European Technical Approval ETA-11/0346

Size: px
Start display at page:

Download "European Technical Approval ETA-11/0346"

Transcription

1 SINTEF Building and Infrastructure P.O.Box 124 Blindern N-0314 Oslo Tel Fax Authorised and notified according to Article 10 of the Council Directive 89/106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating to construction products MEMBER OF EOTA European Technical Approval ETA-11/0346 Trade name: Holder of approval: Generic type and use of construction product: RVK and TSS staircase connections SB Produksjon AS Øran Vest N-6300 Åndalsnes Norway Connections for precast concrete staircase and landing elements to the stairway walls. Valid from: to: Manufacturing plant: SB Produksjon AS Øran Vest N-6300 Åndalsnes Norway This European Technical Approval contains: 49 pages including 33 Annex which forms an integral part of the document European Organisation for Technical Approvals

2 European Technical Approval No. ETA-11/0346 Page 2 of 16 I LEGAL BASIS AND GENERAL CONDITIONS 1 This European Technical Approval is issued by SINTEF Building and Infrastructure, in the following called SINTEF, in accordance with: - Council Directive 89/106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating to construction products 1, modified by the Council Directive 93/68/EEC 2 and Regulation (EC) Nº 1882/2003 of the European Parliament and of the Council 3 - Common Procedural Rules for Requesting, Preparing and the Granting of European technical approvals set out in the Annex of Commission Decision 94/23/EC 4 - Common Understanding of Assessment Procedure (CUAP) for ETA request N 06.01/25 2 SINTEF is authorised to check whether the provisions of this European Technical Approval are met. Checking may take place in the manufacturing plant. Nevertheless, the responsibility for the conformity of the products to the European Technical Approval and for their fitness for the intended use remains with the holder of the European Technical Approval. 3 This European Technical Approval is not to be transferred to manufacturers or agents of manufacturers other than those indicated on page 1 of this European Technical Approval. 4 This European Technical Approval may be withdrawn by SINTEF in particular pursuant to information by the Commission according to Article 5(1) of Council Directive 89/106/EEC. 5 Reproduction of this European Technical Approval including transmission by electronic means shall be in full. However, partial reproduction can be made with the written consent of SINTEF. In this case partial reproduction has to be designated as such. Texts and drawings of advertising brochures shall not contradict or misuse the European Technical Approval. 6 The European Technical Approval is issued by the approval body in its official language. This version corresponds fully to the version circulated in EOTA. Translations into other languages have to be designated as such. 1 Official Journal of the European Communities N L40, , p Official Journal of the European Communities N L 220, , p. 1 3 Official Journal of the European Union N L 284, , p. 1 4 Official Journal of the European Communities N L17, , p. 34

3 European Technical Approval No. ETA-11/0346 Page 3 of 16 II SPECIFIC CONDITIONS OF THE EUROPEAN TECHNICAL APPROVAL 1 Definition of product and intended use 1.1 Definition of the product RVK and TSS staircase connections consist of double, extendable, hollow rectangular steel tubes type HUB made of cold worked structural steel S355 to be cast into prefabricated concrete staircase and landing elements. The smaller tube is sliding inside the other and form load carrying connections to stairwell walls. Annex 1 (fig. 1) illustrates the principle of the staircase connections. The position of the inner tube of the RVK unit is adjusted through a slot in the surface of the staircase element. The units have a safety stop at the back of the inner tube to prevent overextension. The TSS unit is identical to the RVK unit except for the TSS unit has no opening to the upper surface. The position of the inner tube is instead adjusted by two strings with different colour. The units have a control line marking the correct position of the sliding tube, and a hole for a locking bolt. The design and main dimensions for RVK staircase connections are shown in Annex 2 (fig. 2 and table 1 and 2). Two sizes of the RVK unit are produced, with vertical load carrying capacity 40 and 100 kn respectively. The latest version of the units with distribution bars welded to the topside front of the units are denominated RVK 41 and RVK 101. An additional letter G indicate hot dip galvanized version. The design and main dimensions for TSS staircase connections are shown in Annex 3 (fig. 3 and table 3). Correspondingly the following types of the TSS unit are produced: TSS 41, TSS 41 G, TSS 101 and TSS 101 G. The additional product Masticord bearing pads is delivered for providing equal support load distribution and elastic support in order to reduce impact sound transmission. The pads are made of a homogeneous blend of ozone resistant rubber elastomers with a high strength random synthetic fibre cord. The bearing pads are 75 mm wide, 125 mm long and 6,5 mm thick. The hardness is 75shore. As additional products the manufacturer also provides Blockout box for RVK/TSS 41 and 101. used to make recesses in the walls. 1.2 Intended use The connection units are designed for connecting precast stairs and landing elements to the stairway shaft walls, and transferring vertical shear loads between the concrete components. The connections may also be used for support of slabs mounted between walls for other purposes. Standard units are used indoor in dry conditions. Connections made of hot dip galvanized steel may be used for external exposure according to the requirements for the individual projects.

4 European Technical Approval No. ETA-11/0346 Page 4 of 16 The TSS unit is specially designed to connect precast stair- and landing elements where the final surface finish of the elements are made in the factory, for example terrazzo. The working life of the connection units for the intended use is assumed to be at least 50 years when installed in the works, provided that the unit are subject to appropriate design and installation based upon the current state of art and the available knowledge and experience. 2 Characteristics of the product and methods of verification 2.1 Mechanical resistance and stability (ER1) Design of load carrying capacity Type and number of RVK or TSS-units shall be chosen in accordance with structural calculations for sufficient load carrying capacity in each case. The position of the units in stairs- and landings elements and the recess in the stairwell walls shall be accurately designed and specified in construction drawings. The load carrying capacity and minimum thickness of the landings for full utilization of the capacity for type RVK and TSS are given in Annex 4 (table 4). Full utilization of the capacity requires standard reinforcement design of the regions around the RVK- and TSS units and minimum concrete strength class C35/45. Also required is a minimum corner distance and a minimum spacing of the units. Design guidance is given in Annex 5 with enclosed memos concerning reinforcement design and recommended reinforcement pattern. The design of the concrete components must take into consideration that the components are pin point supported in the wall recesses. Structural design for upwards forces at the supports may be required in particular cases, and in such cases the support and the reinforcement around the units must be designed especially to handle such loads. To ensure a good load distribution to the supports of stairs and landings, especially when using four or more RVK or TSS units per element, the units should be supported on a relatively thick and soft rubber pad. This provides also a good impact sound insulation. Effects of horizontal forces caused by friction of the inner tube at the support shall be taken into account for design. Transfer of horizontal forces are initially limited to friction resistance at the supports. This is usually sufficient for stabilizing stair and landing elements subjected to small accidental horizontal loads. In special cases the horizontal load distribution may be attended to by castin, adjustable bolts with rubber dampers at the end, which are pressed against the stairwell walls. Joint width Recommended joint widths between staircase and landing elements and the walls are 20 mm ± 10 mm for the RVK unit, and 30 mm ± 10 mm for the TSS unit. The joint width must not exceed 40 mm if the load carrying capacities indicated in Annex 4 (table 4) are used.

5 European Technical Approval No. ETA-11/0346 Page 5 of Safety in case of fire (ER2) Staircases are normally escape routes during fire and are not supposed to be exposed directly to fire. High fire rating is usually required only for the stairwell walls themselves. The units may therefore often be used unprotected even though the fire resistance of the connection with open joint gap is limited. Significant fire resistance may be achieved for RVK and TSS staircase connections by filling the joint between the stairs or landings and the wall with mortar. However, filling with mortar reduces strongly the possibility to achieve low impact sound transmission and thermal movement. An alternative is to protect the units in the joint between the stairs or landings and the wall with mineral wool around the RVK/TSS unit. The filling shall be sealed off with an elastic sealant to prevent the mineral wool filling from falling out. The filling shall cover the full element thickness Reaction to fire Reactions to fire for steel products are classified as Class A1 according to EN without testing on the basis of EC Decision 1996/603/EC Resistance to fire The connections having minimum 50 mm concrete cover will probably have at least the same fire resistance as normal concrete stairs and landings by filling the joint between the stairway components and the wall with mortar. This statement requires full scale tests for verification. 2.3 Hygiene, health and environment (ER 3) No special environmental declaration has been worked out for RVK and TSS connections. The products do not contain any chemical substances listed on the Norwegian environmental authorities observation list of compounds hazardous to human health or the environment, and are not regarded as emitting any particles, gases or radiation that have a perceptible impact on the indoor climate or that have any significant impact on health. Note: In addition to the specific clauses relating to dangerous substances contained in this European Technical Approval, there may be other requirements applicable to the products falling within its scope (e.g. transposed European legislation and national laws, regulations and administrative provisions). In order to meet the provisions of the Construction Products Directive, these requirements need also to be complied with, when and where they apply. Steel parts and concrete elements may be recycled under given circumstances. Alternatively they may be delivered to a public waste deposit site at the end of the working life. 2.4 Safety in use (ER 4) For TSS a control line marks the correct position of the inner tube and a safety stop at the back of the inner tube ensures overextension.. A safety pin will prevent the inner tube from getting out of position. 2.5 Protection against noise (ER 5) The impact sound insulation achieved by elastic support is depending on the stiffness of the bearing pads. The more elastic pads, the better sound reduction. Field tests have shown that an impact sound reduction of up to 25 db is obtained by using a recommended design criteria equivalent to 1 mm compression of the pad from the dead load of the staircase.

6 European Technical Approval No. ETA-11/0346 Page 6 of 16 Good values of the impact sound insulation assumes that the joint between the stairway components and the wall is open (not filled with mortar) or alternatively filled with mineral wool. To achieve the best sound reduction it is important that the stairway is not in direct contact with the walls at any places 2.6 Energy economy and heat retention (ER 6) Not relevant 2.7 Aspects of durability, serviceability and identification? Hot dip galvanized products shall have a minimum zinc thickness of 0,08 mm according to ISO 2081 / NS Black steel products are normally acceptable in dry stairways. Galvanized versions are recommended for stairs or landings stored outdoor for some time, for stairways that may be exposed to salt water and chlorides (for example parking facilities), and for outdoor stairways.. The durability of the product shall be declared with reference to the relevant intended use and the exposure conditions. For use in dry interior applications the durability may be regarded as satisfactory for standard uncoated steel connections, where concrete cover gives sufficient resistance against corrosion. Connections made of hot dip galvanized steel or stainless steel may be declared as applicable for normal external conditions or for special environmental applications which have to be assessed case by case. 2.8 Special conditions for use and installation Recesses in stairway walls The recess elevation in the walls must be measured accurately to minimize the need for vertical adjustments. Using the additional product "Blockout box" simplifies positioning of recesses with accurate measures in the wall elements.. The recommended level of the recess bottom is 20 mm below the inner tube (fig 2 and 3). Support materials in layers consisting of a standard steel support plate + elastic bearing pad + levelling steel sheets (shims) is recommended. Installation Staircase and landing elements are lifted into the shaft while the inner tube is retracted into the unit. When the precast element is in correct position the inner tube of the RVK is pushed out through the open slot at the upper part of the element. The inner tube of the TSS unit is pushed out by pulling the extension string. A red and white control line will mark the correct position. If needed, e.g. at mistakes during erection, the inner tube can be retracted by the returning string. A safety stop at the back of the inner tube ensures that maximum cantilever is not exceeded. A safety bolt will prevent the inner tube from getting out of position. Both the installation slot in the RVK units and the recess in the shaft wall are normally filled with mortar after erection. It is recommended to put some mineral wool around the steel unit in the joint before filling the grout into the recess.

