Earthing in electrical network purpose, methods and measurement

Size: px
Start display at page:

Download "Earthing in electrical network purpose, methods and measurement"

Transcription

1 Earthing in electrical network purpose, methods and measurement Earth / Ground Conductive ground whose electrical potential at each point is set equal to zero, It is a conductor which provides a low impedance path to prevent hazardous voltages during abnormal and fault conditions Earthing in electrical network The main reason for doing earthing in electrical network is for the safety. When all metallic parts in electrical equipment s are grounded then if the insulation inside the equipment s fails there are no dangerous voltages present in the equipment case. If the live wire touches the grounded case then the circuit is effectively shorted and fuse will immediately blow. When the fuse is blown then the dangerous voltages are away. Purpose of Earthing 1. Safety for Human life / Building /Equipment To save human life from danger of electrical shock or death by blowing a fuse i.e. To provide an alternative path for the fault current to flow so that it will not endanger the user To protect buildings, machinery & appliances under fault conditions. To ensure that all exposed conductive parts do not reach a dangerous potential. To provide safe path to dissipate lightning and short circuit currents. To provide stable platform for operation of sensitive electronic equipment s i.e. to maintain the voltage at any part of an electrical system at a known value so as to prevent over current or excessive voltage on the appliances or equipment. 2. Over voltage protection Lightning, line surges or unintentional contact with higher voltage lines can cause dangerously high voltages to the electrical distribution system. Earthing provides an alternative path around the electrical system to minimize damages in the System. 3. Voltage stabilization There are many sources of electricity. Every transformer can be considered a separate source. If there were not a common reference point for all these voltage sources it would be extremely difficult to calculate their relationships to each other. The earth is the most omnipresent conductive surface, and so it was adopted in the very beginnings of electrical distribution systems as a nearly universal standard for all electric systems.

2 Conventional methods of earthing 1. Plate type Earthing Generally for plate type earthing normal Practice is to use Cast iron plate of size 600 mm x600 mm x12 mm. OR Galvanized iron plate of size 600 mm x600 mm x6 mm. OR Copper plate of size 600 mm * 600 mm * 3.15 mm Plate burred at the depth of 8 feet in the vertical position and GI strip of size 50 mmx6 mm bolted with the plate is brought up to the ground level. These types of earth pit are generally filled with alternate layer of charcoal & salt up to 4 feet from the bottom of the pit. 2. Pipe type Earthing For Pipe type earthing normal practice is to use GI pipe [C-class] of 75 mm diameter, 10 feet long welded with 75 mm diameter GI flange having 6 numbers of holes for the connection of earth wires and inserted in ground by auger method. These types of earth pit are generally filled with alternate layer of charcoal & salt or earth reactivation compound.

3 3. Copper coated solid rod earthing Copper coated solid rod of diameter 17mm, 19mm, 20mm,25mm Low carbon steel rod bonded with copper for contact surface and corrosion resistance Stainless steel clamp to connect flat or cable Factors affecting on Earth resistivity 1. Soil Resistivity It is the resistance of soil to the passage of electric current. The earth resistance value (ohmic value) of an earth pit depends on soil resistivity. It is the resistance of the soil to the passage of electric current. It varies from soil to soil. It depends on the physical composition of the soil, moisture, dissolved salts, grain size and distribution, seasonal variation, current magnitude etc. In depends on the composition of soil, Moisture content, Dissolved salts, grain size and its distribution, seasonal variation, current magnitude. Importance of soil resistivity: To choose the location and type of earth electrode To define the electrical specification of earth electrode and earth network Optimize the construction cost for the earth electrodes and earth networks ( required earth resistance is obtained more quickly )

