSTEMS 1 Grondzik 1. Building Heat Loss
DESIGN HEAT LOSS (part 1) Ball State Architecture ENVIRONMENTAL SYSTEMS 1 Grondzik 1 Building Heat Loss Generally speaking, heat loss occurs in winter or More specifically during any underheated time period*
More informationOPTION 1: PERFORMANCE RATING METHOD
OPTION 1: PERFORMANCE RATING METHOD I confirm that the energy simulation software used for this project has all capabilities described in EITHER section `G2 Simulation General Requirements' in Appendix
More informationJun Luis Fernando Garcia Gonzalez TRANSSOLAR ACADEMY. Passive Power Hospital
Luis Fernando Garcia Gonzalez TRANSSOLAR ACADEMY Passive Power Hospital My Home, Colombia Cota Cundinamarca (Close to the capital city Bogota) Jun 2015 Transsolar Academy 0 My Design 2013 Long Long time
More informationWhite Paper ENVELOPE-FIRST APPROACH TO NET-ZERO ENERGY BUILDINGS
BOULDER CHICAGO NASHVILLE SALT LAKE CITY SAN FRANCISCO SPRINGFIELD, MO WASHINGTON, DC 2540 Frontier Avenue, Suite 100 Boulder, Colorado 80301 303.444.4149 White Paper ENVELOPE-FIRST APPROACH TO NET-ZERO
More informationUniversity of Minnesota Duluth Civil Engineering Building
Energy Data Attachment University of Minnesota Duluth Civil Engineering Building LEED Energy Modeling The energy modeling for LEED NC 2.2 was performed against ASHRAE 9.1-24 Appendix using equest version
More informationStudent Modeling Competition
Student Modeling Competition Design and Simulation of a Laboratory Building Building Simulation 2017 Briefing Document Updated: Feb. 04, 2017 Zahraa Saiyed Ben Brannon Anna Brannon Christina Hopfe Gerhard
More informationReminder: Above-Ground Envelope Heat Loss
good envelope DESIGN HEAT LOSS (part 2) bad envelope Ball State Architecture ENVIRONMENTAL SYSTEMS 1 Grondzik 1 Reminder: Above-Ground Envelope Heat Loss Heat loss through any assembly with air on both
More informationEnergy Saving Analysis of High Performance Commercial Buildings in India
International Journal of Engineering Research and Technology. ISSN 0974-3154 Volume 6, Number 5 (2013), pp. 605-610 International Research Publication House http://www.irphouse.com Energy Saving Analysis
More informationScienceDirect. Simulation based mixed mode building design
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 00 (2016) 000 000 www.elsevier.com/locate/procedia 5th International Conference on Advances in Energy Research, ICAER 2015, 15-17
More informationTHE COLLEGE OF WILLIAM & MARY MA STER PLA N
THE COLLEGE OF WILLIAM & MARY MA STER PLA N PU BLIC C LASSR OOM AN ALYSIS 10 April 2014 Distribution of Weekly Scheduled Contact Hours (WSCH) Other (conf., office, etc.) 4% No Space 5% Non-public Classrooms
More information681: Environmentally Responsive Architecture; Passive Design for School in Southern India
681: Environmentally Responsive Architecture; Passive Design for School in Southern India Varun Kohli* Architectural Association School of Architecture, London, UK * varun.kohli@som.com Abstract This paper
More informationSample Reports. for. HAP v4.90 Example Problem
Sample Reports for HAP v4.90 Example Problem December, 2014 Carrier Software Systems Copyright 2014 Carrier Corporation, All Rights Reserved Introduction This document contains reports generated using
More informationequest Home Energy Model ME 514 ~ HVAC Sean Rosin University of Idaho/Boise State University Spring 2016
equest Home Energy Model ME 514 ~ HVAC Sean Rosin University of Idaho/Boise State University Spring 2016 ABSTRACT There is a growing need for energy modeling as commercial buildings get more and more complex.