7 European Technical Approval No. ETA-11/0346 Page 7 of 16 The joint between the stairs and the wall shall normally not be filled, because this causes higher impact sound transmission. Filling the joint may be done when the stairway shaft are an active part of the stabilisation of the building, or in order to prevent dirt from gathering in the joint. An alternative to prevent dirt in the joints is to use an elastic sealant with a backing strip at the top. The installation of the staircase connections, including concrete reinforcement and positioning, shall in general be carried out in accordance with the manufacturer s installation guide. All installation is done inside the stairway, without perforating holes in the walls. 3 Evaluation and attestation of conformity and CE marking 3.1 System of attestation of conformity According to Decision 97/597/EC of the European Commission has decided that System 2+ of attestation of conformity applies. This system of attestation of conformity is defined as follows: Certification of the conformity of the product by a notified certification body on the basis of: (a) Tasks for the manufacturer: (1) initial type testing of the product; (2) factory production control; (3) testing of samples taken at the factory in accordance with a prescribed test plan. (b) Tasks for the approved body: (4) certification of factory production control on the basis of: initial inspection of factory and of factory production control; continuous surveillance, assessment and approval of factory production control 3.2 Responsibilities Tasks of the manufacturer Factory production control The manufacturer shall exercise permanent internal control of the production. All the elements, requirements and provisions adopted by the manufacturer shall be documented in a systematic manner in the form of written policies and procedures, including records of results performed. This production control system shall insure that the product is in conformity with this European technical approval. The manufacturer may only use constituent materials stated in the technical documentation of this European technical approval. The factory production control shall be in accordance with the Control Plan for RVK and TSS stair connections relating to the this European technical approval. The Control Plan is part of the technical documentation of this European technical approval, and is laid down in the context of the factory production control system operated by the manufacturer. The Control Plan is deposited at SINTEF. 5 5 The "control plan" is a confidential part of the European technical approval and only handed over to the notified body or bodies involved in the procedure of attestation of conformity. See section

8 European Technical Approval No. ETA-11/0346 Page 8 of 16 The results of factory production control shall be recorded and evaluated in accordance with the provisions of the Control Plan Other tasks of manufacturer The manufacturer shall, on the basis of a contract, involve a body (bodies) which is (are) notified for the tasks referred to in section 3.1 in the field of reinforcement steel products in order to undertake the actions laid down in section For this purpose, the Control Plan referred to in sections and shall be handed over by the manufacturer to the notified body or bodies involved Tasks of the notified body The approval body (bodies) shall perform the - initial inspection of factory and of factory production control - continuous surveillance, assessment and approval of factory production control in accordance with the provisions laid down in the Control Plan relating to this European technical approval ETA. The approval body (bodies) shall retain the essential points of its (their) actions referred to above and state the results obtained and conclusions drawn in written reports. The approved certification body involved by the manufacturer shall issue an EC certificate of conformity of the factory production control stating the conformity with the provisions of this European technical approval. In cases where the provisions of the European technical approval and its Control Plan are no longer fulfilled the certification body shall withdraw the certificate of conformity and inform SINTEF without delay. 3.3 CE marking The CE marking shall be affixed to the packaging or accompanying commercial documents. The letters CE shall be followed by the identification number of the notified certification body and be accompanied by the following additional information: - the name and address of the producer (legal entity responsible for the manufacture), - the last two digits of the year in which the CE marking was affixed, - the number of the EC certificate for the factory production control - the number of the European technical approval, - identification of the product 4 Assumptions under which the fitness of the product for the intended use was favourably assessed 4.1 Manufacturing The European technical approval is issued for RVK and TSS staircase connections on the basis of agreed data/information deposited with SINTEF, which identifies the product that has been assessed and judged. Changes to the product or production process, which could result in this deposited data/information being incorrect, should be notified to SINTEF before the changes are introduced. SINTEF will decide whether or not such changes affect the ETA and consequently the validity of the CE marking on the basis of the ETA, and if so whether further assessment or alterations to the ETA is necessary.

9 European Technical Approval No. ETA-11/0346 Page 9 of Installation The RVK and TSS staircase connections shall be installed in accordance with detailed construction drawings worked out for the individual works, based on the structural design for the works according to applicable standards. 5 Indications to the manufacturer and supplier 5.1 Packaging, transport and storage The RVK and TSS staircase connections must be transported and stored in such a way that the material is protected against salt due to the risk of corrosion. During outdoor storage all openings in the beam and column units must be covered in order to prevent water or ice to enter the connections. On behalf of SINTEF Building and Infrastructure Oslo, xx.xx.2011 Annex 1: Product description (principle) of RVK and TSS Annex 2: Design and main dimensions for RVK staircase connections Annex 3: Design and main dimensions for TSS staircase connections Annex 4: Design load carrying capacity for RVK and TSS staircase connections Annex 5: Design guide

10 European Technical Approval No. ETA-11/0346 Page 10 of 16 Annex 1 Product description (principle) of RVK and TSS Fig. 1 Principle for RVK and TSS stairway connectors. The RVK connections have a sliding inner tube accessible from a slot at the surface of the stair or landing. The slot may be filled with mortar after installation. Type TSS has no slot and the position of the inner tube may be adjusted by two strings from the end of the unit. The inner tube form load carrying connections to stairway walls.

11 European Technical Approval No. ETA-11/0346 Page 11 of 16 Annex 2 Design and main dimensions for RVK staircase connections Fig. 2 Type RVK. Design and main dimensions. See also table 1 and 2. Table 1 Main dimensions for RVK in mm RVK L L 1 L 2 L 3 L 4 h h 1 b 1 b Table 2 Additional dimensions for RVK Rectangular steel tube dimensions Free space between tubes RVK w/h/t (mm) (mm) Outer Inner Verti Horizon tube tube cally tally 41 80/50/4 70/40/ /60/4 100/50/6 2 12

12 European Technical Approval No. ETA-11/0346 Page 12 of 16 Annex 3 Design and main dimensions for TSS staircase connections Fig. 3 Type TSS. Design and main dimensions. See also table 4. Table 3 Main dimensions for TSS in mm TSS L L 1 L 2 h Rectangular steel tube dimensions w/h/t (mm) Inner Outer tube tube Free space between tubes (mm) Vertical Horizontal /50/4 70/40/ /60/4 100/50/6 2 12

13 European Technical Approval No. ETA-11/0346 Page 13 of 16 Annex 4 Design load carrying capacity for RVK and TSS staircase connections Table 4 Load carrying capacity and minimum thickness of concrete landings for RVK and TSS. Full utilization of the capacity requires standard reinforcement. minimum concrete strength class C35/45, and minimum corner distance and spacing of the units. RVK/TSS Max. vertical capacity V dv in kn Minimum landing thickness in mm To make For max. sufficient capacity space Design guidance is given in Annex 5 with enclosed memos concerning reinforcement design and recommended reinforcement pattern.

14 European Technical Approval No. ETA-11/0346 Page 14 of 16 Annex 5 Design Guide The RVK/TSS connections are subject to three possible local failure modes: Combined moment and shear failure of the inner tube (ITY) Push off of concrete above the unit (POC) Local shear failure of the reinforced concrete slab (SF) The capacity of the HUP tubes of steel quality S355 have been calculated according to Eurocode 3 with recommended parameters. The bending moments are calculated with maximum extension (110 mm), maximum gap (40 mm) and unfavourable tolerance on the position of the suspension reinforcement (5 mm). The calculation reveals that the ULS capacities of the inner tubes are only slightly above the nominal capacity of the units. 40 kn for RVK/TSS 41 and 100 kn for RVK/TSS 101 therefore represent the maximum capacity of the units irrespective of the slab thickness and reinforcement The capacity against push off of the concrete above the steel unit is mainly related to the strength and detailing of the suspension reinforcement in the form of two spatial stirrups placed over the unit near the slab edge. Design Memo 54 a-d prepared by the manufacturer shows the capacity calculation and detailing of the stirrups for RVK 41 and 101 and TSS 41 and 101 respectively. The capacity check is based on recommended design parameters according to Eurocode 2 with reinforcement steel B500C applying a conservative model assuming a flexible outer tube. By this model the support reactions from the inner tube are transferred directly to the surrounding reinforced concrete without participation of the outer tube other than local transverse distribution, giving the maximum force in the suspension stirrups. The calculation reveals that the design strength of the standard suspension stirrups 2Ø8 mm for RVK/TSS 41 and 2Ø12 mm for RVK/TSS 101 are almost fully utilized when unfavourable position tolerances are taken into account. Testing of TSS 101 units in 265 mm thick concrete slabs with suspension reinforcement detailing as shown in Memo 54d show characteristic POC failure resistance with material safety factor higher than 1,5. Local shear failure of the slab may occur, especially for slabs with minimum thickness (150 mm for RVK/TSS 41 and 200 mm for RVK/TSS 101). Recommended local reinforcement of the slabs and corresponding ULS design capacities are shown in Memo 55 a-d for RVK 41 and 101 and TSS 41 and 101 respectively. The memos define gradual decrease of the shear capacity with decreasing distances from the centreline of the units to the corner of slabs without distributed shear reinforcement and also absolute minimum corner distances. Fig. 4 a. Recommended ULS vertical shear capacity for RVK/TSS 41 in 150 mm thick slab.

15 European Technical Approval No. ETA-11/0346 Page 15 of 16 Fig. 4 b. Recommended ULS vertical shear capacity for RVK/TSS 101 in mm slabs The recommended shear capacities given in table 5 are based on interpretation of tests. The design shear capacity may also be estimated by the following simple model based on modification of the shear capacity equation 6.2.a in Eurocode 2: V Rd,c = C Rd,c k (100 ρ f ck ) 1/3 b eff d where k = 1 + (200/d) 2,0, C Rd,c = 0,20/γ mc = 0,2/1,5 = 0,133 b uff = 3d + b u + 6Ø b eff,red = b eff /2 + c b uff c = corner distance ρ = A s,eff /d b eff,red A s,eff = Reinforcement normal to the slab edge near to the unit (including suspension stirrups) Table 5 Recommended shear capacities nit RVK/TSS 41 RVK/TSS 41 RVK/TSS 101 RVK/TSS 101 Slab thickness A s,eff 6 Ø 8 6 Ø 8 7 Ø 12 7 Ø 12 Eff. Height (d) Corner dist. (c) b eff/2 160 b eff/2 180 b eff,red Ratio (ρ) % 0,521 0,634 0,705 0,924 Concrete (f ck) V Rd,c (kn) (85) 73 (75)

16 European Technical Approval No. ETA-11/0346 Page 16 of 16 Calculation by the simplified formula of the local shear resistance of slabs with minimum thickness and minimum corner distance for RVK/TSS units 41 and 101 shows vertical support load capacity practically equal to the recommended values deduced from tests. (Values for RVK/TSS 101 in 200 mm thick slabs are rounded to the nearest 5 kn.) The applicability of the formula indicate that the shear capacity can be corrected for different concrete strength classes by the factor η c = (f ck,actual /35) 1/3 (f ck min = 30 MPa) It also indicates that the spacing of the units without capacity reduction should be minimum 500 mm for RVK/TSS 41 and minimum 700 mm for RVK/TSS 101. The POC capacity of RVK/TSS 101 in a 265 mm thick slab is lower than the shear capacity and is therefore decisive. The capacity of RVK/TSS 101 in slabs with thickness between 200 and 265 mm can be interpolated linearly. Likewise the capacity reduction for RVK/TSS 41 near slab corners may be omitted for slabs of thickness 200 mm. Memoes An extract of memos (technical manuals) from the manufacturer concerning reinforcement design and reinforcement pattern for RVK 41 and RVK 101 are given here in the following memos: Memo 54a Reinforcement design for RVK 41, Memo 54b Reinforcement design for RVK 101, Memo 55a Recommended reinforcement pattern RVK 41 and Memo 55b Recommended reinforcement pattern RVK 101. The corresponding memos (technical manuals) for TSS units are almost identical and are not given here. A complete list of memos are given i table 6 Table 6 List of memos for TSS/RVK 41/101 (Technical manuals) MEMOS in English for TSS/RVK 41/101 DATE LAST REV. Design RVK 41 and TSS Design RVK 101 and TSS Memo-52 Capacities and main dimensions RVK 41 and RVK Memo-53 Capacities and main dimensions TSS 41 and TSS Memo-54a Reinforcement design for RVK Memo-54b Reinforcement design for RVK Memo-54c Reinforcement design for TSS Memo-54d Reinforcement design for TSS Memo-55a Recommended reinforcement pattern for RVK Memo-55b Recommended reinforcement pattern for RVK Memo-55c Recommended reinforcement pattern for TSS Memo-55d Recommended reinforcement pattern for TSS All the memos are available through the manufacturers home site:

17 Design MEMO 54a Reinforcement design for RVK 41 Date: Sign: sss Page 1 of 9 CONTENTS PART 1 BASIC ASSUMTIONS... 2 GENERAL... 2 STANDARDS... 2 QUALITIES... 3 DIMENSIONS... 3 LOADS... 3 PART 2 - REINFORCEMENT... 4 EQUILIBRIUM... 4

18 Design MEMO 54a Reinforcement design for RVK 41 Date: Sign: sss Page 2 of 9 PART 1 BASIC ASSUMTIONS GENERAL The following calculations of anchorage of the units and the corresponding reinforcement must be considered as an example illustrating the design model. It must always be checked that the forces from the anchorage reinforcement can be transferred to the main reinforcement of the concrete components. The recommended reinforcement includes only the reinforcement necessary to anchor the unit to the concrete. In the vicinity of the unit the element must be designed for the force R 1. STANDARDS The calculations are carried out in accordance with: Eurocode 2: Design of concrete structures. Part 1-1: General rules and rules for buildings. Eurocode 3: Design of steel structures. Part 1-1: General rules and rules for buildings. Eurocode 3: Design of steel structures. Part 1-8: Design of joints. EN 10080: Steel for the reinforcement of concrete. Weldable reinforcing steel. General. For all NDPs (Nationally Determined Parameter) in the Eurocodes the recommended values are used. NDP s are as follows: Parameter c s α cc α ct C Rd,c v min k 1 Recommended value Table 1: NDP-s in EC k 1/3 f ck 1/ Parameter M0 M1 M2 Recommended value Table 2: NDP-s in EC-3.

19 Design MEMO 54a Reinforcement design for RVK 41 Date: Sign: sss Page 3 of 9 QUALITIES Concrete grade C35/45: f ck = 35,0 MPa EC2, Table 3.1 f cd = α cc f ck /γ c = 1 35/1,5 = 23,3 MPa EC2, Pt.3.15 f ctd = α ct f ctk,0,05 /γ c = 1 2,20/1,5 = 1,46 MPa EC2, Pt.3.16 f bd = 2,25 η 1 η 2 f ctd = 2,25 0,7 1,0 1,46 = 2,3 MPa EC2, Pt Reinforcement B500C: Structural steel S355: DIMENSIONS f yd = f yk /γ s = 500/1,15 = 435 MPa Tension: f yd = f y / γ M0 = 355/1,0 = 355 MPa Compression: f yd = f y / γ M0 = 355/1,0 = 355 MPa Shear: f sd = f y /( M0 3) = 355/(1,0 3) = 205 MPa EC2, Pt Inner tube: HUP 70x40x4, Cold formed, S355 Outer tube: HUP 80x50x4, Cold formed, S355 LOADS Vertical ultimate limit state load = F V = 40kN.

20 Design MEMO 54a Reinforcement design for RVK 41 Date: Sign: sss Page 4 of 9 PART 2 - REINFORCEMENT EQUILIBRIUM Figure 1: Forces acting on the unit. F V = External force on the inner tube R 1i, R 2i = Internal forces between the inner and the outer tubes. R 1, R 2, R 3 = Support reaction forces of the outer tube. g= distance to the middle plane of the anchoring stirrups in front of the unit.

21 Design MEMO 54a Reinforcement design for RVK 41 Date: Sign: sss Page 5 of 9 I) Equilibrium inner tube: Figure 2: Forces acting on the inner tube. Equilibrium equations of the inner tube: 1): M=0: F v (L 1 -b-e) - R 1i (L 1 -b-a-g-e)=0 (1) 2): F y =0: F v -R 1i +R 2i =0 (2) Assuming nominal values: L 1 =275mm, a=75mm, b=35mm, g=35mm, e=10mm Solving R 1i from eq. 1: Fv ( L1 b e) R1 i (3) ( L b a g e) 1 Solving R 2i from eq. 2: R 2i = R 1i -F v (4) Results: 40kN( ) mm R1 i 76. 7kN ( ) mm R i 76.7kN 40kN 36. 7kN 2

22 Design MEMO 54a Reinforcement design for RVK 41 Date: Sign: sss Page 6 of 9 II) Equilibrium outer tube: Figure 3: Forces acting on the outer tube. Exact distribution of forces depends highly on the behavior of the outer tube. Both longitudinal bending stiffness and local transverse bending stiffness in the contact points between the inner and the outer tubes affects the equilibrium. Two situations are considered: 1) Rigid outer tube. Outer tube rotates as a stiff body. This assumption gives minimum reaction force at R 1, and maximum reaction force at R 2. R 3 is assumed zero. (The force R 3 will actually be negative, but since no reinforcement to take the negative forces is included at this position, it is assumed to be zero.) Equilibrium equations of the outer tube: 1): M=0: (R 1i -R 1 ) (L-3-g-d) (R 2i -R 3 ) (L-3-g-c-d)=0 (5) 2): F y =0: R 2 +R 3 +R 1i - R 2i -R 1 =0 (6) Assuming nominal values: L=298mm, c=120mm, g=35mm, e=10mm, d=10mm; (c=l 1 -b-a-g-e= =120mm) Solving R 1 from eq. 5: ( R R ) ( L 3 g d) ( R 1i 1 (76.7 R ) ( ) (36.7 0) ( ) R R1 57.6kN i R ) ( L 3 g c d) 0 3

23 Design MEMO 54a Reinforcement design for RVK 41 Date: Sign: sss Page 7 of 9 Solving R 2 from eq. 6: R R R i R1 i kN ) Outer tube without bending stiffness. No forces transferred to outer tube at the back of inner tube. This assumption gives maximum reaction forces R 1 and R 3. R 2 becomes zero. The forces follow directly from the assumption: R 1 = R 1i R 3 = R 2i and R 2 =0 R 76.7kN R R kN 36.7kN The magnitude of the forces will be somewhere in between the two limits, and the prescribed reinforcement ensures integrity for both situations. Reinforcement is to be located at the assumed attack point for support reactions. Reinforcement for R 1, R 2 and R 3 : Figure 4: Forces. Reinforcement necessary to anchor the unit to the concrete: Reinforcement R 1 : A s1 = R 1 /f sd 76.7kN/435Mpa =176 mm 2 Select 2-Ø8 = =200 mm 2 Capacity selected reinforcement: R=200 mm 2 435MPa=87kN Reinforcement R 3 : A s3 = R 3 /f sd = 36.7kN/435MPa =84 mm 2 Select 1-Ø8 = = 100mm 2 Capacity selected reinforcement: R=100 mm 2 435MPa=43.5kN Reinforcement R 2 : A s2 = R 2 /f sd = 17.6kN/435MPa =41 mm 2 Select 1-Ø8 = = 100mm 2 Capacity selected reinforcement: R=100 mm 2 435MPa=43.5kN

24 Design MEMO 54a Reinforcement design for RVK 41 Date: Sign: sss Page 8 of 9 Tolerances on the positioning of the reinforcement: Due to the small internal distances, the magnitude of the forces will change when changing the position of the reinforcement. Thus, strict tolerances are required. Alt 1) Assume: L 1 =275mm, a=75mm, b=35mm, g=35+5=40mm, e=10mm Gives: 40kN ( ) mm R kN ( ) mm R 80.0kN 40kN 40. 0kN 2 Alt 2) Assume: L 1 =275mm, a=75mm, b=35mm, g=35+5=40mm, e=10+5mm, Gives: 40kN ( ) mm R kN ( ) mm R 81.8kN 40kN 41. 8kN 2 Conclusion tolerances: Alt 2 represents the most unfavorable position of reinforcement allowed without exceeding the reinforcement capacity. Thus, the assembling tolerances for P1, P2 and P4 should be ±5mm. For recommended reinforcement pattern, see Memo 55a. Transverse reinforcement: One transverse bar with the same diameter as the anchorage bar to be placed in the bend of every anchoring bar.

25 Design MEMO 54a Reinforcement design for RVK 41 Date: Sign: sss Page 9 of 9 Figure 5: Anchoring reinforcement.

26 Design MEMO 54b Reinforcement design for RVK 101 Date: Sign: sss Page 1 of 9 CONTENTS PART 1 BASIC ASSUMTIONS... 2 GENERAL... 2 STANDARDS... 2 QUALITIES... 3 DIMENSIONS... 3 LOADS... 3 PART 2 - REINFORCEMENT... 4 EQUILIBRIUM... 4

27 Design MEMO 54b Reinforcement design for RVK 101 Date: Sign: sss Page 2 of 9 PART 1 BASIC ASSUMTIONS GENERAL The following calculations of anchorage of the units and the corresponding reinforcement must be considered as an example illustrating the design model. It must always be checked that the forces from the anchorage reinforcement can be transferred to the main reinforcement of the concrete components. The recommended reinforcement includes only the reinforcement necessary to anchor the unit to the concrete. In the vicinity of the unit the element must be designed for the force R 1. STANDARDS The calculations are carried out in accordance with: Eurocode 2: Design of concrete structures. Part 1-1: General rules and rules for buildings. Eurocode 3: Design of steel structures. Part 1-1: General rules and rules for buildings. Eurocode 3: Design of steel structures. Part 1-8: Design of joints. EN 10080: Steel for the reinforcement of concrete. Weldable reinforcing steel. General. For all NDPs (Nationally Determined Parameter) in the Eurocodes the recommended values are used. NDP s are as follows: Parameter c s α cc α ct C Rd,c v min k 1 Recommended value Table 1: NDP-s in EC k 1/3 f ck 1/ Parameter M0 M1 M2 Recommended value Table 2: NDP-s in EC-3.

28 Design MEMO 54b Reinforcement design for RVK 101 Date: Sign: sss Page 3 of 9 QUALITIES Concrete grade C35/45: f ck = 35,0 MPa EC2, Table 3.1 f cd = α cc f ck /γ c = 1 35/1,5 = 23,3 MPa EC2, Pt.3.15 f ctd = α ct f ctk,0,05 /γ c = 1 2,20/1,5 = 1,46 MPa EC2, Pt.3.16 f bd = 2,25 η 1 η 2 f ctd = 2,25 0,7 1,0 1,46 = 2,3 MPa EC2, Pt Reinforcement B500C: Structural steel S355: DIMENSIONS f yd = f yk /γ s = 500/1,15 = 435 MPa Tension: f yd = f y / γ M0 = 355/1,0 = 355 MPa Compression: f yd = f y / γ M0 = 355/1,0 = 355 MPa Shear: f sd = f y /( M0 3) = 355/(1,0 3) = 205 MPa EC2, Pt Inner tube: HUP 100x50x6, Cold formed, S355 Outer tube: HUP 120x60x4, Cold formed, S355 LOADS Vertical ultimate limit state load = F V = 100kN.

