Forensic Mycology How do Hygienist Add Value? Dr Heike Neumeister-Kemp Mariam Begum Sam Athanasios

Size: px
Start display at page:

Download "Forensic Mycology How do Hygienist Add Value? Dr Heike Neumeister-Kemp Mariam Begum Sam Athanasios"

Transcription

1 Forensic Mycology How do Hygienist Add Value? Dr Heike Neumeister-Kemp Mariam Begum Sam Athanasios

2 Case study Tenant claimed lack of maintenance by landlord of a commercial building resulting in defects causing mould proliferation Building mould proliferation claimed to be causing extensive mould proliferation/damage to stock, and repository symptoms in staff handling the stock Inspection and sampling identified inconsistent and disparate mould levels on stock items Forensic analysis of samples different species of mould in the building to that on stock Concluded that source of observed mould was not in the building

3

4 Methods Used three different sampling techniques Each technique targeted at producing answer to slightly different question Viable airborne sampling what is the level and species of live mould in the air? Non-Viable airborne sampling what is the total level mould in the air, and the relative quantities of each genera in the genera spectrum? Non-viable surface sampling what is the total level mould on stock items, and the relative quantities of each genera in the genera spectrum?

5 Table 1: Viable Airborne Fungal Concentrations (CFU/m3) Location CFU/m3 Rating Above / Below OA Outdoor Air Reference 618 High NA 530 High NA Shoes section middle 106 Very Low Below Shoes section front 230 Moderate Below Shoes section end wall 194 Moderate Below Shop front aisle 106 Very Low Below Shop end LH 141 Low Below Cashier 247 Moderate Below Shop middle aisle BDL BDL Below Shop end aisle RH 71 Very Low Below Indoor Average 137 Low Below Outdoor Average 574 High -

6 Table 1: Viable Airborne Fungal Concentrations (CFU/m3) CFU/m 3 BDL 18 <107 <142 <177 <354 <707 <2827 <5652 >7067 Rating BDL Single Colon y Low to Very Low Low Moderat e Moderat e High Very High Extremel y High TNTC

7

8 Table 2: Legend Viable Airborne Fungal Genera Mixture

9 Table 2: Legend Viable Airborne Fungal Genera Mixture

10 Results The various sampling techniques employed showed that there were two main groups of mould genera/species present One genera/species was found predominantly of the stock items The second genera/species group was found predominately in the building environment The levels of genera/species group found on the stock items was generally much higher than the level of the genera/species group found in the building environment Not all stock items were equally affected, with some heavily affected, and others almost clear of mould

11

12

13 Table 3: Viable Surface Fungal Concentrations (CFU/Plate) Location CFU/Plate Rating Inside shoe contamination 25 Moderate Inside shoe clean BDL BDL HVAC vent 2 Very Low Rating BDL Very Low Low Moderate High Very High Extremely High TNTC CFU/Plate < >594 CFU/cm2 < >25.0

14

15 Figure 2: Viable Surface Fungal Concentrations (CFU/Plate)

16 Symbol CFU/Plate <1 <6 <18 <30 <60 >150 Rating BDL Several Establishe Moderate High Dominant Colonie d Concentration Concentration Genera s Genera s s

17 Table 5: Non-Viable Bio-Tape Surface Fungal Spore Concentrations (spores/cm2) Conce ntratio ns (spore s/cm2 ) Asper gillus/ Penicil lium sp. Clados poriu m sp. Altern aria sp. Gen Dirt & Debris (L, M, H, VH) RATI NGS (BDL, L, N, E, C, EC) Location Inside shoe contamination Low EC HVAC vent Very High EC Inside shoe contamination Low EC

18 Total (Viable + Non-viable) Fungal Hygiene Guide for Indoor Surfaces Hygiene Rating Below Detectable Limits (BDL) Lowb (L) Normal (N) Elevatedc (E) Contaminatedd (C) Extreme Contaminatione (EC) Totala Surface Fungal Spora Concentration <1 spore/m3 < 50 spores/cm2 50 to 500 spores/cm2 500 to 1000 spores/cm2 + prevailing species > 1000 spores/cm2 + dominant species + Propagules > 5000 spores/cm2 + dominant species + Propagules + confluent spores

19 Figure 3: Non-Viable Surface Fungal Spores Concentrations (spores/cm2)

20 Table 6: Indoor Air Quality Results Location CO2 (ppm) Air Temp ( C) RH (%) Outdoor Air Shoes end Shoes middle Cashier Shop front Shoes front Ladies shoes

21 Results The various sampling techniques employed showed that there were two main groups of mould genera/species present One genera/species was found predominantly of the stock items The second genera/species group was found predominately in the building environment The levels of genera/species group found on the stock items was generally much higher than the level of the genera/species group found in the building environment Not all stock items were equally affected, with some heavily affected, and others almost clear of mould

22

23 Summary A building defects dispute was claimed to have resulted in mould proliferation and consequent contamination, reportedly affecting staff and stock Inspection, sampling and analysis were conducted to inform a forensic mycology analysis Two distinct genera/species groups were identified, with one group exhibiting much higher levels than the other A forensic mycology analysis concluded that the source of mould proliferation was not the building environment It was found that contaminated stock was brought into the building the building was not the source of mould proliferation

24 Conclusion A carefully targeted sampling strategy, and forensic mycology analysis can be a very powerful and significant value-add tool A robust and structured approach can produce an accurate evidencebased result, even though the result may have appeared completely counter-intuitive at the outset The accurate identification of the source of mould, ensured steps for the protection of staff and other stock Forensic mycology analysis likely saved hundred's of thousands of dollars, in litigation costs, and presented a very significant value-add.

ANALYTICAL REPORT. Airconstruct HVAC Pty Ltd 37 Carlyle Street Mackay QLD Withheld PROPERTY:

ANALYTICAL REPORT. Airconstruct HVAC Pty Ltd 37 Carlyle Street Mackay QLD Withheld PROPERTY: NSJ EnviroSciences Pty Ltd t/a MouldLab ABN 27 143 789 995 PO Box 306 WICKHAM NSW 2293 Phone: 02 4968 8448 Fax: 02 8004 3576 Mobile: 0410 239 848 Email: ---------------------------- ANALYTICAL REPORT CLIENT:

More information

The attached report is the result of a mold and bacterial assessment conducted at th Street, Franklin, Ohio on April 24 and 25, 2008.