4 Soil resistivity depends on: 1. Soil composition 2. Moisture content, and 3. Temperature Formula to calculate soil resistivity: ρ (Rho) ρ = 2 X π X A X R Ω m ρ = average soil resistivity, A = dist between electrodes in meter, R = Measured resistance in ohms from the earth tester 2. Soil Condition Different soil conditions give different soil resistivity. Most of the soils are very poor conductors of electricity when they are completely dry. Soil resistivity is measured in ohm-meters or ohm-cm. Soil plays a significant role in determining the performance of electrode. Soil with low resistivity is highly corrosive. If soil is dry then soil resistivity value will be very high. If soil resistivity is high, earth resistance of electrode will also be high. 3. Moisture Moisture has a great influence on resistivity value of soil. The resistivity of a soil can be determined by the quantity of water held by the soil and resistivity of the water itself. Conduction of electricity in soil is through water. The resistance drops quickly to a more or less steady minimum value of about 15% moisture. And further increase of moisture level in soil will have little effect on soil resistivity. In many locations water table goes down in dry weather conditions. Therefore, it is essential to pour water in and around the earth pit to maintain moisture in dry weather conditions. Moisture significantly influences soil resistivity.

5 4. Dissolved salts Pure water is poor conductor of electricity. Resistivity of soil depends on resistivity of water which in turn depends on the amount and nature of salts dissolved in it. Small quantity of salts in water reduces soil resistivity by 80%. Common salt is most effective in improving conductivity of soil. But it corrodes metal and hence discouraged. 5. Climate Condition Increase or decrease of moisture content determines the increase or decrease of soil resistivity. Thus in dry whether resistivity will be very high and in monsoon months the resistivity will be low. 6. Physical Composition Different soil composition gives different average resistivity. Based on the type of soil, the resistivity of clay soil may be in the range of ohm-meter, whereas for rocky or gravel soils, the same may be well above 1000 ohm-meter. 7. Location of Earth Pit The location also contributes to resistivity to a great extent. In a sloping landscape, or in a land with made up of soil, or areas which are hilly, rocky or sandy, water runs off and in dry weather conditions water table goes down very fast. In such situation back fill compound will not be able to attract moisture, as the soil around the pit would be dry. The earth pits located in such areas must be watered at frequent intervals, particularly during dry weather conditions. Though back fill compound retains moisture under normal conditions, it gives off moisture during dry weather to the dry soil around the electrode, and in the process loses moisture over a period of time. Therefore, choose a site that is naturally not well drained. 8. Effect of current magnitude Soil resistivity in the vicinity of ground electrode may be affected by current flowing from the electrode into the surrounding soil. The thermal characteristics and the moisture content of the soil will determine if a current of a given magnitude and duration will cause significant drying and thus increase the effect of soil resistivity.

6 9. Area Available Single electrode rod or strip or plate will not achieve the desired resistance alone. If a number of electrodes could be installed and interconnected the desired resistance could be achieved. The distance between the electrodes must be equal to the driven depth to avoid overlapping of area of influence. Each electrode, therefore, must be outside the resistance area of the other. 10. Obstructions The soil may look good on the surface, but there may be obstructions below a few feet like virgin rock. In that event resistivity will be affected. Obstructions like concrete structure near about the pits will affect resistivity. If the earth pits are close by, the resistance value will be high. Components of earth system Earth conductor Connection between the earth conductor and earth electrode Earth electrode

7 Spacing between earth electrodes There must be proper spacing between ground electrodes to reduce or eliminate their spheres of influence (Minimum spacing shall be > Length of the electrode). Without proper spacing, their sphere of influence will intersect and resistance will not lowered. Earth Resistance: The earth resistance of an electrode is made up of resistance of metal, contact resistance between the electrode and the soil, resistance of soil from the electrode surface in the, geometry setup for the flow of current from the electrode to the earth. Variables that affects Earth resistance: 1. Length / depth of the Copper coated earth rod Soil is not consistent in its resistivity and can be highly unpredictable, it is critical when installing earth electrode that it is below frost line. This is done so that the resistance to earth will not be greatly influenced by the freezing of the surrounding soil. By increasing the length of the electrode the resistance will be reduced additionally by 40 %

