North Carolina Energy Code Future of Commercial Requirements

Size: px
Start display at page:

Download "North Carolina Energy Code Future of Commercial Requirements"

Transcription

1 North Carolina Energy Code Future of Commercial Requirements 2008 North Carolina Energy Star Conference Conducted by: Appalachian State University Dept. of Technology & Energy Center Boone, NC Jeff Tiller, PE, Chris Mathis and Associates Asheville, NC Margie Meares,

2 Total Energy Use by Sector (TBtu) 3000 Transportation Industrial 2500 Residential Commercial Transporportation 27% Industrial 2004 Commercial 20% Residential 26% % Com- mercial 7% Transpor -tation 28% Residential 29% Industrial 36% 1960

3 Two Sets of Requirements multiple pathways to compliance Building Design for All Commercial Buildings Chapter 7 -- ASHRAE in the North Carolina energy code Design by Acceptable Practice for Commercial Buildings Chapter 8 part of the IECC 2004 with local amendments 1/28/2008 Mathis Consulting Company Page 3

4 Energy Consumption in Commercial Buildings More than half of energy use is for HVAC and lighting Energy bill equals 25% of total operating costs Climate sensitive design and off-the-shelf h technologies can cut energy bill by 50%

5 Typical Commercial Building Energy Consumption Patterns Misc Other Equip. Cooking Refrgd'n Lighting HVAC Water Htg 1/28/2008 Mathis Consulting Company Page 5

6 Chapter 7 ASHRAE 90.1 The BIG chapter Referenced Standards ASHRAE Energy Standard for Buildings Except Low- Rise Residential Buildings Scope. Commercial buildings shall meet the requirements of ASHRAE/IESNA Exception: Commercial buildings that comply with Chapter 8. 1/28/2008 Mathis Consulting Company Page 6

7 Organization of ASHRAE Standard Purpose 7 Service Water Heating 2 Scope 3 Definitions 4 Administration and Enforcement 5 Building Envelope 6 Heating, Ventilating, and Air-Conditioning 8 Power 9 Lighting g 10 Other Equipment 11 Energy Cost Budget Method 12 Normative References 1/28/2008 Mathis Consulting Company Page 7

8 High Rise Residential Which Energy Code?

9 Section 5 Envelope Key Concepts Building envelope does not use energy Design affects heating and cooling loads Insulation affects the temperature of inside surfaces; comfort Daylighting can reduce electric lighting 1/28/2008 Mathis Consulting Company Page 9

10 Section 5 Envelope, cont d Integrated design approach saves energy Building envelope requirements address: Opaque elements Roofs, walls, floors, below-grade walls, slabs, opaque doors Fenestration Windows, doors, skylights How often do we get the chance to get this part of the building right? 1/28/2008 Mathis Consulting Company Page 10

11 Section 5 Envelope Compliance Methods Section 5.2 Mandatory Provisions Prescriptive Option Trade-Off Option Energy Cost Budget Compliance 1/28/2008 Mathis Consulting Company Page 11

12 502.3 Basic Requirement: Air Leakage - Building Envelope Sealing Caulk around penetrations of chimney flue vents or attic hatches Caulk between wall and roof Caulk between wall panels and top and bottom plates in exterior walls Caulk between wall panels particularly at corners and changes in orientation Weatherstrip doors Caulk between wall and foundation Caulk around doors and windows Caulk between wall arch floor where floor penetrates wall Caulk at penetrations of utility services or other service entry through walls floors and roofs

13 Major Air Leakage Sites Cavities above suspended ceilings Plenum return spaces (Highly depressurized) Ventilated walls Equipment tunnels and chases Mechanical rooms and mezzanines Unconditioned adjacent space (Storage, warehouse, plant, etc.) Exhaust and ventilation fans, plus wind and stack effect, are major driving forces

14 Return Plenum Problems - Canopy

15 Is Air Barrier Continuous? Brand-new NC building Drywall left off of exterior wall above dropped ceiling Building uses above-ceiling area as return When HVAC operates, entire wall cavity goes to a negative e pressure, increasing air leakage, effectively reducing insulation value, and potentially causing moisture problems

16 Limiting Air Leakage Pathways Materials and connections must: stop air flow withstand jobsite abuses withstand forces of wind and pressure Penetrations must be sealed plumbing, wiring, communications ductwork windows and doors Functional penetrations, such as air intakes for exhaust fans, must be dampered Vestibules (5 Stories or more, with exceptions)

17 Section 5 Envelope -- Vestibules Required at building entrances Self closing doors Exceptions: a. Building entrances with revolving doors. b. Doors not used as a building entrance. c. Doors opening directly from a dwelling unit. d. Building entrances in buildings located in climate zone 1 or 2. e. Building entrances in buildings located in climate zone 3 or 4 that are less than four stories above grade and less than 10,000 ft 2 in area. f. Building entrances in buildings located in climate zone 5, 6, 7, or 8 that are less than 1,000 ft 2 in area. g. Doors that t open directly from a space that t is less than 3,000 ft 2 in area and is separate from the building entrance. 1/28/2008 Mathis Consulting Company Page 17

18 Section 5 - Prescriptive Requirements, Building Envelope Ventilated Attic Semiheated Storage Conditioned Space Unconditioned Space Ventilated Crawlspace Exterior Envelope Semi-Exterior Envelope 1/28/2008 Mathis Consulting Company Page 18

19 U-Factors The amount of heat in Btus (British thermal units) that flows each hour through one square foot, when there is a 1ºF temperature difference across the surface The smaller the number the better 1 U - Factor = R - Value 1/28/2008 Mathis Consulting Company Page 19

20 Common R-values Resistance to Conductive Heat Flow Concrete 0.2 per inch ½ Drywall 0.5 Double-paned glass 1.8 Low-e glass about 3.0 Fiberglass insulation 3 to 4 per inch Cellulose insulation 3.7 per inch Expanded polystyrene 4 per inch Extruded polystyrene 5 per inch Icynene foam 3.6 to 3.7 per inch Polyurethane foam 6.7 to 7.0 per inch

21 Steel Framing and Insulation 1/28/2008 Mathis Consulting Company Page 21

22 Thermal Losses from Steel Stud Walls

23 U-factors for Metal Stud Walls Nominal R-value Effective R-value U-factor Continuous Insulated Sheathing 1/2" EPS 5/8" Poly-Iso 1" XPS R-2.0 R-4.0 R x 4 Metal Framing at 16 inches on Center (3.5 in cavity depth) None (0.0) 0) R-11 (5.5) R-13 (6.0) R-15 (6.4) x 4 Metal Framing at 24 inches on Center (3.5 in cavity depth) R-11 (6.6) R-13 (7.2) R-15 (7.8)

24 Effective R-value of 2x4 Metal Framed Walls (16 oc) o.c.) R R-13 Effective R-Value of 2x4 14 R-11 Metal Framed Wall with R- 12 None 13 Batt Insulation 10 Sheathing R-value 8 OSB/ Drywall /2" XPS /2" Poly-Iso " XPS " XPS 17.5 R-0.5 R-2.5 R-3.4 R-5.0 R-10.0 OSB/ 1/2" XPS 1/2" Poly- 1" XPS 2" XPS Drywall Iso

25 Above Grade Floors Is the Insulation Missing? Continuous insulation is the key 1 of foam is vital for exposed slab edges Heat loss will be more than just 4 of missing insulation Trace other potential Trace other potential discontinuities in wall insulation system

26 Make Insulation Continuous Block walls -- should be insulated; insulating cores very ineffective Floors over unheated spaces, such as parking areas, need insulation For discontinuities in walls, such as offset areas for stairwells, elevators, and other spaces, the exterior envelope must be determined. d The envelope requires both insulation and air sealing.

27 2006 IECC Climate Zones: Zones 4 and Below Don t Require Wall Vapor Barriers (Only NW Mountains need one)

28 2009 NCECC 5 4 3

29 Roof Insulation Requirements: IECC 2003 (Chapter 8 of current code) IECC (Chapter 8): Roof Insulation Requirements Cavity Insulation Maximum Glazing Area 10% 25% 40% 50% Continuous Insulation Cavity Insulation Continuous Insulation Cavity Insulation Continuous Insulation Cavity Insulation Continuous Insulation All-wood R-19 R-14 R-19 R-16 R-25 R-19 R-25 R-19 joist/truss Metal joist/truss R19 R-19 R15 R-15 R25 R-25 R17 R-17 R25 R-25 R20 R-20 R25 R-25 R20 R-20 Concrete slab or NA R-14 NA R-16 NA R-19 NA R-19 deck Metal purlin with R-25 R-15 R-25 R-17 R-30 R-20 R-30 R-20 thermal block Metal purlin X R15 R-15 X R17 R-17 X R20 R-20 R30 R-30 R20 R-20 without thermal block

30 Roof Insulation Requirements: ASHRAE (Chapter 7 of current code and Chapter 5, section 501 of new code) Table ASHRAE Nonresidential Residential Semiheated ASHRAE (Chapter 5) Nonresidential Roof Zone 3 Zone 4 Zone 5 Insulation Entirely above Deck R-15 c.i.* R-15 c.i.* R-15 c.i.* Metal Building R-19.0 R-19.0 R-19.0 Attic and Other R-30.0 R-30.0 R-30.0 Residential Roof Zone 3 Zone 4 Zone 5 Insulation Entirely above Deck R-15.0 c.i. R-15.0 c.i. R-15.0 c.i. Metal Building R-19.0 R-19.0 R-19.0 Attic and Other R-38 R38.0 R-38 R38.0 R-38 R38.0 Semiheated Roof Zone 3 Zone 4 Zone 5 Insulation Entirely above Deck R-4.0 c.i. R-4.0 c.i. R-5.0 c.i. Metal Building R-10.0 R-10.0 R-10.0 Attic and Other R-13.0 R-13.0 R-19.0 * c.i. = continuous insulation -- typically foam

31 Roof Insulation Requirements: IECC 2003 (Chapter 8 of current code) Climate Zone Roofs Insulation entirely above deck R-15, c.i. R-15, c.i. R-20, c.i. Metal buildings (with R-5 thermal blocks) R-19 R-19 R-19 Attic and other R-30 R-30 R-30 Roofs for Metal Buildings: R-19 + R-10 Filled cavity roof -- Thermal blocks are a minimum, R-5 of rigid insulation, which extends 1 in. beyond the width of the purlin on each side, perpendicular p to the purlin. This construction is R-10 insulation batts draped perpendicularly over the purlins, with enough looseness to allow R-19 batt to be laid above it, parallel to the purlins. Thermal blocks are then placed above the purlin/batt, and the roof deck is secured to the purlins. In the metal building industry, this is known as the sag and bag insulation system. R-19: Standing seam with single insulation layer. Thermal blocks are a minimum R-5 of rigid insulation, which extends 1 in. beyond the width of the purlin on each side, perpendicular to the purlin. This construction R-19 insulation batts draped perpendicularly over the purlins. Thermal blocks are then placed above the purlin/batt, and the roof deck is secured to the purlins.