The attached report is the result of a mold and bacterial assessment conducted at th Street, Franklin, Ohio on April 24 and 25, 2008. May 8, 2008 Jon Lampros President Clean Air Systems 701 Rockland Rd. Lake Bluff, IL 60044 Re: Assessment of Ozone Treatment on Microbial Populations Dear Mr. Lampros, The attached report is the result

More information

MICROBIAL MEASUREMENTS AT VENTILATION SYSTEMS SUPPLY VENTS

MICROBIAL MEASUREMENTS AT VENTILATION SYSTEMS SUPPLY VENTS MICROBIAL MEASUREMENTS AT VENTILATION SYSTEMS SUPPLY VENTS M.Hinker * Allgemeine Unfallversicherungsanstalt, Wien, Österreich (General Workers Compensation Board, Vienna, Austria) ABSTRACT The number of

More information

THE EFFECT OF DUCT CLEANING ON INDOOR AIR QUALITY IN OFFICE BUILDINGS

THE EFFECT OF DUCT CLEANING ON INDOOR AIR QUALITY IN OFFICE BUILDINGS THE EFFECT OF DUCT CLEANING ON INDOOR AIR QUALITY IN OFFICE BUILDINGS S Kolari 1*, M Luoma 1, M Ikäheimo 2 and P Pasanen 2 1 VTT Technical Research Centre of Finland, Espoo, Finland 2 University of Kuopio,

More information

October 14, Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona PO#

October 14, Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona PO# Asbestos Testing Lead Testing Microbial Testing Management Analysis Environmental Assessment October 14, 2014 Attn: Deer Valley Unified School District Jim Migliorino 20402 North 15th Avenue Phoenix, Arizona

More information

September 18, 204. Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona 85383

September 18, 204. Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona 85383 Asbestos Testing Lead Testing Microbial Testing Management Analysis Environmental Assessment September 18, 204 Attn: Valley Schools Insurance Trust and Pools Scott McCleary PO Box 41760 Phoenix, Arizona

More information

Basic Industrial Hygiene Sampling Overview of Indoor Air Quality

Basic Industrial Hygiene Sampling Overview of Indoor Air Quality Basic Industrial Hygiene Sampling Overview of Indoor Air Quality Bryan K. Stolte, Ph.D., C.I.H. Alcatel-Lucent Corporate EHS Office International Telecommunication Safety Conference Denver, CO Sept 14

More information

NCCEH Mould Investigation Toolkit

NCCEH Mould Investigation Toolkit NCCEH Mould Investigation Toolkit Interpretation of Microbial Laboratory Reports NOVEMBER 2014 Table of Contents Introduction... 2 Generic Information All Microbial Laboratory Reports... 3 Direct Examination

More information

INTERPRETING MICROBIAL MEASUREMENT AND ANALYSIS

INTERPRETING MICROBIAL MEASUREMENT AND ANALYSIS INTERPRETING MICROBIAL MEASUREMENT AND ANALYSIS T Nathanson* Public Works and Government Services Canada, Ottawa, Canada ABSTRACT The potential for microbial contamination exists in every building and

More information

November 18, Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona PO#

November 18, Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona PO# Asbestos Testing Lead Testing Microbial Testing Management Analysis Environmental Assessment November 18, 2014 Attn: Deer Valley Unified School District Jim Migliorino 20402 North 15th Avenue Phoenix,

More information

NCCEH Mould Investigation Toolkit

NCCEH Mould Investigation Toolkit NCCEH Mould Investigation Toolkit Overview of Microbial Sampling Methods NOVEMBER 2014 Table of Contents Air Sampling... 2 Liquid Impinger... 2 Fungal Spore Sampling/Spore Traps... 3 Impactor Samplers

More information

INDOOR AIR QUALITY ASSESSMENT

INDOOR AIR QUALITY ASSESSMENT INDOOR AIR QUALITY ASSESSMENT Biddeford Intermediate School Biddeford Primary School JFK Memorial Kindergarten Center Biddeford High School Air Quality Management Services, Inc. PREPARED FOR Biddeford

More information

AN INVESTIGATION ON THE OCCURRENCE OF FUNGI AND BACTERIA IN THE MVAC SYSTEM IN AN OFFICE PREMISE

AN INVESTIGATION ON THE OCCURRENCE OF FUNGI AND BACTERIA IN THE MVAC SYSTEM IN AN OFFICE PREMISE AN INVESTIGATION ON THE OCCURRENCE OF FUNGI AND BACTERIA IN THE MVAC SYSTEM IN AN OFFICE PREMISE PK Chow, WY Chan *, LLP Vrijmoed Department of Biology and Chemistry, City University of Hong Kong, Tat

More information

HVAC. Hygiene. abstract. Mr Jeremy Stamkos

HVAC. Hygiene. abstract. Mr Jeremy Stamkos NADCA Mr Jeremy Stamkos Managing Director, Enviroair Pty Ltd Certified Air Systems Cleaning Specialist abstract This article has been written to assist those responsible for the maintenance and operation

More information

Indoor Air Quality Monitoring. Aerosol Particle Counter used in Mold Investigation at Local School

Indoor Air Quality Monitoring. Aerosol Particle Counter used in Mold Investigation at Local School A p p l i c a t i o n N o te Indoor Air Quality Monitoring Aerosol Particle Counter used in Mold Investigation at Local School Aerosol Particle Counter used in Mold Investigation at Local School by Jim

More information

TN Tatem Middle School Indoor Air Quality Assessment September 2016

TN Tatem Middle School Indoor Air Quality Assessment September 2016 TN Tatem Middle School Indoor Air Quality Assessment September 2016 Completed by Island Air Quality Services P.O. Box SN139 Southampton SNBX Bermuda Table of Contents 1 Report Summary... 1 2 Introduction

