1 A FEASIBILITY STUDY ON SPACE COOLING WITH OUTDOOR AIR USING A DYNAMIC ENERGY SIMULATION PROGRAM PART 1: PARAMETRIC STUDY ON FEASIBILITY OF SPACE COOLING WITH OUTDOOR AIR ON SEVERAL WEATHER CONDITIONS Shin-ichi Matsumoto 1, Motonori Futamura 2, Hiroshi Kobayashi 3, Kahori Genjo 1, Yasuo Utsumi 3, and Ken-ichi Hasegawa 1 1 Department of Architecture & Environment System, Akita Prefectural University, Yurihonjo, Japan 2 Yamatake Corporation, Fujisawa, Japan 3 Department of Architecture, Miyagi National College of Technology, Natori, Japan ABSTRACT As a part of our research on energy conservation and thermal comfort of detached houses having centralized HVAC systems, study with numerical simulation techniques was started. The model is the house that has mechanical supply and exhaust ventilation systems with a centralized air duct equipped with a sensible heat exchanger and has large return air (4 times an hour). The parameters in the simulation are the set point temperature and outdoor air flow rate. The authors have already showed energy calculation results for Tokyo, and it has been discussed that the utilization of fresh outdoor air as a cooling source during the intermediate season save a few percent of the annual heating/cooling loads (Matsumoto et al. 23). However, whether this finding is sure except for Tokyo is not clear. This paper discusses the generality of this finding by showing the results of the similar energy calculations using several weather data differing from that of Tokyo. As a result, it would be rash to conclude that the effect of space cooling with outdoor air is small without considering of building conditions, for example, in case of the building with high heat storage performance, large solar heat gain and large internal heat load during intermediate season. KEYWORDS Parametric study, Space cooling with outdoor air, Simulation, Centralized HVAC system, Weather conditions INTRODUCTION The authors have examined the energy saving application method of the centralized HVAC system with a centralized air duct for the detached houses with the numerical simulation. Outline of the simulation program and the results of the feasibility study on the outdoor air cooling with the weather data of Tokyo have already been reported. According to the results, the effect of the outdoor air cooling during intermediate season was found to reduce the annual thermal load by only 2 or 3 %, and found to be small compared to the energy saving effect by control of the setting temperature level for each season. However, it would be rash to conclude that the effect of the outdoor air cooling is small. The reasons of this are as follows: 1) we have just examined the weather data of Tokyo, and we have not examined the possibility that the quantitative effect will differ by weather condition of each city. 2) it is considered that the effect of outdoor air cooling will be relatively larger depending on the building conditions with different thermal performance, internal heat load and solar shading. Then, this paper discusses and confirms the generality of this finding by showing the results of the similar energy calculations using several weather data differing from that of Tokyo. Corresponding Author: Tel: , Fax: address: matsu@akita-pu.ac.jp
2 ANALYSIS OF OUTDOOR AIR COOLING HOUR POTENTIAL BASED ON WEATHER DATA Method of the analysis The outdoor air cooling hour potential is defined as shown in the Figure 1. Average value for each point is calculated from the data over 15 years with the expanded AMeDAS weather data (Akasaka et al. 23), and the distribution for the each average value is examined. Results and discussions The average of outdoor air cooling potential was 35.% and ranged from 23.3% to 53.1%. Figure 1 shows the results of the analysis as the map. Generally, the outdoor air cooling potential was found to be large around the coast and small around the inland, in addition, it was found to be large at the point located over low latitude. In this study, based on the climatic zones of the Japanese residential standard, Sendai and Nagano were selected from Zone III, Nagoya, Osaka, Fukuoka were selected from Zone IV in addition to Tokyo. This index suggests that the energy saving effect of outdoor air cooling for each city is smaller than that for Tokyo. SIMULATION OF ANNUAL HEAT LOAD ON SEVERAL WEATHER CONDITIONS Purpose of the simulation The main purpose of the simulation is to clarify the energy saving effect of outdoor air cooling during the intermediate season under various weather conditions. The energy saving effect of the setting temperature level that differs with each season as well as the weather conditions is investigated. The simulation results of annual heat load, cooling load during intermediate season are mainly compared. Methods and conditions of simulation The shape and wall structure of the model are almost same as the wooden detached house model of AIJ standard problem (Udagawa 15). The heat insulation of wall, floor and ceiling and the kind and the thickness of window are set as Table 1 according to the weather conditions because of assumption of thermal performance as to the purpose of the simulation. Airtightness performance is constant in this simulation, and the simulation is conducted for the model with the distribution of the cracks that are 55 Outdoor air cooling hour potential 5 outdoor air cooling possible hours 45 (annual hours complete with conditions 1)-3)) = annual hours (87h) 4 1)14 <daily average temperature< ) <hourly average temperature<26 3 3)hourly average humidity ratio<12g/kg' 25 2 (%) Fukuoka (42.5%) Nagano (34.3%) Nagoya (38.6%) Osaka (41.9%) Sendai (38.%) Tokyo (43.7%) Figure 1. Distribution of the outdoor air cooling hour potential and the calculation point
