INDEPENDENT ASSESSMENT OF THE PREMATURE FAILURE OF THE X- 670A COOLING TOWER COILS

Size: px
Start display at page:

Download "INDEPENDENT ASSESSMENT OF THE PREMATURE FAILURE OF THE X- 670A COOLING TOWER COILS"

Transcription

1

2

3 INDEPENDENT ASSESSMENT OF THE PREMATURE FAILURE OF THE X- 67A COOLING TOWER COILS CONTRACT NO. PO SOLICITATION NO. FBP13SC364 DOCUMENT NO. PREPARED BY:

4 TABLE OF CONTENTS PURPOSE... 1 EVENT SUMMARY... 2 SUMMARY TIMELINE OF SIGNIFICANT EVENTS... 3 ORIGINAL DESIGN SPECIFICATION FOR COOLING TOWER COILS... 6 X-67 RCW SYSTEM WATER SPECIFICATIONS... 6 HISTORICAL WATER CHEMISTRY DATA... 8 WATER TREATMENT EFFORTS CAUSES OF PREMATURE FAILURE PROPOSED RECOMMENDATIONS Page i

5 PURPOSE A new Dry Air Plant, Bldg X-67, was constructed at the DOE Portsmouth Facility and placed in operation by September 21. Five cooling tower cells constructed as part of this project provided cooling water for Bldg X-67, X-3, and Bldg X-71. By September 213, all five of the cooling tower coils on the closed loop cooling system had failed due to leaks in the coils. An independent investigation was performed to determine the probable cause of the cooling coil failures and to evaluate proposed corrective actions. The investigation included: review of EVAL-TS-214-1; review of the Bldg X-67 and the X-67A Cooling Tower System P&IDs, design specifications, vendor data, as-built drawings, water quality data; and interviews with personnel associated with the project. Personnel interviewed or consulted included: NAME COMPANY POSITION Wayne Hacker FBP* Lead Engineer Bob Penn FBP* System Engineer Bernie Carrick FBP* Design Authority Al Hoffman FBP* Utilities Lead Dick Armstrong FBP* Utilities Manager Wendell Jenkins FBP* Technical Support Chris Kelly GE Water & Process Technologies FBP water quality vendor Brian Bridgeford Stoermer-Anderson, Inc. Manufacturer s Rep. for Marley Cooling Technologies/SPX, cooling tower supplier Scott Massie Geiger Brothers President, mechanical contractor Larry Smith Camp Dresser & McKee (CDM) Design Manager, design/build prime contractor Jeff Bowley Air Relief Technical Support, air compressor vendor Leisa Corbett Houghton Chemical Corp Water Treatment Business Manager, propylene glycol supplier Richard De Martino Industrial Water Technologies Corrosion consultant for Houghton Chemical Corp * USEC employee during the Dry Air Plant construction The purpose of this report is to address the following: a) Event Summary including a timeline of significant events for X-67A Cooling Tower and X-67 RCW Systems. b) Analysis of the original project design specification for the X-67A Cooling Tower coils and the required water quality. c) Analysis of the water specifications provided by the X-67 RCW systems and limitations d) Analysis of the historical X-67 RCW System water chemistry from day 1 (start-up) of the X-67A Cooling Tower to the present time. e) Analysis of the efforts to maintain and control the water chemistry over time. f) Conclusion summary of the cause(s) of the premature failure of the X-67A Cooling Tower coils and the cause(s) of other heat exchanger problems in the X-67 RCW system. g) Analysis of proposed recommendations of how to correct the problem for the long term. Page 1/16

6 EVENT SUMMARY The X-67A cooling towers were installed as part of a design-build project to provide recirculating cooling water (RCW) to the Portsmouth DOE site. The recirculating cooling water system was designed to provide cooling to the Bldg X-67 Dry Air Plant, the X-3 Plant Control Facility chiller, and the two X-71 Laboratory chillers. The RCW system was started up on September 3, 21. Flushing was performed using Ferroquest FQ713 to clean and passivate the steel piping. The initial flushing was noted to have been incomplete, in that the water in the system was still visibly rusty after three flushes. A corrosion inhibitor, Corrshield OR447, and glycol were added to the glycol closed-loop system and startup activities continued. The Dry Air Plant system was put into operation on Although efforts were made to filter out the iron, the system was plagued with excess iron in the glycol system. This apparently caused fouling of the equipment which necessitated increased flow and lower cooling water temperatures. The ph declined steadily from the point of startup. Within a year of startup, the copper corrosion coupon indicated increased corrosion rate, from mpy to.3 mpy. A copper corrosion inhibitor was added in December 211, which reduced the rate of corrosion and increased the ph briefly, but the system continued to decline in ph and the corrosion issue persisted. Almost two years after the system was put in operation, the plant began experiencing issues with leaks in the compressor and dryer cooling systems. During repairs by the air compressor vendor, it was discovered that the cooling water side of the system was filled with iron sludge. The X-67 Dry Air Plant compressed air system was shut down but the cooling towers continued to operate to provide cooling for the X-3 and X-71 chillers. Copper corrosion rates appear to have increased to.8 mpy by December 212. A maintenance shutdown from March 213 to May 213 prevented treatment of the system during this time period. Copper corrosion inhibitor was added to the glycol system in April 213 with no noticeable impact. Leaks began developing in the cooling tower closed-loop coils in May 213. Between May 213 and September 213, GE Water added copper corrosion inhibitor and borate to the glycol system, in an effort to raise the system ph. During this time, each of the cooling tower closed loop coils developed leaks. Eventually, the cooling tower glycol system coils failed, resulting in total shutdown of the X-67A RCW system. The X-3 and X-71 chillers were switched over to the X-726 RCW system. A summary timeline of events is shown below. Page 2/16

7 SUMMARY TIMELINE OF SIGNIFICANT EVENTS DATE EVENT X-67 RCW initial construction completed, flushing performed using Ferroquest FQ713 Three flushes completed but the water was still visibly rusty X-67 RCW system filled with corrosion inhibitor, CorrShield OR447, and propylene glycol solution X-67 air compressors placed in service GE Water performs particle size analysis to determine filtration requirements Corrosion coupons installed Iron sludge sample provided to GE Water for analysis Jan 211 GE Water recommends filtration to remove excess iron from glycol system Meeting to discuss iron removal Aug 211 Side-stream filter skid installed Aug Dec 211 Coupons indicate increase in corrosion rate in glycol system (up to.2 mpy for mild steel and.4 mpy for copper) GDP M&O responsibilities transferred to FBP Azole copper corrosion inhibitor (AZ814), dispersant (DIANODIC DN23), and phosphate added to glycol system Corrosion rates drop, ph increases Page 3/16

8 DATE EVENT #1 Compressor shut down on high vibration after cooler leak discovered, due to tube pitting cooler cavities full of iron sludge #2 compressor shut down on surging Oct #3 Compressor shut down on surging Intercooler leak discovered Replaced intercooler #2 Compressor aftercooler leaks found Iron sludge in water side of cooler #3 oil cooler failed Found leaks in oil cooler Iron sludge in water side of cooler GE Water performs test to determine feasibility of using polymers for coagulation of iron to improve filtration from glycol system Tests indicate polymer use to be impractical #3 Compressor surging All three compressors shut down until water quality resolved X-67 RCW continues to operate for cooling X-3 & X Brass corrosion coupon exhibits signs of tarnish Mar May 213 Work activities suspended until JHAs and work packages prepared Corrosion inhibitor (azole) added to glycol system Cooling Tower Cell #2 glycol system coil failure, leaks gallons of azole (AZ814) added to glycol system Page 4/16