32 Building Envelope Example: Roofs No longer counts: Batts over suspended ceiling tiles

33 Inspection is Critically Important! Insulation specification was R-30 foam on roof deck according to the plans (and HVAC design) The 2 5 inches found 2.5 The 2.5 inches found installed in the field would only provide about R-15

34 Commercial Wall Requirements: ASHRAE (Chapter 7 of current code and Chapter 5, Section 501 of new code) Nonresidential Zone 3 Zone 4 Zone 5 Walls, Above Grade Mass R-57ci R-5.7 c.i. R-57ci R-5.7 c.i. R-75ci R-7.5 c.i. Metal Building R-13 R-13 R-13 Steel Framed R-13 R-13 R-13 + R-4 c.i. Wood Framed and Other R-13 R-13 R-13 Below Grade Wall NR NR NR Residential Walls, Above Grade Mass R-7.3 c.i. R-10 c.i. R-11 c.i. Metal Building R-13 R-13 R-13 + R-13 c.i. Steel Framed R-13 + R-4 c.i. R-13 + R-7 c.i. R-13 + R-7 c.i. Wood Framed and Other R-13 R-13 R-13 Below Grade Wall NR NR NR Semiheated Walls, Above Grade Mass NR NR NR Metal Building R-6 R-10 R-11.0 Steel Framed NR R-13 R-13.0 Wood Framed and Other R-13 R-13 R-13.0 Below Grade Wall NR NR NR

35 Commercial Wall Insulation Requirements: IECC 2006 (Chapter 5 of new code) Climate Zone Walls, Above Grade Mass R-57ci R-5.7 c.i. R-5.7 c.i. R-76ci R-7.6 c.i. Metal building R-13 R-13 R-13+R-13 Metal framed R-13 R-13 R-13+R-3.8 c.i. Wood framed and other R-13 R13 R-13 R13 R-13 R13 Walls, Below Grade NR NR NR Walls for Metal Buildings: R-13 Single insulation layer: The first layer of R-13 insulation batts is installed continuously perpendicular to the girts and is compressed as the metal skin is attached to the girts. R-13 + R-13 Double insulation layer: The first layer of R-13 insulation batts is installed continuously perpendicular to the girts, and is compressed as the metal skin is attached to the girts. The second layer of R-13 insulation batts is installed within the framing cavity. 1/28/2008 Mathis Consulting Company Page 35

36 Typical? Non-Compliant! 1/28/2008 Mathis Consulting Company Page 36

37 How about now? 1/28/2008 Mathis Consulting Company Page 37

38 Commercial Floor Requirements: ASHRAE (Chapter 7 of current code and Chapter 5, Section 501 of new code) ASHRAE Nonresidential Zone 3 Zone 4 Zone 5 Floors Mass R63ci R-6.3 c.i. R63ci R-6.3 c.i. R85ci R-8.5 c.i. Steel Joist R-19 R-19 R-19 Wood Framed and Other R-19 R-19 R-30 Slab-On-Grade Floors Unheated NR NR NR Heated R-7.5, 12 in. R-7.5, 24 in. R-10, 36 in. Opaque Doors Swinging U U U Non-Swinging U U U Residential Zone 3 Zone 4 Zone 5 Floors Mass R-8.3 c.i. R-8.3 c.i. R-10 c.i. Steel Joist R-19 R-30 R-30 Wood Framed and Other R-30 R-30 R-30 Slab-On-Grade Floors Unheated NR NR NR Heated R-7.5, 24 in. R10 R-10, 36i in. R10 R-10, 36i in. Opaque Doors Swinging U U U Non-Swinging U U U-0.500

39 Commercial Floor Requirements: IECC 2006 (Chapter 5 of new code) Floors Zone 3 Zone 4 Zone 5 Mass R5 R-5 c.i. R10 R-10 c.i. R-10 c.i. Joist/ Framing R-19 R-19 R-19 Slab-on-Grade Floors Unheated slabs NR NR Heated slabs R-7.5 (12 in R-7.5 (12 in R-7.5 (24 in vert) vert) vert)

40 Section 5 Compliance Meet or exceed minimum R-values in Table 5.3 Only R-value of insulation, not to include air films, etc. OR Meet maximum U-factor, C-factor, or F-factor for the entire assembly OR Perform area-weighted average U-factor, C- factor, or F-factor 1/28/2008 Mathis Consulting Company Page 40

41 Glazing Area Percentage Glazing percentage to Above Grade Wall Gross window area / gross wall area Gross wall area includes Above-grade walls Band joist and subfloor between floors Area of all doors and windows Section 802 1/28/2008 Mathis Consulting Company Page 41

42 NFRC Label Section /28/2008 Mathis Consulting Company Page 42

43 IECC 2006 Commercial Glazing Requirements (new code) Vertical Fenestration (40% maximum of above-grade walls) Required U-factors Zone 3 Zone 4 Zone 5 Framing materials other than metal Metal framed windows with or without thermal break Curtain Wall/ Storefront Entrance Door All Other Solar Heat Gain Coefficient SHGC: Projection Factor < SHGC: 0.25 to NR NR SHGC: >= NR NR

44 ASHRAE (Chapter 5) Nonresidential Residential Semiheated ASHRAE 90.1 Fenestration U oper -0.67, SHGC north U oper -0.67, SHGC north U oper -1.27, SHGC north - NR Requirements U oper -0.67, SHGC north U oper -0.67, SHGC north U oper -1.27, SHGC north - NR for Climate U oper -0.67, 067 SHGC north U oper -0.67, 067 SHGC north U oper -1.27, 127 SHGC north - NR Zones 3 and % U fixed -0.57, SHGC all U fixed -0.57, SHGC all U fixed -1.22, SHGC all - NR % U fixed -0.57, SHGC all U fixed -0.57, SHGC all U fixed -1.22, SHGC all - NR % U fixed -0.57, SHGC all U fixed -0.57, SHGC all U fixed -1.22, SHGC all - NR U oper -0.67, SHGC north U oper -0.67, SHGC north U oper -1.27, SHGC north - NR % U fixed -0.46, SHGC all U fixed -0.46, SHGC all U fixed -0.98, SHGC all - NR U oper -0.47, SHGC north U oper -0.47, SHGC north U oper -1.02, SHGC north - NR p p p Fenestration Values for Climate Zone 3 Window- Wall Ratio % U fixed -0.57, SHGC all U fixed -0.57, SHGC all U fixed -1.22, SHGC all - NR U fixed = U-value of fixed windows; U oper = U-value of operable windows SHGC all = Solar Heat Gain Coefficient of all windows SHGC north = Solar Heat Gain Coefficient of north windows Fenestration Values for Climate Zone 4 Window- Nonresidential Residential Semiheated Wall Ratio % U fixed -0.57, SHGC all U fixed -0.57, SHGC all U fixed -1.22, SHGC all - NR U oper -0.67, SHGC north U oper -0.67, SHGC north U oper -1.27, SHGC north - NR % U fixed -0.57, SHGC all U fixed -0.57, SHGC all U fixed -1.22, SHGC all - NR U oper -0.67, SHGC north U oper -0.67, SHGC north U oper -1.27, SHGC north - NR % U fixed -0.57, SHGC all U fixed -0.57, SHGC all U fixed -1.22, SHGC all - NR U oper -0.67, SHGC north U oper -0.67, SHGC north U oper -1.27, SHGC north - NR % % U fixed -0.57, 057 SHGC all U fixed -0.57, 057 SHGC all U fixed -1.22, 122 SHGC all - NR U oper -0.67, SHGC north U oper -0.67, SHGC north U oper -1.27, SHGC north - NR % U fixed -0.46, SHGC all U fixed -0.46, SHGC all U fixed -0.98, SHGC all - NR U oper -0.47, SHGC north U oper -0.47, SHGC north U oper -1.02, SHGC north - NR Note: ASHRAE is an option for the current and new codes

45 Product Information and Installation ti (Section 5.8) Insulation (5.8.1) Not compressed Substantial contact/supported Recessed equipment if >1% Not above suspended ceilings Insulation needs to be protected 1/28/2008 Mathis Consulting Company Page 45

46 Organization of ASHRAE Standard Purpose 7 Service Water 2 Scope Heating 3 Definitions 8 Power 4 Administration and 9 Lighting Enforcement 10 Other Equipment 5 Building Envelope 11 Energy Cost 6 Heating, Ventilating, Budget Method and Air-Conditioning 12 Normative References 1/28/2008 Mathis Consulting Company Page 46

47 Section 6 HVAC Key Concepts Goal a system which minimizes system losses and utilizes free heating and cooling Scope and Compliance Paths Establish minimum equipment efficiencies Establish a min. level of control for systems Establish minimum levels of construction and insulation of systems. Simplified Approach/Prescriptive Path Submittals 1/28/2008 Mathis Consulting Company Page 47

48 Section 6 HVAC Scope (6.1.1) 1) New Buildings Mechanical equipment & systems serving HVAC needs of new buildings Additions Same as new buildings Exception if served by existing systems need not comply except for any new equipment or systems Alterations Replacement equipment minimum efficiency only New cooling for un-cooled spaces to comply Alterations to cooling system not decrease economizer capability unless meets prescriptive requirements New ductwork & piping to comply Exceptions repairs, refrigerant change, relocation, space constraints 1/28/2008 Mathis Consulting Company Page 48

49 Section 6 Simplified Approach Option Limited to buildings that meet the following criteria buildings with 1 or 2 stories buildings < 25,000 ft2 single-zone systems Unitary packaged or split system; air-cooled or evaporatively-cooled only; equipment efficiencies per tables Economizer if required Outside air requirements are less than 3000 CFM and less than 70% of airflow Manual changeover or dual set-point thermostat Heat pump supplementary control No reheat or simultaneous heating and cooling for humidity control 1/28/2008 Mathis Consulting Company Page 49

50 ASHRAE / IESNA Simplified Approach 1. Each system must serve a single zone. 2. Cooling shall be packaged or split system either air or evaporative cooled. 3. Economizers required in certain circumstances. 4. Heating shall be packaged or split system heat pump, gas, electric, or hot water. 1/28/2008 Mathis Consulting Company

51 ASHRAE / IESNA Simplified Approach (cont.) 5. Outside air requirements shall be less than 3,000 cfm and less than 70% of supply air quantity; or energy recovery system. 6. Requires manual changeover or dual set point thermostat. 7. When possible, heat pump feature will always provide heating.