29 Design MEMO 54b Reinforcement design for RVK 101 Date: Sign: sss Page 4 of 9 PART 2 - REINFORCEMENT EQUILIBRIUM Figure 1: Forces acting on the unit. F V = External force on the inner tube R 1i, R 2i = Internal forces between the inner and outer tubes. R 1, R 2, R 3 = Support reaction forces the outer tube. g= distance to the middle plane of the anchoring stirrups in front of the unit.

30 Design MEMO 54b Reinforcement design for RVK 101 Date: Sign: sss Page 5 of 9 I) Equilibrium inner tube: Figure 2: Forces acting on the inner tube. Equilibrium equations of the inner tube: 1): M=0: F v (L 1 -b-e) - R 1i (L 1 -b-a-g-e)=0 (1) 2): F y =0: F v -R 1i +R 2i =0 (2) Assuming nominal values: L 1 =295mm, a=75mm, b=35mm, g=40mm, e=10mm Solving R 1i from eq. 1: Fv ( L1 b e) R1 i (3) ( L b a g e) 1 Solving R 2i from eq. 2: R 2i = R 1i -F v (4) Results: 100kN ( ) mm R1 i kN ( ) mm R i 185.2kN 100kN 85. 2kN 2

31 Design MEMO 54b Reinforcement design for RVK 101 Date: Sign: sss Page 6 of 9 II) Equilibrium outer tube: Figure 3 Forces acting on the outer tube. Exact distribution of forces depends highly on the behavior of the outer tube. Both longitudinal bending stiffness and local transverse bending stiffness in the contact points between the inner and the outer tubes affects the equilibrium. Two situations are considered: 1) Rigid outer tube. Outer tube rotates as a stiff body. This assumption gives minimum reaction force at R 1, and maximum reaction force at R 2. R 3 becomes zero. (The force R 3 will actually be negative, but since no reinforcement to take the negative forces is included at this position, it is assumed to be zero.) Equilibrium equations of the outer tube: 1): M=0: (R 1i -R 1 ) (L-3-g-d) (R 2i -R 3 ) (L-3-g-c-d)=0 (5) 2): F y =0: R 2 +R 3 +R 1i - R 2i -R 1 =0 (6) Assuming nominal values: L=348mm, c=135mm, g=40mm, e=10mm, d=10mm ; (c=l 1 -b-a-g-e= =135mm, see Figure 1) Solving R 1 from eq. 5: ( R R ) ( L 3 g d) ( R (185.2 R ) ( ) (85.2 0) ( ) R R 1 1i kN 295 Solving R 2 from eq. 6: 2i R ) ( L 3 g c d) 0 3

32 Design MEMO 54b Reinforcement design for RVK 101 Date: Sign: sss Page 7 of 9 R R1 R2i R1 i R kN 2 2) Outer tube without bending stiffness. No forces transferred to outer tube at the back of inner tube. This assumption gives maximum reaction forces R 1 and R 3. R 2 becomes zero. The forces follow directly from the assumption: R 1 = R 1i R 3 = R 2i and R 2 =0 R R R kN 0kN 85.2kN The magnitude of the forces will be somewhere in between the two limits, and the prescribed reinforcement ensures integrity for both situations. Reinforcement is to be located at the assumed attack point for support reactions. Reinforcement for R 1, R 2 and R 3 : Figure 4: Forces. Reinforcement necessary to anchor the unit to the concrete: Reinforcement R 1 : A s1 = R 1 /f sd = 185.2kN/435Mpa =426 mm 2 Select 2-Ø12 = =452 mm 2 Capacity selected reinforcement: R=452 mm 2 435MPa=196.6kN Reinforcement R 3 : A s3 = R 3 /f sd = 85.2kN/435MPa =196 mm 2 Select 1-Ø12 = = 226 mm 2 Capacity selected reinforcement: R=226 mm 2 435MPa=98.3kN Reinforcement R 2 : A s2 = R 2 /f sd = 39kN/435MPa =89 mm 2 Select 1-Ø12 = = 226mm 2 Capacity selected reinforcement: R=226 mm 2 435MPa=98.3kN

33 Design MEMO 54b Reinforcement design for RVK 101 Date: Sign: sss Page 8 of 9 Tolerances on the positioning of the reinforcement: Due to the small internal distances, the magnitude of the forces will change when changing the position of the reinforcement. Thus, strict tolerances are required. Alt 1) Assume: L 1 =295mm, a=75mm, b=35mm, g=40+5=45mm, e=10mm Gives: 100kN( ) mm R kN ( ) mm R 192.3kN 100kN 92. 3kN 2 Alt 2) Assume: L 1 =295mm, a=75mm, b=35mm, g=40-5=35mm, e=10mm Gives: 100kN( ) mm R kN ( ) mm R 178.6kN 100kN kN 2 Alt 3) Assume: L 1 =295mm, a=75mm, b=35mm, g=40mm, e=10-5=5mm Gives: 100kN( ) mm R kN ( ) mm R 182.1kN 100kN 82. 1kN 2 Alt 4) Assume: L 1 =295mm, a=75mm, b=35mm, g=40mm, e=10+5=15mm Gives: 100kN( ) mm R kN ( ) mm R 188.5kN 100kN 88. 5kN 2

34 Design MEMO 54b Reinforcement design for RVK 101 Date: Sign: sss Page 9 of 9 Alt 5) Assume: L 1 =295mm, a=75mm, b=35mm, g=40+5=45mm, e=10+5=15mm Gives: 100kN( ) mm R1 196kN ( ) mm R 196kN 100kN 96kN 2 Conclusion tolerances: Alt 5 represents the most unfavorable position of reinforcement allowed without exceeding the reinforcement capacity. Thus, the assembling tolerances for P1, P2 and P4 should be ±5mm. For recommended reinforcement pattern, see Memo 55b. Transverse reinforcement: One transverse bar with the same diameter as the anchorage bar to be placed in the bend of every anchoring bar. Figure 5: Anchoring reinforcement.

35 Date: Sign: sss Design MEMO 55a Recommended reinforcement pattern RVK 41 Page 1 of 7 Figure 1: Recommended reinforcement pattern for RVK 41 units. Edge distance k>300mm. Figure 2: Recommended reinforcement pattern for RVK 41 units. Edge distance 160mm k 300mm. Ultimate limit load according to Figure 5.

36 Date: Sign: sss Design MEMO 55a Recommended reinforcement pattern RVK 41 Page 2 of 7 Figure 3: Recommended reinforcement pattern RVK 41. Slab thickness t<200mm and edge distance 160mm k 240mm. Ultimate limit load according to Figure 5. The following comments can be made in connection with the recommended reinforcement pattern shown in Figure 1: Reinforcement is illustrated in a slab with thickness 200mm, concrete cover 30mm and large edge distance. In the area marked c/c*), the tested elements (thickness t=150mm) were reinforced with P9 c/c 100mm along the whole edge. Two stirrups P9 to be placed closed to the unit. One on each side. Edge reinforcement P9 beyond the prescribed locations should be in accordance with calculations. However, according to EC 2 clauses 6.4.2(5) and , stirrups continuously along the edge are always recommended. Transverse reinforcement P5 in the bends of P9. When the concrete cover is 20mm, or less, the upper P5 bar can run above the 12mm round steel in front of the unit. With 30mm concrete cover, the upper P5 bar may have to be cut. Then, a straight bar P8 is to be placed transverse of the unit as illustrated, in overlap with P5. If possible, the P5 bar should be made continuously. The illustrated reinforcement is the necessary reinforcement required to transfer the forces in the unit to the concrete. It is not to be understood as the complete slab reinforcement. The main reinforcement for the slab/landings, inclusive edge reinforcement must be calculated in each case.

37 Date: Sign: sss Design MEMO 55a Recommended reinforcement pattern RVK 41 Page 3 of 7 The following comments can be made in connection with the recommended reinforcement pattern shown in Figure 2: Reinforcement is illustrated in a slab with thickness 150mm, concrete cover 20mm and edge distance 160mm. Notice the reduction in load in this case, see Figure 5. In the areas marked c/c*), the tested elements (thickness t=150mm) were reinforced with P10 c/c 150mm and P9 c/c 100mm along the two edges. Mesh reinforcement with transverse reinforcement P10 (closed bars) below. P10 runs above the unit, and below P1/P2. The mesh reinforcement may be replaced with straight bars with corresponding cross section area and c/c distance. When the unit is located at 300mm, or closer to the corner than 300mm, stirrups shall always be used along both edges as prescribed (P9/P10). The stirrups anchor the main reinforcement, and will in addition function as shear reinforcement in the slab. Edge reinforcement P9/P10 beyond the prescribed locations should be in accordance with calculations. However, according to EC 2 clauses 6.4.2(5) and , stirrups continuously along the edge are always recommended. P10 may be replaced with u-shaped stirrups in overlap with straight bars. The illustrated reinforcement is to be understood as a minimum of reinforcement which always should be found when the unit is located close to the corner. It is not to be understood as the complete slab reinforcement. The main reinforcement for the slab/landings, inclusive edge reinforcement must be calculated in each case. The following comments can be made in connection with the recommended reinforcement pattern shown in Figure 3: Reinforcement is illustrated in a slab with thickness 150mm, concrete cover 20mm and edge distance 160mm. In the areas marked c/c*), the tested elements (thickness t=150mm) were reinforced with P10 c/c 150mm and P9 c/c 150mm along the two edges. Mesh reinforcement with transverse reinforcement P10 (closed bars) below. P10 runs above the unit, and below P1/P2. The mesh reinforcement may be replaced with straight bars with corresponding cross section area and c/c distance. When the unit is located at 240mm, or closer to the corner than 240mm, stirrups P13 shall always be used in the corner area if utilizing the full unit capacity in slabs with thickness less than t=200mm. Transverse reinforcement 3Ø8 P5 behind the unit as illustrated. The illustrated reinforcement is to be understood as a minimum of reinforcement which always should be found. It is not to be understood as the complete slab reinforcement. The main reinforcement for the slab/landings, inclusive edge reinforcement must be calculated in each case.