9 DATE EVENT Replaced side stream filter skid with larger capacity filter system (2% f system flow) Marginal decrease in glycol system iron content Meeting held to discuss changes in chemical treatment in order to remove iron Ordered mixed metal corrosion inhibitor (Corrshield MD41), dispersant (GENGARD GN74), and a biodispersant (SPECTRUs BD157) Cooling Tower Cell #1 glycol system coil failure, leaks gallons of borate (Corrshield BT431) added to glycol system copper coupon corrosion rate drops to.2 mpy gallons of azole (AZ814) added to glycol system Borate (Corrshield BT431) added to system ph increases from 6 to Cooling Tower Cell #3 glycol system coil failure, leaks gallons of borate (Corrshield BT431) added to glycol system ph increases to gallons of borate (Corrshield BT431) added to glycol system Cooling Tower Cell #4 glycol system coil failure, leaks GE performed analysis to determine borate concentration required to neutralize the glycol system Cooling Tower Cell #5 glycol system coil failure, leaks All cooling towers out of service X-71 and X-3 chillers switched over to X-626 RCW system Page 5/16

10 ORIGINAL DESIGN SPECIFICATION FOR COOLING TOWER COILS REQUIREMENTS USEC ESO E3373, Specification , MAJOR EQUIPMENT PROCUREMENT SPECIFICATION, X-67A Dry Air Plant Cooling Tower Procurement, Par. 2.1 J. identified the cooling tower Heat-Exchanger Coils requirements as: 1. Tube and Tube Sheet Materials: Prime-coated steel tube and sheet with outer surface of tube and sheet hot-dip galvanized after fabrication. 2. Heat-Exchanger Arrangement: Serpentine tubes 3. Field Piping Connections: Vent, supply, and return suitable for mating to ASME B16.5, Class 15 flange Par. 2.1.T.3. identified the following heat exchanger coil requirements: a. Fluid Type: 4% Propylene Glycol and Water b. Fluid Flow/Cell: 125 gpm per cell c. Fluid Pressure Drop: psig d. Entering-Fluid Temperature: 1 deg. F e. Leaving-Fluid Temperature: 85 deg. F f. Entering-Air Wet-Bulb Temperature: 78 deg F EVALUATION The SPX vendor data for the cooling tower coils, submitted by Stoermer-Anderson, was consistent with the performance requirements identified in the specification. The specification did not directly address water quality requirements for the closed loop (glycol loop). REQUIREMENTS X-67 RCW SYSTEM WATER SPECIFICATIONS USEC ESO E3373, Specification , MAJOR EQUIPMENT PROCUREMENT SPECIFICATION, Air Compressor Procurement, Par. 4, identified the following design criteria: Cooling Water Design Temperature: 85 F +1/-5 F Cooling Water Design Pressure: 7 psig +5/-35 psig USEC ESO E3373, Specification , Par required the cooling water for the dryer aftercooler to be treated for corrosion control and have a supply design temperature of 65 F at 5-65 psig. USEC SOW-ENG-1-21, Specification Section 1574, Cleaning of Utility Piping, addressed cleaning of the internal surfaces of piping designated as utility piping for tower cooling water service (TWC) and Process Water (PW). Par. 1.3 required the Contractor submit a TWC Pipe Cleaning and Flushing Plan. Par. 3.2 required that all pipelines shall be flushed at no less than their design flow rate unless a lesser rate is approved by the STR. USEC SOW-ENG-1-21, Specification Section 1551-F138, Process Cooling, Raw and Cooling Tower Water, indicated that, unless otherwise specified, all material includes a minimum corrosion allowance of.65 inch. Page 6/16

11 The proposed New Coolant Piping Cleaning Sequence reviewed for this assessment required charging the new X-67 system piping with cleaning chemicals then recirculating the water for hours while controlling ph in the 6.5 to 7. range. Par. 2.1 required replacing one-half the system volume with fresh water and new cleaning chemicals if the iron level exceeded 12 ppm. Par required flushing the entire new X-67 piping system when the iron levels reached a plateau. Section 3. proposed addition of the propylene glycol to the X-67 piping then adding inhibitors through the equalization tank. EVALUATION The cooling water heat transfer requirements appear to be adequate. More information is required to perform a detailed analysis of the cooling capacity of the system. The design documents did not provide details of the design basis. Specific water quality requirements for the glycol loop were not located during this assessment. The proposed New Coolant Pipe Cleaning Sequence recirculation duration of hours is not consistent with the product data sheet for Ferroquest FQ713, which indicates a minimum recirculation period of 72 hours, followed by a 24 hour rinse. The propylene glycol product sheets provided by the project were for Safe-T-Therm, which is inhibited. Conversations with Houghton Chemical, the propylene glycol supplier, indicated that the product that was ordered and delivered was uninhibited glycol. Uninhibited glycol is corrosive to steel and copper, which could have a detrimental impact on the system until corrosion inhibitors are added. The impact of the contact with the uninhibited glycol would be proportionate to the amount of time between introduction of the propylene glycol and addition of the corrosion inhibitor. Page 7/16

12 HISTORICAL WATER CHEMISTRY DATA The water chemistry data indicate the following trends: The general trend over time was an increase in iron and copper (See FIGURE 1 below). This would be consistent with an increase in corrosion over time. FIGURE 1 METAL CONCENTRATION vs TIME Iron (ppm) Copper (ppm) Linear (Iron) Linear (Copper) Iron (ppm) Copper (ppm) Date Page 8/16

13 The ph trend for the X-67 glycol cooling system was a fairly consistent drop from the time the system monitoring began until the system was shut down (see FIGURE 2 below). Chemical addition accounts for the local points of rise in ph. FIGURE 2 ph vs TIME 9. ph Linear (ph) ph DATE Page 9/16

14 The trend for the level of iron and copper in the water was consistent with the ph level (see FIGURE 3 below), which would be expected. Data for events such as water addition, glycol addition, and removal of metals by filtration was not available but did not appear to have a significant impact on the overall trend. FIGURE 3 METAL CONCENTRATION vs ph Iron (ppm) Copper (ppm) Linear (Iron) Linear (Copper) 6, 4 5, , 25 Iron (ppm) 3, 2, 2 15 Copper (ppm) 1 1, ph Page 1/16

15 The trend for propylene glycol concentration over time (FIGURE 4) is similar to the trend for ph over time (FIGURE 2), which is consistent with the fact that glycol breaks down into organic acids at an accelerated rate when the ph drops below about 7. The general trend for propylene glycol concentration was to drop as the ph decreased (FIGURE 5), which would be expected. The individual points would be affected by glycol or make-up water addition, if they occurred. These events were not identified in the timeline but seem likely to have been necessary. 45 FIGURE 4 GLYCOL CONCENTRATION vs TIME Propylene Glycol % Linear (Propylene Glycol %) Propylene Glycol (%) DATE FIGURE 5 GLYCOL CONCENTRATION vs ph Propylene Glycol % Linear (Propylene Glycol %) Propylene Glycol (%) ph Page 11/16

16 The level of potassium in the cooling water is an indicator of the amount of corrosion inhibitor present. The levels of potassium were generally too low to determine the impact on the amount of iron in the water, which would be an indication of the rate of corrosion. FIGURE 6 shows the relationship between the amount of iron in the water and the amount of corrosion inhibitor. FIGURE 7 shows the change in the level of corrosion inhibitor over time. The increase in potassium in January 212 correlates with the addition of corrosion inhibitor in December 211. Data points for potassium were not provided for the period after July 213. FIGURE 6 METAL CONCENTRATION vs POTASSIUM CONCENTRATION Iron (ppm) Copper (ppm) Linear (iron) Linear (Copper) Potassium (ppm) Iron (ppm) , 5, 4, 3, 2, 1, Potassium (ppm) FIGURE 7 POTASSIUM CONCENTRATION vs TIME Potassium (ppm) Linear (Potassium) Copper (ppm) DATE Page 12/16