3 Table 1 Setting of the building model for each weather condition Weather conditions Heat insulation level Details of window Heat loss (Climatic zone) Ceiling Wall & Floor coefficient Sendai (Zone III) Low-E double glazing Nagano (Zone III) (G3-A6-G3) 1.82 W/m 2 K Glass wool Glass wool K=3.49, τ=.44*, a=.14 Tokyo (Zone IV) K 16K Aluminum double glazing Nagoya (Zone IV) 2 mm mm (G3-A6-G3) Osaka (Zone IV) K=4.65, τ=.49*, a= W/m 2 K Fukuoka (Zone IV) K: heat transfer coefficient (W/m 2 K), τ: solar transmittance (-), a: solar absorptance (-) Equivalent leakage area 2 cm 2 /m 2 Table 2 Calculation conditions excepting weather conditions Parameters Level Winter Intermediate season Summer Setting temperature level Energy saving Normal Rich Outdoor air cooling Off (outdoor airflow rate) On - 2 ach at space cooling with outdoor air - displaced with the point openings. The living schedule is identical to the one of the standard problem. The weather conditions of six points shown in Figure 1 are used. The calculation conditions excepting weather conditions are displayed in Table 2. Winter and summer are defined as the days that the daily averaged temperature is under 14 and over 26, respectively. Intermediate season is defined as the days except for winter and summer. The outdoor air cooling mode is operated during intermediate season when the conditions 2) and 3) given in Figure 1 are complete. In this paper, the heat load means the building load. The simulation program and the setting of the air conditioning system model are same as the previous paper. RESULTS OF THE SIMULATION The effect of the setting temperature level on the annual heat load Figure 2 shows the results of the annual heat loads. The annual heat loads were found to vary widely with the setting temperature level. The annual heat loads for rich and energy saving ranged -134% and 72-77% of those for normal, respectively. These ratios vary small, unexpectedly. The effect of outdoor air cooling operation on the annual heat load By comparison of the simulation results of the same weather condition and setting temperature level in the case on with those in the case off, the outdoor air cooling operation was found to reduce the annual heat load by only 1-3 % and the energy saving effect was smaller than the setting temperature level. This finding was in accordance with the simulation result of Tokyo in the previous paper, the same tendency was seen for the other five points except for Tokyo. The saving effect of the annual heat load is expected to be the smallest in Nagano of the six points from Figure 1. In this point, Figure 2 presented the results as expected, but the difference with each point was small. Simulation under the extreme weather conditions was not conducted this time, therefore the saving effect of the annual heat load by the outdoor air cooling method can be said to be several percentage, and it can not be widely different by the weather conditions. However, it is needed to confirm the saving effect under the different building conditions such as thermal performance, internal heat load and solar shading.
4 % Cooling (GJ/yr) Off On Off On Off On Off On Off On Off On Outdoor air cooling Sendai Nagano Tokyo Nagoya Osaka Fukuoka Weather condition (4.6) (47.2) (38.4) (44.3) (41.1) (42.2) the value within round bracket: annual thermal load in case of normal SP and outdoor air cooling off (GJ/yr) the value at the side of a bar: relative value in case of a value within round bracket as Heating Annual thermal load Rich Normal Energy saving Setting temperature level Figure 2. Comparison among annual heat loads GJ GJ GJ GJ (GJ/yr) % GJ 9.1 Off On Off On Off On Off On Off On Off On Sendai Nagano Tokyo Nagoya Osaka Fukuoka the value at the top of a bar: cooling load during intermediate season in case of outdoor air cooling off (GJ/yr) the value at the side of a bar: relative value in case of outdoor air cooling on against that in case of outdoor air cooling off as.1.2gj Rich Normal Energy saving Cooling loads during intermediate season Setting temperature level Outdoor air cooling Weather condition Figure 3. Comparison of the cooling loads during intermediate season The effect of outdoor air cooling operation on the cooling load during intermediate season Figure 3 presents the comparison of the cooling loads during intermediate season. From Figure 3, the energy saving effect of outdoor air cooling method on the cooling loads during intermediate season was clearly found to be 7-11% in the setting temperature level of rich and normal, and -16% in that of energy saving, respectively. Therefore, another way of saying this would be that the definite energy saving effect of the outdoor air cooling method shown in Figure 3 is behind with the large heat and cooling loads of summer and winter when the annual heat load is used as the index of the comparison. It can be said that the outdoor air cooling is the effective method in the following cases: the case that the solar heat gain during intermediate season is more than that of summer due to the relation between shapes of the eaves and solar altitude in the building with high heat storage performance, or the case that the space cooling is the main air-conditioning operation for the removal of relatively large internal heat load during intermediate season.