More information

MACRO- AND MICRO-EVALUATION OF AIR INTAKE - A DEMONSTRATION OF THE NEED FOR MORE OPTIMAL TOOLS

MACRO- AND MICRO-EVALUATION OF AIR INTAKE - A DEMONSTRATION OF THE NEED FOR MORE OPTIMAL TOOLS MACRO- AND MICRO-EVALUATION OF AIR INTAKE - A DEMONSTRATION OF THE NEED FOR MORE OPTIMAL TOOLS F Frydenlund, EN Haugen *, C Ahlén, I Bryn, H Davidsen, SO Hanssen and GT Møgedal SINTEF Energy Research,

More information

According to our research and study most occupant complaints relating to IAQ are attributable to the following factors:

According to our research and study most occupant complaints relating to IAQ are attributable to the following factors: Report pertaining to the Duct Cleaning of ICU! &ICU2 at Hospital 5 th & 6 th Floor. The IAQ Report documents by Photograph (at random) photo shots of the various ducting systems & AHU Systems for work

More information

MVOC EMISSIONS FROM FUNGI IN HVAC SYSTEM

MVOC EMISSIONS FROM FUNGI IN HVAC SYSTEM MVOC EMISSIONS FROM FUNGI IN HVAC SYSTEM JS Park * and K Ikeda Dept. Of Architectural Hygiene Engineering and Housing, National Institute of Public Health, Japan ABSTRACT The purpose of this research was

More information

A L A R A Environmental Health & Safety Ltd.

A L A R A Environmental Health & Safety Ltd. Metro Home Inspections October 4, 2010 7626 Arvin Court Burnaby, BC V5A 4M9 ATTENTION: Mr. Mark Fagrie RE: Indoor Air Quality Investigation at Little Mountain Housing, 159 Grouse Walk, Vancouver, BC Dear

More information

Dalrymple Consulting, Inc. "Your Environmental Engineering Source" 7841 SW 1 i b Street, Topeka, Kansas (785) FAX (785)

Dalrymple Consulting, Inc. Your Environmental Engineering Source 7841 SW 1 i b Street, Topeka, Kansas (785) FAX (785) Dalrymple Consulting, Inc. "Your Environmental Engineering Source" 7841 SW 1 i b Street, Topeka, Kansas 66615-1406 (785) 273-0345 FAX (785) 273-3071 January 10,2012 Mr. Steve Wiseman, Superintendent Atchison

More information

MATT FRAGALA, M.S., C.I.H. PRACTICE DIRECTOR, EDUCATION AND COMMERCIAL / SENIOR SCIENTIST ENVIRONMENTAL HEALTH & ENGINEERING

MATT FRAGALA, M.S., C.I.H. PRACTICE DIRECTOR, EDUCATION AND COMMERCIAL / SENIOR SCIENTIST ENVIRONMENTAL HEALTH & ENGINEERING PRESENTERS MATT FRAGALA, M.S., C.I.H. PRACTICE DIRECTOR, EDUCATION AND COMMERCIAL / SENIOR SCIENTIST ENVIRONMENTAL HEALTH & ENGINEERING Matt is a Senior Scientist / Practice Director, Education and Commercial

More information

Indoor Air Quality Report

Indoor Air Quality Report Indoor Air Quality Report Shawnee City Hall 222 N. Broadway, Shawnee, Oklahoma 74801 INDOOR AIR QUALITY SAMPLING REPORT Project Locations: Shawnee City Hall 222 N. Broadway, Shawnee, Oklahoma 74801 Prepared

More information

MOLD REMEDIATION PROCEDURES AT A NEW JERSEY ELEMENTARY SCHOOL

MOLD REMEDIATION PROCEDURES AT A NEW JERSEY ELEMENTARY SCHOOL MOLD REMEDIATION PROCEDURES AT A NEW JERSEY ELEMENTARY SCHOOL M McGuinness * R.K. Occupational and Environmental Analysis, Phillipsburg, NJ, USA ABSTRACT Microbiological remediation procedures at an Elementary

More information

ANALYSIS OF FUNGI (MOLD) IN THE INDOOR ENVIRONMENTS BY DIRECT MICROSCOPIC EXAMINATION. (Analysis Code: FDE)

ANALYSIS OF FUNGI (MOLD) IN THE INDOOR ENVIRONMENTS BY DIRECT MICROSCOPIC EXAMINATION. (Analysis Code: FDE) Expert Services in Environmental Microbiology Report Supporting Document ANALYSIS OF FUNGI (MOLD) IN THE INDOOR ENVIRONMENTS BY DIRECT MICROSCOPIC EXAMINATION (Analysis Code: FDE) INTRODUCTION Fungi are

More information

A Study of Indoor Environmental Quality Parameters in a South Central Kentucky Daycare Facility

A Study of Indoor Environmental Quality Parameters in a South Central Kentucky Daycare Facility A Study of Indoor Environmental Quality Parameters in a South Central Kentucky Daycare Facility Emmanuel Iyiegbuniwe, Ph.D. Western Kentucky University Bowling Green, KY 42101 Introduction Rapid advances

More information

Airborne Mould Spore Assessment and Inspections

Airborne Mould Spore Assessment and Inspections Sterling IAQ Consultants Ltd. Suite 310-1122 Mainland Street Vancouver, B.C., V6B 5L1 (t) 604.681.2701 (f) 604.681.2702 www.sterlingiaqconsultants.com Airborne Mould Spore Assessment and Inspections Sungod

More information

Proceedings: Indoor Air 2002

Proceedings: Indoor Air 2002 MICROBIAL ANALYSIS OF DEPOSIT DUST ON SURFACES IN BUILDINGS OFFICES EQUIPPED WITH CENTRAL AIR- CONDITIONING INSTALLATIONS: PROPOSED MICROBIAL PRACTICAL VALUES WITH A NEW STANDARDIZED METHOD C Chasseur

More information

Microbial Contamination

Microbial Contamination Microbial Contamination IN HVAC SYSTEMS M r J e r e m y S t a m k o s Managing Director Enviroair Pty Ltd NADCA Certified Air Systems Cleaning Specialist (USA) IAQA Certified Mould Remediator (USA) ABSTRACT