More informationHIGH POINT NEIGHBORHOOD CENTER ENERGY MODELING REPORT CONTENTS. Goals 2. Method 2. Acknowledgements 3. Challenges and Standards 3. equest Results 4-13
Community Design Center HIGH POINT NEIGHBORHOOD CENTER ENERGY MODELING REPORT CONTENTS Goals 2 Method 2 Acknowledgements 3 Challenges and Standards 3 equest Results 4-13 Summary Table 14 Comments 15 Going
More informationREC HVAC Load Calculations
HVAC Load Calculations for Builder Bob 200 Hawk Rd AnyTown NY, 11788 Prepared By: Glenn Hooper 3771 Nsconset Hwy Suite 101A S. Setauket NY 11720 751-7911 Wednesday, August 26, 2009 Centereach, NY 11720
More informationASHRAE s LowDown Showdown
ASHRAE s LowDown Showdown Presented to the Building Energy Simulation Forum 14 February 2018 James Cullin, PhD, PE Overview Project Approach Existing Building Modeling/Calibration Proposed Design Proposed
More informationThe energy benefits of View Dynamic Glass
Workplace demonstration Energy monitoring over a period of 12 months resulted in the commercial office room installed with View Dynamic Glass saving 39 percent of the total energy consumed compared to
More informationTechnical Report 2. Bellevue Ambulatory Care Pavilion New York, NY. Building and Plant Energy Analysis
Technical Report 2 Building and Plant Energy Analysis Bellevue Ambulatory Care Pavilion New York, NY Prepared for: Dr. Jelena Srebric, PhD Department of Architectural Engineering The Pennsylvania State
More informationENERGY MODELING GUIDELINES. D. Section Building Automation and Control System Guidelines
018130 ENERGY MODELING GUIDELINES PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 018110 Green Building Guidelines B. Section 230000 Basic HVAC Requirements C. Section 230540 Laboratories D. Section 230900
More informationModeling Energy Consumption Effects of Glazing
Modeling Energy Consumption Effects of Glazing Daniel Lu 12/7/2012 Table of Contents Introduction... 3 Design Options... 5 Option 1... 5 Option 2... 5 Preliminary Energy Simulation... 7 Objectives... 7
More informationBuilding Energy Analysis for a Multi-Family Residential Building (Multi V III VRF Heat-Pump System)
Building Energy Analysis for a Multi-Family Residential Building (Multi V III VRF Heat-Pump System) Residential-Building Energy-Modeling Engineering Study VRF-ES-BH-001-US 012E03 Executive Summary Contents
More informationThermal Thermal Applications Category Version 6.4. Integrated Environmental Solutions
Thermal Thermal Applications Category Version 6.4 Integrated Environmental Solutions Contents 1. What is the Thermal Applications Category?... 4 1.1. Compliance View... 4 1.2. Apache
More informationIntroduction to Outcome-Based Energy Codes. New Buildings Institute
Introduction to Outcome-Based Energy Codes Mark Frankel Mark Frankel New Buildings Institute Definitions Prescriptive Specific discrete components or features required (R-values, system efficiency ratings,
More informationDISCOVERIES AT NET ZERO. Michael Leckman Diamond Schmitt Architects Chris Piche Integral Group
DISCOVERIES AT NET ZERO Michael Leckman Diamond Schmitt Architects Chris Piche Integral Group DISCOVERIES AT NET ZERO So, what is a Net Zero Energy building? A building achieves Net Zero Energy when it
More informationPart 1 Review Questions on material covered in Midterms I & II
1 Arch 463 ECS Fall 2001 Name FINAL 40 Multiple Choice Questions Part 1 Review Questions on material covered in Midterms I & II 1. Passive systems for environmental control A. can enhance human comfort
More informationPCMs in Building America Projects - Roof Retrofit Technology with Use of the PCM Heat Sink
Fraunhofer Center for Sustainable Energy Systems PCMs in Building America Projects - Roof Retrofit Technology with Use of the PCM Heat Sink Jan Kosny Ph.D. - Fraunhofer CSE MCA-ORNL Project Leader 2008-2010
More informationDetermining Energy Use Volatility for Commercial Mortgage Valuation
Determining Energy Use Volatility for Commercial Mortgage Valuation Paul Mathew, XiuFeng Pang, Liping Wang Building Technologies and Urban Systems Department Lawrence Berkeley National Laboratory June
More informationCoppin State University Physical Education Complex - Technical Report 2
Coppin State University Physical Education Complex - Technical Report 2 Building and Plant Energy Analysis Report Kaylee M Damico Advisor: Dr. Jelena Srebric Location: Baltimore, MD Table of Contents Contents
More informationCornell University Energy and Sustainability: ECI Campus Energy Metrics Fiscal Year 2017 Annual Analysis Purpose and Methodology. ECI Campus Summary:
Purpose and Methodology ECI Campus Summary: Starting in the 2011/2012 fiscal year, a yearly energy metrics analysis is being performed. This analysis supports creating Facilities Metrics and evaluation
More informationIMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE
IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE Dr. Essam Al-Sayed Omar Department Manager Kuwait Institute for Scientific Research Kuwait ABSTRACT This paper addresses the
More informationLAHU Heat Recovery System Optimal Operation and Control Schedules
Yujie Cui Nexant, Inc., 44 South Broadway, 5th Floor, White Plains, NY 10601 e-mail: ycui@nexant.com Mingsheng Liu Architectural Engineering, University of Nebraska Lincoln, 206C, PKI, 1110 S. 67th St.,