5 The effect of outdoor air cooling operation on the outdoor air cooling hours The percentage of the operation hours when outdoor air cooling is conducted to the annual 87 h was calculated as the outdoor air cooling hour rate in the case of the setting temperature level normal, and then it was plotted with outdoor air cooling hour potential mentioned above as the horizontal axes, illustrated in Figure 4. There was found to be positive linear correlation between the outdoor air cooling hour potential and the outdoor air cooling hour rate, and the outdoor air cooling hour rate was expected to be -17% (-14 h: about two months) if the extrapolation of the regression line permits. The ratio within round bracket in Figure 4 means that how long the cooling hours during intermediate season in case of outdoor air cooling off are reduced. As seen in Figure 4, the cooling hours were able to reduce by 4% in Tokyo, Osaka and Fukuoka, and % in Sendai and Nagano. The effect of outdoor air cooling operation on the peak cooling load during intermediate season Figure 5 presents the examples of the cumulative relative frequency distribution for the cooling load in Nagano and Tokyo. The outdoor air cooling is set to be operated during intermediate season, therefore the hourly cooling load in summer (cooling season) is not effected by its operation as seen in Figure 5. It was found that the cooling load during intermediate season differ by the outdoor air cooling operation on or off and the outdoor air cooling operation have the effect to reduce hourly cooling load. However, the saving effect of the hourly cooling load was found to be large only when it is small and there would be not so much difference near the peaks of it. On the other hand, the saving effect of the outdoor air cooling on the cooling load was about 3 % in both Nagano and Tokyo in terms of the cooling load of excessive hazard rate 2.5 %. This is probably because that outdoor air available for space cooling is generated mainly at night. Validity to this supposition was able to be confirmed in Outdoor air cooling possible hours (h) the value within round bracket: the ratio of the cooling hours in case of outdoor air cooling on to the cooling hours during Fukuoka (39.7%) intermediate season in case of Osaka outdoor air cooling off (36.7%) Nagoya Tokyo (45.4%) (39.8%) y =.52 x (R 2 =.897) Nagano (58.2%) Sendai (57.2%) Outdoor air cooling hour potential, x (%) Figure 4. Relationship between the weather condition and the outdoor air cooling hours Outdoor air cooling hour rate, y (%) Outdoor air cooling hours (h) Cumulative relative frequency (%) 5 (a) Nagano (Normal setting temperature level) Intermediate season broken line: outdoor air cooling off Summer (Cooling season) outdoor air cooling on : kW outdoor air cooling off :5.273kW Summer(Cooling season): 5.919kW the line for excessive hazard rate 2.5% (b) Tokyo (Normal setting temperature level ) Intermediate season broken line: outdoor air cooling off Summer (Cooling season) 5 5 Hourly cooling load (kw) Hourly cooling load (kw) Figure 5. Examples of the cumulative relative frequency distribution for the cooling load outdoor air cooling on : 4.963kW outdoor air cooling o ff :5.137kW Summer(Cooling season): 5.1kW
6 Cumulative frequency(%) Hourly heat load (kw) 8 7 (a) Tokyo, Normal setting temperature level, outdoor air cooling off. 7.5 Cumulative frequency(%) Hourly heat load (kw) (b) Tokyo, Normal setting temperature level, outdoor air cooling on Hour (h) Hour(h) Figure 6. Examples of the cumulative relative frequency distribution over % for the cooling load per hour during intermediate season Figure 6, that is to say, the main difference of Figure 6(a) and Figure 6(b) was the wideness of the bottom of a ravine seen after 19: and it was narrow in the case of the outdoor air cooling on. CONCLUSIONS This paper has investigated the energy saving effect of the outdoor air cooling method as the energy saving method of the centralized HVAC system for the detached houses with numerical simulation as changing of the parameters such as the weather conditions. The conclusions are as followed. 1) Building thermal load show a dynamic change with the setting temperature level. 2) The space cooling with outdoor air saves only three percent of the annual air-conditioning loads, similarly the peak air-conditioning loads during intermediate season. 3) It is difficult to consider that the above-mentioned two findings occur an exception because of different weather conditions. 4) The space cooling loads during intermediate season are decreased largely using space cooling with outdoor air. 5) It would be rash to conclude that the effect of space cooling with outdoor air is small without any considering of building conditions, for example, in case of the building with high heat storage performance, large solar heat gain and large internal heat load during intermediate season. Systematic parametric study based on the above finding 5) would be developed in the future. REFERENCES 1. S. Matsumoto et al. (23) Analysis of Air-Conditioning Loads for Detached Houses with Centralized HVAC Systems Using d Dynamic Simulation Program TASP++ Part1: Description of the Program and a Feasibility Study on Space Cooling by Fresh Air, Technical Papers pf Annual Meeting The Society of Heating, Air-Conditioning and Sanitary Engineers of Japan, Vol. I, (in Japanese). 2. H. Akasaka et al. (23) Expanded AMEDAS Weather Data, published by Maruzen. 3. M. Udagawa (15) The proposal of standard problem-residential standard problem, The 15th thermal symposium, Architectural Institute of Japan, (in Japanese).
performance. In order to make clear the effects of thermal performance and lifestyle on thermal environment and energy consumption for well-insulated