8 In areas where deeper rods are physically impossible alternate methods including earth enhancing mineral compounds are recommended 2. Diameter of the ground rod Increasing the Diameter of the rod has very little effect in lowering the resistance, By doubling the diameter of the rod, Resistance will decrease only by 10 % 3. Number of earth electrodes In this method multiple earth electrodes are used and connected in parallel., This method is effective only if the spacing between the electrode is depth of the rod., Without proper spacing, their sphere of influence will intersect and resistance will not lowered Method adapted to measure earth resistance value Fall-of-Potential Measurement The Fall-of-Potential test method is used to measure the ability of an earth ground system or an individual electrode to dissipate energy from a site. How Does the Fall-of-Potential Test Work? First, the earth electrode of interest must be disconnected from its connection to the site. Second, the tester is connected to the earth electrode. Then, for the 3-pole Fall-of-Potential test, two earth stakes are placed in the soil in a direct line away from the earth electrode. Normally, spacing of 20 meters (65 feet) is sufficient. A known current is generated by the earth tester between the outer stake (auxiliary earth stake) and the earth electrode, while the drop in voltage potential is measured between the inner earth stake and the earth electrode. Using Ohm's Law (V = IR), the tester automatically calculates the resistance of the earth electrode. Connect the ground tester as shown in the picture. Press START and read out the RE (resistance) value. This is the actual value of the ground electrode under test. If this ground electrode is in parallel or series with other ground rods, the RE value is the total value of all resistances.

9 How Do You Place the Stakes? To achieve the highest degree of accuracy when performing a 3 pole ground resistance test, it is essential that the probe is placed outside the sphere of influence of the ground electrode under test and the auxiliary earth. If you do not get outside the sphere of influence, the effective areas of resistance will overlap and invalidate any measurements that you are taking. The table is a Depth of the ground electrode guide for appropriately setting the probe (inner stake) and auxiliary ground (outer stake). Distance to the inner stake Distance to the outer stake 2 m 15 m 25 m 3 m 20 m 30 m 6 m 25 m 40 m 10 m 30 m 50 m To test the accuracy of the results and to ensure that the ground stakes are outside the spheres of influence, reposition the inner stake (probe) 1 meter (3 feet) in either direction and take a fresh measurement. If there is a significant change in the reading (30 %), you need to increase the distance between the ground rod under test, the inner stake (probe) and the outer stake (auxiliary ground) until the measured values remain fairly constant when repositioning the inner stake (probe). For further information please do call us.. Also we request you to kindly share your valuable comments, suggestions and feedback to improve us

SABO EARTHING SOLUTION

SABO EARTHING SOLUTION SABO SABO EARTHING SOLUTION The installation and maintenance of an effective low resistance earthing system is essential due to the following- - Efficiently dissipate heavy fault currents and electrical

More information

THE OFFICIAL TRADE JOURNAL OF BICSI

THE OFFICIAL TRADE JOURNAL OF BICSI ICT TODAY THE OFFICIAL TRADE JOURNAL OF BICSI January/February 2017 PLUS + + Information Security and ESS in the Age of the Internet of Things + Grounding System Design and Testing for Critical Facilities

More information

Grounding Principles. The need to ground! Definitions. Introduction. Grounding Codes and Standards. 2 Ph:

Grounding Principles. The need to ground! Definitions. Introduction. Grounding Codes and Standards. 2 Ph: Introduction Grounding and bonding are an integral part of any modern electrical protection system design. An effective, low-impedance ground system is a key element of this system. It is crucial in ensuring

More information

Journal of American Science 2014;10(7) A. H. Almasoud, Mosallam Al-Solami

Journal of American Science 2014;10(7)  A. H. Almasoud, Mosallam Al-Solami Jeddah Soil Resistivity and Grounding Resistance A. H. Almasoud, Mosallam Al-Solami Electrical and Computer Engineering Dept., King Abdulaziz University, Jeddah, Saudi Arabia amasoud@kau.edu.sa Abstract:

More information

4. POINTS ON SWITCH AND CIRCUIT BREAKER PLATFORM GROUNDING.

4. POINTS ON SWITCH AND CIRCUIT BREAKER PLATFORM GROUNDING. 4. POINTS ON SWITCH AND CIRCUIT BREAKER PLATFORM GROUNDING. 4.1 All equipment (i.e., switches, breakers, control cabinets, etc.) inside switchyards or substations which require operations by workers must

More information

Facility and Equipment Grounding

Facility and Equipment Grounding Facility and Equipment Grounding - 2005 Course: PQE203 Presented by: PowerCET Corporation 3350 Scott Blvd. Bldg. 55 Unit 1 Santa Clara, CA 95054 408/988-1346 Fax 408/988-4869 E-mail: training@powercet.com

More information

Grounding & Bounding. 1. Bonded Connected to establish electrical continuity and conductivity.