17 6 The level of azole in the water was typically too low to contribute to a trend. Azole is a copper corrosion inhibitor. The comparison of the level of copper to azole in the glycol water is shown in FIGURE 8. The level of azole in the water over time is shown in FIGURE 9. FIGURE 8 METAL CONCENTRATION vs AZOLE CONCENTRATION Iron (ppm) Copper (ppm) Linear (Iron) Linear (Copper) Iron (ppm) Copper (ppm) Azole (ppm) FIGURE 9 AZOLE CONCENTRATION vs TIME Azole (ppm) Linear (Azole) 1 Azole (ppm) DATE Page 13/16

18 The corrosion rates for the mild steel and copper were generally low. The mild steel corrosion rate varied from to 1.3 mpy with half of the readings at mpy. The copper corrosion rate varied from to 1 mpy, with 3% of the readings at mpy. The coupon corrosion rates would be expected to correspond with the levels of iron and copper in the solution but the general trend indicated no significant change in metal level with change in corrosion rate. The design allowance for corrosion was identified as.65 inches. Assuming a useful life of 3 years for the equipment results in an allowable corrosion rate of mils per year (mpy). The corrosion rates measured for mild steel never exceeded 1.3 mpy, with the majority of the rates at mpy. FIGURE 1 shows the relationship between the amount of iron in the cooling water and the mild steel corrosion rate. FIGURE 1 IRON CONCENTRATION vs CORROSION RATE Iron (ppm) Linear (ppm) 6, 5, 4, Iron (ppm) 3, 2, 1, Mild Steel Corrosion (mpy) Page 14/16

19 DISCUSSION WATER TREATMENT EFFORTS The timeline indicates that water treatment for the X-67 project glycol loop consisted of cleaning and passivation of the glycol pipe, prior to introduction of propylene glycol. The cleaning and passivation plan included adding Ferroquest FQ713 to the cooling water loop and circulating the water for 48 to 72 hours while flushing as needed to ensure the iron levels remained below 1,2 ppm. The actual sequence of events from the construction logs is not clear. The timeline information provided indicates that three flushes were performed and the flush water was still visibly rusty. It is not clear as to whether water quality data was taken. The decision was made to discontinue the cleaning effort and add the necessary quantity of propylene glycol to bring the glycol concentration in the system to 4%. The plan for propylene glycol addition included adding propylene glycol then circulating the mixture through the glycol cooling loop. Corrosion inhibitors were then to be added to the glycol loop through the equalization tank. The timeline shows that corrosion inhibitor, CorrShield OR447, was added to the propylene glycol solution between and No water quality data was available until November 21, so the condition of the glycol loop water is unknown until that date. The data for November 21 shows the ph was 8.8, copper was <.5 ppm, iron was 91 ppm, and tolyltriazole was 1 ppm. No value was provided for potassium. Treatment efforts from that point on appear to have been primarily focused on removal of the iron particles in the water through filtration. Filtration appears to have had little impact on the total iron in the water. In December of 211, corrosion inhibitors were added in response to what was characterized as increased corrosion in the test coupons. A brass corrosion coupon was installed prior to January 213. Indication of corrosion in the coupon resulted in addition of a copper corrosion inhibitor in April 213 and May 213. In June 213, the side stream filtration rate was increased in an attempt to reduce the level of iron in the glycol loop water. In July, the decision to change chemical treatment resulted in a plan to treat the water with a corrosion inhibitor, dispersant, and biodispersant. These chemicals were ordered but not received before the system was shut down. A buffer (Corrshield BT431) was added several times in August 213 in an attempt to control the corrosion by increasing the glycol system ph. The ph did increase but the system failed before further treatment could be applied. EVALUATION It appears that the treatment of the glycol water system was primarily limited to removing excess iron through filtration and controlling perceived accelerated corrosion of copper until the system was close to failure. At that point efforts to control corrosion by adding corrosion inhibitor and dispersants were curtailed by failure of the cooling tower coils. Page 15/16

20 CAUSES OF PREMATURE FAILURE Excess iron in the X-67 glycol loop, left from incomplete cleaning and passivation of the system, appears to have caused restrictions through the heat exchangers and coils of the equipment. This required increased flow and lower cooling water temperatures in order to achieve the required cooling. The excess iron may have contributed to consumption of the initial batch of corrosion inhibitor and a drop in ph of the system. As the ph dropped, the degradation rate of the propylene glycol increased, resulting in the presence of organic acids which caused the corrosion of the steel to increase. The continued corrosion of the steel prevented the filtration from significantly impacting the iron levels in the water. The use of uninhibited propylene glycol compounded the difficulty in the initial treatment of the system and may have contributed to the increased rate of system degradation. Corrosion inhibitor for the steel was not added to the system until August 213, when the cooling tower coils were failing. By this time, the propylene glycol had been subjected to low ph levels for extended periods of time, resulting in accelerated degradation of the glycol and increased production of organic acids. The degradation of the glycol may have caused bacterial colonies to develop. The restrictions in the coils may have caused high velocities and erosion may have caused excess wear in the coils. It is also possible that the copper in the water may have caused pitting in the coils. Microbial corrosion could also have been a factor in the coil failure. PROPOSED RECOMMENDATIONS The X-67 loop should be emptied of the existing treated water and flushed clean. The failed coils should be removed and the failed sections examined to determine the cause of the leaks. Examination should reveal the type of failure and provide insight into possible issues impacting corrective actions. All components of the system should be physically cleaned and examined for damage. The extent and method of cleaning should be determined, based on the component characteristics, so that the majority of deposits are removed and so as to limit interference with examination. The method and frequency of examination should be based on the salient features of the component and the failure modes determined from the analysis of the failed components. The fill lines into the equalization tank should be extended beneath the operating level of the tank, to limit aeration of the water. The lines should be thoroughly flushed and passivated prior to adding glycol. Leak testing of the system should be performed prior to glycol addition. An inhibited glycol solution should be added to the system. Monitoring of the water quality should be performed regularly, including testing for biological activity. Page 16/16

Sulfuric Acid Plant Cooling Tower Improvements

Sulfuric Acid Plant Cooling Tower Improvements Technical Paper Sulfuric Acid Plant Cooling Tower Improvements Ryan Barbour, Herb Quinones and Tom Refi GE Water & Process Technologies 4636 Somerton Road Trevose, PA 19053 Find a contact near you by visiting

More information

NACE CORROSION 2008 TEG 096X Symposia - Paper 1421

NACE CORROSION 2008 TEG 096X Symposia - Paper 1421 NACE CORROSION 2008 TEG 096X Symposia - Paper 1421 Electrochemical Studies with Coupled Multielectrode Array Sensors on Corrosion Inhibition of Copper and Affected Metals in the Presence of Ammonia and

More information

SECTION HVAC WATER TREATMENT

SECTION HVAC WATER TREATMENT PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 25 00 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between //-----// if not applicable to project. Also delete any other item or paragraph

More information

EXHIBIT A UNIVERSITY OF NEVADA - LAS VEGAS WATER TREATMENT BEST PRACTICES

EXHIBIT A UNIVERSITY OF NEVADA - LAS VEGAS WATER TREATMENT BEST PRACTICES UNIVERSITY OF NEVADA - LAS VEGAS WATER TREATMENT BEST PRACTICES This document is designed to guide the UNIVERSITY OF NEVADA - LAS VEGAS HVAC systems through the difficult task of managing the water treatment