Effect of Thermal Performance and Lifestyle on the Thermal Environment and Energy Consumption for a Well-insulated and Airtight Detached House in a Warm Climatic Area K. Genjo 1,* and H. Matsumoto 2 1
More informationPassive cooling effect of building features in traditional Japanese buildings
International Conference Passive and Low Energy Cooling 573 for the Built Environment, May 5, Santorini, Greece Passive cooling effect of building features in traditional Japanese buildings H. Yoshino
More informationComparison of the Effects of Various Countermeasures on Energy Consumption in a Residential Building
Comparison of the Effects of Various Countermeasures on Energy Consumption in a Residential Building TAKAHIRO UEMOTO 1, DAISUKE NARUMI 1, YOSHIYUKI SHIMODA 1 1 Division of Sustainable Energy and Environmental
More information362: Indoor climate control effect of AAC panels as determined by house model measurements and simulations
PLEA 8 th Conference on Passive and Low Energy Architecture, Dublin, 22 nd to 24 th October 8 362: Indoor climate control effect of AAC panels as determined by house model measurements and simulations
More informationENERGY SAVING EFFECT BY CENTRAL VENTILATION WITH TOTAL HEAT RECOVERY INSTALLED IN A DETACHED HOUSE
ENERGY VING EFFECT BY CENTRAL VENTILATION WITH TOTAL HT RECOVERY INSTALLED IN A DETACHED HOUSE Yoshihiro Toriumi 1, Takashi Kurabuchi, Hiroyasu Okuyama 3, and Hiroshi Nanaoka 4 1 Department of Architectural
More informationThermal Performance of Solar Heating System with Water Floor
Plea24 - The 21 st Conference on Passive and Low Architecture. Eindhoven, The Netherlands, 19-22 September 24 Page 1 of 6 Thermal Performance of Heating System with Water Floor Part 3. Verification of
More informationComparative Study On Simulation Tools Of Annual Heat Load For Energy Management Y. Takahashi 1 *, G. Yoon 1, M. Yoshinaga 2, and R. Chiba 3 1 Graduate
Comparative Study On Simulation Tools Of Annual Heat Load For Energy Management Y. Takahashi 1 *, G. Yoon 1, M. Yoshinaga 2, and R. Chiba 3 1 Graduate School of Design and Architecture, Nagoya City University,
More informationESTIMATION OF ENERGY CONSUMPTION FOR AIR-CONDITIONING OF RESIDENCES
ESTIMATION OF ENERGY CONSUMPTION FOR AIR-CONDITIONING OF RESIDENCES Qingyuan Zhang, Kenji Asano and Hajime Imai Tsukuba College of Technology 4-3-15 Amakubo, Tsukuba, Japan Tetsuo Hayashi Kyushu University
More informationCOMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES
COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES Lusi Susanti 1, Hiroshi Matsumoto 2, and Hiroshi Homma 2 1 Department of
More informationTomohiko Ihara *, Yutaka Genchi National Institute of Advanced Industrial Science and Technology, Tsukuba, Ibaraki, Japan
4.4 EFFECT ON CO 2 EMISSIONS OF BUILDING-URBAN AREA BY INTRODUCING SOLAR REFLECTIVE PAINT Tomohiko Ihara *, Yutaka Genchi National Institute of Advanced Industrial Science and Technology, Tsukuba, Ibaraki,
More informationSTUDY ON OPTIMAL ENERGY SYSTEM DESIGN FOR APARTMENT HOUSE USING GENETIC ALGORITHMS. 375 Seosuk-dong, Dong-gu, Gwangju Korea METHODS
Eleventh International IBPSA Conference Glasgow, Scotland July 7-3, 9 STUDY OPTIMAL ENERGY SYSTEM DESIGN FOR APARTMENT HOUSE USING GENETIC ALGORITHMS Janghoo Seo *, Ryozo Ooka, and Genku Kayo 3 College
More informationChapter 6. Space heating load
Chapter 6 Space heating load 1 Outdoor Design Conditions Heating systems should provide just enough heat to match the heat loss from the structure. Local knowledge should be obtained for design conditions.
More informationRadiative heat transfer simulation between outdoor and indoor. spaces for predicting the performance of a direct heat gain system
Radiative heat transfer simulation between outdoor and indoor spaces for predicting the performance of a direct heat gain system H. Kawai 1, T. Asawa 1 and A. Hoyano 2 1 Department of Environmental Science
More informationRadiant Barriers Why Contractors and Homeowners Need to Understand this Option for Heat Load Reduction
Radiant Barriers Why Contractors and Homeowners Need to Understand this Option for Heat Load Reduction Mario A. Medina, Ph.D., P.E. Civil, Environmental &Architectural Engineering The University of Kansas
More informationADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING
ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING M. Kragh, M. Colombari and M. Zobec Permasteelisa Group, Research & Engineering, 31020 San Vendemiano (TV), Italy www.permasteelisa.com,
More informationReducing energy demand in non-domestic buildings: integrating smart facades, ventilation, and surface heating and cooling
Reducing energy demand in non-domestic buildings: integrating smart facades, ventilation, and surface heating and cooling Phil Jones, Shan Shan Hou and XiaoJun Li Welsh School of Architecture, Cardiff
More informationTHERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE
S447 THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE by Bojan V. ANDJELKOVIĆ *,a, Branislav V. STOJANOVIĆ b, Mladen M. STOJILJKOVIĆ b, Jelena N. JANEVSKI
More informationPrediction of Energy Efficiency and Thermal Environment of Residential Buildings Utilizing PEFC-CGS Combined Floor Heating System
Proceedings: Building Simulation 7 Prediction of Energy Efficiency and Thermal Environment of Residential Buildings Utilizing PEFC-CGS Combined Floor Heating System Nobuyasu Ayagaki, Akihito Ozaki, Hiroto
More informationCHAPTER 3. BUILDING THERMAL LOAD ESTIMATION
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating
More informationHourly Analysis Program v.4.1 Page 1 of 1
Air System Design Load Summary for Zona 6 DESIGN COOLING DESIGN HEATING COOLING DATA AT Feb 1600 HEATING DATA AT DES HTG COOLING OA DB / WB 34.5 C / 23.7 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent
More informationTHERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE
Andjelković, V., B.et. al.: Thermal Mass Impact on Energy Performance of A Low, Medium and Heavy S507 THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE by Bojan
More informationENERGY SAVING OF AIR-CONDITIONING IN MASS MERCHANDISERS BY OPERATIONAL CHANGE OF AIR-CONDITIONING SYSTEM
Numbers of Abstract/Session (given by NOC) - 1 - ENERGY SAVING OF AIR-CONDITIONING IN MASS MERCHANDISERS BY OPERATIONAL CHANGE OF AIR-CONDITIONING SYSTEM Masafumi Hirota, Professor, Department of Mechanical
More informationAREN 3050 ENVIRONMENTAL SYSTEMS FOR BUILDINGS I FALL 2005
1. Psychrometrics a) Moist air has a dry bulb temperature of 80 F and a wet bulb temperature of 67 F? What is the enthalpy at sea level? What is the enthalpy at 5000 ft above sea level? b) A building zone
More informationHourly Analysis Program v.4.1 Page 1 of 1
Air System Design Load Summary for Zona 9 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 1400 HEATING DATA AT DES HTG COOLING OA DB / WB 34.5 C / 23.7 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent
More informationInfluence of wall composition on thermal environment of wooden houses
J Wood Sci (2014) 60:117 126 DOI 10.1007/s10086-013-1383-x ORIGINAL ARTICLE Influence of wall composition on thermal environment of wooden houses Takashi Nakaya Mariko Yamasaki Yasutoshi Sasaki Received:
More informationSUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION ENHANCEMENT
13th Conference of International Building Simulation Association, Chambéry, France, August 26-28 SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION
More informationHourly Analysis Program v.4.1 Page 1 of 1
Air System Design Load Summary for Zona 3 Project Name: Av. Cabildo 3067, 4 piso 02/13/2011 DESIGN COOLING DESIGN HEATING COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 34.9 C / 23.8
More informationHourly Analysis Program v.4.1 Page 1 of 1
Air System Design Load Summary for Zona 8 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent
More informationSURVEY ON INDOOR AIR QUALITY IN CONTEMPORARY RESIDENTIAL BUILDINGS IN JAPAN
SURVEY ON INDOOR AIR QUALITY IN CONTEMPORARY RESIDENTIAL BUILDINGS IN JAPAN Teruaki Mitamura 1, Haruki Osawa 2, Yasuo Kuwasawa 2, and Hisashi Miura 2 1 Department of Architecture, Ashikaga Institute of
More informationHourly Analysis Program v.4.1 Page 1 of 1
Air System Design Load Summary for Zona 11 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible
More informationCOMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING
COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING ABSTRACT F. Bagheri 1, M. Fakoor 1, B. Young 1, C. Cranswick 1 1 BC Building Science Ltd. 611 Bent
More informationENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE
Bulletin of the Transilvania University of Braşov Vol. 3 (52) - 2010 Series I: Engineering Sciences ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE M. MOLDOVAN 1 I. VIŞA 1 A. DUŢĂ 1 Abstract: Into
More informationconsumption. As the first step of calculating indoor energy consumption, this study investigated the net radiation heat gain of building exterior surf
Analysis of the Net Radiation Heat Gain of Buildings by Changing Building Distance in Guangzhou and Sendai J. HU 1,*, Y. XUAN 2, and A. MOCHIDA 1 1 Graduate School of Engineering, Tohoku University, Sendai,
More informationAssessing the energy performance of modern glass facade systems
Assessing the energy performance of modern glass facade systems Abdelsalam Aldawoud * Architectural Engineering Department, University of Sharjah Sharjah, United Arab Emirates Abstract. The design and
More informationA Sensitivity Analysis on Mixing Energy Loss in Air-Conditioned Rooms by Using CFD
A Sensitivity Analysis on Mixing Energy Loss in Air-Conditioned Rooms by Using CFD S. Iizuka 1, S. Shiba 1,*, M. Sasaki 1, M. Okumiya 1 1 Nagoya University, Nagoya, Japan ABSTRACT In some office buildings,
More informationNocturnal natural ventilation for low and zero energy office buildings in Central Chile
SET2009-8 th International Conference on Sustainable Energy Technologies,.Aachen, Germany. August 31 st to 3 rd September 2009 Page 1 of 6 Nocturnal natural ventilation for low and zero energy office buildings
More informationThe Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort
The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort Ongun Berk Kazanci, Bjarne W. Olesen 1 1 International Center for Indoor Environment and
More informationThe Bahen Centre for Information Technology. Glazing Studies of the Gallery. Introduction. University of Toronto ~ Toronto, Ontario, Canada
Glazing Studies of the Gallery Introduction The gallery in the Bahen Centre is a circulation space located in the northeast side of the building. One side of the corridor composed of the walls of an auditorium
More informationEFFECTS OF TREES ON THE ROOM TEMPERATURE AND HEAT LOAD OF RESIDENTIAL BUILDING. Tokyo, Japan
Proceedings: Building Simulation 27 EFFECTS OF TREES ON THE ROOM TEMPERATURE AND HEAT LOAD OF RESIDENTIAL BUILDING Yoshiki Higuchi 1 and Mitsuhiro Udagawa 1 1 Department of Architecture, Kogakuin University,
More informationThermal Thermal Applications Category Version 6.4. Integrated Environmental Solutions
Thermal Thermal Applications Category Version 6.4 Integrated Environmental Solutions Contents 1. What is the Thermal Applications Category?... 4 1.1. Compliance View... 4 1.2. Apache
More informationJOTUN Cool Shades. Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings. ai³ Werner Jager
JOTUN Cool Shades Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings ai³ Werner Jager Exclusion of warranty: All tables, graphical charts and results presented within
More informationPASSIVHAUS Designed for you to enjoy maximum comfort with minimum energy.