52 ASHRAE / IESNA Simplified Approach (cont.) 8. No reheat or simultaneous heating and cooling. 9. Control for systems larger than 65,000 Btuh and ¾ HP fan motor require a time clock. 10. Piping insulation and weather protection. 11. Ductwork and plenum insulation. 1/28/2008 Mathis Consulting Company

53 ASHRAE / IESNA Simplified Approach (cont.) 12. Ducted systems air balanced to 10% of design. 13. Separate thermostats interlocked to prevent simultaneous heating and cooling. 14. Exhausts over 300 cfm shall have gravity or motor dampers. 15 System greater than cfm 15. System greater than 10,000 cfm shall have optimum start controls.

54 Condensation Challenges A/C ductwork: F Cooling below 71 0F Metal framing in winter Metal framing in summer Cool piping for chilled water

55 What Happened?

56

57 Non-Code Compliant

58

59 Example; 25-ton: Cooling Efficiency Cooling efficiency: 25 tons = 300, Btuh

60 Example; 25 ton: Heating Heating efficiency: 25 tons = 300,000 Btuh

61 Economizers in North Carolina IECC 2003 Chapter 7 (ASHRAE 90.1): Would be required in Asheville and high elevations IECC 2003 Chapter 8: Economizers required in all zones except 1,2,3b,5a and 6b (meaning all of North Carolina except the coastal areas to Charlotte)

62 Example; 25 ton: Duct Insulation

63 Example; 25 ton: Ducts Table 6-D in User Manual R-3.5: 1-inch duct liner, fiberboard, duct board, flex duct; 1.5-inch mineral fiber duct wrap R-6.0: 1.5-inch duct liner, fiberboard, duct board, flex duct; 2.5-inch flex duct, mineral fiber duct wrap R-8.0: 2-inch duct liner, fiberboard, duct board, flex duct; 3-inch flex duct, mineral fiber duct wrap Duct Sealing Required (to be discussed later)

64 Example; 25 ton: Other Air Balancing add note to the design drawings or specs calling for balancing according to ASHRAE 111, NEBB, AABCm or other industry-recognized recognized standard Since no fan exceeds 300 cfm, a backdraft damper is not required per

65 ASHRAE / IESNA HVAC Mandatory Provisions Applies to the Prescriptive Path and the Energy Cost Budget method Requirements address Life cycle cost analysis Equipment efficiencies Load calculations Controls Construction and insulation Completion requirements

66 Constant vs. Variable Speed Systems Constant speed fans and pumps, constant temperature heating and cooling systems and constant volume ventilation and exhaust systems are efficient only at full load conditions. Variable systems are efficient at part loads. Motors: Multiple speed, modular, variable speed. Supply Air: Bypass, variable air volume. Supply temperature: Reset based on demand or outdoor air temperature. Outdoor air: Reset based on occupancy. Primary heating and cooling equipment: staged, modular.

67 Section 6 Mechanical Equipment Efficiency Section 6.4 Air conditioners & Condensing Units Heat Pumps Water Chilling Packages standard conditions Packaged Terminal and Room Air Conditioners & Heat Pumps Furnaces, Duct Furnaces and Unit Heaters Boilers Heat Rejection Equipment 1/28/2008 Mathis Consulting Company Page 67

68 Section 6 Load Calculations Load Calculations are required! Akf Ask for them! 1/28/2008 Mathis Consulting Company Page 68

69 Section 9 Lighting 1/28/2008 Mathis Consulting Company Page 69

70 Energy-Efficient Efficient Lighting Sources

71 Lighting Power Densities Using the Building Area Method Building Area Type a Lighting g Power Density (Watt/ft 2 ) Automotive Facility 1.5 Convention Center 1.4 Court House 1.4 Office 1.3 Dining: Bar, Lounge/ Leisure 1.5 Parking Garage 0.3 Dining: Cafeteria/ Fast Food 1.8 Penitentiary 1.2 Dining: Family 1.9 Performing Arts Theater 1.5 Dormitory Police/Fire Station 1.3 Exercise Center 1.4 Gymnasium 1.7 Hospital/Health Care 1.6 Hotel Library 1.5 Manufacturing Facility 2.2 Motel 2.0 Motion Picture Theater 16 Post Office 1.6 Religious Building 2.2 Retail 1.9 School/University Sports Arena 1.5 Town Hall 1.4 Transportation 1.2 Motion Picture Theater 1.6 Warehouse

72 Does the Building Comply? Determine the total connected power in watts for the proposed lighting Determine the interior lighting power budget for the entire building or space Building complies if: Interior lighting power budget - total t connected power 0

73 Exterior Lighting Criteria Lighting power supplied through building electrical service Must use energy-efficient efficient lighting sources to highlight paths, walkways and parking areas 45 Lumens/Watt Fluorescent or Compact Fluorescent Metal Halide or High Pressure Sodium Exceptions Historical Section 805.5/805.6 Safety Signage Emergency

74 Section 11 Energy Cost Budget Method Alternative to prescriptive method except buildings with no mechanical systems Based on overall building performance expressed as energy cost budget Mandatory Provisions all must be met Budget (or baseline) based on prescriptive measures Allows trade-offs between measures Useful for optimizing design 1/28/2008 Mathis Consulting Company Page 74

75 So, What Now? In Commercial, Appendix B is not enough Plan review and inspection of energy features is needed 1/28/2008 Mathis Consulting Company Page 75

76 Key Inspection Points Envelope Insulation values correct? Proper installation? i Fenestration -- % glass Fenestration U-factor and SHGC (on plans and in field) Air sealing details HVAC Programmable controls? Economizer? Duct and pipe insulation? Ducts sealed? ed 1/28/2008 Mathis Consulting Company Page 76

77 Key Inspection Points (cont.) HVAC (continued) No simultaneous heating and cooling (except where allowed for reheat) Complex systems Lighting Fan power Temperature reset Zoning Reheat limitation Etc. If most lamps are not T-8 fluorescent or more efficient lamps, need to check Check controls Exit signs Exterior lighting 1/28/2008 Mathis Consulting Company Page 77

78 ASHRAE 90.1: Advanced Design Guide Office Building ASHRAE Advanced Design Guide Roof Zone 4 Zone 4 Insulation Entirely above Deck R-15 c.i.* R-20 c.i.* Metal Building R-19.0 R Attic and Other R R-38 Walls, Above Grade Mass R-5.7 c.i. R-11.4 c.i. Metal Building R-13 R-13 Steel Framed R-13 R-13+R-7.5 Wood Framed and Other R-13 R-13 Below Grade Wall NR NR Floors Mass R83ci R-8.3 c.i. R83ci R-8.3 c.i. Steel Joist R-30 R-30 Wood Framed and Other R-30 R-30

79 ASHRAE 90.1: Advanced Design Guide Office Building Fenestration Values for Climate Zone 4 Window- ASHRAE Advanced Design Guide Wall Ratio % U fixed -0.57, SHGC all Up to 40% of wall area U oper -0.67, SHGC north U U fixed -0.57, SHGC all SHGC U oper -0.67, SHGC north Area of north glass * SHGCn U fixed -0.57, SHGC all Area of south glass * SHGCs > U oper -0.67, SHGC north Area of east glass * SHGCe U fixed -0.57, SHGC all Area of west glass * SHGCw U oper -0.67, SHGC north South, east, west has overhang U fixed -0.46, 046 SHGC all U oper -0.47, SHGC north -0.36

80 ASHRAE 90.1: Advanced Design Guide Office Building Interior Lighting ASHRAE Advanced Design Guide 1.30 Watts/. Sq ft 0.90 Watts/ sq ft 90 lumen/ watt linear fluorescent Dimmable fixture within 12 ft of N/S window wall or within 8 ft of skylight edge Auto-off in all unoccupied rooms Reflectance of 80% on ceilings, 70% on walls and vertical partition

81 Cooling ASHRAE 90.1: Advanced Design Guide Office Building ASHRAE Advanced Design Guide 0-65 kbtuh 10 SEER 13 SEER kbtuh 103EER/112IPLV EER/ 11.4 IPLV kbtuh 9.7 EER/ 11.2 IPLV 10.8 EER/ 11.2 IPLV > 240 kbtuh 9.5 EER/ 11.2 IPLV 10 EER/ 10.4 IPLV Furnaces All sizes 80% AFUE 80% AFUE Heat pumps 0-65 kbtuh 10 SEER/ 6.8 HSPF 13 SEER/ 7.7 HSPF kbtuh 10.1 EER 10.6 EER/ 11 IPLV >135 kbtuh 9.3 EER/ 9.2 IPLV (>240) 10.1 EER/ 11 IPLV Other Economizers -- depend Economizers > 54 kbtuh Ventilation controls Motorized control with optional CO2 sensors Sealed ducts Sealed ducts 81% gas instantaneous water htr EF > 99%

82 ASHRAE 90.1: Advanced Design Guide Office Building ASHRAE Advanced Design Guide Roof Zone 4 Zone 4 Insulation Entirely above Deck R-15 c.i.* R-20 c.i.* Metal Building R-19.0 R Attic and Other R R-38 Walls, Above Grade Mass R-5.7 c.i. R-11.4 c.i. Metal Building R-13 R-13 Steel Framed R-13 R-13+R-7.5 Wood Framed and Other R-13 R-13 Below Grade Wall NR NR Floors Mass R83ci R-8.3 c.i. R83ci R-8.3 c.i. Steel Joist R-30 R-30 Wood Framed and Other R-30 R-30