More information

HVAC WATER TREATMENT 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. D. Section Plumbing (Potable) Water Treatment

HVAC WATER TREATMENT 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. D. Section Plumbing (Potable) Water Treatment 232500 HVAC WATER TREATMENT PART 1 GENERAL 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS A. Section 230510 Chilled Water Systems B. Section 230520 Heat Generation C. Section 230530 Clean Steam

More information

Why wait until catastrophe strikes? Prevent the Chain Reaction of Equipment Wear, Maximize Heat Transfer, Protect Equipment Life

Why wait until catastrophe strikes? Prevent the Chain Reaction of Equipment Wear, Maximize Heat Transfer, Protect Equipment Life Why wait until catastrophe strikes? Prevent the Chain Reaction of Equipment Wear, Maximize Heat Transfer, Protect Equipment Life IAS has pioneered and utilizes a new generation high-velocity, chemical

More information

COMMERCIAL / INDUSTRIAL COOLING TOWER SIDE STREAM FILTER SYSTEMS

COMMERCIAL / INDUSTRIAL COOLING TOWER SIDE STREAM FILTER SYSTEMS COMMERCIAL / INDUSTRIAL COOLING TOWER SIDE STREAM FILTER SYSTEMS When performance & value matters. WHY DO COOLING TOWERS REQUIRE FILTRATION? Cooling towers are excellent air scrubbers. High volumes of

More information

Water Treatment Program. Training Manual

Water Treatment Program. Training Manual Water Treatment Program Training Manual First Edition, SECTION A INTRODUCTION The Operating Personnel involved in the Water Treatment Program come from various trade backgrounds and they may not have received

More information

A. Submit manufacturer s data, qualifying documents, and shop drawings on the proposed water treatment system before starting any work.

A. Submit manufacturer s data, qualifying documents, and shop drawings on the proposed water treatment system before starting any work. 15545 WATER TREATMENT ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 232516 An optional keynote to

More information

Tech Byte 11: Benefits of Filtration for Open Cooling Tower Systems

Tech Byte 11: Benefits of Filtration for Open Cooling Tower Systems The need for filtration of any cooling tower system is somewhat understood and accepted by most building professionals and plant operating engineers. However, for some, that need is finally driven home

More information

Risk to GSHP Closed Circuit Systems Methodology & Analysis. John Westerman

Risk to GSHP Closed Circuit Systems Methodology & Analysis. John Westerman Risk to GSHP Closed Circuit Systems Methodology & Analysis John Westerman Suppliers of Innogreen GeoPro Zero Toxicity Maximum Efficiency- Triazole Free NSF Certified InnoGreen LTD. Oxford Science Park-OX4

More information

W ater T alk. Field Corrosion Testing using Coupons

W ater T alk. Field Corrosion Testing using Coupons W ater T alk Field Corrosion Testing using Coupons Volume 12, Issue 1 April 2012 Most Cooling Water systems are continuously in use. Therefore it is rare to have access to inspect the actual system to

More information

Metropolitan Washington Airports Authority PROCUREMENT AND CONTRACTS DEPT. AMENDMENT OF SOLICITATION

Metropolitan Washington Airports Authority PROCUREMENT AND CONTRACTS DEPT. AMENDMENT OF SOLICITATION PROCUREMENT AND CONTRACTS DEPT. AMENDMENT OF SOLICITATION Metropolitan Washington Airports Authority Procurement and Contracts Dept., MA-29 2733 Crystal Drive Arlington, VA 22202 1A. AMENDMENT OF SOLICITATION

More information

Radiator Maintenance

Radiator Maintenance 45 Heales Road, Lara VIC, Australia 3212 Phone +61 3 5275 6644 Facsimile +61 3 5275 3333 Radiators are designed to give maximum life with minimum maintenance, thus providing efficient reliable service

More information

Corrosion Solutions. What is MIC? You can t be sure unless you know your system is free of both Oxygen corrosion and MIC.

Corrosion Solutions. What is MIC? You can t be sure unless you know your system is free of both Oxygen corrosion and MIC. Are you sure that your Fire Sprinkler System will actually work after one, five, ten or more years? Are you sure it will even work properly right now? You can t be sure unless you know your system is free

More information

Cleaning Techniques for Cooling Systems and Boilers

Cleaning Techniques for Cooling Systems and Boilers Cleaning Techniques for Cooling Systems and Boilers Cleaning Applications in Industrial Utility Systems Pre Operational Cleaning and Passivation Removal of Organic Buildup caused by leaks or biofilms Exchanger

More information

1. Introduction. Figure 1: Open Recirculation Cooling Water Tower (image courtesy of Solenis) Page 3

1. Introduction. Figure 1: Open Recirculation Cooling Water Tower (image courtesy of Solenis) Page 3 Table of Contents 1. Introduction... 3 2. Description of Root Causes of Corrosion... 4 3. Electrochemical Corrosion... 6 4. Under-Deposit Corrosion... 8 5. Microbial-Induced Corrosion... 9 6. Corrosion

More information

IWC ZLD: New Silica Based Inhibitor Chemistry Permits Cost Effective Water Conservation for HVAC and Industrial Cooling Towers

IWC ZLD: New Silica Based Inhibitor Chemistry Permits Cost Effective Water Conservation for HVAC and Industrial Cooling Towers IWC 07-11 ZLD: New Silica Based Inhibitor Chemistry Permits Cost Effective Water Conservation for HVAC and Industrial Cooling Towers Report by Dan Duke Water Conservation Technology International water-cti.com

More information

heat transfer fluid propylène glycol Inhibé Fluide de transfert de chaleur available in : Do not mix with ethylene glycol heat transfer fluids.

heat transfer fluid propylène glycol Inhibé Fluide de transfert de chaleur available in : Do not mix with ethylene glycol heat transfer fluids. description SPECIFICATIONS This high quality, heavy duty heat transfer fluid contains a specially designed package of corrosion inhibitors. It provides an operating temperature range of -46 C to 163 C,

More information

high cycles cooling tower operation using a revolutionary alkaline treatment program Continuum* AEC (Alkyl Epoxy Carboxylate)

high cycles cooling tower operation using a revolutionary alkaline treatment program Continuum* AEC (Alkyl Epoxy Carboxylate) Water Technologies & Solutions technical paper high cycles cooling tower operation using a revolutionary alkaline treatment program Continuum* AEC (Alkyl Epoxy Carboxylate) Authors: Joseph Janeczko (SUEZ),

More information

HOUGHTO-PHOS 6300 LOW TEMPERATURE MANGANESE PHOSPHATE

HOUGHTO-PHOS 6300 LOW TEMPERATURE MANGANESE PHOSPHATE Process Instructions HOUGHTO-PHOS 6300 LOW TEMPERATURE MANGANESE PHOSPHATE Houghto-Phos 6300 is a manganese phosphate product designed to be used for break-in lubrication of iron and steel materials. Houghto-Phos

More information

Evaporative Condenser Passivation. Cameron Klein Strand Associates, Inc.

Evaporative Condenser Passivation. Cameron Klein Strand Associates, Inc. Evaporative Condenser Passivation Cameron Klein Strand Associates, Inc. Evaporative Condenser Wetted Surface Materials of Construction Galvanized Steel Protective zinc coating fused to a steel substrate

More information

Real World Experiences with a Plant- Based Alternative to Chemical Treatment in Cooling Water Systems

Real World Experiences with a Plant- Based Alternative to Chemical Treatment in Cooling Water Systems Real World Experiences with a Plant- Based Alternative to Chemical Treatment in Cooling Water Systems Steve Chewning, CWT, Southeastern Laboratories, Inc. September 2018 Companies adopting sustainable

More information

Applied ATP: Monitoring Treatment Performance Case Histories

Applied ATP: Monitoring Treatment Performance Case Histories Applied ATP: Monitoring Treatment Performance Case Histories Richard W. Walter Jr., Ph. D. Antimicrobial Specialists and Associates, Inc. P.O. Box 88 Midland, MI 4864 ABSTRACT AWT members focus on treatment

More information

Zero Blowdown Technology - ZBT Arizona Transportation Center

Zero Blowdown Technology - ZBT Arizona Transportation Center Zero Blowdown Technology - ZBT Arizona Transportation Center A major transportation center in Arizona was designed to be certified by the USGBC LEED green building program to its highest level, Platinum.