More information

International Perspective on Clean Air and Energy Efficiency in Buildings. Morad R. Atif, PhD. Director, Architectural Engineering

International Perspective on Clean Air and Energy Efficiency in Buildings. Morad R. Atif, PhD. Director, Architectural Engineering International Perspective on Clean Air and Energy Efficiency in Buildings Morad R. Atif, PhD. Director, Architectural Engineering Architectural Engineering at Texas A&M New Bachelor of Science in Interdisciplinary

More information

Developed and Presented by: Wisconsin Healthcare Engineering Association

Developed and Presented by: Wisconsin Healthcare Engineering Association Infection Control Risk Assessment (ICRA) Developed and Presented by: Wisconsin Healthcare Engineering Association What is an ICRA? An Infection Control Risk Assessment is a tool devised to protect patients

More information

NADCA S MOLD AWARENESS

NADCA S MOLD AWARENESS NADCA S MOLD AWARENESS WHAT IS MOLD? According to Webster, mold is a surface growth of fungus (molds, mildews, and mushrooms) especially on damp or decaying matter. BASIC DEFINITIONS Mold a one or many

More information

UBC Social Ecological Economic Development Studies (SEEDS) Student Report

UBC Social Ecological Economic Development Studies (SEEDS) Student Report UBC Social Ecological Economic Development Studies (SEEDS) Student Report Indoor Air Quality Assessment CHBE building Second floor Bojosi Gamontle, Jackie Law, Navid Taherdin University of British Columbia

More information

Indoor Air Quality Tools for Schools

Indoor Air Quality Tools for Schools CT School Indoor Environment Resource Team 2nd Training Session: Walkthrough Investigations Indoor Air Quality Tools for Schools Agenda: Welcome, Introductions Show and Tell: Presentation of Blueprints,

More information

Indoor air quality at selected wards at a South African government hospital. *N.J. Malebo 1 and K. Shale 2

Indoor air quality at selected wards at a South African government hospital. *N.J. Malebo 1 and K. Shale 2 Indoor air quality at selected wards at a South African government hospital *N.J. Malebo 1 and K. Shale 2 1. Central University of Technology, Bloemfontein, Republic of South Africa 2. Central University

More information

What s in the Air - Truths, Myths & Simple Strategies

What s in the Air - Truths, Myths & Simple Strategies What s in the Air - Truths, Myths & Simple Strategies Presented By: Marek Plawinski, M.Sc., MPH, R.Kin. About Inc. Workshop Objectives 1. What is indoor Air Quality 2. IAQ Investigation 3. Simple Field

More information

AIVC #12,964 ABSTRACT INTRODUCTION THE PACT OF H.V.A.C. SYSTEM CLEANING ON LEVELS OF SURFACE DUST AND VIABLE FUNGI IN DUCTWORK

AIVC #12,964 ABSTRACT INTRODUCTION THE PACT OF H.V.A.C. SYSTEM CLEANING ON LEVELS OF SURFACE DUST AND VIABLE FUNGI IN DUCTWORK . -,., _,.. - ---......,..----- -- - ------- AIVC #,96 THE PACT OF H.V.A.C. SYSTEM CLEANING ON LEVELS OF SURFACE DUST AND VIABLE FUNGI IN DUCTWORK CW Collett\ T Nathanson, J A Scott', K Baer and J Waddington6

More information

A FIELD COMPARISON OF METHODS FOR ENUMERATING AIRBORNE FUNGAL BIOAEROSOLS

A FIELD COMPARISON OF METHODS FOR ENUMERATING AIRBORNE FUNGAL BIOAEROSOLS A FIELD COMPARISON OF METHODS FOR ENUMERATING AIRBORNE FUNGAL BIOAEROSOLS KS Lee 1*, W Black 2, M Brauer 1, G Stephens 2, K Teschke 1, J Hsieh 1 and K Bartlett 1 1 School of Occupational and Environmental

More information

INTRODUCTION: METHODOLOGY: November 11, Mr. Tim Squier 487 Deerfield Dakota Dunes, SD 57049

INTRODUCTION: METHODOLOGY: November 11, Mr. Tim Squier 487 Deerfield Dakota Dunes, SD 57049 November 11, 2011 Mr. Tim Squier 487 Deerfield Dakota Dunes, SD 57049 Re: Project #: 4004-040 487 Deerfield, Dakota Dunes SD Microbial Clearance Testing INTRODUCTION: This report presents the findings

More information

February 21, Mold Assessment. 400 East Avenue, Warwick, Rhode Island. Dear Mr. McCabe:

February 21, Mold Assessment. 400 East Avenue, Warwick, Rhode Island. Dear Mr. McCabe: February 21, 2014 Mr. Ken McCabe Lincoln Campus Physical Plant Director Community College of Rhode Island Knight Campus 400 East Avenue Warwick, Rhode Island 02866 Re: Mold Assessment Community College

More information

MICROBIO BIOAEROSOL SAMPLING

MICROBIO BIOAEROSOL SAMPLING MICROBIO BIOAEROSOL SAMPLING BIOAEROSOL BROCHURE MICROBIO BIOAEROSOL SAMPLERS Bioaerosols are airborne particles, solid or liquid. They can be large molecules or volatile compounds. They contain living

More information

AIR AND SURFACE SAMPLING MEASUREMENTS OF FUNGAL CONTAMINANTS IN INDOOR ENVIRONMENTS

AIR AND SURFACE SAMPLING MEASUREMENTS OF FUNGAL CONTAMINANTS IN INDOOR ENVIRONMENTS AIR AND SURFACE SAMPLING MEASUREMENTS OF FUNGAL CONTAMINANTS IN INDOOR ENVIRONMENTS P Cruz Perez, JL Henry, AK Klima-Comba and LD Stetzenbach Harry Reid Center for Environmental Studies, University of

More information

Re: Elizabeth Middle School at County Road 13 in Elizabeth, CO Limited Ambient Microflora Inspection & Sampling