Grounding & Bounding. 1. Bonded Connected to establish electrical continuity and conductivity. & Bounding Article 100 Definitions 1. Bonded Connected to establish electrical continuity and conductivity. 2. Raceway fittings bonds sections of raceway Bonding jumper bonds receptacles to boxes Threaded

More information

SECTION FACILITY LIGHTNING PROTECTION

SECTION FACILITY LIGHTNING PROTECTION PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 41 00 FACILITY LIGHTNING PROTECTION SPEC WRITER NOTE: Delete between //----//if not applicable to project. Also delete any other item or paragraph not applicable

More information

TESTING PTE EARTHING

TESTING PTE EARTHING 1 SCOPE This section of the Power Systems Live Working Manual details the procedures to be followed to achieve Safety from the System when carrying out examination, testing and remedial work on PTE (Pole

More information

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL). 16450 GROUNDING ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 26 An optional keynote to the

More information

Lightning Protection and Trees

Lightning Protection and Trees Lightning Protection and Trees By Ben Fuest INTRODUCTION This research was established for the purpose of developing a better understanding of lightning protection systems specifically designed to be fitted

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract apply to this Section. 1.2 SUMMARY A. This Section

More information

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS SECTION 26 05 26 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide labor, materials, equipment, and incidentals as shown, specified, and

More information

DESIGNING FOR A LOW RESISTANCE EARTH INTERFACE (GROUNDING)

DESIGNING FOR A LOW RESISTANCE EARTH INTERFACE (GROUNDING) Newage Energy Holdings DESIGNING FOR A LOW RESISTANCE EARTH INTERFACE (GROUNDING) http://newage-energy.net http://newage-energy.com Newage Energy Page 1 Introduction Grounding (or earthing) is the art

More information

STANDARD SPECIFICATION EARTH GROUNDING Section (Straight Shaft Model)

STANDARD SPECIFICATION EARTH GROUNDING Section (Straight Shaft Model) STANDARD SPECIFICATION EARTH GROUNDING Section 16000 (Straight Shaft Model) PART 1 - GENERAL 1.01 DESCRIPTION A. Related Work Specified Elsewhere: 1. Electrical General Provisions ( Section xxx) 2. Basic

More information

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING 2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING E3305.3: now reads The space equal to the width and depth of the panelboard and extending

More information

SERVICES CHAPTER 35. wire. For all other installations, the rating of the ungrounded conductors shall be not less than 60 amperes.

SERVICES CHAPTER 35. wire. For all other installations, the rating of the ungrounded conductors shall be not less than 60 amperes. CHAPTER 35 SERVICES SECTION E3501 GENERAL SERVICES E3501.1 Scope. This chapter covers service conductors and equipment for the control and protection of services and their installation requirements. E3501.2

More information

Elpress system for deep earthing

Elpress system for deep earthing Elpress system for deep earthing Principal design The Elpress deep earthing concept is a system without extra connection points. The earthing electrode is a copper wire which is pulled down by means of

More information

An Overview of Earthing

An Overview of Earthing 2018 Earthing An Overview of Earthing Gary Blackshaw, Global Business Development Manager Founded by William Joseph Furse Originally as a Steeplejack company Relocated to Traffic Street More emphasis on

More information

CHAPTER 13 GROUNDING AND BONDING

CHAPTER 13 GROUNDING AND BONDING GROUNDING AND BONDING CHAPTER 13 GROUNDING AND BONDING Grounding and bonding must be in accordance with Article 250 of the National Electrical Code (NEC). Bonding is defined in the NEC as the permanent

More information

Ensure no person makes contact with the steel pole streetlight or temporary earth electrode while the testing procedures are being undertaken.