38 Date: Sign: sss Design MEMO 55a Recommended reinforcement pattern RVK 41 Page 4 of 7 General comments in connection with both reinforcement patterns: Minimum slab thickness: t=150mm. Notice the reduction in load when the slab thickness is less than 200mm, the unit is located closer to the corner than 240mm and no additional shear reinforcement is introduced, see Figure 5. P1 and P2 to be placed directly onto the top of the unit, with the 12mm round steel positioned in the bend of P1/P2. It is recommended to spot weld P1 and P2 to the unit in order to ensure the correct position. Position, shape and anchorage of the stirrups P1 and P2 in the front is the governing factor concerning force transfer from the unit to the slab. Exact and careful detailing is therefore important. Inaccuracy may cause minor concrete cracks to develop before activating the reinforcement as assumed. Transverse reinforcement in the bend of P1/P2 (P5). P5 shall have the same diameter as P1/P2 and should run along the whole width of the slab. The transverse reinforcement P5 may be a part of the main transverse reinforcement and should have proper anchoring on the outside of the unit on both sides, especially towards the edge. This may require anchoring of P5 with an upward bend, or u-shaped bars. The required anchoring must be evaluated in every case. P1 and P2 should be anchored to the maximum depth, depending on the slab thickness. The inner width of the stirrups P1 and P2 should correspond to the width of the outer tube. This in order to have the most direct transfer of forces from the outer tube to the vertical legs of the stirrups. The main reinforcement of the slab should have sufficient overlap with P1 and P2. This is illustrated with four straight bars P12. The total amount of main reinforcement must be calculated in each case. All recommended reinforcement assumed to continue beyond the boundary of the illustrated area shall have a proper anchoring on the outside of the area. Thus, the reinforcement should continue at least one anchoring length outside the illustrated area, or be anchored by hooks. Shear reinforcement due to punching shear according to EC 2, clause

39 Date: Sign: sss Design MEMO 55a Recommended reinforcement pattern RVK 41 Page 5 of 7 Tolerances on location of anchoring bars: Figure 4: Tolerances P1, P2 and P4. Figure 5: Slab thickness and load limitations. The coloured arrows refer to the recommended reinforcement patterns at different edge distances, as given in above Figures. The colour of the arrow giving the recommended reinforcement pattern corresponds to the colour of the line giving the load limitation. (In Memo 52, Figure 2, the load limitation is illustrated alone, without the arrows and references to reinforcement pattern)

40 Date: Sign: sss Design MEMO 55a Recommended reinforcement pattern RVK 41 Page 6 of 7 Pos Diameter Cutting Nr. Pr length unit P1 8 1 Bar schedule Grade B500C P2 8 1 Mandrel diameter=20mm (if this is in accordance with national regulations.) h=decided locally, but as deep as possible. Normally: Slab thickness - 30mm - national rules for concrete cover. If the mandrel diameter is 4xØ (in accordance with EC-2) the width should be increased to 84mm to ensure good contact between the stirrups and the round steel. The contact point should be in approximate 45degrees from the centre of the round steel, and in the middle of the curved part of the stirrup. B500C P4 8 2 Mandrel diameter=20mm (if this is in accordance with national regulations.) h=decided locally, but as deep as possible. Normally: Slab thickness - 30mm - national rules for concrete cover. If the mandrel diameter is 4xØ (in accordance with EC-2) the widths should be increased to respectively 84mm and 104 mm to ensure good contact between the stirrups and the round steel. The contact point should be in approximate 45degrees from the centre of the round steel, and in the middle of the curved part of the stirrup. B500C P ) + 7 2) + h= Decided locally. Normally: Slab thickness 20mm 2 x national rules for concrete cover. B500C Normally: Width of slab 2 x national rules for concrete cover. P B500C

41 Date: Sign: sss Design MEMO 55a Recommended reinforcement pattern RVK 41 Page 7 of 7 Pos Diameter Cutting Nr. Pr length unit P Bar schedule Grade B500C P8 8 1 Slab thickness t=150mm: There is not enough space for the bars, and they don t need to be used. B500C P ) + 6 2) + Normally: Width of slab 2 x national rules for concrete cover. Alternatively u-shaped or closed stirrups may be used. B500C P ), 2) + h= Decided locally. Normally: Slab thickness 30mm 2 x national rules for concrete cover. Recommended along whole edge. B500C P11 P ) + 6 2) + P ) h= Decided locally. Normally: Slab thickness 2 x national rules for concrete cover thickness of mesh reinforcement. Minimum mesh reinforcement K131, or main reinforcement in both directions with corresponding cross section area and c/c. The amount of main reinforcement must be according to calculations in each case. Minimum 4xØ8 in overlap with P1/P2 as illustrated. Normally: Length of slab 2 x national rules for concrete cover B500C B500C B500C h= Decided locally. Normally: Slab thickness 2 x national rules for concrete cover thickness of mesh reinforcement. 1) Edge distance 300mm 2) Edge distance 240mm, slab thickness t<200mm. Table 1: List of reinforcement RVK 41.

42 Date: Sign: sss Last Rev: Sign: sss Design Doc.no: Page 1 of 8 MEMO 55b Recommended reinforcement pattern RVK 101 Figure 1: Recommended reinforcement pattern for RVK 101 units. Slab thickness t=265mm and edge distance k>450mm. Slab thickness t=200mm and edge distance k>400mm. Figure 2: Recommended reinforcement pattern for RVK 101 units. Slab thickness t=265mm and edge distance 180mm k 450mm. Slab thickness t=200mm and edge distance 180mm k 400mm. Ultimate limit load according to Figure 5.

43 Date: Sign: sss Last Rev: Sign: sss Design Doc.no: Page 2 of 8 MEMO 55b Recommended reinforcement pattern RVK 101 Figure 3: Recommended reinforcement pattern for RVK 101 units. Slab thickness t<265mm and edge distance 180mm k<300mm. Ultimate limit load according to Figure 5.

44 Date: Sign: sss Last Rev: Sign: sss Design Doc.no: Page 3 of 8 MEMO 55b Recommended reinforcement pattern RVK 101 The following comments can be made in connection with the recommended reinforcement pattern shown in Figure 1: Reinforcement is illustrated in a slab with thickness 265mm, concrete cover 30mm and large edge distance. In the area marked c/c*), the tested elements (thickness t=265mm) were reinforced with P9 c/c 150mm along the whole edge. Two stirrups P9 to be placed closed to the unit. One on each side. Edge reinforcement P9 beyond the prescribed locations should be in accordance with calculations. However, according to EC 2 clauses 6.4.2(5) and , stirrups continuously along the edge are always recommended. Transverse reinforcement P5 in the bends of P9. When the concrete cover is 25mm, or less, the upper P5 bar can run above the half round steel in front of the unit. With 30mm concrete cover, the upper P5 bar may have to be cut. Then, a straight bar P8 is to be placed transverse of the unit as illustrated, in overlap with P5. If possible, the P5 bar should be made continuously. The illustrated reinforcement is the necessary reinforcement required to transfer the forces in the unit to the concrete. It is not to be understood as the complete slab reinforcement. The main reinforcement for the slab/landings, inclusive edge reinforcement must be calculated in each case. The following comments can be made in connection with the recommended reinforcement pattern shown in Figure 2: Reinforcement is illustrated in a slab with thickness 265mm, concrete cover 30mm and edge distance 180mm. In the areas marked c/c*), the tested elements (thickness t=265mm) were reinforced with P10 c/c 150mm and P9 c/c 150mm along the two edges. Mesh reinforcement with transverse reinforcement P10 (closed bars) below. P10 runs above the unit, and below P1/P2. The mesh reinforcement may be replaced with straight bars with corresponding cross section area and c/c distance. Slab thickness t=200mm: When the unit is located at 400mm, or closer to the corner than 400mm, stirrups shall always be used along both edges as prescribed (P9/P10). Slab thickness t=265mm: When the unit is located at 450mm, or closer to the corner than 450mm, stirrups shall always be used along both edges as prescribed (P9/P10). These stirrups anchor the main reinforcement, and will in addition function as shear reinforcement in the slab. Edge reinforcement P9/P10 beyond the prescribed locations should be in accordance with calculations. However, according to EC 2 clauses 6.4.2(5) and , stirrups continuously along the edge are always recommended. P10 may be replaced with u-shaped stirrups in overlap with straight bars. The illustrated reinforcement is to be understood as a minimum of reinforcement which always should be found when the unit is located close to the corner. It is not to be understood as the complete slab

45 Date: Sign: sss Last Rev: Sign: sss Design Doc.no: Page 4 of 8 MEMO 55b Recommended reinforcement pattern RVK 101 reinforcement. The main reinforcement for the slab/landings, inclusive edge reinforcement must be calculated in each case. The following comments can be made in connection with the recommended reinforcement pattern shown in Figure 3: Reinforcement is illustrated in a slab with thickness 200mm, concrete cover 30mm and edge distance 180mm. Notice the reduction in load in this case, see Figure 5. In the areas marked c/c*), the tested elements (thickness t=200mm) were reinforced with P10 c/c 150mm and P9 c/c 100mm along the two edges. Mesh reinforcement with transverse reinforcement P10 (closed bars) below. P10 runs above the unit, and below P1/P2. The mesh reinforcement may be replaced with straight bars with corresponding cross section area and c/c distance. Slab thickness t=200mm: When the unit is located at 400mm, or closer to the corner than 400mm, stirrups shall always be used along both edges as prescribed (P9/P10). Slab thickness t=265mm: When the unit is located at 450mm, or closer to the corner than 450mm, stirrups shall always be used along both edges as prescribed (P9/P10). These stirrups anchor the main reinforcement, and will in addition function as shear reinforcement in the slab. Edge reinforcement P9/P10 beyond the prescribed locations should be in accordance with calculations. However, according to EC 2 clauses 6.4.2(5) and , stirrups continuously along the edge are always recommended. When the slab thickness is less than 265mm, and the unit is located closer to the corner than 300mm, stirrups P13 (shear reinforcement) may be used in the corner area, as illustrated, to increase the concrete capacity, see Figure 5. P10 may be replaced with u-shaped stirrups in overlap with straight bars. Transverse reinforcement 4Ø12 P5 behind the unit as illustrated. The illustrated reinforcement is to be understood as a minimum of reinforcement which always should be found when the unit is located close to the corner. However, is not to be understood as the complete slab reinforcement. The main reinforcement for the slab/landings, inclusive edge reinforcement must be calculated in each case. General comments in connection with all reinforcement patterns: Minimum slab thickness: t=200mm. Notice the reduction in load, see Figure 5. P1 and P2 to be placed directly onto the unit, with the half round steel at top of the unit positioned in the bend of P1/P2. It is recommended to spot weld P1 and P2 to the unit in order to ensure the correct position. Position, shape and anchorage of the stirrups P1 and P2 in the front is the governing factor concerning force transfer from the unit to the slab. Exact and careful detailing is therefore important. Inaccuracy may cause minor concrete cracks to develop before activating the reinforcement as assumed.

46 Date: Sign: sss Last Rev: Sign: sss Design Doc.no: Page 5 of 8 MEMO 55b Recommended reinforcement pattern RVK 101 Transverse reinforcement in the bend of P1/P2 (P5). P5 shall have the same diameter as P1/P2 and should run along the whole width of the slab. The transverse reinforcement P5 may be a part of the main transverse reinforcement and should have proper anchoring on the outside of the unit on both sides, especially towards the edge. This may require anchoring of P5 with an upward bend, or u-shaped bars. The required anchoring must be evaluated in every case. P1 and P2 should be anchored to the maximum depth, depending on the slab thickness. The inner width of the stirrups P1 and P2 should correspond to the width of the outer tube. This in order to have the most direct transfer of forces from the outer tube to the vertical legs of the stirrups. The main reinforcement of the slab should have sufficient overlap with P1 and P2. This is illustrated with four straight bars P12. The total amount of main reinforcement must be calculated in each case. All recommended reinforcement assumed to continue beyond the boundary of the illustrated area shall have a proper anchoring on the outside of the area. Thus, the reinforcement should continue at least one anchoring length outside the illustrated area, or be anchored by hooks. Shear reinforcement due to punching shear according to EC 2, clause Tolerances on location of anchoring bars: Figure 4: Tolerances P1, P2 and P4.