83

84

85 Corners 1/28/2008 Mathis Consulting Company Page 85

86 Wall Insulation Zone 11a: Wall Insulation Requirements (NC 2006 Code -- Chaper 8) Maximum Glazing Area 10% 25% 40% 10% Wood Framing R11 R-11 R11 R-11 R11 R-11 R11 R-11 Metal Framing R-11 R-11 R-11 R-11 CMU with integral insulation R-11/ R-5* R-11/ R-5* R-11/ R-5* R-11/ R-5* Other masonry walls R11 R-11 R11 R-11 R11 R-11 R11 R-11 * R-11 metal or wood stud wall or R-5 continuous foam 1/28/2008 Mathis Consulting Company Page 86

87 Economizers (Simple) Air economizers required on systems if cooling capacity: > 90,000 Btu/h Not required in climate zones: 1, 2, 3b,5a or 6b Not required if the cooling of proposed equipment meets or exceeds the EER listed in Table Not required on system with air or evaporative cooling condensers and which serve spaces with open case refrigeration or that require filtration equipment in order to meet the minimum ventilation requirements of Chapter 4 of IMC. Zone 7 >135,000Btu/h Section /28/2008 Mathis Consulting Company Page 87

88 Economizers (Simple) Trade-off high cooling efficiency for economizer Total cooling capacity Table Climate zones Equipment efficiency (EER) Total Cooling Capacity of Equipment Building Location Zones 6a, 9a, 10a, 11a, 12a, Zones 3a, 3b, 4a, 7a, Zones 4b, 5a, 5b, 12b, 13a, 13b, 14a, 14b, , 9b, 10b, 11b 6b, 7b 90,000 Btu/h to 134,999 Btu/h N/A 11.4 EER 10.4 EER 135,000 Btu/h to 759,999 Btu/h N/A 10.9 EER 9.9 EER 760,000 Btu/h or more N/A 10.5 EER 9.6 EER Section /28/2008 Mathis Consulting Company Page 88

89 Economizers (Complex) In Accordance with Simple Requirements of Section Air economizers required on systems if cooling capacity: > 90,000 Btu/h > 65,000 Btu/h Not required in climate zones: 1, 2, 3b 1, 2, 3b, 5a or 6b Exception Water economizers that can cool supply air by either direct or indirect evaporation or both and provide up to 100% of expected system cooling load at outside air temperatures of 50 F dry bulb/45 F wet bulb and below Not required in systems under 135,000 Btu/h cooling capacity in climate zones 3c, 5b, 7, 13b, 14 1/28/2008 Section Mathis Consulting Company Page 89

90 Air-Side Economizers Use dampers to increase outside air when outside air cool system requires cooling 100% Economizer o Operation Outside Air 55º F Outside air dampers are fully open. Maximum outside air 100% 80º is provided Exhaust F 55º F Normal Operation Outside air dampers are positioned to provide the minimum outside air 80º F 1/28/2008 Section Mathis Consulting Company Page 90

91 Water-Side Economizer Strainer Cycle 1/28/2008 Mathis Consulting Company Page 91

92 Shutoff Dampers (Simple and Complex) Required for outdoor-air and exhaust systems with design air flow rates > 3000 cfm Must automatically close during periods of non-use Simple: Exceptions Where restricted by health and life safety codes Where serving areas designed for continuous operation Systems with readily accessible manual dampers 1/28/2008 Section / Mathis Consulting Company Page 92

93 VAV Fan Control (Complex) Individual fans with motors 25hp Driven by a mechanical or electrical variable speed ddi drive Be a vane-axial fan with variable pitch blades OR Have controls or devices to result in fan motor demand 50% of their design wattage at 50% of design airflow when static pressure set point = 1/3 of the total design static pressure 1/28/2008 Section Mathis Consulting Company Page 93

94 Heat Rejection Equipment (Complex) New 2004 Requirement Each fan powered by a motor 7.5 hp to have capability to operate that fan at 2/3 of full speed or less Have controls to automatically change the fan speed to control the leaving fluid temperature or condensing temperature/pressure of the heat rejection device Exception Factory-installed heat rejection devices within HVAC equipment tested and rated in accordance with Tables (1) 3 through (3) 3 1/28/2008 Section Mathis Consulting Company Page 94

95 Requirements for Multiple Zone Systems (Complex) Systems shall be VAV systems that are designed d and capable of being controlled to reduce primary air supply to each zone to a minimum before reheating, recooling or mixing takes place Several exceptions 1/28/2008 Section Mathis Consulting Company Page 95

96 Duct and Plenum Insulation (Simple and Complex) Required for supply and return ducts and plenums Located in unconditioned d space - R5 Located outside the building envelope - R8 Exceptions Located within equipment Design temperature difference between interior and exterior of duct or plenum > 15 F Ducts designed d to operate at static ti pressures > 3 in. wg to be leak tested in accordance with SMACNA Complex: Furnish documentation that representative sections totaling at least 25% of the duct area have been tested and meet the requirements Section / /28/2008 Mathis Consulting Company Page 96

97 Duct Sealing (Simple and Complex) Seal and securely fasten all joints, longitudinal and transverse seams and connections with: welds gaskets mastics mastic-plus-embedded fabric systems Tapes Duct tape is not permitted as a sealant on any metal ducts 1/28/2008 Section / Mathis Consulting Company Page 97

98 Pipe Insulation (Simple and Complex) Thermally insulated according to Section (complex system requirements refer to Table ) 1/28/2008 Section / Mathis Consulting Company Page 98

99 Pipe Insulation Exceptions Exceptions Factory-installed piping within equipment Piping conveying fluids between 55 F and 105 F Piping conveying fluids not heated or cooled through h the use of fossil fuels or electric power Runout piping not exceeding 4 ft in length and 1 in. in diameter between the control valve and HVAC coil 1/28/2008 Section / Mathis Consulting Company Page 99

100 HVAC System Completion (Complex) Before issuance of certificate t of occupancy Air system balancing Hydronic system balancing Manuals 1/28/2008 Section Mathis Consulting Company Page 100

101 System Balancing (Complex) Supply Air Outlets and Zone Terminal Devices Must Have Means to Air Balance Discharge Dampers Prohibited on Constant Volume and Variable Volume Fans with Motors > 25 Hp Hydronic Systems Individual Hydronic Heating and Cooling Coils to be Equipped with Means for Balancing and Pressure Test Connections Section /28/2008 Mathis Consulting Company Page 101

102 Manuals (Complex) O & M Manual Required Contents Equipment Capacity and Required Maintenance Equipment O & M Manuals HVAC System Control Maintenance and Calibration Information Written Narrative of Each System Operation 1/28/2008 Section Mathis Consulting Company Page 102

103 Heat Recovery for SWH Condenser heat recovery required for heating/reheating h of SWH provided: d Facility operates 24 hours/day Total installed heat capacity of water-cooled systems >6,000,000 Btu/hr of heat rejection Design SWH load >1,000,000 Btu/h The required heat recovery system shall have the capacity to provide the smaller of : 60% of the peak heat rejection load at design conditions or the preheating required to raise the peak service hot water draw to 85 degree F Section /28/2008 Mathis Consulting Company Page 103

104 Service Water Heating Summary of requirements Heat traps to reduce standby losses Pipe insulation to reduce distribution and standby losses Circulation loop temperature controls to reduce distribution losses 1/28/2008Section 804 Mathis Consulting Company Service Water Heating Page 104

105 Typical Commercial Building Energy Consumption Patterns Misc Other Equip. Cooking Refrgd'n Lighting HVAC Water Htg 1/28/2008 Mathis Consulting Company Page 105

106 Heat Traps Required on noncirculating hot water systems Section /28/2008 Mathis Consulting Company Service Water Heating Page 106

107 Pipe Insulation Noncirculating system insulation requirements First eight feet of outlet piping on systems with no integral heat traps 1/2 inch of insulation required Circulating systems 1 inch of insulation Section /28/2008 Mathis Consulting Company Service Water Heating Page 107

108 Hot Water System Controls Application: circulating hot water systems Automatic time switches required to turn off the pump and heat tracer tape when it is not in use Section /28/2008 Mathis Consulting Company Service Water Heating Page 108

109 More Information For additional training materials see s.stm Code Books: 1/28/2008 Mathis Consulting Company Page 109

110 Commercial Energy Code Compliance Lighting Requirements Chapter 8 NCECC 1/28/2008 Mathis Consulting Company Page 110

111 Outline Overview of Commercial Energy Codes Code Requirements Building Envelope Mandatory Requirements Prescriptive Requirements Mechanical Systems Simple Systems Complex Systems Service Water Heating Lighting Systems Requirements for Chapter 7 (ASHRAE 90.1) are covered in a separate presentation 1/28/2008 Mathis Consulting Company Page 111

112 IECC Chapters 7 and 8 Commercial Building Compliance Options Chapter 7 ASHRAE 90.1 Energy Standards for Buildings Except Low- Rise Residential Buildings p Design by Acceptable Practice for Commercial Buildings Scope Section 2 Building Envelope Building Mechanical Systems Section 5 Section 6 (Simple Approach If Bldg < 25,000 s.f.) Service Water Heating Systems Section 7 Building Lighting Systems Section 9 Total Building Performance Section 10 Chapter 8 Section Section Section Section Section Section (less than 50% glazing only) ) 1/28/2008 Mathis Consulting Company Page 112

113 IECC Chapter 8 Design by Acceptable Practice Building System Compliance Options Envelope Lighting Mandatory Provisions (required for all compliance options) Prescriptive Option Trade Off Option Energy Code Compliance Mechanical HVAC Performance Option SWH 1/28/2008 Mathis Consulting Company Page 113

114 Scope General Lighting system controls Connection of ballasts Max. interior lighting power Min. acceptable exterior lighting equipment 1/28/2008 Mathis Consulting Company Page 114

115 Interior Lighting Compliance Mandatory Requirements and Interior Lighting Power Requirements Controls Switching The building complies if its total connected power is no greater than the interior lighting power. Total Connected Power ( ) < Interior Lighting g Power ( ) Entire Building Partial Building 1/28/2008 Mathis Consulting Company Page 115