More information

SODIUM SULPHITE BASED WATER TREATMENT PROGRAM FOR CLOSED CHILLED WATER SYSTEMS

SODIUM SULPHITE BASED WATER TREATMENT PROGRAM FOR CLOSED CHILLED WATER SYSTEMS SODIUM SULPHITE BASED WATER TREATMENT PROGRAM FOR CLOSED CHILLED WATER SYSTEMS Presented at ALBERTA Public Works, Supply & Services Property Management Operations Division Water Treatment Co-ordinators'

More information

Copyright 2004 and 2005 by The American Institute of Architects (AIA)

Copyright 2004 and 2005 by The American Institute of Architects (AIA) Page 232500-1 Copyright 2004 and 2005 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical

More information

Scale and Deposition are Often the First Problem Associated With Tower and Refrigeration Systems

Scale and Deposition are Often the First Problem Associated With Tower and Refrigeration Systems Scale and Deposition are Often the First Problem Associated With Tower and Refrigeration Systems Scale and Deposition Occur Due to Chemical and Mechanical Reasons Potential Causes Poor control of scale

More information

Obsolete. Description. Rhinor SD2/XD2 Type-H Follower Modules

Obsolete. Description. Rhinor SD2/XD2 Type-H Follower Modules Description See Figure. The Type-H follower module attaches onto the hydraulic section of the pump (). It is designed to force material out of straight-sided containers. Type-H follower plate modules are

More information

COMPREHENSIVE REPORT PRE CLEANING & PASSIVATION PROGRAMME OF ENTIRE RECIRCULATING COOLING WATER SYSTEM OF ECO PLANT BILAG INDUSTRIES LTD.

COMPREHENSIVE REPORT PRE CLEANING & PASSIVATION PROGRAMME OF ENTIRE RECIRCULATING COOLING WATER SYSTEM OF ECO PLANT BILAG INDUSTRIES LTD. A COMPREHENSIVE REPORT OF PRE CLEANING & PASSIVATION PROGRAMME OF ENTIRE RECIRCULATING COOLING WATER SYSTEM OF ECO PLANT AT BILAG INDUSTRIES LTD., VAPI ALTRET Performance Chemicals Guj. Pvt. Ltd. 12/2881,

More information

ABSTRACT. Key words: high silica, silica polymerization, scale formation, water scarcity, water reuse INTRODUCTION

ABSTRACT. Key words: high silica, silica polymerization, scale formation, water scarcity, water reuse INTRODUCTION Paper No. 5779 Managing a Cooling System to Prevent Silica Deposition Libardo Perez, Zahid Amjad, and Robert W. Zuhl The Lubrizol Corporation, Energy and Water 29400 Lakeland Blvd., Wickliffe, Ohio 44092

More information

TITLE: WATER TREATMENT PROGRAM FOR CHILLED WATER PLANTS THIS ADDENDUM IS FOR THE PURPOSE OF MAKING THE FOLLOWING CHANGES OR CLARIFICATIONS IN RED:

TITLE: WATER TREATMENT PROGRAM FOR CHILLED WATER PLANTS THIS ADDENDUM IS FOR THE PURPOSE OF MAKING THE FOLLOWING CHANGES OR CLARIFICATIONS IN RED: Procurement Department Bid Section Customer Center 1 st Floor, Room 002 21 W. Church Street Jacksonville, Florida 32202 May 17, 20 ADDENDUM NUMBER: ONE (1) TITLE: WATER TREATMENT PROGRAM FOR CHILLED WATER

More information

Recirculating Hot Water Systems

Recirculating Hot Water Systems Recirculating Hot Water Systems While copper pipe has long been used for the transmission of hot water, the service to which the corroded copper pipe in Kearney, MO was put is a comparatively new application.

More information

Western Regional Boiler Association

Western Regional Boiler Association Western Regional Boiler Association Tubesheet coating Tube-end ID coating Full-length tube coating Channel Head/Waterbox coating Flange sealing Coating Service And Circulating Water Piping Mechanical stress

More information

PERFORMANCE AND RESIDUAL MANAGEMENT ASSESSMENT OF 5 MGD MEMBRANE WATER PLANT. Presented by: Stephen P. Dorman, P.E.

PERFORMANCE AND RESIDUAL MANAGEMENT ASSESSMENT OF 5 MGD MEMBRANE WATER PLANT. Presented by: Stephen P. Dorman, P.E. PERFORMANCE AND RESIDUAL MANAGEMENT ASSESSMENT OF 5 MGD MEMBRANE WATER PLANT Presented by: Stephen P. Dorman, P.E. sdorman@ksaeng.com 1 Outline Background Assessment of: Clarification Filtration Residuals

More information

Hydrosol System Furnace Cooling Water Cleaning Case Study: North American Stainless

Hydrosol System Furnace Cooling Water Cleaning Case Study: North American Stainless Hydrosol System Furnace Cooling Water Cleaning Case Study: North American Stainless Prepared by: Shane M. Slack BSWE, MBA Hydrosol System, Inc. 4175 Karg Industrial Parkway Kent, Ohio 44240 shane@hydrosolsystem.com

More information

ADDITIVE DEPLETION: IMPACT ON USEABLE OIL LIFE AND EQUIPMENT WEAR

ADDITIVE DEPLETION: IMPACT ON USEABLE OIL LIFE AND EQUIPMENT WEAR ADDITIVE DEPLETION: IMPACT ON USEABLE OIL LIFE AND EQUIPMENT WEAR Abstract Pentair Additives are introduced into lubrication and hydraulic oils in order to minimize the rate of wear occurring in costly

More information

EVALUATION OF A CHEMICAL CLEANING FORMULATION FOR THE STEAM GENERATOR OF NUCLEAR POWER PLANTS

EVALUATION OF A CHEMICAL CLEANING FORMULATION FOR THE STEAM GENERATOR OF NUCLEAR POWER PLANTS EVALUATION OF A CHEMICAL CLEANING FORMULATION FOR THE STEAM GENERATOR OF NUCLEAR POWER PLANTS A.L.Rufus, H.Subramanian, V.S.Sathyaseelan, Padma S.Kumar, S.Veena B.Anupkumar, M.P.Srinivasan, S.Velmurugan

More information

The Application of Non-phosphorous AEC Program in Cooling Water Systems of Petrochemical Industry

The Application of Non-phosphorous AEC Program in Cooling Water Systems of Petrochemical Industry CORROSION SCIENCE AND TECHNOLOGY, Vol.7, No.1(2008), pp.16~21 The Application of Non-phosphorous AEC Program in Cooling Water Systems of Petrochemical Industry Li Dagang, Mike Hong, and He Gaorong Suite

More information

Energy and Water Savings

Energy and Water Savings Join the Green Team Since 1998 Energy and Water Savings 10%+ Energy Savings 20% Water Savings Fully Automated Skid-Mount Particle Precipitator Water Filtration System Full Service Control of - Total Dissolved

More information

Optimizing Steam and Cooling Systems for Reliability and Sustainability. Presented By: Kevin Emery