More informationBuilding Energy Asset Score
Building Energy Asset Score An opportunity to participate with pioneering programs guided by the Consortium for Building Energy Innovation (CBEI) 15 th October, 2015 2 Consortium for Building Energy Innovation
More informationBETA OPTION 1: PERFORMANCE RATING METHOD. Section General Information
LEED-CS 2. Certification Submittal Template OPTION 1: PERFORMANCE RATING METHOD I confirm that the energy simulation software used for this project has all capabilities described in EITHER section `G2
More informationEnergy 10/19/2011. Inc. New. Castle, DEE. Image. By: Skanska
Technical Report Two Building, Plant Energy and Emission Analysis Report 10/19/ New Castle Center for Delaware Hospice, Inc. New Castle, DEE Image By: Skanska Pennn State University Architectural Engineering
More informationCommercial HVAC. Emerging Technologies
Commercial HVAC Showcase Commercial HVAC Webinar #2 April 14, 2015 Welcome. Today s webinar is being recorded and will be posted at: www.nw.org www.conduitnw.org 1 GoToWebinar Logistics Minimize or maximize
More informationSenior Design Project for UNO. Design of the International Studies Building: An Environmental Analysis
Senior Design Project for UNO Design of the International Studies Building: An Environmental Analysis Design Intent Implement Passive & Active design strategies in order to make the building: More Energy
More informationHigher Education Energy Efficiency Partnership Program BEST PRACTICES AWARDS
Higher Education Energy Efficiency Partnership Program BEST PRACTICES AWARDS UC / CSU Sustainability Conference, June 2005 A program created by the UC/CSU/IOU Partnership and under the auspices of the
More informationProcedia - Social and Behavioral Sciences 216 ( 2016 )
Available online at www.sciencedirect.com ScienceDirect Procedia - Social and Behavioral Sciences 216 ( 2016 ) 655 661 Urban Planning and Architecture Design for Sustainable Development, UPADSD 14-16 October
More informationTechnical Assignment 2 Building and Plant Energy Analysis
Technical Assignment 2 Building and Plant Energy Analysis Des Places Residence Hall Duquesne University Pittsburgh, PA Peter Edwards Advisor: James Freihaut October 4, 2010 Table of Contents Executive
More informationProject Name: Example Building OFPC Project No.: 12345
Energy Impact Statement Project Name: Example Building OFPC Project : 12345 Building Description and Assumptions: The design professional shall provide a brief narrative describing various building related
More informationChapter 6. Space heating load
Chapter 6 Space heating load 1 Outdoor Design Conditions Heating systems should provide just enough heat to match the heat loss from the structure. Local knowledge should be obtained for design conditions.
More informationASHRAE Standard 209. ASHRAE Golden Gate Seminar October 17, Erik Kolderup
ASHRAE Standard 209 ASHRAE Golden Gate Seminar October 17, 2018 Erik Kolderup erik@kolderupconsulting.com www.kolderupconsulting.com (415) 531-5198 1 Outline ASHRAE Standard 209 Why and how it came to
More informationEffective Energy Modeling WGBA Leadership Conference October 19, 2005
Effective Energy Modeling WGBA Leadership Conference October 19, 2005 Steven Carlson, P.E. CDH Energy Corp. Evansville, WI www.cdhenergy.com Presentation Overview What Why How Illustrated by experiences
More informationRod Roy Eads Lane, Lane Consulting Services.
Project: Address: Happy OXNARD Community VILLAS, NORTH Apartments BLDG (INITIAL APP P 111 1445 Sample OXNARD Blvd. ST Los VAN Angeles, NUYS, CA CA9141 Prepared By: Phone: Fax: E-mail: Date: Rod Roy Eads
More informationDESIGN OF A GREEN DEMO BUILDING IN A HOT AND HUMID CITY IN CHINA. Ana Bacall Sebesta Blomberg & Associates Woburn, MA
DESIGN OF A GREEN DEMO BUILDING IN A HOT AND HUMID CITY IN CHINA Yi Jiang Sebesta Blomberg & Associates Woburn, MA William Hammer HKT Architects Somerville, MA Ana Bacall Sebesta Blomberg & Associates
More informationSummer thermal comfort in traditional buildings of the 19th century in Florina, north-western Greece
International Conference Passive and Low Energy Cooling 239 Summer thermal comfort in traditional buildings of the 19th century in Florina, north-western Greece A. Oikonomou Department of Architectural
More informationDuluth Energy Future Chapter 2: Investigating Zero-Energy Potential
2016 Duluth Energy Future Chapter 2: Investigating Zero-Energy Potential August 2016 August 2016 0 Duluth Energy Transition, Chapter 2: Investigating Zero- Energy Potential Authors: Jacob Cherry, Graduate
More informationJames Marston Fitch American Building: The Environmental Forces that Shape It
THERMAL COMFORT Ball State Architecture ENVIRONMENTAL SYSTEMS 1 Grondzik 1 James Marston Fitch American Building: The Environmental Forces that Shape It The fundamental thesis of this book is that the
More informationTable 1: Summary of Tracking and Evaluation Savings Results
Facility Type: Multi-Tenant Commercial Building Project ID: _dnv 1.0 Summary of Savings and Adjustments This project includes the installation of new T8 lighting and compact fluorescent lamps in place
More information