116 Interior Lighting Controls Lighting controls required for each area enclosed by ceiling height partitions Switch locations In view of lights On or off indication from remote location Occupancy sensor Section /28/2008 Mathis Consulting Company Page 116

117 Interior Lighting Controls Exceptions Emergency/security lighting Stairway or corridor lighting for egress Section /28/2008 Mathis Consulting Company Page 117

118 Additional Controls Each area with mandatory controls must have: Light reduction controls ( ) Automatic ti lighting shutoff ( ) Guestrooms ( ) Exceptions only 1 luminaire an occupant-sensing device corridors, storerooms, restrooms, or public lobbies Section /28/2008 Mathis Consulting Company Page 118

119 Bi-Level Switching Light Reduction Controls Areas that are required to have manual control shall also Reduce connected lighting load uniformly by 50% for each space Exceptions Section /28/2008 Mathis Consulting Company Page 119

120 Bi-Level Switching Compliance Examples Example: Alternate Luminaries S S 1/28/2008 Mathis Consulting Company Page 120

121 Bi-Level Switching Compliance Examples Example: Dimmer Control Option Example: Alternate Lamps (a/b) D S S Dimmer Switch 1/28/2008 Mathis Consulting Company Page 121

122 Automatic Lighting Shutoff In buildings > 5000 ft 2 must have automatic control devices to function cto et either e on Scheduled basis using time-ofday Unscheduled basis by occupant intervention In 2004 IECC requirement for spaces >250 ft 2 in buildings larger than 5,000 ft 2 Section /28/2008 Mathis Consulting Company Page 122

123 Occupant Override Where automatic time switch control devices are installed to comply with Automatic ti Lighting Shutoff, device shall be equipped with an override switching device that: Readily accessbile Located so that person using the device can see the lights or area controlled by the switch Manually operated Allows lighting to remain on for no more than 2 hours when an override is initiated Controls an area <5,000 square feet Some Exceptions Section /28/2008 Mathis Consulting Company Page 123

124 Holiday scheduling If automatic time switch is installed: Automatic holiday scheduling feature that turns off all loads for at least 24 hours and then resumes to normally scheduled operation Exceptions Retail stores and associated malls, restaurants, grocery stores, churches and theaters 1/28/2008 Mathis Consulting Company Page 124

125 Guest Rooms Master switch required at entry $ $ $ $ $ Standard d Room Suite Section /28/2008 Mathis Consulting Company Page 125

126 Exterior Lighting g Controls Automatic switching or photocell controls shall be provided for all exterior lighting not intended for 24 hour operation. Automatic time switches shall have a combination Seven-day and seasonal daylight program schedule adjustment A minimum 4-hour power backup 1/28/2008 Mathis Consulting Company Page 126

127 Tandem Wiring Center to Center Exceptions Luminaires with electronic high-frequency ballasts Luminaires not on same switch controls or not in the same area Section /28/2008 Mathis Consulting Company Page 127

128 Exit Signs Internally illuminated exit signs shall not exceed 5 Watts per side Section /28/2008 Mathis Consulting Company Page 128

129 Interior Lighting Power Requirements Mandatory Requirements and Interior Lighting Power Requirements Controls Switching The building complies if its total connected power is no greater than the interior lighting power. Total Connected Power < Interior Lighting g Power Entire Building Partial Building 1/28/2008 Mathis Consulting Company Page 129

130 Total Connected Power Total connected lighting wattage includes: Lamp wattage Ballast wattage Sources of bulb/ballast wattages Manufacturer s literature Industry default tables Exceptions Specialized medical, dental, and research lighting Professional sports arena playing field lighting Display lighting for gallery exhibits, museums, and monuments Guest room lighting in hotels, motels, boarding houses, or similar buildings Emergency lighting automatically ti off during normal building operation 1/28/2008 Mathis Consulting Company Page 130

131 Energy-Efficient Lighting Sources White LED 1/28/2008 Mathis Consulting Company Page 131

132 Interior Lighting Power Mandatory Requirements and Interior Lighting Power Requirements Controls Switching The building complies if its total connected power is no greater than the interior lighting power. Total Connected Power < Interior Lighting g Power Entire building Building is all one occupancy or a majority occupancy exists (Section ) Tenant area or partial building Use for tenant spaces in larger building or divide whole building into area types Table /Table Entire Building Partial Building 1/28/2008 Mathis Consulting Company Page 132

133 What is the Interior Lighting Power Budget for this Building? Bathrooms Office A: 400 ft 2 Office A Office B: 850 ft 2 Bathrooms: 350 ft 2 Corridor: 50 ft 2 Corridor Retail A: 500 ft 2 Retail B: 500 ft 2 Future: 350 ft 2 Future Development Retail A Retail B Office B Total Building Area = 3000 ft 2 1/28/2008 Mathis Consulting Company Page 133

134 Does the Building Comply? Determine the total connected power in watts for the proposed lighting Determine the interior lighting power budget for the entire building or space Building complies if: Interior lighting power budget - total connected power = 0 1/28/2008 Mathis Consulting Company Page 134

135 Exterior Lighting Criteria Lighting g power supplied through building electrical service Must use energy-efficient lighting sources to highlight paths, walkways and parking areas 45 Lumens/Watt Fluorescent Compact Fluorescent Metal Halide High Pressure Sodium Exceptions Where approved because of the following considerations: Historical Safety Section 805.5/ /28/2008 Signage Mathis Consulting Company Page 135

136 Electrical Energy Consumption In buildings having individual dwelling units, provisions shall be made to determine the electrical energy consumed by each tenant by separately metering individual dwelling units Section /28/2008 Mathis Consulting Company Page 136

137 Conclusion? We can t do it all in a day Web resources Future workshops Plan review training Worked examples But we have to start somewhere! Simple prescriptive techniques will be most common Performance techniques usually involve professionals with a license on the line AIA, PE, etc. 1/28/2008 Mathis Consulting Company Page 137

138 Energy Consumption in Commercial Buildings Matters! More than half of energy use is for HVAC and lighting g Typical energy bill equals 25% of total operating costs Climate sensitive design and off-theshelf technologies can cut energy bill by 50% 1/28/2008 Mathis Consulting Company Page 138

139 Additional Resources gov/training/presentati ons.stm /iecc_com_wb.pdfcom 1/28/2008 Mathis Consulting Company Page 139

140 Occupancy Sensors Section For high usage areas with irregular schedules Applications Private offices Classrooms Conference rooms Break rooms Restrooms 1/28/2008 Mathis Consulting Company Page 140

141 Section 9 Mandatory Provisions Exit Signs (section 9.4.3) New Exit Sign Requirements Internally illuminated exit signs shall not exceed 5 watts per face , IECC /28/2008 Mathis Consulting Company Page 141

IECC 2006 with Hawaii Amendments

IECC 2006 with Hawaii Amendments IECC 2006 with Hawaii Amendments COMMERCIAL PLAN REVIEW CHECKLIST ENVELOPE REQUIREMENTS Instructions This form is intended for use by energy code plan reviewers. Please see also a separate set of checklists

More information

IECC 2006 with Hawaii Amendments

IECC 2006 with Hawaii Amendments IECC 2006 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other notes to the reviewer.

More information

Presentation to Appalachian State University

Presentation to Appalachian State University Presentation to Appalachian State University Boone, NC NC Commercial Energy Code Overview Renee Hutcheson, AIA, LEED AP, PEM Reid Conway, PEM North Carolina State Energy Office Department of Commerce January

More information

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Project: Date: Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other

More information

COMcheck Software Version Envelope Compliance Certificate

COMcheck Software Version Envelope Compliance Certificate COMcheck Software Version 4.0.2.8 Envelope Compliance Certificate Project Information Energy Code: 20 IECC Location: Cedar Hills, Utah Climate Zone: 5b Project Type: New Construction Vertical Glazing /

More information

NC ECC Commercial Training June 2011

NC ECC Commercial Training June 2011 Mathis Consulting Company North Carolina Energy Conservation Code: Commercial Prescriptive Provisions Mathis Consulting Company Building Solutions Chris Mathis 100+ Years of Experience as Building Scientists,

More information

Boulder City NV Prepared by (Print Name) Signature Date

Boulder City NV Prepared by (Print Name) Signature Date City of Boulder City Community Development Department Building & Safety Division 401 California Avenue Boulder City, NV 89005-2600 702-293-9282 (Main Line) 702-293-9392 (Fax) 2009 International Energy

More information

Dayton Chapter February 9, Bob Thomson, P.E., LEED-AP, CDT

Dayton Chapter February 9, Bob Thomson, P.E., LEED-AP, CDT Dayton Chapter February 9, 2009 Bob Thomson, P.E., LEED-AP, CDT World Population is estimated to be 6,000,000,000 people U.S. Population is estimated to be 3,000,000 people U.S. makes up 5% of the world

More information

Next Connecticut Energy Code

Next Connecticut Energy Code Connecticut Chapter Association of Energy Engineers Next Connecticut Energy Code 1 Next Connecticut State Building Code n 2012 International Building Code n 2012 International Existing Building Code n

More information

IECC Commercial Significant Changes Summary Tier I

IECC Commercial Significant Changes Summary Tier I 2009-2015 IECC Commercial Significant Changes Summary Tier I The first change is in the layout of the book. Instead of having Chapters 1-3 that applied to all projects and then having Chapter 4 Residential

More information

Hardin County Planning and Development Commission

Hardin County Planning and Development Commission Location by Climate Zone: Hardin County (per Table N1101.2), and the entire state of Kentucky is located in Climate Zone 4, the HDD is 4000 to 4999. Building Requirements; Building Thermal Envelope The

More information

A Closer Look Inspection Service 2015 IECC Residential DFW area handout

A Closer Look Inspection Service 2015 IECC Residential DFW area handout 103.2 Information required on construction documents 1. Designation of the Thermal Building Envelope on the plans 2. Insulation Material and their R Value 3. Fenestration U and SHGC values 4. Area weighted

More information

REScheck Software Version Compliance Certificate

REScheck Software Version Compliance Certificate REScheck Software Version 4.3.1 Compliance Certificate Project Title: Chow Residence Renovation Energy Code: 2009 IECC Location: Boston, Massachusetts Construction Type: Single Family Project Type: Addition/Alteration

More information

APPROVED. Acceptable to the code official for compliance with the provisions of the applicable Code or referenced Standard.