Re: Elizabeth Middle School at County Road 13 in Elizabeth, CO Limited Ambient Microflora Inspection & Sampling November 19, 2012 Mr. Ron Patera Elizabeth School District 633 Dale Court Elizabeth, CO 80107 Re: Elizabeth Middle School at 34427 County Road 13 in Elizabeth, CO 80107 Limited Ambient Microflora Inspection

More information

MARTIN AND WILLIAMSON HALL BUILDINGs Eastern Washington University, Cheney, Washington INDOOR AIR QUALITY SAMPLING PLAN

MARTIN AND WILLIAMSON HALL BUILDINGs Eastern Washington University, Cheney, Washington INDOOR AIR QUALITY SAMPLING PLAN MARTIN AND WILLIAMSON HALL BUILDINGs Eastern Washington University, Cheney, Washington INDOOR AIR QUALITY SAMPLING PLAN Prepared for Eastern Washington University Facilities and Planning Department 101

More information

To help protect your privacy, PowerPoint has blocked automatic download of this picture. Long Term Care Building Conference NOVEMBER 29,2013

To help protect your privacy, PowerPoint has blocked automatic download of this picture. Long Term Care Building Conference NOVEMBER 29,2013 To help protect your privacy, PowerPoint has blocked automatic download of this picture. Long Term Care Building Conference NOVEMBER 29,2013 PRESENTERS Wanda Mitton - Technical Sales for 27 years - Sales

More information

INTRODUCTION: METHODOLOGY: November 4, Mr. Tom Heinz 353 West Sawgrass Dakota Dunes, SD 57049

INTRODUCTION: METHODOLOGY: November 4, Mr. Tom Heinz 353 West Sawgrass Dakota Dunes, SD 57049 November 4, 2011 Mr. Tom Heinz 353 West Sawgrass Dakota Dunes, SD 57049 Re: Project #: 4004-050 353 West Sawgrass, Dakota Dunes SD Microbial Clearance Testing INTRODUCTION: This report presents the findings

More information

Powers Environmental LLC

Powers Environmental LLC Powers Environmental LLC POST-REMEDIATION VERIFICATION CLEARANCE REPORT GENERAL INFORMATION Report Date: 09/06/2017 Assessment Date: 09/05/2017 Project Number: 2017222 Time: 7:00 AM Ground Condition: Dry

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Evaluation of Risk of Mold Damages Based on a Novel Dust Sampling Method

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Evaluation of Risk of Mold Damages Based on a Novel Dust Sampling Method Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0279 ISBN: 978-83-7947-232-1 Evaluation of Risk of Mold Damages Based on a Novel Dust Sampling Method Mari Sand Austigard 1, Ingeborg

More information

Prepared by: LBS HSE Approved by: Geoff Atkins Issue Date: New Policy

Prepared by: LBS HSE Approved by: Geoff Atkins Issue Date: New Policy The University of British Columbia Land and Building Services MOULD PROCEDURE Work Procedure I-B-46 Prepared by: LBS HSE Approved by: Geoff Atkins Issue Date: New Policy Replaces: 1.0 APPLICATION Moulds

More information

SPORE TRAP SAMPLING REPORT FOR CENTENNIAL LANE ELEMENTARY SCHOOL 3825 CENTENNIAL LANE ELLICOTT CITY, MARYLAND PREPARED FOR:

SPORE TRAP SAMPLING REPORT FOR CENTENNIAL LANE ELEMENTARY SCHOOL 3825 CENTENNIAL LANE ELLICOTT CITY, MARYLAND PREPARED FOR: SPORE TRAP SAMPLING REPORT FOR CENTENNIAL LANE ELEMENTARY SCHOOL 3825 CENTENNIAL LANE ELLICOTT CITY, MARYLAND 21042 PREPARED FOR: HOWARD COUNTY PUBLIC SCHOOL SYSTEM 10910 ROUTE 108 ELLICOTT CITY, MD 21043

More information

Table of Contents. C. Recommended Remediation Firms: upon request

Table of Contents. C. Recommended Remediation Firms: upon request Table of Contents I. Job, Contact & Site Information II. Scope of Work III. Building Overview IV. Findings V. Conclusions and Recommendations VI. Expectations VII. References VIII. Limits of Liability

More information

Re: Casey Middle School at 1301 High Street in Boulder, Colorado Follow-Up Indoor Air Quality Monitoring (Hydrogen Sulfide)

Re: Casey Middle School at 1301 High Street in Boulder, Colorado Follow-Up Indoor Air Quality Monitoring (Hydrogen Sulfide) April 16, 2014 Mike Cuskelly Boulder Valley School District 6500 Arapahoe, P.O. Box 9011 Boulder, CO 80301 Re: Casey Middle School at 1301 High Street in Boulder, Colorado 80304 Follow-Up Indoor Air Quality

More information

SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD PREPARED FOR:

SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD PREPARED FOR: SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD 21738 PREPARED FOR: HOWARD COUNTY PUBLIC SCHOOL SYSTEM 10910 ROUTE 108 ELLICOTT CITY, MD 21043 PREPARED BY: ARIA ENVIRONMENTAL,

More information

State of Kuwait Ministry of Health Infection Control Directorate. The role of infection control In design of health care facilities

State of Kuwait Ministry of Health Infection Control Directorate. The role of infection control In design of health care facilities State of Kuwait Ministry of Health Infection Control Directorate The role of infection control In design of health care facilities 2007 INTRODUCTION Hospital design should ensure that patients, especially

More information

Molecular Entrapment to Capture Airborne Mold Spores

Molecular Entrapment to Capture Airborne Mold Spores An Assured Bio Labs, LLC White Paper 228 Midway Ln, Suite B Oak Ridge,TN 37830 865.813.1700 www.assuredbio.com Molecular Entrapment to Capture Airborne Mold Spores By Edward A. Sobek, Ph.D. July 3, 2012

More information

FILED: NEW YORK COUNTY CLERK 07/14/ :42 PM INDEX NO /2016 NYSCEF DOC. NO. 25 RECEIVED NYSCEF: 07/14/2016

FILED: NEW YORK COUNTY CLERK 07/14/ :42 PM INDEX NO /2016 NYSCEF DOC. NO. 25 RECEIVED NYSCEF: 07/14/2016 FILED: NEW YORK COUNTY CLERK 07/14/2016 01:42 PM INDEX NO. 154125/2016 NYSCEF DOC. NO. 25 RECEIVED NYSCEF: 07/14/2016 Project: Post-Mold Remediation Verification Survey Location: 1045 Park Avenue Apt.