European Technical Approval No. ETA-12/0056

European Technical Approval No. ETA-12/0056 SINTEF Building and Infrastructure P.O.Box 124 Blindern N-0314 Oslo Tel. 47 22 96 55 55 Fax 47 22 69 94 38 Authorised and notified according to Article 10 of the Council Directive 89/106/EEC of 21 December

More information

CAPACITIES AND MAIN DIMENSIONS TSS 41/TSS 101

CAPACITIES AND MAIN DIMENSIONS TSS 41/TSS 101 Dato: 26.04.2011 Sign.: sss TSS 41 / TSS 101 Siste rev.: 20.06.2018 Sign.: jb CAPACITIES AND MAIN DIMENSIONS Dok. nr.: K3-11/53E Control: ps PLANNING CAPACITIES AND MAIN DIMENSIONS TSS 41/TSS 101 The TSS-unit

More information

CUAP 06.02/13. Blind rivets for metal members and sheeting

CUAP 06.02/13. Blind rivets for metal members and sheeting CUAP 06.02/13 Common Understanding of Assessment Procedure for European Technical Approval according to Article 9.2 of the Construction Products Directive Blind rivets for metal members and sheeting Version

More information

European Technical Approval ETA-05/0069

European Technical Approval ETA-05/0069 European Technical Approval ETA-05/0069 - Original version in German language Handelsbezeichnung Trade name Zulassungsinhaber Holder of approval Zulassungsgegenstand und Verwendungszweck Generic type and

More information

European Technical Approval No. ETA-06/0170

European Technical Approval No. ETA-06/0170 SINTEF Building and Infrastructure P.O.Box 124 Blindern N-0314 Oslo Tel. 47 22 96 55 55 Fax 47 22 69 54 38 Authorised and notified according to Article 10 of the Council Directive 89/106/EEC of 21 December

More information

European Technical Approval ETA-12/0456

European Technical Approval ETA-12/0456 European Technical Approval ETA-12/0456 - Original version in German language Handelsbezeichnung Trade name Zulassungsinhaber Holder of approval Zulassungsgegenstand und Verwendungszweck Generic type and

More information

European Technical Assessment. ETA-15/0540 of Member of. General part

European Technical Assessment. ETA-15/0540 of Member of. General part INSTITU Schenkenstrasse 4 T +43 1 533 65 50 1010 Vienna Ι Austria F +43 1 533 64 23 www.oib.or.at Ι mail@oib.or.at Designated according to Article 29 of Regulation (EU) No 305/2011 Member of www.eota.eu

More information

(English language translation, the original version is in Czech language) DEWALT BSC-PBZ-PRO. DeWalt Black & Decker Str Idstein Germany

(English language translation, the original version is in Czech language) DEWALT BSC-PBZ-PRO. DeWalt Black & Decker Str Idstein Germany TECHNICKÝ A ZKUŠEBNÍ ÚSTAV STAVEBNÍ PRAHA, s.p. Prosecká 811/76a CZ-190 00 Praha 9 Tel.: +420 286 019 458 Internet: www.tzus.cz Authorised and notified according to Article 10 of the Council Directive

More information

European Technical Assessment ETA-10/0422 of 08/01/2016

European Technical Assessment ETA-10/0422 of 08/01/2016 ETA-Danmark A/S Göteborg Plads 1 DK-2150 Nordhavn Tel. +45 72 24 59 00 Fax +45 72 24 59 04 Internet www.etadanmark.dk Authorised and notified according to Article 29 of the Regulation (EU) No 305/2011

More information

Österreichisches Institut für Bautechnik Schenkenstrasse Vienna Austria T F

Österreichisches Institut für Bautechnik Schenkenstrasse Vienna Austria T F Authorised and notified according to Article 10 of the Council Directive 89/ 106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating

More information

European Technical Assessment ETA-10/0067 of

European Technical Assessment ETA-10/0067 of European Technical Assessment ETA-10/0067 of 09.07.2015 GENERAL PART Technical Assessment Body issuing the European Technical Assessment Trade name of the construction product Product family to which the

More information

How to calculate anchorage and lap lengths to Eurocode 2

How to calculate anchorage and lap lengths to Eurocode 2 How to calculate anchorage and lap lengths to Eurocode 2 This is the first in a series of articles, previously printed in The Structural Engineer magazine, which will be collated to form a Concrete Structures

More information

European Technical Approval

European Technical Approval INSTYTUT TECHNIKI BUDOWLANEJ PL 00-611 WARSZAWA ul. FILTROWA 1 tel.: (48 22) 825-04-71; (48 22) 825-76-55; fax: (48 22) 825-52-86; www.itb.pl Członek EOTA European English language translation - the original

More information

European Technical Approval ETA-02/0030

European Technical Approval ETA-02/0030 European Technical Approval ETA-02/0030 - Original version in German language Handelsbezeichnung Trade name Zulassungsinhaber Holder of approval Zulassungsgegenstand und Verwendungszweck Generic type and

More information

European Technical Approval ETA-07/0025

European Technical Approval ETA-07/0025 European Technical Approval ETA-07/0025 - Original version in German language Handelsbezeichnung Trade name Zulassungsinhaber Holder of approval Zulassungsgegenstand und Verwendungszweck Generic type and

More information

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)

More information

European Technical Approval ETA-06/0238

European Technical Approval ETA-06/0238 British Board of Agrément P O Box 195 Bucknalls Lane Garston, Watford Herts WD25 9BA Tel: + 44 (0)1923 665300 Fax: + 44 (0)1923 665301 e-mail: mail@bba.star.co.uk Authorised and notified according to Article

More information

European Technical Approval ETA 13/0438

European Technical Approval ETA 13/0438 LABORATÓRIO NACIONAL DE ENGENHARIA CIVIL, I. P. Av. do Brasil, 101 1700-066 LISBOA PORTUGAL phone: (351) 21 844 30 00 fax: (351) 21 844 43 01 e-mail: lnec@lnec.pt www.lnec.pt Authorised a n d n o t i f

More information

European Technical Assessment. ETA-18/0083 of Member of. General part

European Technical Assessment. ETA-18/0083 of Member of. General part INSTITU Schenkenstrasse 4 T +43 1 533 65 50 1010 Vienna Ι Austria F +43 1 533 64 23 www.oib.or.at Ι mail@oib.or.at Designated according to Article 29 of Regulation (EU) No 305/2011 Member of www.eota.eu

More information

European Technical Approval ETA-13/0520

European Technical Approval ETA-13/0520 Centre Scientifique et Technique du Bâtiment 84 avenue Jean Jaurès CHAMPS-SUR-MARNE F-77447 Marne-la-Vallée Cedex 2 Tél. : (33) 01 64 68 82 82 Fax : (33) 01 60 05 70 37 Autorisé et notifié conformément

More information

European Technical Approval ETA-13/0623

European Technical Approval ETA-13/0623 SITAC Box 553 SE 371 23 Karlskrona SWEDEN MEMBER OF EOTA Tfn.: +46-(0)10-516 63 00 Fax: +46-(0)455-206 88 E-mail: info@sitac.se European Technical Approval ETA-13/0623 Handelsnamn Trade name Papiruld/Envinsu

More information

European Technical Approval ETA 11/0243

European Technical Approval ETA 11/0243 Centre Scientifique et Technique du Bâtiment 84 avenue Jean Jaurès CHAMPS-SUR-MARNE F-77447 Marne-la-Vallée Cedex 2 Tél. : (33) 0 64 68 82 82 Fax : (33) 0 60 05 70 37 Autorisé et notifié conformément à

More information

European Technical Approval ETA-13/0078

European Technical Approval ETA-13/0078 SITAC Box 553 SE 371 23 Karlskrona SWEDEN MEMBER OF EOTA Tfn.: +46-(0)10-516 63 00 Fax: +46-(0)455-206 88 E-mail: info@sitac.se European Technical Approval ETA-13/0078 Handelsnamn Trade name Innehavare

More information

Trade name EZ-Path Fire-Rated Pathway (Series 33 and Series 44+) Cable Penetration Seals

Trade name EZ-Path Fire-Rated Pathway (Series 33 and Series 44+) Cable Penetration Seals UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. Phone : +44 1483 302130 Fax : +44 1483 302230 Email : Inform.NB@uk.ul.com Website

More information

Precast concrete composite wall with point connectors

Precast concrete composite wall with point connectors EAD 010001-00-0301 April 2015 Precast concrete composite wall with point connectors 2015 European Assessment Document - EAD 010001-00-0301 2/24 The reference title and language for this EAD is English.

More information

European Technical Assessment. ETA-11/0135 of Member of. General part

European Technical Assessment. ETA-11/0135 of Member of. General part INSTITU Schenkenstrasse 4 T +43 1 533 65 50 1010 Vienna Ι Austria F +43 1 533 64 23 www.oib.or.at Ι mail@oib.or.at Designated according to Article 29 of Regulation (EU) No 305/2011 Member of www.eota.eu

More information

European Technical Approval ETA-08/0058

European Technical Approval ETA-08/0058 ETA-Danmark A/S Kollegievej 6 DK-2920 Charlottenlund Tel. +45 72 24 59 00 Fax +45 72 24 59 04 Internet www.etadanmark.dk Authorised and notified according to Article 10 of the Council Directive 89/106/EEC

More information

European Technical Approval ETA-03/0014

European Technical Approval ETA-03/0014 British Board of Agrément Bucknalls Lane Garston Watford Herts WD25 9BA Tel: + 44 (0) 1923 665300 Fax: + 44 (0) 1923 665301 e-mail: mail@bba.star.co.uk Authorised and notified according to Article 10 of

More information

(English language translation, the original version is in French language) JIPÉCO. JIPÉ Réunion

(English language translation, the original version is in French language) JIPÉCO. JIPÉ Réunion Centre Scientifique et Technique du Bâtiment 84 avenue Jean Jaurès CHAMPS-SUR-MARNE F-77447 Marne-la-Vallée Cedex 2 Tél. : (33) 01 64 68 82 82 Fax : (33) 01 60 05 70 37 Autorisé et notifié conformément

More information

This European technical approval

This European technical approval Authorised and notified according to Article 10 of the Council Directive 89/ 106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating

More information

Technical Assessment Body issuing the ETA: Kiwa Nederland B.V. Sinh Board

Technical Assessment Body issuing the ETA: Kiwa Nederland B.V. Sinh Board Member of Kiwa Nederland B.V. www.eota.eu Sir Winston Churchilllaan 273 NL-2288 EA Rijswijk Postbus 70 NL-2280 AB Rijswijk Tel.: +31 (0)88 998 44 00 Fax: +31 (0)88 998 44 20 E-mail: info@kiwa.nl European

More information

(English language translation, the original version is in French language) MODULISO

(English language translation, the original version is in French language) MODULISO Centre Scientifique et Technique du Bâtiment 84 avenue Jean Jaurès CHAMPS-SUR-MARNE F-77447 Marne-la-Vallée Cedex 2 Tél. : (33) 01 64 68 82 82 Fax : (33) 01 60 05 70 37 Autorisé et notifié conformément

More information

European Technical Assessment. ETA-18/0041 of Member of. General part

European Technical Assessment. ETA-18/0041 of Member of. General part INSTITU Schenkenstrasse 4 T +43 1 533 65 50 1010 Vienna Ι Austria F +43 1 533 64 23 www.oib.or.at Ι mail@oib.or.at Designated according to Article 29 of Regulation (EU) No 305/2011 Member of www.eota.eu

More information

R-Group Finland Oy. RLA Lifting Inserts Technical Manual According to Eurocodes, EU Machinery directive 2006/42/EC and VDI/BV-BS 6205 CE Approved

R-Group Finland Oy. RLA Lifting Inserts Technical Manual According to Eurocodes, EU Machinery directive 2006/42/EC and VDI/BV-BS 6205 CE Approved R-Group Finland Oy RLA Lifting Inserts Technical Manual According to Eurocodes, EU Machinery directive 2006/42/EC and VDI/BV-BS 6205 CE Approved 16.8.2017 2 Table of Contents 1 DESCRIPTION OF THE SYSTEM...