Optimizing Steam and Cooling Systems for Reliability and Sustainability. Presented By: Kevin Emery Optimizing Steam and Cooling Systems for Reliability and Sustainability Presented By: Kevin Emery Kevine@chemtreat.com 804-317-2381 Optimizing Steam and Cooling Systems for Reliability and Sustainability

More information

Water Quality Specification for Power Supplies

Water Quality Specification for Power Supplies Technical Note #6 Water Quality Specification for Power Supplies Introduction The cooling water for Alpha Scientific Power Supplies must meet certain minimum specifications in regard to quality and flow

More information

Schematic diagram of a cooling water system

Schematic diagram of a cooling water system Cooling Tower Water Treatment Cooled water is needed for, example, air conditioners, manufacturing processes or power generation. A cooling tower is an equipment used to reduce the temperature of a water

More information

Green FSRU for the future

Green FSRU for the future Green FSRU for the future Presentation at GREEN4SEA Athens April 6 th 2016 Dr. John Kokarakis Vice President Technology & Business Development, Africa, S. Europe Hellenic, Black Sea & Middle East Zone

More information

OPTIDOSE 1000 Traceable Polymer A Tool for Maintaining Maximum Heat Transfer

OPTIDOSE 1000 Traceable Polymer A Tool for Maintaining Maximum Heat Transfer OPTIDOSE 1000 Traceable Polymer A Tool for Maintaining Maximum Heat Transfer Description OPTIDOSE traceable polymer technology is a revolutionary method of tracking polymer levels in cooling water, boiler

More information

Water Chiller and Laser Engraver Installation For Coherent G-100/150 laser

Water Chiller and Laser Engraver Installation For Coherent G-100/150 laser Water Chiller and Laser Engraver Installation For Coherent G-100/150 laser SAFETY NOTICE: The Water Chiller has to be switched on before turning on the laser engraver. Please follow the instruction below

More information

ALBERTA INFRASTRUCTURE CORROSION RATE MONITORING PROGRAM

ALBERTA INFRASTRUCTURE CORROSION RATE MONITORING PROGRAM ALBERTA INFRASTRUCTURE CORROSION RATE MONITORING PROGRAM Presented at Alberta Infrastructure Property Management Water Treatment Co-ordinators' Meeting #37 Sam Livingston Fish Hatchery Calgary, Alberta

More information

ADDENDUM 2 TO REQUEST FOR PROPOSAL 673-FG UNLV FULL SERVICE WATER TREATMENT

ADDENDUM 2 TO REQUEST FOR PROPOSAL 673-FG UNLV FULL SERVICE WATER TREATMENT ADDENDUM 2 TO REQUEST FOR PROPOSAL 673-FG UNLV FULL SERVICE WATER TREATMENT University of Nevada, Las Vegas Purchasing Department 4505 Maryland Parkway Las Vegas, Nevada 89154-1033 (702) 895-3521 Date

More information

Energy Optimized Resource Recovery Project Presented By: Curtis Czarnecki, P.E.

Energy Optimized Resource Recovery Project Presented By: Curtis Czarnecki, P.E. Kenosha Wastewater Treatment Plant Energy Optimized Resource Recovery Project Presented By: Curtis Czarnecki, P.E. Kenosha Water Utility March 22, 2016 WWTP Service Area Overview Population: 110,000 Service

More information

OPERATIONAL UPDATE ON INNOVATIVE COOLING TOWER PRETREATMENT TECHNOLOGY

OPERATIONAL UPDATE ON INNOVATIVE COOLING TOWER PRETREATMENT TECHNOLOGY OPERATIONAL UPDATE ON INNOVATIVE COOLING TOWER PRETREATMENT TECHNOLOGY Presented By: Joel E. Bowdan III, P.E. PRESENTATION OUTLINE: Subject Introduction Amylin Project Background Cooling Tower Basics Typical

More information

Materials Selection and Quality Assurance in Capital Projects Materials Technology

Materials Selection and Quality Assurance in Capital Projects Materials Technology Materials Selection and Quality Assurance in Capital Projects Materials Technology Presented by Wilson Pascheto Wilson.Pascheto@xps.ca Presented at CMP, Sudbury, ON November 2015 Introduction - History

More information

Case Study 3M Corporate Headquarters 2014 Distributed by:

Case Study 3M Corporate Headquarters 2014 Distributed by: Industrial Water Division Case Study 3M Corporate Headquarters 2014 Distributed by: Introduction Creative Water Solutions LLC and 3M conducted a 2 year trial of treatment at their corporate campus cooling

More information

ROTATING CYLINDER ELECTRODE: CORROSION INHIBITOR EVALUATION

ROTATING CYLINDER ELECTRODE: CORROSION INHIBITOR EVALUATION ROTATING CYLINDER ELECTRODE: CORROSION INHIBITOR EVALUATION Cormetrics Job #: 12-234 Prepared for: XYZ Company Page 1 of 10 1. Introduction Two batch and two continuous corrosion inhibitors were submitted

More information

Corrosion Potential - Refinery Overhead Systems

Corrosion Potential - Refinery Overhead Systems Corrosion Potential - Refinery Overhead Systems Amit Patel Bartlesville, Oklahoma OLI Simulation Conference November 16-18, 2010 Whippany, NJ Corrosivity Amine Hydrochlorides Impact of overhead corrosion

More information

HEAVY INDUSTRY PLANT WASTEWATER TREATMENT, RECOVERY AND RECYCLE USING THREE MEMBRANE CONFIGURATIONS IN COMBINATION WITH AEROBIC TREATMENT A CASE STUDY

HEAVY INDUSTRY PLANT WASTEWATER TREATMENT, RECOVERY AND RECYCLE USING THREE MEMBRANE CONFIGURATIONS IN COMBINATION WITH AEROBIC TREATMENT A CASE STUDY HEAVY INDUSTRY PLANT WASTEWATER TREATMENT, RECOVERY AND RECYCLE USING THREE MEMBRANE CONFIGURATIONS IN COMBINATION WITH AEROBIC TREATMENT A CASE STUDY ABSTRACT Francis J. Brady Koch Membrane Systems, Inc.

More information

Well Water Quality Update and Next Steps. Public Works Commission Meeting April 17,

Well Water Quality Update and Next Steps. Public Works Commission Meeting April 17, Well Water Quality Update and Next Steps Public Works Commission Meeting April 17, 2017 1 Background The Water Treatment Plant (WTP) was taken off-line in February 2015 for maintenance rehab & upgrades

More information

Glycol Management Paper. By Niels Bogh

Glycol Management Paper. By Niels Bogh Glycol Management Paper By Niels Bogh Aqueous - Based Quench Fluid Control Introduction: -based polymer solutions are being used in an increasing amount in the metal industries for both safety and environmental

More information

Zero Liquid Discharge Cooling Tower Treatment at CSI

Zero Liquid Discharge Cooling Tower Treatment at CSI AIST 2007 Zero Liquid Discharge Cooling Tower Treatment at CSI Dan Duke & John Kubis Water & Enviro Tech Company, Mission Viejo CA Jeff Reed California Steel Industries, Fontana CA This technology is patent*

More information

The Cost of Improper Water Treatment

The Cost of Improper Water Treatment Technical Paper The Cost of Improper Water Treatment It's easy to underestimate the importance of your water treatment program, whether you manage it in-house or rely on an outside water treatment supplier.