APPROVED. Acceptable to the code official for compliance with the provisions of the applicable Code or referenced Standard. Chapter 1 101.1 Title. These regulations shall be known as the North Carolina Energy Conservation Code as approved by the North Carolina Building Code Council on March 11, 2008, to be effective January

More information

Plan Check & Field Inspection Guide

Plan Check & Field Inspection Guide Plan Check & Field Inspection Guide 1992 MEC, 1993 MEC, and 1995 MEC Inside This Guide Plan Check Field Inspection Plan Check Building plans and specifications must be submitted with each building application

More information

1. PREINSPECTION RESIDENTIAL ENERGY EFFICIENCY 7

1. PREINSPECTION RESIDENTIAL ENERGY EFFICIENCY 7 Chapter 4 Residential Energy Efficiency [Residential structures include R-3 buildings; R-2 and R-4 buildings three stories or less in height built to the International Building Code (see IBC classifications)]

More information

Charter Township of Washington

Charter Township of Washington Charter Township of Washington Building Department 57900 V an Dyke Washington, MI. 48094 Phone:(586) 786-0010 Ext. 211 Fax: 586-752-6463 2015 Michigan Residential Code Energy Worksheet for New Single-family

More information

Date Rater Verified. Rater Verified. Slab / Pre-Drywall / Thermal Inspection

Date Rater Verified. Rater Verified. Slab / Pre-Drywall / Thermal Inspection Slab on Grade & Basements: A capillary break is installed on top of all footings Slab / Pre-Drywall / Thermal Inspection A minimum of 4" of clean or washed gravel (0.5" diameter or greater) is placed over

More information

Development and Introduction to the 2012 North Carolina Energy Conservation Code

Development and Introduction to the 2012 North Carolina Energy Conservation Code Development and Introduction to the 2012 North Carolina Energy Conservation Code Overview of Today s Discussion Accepting the challenge to develop a stretch energy conservation code The process for preparing

More information

ENERGY STAR Qualified Homes National Program Requirements, Version 3.0

ENERGY STAR Qualified Homes National Program Requirements, Version 3.0 Qualifying Homes The following homes are eligible to earn the ENERGY STAR: Single-family homes; Units in multi-family buildings that are three stories or less; Units in multi-family buildings that are

More information

Energy Code Compliance It s the Law

Energy Code Compliance It s the Law Energy Code Compliance It s the Law Evan Hallas & Yossi Bronsnick Multifamily Performance Program Partner Summit October 24, 2011 Taitem Engineering Taitem Engineering, PC, is a consulting engineering

More information

2015 Michigan Residential Code Energy Worksheet for New Single-family Residential Building

2015 Michigan Residential Code Energy Worksheet for New Single-family Residential Building 2015 Michigan Residential Code Energy Worksheet for New Single-family Residential Building Building Department 52700 Van Dyke, Shelby Township, MI 48316 Phone (586) 731-5969 Fax (586) 803-2099 building@shelbytwp.org

More information

Applying Energy Code to Existing Buildings

Applying Energy Code to Existing Buildings Applying Energy Code to Existing Buildings Massachusetts Energy Code Technical Support Program 1 Who Is Mass Save? Mass Save is an initiative sponsored by Massachusetts gas and electric utilities and energy

More information

2015 Michigan Residential Code Energy Worksheet for New Single-family Residential Building

2015 Michigan Residential Code Energy Worksheet for New Single-family Residential Building 2015 Michigan Residential Code Energy Worksheet for New Single-family Residential Building Building Department 52700 Van Dyke, Shelby Township, MI 48316 Phone (586) 731-5969 Fax (586) 803-2099 building@shelbytwp.org

More information

2009 IECC with St Louis Amendments. Fenestration U-factor Skylight U-factor Glazed fenestration SHGC NR 0.

2009 IECC with St Louis Amendments. Fenestration U-factor Skylight U-factor Glazed fenestration SHGC NR 0. Comparison Between Residential 2009 IECC with St Louis amendments, the 2015 IECC, and 2015 IECC w/ Building Codes Review Committee (BCRC) proposals: Climate Zone 4 Note: This document does not contain

More information

Title 24: Where We're Headed with the 2013 Standards. Featuring: Martyn C. Dodd EnergySoft, LLC

Title 24: Where We're Headed with the 2013 Standards. Featuring: Martyn C. Dodd EnergySoft, LLC Title 24: Where We're Headed with the 2013 Standards Featuring: Martyn C. Dodd EnergySoft, LLC www.energysoft.com Overall Changes in Scope and Application Welcome Overall Changes in Scope and Application

More information

Residential Requirements of the Texas Energy Code 2009 IRC Chap 11

Residential Requirements of the Texas Energy Code 2009 IRC Chap 11 BUILDING ENERGY CODES UNIVERSITY Residential Requirements of the Texas Energy Code 2009 IRC Chap 11 Ken Baker PNNL-SA-65859 The Family of I-Codes International Building Code International Mechanical Code

More information

Feature Zone IECC 2009 IECC

Feature Zone IECC 2009 IECC Feature Zone 3 2006 IECC 2009 IECC Window U factor 0.65 0.50 Skylight U factor 0.65 0.65 Window SHGC 0.40 0.30 Ceiling R value 30 30 Wood frame R value 13 13 Mass wall R value 1 5 5/8 Floor R value 19

More information

2015 Michigan Residential Code Energy Worksheet for Single-family Additions, Alterations, Renovations and Repairs

2015 Michigan Residential Code Energy Worksheet for Single-family Additions, Alterations, Renovations and Repairs 2015 Michigan Residential Code Energy Worksheet for Single-family Additions, Alterations, Renovations and Repairs Building Department 52700 Van Dyke, Shelby Township, MI 48316 Phone (586) 731-5969 Fax

More information

2005 BUILDING ENERGY EFFICIENCY STANDARDS

2005 BUILDING ENERGY EFFICIENCY STANDARDS CALIFORNIA ENERGY COMMISSION 2005 BUILDING ENERGY EFFICIENCY STANDARDS FOR RESIDENTIAL AND NONRESIDENTIAL BUILDINGS S T A N D A R D S / R E G U L A T I O N S Effective Date October 1, 2005 September 2004

More information

2015 MICHIGAN UNIFORM ENERGY CODE Effective: February 8, 2016

2015 MICHIGAN UNIFORM ENERGY CODE Effective: February 8, 2016 CHEBOYGAN COUNTY DEPARTMENT OF BUILDING SAFETY 870 South Main Street P.O. Box 70 Cheboygan, Michigan 49721 Phone: (231) 627-8813 Fax: (231) 627-8454 www.cheboygancounty.net 2015 MICHIGAN UNIFORM ENERGY

More information

Changes to the Minnesota Commercial Energy Code. Presented by: Andy Thielen, PE

Changes to the Minnesota Commercial Energy Code. Presented by: Andy Thielen, PE Changes to the Minnesota Commercial Energy Code Presented by: Andy Thielen, PE Warning! The following is an outline of proposed code changes. There is no guarantee that the final code adopted by the State

More information

Compliance Certificate

Compliance Certificate REScheck Software Version 4.6.3 Compliance Certificate Project Energy Code: 2012 IECC Location: Frederick, Colorado Construction Type: Single-family Project Type: New Construction Conditioned Floor Area:

More information

Energy Code Analysis - Current Requirements & What is Coming International Energy Conservation Code & ASHRAE Standard 90.1

Energy Code Analysis - Current Requirements & What is Coming International Energy Conservation Code & ASHRAE Standard 90.1 The following material provides a general summary of typical energy code requirements for an office building in the St. Louis, MO climate zone, and how they are changing. As one might expect, as time marches

More information

RESIDENTIAL ENERGY CODE. The 2015 International Energy Conservation Code (IECC) as modified below.

RESIDENTIAL ENERGY CODE. The 2015 International Energy Conservation Code (IECC) as modified below. 305-2-4-.10 RESIDENTIAL ENERGY CODE. The 2015 International Energy Conservation Code (IECC) as modified below. (1) IECC CHAPTER 1 SCOPE AND ADMINISTRATION. (a) SECTION R101 SCOPE AND GENERAL REQUIREMENTS.

More information

General Contractor: Company Name: Location of Proposed Structure: Tax Map #: Lot #:

General Contractor: Company Name: Location of Proposed Structure: Tax Map #: Lot #: New Hampshire Residential Energy Code Application Town of Sutton for Certification of Compliance for New Construction, Additions and/or Renovations to be submitted with completed building permit (EC-1

More information

1998 and 2000 International Energy Conservation Code Version 3.0 April 2000

1998 and 2000 International Energy Conservation Code Version 3.0 April 2000 1998 and 2000 International Energy Conservation Code Version 3.0 April 2000 MECcheck TM was developed by the Building Energy Standards Program at Pacific Northwest National Laboratory for use by the U.S.

More information

COMcheck Software Version Envelope Compliance Certificate

COMcheck Software Version Envelope Compliance Certificate COMcheck Software Version 3.9.4 Envelope Compliance Certificate 2009 IECC Section 1: Project Information Project Type: New Construction Project Title : AGORA PALMS APARTMENTS-BUILDING # 1 Construction

More information

Instructions for the Residential Building Data Collection Checklist 2009 International Energy Conservation Code with 2011 Georgia Amendments

Instructions for the Residential Building Data Collection Checklist 2009 International Energy Conservation Code with 2011 Georgia Amendments Instructions for the Residential Building Data Collection Checklist 2009 International Energy Conservation Code with 2011 Georgia Amendments Use of these instructions with a residential data collection

More information

Energy Codes and the Building Envelope

Energy Codes and the Building Envelope Energy Codes and the Building Envelope Goal of Energy Efficient Design A Few Acronyms ASHREA = American Society of Heating, Refrigerating, and Air-Conditioning Engineers ICC = International Code Council

More information

Energy Efficiency Programs

Energy Efficiency Programs Program Overviews Efficiency Programs Description Delivery Model Audit Requirement/ Multifamily - Existing Building Efficiency Alliant Services include free energy assessments, rebates for property owners

More information

Energy Star Qualified - New Homes

Energy Star Qualified - New Homes PDHonline Course G226 (6 PDH) Energy Star Qualified - New Homes Instructor: Jeffrey Havelin, PE 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org

More information

Town/City: State: Zip: Town/City: State: Zip: Phone: Cell: Phone: Cell:

Town/City: State: Zip: Town/City: State: Zip: Phone: Cell: Phone: Cell: Town of Durham, N.H. Residential Energy Code Application for 2012 IECC Code for Certification of Compliance for New Construction, Additions and/or Renovations (EC-1A Form) Minimum Provisions Effective

More information

Page 1. ASHRAE STANDARD Section. COMMENTS This is opinion and not comprehensive.