More information

SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD PREPARED FOR:

SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD PREPARED FOR: SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD 21738 PREPARED FOR: HOWARD COUNTY PUBLIC SCHOOL SYSTEM 10910 ROUTE 108 ELLICOTT CITY, MD 21043 PREPARED BY: ARIA ENVIRONMENTAL,

More information

Mold and Moisture Awareness

Mold and Moisture Awareness www.forensicanalytical.com Mold and Moisture Awareness Presented by: Michelle Rosales, MPH, CIH ASCIP Webinar March 15, 2017 10am 12pm PST AUDIO: To enable audio be sure you ve selected YES to the Integrated

More information

MOLD SCREENING REPORT

MOLD SCREENING REPORT MOLD SCREENING REPORT Mount Washington Middle School 269 Water Street Mt. Washington, KY 40047 Project # 115-7346 BCBOE PO#156081 Prepared for: Mr. Mark Mitchell Director, Buildings and Grounds Bullitt

More information

GAO Report Reports the Top Dozen Mold Health Problems

GAO Report Reports the Top Dozen Mold Health Problems GAO Report Reports the Top Dozen Mold Health Problems The September 30, 2008, U.S. Government Accounting Office (GAO) summary of the health effects caused by exposure to mold ("INDOOR MOLD," and subtitled,

More information

THE EFFECT OF INTENSIVE VACUUMING ON INDOOR PM MASS CONCENTRATION

THE EFFECT OF INTENSIVE VACUUMING ON INDOOR PM MASS CONCENTRATION THE EFFECT OF INTENSIVE VACUUMING ON INDOOR PM MASS CONCENTRATION K White 1 and P Dingle 1 School of Environmental Science, Murdoch University, Murdoch, WA, Australia ABSTRACT A study was conducted in

More information

Post Fire IAQ and Clean-up Issues

Post Fire IAQ and Clean-up Issues Po Post Fire IAQ and Clean-up Issues Emergency Line 1-866-530-4086 Introduction When a disaster such as the Fort McMurray fire strikes, part of the task of restoring a property to its former use or occupancy

More information

Infection Control Risk Assessment Matrix of Precautions for Construction & Renovation

Infection Control Risk Assessment Matrix of Precautions for Construction & Renovation Figure 3-6. Sample ICRA Matrix of Precautions Infection Control Risk Assessment Matrix of Precautions for Construction & Renovation Step 1: Using the following table, identify the Type of Construction

More information

The basic qualifications for mold investigators and remediation contractors should include:

The basic qualifications for mold investigators and remediation contractors should include: Technical Analysis Mold Inspections - What To Expect Mark Misner CIE, CMI, CMRC Introduction If you are in the market for a mold inspector, then you already have a pretty good idea that your home has a

More information

IAQ Walkthrough. Jordan Elementary. J o r d a n P u b l i c S c h o o l s IEA, INC. Contact Us: Inspection Date:

IAQ Walkthrough. Jordan Elementary. J o r d a n P u b l i c S c h o o l s IEA, INC. Contact Us: Inspection Date: IEA, INC. J o r d a n P u b l i c S c h o o l s 2016-2017 IAQ Walkthrough Contact Us: BROOKLYN PARK OFFICE 9201 W. BROADWAY, #600 BROOKLYN PARK, MN 55445 763-315-7900 Jordan Elementary MANKATO OFFICE 610

More information

RE: Remediation Plan regarding Contents of Hackman Apartments (N/S).

RE: Remediation Plan regarding Contents of Hackman Apartments (N/S). August 22, 2018 Greg Zelt Compleat Restorations Inc. 702 Pointview Ave. Ephrata, PA 17522 717-344-4151 gzelt@compleatrestorations.com RE: Remediation Plan regarding Contents of Hackman Apartments (N/S).

More information

SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD PREPARED FOR:

SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD PREPARED FOR: SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD 21738 PREPARED FOR: HOWARD COUNTY PUBLIC SCHOOL SYSTEM 10910 ROUTE 108 ELLICOTT CITY, MD 21043 PREPARED BY: ARIA ENVIRONMENTAL,

More information

Indoor Air Quality Duty Of Care. Guidelines For A Healthier Workplace

Indoor Air Quality Duty Of Care. Guidelines For A Healthier Workplace Indoor Air Quality Duty Of Care Guidelines For A Healthier Workplace Contents Your Right To Healthy Air Duty Of Care A Cocktail For Illness Legionella An Acute Manifestation Of Poor Maintenance Prevention

More information

360-INDOOR AIR QUALITY PROGRAM

360-INDOOR AIR QUALITY PROGRAM 360.1 PURPOSE A. To help ensure employees and students at Central New Mexico Community College (CNM) are provided a workplace free of recognized indoor air quality hazards. 360.2 SCOPE A. CNM recognizes

More information

INFECTION CONTROL ISSUES IN CONSTRUCTION AND RENOVATION

INFECTION CONTROL ISSUES IN CONSTRUCTION AND RENOVATION INFECTION CONTROL ISSUES IN CONSTRUCTION AND RENOVATION Evelyn Cook SPICE.unc.edu 919 966 1304 I want to begin with the premise that patients can leave the hospital sicker than they arrived if construction

More information

All questions regarding the attached study should be directed to the Howard County Government s public information office at

All questions regarding the attached study should be directed to the Howard County Government s public information office at All questions regarding the attached study should be directed to the Howard County Government s public information office at 410-313-2022. 449 Eisenhower Boulevard, Suite 300 Harrisburg, PA 17111-2302

More information

Sampling for Mould in Red Bluff Elementary School, Quesnel

Sampling for Mould in Red Bluff Elementary School, Quesnel Sampling for Mould in Red Bluff Elementary School, Quesnel Introduction What are moulds? Moulds are part of the fungi kingdom and serve an important role in breaking down organic matter. They are found