More information

POREX Tubular Membrane Filter Modules For Metal Contaminated Wastewater Treatment & Reclamation

POREX Tubular Membrane Filter Modules For Metal Contaminated Wastewater Treatment & Reclamation POREX Tubular Membrane Filter Modules For Metal Contaminated Wastewater Treatment & Reclamation Background Industrial processes can often result in waste water contaminated with heavy metals (Hg, Pb, Zn,

More information

Evaluation of the C&K Coal Pit 431 Passive Treatment System, Glasgow, Cambria County

Evaluation of the C&K Coal Pit 431 Passive Treatment System, Glasgow, Cambria County Evaluation of the C&K Coal Pit 431 Passive Treatment System, Glasgow, Cambria County Technical report provided by Hedin Environmental through the Trout Unlimited AMD Technical Assistance Program TUTAG-09

More information

ROTATING CYLINDER ELECTRODE CORROSION INHIBITOR EVALUATION

ROTATING CYLINDER ELECTRODE CORROSION INHIBITOR EVALUATION XYZ COMPANY ROTATING CYLINDER ELECTRODE CORROSION INHIBITOR EVALUATION Report by: Frank Hornsby Job# 14-XXX Date: 2014 Cormetrics Ltd; #4-2280 39 th Avenue NE, Calgary, AB. T2E 6P7 Phone: 403-258-2853

More information

HIGH EFFICIENCY 0.5 & 0.25 MICRON COOLING WATER FILTRATION SYSTEM

HIGH EFFICIENCY 0.5 & 0.25 MICRON COOLING WATER FILTRATION SYSTEM HIGH EFFICIENCY 0.5 & 0.25 MICRON COOLING WATER FILTRATION SYSTEM THE HIGHEST QUALITY COMMERCIAL AND INDUSTRIAL WATER FILTRATION EQUIPMENT 28 APPLETON STREET HOLYOKE, MA 01040 Phone: 413/536-8186 Fax:

More information

AP1000 European 9. Auxiliary Systems Design Control Document

AP1000 European 9. Auxiliary Systems Design Control Document 9.2 Water Systems 9.2.1 Service Water System The service water system (SWS) supplies cooling water to remove heat from the nonsafety-related component cooling water system (CCS) heat exchangers in the

More information

An Introduction to Water Sampling and Testing of Water Systems

An Introduction to Water Sampling and Testing of Water Systems An Introduction to Water Sampling and Testing of Water Systems J. Paul Guyer, P.E., R.A. Paul Guyer is a registered civil engineer, mechanical engineer, fire protection engineer and architect with 35 years

More information

Gregory E. Choryhanna and Alan R. Daza, SEPROTECH SYSTEMS INC. Process Development Division Ottawa, Canada

Gregory E. Choryhanna and Alan R. Daza, SEPROTECH SYSTEMS INC. Process Development Division Ottawa, Canada SUCCESSFUL IMPLEMENTATION OF MEMBRANE TECHNOLOGY IN DYE ASTEATER RECYCLING Gregory E. Choryhanna and Alan R. Daza, SEPROTECH SYSTEMS INC. Process Development Division Ottawa, Canada ABSTRACT A pilot test

More information

Cooling Tower Water Management Plan. 901 Fifth Avenue

Cooling Tower Water Management Plan. 901 Fifth Avenue 2013 Cooling Tower Water Management Plan 901 Fifth Avenue Table of Contents I. INTRODUCTION II. GOAL III. SCOPE IV. RESPONSIBILITIES V. TIME PERIOD VI. PERFORMANCE METRIC VII. PROCEDURES AND STRATEGIES

More information

Wastewater Characterization. Tenaska Westmoreland Generating Station

Wastewater Characterization. Tenaska Westmoreland Generating Station Wastewater Characterization Tenaska Westmoreland Generating Station Issued December 20, 2011 Rev 0 Revised October 23, 2012 Rev 1 Revised November 8, 2012 Rev 2 Prepared by GEWPT: R. Henry Weed, P.E. 1

More information

1. Magnetic devices work best on water the have colloidal size particles present prior to being exposed to a magnetic field.

1. Magnetic devices work best on water the have colloidal size particles present prior to being exposed to a magnetic field. 1. PURPOSE OF TEST The use of catalytic and or magnetic water treatment for scale reduction/elimination has been going on for many years. Contact with professional water treatment dealers, engineers in

More information

SYMPOSIUM ON INDUSTRIAL APPLICATIONS OF GAS TURBINES

SYMPOSIUM ON INDUSTRIAL APPLICATIONS OF GAS TURBINES 20TH SYMPOSIUM ON INDUSTRIAL APPLICATIONS OF GAS TURBINES Inlet Fogging and Overspray Impact on Gas Turbine Life and Performance by Klaus Brun / Southwest Research Institute Rainer Kurz / Solar Turbines

More information

INTRODUCTION HEAT TRANSFER AND HYDROMX

INTRODUCTION HEAT TRANSFER AND HYDROMX WITH NANO THERMO TECHNOLOGY! INTRODUCTION TO HEAT TRANSFER AND HYDROMX Brought to you by Green Way Solutions, Inc., exclusive distributers of Hydromx in North America INDEX WHAT IS HYDROMX PAGE 2 WHAT

More information

Condensate Management Monitoring Condensate

Condensate Management Monitoring Condensate Condensate Management Monitoring Condensate Virginia Durham May 2008 Weyerhaeuser_October 2007-1 Outline Goals in condensate management Monitoring Purpose Sampling Testing Major Streams Contaminants Automatic

More information

OPTIDOSE 1000 Traceable Polymer A Tool for Maintaining Maximum Heat Transfer

OPTIDOSE 1000 Traceable Polymer A Tool for Maintaining Maximum Heat Transfer Technical Data Sheet OPTIDOSE 1000 Traceable Polymer A Tool for Maintaining Maximum Heat Transfer Description OPTIDOSE traceable polymer technology is a revolutionary method of tracking polymer levels

More information

Saturation Index -100 F

Saturation Index -100 F Case History Report Dolphin Nonchemical Device Cooling Tower Device Evaluated While this is our third case history report (Dolphin III), on the "Dolphin Pulsed Power non chemical device (NCD) for water

More information

Maintenance Program Guideline for Owners of Ammonia Plants

Maintenance Program Guideline for Owners of Ammonia Plants Maintenance Program Guideline for Owners of Ammonia Plants Contents Maintenance Program Guideline for Owners of Ammonia Plants... 0 a) Title Page, owner/operator, the plant location.... 4 b) Contents Page...

More information

Available from IPP: 3.2MW Cogeneration Plant. (4x 800KW Reciprocating Natural Gas Generators)

Available from IPP: 3.2MW Cogeneration Plant. (4x 800KW Reciprocating Natural Gas Generators) Available from IPP: 3.2MW Cogeneration Plant (4x 800KW Reciprocating Natural Gas Generators) IPP Plant Dept. Stock No. 600658, Equipment Stock No s 216310 216324 Prepared By: Ross Gale 1 About the Plant:

More information

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. FAS Welding and Solder Flange

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. FAS Welding and Solder Flange Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU FAS Welding and Solder Flange Please read these operating instructions carefully to ensure a safe operation and keep the

More information

PRODUCT PROGRAMMING GUIDELINES CHEMICAL GUIDELINES

PRODUCT PROGRAMMING GUIDELINES CHEMICAL GUIDELINES CHEMICAL GUIDELINES INDEX : BOILER treatment program - Oxygen scavengers - Multi purpose - Deposit controllers - Return line treatment - ph controller /phosphate COOLING treatment program - Scale inhibition

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION HVAC PIPES AND TUBES

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION HVAC PIPES AND TUBES SECTION 23 20 00 - HVAC PIPES AND TUBES PART 1 - GENERAL 1.1 SUMMARY: A. Section includes pipe and pipe fittings for: heating water, chilled water, steam and steam condensate, condenser water, glycol,

More information

Evaluation of Failed Contactor Chill Blocks Due to Corrosion / Erosion By Bruce G. Kelly P.E. 1 and David J. Darrah 2

Evaluation of Failed Contactor Chill Blocks Due to Corrosion / Erosion By Bruce G. Kelly P.E. 1 and David J. Darrah 2 IB 1156 Abstract Evaluation of Failed Contactor Chill Blocks Due to Corrosion / Erosion By Bruce G. Kelly P.E. 1 and David J. Darrah 2 "Evaluation of failed SCR cooling blocks due to corrosion/erosion."