PASSIVHAUS Designed for you to enjoy maximum comfort with minimum energy. + Energy efficiency + Savings +Comfort WHAT IS PASSIVHAUS? The Passivhaus (Passive House) standard is the most stringent international
More informationLoad Estimation. Ir. Dr. Sam C. M. Hui Faculty of Science and Technology
SPD4121 HVAC Technology for Plumbing Engineers http://ibse.hk/spd4121/ Load Estimation Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Jul 2016 Contents Basic Concepts
More informationSimulation and Energy Analysis of Thermal Environment of Unassisted Passive Solar House
, pp.84-89 http://dx.doi.org/10.14257/astl.2016.123.17 Simulation and Energy Analysis of Thermal Environment of Unassisted Passive Solar House Hou Gang 1, Li Bing 2 1 School of Civil Engineering and Architecture,
More informationAnalysis of a plus-energy house for improved building and HVAC system design
Downloaded from orbit.dtu.dk on: Nov 21, 2018 Analysis of a plus-energy house for improved building and HVAC system design Andersen, M.E. ; Schøtt, J.; Kazanci, Ongun Berk; Olesen, Bjarne W. Published
More informationThe Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies
COM Elithis Tower in Dijon, France Elithis Tower, located in Dijon, France, provides strong evidence that net zero energy office buildings are achievable in near future. The building, which was designed
More informationDr. Eng., Professor, Faculty of Science and Technology, Keio University
中空層ESTIMATION OF EFFECT OF INJECTING POLYURETHANE FOAM INTO WALLS AND RENOVATING WINDOWS IN HOUSES IN JAPAN UP TO 22 STUDY ON REDUCTION OF GREENHOUSE GASES FROM RENOVATING THERMAL INSULATION IN HOUSES
More informationHomesol Passive House Design Process
Homesol Passive House Design Process Passive Houses are residential, commercial and institutional buildings in which a comfortable temperature can be achieved year round with a 75% 85% reduction in energy
More informationIndoor environment for energy performance of buildings a new European draft standard
International Conference Passive and Low Energy Cooling 1109 Indoor environment for energy performance of buildings a new European draft standard O. Seppänen Helsinki University of Technology, Finland
More informationSummer season temperature control in Finnish apartment buildings
Summer season temperature control in Finnish apartment buildings Jarek Kurnitski, Pasi Tauru and Jari Palonen Helsinki University of Technology, Finland Corresponding email: jarek.kurnitski@tkk.fi SUMMARY
More informationThermal Characteristics and Energy Performance of Double Skin. Façade System in the Hot Summer and Cold Winter Zone
Thermal Characteristics and Energy Performance of Double Skin Façade System in the Hot Summer and Cold Winter Zone L.F. Shu 1, G.Q. He 1,*, S.M. Zhang 1 and Q.A. Bai 2 1 College of Civil Engineering and
More informationThe Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario
The Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario Visionwall Technologies Inc. 14904-123 Avenue Edmonton, Alberta, Canada T5V 1B4 Tel: 403 451 4000 Fax:
More informationctbuh.org/papers Effects of Vertical Meteorological Changes on Heating and Cooling Loads of Super Tall Buildings Title:
ctbuh.org/papers Title: Authors: Subjects: Keywords: Effects of Vertical Meteorological Changes on Heating and Cooling Loads of Super Tall Buildings Doosam Song, Sungkyunkwan University Yang Su Kim, Samsung
More informationCould a European Super Energy Efficient Standard Be Suitable for the U.S.? John Broniek, IBACOS BEST1 CONFERENCE June 12, 2008
Could a European Super Energy Efficient Standard Be Suitable for the U.S.? John Broniek, IBACOS BEST1 CONFERENCE June 12, 2008 Agenda European Passive House Program Creating Passive House Designs in U.S.
More informationCAE 331/513 Building Science Fall 2017
CAE 331/513 Building Science Fall 2017 November 14, 2017 Heating load calculations Advancing energy, environmental, and sustainability research within the built environment www.built-envi.com Twitter:
More informationSTEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS
STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS 1. ABSTRACT In modern architecture the buildings are often designed with large glass facades or windows. Due to these
More informationPROPOSAL OF JAPANESE STANDARD OF THE MEASURING METHOD OF AIRFLOW RATES OF BUILDING EQUIPMENTS
PROPOSAL OF JAPANESE STANDARD OF THE MEASURING METHOD OF AIRFLOW RATES OF BUILDING EQUIPMENTS Y. Utsumi 1, S. Hayakawa 2, T. Kurabuchi 3, and H. Yoshino 4 1 Department of Architecture, Miyagi National
More informationcarbon-neutral architectural design Pablo La Roche CRC Press Taylor & Francis Croup Boca Raton London NewYork CRC Press is an imprint of the
carbon-neutral architectural design Pablo La Roche CRC Press Taylor & Francis Croup Boca Raton London NewYork CRC Press is an imprint of the Taylor fit Francis Group, an informs business Contents Preface
More informationEFFECT OF HEAT DISCHARGE BY NATURAL VENTILATION ON INDOOR ENVIRONMENT AND HEAT REMOVAL STRUCTURE
Proceedings of Building Simulation : EFFECT OF HEAT DISCHARGE BY NATURAL VENTILATION ON INDOOR ENVIRONMENT AND HEAT REMOVAL STRUCTURE Hiromi Habara and Yoshiyuki Shimoda Graduate School of Engineering,
More informationWhere,h(t)the indicial response of thermal flow rate, B 0 the
This paper presents the results of investigations that were made on a simulation program, which calculates the temperature, the heat loads, the ventilation rates and the indoor air quality considering
More informationNUMERICAL ANALYSIS OF ANNUAL EXERGY CONSUMPTION FOR DAYLIGHTING, ELECTRIC-LIGHTING, AND SPACE HEATING/COOLING SYSTEM