More information

STEP UP TO THE ENERGY STAR INDOOR AIR PACKAGE. A new opportunity for leading builders to create better environments inside and out

STEP UP TO THE ENERGY STAR INDOOR AIR PACKAGE. A new opportunity for leading builders to create better environments inside and out STEP UP TO THE ENERGY STAR INDOOR AIR PACKAGE A new opportunity for leading builders to create better environments inside and out WHY DOES INDOOR AIR QUALITY MATTER? People are increasingly concerned about

More information

CHAPTER 30 INDOOR AIR QUALITY MANAGEMENT

CHAPTER 30 INDOOR AIR QUALITY MANAGEMENT CHAPTER 30 INDOOR AIR QUALITY MANAGEMENT 3001. Discussion a. Poor indoor air quality (IAQ) detracts from the quality of the work environment. Problems such as uncomfortable air temperature and humidity

More information

Protecting the HVAC System During Construction: An Industry Standard of Care for Contractors

Protecting the HVAC System During Construction: An Industry Standard of Care for Contractors Protecting the HVAC System During Construction: An Industry Standard of Care for Contractors Vernard D. Holden, CIH, CSP, ARM Hydro-Environmental Technologies, Inc., Acton, Massachusetts, USA Corresponding

More information

UNDER SECRETARY FOR HEALTH S INFORMATION LETTER MICROBIOLOGICAL ASSESSMENT OF PHARMACEUTICAL CLEANROOMS

UNDER SECRETARY FOR HEALTH S INFORMATION LETTER MICROBIOLOGICAL ASSESSMENT OF PHARMACEUTICAL CLEANROOMS DEPARTMENT OF VETERANS AFFAIRS Veterans Health Administration Washington DC 20420 IL 10-2006-008 In Reply Refer To: 10NB UNDER SECRETARY FOR HEALTH S INFORMATION LETTER MICROBIOLOGICAL ASSESSMENT OF PHARMACEUTICAL

More information

Guelph, Guelph, Ontario, Canada. N1G 2W1.

Guelph, Guelph, Ontario, Canada. N1G 2W1. ABSTRACT THE BIOFILTRATION OF INDOOR AIR II: MICROBIAL LOADING OF THE INDOOR SPACE. Jeff Mallany 1, Alan Darlington and Michael Dixon Two ecologically complex indoor air biofilters were tested for their

More information

PAPER TEMPLATE FOR THE 34 TH AIVC-3 RD TIGHTVENT-2 ND COOL ROOFS - 1 ST VENTICOOL CONFERENCE, 2013

PAPER TEMPLATE FOR THE 34 TH AIVC-3 RD TIGHTVENT-2 ND COOL ROOFS - 1 ST VENTICOOL CONFERENCE, 2013 PAPER TEMPLATE FOR THE 34 TH AIVC-3 RD TIGHTVENT-2 ND COOL ROOFS - 1 ST VENTICOOL CONFERENCE, 2013 Sanitary aspects of domestic ventilation systems: an in situ study Joris Van Herreweghe*, Samuel Caillou,

More information

Rowan University Department of Environmental Health and Safety. A Brief Overview for Building Maintenance

Rowan University Department of Environmental Health and Safety. A Brief Overview for Building Maintenance Rowan University Department of Environmental Health and Safety A Brief Overview for Building Maintenance Mold Overview Wide variety of molds may be present in building materials Common ones include: Alternaria

More information

INSTALLATION INSTRUCTIONS FOR WICANDERS DEKWALL

INSTALLATION INSTRUCTIONS FOR WICANDERS DEKWALL INSTALLATION INSTRUCTIONS FOR WICANDERS DEKWALL GENERAL INFORMATION Wicanders Dekwall coverings are intended for indoor use only. Please, read the following instructions before installation. Store tiles

More information

ASBESTOS SCIENCE TECHNOLOGIES, INC.

ASBESTOS SCIENCE TECHNOLOGIES, INC. ASBESTOS SCIENCE TECHNOLOGIES, INC. P.O. Box 505 Bangor, CA 95914 Phone (530) 518-0934 Email - astinc17@yahoo.com Report for Hoopa Valley Elementary School 11500 State Highway 96 Hoopa, Ca. 95546 Mold

More information

Environmental Pollution and Animal Health. Dr Abdul-Hadi Abbass Abd

Environmental Pollution and Animal Health. Dr Abdul-Hadi Abbass Abd Environmental Pollution and Animal Health Dr Abdul-Hadi Abbass Abd Viable micro-organisms found in a very wide range of habitats: The coldest of seawater ponds in the frozen wastes of polar regions. The

More information

Indoor Air Quality Assessment Morell Consolidated School Morell, PEI

Indoor Air Quality Assessment Morell Consolidated School Morell, PEI Project No. 14602 Indoor Air Quality Assessment Morell Consolidated School Morell, PEI Prepared for: PEI Dept. Transportation & Infrastructure Renewal P.O. Box 2000 Charlottetown, PE C1A 7N7 Attention:

More information

Good (4 points each) > mg/m Bq m Bq m Bq m -3 < ,000 1,000-10,000 10, ,000

Good (4 points each) > mg/m Bq m Bq m Bq m -3 < ,000 1,000-10,000 10, ,000 Rating (5 points each) (4 points each) (3 points each) (2 points each) (1 point each) Temperature ( C) 18-21 C Plus or minus 1 C (including Plus or minus 2 C (including Plus or minus 3 C (including Plus

More information

Technical Analysis. Mold Remediation Proposal Evaluation. Introduction. Where To Begin?