Page 1. ASHRAE STANDARD Section. COMMENTS This is opinion and not comprehensive. OVERVIEW. 1 PURPOSE. The purpose of this standard is to provide minimum requirements for the energyefficient design of buildings except low rise residential buildings. COMPARISON BETWEEN THE 2009 ICC INTERNATIONAL

More information

2009 IECC Chapter 1 Additions, alterations, renovations or repairs.

2009 IECC Chapter 1 Additions, alterations, renovations or repairs. 2009 IECC Chapter 1 Additions, alterations, renovations or repairs. Additions, alterations, renovations or repairs to an existing building, building system or portion thereof shall conform to the provisions

More information

ASHRAE 90.1 The evolution continues

ASHRAE 90.1 The evolution continues ASHRAE 90.1 The evolution continues 4 March 2009 Mick Schwedler, PE ASHRAE SSPC 90.1 Chair Manager, Trane Applications Engineering Historical Timeline 90.1-1980 updated 90.1-1999 major rewrite 90.1-2001

More information

Ontario s Building Code

Ontario s Building Code Ministry of Municipal Affairs and Housing ONTARIO ONLY Ontario s Building Code PROPOSED CHANGE TO THE 2006 BUILDING CODE CHANGE NUMBER E-SB-10-03-01 CODE REFERENCE Supplementary Standard SB-10 Chapter

More information

Using ASHRAE s ECB Method for determining the LEED TM Energy & Atmosphere Credits

Using ASHRAE s ECB Method for determining the LEED TM Energy & Atmosphere Credits Using ASHRAE s ECB Method for determining the LEED TM Energy & Atmosphere Credits LEED TM NC-2.1 Point Distribution Possible Points Percent Sustainable Site 14 20 Water Efficiency 5 7 Energy & Atmosphere

More information

Retail Effects of ANSI/ASHRAE/IES Standard

Retail Effects of ANSI/ASHRAE/IES Standard Retail Effects of ANSI/ASHRAE/IES Standard 90.1-2016 Prepared by Dialectic Inc. INTRODUCTION Background ANSI/ASHRAE/IES 90.1-2016 Energy Standard for Buildings Except Low-Rise Residential Buildings replaces

More information

THE CITY OF FAYETTEVILLE ADOPTED THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) ON JULY 17, 2012

THE CITY OF FAYETTEVILLE ADOPTED THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) ON JULY 17, 2012 THE CITY OF FAYETTEVILLE ADOPTED THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) ON JULY 17, 2012 Compliance with the code for new residential construction, additions, and substantial remodels will

More information

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal The following documentation provides an example submittal for the LEED-NC v2.1 Energy & Atmosphere Credit 1 (EAc1). This sample EAc1 submittal

More information

Building Envelope

Building Envelope 9.36.2. Building Envelope Module 2 BCBC 9.36. 2014 1 Richard Kadulski Architect 9.36.2. Building Envelope Focus is on total building performance, not just thermal insulation Heat transfer and air leakage

More information

IECC Residential Significant Changes Summary. Tier I

IECC Residential Significant Changes Summary. Tier I 2009-2015 IECC Residential Significant Changes Summary Tier I R401.2 Compliance options for compliance are now prescriptive path, Total UA (which is part of prescriptive), Performance and the new Energy

More information

Town of Farragut RESIDENTIAL CONSTRUCTION ENERGY EFFICIENCY. LAST UPDATE: July 03, 2014

Town of Farragut RESIDENTIAL CONSTRUCTION ENERGY EFFICIENCY. LAST UPDATE: July 03, 2014 Town of Farragut RESIDENTIAL CONSTRUCTION ENERGY EFFICIENCY LAST UPDATE: July 03, 2014 TABLE OF CONTENTS Front Cover Sheet Page 1 Table of Contents Page 2 Applying for a Gas/Mechanical Permit Page 2 Important

More information

Energy Efficiency Requirements 9.36

Energy Efficiency Requirements 9.36 The following information has been obtained from the HPO Illustrated Guide, Energy Efficiency Requirements for Houses in British Columbia, BCBC 9.36 & 9.32, Building Officials Association of British Columbia

More information

1 Exam Prep Florida Building Code-Energy Conservation Edition Tabs and Highlights

1 Exam Prep Florida Building Code-Energy Conservation Edition Tabs and Highlights 1 Exam Prep Florida Building Code-Energy Conservation- 2014 Edition Tabs and s These 1 Exam Prep Tabs are based on the Florida Building Code-Energy Conservation-2014 Edition. Each 1 Exam Prep tabs sheet

More information

OBC SB-10 AND ASHRAE COMPLIANCE SUMMARY

OBC SB-10 AND ASHRAE COMPLIANCE SUMMARY ONTARIO BUILDING CODE SUPPLEMENTARY STANDARD SB-10 PROJECT INFORMATION Project: Building Permit Application No.: Location: Date: Architectural Designer Information* Mechanical Designer Information* Electrical

More information

Welcome IECC Fundamentals. Your Instructor today is: William H. (Bill) Hudson, CBO, MCP

Welcome IECC Fundamentals. Your Instructor today is: William H. (Bill) Hudson, CBO, MCP Welcome 2009 IECC Fundamentals Based on the 2009 International Energy Conservation Code Meet the instructor Participant introductions Why are you here? Your Instructor today is: William H. (Bill) Hudson,

More information

Project Type: New Home Addition Alteration (Describe)

Project Type: New Home Addition Alteration (Describe) MICHIGAN ENERGY CODE WORKSHEET City of Mt. Pleasant - Building Safety Department 320 W. Broadway Street, Mt. Pleasant, MI 48858 (989) 779-5347 www.mt-pleasant.org Effective September 20, 2017, all NEW

More information

Compliance Certificate

Compliance Certificate REScheck Software Version 4.6.2 Compliance Certificate Project Sample Energy Code: 2012 IECC Location: Coeur d'alene, Idaho Construction Type: Single-family Project Type: New Construction Conditioned Floor

More information

Rhode Island Commercial Codes FAQs

Rhode Island Commercial Codes FAQs Rhode Island Commercial Codes FAQs When does the new code go into effect? The new suite of building codes (including the new state energy conservation code, SBC-8) was adopted on July 1, 2013. A brief

More information

New Hampshire Residential Energy Code

New Hampshire Residential Energy Code CHAIRMAN STATE OF NEW HAMPSHIRE EXECUTIVE DIRECTOR Thomas B. Getz AND SECRETARY COMMISSIONERS Debra A. Howland Susan S. Geiger TDD Access: Relay NH Nancy Brockway 1-800-735-2964 Tel. (603) 271-2431 FAX

More information

New Construction Procurement Guidelines for the Pacific Northwest

New Construction Procurement Guidelines for the Pacific Northwest Northwest Portable Classroom Project New Construction Procurement Guidelines for the Pacific Northwest March 31, 2003 WSUCEEP03_063 Washington State University Extension Energy Program 925 Plum Street

More information

Compliance Certificate

Compliance Certificate REScheck Software Version 4.6.4 Compliance Certificate Project RESIDENCE Energy Code: 2009 IECC Location: Perkasie, Pennsylvania Construction Type: Single-family Project Type: New Construction Conditioned

More information

Residential Data Collection Checklist 2009 International Energy Conservation Code Climate Zone 2

Residential Data Collection Checklist 2009 International Energy Conservation Code Climate Zone 2 Residential Data Collection Checklist 2009 International Energy Conservation Code Climate Zone 2 Building Name & Address: Subdivision: Lot #: Conditioned Floor Area: ft 2 State: County: Jurisdiction: Building

More information

ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD (I-P edition) Energy Standard for Buildings Except Low-Rise Residential Buildings.

ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD (I-P edition) Energy Standard for Buildings Except Low-Rise Residential Buildings. ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD 90.1-2010 (I-P edition) Energy Standard for Buildings Except Low-Rise Residential Buildings March 8, 2018 The corrections listed in this errata sheet apply to

More information

Fenestration Components: Mechanical Summary. Water heater energy factor: Ef Fuel type: Gas Electric Other

Fenestration Components: Mechanical Summary. Water heater energy factor: Ef Fuel type: Gas Electric Other This information must be on the drawing documents not attached to plans. The following Compliance statements must be on the drawings: 2009 International Energy Conservation Code Statement of acknowledgement

More information

Prescriptive Checklist for the 2015 Washington State Energy Code

Prescriptive Checklist for the 2015 Washington State Energy Code Prescriptive Checklist for the 2015 Washington State Energy Code Chapter 51-11R WAC STATE BUILDING CODE ADOPTION AND AMENDMENT OF THE 2015 EDITION OF THE INTERNATIONAL ENERGY CONSERVATION CODE, RESIDENTIAL

More information

2012 IECC Residential with State Adopted Changes

2012 IECC Residential with State Adopted Changes 2012 IECC Residential with State Adopted Changes Salt Lake County Townships 385-468-6694 801-381-1449 bursenbach@slco.org bursenbach@yahoo.com BUILDING TALK 1 2 The Family of I-Codes International Building

More information

Residential Buildings Energy Code Summary

Residential Buildings Energy Code Summary CITY OF PLEASANT HILL BUILDING DEPARTMENT Residential Buildings Energy Code Summary Overview Iowa homebuyers appreciate the comfort and warmth of well-designed, energy-efficient houses. With the upgrade

More information

ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD (I-P edition) Energy Standard for Buildings Except Low-Rise Residential Buildings.

ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD (I-P edition) Energy Standard for Buildings Except Low-Rise Residential Buildings. ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD 90.1-2010 (I-P edition) Energy Standard for Buildings Except Low-Rise Residential Buildings April 17, 2013 The corrections listed in this errata sheet apply to

More information

ATS Le Grandiose, Sector 150 Noida. Energy Conservation Building Code (ECBC) Compliance Report

ATS Le Grandiose, Sector 150 Noida. Energy Conservation Building Code (ECBC) Compliance Report Energy Conservation Building Code (ECBC) Compliance Report ATS Le Grandiose, Sector 150 Noida Energy Conservation Building Code (ECBC) Compliance Report For M/s. Nobility Estates Pvt. Ltd. ECBC CONTENTS

More information

RESIDENTIAL ENERGY EFFICIENCY

RESIDENTIAL ENERGY EFFICIENCY CHAPTER 4 RESIDENTIAL ENERGY EFFICIENCY This chapter has been revised in its entirety; there will be no marginal markings. SECTION 401 GENERAL 401.1 Scope. This chapter applies to residential buildings.

More information

Air Sealing for 5 ACH 50

Air Sealing for 5 ACH 50 November 13th, 2018 Christopher Hine Air Sealing for 5 ACH 50 www.phrc.psu.edu Provider # 60114115 PPP ID: 1562 November 13th, 2018 Christopher Hine Air Sealing for 5 ACH 50 www.phrc.psu.edu Provider #

More information

2009 IECC Fundamentals. Your Instructor today is: William H. (Bill) Hudson, CBO, MCP. Based on the 2009 International Conservation Energy Code

2009 IECC Fundamentals. Your Instructor today is: William H. (Bill) Hudson, CBO, MCP. Based on the 2009 International Conservation Energy Code 2009 IECC Fundamentals Based on the 2009 International Conservation Energy Code Your Instructor today is: 2 William H. (Bill) Hudson, CBO, MCP 3 1 Standards Technical Panel for Energy Management Equipment,

More information

COMMERCIAL ENERGY EFFICIENCY

COMMERCIAL ENERGY EFFICIENCY COMMERCIAL ENERGY EFFICIENCY Commercial buildings are all buildings that are not detached one- or two-family dwellings, multiple single-family dwellings (townhouses), or Group R-2, R-3 or R-4 buildings

More information

REScheck Compliance Certificate Massachusetts Energy Code REScheck Software Version 3.6 Release 1 Data filename: O:\REScheck 38\38258.

REScheck Compliance Certificate Massachusetts Energy Code REScheck Software Version 3.6 Release 1 Data filename: O:\REScheck 38\38258. Permit Number REScheck Compliance Certificate Massachusetts Energy Code REScheck Software Version 3.6 Release 1 Data filename: O:\REScheck 38\38258.rck Checked By/Date PROJECT TITLE: All American / Whalen

More information

A LOOK INTO THE 2015 IECC RESIDENTIAL PROVISIONS. Presented by: Shaunna Mozingo, Colorado Code Consulting

A LOOK INTO THE 2015 IECC RESIDENTIAL PROVISIONS. Presented by: Shaunna Mozingo, Colorado Code Consulting A LOOK INTO THE 2015 IECC RESIDENTIAL PROVISIONS Presented by: Shaunna Mozingo, Colorado Code Consulting WHAT CAN WE EXPECT TO SEE? Some consensus on enough is enough for now - No real roll backs, no real

More information

Single Family Residence Building Permits

Single Family Residence Building Permits Village of Northbrook Department of Building & Development Guide to: Designing, Documenting & Inspecting For Energy Code Compliance Single Family Residence Building Permits New Construction Additions Alterations

More information

Standards for Jackson EMC s Right Choice Program Revised: June 2011

Standards for Jackson EMC s Right Choice Program Revised: June 2011 Standards for Jackson EMC s Right Choice Program Revised: June 2011 All homes in the program must meet the requirements of the Georgia Energy Code, which is the International Energy Conservation Code (IECC)

More information

Energy Code Compliance:

Energy Code Compliance: Energy Code Compliance: Wood-Frame Buildings and the IECC Presented 4 March 2015 by Andrew Klein, P.E. Disclaimer: This presentation was developed by a third party and is not funded by WoodWorks or the

More information

CREDIT COMPLIANCE (Please complete the color coded criteria(s) based on the option path selected)

CREDIT COMPLIANCE (Please complete the color coded criteria(s) based on the option path selected) (Responsible Individual) (Company Name) I,, from verify that the information provided below is accurate, to the best of my knowledge. CREDIT COMPLIANCE (Please complete the color coded criteria(s) based

More information

The baseline building system for compliance with Senate Bill 668 is defined by Appendix G,

The baseline building system for compliance with Senate Bill 668 is defined by Appendix G, Project: North Carolina A&T State University New Student Health Center SCO #: 08-08109-01A 1.0 Heating, Ventilating and Air Conditioning (HVAC) Baseline Building Systems Senate Bill 668 Compliance The

More information

Supplementary Standard SB-12. Energy Efficiency For Housing

Supplementary Standard SB-12. Energy Efficiency For Housing OBC Excerpt: SB 12 Ministry of Municipal Affairs and Housing Building and Development Branch 2006 Building Code - Supplementary Standards Supplementary Standard SB-12 Energy Efficiency For Housing November

More information

Presented by: Stephen Carr Regional Building Science Manager (386)

Presented by: Stephen Carr Regional Building Science Manager (386) Presented by: Stephen Carr Regional Building Science Manager (386) 846-9155 stephen.carr@topbuild.com Understanding the Energy Code 2015 IECC CZ 1 CZ 2 CZ 3 CZ 4 CZ 5 CZ 6 CZ 7&8 Ceiling 30 38 38 49 49

More information

how to read an energy model

how to read an energy model how to read an energy model Kohler Ronan, LLC is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported

More information

2014 British Columbia Building Code Changes

2014 British Columbia Building Code Changes 2014 British Columbia Building Code Changes A City of Prince George interpretation of the 2014 Building Code Changes for 9.32 & 9.36 The following changes reflect the most notable revisions and staff interpretations.

More information

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort Please add relevant logo here Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort Presented by: Peter J. Arsenault, FAIA, NCARB, LEED-AP Disclaimer: This presentation was developed by

More information

CHAPTER 1: OVERVIEW OF ENERGY EFFICIENT CONSTRUCTION

CHAPTER 1: OVERVIEW OF ENERGY EFFICIENT CONSTRUCTION Chapter 1: Overview of Energy Efficient Construction 1 CHAPTER 1: OVERVIEW OF ENERGY EFFICIENT CONSTRUCTION Chapter 1 is a quick reference guide that discusses the key components and features of energy

More information

2009 IECC Commercial Lighting Requirements

2009 IECC Commercial Lighting Requirements BUILDING ENERGY CODES UNIVERSITY 2009 IECC Commercial Lighting Requirements Ken Baker ken@kenergy.us PNNL-SA-66170 Learning(Objec-ves(( ( 1. List(2(exemp-ons(to(mee-ng(ligh-ng(and(power( requirements.(

More information

2015 IECC Air Sealing Multifamily For Code Compliance Funding for Energy Code Training

2015 IECC Air Sealing Multifamily For Code Compliance Funding for Energy Code Training 2015 IECC Air Sealing Multifamily For Code Compliance 2 Funding for Energy Code Training 1 Sponsor Also Recognize Resources Provided by Department of Energy: DOE Building America Program https://www.energycodes.gov/

More information

Table Air Barrier and Insulation Inspection Component Criteria

Table Air Barrier and Insulation Inspection Component Criteria Table 40.4. Air Barrier and Insulation Inspection Component Criteria NUMBER COMPONENT CRITERIA Air barrier and thermal barrier Exterior thermal envelope insulation for framed walls is installed in substantial

More information

2016 ASHRAE 90.1 Summary of Important Changes

2016 ASHRAE 90.1 Summary of Important Changes 2016 ASHRAE 90.1 Summary of Important Changes 1 Overview ANSI/ASHRAE/IES Standard 90.1-2016, Energy Efficiency Standard for Buildings Except Low-Rise Residential Buildings, incorporates more than 120 updates

More information

Appendix E-1f: Small Building Methodology for Pre-SB2030 Projects

Appendix E-1f: Small Building Methodology for Pre-SB2030 Projects Appendix E-1f: Small Building Methodology for Pre-SB2030 Projects Prescriptive Bundle Option Method for Office Buildings less than 30,000 GSF This section describes energy strategy requirements for three

More information

CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8)

CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8) CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8) Builder or Installer Name Builder or Installer Contact Telephone Plan/Permit (Additions or Alterations) Number Compliance Method (Prescriptive)

More information

2010 Residential Energy Checklist: Additions/Alterations (Prescriptive Approach)

2010 Residential Energy Checklist: Additions/Alterations (Prescriptive Approach) 2010 Residential Energy Checklist: Additions/Alterations (Prescriptive Approach) Component Less than equal to 100 sq. ft. Addition Less than equal to 1000 sq. ft. Addition Greater than 1000 sq. ft. Addition

More information

Michigan Energy Code Training and Implementation Program

Michigan Energy Code Training and Implementation Program Michigan Energy Code Training and Implementation Program 1.0 Hour Advanced Program Course Number 16202 Residential Energy Plan Review School of Planning, Design & Construction Michigan State University

More information

Rebates for Improvements Home Efficiency Program Fort Collins Utilities

Rebates for Improvements Home Efficiency Program Fort Collins Utilities Rebates for Improvements Home Efficiency Program Fort Collins Utilities Revised 03/04/2013 This matrix summarizes information regarding Home Efficiency Program rebates for improving homes in Fort Collins.

More information

Hawaii Amendments to the 2009 International Energy Conservation Code (IECC) January 30, 2012 version. Training Handout

Hawaii Amendments to the 2009 International Energy Conservation Code (IECC) January 30, 2012 version. Training Handout Hawaii Amendments to the 2009 International Energy Conservation Code (IECC) January 30, 2012 version Training Handout Hilo, Feb. 21, 2012 Kona, Feb. 22, 2012 Honolulu Feb. 23 & 24, 2012 Kahului, Feb. 27,

More information

REScheck Software Version Compliance Certificate

REScheck Software Version Compliance Certificate REScheck Software Version 4.3.0 Compliance Certificate Project Title: Breen Sample Residence Energy Code: 2006 IRC Location: Denver, Colorado Construction Type: Single Family Glazing Area Percentage: 14%

More information