More information

TECHNICAL MANUAL. TENLOC Panel Connector. Hidden Latch Connection for Precast Panels

TECHNICAL MANUAL. TENLOC Panel Connector. Hidden Latch Connection for Precast Panels TECHNICAL MANUAL TENLOC Panel Connector Hidden Latch Connection for Precast Panels Version: Peikko Group 06/2018 TENLOC Panel Connector Fast connection for precast elements TENLOC Panel Connector is a

More information

European Technical Assessment. ETA-12/0398 of 29/12/2017. General Part. Instytut Techniki Budowlanej. Technical Assessment Body issuing the

European Technical Assessment. ETA-12/0398 of 29/12/2017. General Part. Instytut Techniki Budowlanej. Technical Assessment Body issuing the European Technical Assessment General Part of 29/12/2017 (English language translation the original version is in Polish language) Body issuing the European Trade name of the construction product Product

More information

SINTEF Building and Infrastructure confirms that. HRC 700 cast-in connection system

SINTEF Building and Infrastructure confirms that. HRC 700 cast-in connection system SINTEF Certification No. 20072 Issued t: 26.11.2010 Revised: 05.10.2015 Valid until: 01.01.2021 Page: 1 of 5 SINTEF Building and Infrastructure confirms that HRC 700 cast-in connection system has been

More information

Rakennustuotedirektiivin (89/106/EEC) artiklan 10, neuvoston direktiivi 21. joulukuuta 1988, mukaisesti notifioitu tuotehyväksyntälaitos EOTAN JÄSEN

Rakennustuotedirektiivin (89/106/EEC) artiklan 10, neuvoston direktiivi 21. joulukuuta 1988, mukaisesti notifioitu tuotehyväksyntälaitos EOTAN JÄSEN Page 1 of European Technical Approval ETA 08/0018 VTT Valtion Teknillinen Tutkimuskeskus PL 1000 02044 VTT Puh. +358 20 722 4911 Telekopio +358 20 722 7003 Rakennustuotedirektiivin (89/106/EEC) artiklan

More information

BSF - DESIGN OF REINFORCEMENT, CANTILEVERED BEAM- BEAM

BSF - DESIGN OF REINFORCEMENT, CANTILEVERED BEAM- BEAM MEMO 55 BSF - DESIGN OF REINFORCEMENT, CANTILEVERED BEAM-BEAM Dato: Siste rev.: Dok. nr.: 1.10.013 4.05.016 K4-10/55E Sign.: Sign.: Control: sss sss ps DESIGN BSF - DESIGN OF REINFORCEMENT, CANTILEVERED

More information

European Technical Approval No. ETA-08/0285

European Technical Approval No. ETA-08/0285 SINTEF Building and Infrastructure P.O.Box 124 Blindern N-0314 Oslo Tel. 47 22 96 55 55 Fax 47 22 69 54 38 Authorised and notified according to Article 10 of the Council Directive 89/106/EEC of 21 December

More information

THERMOFLOC. Peter Seppele GmbH Bahnhofstrasse 79 A 9710 Feistritz/Drau

THERMOFLOC. Peter Seppele GmbH Bahnhofstrasse 79 A 9710 Feistritz/Drau European Technical Approval (English language translation, the original version is in German language) ETA-05/0186 Handelsbezeichnung Trade name THERMOFLOC Zulassungsinhaber Holder of approval Peter Seppele

More information

European Technical Assessment ETA-14/0354 of

European Technical Assessment ETA-14/0354 of European Technical Assessment ETA-14/0354 of 20.02.2015 GENERAL PART Technical Assessment Body issuing the European Technical Assessment Trade name of the construction product Product family to which the

More information

The nominal cover can be assessed as follows: C nom

The nominal cover can be assessed as follows: C nom Detailing and durability requirements are to ensure that a structure has satisfactory durability and serviceability performance under normal circumstances throughout its lifetime. These requirements will

More information

EN REINFORCED MASONRY DESIGN EXAMPLE 1 (NOTE: THIS USES THE UK NATIONAL ANNEX NDP VALUES)

EN REINFORCED MASONRY DESIGN EXAMPLE 1 (NOTE: THIS USES THE UK NATIONAL ANNEX NDP VALUES) 42.50 10.00 3.00 20.00 EN 1996-1-1 REINFORCED MASONRY DESIGN EXAMPLE 1 (NOTE: THIS USES THE UK NATIONAL ANNEX NDP VALUES) Reinforced Masonry - Reinforced Brickwork Stem Cantilever Pocket-Type Retaining

More information

SUMO Wall Shoe. For bolted wall connections. Technical Manual. Version: Canada and United States 08/2016

SUMO Wall Shoe. For bolted wall connections. Technical Manual. Version: Canada and United States 08/2016 Wall Shoe For bolted wall connections Version: Canada and United States 08/2016 Technical Manual Wall Shoe For bolted wall connections Strong tensile connection: enables shear walls to be built of precast

More information

R-Group Finland Oy. REA Lifting Inserts Technical Manual According to Eurocodes, EU Machinery directive 2006/42/EC and VDI/BV-BS 6205 CE Approved

R-Group Finland Oy. REA Lifting Inserts Technical Manual According to Eurocodes, EU Machinery directive 2006/42/EC and VDI/BV-BS 6205 CE Approved R-Group Finland Oy REA Lifting Inserts Technical Manual According to Eurocodes, EU Machinery directive 2006/42/EC and VDI/BV-BS 6205 CE Approved 10.2.2017 2 Table of Contents 1 DESCRIPTION OF THE SYSTEM...

More information

Date of update January 25, 2018 Valid until

Date of update January 25, 2018 Valid until CERTIFICATE PRODUCT APPLICATION VTT-C-4805-09 Date of update January 25, 2018 Valid until 12.10.2020 U Protect fire insulation solutions for ventilation ducts MANUFACTURER Saint-Gobain Finland Oy / ISOVER

More information

(English language translation, the original version is in French language) SPIT HIT M. Société SPIT Route de Lyon. France 05/12/ /12/2016

(English language translation, the original version is in French language) SPIT HIT M. Société SPIT Route de Lyon. France 05/12/ /12/2016 Centre Scientifique et Technique du Bâtiment 84 avenue Jean Jaurès CHAMPS-SUR-MARNE F-77447 Marne-la-Vallée Cedex 2 Tel. : (33) 01 64 68 82 82 Fax : (33) 01 60 05 70 37 Autorisé et notifié conformément

More information

COLUMN SHOES HPKM, PPKM, PEC

COLUMN SHOES HPKM, PPKM, PEC COLUMN SHOES HPKM, PPKM, PEC Version 9/2007 (Update 7/2009) Replaces brochure /2006 HPKM, PPKM, PEC -column shoes Benefits of Peikko -column joints Saves time, costs and materials Easy and fast adjustments

More information

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)

More information

ETA-11/0141 of 08/08/2016. European Technical Assessment. General Part. Technical Assessment Body issuing the. Instytut Techniki Budowlanej

ETA-11/0141 of 08/08/2016. European Technical Assessment. General Part. Technical Assessment Body issuing the. Instytut Techniki Budowlanej INSTYTUT TECHNIKI BUDOWLANEJ PL 00-611 WARSZAWA ul. Filtrowa 1 tel.: (+48 22) 825-04-71 (+48 22) 825-76-55 fax: (+48 22) 825-52-86 www.itb.pl European Technical Assessment of 08/08/2016 General Part (English

More information

ETA-07/0291 of 30/06/2014. European Technical Assessment. Draft. General Part. Technical Assessment Body issuing the. Instytut Techniki Budowlanej

ETA-07/0291 of 30/06/2014. European Technical Assessment. Draft. General Part. Technical Assessment Body issuing the. Instytut Techniki Budowlanej 25 INSTYTUT TECHNIKI BUDOWLANEJ PL 00-611 WARSZAWA ul. Filtrowa 1 tel.: (+48 22) 825-04-71 (+48 22) 825-76-55 fax: (+48 22) 825-52-86 www.itb.pl Draft Designated according to Article 29 of Regulation (EU)

More information

European Technical Approval ETA-11/0182

European Technical Approval ETA-11/0182 European Technical Approval ETA-11/0182 - Original version in German language Handelsbezeichnung Trade name Zulassungsinhaber Holder of approval Zulassungsgegenstand und Verwendungszweck Generic type and

More information

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)

More information

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)

More information

BS EN :2004 EN :2004 (E)

BS EN :2004 EN :2004 (E) Contents List 1. General 1.1 Scope 1.1.1 Scope of Eurocode 2 1.1.2 Scope of Part 1-1 of Eurocode 2 1.2 Normative references 1.2.1 General reference standards 1.2.2 Other reference standards 1.3 Assumptions

More information

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)

More information

European Technical Assessment ETA-14/0392 of 04/12/2014

European Technical Assessment ETA-14/0392 of 04/12/2014 ETA-Danmark A/S Göteborg Plads 1 DK-2150 Nordhavn Tel. +45 72 24 59 00 Fax +45 72 24 59 04 Internet ww.etadanmark.dk Authorised and notified according to Article 29 of the Regulation (EU) No 305/2011 of

More information

European Technical Approval

European Technical Approval INSTYTUT TECHNIKI BUDOWLANEJ PL 00-611 WARSZAWA ul. FILTROWA 1 tel.: (48 22) 825-04-71; (48 22) 825-76-55; fax: (48 22) 825-52-86; www.itb.pl Członek EOTA European English language translation - the original

More information

(English language translation, the original version is in French language) SPIT ISO. Société SPIT Route de Lyon. France 04/01/ /01/2015

(English language translation, the original version is in French language) SPIT ISO. Société SPIT Route de Lyon. France 04/01/ /01/2015 Centre Scientifique et Technique du Bâtiment 84 avenue Jean Jaurès Champs sur Marne F-77447 Marne-la-Vallée Cedex 2 Tél. : (33) 01 64 68 82 82 Fax : (33) 01 60 05 70 37 Autorisé et notifié conformément

More information

(English language translation, the original version is in French language) SORMAT LYT. SORMAT OY Harjutie 5 FIN Rusko Finlande

(English language translation, the original version is in French language) SORMAT LYT. SORMAT OY Harjutie 5 FIN Rusko Finlande Centre Scientifique et Technique du Bâtiment 84 avenue Jean Jaurès CHAMPS-SUR-MARNE F-77447 Marne-la-Vallée Cedex 2 Tel. : (33) 01 64 68 82 82 Fax : (33) 01 60 05 70 37 Autorisé et notifié conformément

More information

SINTEF Building and Infrastructure confirms that. Separating floors with Hunton Silencio 36 / Hunton Silencio Thermo

SINTEF Building and Infrastructure confirms that. Separating floors with Hunton Silencio 36 / Hunton Silencio Thermo SINTEF Certification No. 2330 Issued t: 18.02.2002 Revised: 17.06.2013 Valid until: 01.07.2018 Page: 1 of 5 SINTEF Building and Infrastructure confirms that Separating floors with Hunton Silencio 36 /

More information

(English language translation, the original version is in French language) SPIT FIX3. Société Spit Route de Lyon F BOURG-LES-VALENCE France

(English language translation, the original version is in French language) SPIT FIX3. Société Spit Route de Lyon F BOURG-LES-VALENCE France Centre Scientifique et Technique du Bâtiment 84 avenue Jean Jaurès CHAMPSSURMARNE F77447 MarnelaVallée Cedex 2 Tél. : (33) 01 64 68 82 82 Fax : (33) 01 60 05 70 37 Autorisé et notifié conformément à l

More information

European Technical Assessment ETA 12/0018 of 14/08/2018

European Technical Assessment ETA 12/0018 of 14/08/2018 RISE Research Institutes of Sweden AB RISE Certifiering Box 553 SE-371 23 Karlskrona Sweden Member of www.eota.eu Tel: +46 10 516 63 00 Web: www.ri.se/eta Mail: certifiering@ri.se European Technical Assessment

More information

ITW Construction Products Italy S.r.l. V.le Regione Veneto, PADOVA (PD) ITALIEN. V.le Regione Veneto, PADOVA (PD) ITALIEN

ITW Construction Products Italy S.r.l. V.le Regione Veneto, PADOVA (PD) ITALIEN. V.le Regione Veneto, PADOVA (PD) ITALIEN European Technical Assessment ETA-13/1068 of 28 February 2014 General Part Technical Assessment Body issuing the European Technical Assessment: Trade name of the construction product Product family to

More information

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)

More information

European Technical Approval ETA-13/0689

European Technical Approval ETA-13/0689 ETA-Danmark A/S Kollegievej 6 DK-2920 Charlottenlund Tel. +45 72 24 59 00 Fax +45 72 24 59 04 Internet www.etadanmark.dk Authorised and notified according to Article 10 of the Council Directive 89/106/EEC

More information

HIGH PERFORMANCE REINFORCEMENT PRODUCTS. Product Catalogue.