Technical Analysis. Mold Remediation Proposal Evaluation. Introduction. Where To Begin? Technical Analysis Mold Remediation Proposal Evaluation Mark Misner CIE, CMI, CMRC Introduction Unlike many professional trades, the mold remediation industry is largely unregulated. There is no national

More information

SANITATION SURVEY OF CITRUS PACKINGSHEDS

SANITATION SURVEY OF CITRUS PACKINGSHEDS SANITATION SURVEY OF CITRUS PACKINGSHEDS Florida Citrus Packingline,, 2000. (incorporating fungicide resistance survey results) Peter Taverner, Nancy Cunningham and Karolina Steciuk June 2012 SOUTH AUSTRALIAN

More information

Post Remediation Testing Site Evaluation with Environmental Sampling

Post Remediation Testing Site Evaluation with Environmental Sampling Nationwide Locations Locally Served Corporate Headquarters: 7700 Congress Avenue Suite 1119 Boca Raton, FL 33487 Industrial Hygiene IAQ/Mold Assessments Water Loss Projects Restoration Project Mgmt Post

More information

Post Remediation Testing Site Evaluation with Environmental Sampling

Post Remediation Testing Site Evaluation with Environmental Sampling Nationwide Locations Locally Served Corporate Headquarters: 7700 Congress Avenue Suite 1119 Boca Raton, FL 33487 Industrial Hygiene IAQ/Mold Assessments Water Loss Projects Restoration Project Mgmt Post

More information

Auditor Checklist. Age: Height: (ft) (inches)

Auditor Checklist. Age: Height: (ft) (inches) Assignment Overview: You will visit your assigned Kmart location to evaluate exterior and interior facility features, focusing on cleanliness, condition, and access for disabled customers. You will also

More information

One World LED Reseller Installation Guide

One World LED Reseller Installation Guide One World LED Reseller Installation Guide Double Pole Support Installation Demonstration This Double Pole support solution is suitable for front serviceable screens. These are used when rear access is

More information

Indoor Air Quality Assessments during Renovations at Waverly Elementary School Project #J (January 4, 12, 15, 25 and 29, 2018)

Indoor Air Quality Assessments during Renovations at Waverly Elementary School Project #J (January 4, 12, 15, 25 and 29, 2018) March 29, 2018 Mr. Jeff Klenk Howard County Public School System (HCPSS) 10910 Route 108 Ellicott City, MD 21043 RE: Indoor Air Quality Assessments during Renovations at Waverly Elementary School Project

More information

INDOOR AIR QUALITY. Ir Al-Khairi Mohd Daud. Pakar Keselamatan dan Persekitaran

INDOOR AIR QUALITY. Ir Al-Khairi Mohd Daud. Pakar Keselamatan dan Persekitaran INDOOR AIR QUALITY Ir Al-Khairi Mohd Daud Pakar Keselamatan dan Persekitaran SCOPE Background Definition of IAQ Related factor contribute to IAQ Indoor environmental quality Importance of IAQ for working

More information

INDOOR AIR QUALITY TESTING AT CARLISLE COUNTY ELEMENTARY SCHOOL

INDOOR AIR QUALITY TESTING AT CARLISLE COUNTY ELEMENTARY SCHOOL INDOOR AIR QUALITY TESTING AT CARLISLE COUNTY ELEMENTARY SCHOOL For: Keith Shoulders Carlisle County Schools 4557 State Route 1377 Bardwell, Kentucky 42023 Testing Performed By: Christopher K. Adkins Air

More information

Measuring Indoor Air Quality presented to AAFAME Members Nov. 14, 2017

Measuring Indoor Air Quality presented to AAFAME Members Nov. 14, 2017 Measuring Indoor Air Quality presented to AAFAME Members Nov. 14, 2017 What is Indoor Air Quality? Appropriate IAQ can be defined as a function of three different components: 1) appropriate thermal comfort,

More information

INDOOR AIR QUALITY CALUMET COUNTY HIGHWAY FACILITY -CARBON MONOXIDE- 206 COURT ST CHILTON, WI

INDOOR AIR QUALITY CALUMET COUNTY HIGHWAY FACILITY -CARBON MONOXIDE- 206 COURT ST CHILTON, WI INDOOR AIR QUALITY CALUMET COUNTY HIGHWAY FACILITY -CARBON MONOXIDE- 206 COURT ST CHILTON, WI SAMPLING DATE: MARCH 14, 2011 REPORT DATE: APRIL 4, 2011 EMC PROJECT NUMBER: 110213-01 PREPARED FOR: MR. JAY

More information

THE FLEXIBLE INSULATION SYSTEM TO PREVENT CONDENSATION AND ENERGY LOSSES

THE FLEXIBLE INSULATION SYSTEM TO PREVENT CONDENSATION AND ENERGY LOSSES THE FLEXIBLE INSULATION SYSTEM TO PREVENT CONDENSATION AND ENERGY LOSSES Reliable condensation control with closed-cell Armaflex structure High flexibility and ease of installation. Increases equipment

More information

Example graphs. Features: System data Component data Hierarchies Hierarchy data links Comment (about function) Status

Example graphs. Features: System data Component data Hierarchies Hierarchy data links Comment (about function) Status Example graphs Features: System data Component data Hierarchies Hierarchy data links Comment (about function) Status 5/10/2011 Features; Implication(s)? 1 Example graphs No difference between measured

More information

ASBESTOS SCIENCE TECHNOLOGIES, INC.

ASBESTOS SCIENCE TECHNOLOGIES, INC. ASBESTOS SCIENCE TECHNOLOGIES, INC. P.O. Box 505 Bangor, CA 95914 Phone (530) 518-0934 Email - astinc17@yahoo.com Report for Trinity Valley Elem. School Willow Creek, Ca. Mold Report - Rooms 12 through

More information

Indoor Air Quality Assessment Report

Indoor Air Quality Assessment Report Indoor Air Quality Assessment Report For M&W Business Centre At Unit B, 19/F, Kyoto Plaza, 491-499 Lockhart Road, Causeway Bay, Hong Kong Tel: 3896 0399 Attn: Melody Ko Tested and prepared by: Carman Lam

More information

Comparison of Two Methods Used By Industrial Hygienists to Evaluate Mold Health Effects In Buildings

Comparison of Two Methods Used By Industrial Hygienists to Evaluate Mold Health Effects In Buildings Comparison of Two Methods Used By Industrial Hygienists to Evaluate Mold Health Effects In Buildings September 21, 2016 Wendell Rahorst, CIH, Wendell Rahorst Inc. & Michael J. Richen, CIH, Boulder County

More information