NUMERICAL ANALYSIS OF ANNUAL EXERGY CONSUMPTION FOR DAYLIGHTING, ELECTRIC-LIGHTING, AND SPACE HEATING/COOLING SYSTEM Hideo ASADA* and Masanori SHUKUYA** * SYSTECH Environmental Research Laboratory, 28
More informationPassive Houses in South West Europe
Dr. Wolfgang Feist Passivhaus Institut Rheinstraße 44/46 D-64283 Darmstadt www.passiv.de Passive Houses in South West Europe A quantitative investigation of some passive and active space conditioning techniques
More informationInfluence of Retro-reflective Material on Public Buildings Energy Consumption in Different Climate Regions
Influence of Retro-reflective Material on Public Buildings Energy Consumption in Different Climate Regions Yanna Gao, Pan Li, Long Xu, Jun Wang, Enshen Long * College of Architecture and Environment, Sichuan
More informationA Study on the Variation of Heating & Cooling Load by the Various Shading and Performance of Window in Office Buildings Seok-Hyun Kim 1, Kyung-ju Shin
A Study on the Variation of Heating & Cooling Load by the Various Shading and Performance of Window in Office Buildings Seok-Hyun Kim 1, Kyung-ju Shin 1, Bo-eun Choi 1, Jae-Hun Jo 2, Young-Hum Cho 3, Soo
More informationCOMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program
COMMERCIAL LOAD ESTIMATING Load Estimating Level 3: Block and Zone Loads Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design,
More informationExperimental Study to Evaluate the Performance of Iraqi Passive House in Summer Season
Journal of Energy and Power Engineering 9 (2015) 386-392 doi: 10.17265/1934-8975/2015.04.008 D DAVID PUBLISHING Experimental Study to Evaluate the Performance of Iraqi Passive House in Summer Season Ghanim
More informationEFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR. Yanping Zhou, Jingyi Wu, Ruzhu Wang
EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR Yanping Zhou, Jingyi Wu, Ruzhu Wang (Institute of Refrigeration and Cryogenics, Shanghai Jiaotong University, Shanghai,
More informationModelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates
Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Kittitach Pichatwatana, and Fan Wang Abstract This paper examines the TAS computer
More informationThermal Characteristics of a Vernacular Building Envelope
Thermal Characteristics of a Vernacular Building Envelope Priyanka Dhar, M.Tech. Department of Energy, Tezpur University, Tezpur, 784028, Assam, India Pallavi Borah, M.Tech. Department of Energy, Tezpur
More informationEvaluation of Subsidy Systems for Energy Retrofit of Existing Dwellings in Japan
Internet Journal of Society for Social Management Systems Issue 1 Vol.1 sms15-9986 (215) ORIGINAL ARTICLE Evaluation of Subsidy Systems for Energy Retrofit of Existing Dwellings in Japan Kotaro KAWATA*
More informationA SIMPLE USER INTERFACE FOR ENERGY RATING OF BUILDINGS
Proceedings of Building Simulation 2011: 1 2 3 4 5 6 7 8 9 10 A SIMPLE USER INTERFACE FOR ENERGY RATING OF BUILDINGS Abraham Yezioro 1, Oren Shapir 1, and Guedi Capeluto 1 1 Faculty of Architecture and
More informationPhase-Change Wallboard and Mechanical Night Ventilation in Commercial Buildings: Potential for HVAC System Downsizing
Phase-Change Wallboard and Mechanical Night Ventilation in Commercial Buildings: Potential for HVAC System Downsizing Corina Stetiu Helmut E. Feustel Lawrence Berkeley National Laboratory, Berkeley, CA
More informationDesign Strategies and Guide lines for Tropical Coast of Pakistan, Using Climate Consultant
European Journal of Sustainable Development (2016), 5, 3, 505-512 ISSN: 2239-5938 Doi: 10.14207/ejsd.2016.v5n3p505 Design Strategies and Guide lines for Tropical Coast of Pakistan, Using Climate Consultant
More informationNatural Ventilation System for a School Building Combined with Solar Chimney and Underground Pit
Natural Ventilation System for a School Building Combined with Solar Chimney and Underground Pit Yoshiteru Shinada, Ken-ichi Kimura, Hiromasa Katsuragi, Sung-ki Song Techno Ryowa Ltd., Japan International
More informationImprovement of Indoor Living Environment by Occupants Preferences for Heat Recovery Ventilators in High-Rise Residential Buildings
Original Paper Indoor and Built Indoor Built Environ 212;21;4:486 52 Accepted: October 17, 211 Environment Improvement of Indoor Living Environment by Occupants Preferences for Heat Recovery Ventilators
More informationBrussels Window. Good Windows. Windows. Objectives. Why Good Windows? Windows. Need to control. Learn. Functions: Same as wall - plus.
Good Windows Brussels Window Dr John Straube Dupont Young Professor Civil Eng Dept and School of Architecture University of Waterloo Waterloo, Ont Canada jfstraube@uwaterloo.ca Windows Objectives Need
More informationNew Generation Office Building
New Generation Office Building Prof. Dr. Berlin University of the Arts Building Service Engineering New Generation Office Building PILOT PROJECTS New Generation Office Building Energy Efficiency Cost Efficiency
More informationSKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION
SKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION Xianou Li, Frederick Wong, and Yihan Li Arup International Consultants (Shanghai) Co Ltd ABSTRACT This paper
More informationCHAPTER 6 CONCLUSION
255 CHAPTER 6 CONCLUSION This study thoroughly assessed the design principles employed in simple, durable and eco-friendly vernacular dwellings in the coastal regions of Tamil Nadu and their effectiveness
More informationAssessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains
Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains Andrzej Baranowski 1,2 and Joanna Ferdyn-Grygierek 1,2 1 Silesian University of
More informationOptimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models
L. Pagliano et al, I: Optimization of air tightness and night ventilation for Passive houses in Italian climates... 1 Optimization of air tightness and night ventilation for Passive houses in Italian climates
More informationSlab cooling system design using computer simulation
Slab cooling system design using computer simulation Lain, M.; Zmrhal, V.; Drkal, F.; Hensen, J.L.M. Published in: Proceedings of the International CESB Conference 07, 24-26 September, Czech Technical
More informationSOUTH AFRICAN NATIONAL STANDARD
ISBN 978-0-626-26403-1 SOUTH AFRICAN NATIONAL STANDARD Energy efficiency in buildings Published by SABS Standards Division 1 Dr Lategan Road Groenkloof Private Bag X191 Pretoria 0001 Tel: +27 12 428 7911
More informationTHERMAL CHARACTERISTICS OF A DOUBLE-GLAZED EXTERNAL WALL SYSTEM WITH ROLL SCREEN IN COOLING SEASON
THRML HRTRISTIS OF DOUBL-LZD XTRNL WLL SYSTM WITH ROLL SRN IN OOLIN SSON H. Tanaka, M. Okumiya, H.Tanaka,.Yoon, and K. Watanabe Nikken Sekkei o.ltd., ichi, Japan Department of nvironment & rchitecture,
More informationApplication of Passive Energy Savings Strategies for Optimization of Building Energy Performance: A Case Study
ISSN 1816-6075 (Print), 1818-0523 (Online) Journal of System and Management Sciences Vol. 8 (2018) No. 3, pp. 52-66 Application of Passive Energy Savings Strategies for Optimization of Building Energy
More informationSummer thermal comfort in traditional buildings of the 19th century in Florina, north-western Greece
International Conference Passive and Low Energy Cooling 239 Summer thermal comfort in traditional buildings of the 19th century in Florina, north-western Greece A. Oikonomou Department of Architectural
More informationInvestigation of comfort temperature and the adaptive model in Japanese houses
Proceedings of 7 th Windsor Conference: The changing context of comfort in an unpredictable world Cumberland Lodge, Windsor, UK, 12-15 April 2012. London: Network for Comfort and Energy Use in Buildings,
More informationPRINCIPLES AND POTENTIALS OF VENTILATIVE COOLING
PRINCIPLES AND POTENTIALS OF VENTILATIVE COOLING PER HEISELBERG OPERATING AGENT IEA EBC ANNEX 62 BACKGROUND THE CURRENT DEVELOPMENT TOWARDS NEARLY- ZERO ENERGY BUILDINGS HAVE LEAD TO AN INCREASED NEED
More informationEFFECTIVENESS OF ENERGY CONSERVATION MEASURES IN RESIDENTIAL SECTOR OF JAPANESE CITIES
EFFECTIVENESS OF ENERGY CONSERVATION MEASURES IN RESIDENTIAL SECTOR OF JAPANESE CITIES Ayako TANIGUCHI 1, Yoshiyuki SHIMODA 1, Takahiro ASAHI 1, Yukio YAMAGUCHI 1, and Minoru MIZUNO 1 1 Division of Sustainable
More informationREGIONAL CHARACTERISTICS OF AIR-CONDITIONING LOADS FOR RESIDENCES IN CHINA
Seventh International IBPSA Conference Rio de Janeiro, Brazil August 13-15, 2001 REGIONAL CHARACTERISTICS OF AIR-CONDITIONING LOADS FOR RESIDENCES IN CHINA Qingyuan Zhang, Kenji Asano, and Hajime Imai,
More informationCost-Benefit Analysis of Dwelling Retrofit Options
Cost-Benefit Analysis of Dwelling Retrofit Options The objective was to study the thermal behaviour of the existing house and suggest cost effective improvements. Over recent years the energy efficiency
More informationThe Centre for Sustainable Building (ZUB) * A Case Study
The Centre for Sustainable Building (ZUB) * A Case Study Dietrich Schmidt Tekn. Lic. 1,2 1 KTH-The Royal Institute of Technology. Division of Building Technology. Brinellvägen 34. SE-100 44 Stockholm.
More informationLong-term Measurement of Indoor Thermal Environment and Energy Performance in a Detached Wooden House with Passive Solar Systems
Long-term Measurement of Indoor Thermal Environment and Energy Performance in a Detached Wooden House with Passive Solar Systems Yoshimi Ishikcnw, Tohoku Institute of Technology, Sendai, Japan Hiroshi
More informationAnalysis of Distributed Energy Supplying Technologies From the Viewpoint of Waste Heat
Analysis of Distributed Energy Supplying Technologies From the Viewpoint of Waste Heat Yutaka Nagata, Central Research Institute of Electric Power Industry ABSTRACT In Japan and other countries cogeneration
More informationInfiltration simulation in a detached house empirical model validation
Infiltration simulation in a detached house empirical model validation Juha Jokisalo¹, Targo Kalamees¹, Jarek Kurnitski¹, Lari Eskola¹, Kai Jokiranta¹ and Juha Vinha² ¹Helsinki University of Technology,
More information7KH3UHGLFWLRQ0HWKRGRI:DWHU 7HPSHUDWXUHLQ'LVWULEXWLRQ3LSHV
7KH3UHGLFWLRQHWKRGRI:DWHU 7HPSHUDWXUHLQ'LVWULEXWLRQ3LSHV 'U.6DNDXH'U.DPDWD'U6,ZDPRWR'U +1LPL\D (1) 6DNDXH#LVFPHLMLDFMS Dept. of Architecture, School of Science and Technology, Meiji University, Japan.
More informationEvaluating the Building Performance of the Center for Promotion of Science in Block 39 in Belgrade, Serbia
Evaluating the Building Performance of the Center for Promotion of Science in Block 39 in Belgrade, Serbia Berrak Balci Abstract This paper presents the evaluation of the building performance of the previously
More informationPotential of natural ventilation in shopping centres
Indoor Air 28, 17-22 August 28, Copenhagen, Denmark - Paper ID: 758 Potential of natural ventilation in shopping centres Alice Diederichsen 1,*, Kristina Friis 1, Henrik Brohus 2 and Gitte T. Tranholm
More informationInvestigation of indoor climate in a naturally ventilated building
Investigation of indoor climate in a naturally ventilated building Indoor Air 2008 Tine S. Larsen Assistant professor Department of Civil Engineering Aalborg University tsl@civil.aau.dk 1/9 Introduction
More information