HIGH PERFORMANCE REINFORCEMENT PRODUCTS. Product Catalogue. HIGH PERFORMANCE REINFORCEMENT PRODUCTS Product Catalogue www.hrc-europe.com HRC and its product philosophy The use of T-headed bars in concrete structures has some remarkable benefits compared to the

More information

TECHNICAL MANUAL. PVL Connecting Loop. Wall Connecting Loop Box with Single Wire

TECHNICAL MANUAL. PVL Connecting Loop. Wall Connecting Loop Box with Single Wire TECHNICAL MANUAL PVL Connecting Loop Wall Connecting Loop Box with Single Wire Version: PEIKKO GROUP 11/2012 PVL Connecting Loop Single wire wall connecting loop Benefits of PVL Easy to install, individual

More information

Design of Column Base Plates

Design of Column Base Plates Design of Column Base Plates Typical column bases, as shown below, consist of a single plate fillet welded to the end of the column and attached to the foundation with four holding down bolts. The bolts

More information

(English language translation, the original version is in French language) Sto-Polydal SP 15/09/ /04/2015

(English language translation, the original version is in French language) Sto-Polydal SP 15/09/ /04/2015 Centre Scientifique et Technique du Bâtiment 84, avenue Jean Jaurès Champs sur Marne BP2 F-77421 Marne-la-Vallée Cedex 2 Tél. : (33) 01 64 68 82 82 Fax : (33) 01 60 05 70 37 Autorisé et notifié conformément

More information

(English language translation, the original version is in French language) SOFRETHANE S3

(English language translation, the original version is in French language) SOFRETHANE S3 Centre Scientifique et Technique du Bâtiment 84, avenue Jean Jaurès Champs sur Marne BP2 F-77421 Marne-la-Vallée Cedex 2 Tél. : (33) 01 64 68 82 82 Fax : (33) 01 60 05 70 37 Autorisé et notifié conformément

More information

European Technical Approval ETA-13/0262

European Technical Approval ETA-13/0262 UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. Phone : +44 1483 302130 Fax : +44 1483 302230 Email : Inform.NB@uk.ul.com Website

More information

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)

More information

TECHNICAL MANUAL. PC Beam Shoe. Hidden Beam Shoe for Corbel System

TECHNICAL MANUAL. PC Beam Shoe. Hidden Beam Shoe for Corbel System TECHNICAL MANUAL PC Beam Shoe Hidden Beam Shoe for Corbel System Version: PEIKKO GROUP 03/2012 PC Beam Shoe Corbel system to support beams System benefits Easy and fast beam installationtion Fits into

More information

RPA Plate Lifting Inserts Technical Manual

RPA Plate Lifting Inserts Technical Manual R-Group Finland Oy RPA Plate Lifting Inserts Technical Manual According to Eurocodes, EU Machinery directive 2006/42/EC and VDI/BV-BS 6205 CE Approved 13.7.2017 2 Table of Contents 1 DESCRIPTION OF THE

More information

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)

More information

European Technical Approval ETA 13/0783

European Technical Approval ETA 13/0783 LABORATÓRIO NACIONAL DE ENGENHARIA CIVIL, I. P. Av. do Brasil, 101 1700-066 LISBOA PORTUGAL phone: (351) 21 844 30 00 fax: (351) 21 844 30 11 e-mail: lnec@lnec.pt www.lnec.pt Authorised a n d n o t i f

More information

CHAPTER 10: GENERAL STRUCTURAL DETAILS

CHAPTER 10: GENERAL STRUCTURAL DETAILS CHAPTER 10: GENERAL STRUCTURAL DETAILS 10.1 GENERAL It shall be in accordance with JSCE Standard Specification (Design), 9.1, "steel" shall be taken to signify "steel or CFRM". 10.2 CONCRETE COVER (1)

More information

European Technical Assessment. ETA 15/0226 of General Part TCM400PE, TCM600PE. Trade name of the construction product

European Technical Assessment. ETA 15/0226 of General Part TCM400PE, TCM600PE. Trade name of the construction product Member of Wellington, 19 ES 08018 Barcelona Tel: (+34) 93 309 34 04 qualprod@itec.cat www.itec.cat www.eota.eu European Technical Assessment ETA 15/0226 of 17.04.2015 General Part Trade name of the construction

More information

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)

More information

EUROPEAN TECHNICAL ASSESSMENT ETA-17/0336

EUROPEAN TECHNICAL ASSESSMENT ETA-17/0336 EUROPEAN TECHNICAL ASSESSMENT ETA-17/0336 HILTI ANCHOR CHANNELS & BOLTS A systematic approach to innovative anchoring Hilti now offers a vast range of Anchor Channels for a variety of applications to the

More information

ETA-13/0584 of 24/09/2014. European Technical Assessment. General Part. Technical Assessment Body issuing the. Instytut Techniki Budowlanej

ETA-13/0584 of 24/09/2014. European Technical Assessment. General Part. Technical Assessment Body issuing the. Instytut Techniki Budowlanej Member of INSTYTUT TECHNIKI BUDOWLANEJ PL 00-611 WARSZAWA ul. Filtrowa 1 tel.: (+48 22) 825-04-71 (+48 22) 825-76-55 fax: (+48 22) 825-52-86 www.itb.pl www.eota.eu European Technical Assessment of 24/09/2014

More information

(English language translation, the original version is in French language) Outifix ISOL

(English language translation, the original version is in French language) Outifix ISOL Centre Scientifique et Technique du Bâtiment 84 avenue Jean Jaurès Champs sur Marne F-77447 Marne-la-Vallée Cedex 2 Tél. : (33) 01 64 68 82 82 Fax : (33) 01 60 05 70 37 Autorisé et notifié conformément

More information

E TA TECHNICAL REPORT. Evaluation of Anchorages in Concrete concerning Resistance to Fire. TR 020 Edition May 2004

E TA TECHNICAL REPORT. Evaluation of Anchorages in Concrete concerning Resistance to Fire. TR 020 Edition May 2004 E TA TECHNICAL REPORT Evaluation of Anchorages in Concrete concerning Resistance to Fire TR 2 Edition May 24 EUROPEAN ORGANISATION FOR TECHNICAL APPROVALS Table of contents 1. General... 2 2. Evaluation

More information

European Technical Approval ETA-13/0982

European Technical Approval ETA-13/0982 British Board of Agrément Bucknalls Lane Watford Herts WD25 9BA Tel: + 44 (0) 1923 665300 Fax: + 44 (0) 1923 665301 e-mail: mail@bba.star.co.uk website: www.bbacerts.co.uk Authorised and notified according

More information

European Technical Approval ETA-10/0352

European Technical Approval ETA-10/0352 European Technical Approval ETA-10/0352 - Original version in German language Handelsbezeichnung Trade name Zulassungsinhaber Holder of approval Zulassungsgegenstand und Verwendungszweck Generic type and

More information

European Technical Approval

European Technical Approval INSTYTUT TECHNIKI BUDOWLANEJ PL 00-6 WARSZAWA ul. FILTROWA tel.: (48 22) 825-04-7; (48 22) 825-76-55; fax: (48 22) 825-52-86; www.itb.pl Członek EOTA Egzemplarz archiwalny European Technical Approval ETA-2/0522

More information

European Technical Approval ETA-05/0164

European Technical Approval ETA-05/0164 European Technical Approval ETA-05/0164 - Original version in German language Handelsbezeichnung Trade name Zulassungsinhaber Holder of approval Zulassungsgegenstand und Verwendungszweck Generic type and

More information

Lecture Retaining Wall Week 12

Lecture Retaining Wall Week 12 Lecture Retaining Wall Week 12 Retaining walls which provide lateral support to earth fill embankment or any other form of material which they retain them in vertical position. These walls are also usually

More information

European Technical Approval

European Technical Approval INSTYTUT TECHNIKI BUDOWLANEJ PL 00-6 WARSZAWA ul. FILTROWA tel.: (48 22) 825-04-7; (48 22) 825-76-55; fax: (48 22) 825-52-86; www.itb.pl Członek EOTA Egzemplarz archiwalny European Technical Approval ETA-3/0584

More information

DECLARATION OF PERFORMANCE. No EN

DECLARATION OF PERFORMANCE. No EN DECLARATION OF PERFORMANCE No. 0004 EN 1. Unique identification code of the product-type: 2. Intended use/es: Product Plastic anchors for use in concrete and masonry Intended use/es Screwed-in plastic

More information

European Technical Approval ETA-12/0258

European Technical Approval ETA-12/0258 European Technical Approval ETA-12/0258 - Original version in German language Handelsbezeichnung Trade name Zulassungsinhaber Holder of approval Zulassungsgegenstand und Verwendungszweck Generic type and

More information

European Technical Assessment ETA-10/0415 of 25/02/2016

European Technical Assessment ETA-10/0415 of 25/02/2016 ETA-Danmark A/S Göteborg Plads 1 DK-2150 Nordhavn Tel. +45 72 24 59 00 Fax +45 72 24 59 04 Internet www.etadanmark.dk Authorised and notified according to Article 29 of the Regulation (EU) No 305/11 of

More information

(English language translation, the original version is in French language) SPIT SAS route de Lyon F BOURG-LES-VALENCE France

(English language translation, the original version is in French language) SPIT SAS route de Lyon F BOURG-LES-VALENCE France Member of Centre Scientifique et Technique du Bâtiment 84 avenue Jean Jaurès CHAMPS-SUR-MARNE F-77447 Marne-la-Vallée Cedex 2 www.eota.eu Tél. : (33) 01 64 68 82 82 Fax : (33) 01 60 05 70 37 European Technical

More information

Slabs and Flat Slabs

Slabs and Flat Slabs Slabs and Flat Slabs Lecture 5 19 th October 2017 Contents Lecture 5 Designing for shear in slabs - including punching shear Detailing Solid slabs Flat Slab Design includes flexure worked example Exercise

More information

TECHNICAL MANUAL. SUMO Wall Shoe. For Bolted Wall Connections

TECHNICAL MANUAL. SUMO Wall Shoe. For Bolted Wall Connections TECHNICAL MANUAL Wall Shoe For Bolted Wall Connections Version: PEIKKO GROUP 11/2014 Wall Shoe For bolted wall connections System benefits Strong tensile connection: enables shear walls to be built of

More information

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)

More information

European Technical Approval ETA-05/0253

European Technical Approval ETA-05/0253 European Technical Approval ETA-05/0253 - Original version in German language Handelsbezeichnung Trade name Zulassungsinhaber Holder of approval Zulassungsgegenstand und Verwendungszweck Generic type and

More information

Quality Regulations for Sandwich Panels

Quality Regulations for Sandwich Panels Quality Regulations for Sandwich Panels October 2012 Quality Regulations for Sandwich Panels Page 2/19 Contents Preface... 3 1. Terms and Definitions... 4 1.1 Third parties... 4 1.2 Independent laboratories...

More information