More information

POTENTIAL ENERGY AND COST SAVINGS THROUGH PROPER TREATMENT OF HEATING AND COOLING SYSTEMS

POTENTIAL ENERGY AND COST SAVINGS THROUGH PROPER TREATMENT OF HEATING AND COOLING SYSTEMS POTENTIAL ENERGY AND COST SAVINGS THROUGH PROPER TREATMENT OF HEATING AND COOLING SYSTEMS A Webinar for Facility Managers and Operators at Institutional and Industrial Facilities October 16, 2018 Jeremy

More information

Technical Summary. 1. Purpose

Technical Summary. 1. Purpose 1. Purpose Technical Summary The purpose of this procurement is to establish a contract to provide mechanical and electrical plant installation works in the following areas on the ITER Site in Saint-Paul

More information

Training Program for Urea Engineers. Tailor Made to Your Wishes

Training Program for Urea Engineers. Tailor Made to Your Wishes Training Program for Urea Engineers Tailor Made to Your Wishes v6 Choose the Modules of Your Interest and Compose your Preferred Training Program ü Highly awarded by all previous participants ü Covering

More information

Guideline for In-Service Assessment of Ammonia Refrigeration Plants

Guideline for In-Service Assessment of Ammonia Refrigeration Plants Guideline for In-Service Assessment of Ammonia Refrigeration Plants This communication is intended to be used by plant owners and operators to provide guidance in preparation for an assessment of the plant

More information

TEMPER. In enclosed packaging and closed systems, TEMPER is stable and lasts long and is, in principle, unlimited.

TEMPER. In enclosed packaging and closed systems, TEMPER is stable and lasts long and is, in principle, unlimited. TEMPER is a ready-to-use heating carrier on a base of acetate and potassium formiate in a water solution, without glycol, and is non-toxic and non-polluting. It contains innovative corrosion inhibitors

More information

NORKOOL Industrial Coolants

NORKOOL Industrial Coolants NORKOOL Industrial Coolants The most trusted brand in the business The NORKOOL Advantage The NORKOOL product line is Dow s premium heat transfer fluid for gas compression engines and line heaters. the

More information

1. Scaling. H.O.: H-5/21, KRISHNA NAGAR, DELHI Tel.: , Fax:

1. Scaling. H.O.: H-5/21, KRISHNA NAGAR, DELHI Tel.: , Fax: Boiler Water Problems and Its Causes Water is the essential medium for steam generation. Conditioning it properly can increase the efficiency of boiler and as well as extend the boiler s life. Treating

More information

Dow Oil and Gas. NORKOOL Cleaner, Degreaser and Inhibitor 244 System Maintenance Solutions

Dow Oil and Gas. NORKOOL Cleaner, Degreaser and Inhibitor 244 System Maintenance Solutions Dow Oil and Gas NORKOOL Cleaner, Degreaser and Inhibitor 244 System Maintenance Solutions Solutions for Heat Transfer Applications from Dow Oil & Gas The family of heat transfer fluids, corrosion inhibitors,

More information

a comparative study of secondary glycol and direct expansion refrigeration systems

a comparative study of secondary glycol and direct expansion refrigeration systems a comparative study of secondary glycol and direct expansion refrigeration systems Second Nature Medium-Temperature secondary systems have been widely applied in commercial refrigeration since their introduction

More information

SECTION FIELD ERECTED INDUCED DRAFT COOLING TOWER

SECTION FIELD ERECTED INDUCED DRAFT COOLING TOWER PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the contract including general and supplementary conditions and specifications section apply to this section. B. Related Sections:

More information

SECTION HVAC WATER TREATMENT

SECTION HVAC WATER TREATMENT PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 25 00 HVAC WATER TREATMENT SPEC WRITER NOTE: 1. Delete between //-----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

Cooling tower efficiency U2 Eco-efficiency resources for the food processing industry

Cooling tower efficiency U2 Eco-efficiency resources for the food processing industry Cooling tower efficiency U2 Eco-efficiency resources for the food processing industry Cool savings Many food processors operate cooling towers to meet the cooling needs of the factory. Cooling towers supply

More information

Valve Nest Filter with Time Clock Control Installation and Operation Manual

Valve Nest Filter with Time Clock Control Installation and Operation Manual Valve Nest Filter with Time Clock Control Installation and Operation Manual Effective 5/24/12 Effective 5/24/12 Table of Contents Operating Data. 1 Pre-Installation Data... 2 Filter Parameters Installation

More information

Water Management Energy and Sustainability Sub Group November Meeting. Brian Boyd, Kate McMordie Stoughton, and Jordan Henderson November 20, 2013

Water Management Energy and Sustainability Sub Group November Meeting. Brian Boyd, Kate McMordie Stoughton, and Jordan Henderson November 20, 2013 Water Management Energy and Sustainability Sub Group November Meeting Brian Boyd, Kate McMordie Stoughton, and Jordan Henderson November 20, 2013 1 Agenda Implementation strategies for Federal Guiding

More information

Modular Oil & Gas Equipment Onshore & Offshore

Modular Oil & Gas Equipment Onshore & Offshore Modular Oil & Gas Equipment Onshore & Offshore Separators & Desalters AI Energy Solutions onshore and offshore oil process solutions offer innovative technologies packaged with global project management

More information

A. This Section includes exterior piping for vertical, direct-buried, ground-loop, heat-pump systems that operate between 23 and 104 deg F.

A. This Section includes exterior piping for vertical, direct-buried, ground-loop, heat-pump systems that operate between 23 and 104 deg F. SECTION 23 21 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Product Information Sheet

Product Information Sheet Product Information Sheet Solarliquid VT51 df -28 C Non Toxic anti-freeze for high temperatures installations Description y applications: VT51 df -28ºC is a transparent red liquid. It is safe to handle

More information

White Paper. Galvanized Pipe Failures in Dry Pipe Sprinkler Systems (April 2016) By Lucas Kirn, PE

White Paper. Galvanized Pipe Failures in Dry Pipe Sprinkler Systems (April 2016) By Lucas Kirn, PE White Paper Galvanized Pipe Failures in Dry Pipe Sprinkler Systems (April 2016) By Lucas Kirn, PE Original article published in Fire Protection Contractor Magazine in May 2016. V.1.0.1 Copyright 2016 Engineered

More information

This Technical Note is to notify you that Tecvalco has changed the brand of glycol in the CWT Heater. This change took affect in April 2016.

This Technical Note is to notify you that Tecvalco has changed the brand of glycol in the CWT Heater. This change took affect in April 2016. UTILITY, MUNICIPAL, AND WHOLESALE SUPPLY May 5, 2016 Technical Note: CWT-20160505-001 Dear Customer, This Technical Note is to notify you that Tecvalco has changed the brand of glycol in the CWT Heater.

More information

Watts Bar Nuclear Plant Unit 2 Completion Project

Watts Bar Nuclear Plant Unit 2 Completion Project Watts Bar Nuclear Plant Unit 2 Completion Project Ninth Quarterly Update to the Estimate to Complete May - July 2014 Published October 2014 Table of Contents Section 1 - Executive Summary... 3 Section

More information