Ensure no person makes contact with the steel pole streetlight or temporary earth electrode while the testing procedures are being undertaken. NOTE: SAFETY: Tests must be carried out after the installation, alteration or repair and before putting back to service. At all times maintain suitable clearance to all other electrical equipment and verify

More information

G R O U N D I N G S Y S T E M S

G R O U N D I N G S Y S T E M S GROUNDING SYSTEMS P R O D U C T S & S E R V I C E S 2 0 1 6 GROUNDING SYSTEMS GENER FETURES GROUNDING EECTRODES EQUIPOTENTI CONNECTION / CHECK-SWITCHING BRIDGES REGISTRTION CHMBERS UMINOTHERMIC WEDING

More information

SECTION LIGHTNING PROTECTION SYSTEM

SECTION LIGHTNING PROTECTION SYSTEM SECTION 16670 - LIGHTNING PROTECTION SYSTEM PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

A. Lemon juice makes the water more conducting as it conducts electricity. But when the lemon juice is not added to it, the conductivity will be low.

A. Lemon juice makes the water more conducting as it conducts electricity. But when the lemon juice is not added to it, the conductivity will be low. Chapter 14-Chemical Effects of Electric Current Topicwise Assignment Chemical Effects of Electric Current Do Liquids Conduct Electricity? A. 1. Yes 2. Yes 3. Lemon juice is a good conductor. 4. The ends

More information

Iron is found in an oxidized state and is mined from the ground as an iron ore.

Iron is found in an oxidized state and is mined from the ground as an iron ore. Iron is found in an oxidized state and is mined from the ground as an iron ore. Energy is used to convert this iron oxide into steel. Ore is loaded into a blast furnace where heat energy removes the oxygen

More information

PART 7 Technical Specification for Overhead and Underground Service Connection works for the Year

PART 7 Technical Specification for Overhead and Underground Service Connection works for the Year PART 7 Technical Specification for Overhead and Underground Service Connection works for the Year 2016-17 Technical Specification for Overhead and Underground Service Connection works for the Year 2016-17

More information

SECTION PART 1 GENERAL

SECTION PART 1 GENERAL SECTION 16060 GROUNDING AND BONDING PART 1 GENERAL 1.1 SUMMARY A. Section Includes: Grounding of electrical systems and equipment and basic requirements for ground for equipment, circuits, and systems.

More information

Part 1: On-land pipelines

Part 1: On-land pipelines Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO 15589-1 Second edition 2015-03-01 Petroleum, petrochemical and natural gas industries Cathodic protection of pipeline systems Part 1: On-land pipelines

More information

APPLICATION NOTE 6. Use of Decouplers for AC Voltage Mitigation. PART 2: DESIGN CONSIDERATIONS

APPLICATION NOTE 6. Use of Decouplers for AC Voltage Mitigation.   PART 2: DESIGN CONSIDERATIONS APPLICATION NOTE 6 Use of Decouplers for AC Voltage Mitigation Introduction AC voltage mitigation is primarily of concern when cathodically protected pipelines are adjacent to electric power distribution

More information

Session Two: SANS 10313:2010 & IEC Part 2 & 3 Explained

Session Two: SANS 10313:2010 & IEC Part 2 & 3 Explained Session Two: SANS 10313:2010 & IEC 62305 Part 2 & 3 Explained T.J. Manas Managing Director Pontins (Pty) Ltd SANS Code 10313:2010 Protection against Lightning Physical Damage and Life Hazard The South

More information

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING SECTION 16060 PART 1 GENERAL 1.01 DESCRIPTION A. Section includes requirements for an electrical grounding system, including electrodes, grounding rods, connectors, insulators, equipment grounding and

More information

INTEGRATED GROUNDING SYSTEM OF WIND-FARMS FOR LIGHTNING AND FAULT PROTECTION

INTEGRATED GROUNDING SYSTEM OF WIND-FARMS FOR LIGHTNING AND FAULT PROTECTION INTEGATED GOUNDING SYSTEM OF WIND-FAMS FO LIGHTNING AND FAULT POTECTION M.I.Lorentzou, N.D.Hatziargyriou G.A.Manos, T.Sietis, National Technical University of Athens, Greece Elliniki Technodomiki Energiaki

More information

Ontario ENGINEERING STANDARD SPECIFICATION 1/10 REV. ELECTRICAL DISTRIBUTION HIGH VOLTAGE SUBSTATION GROUNDING AND BONDING. Approved by.

Ontario ENGINEERING STANDARD SPECIFICATION 1/10 REV. ELECTRICAL DISTRIBUTION HIGH VOLTAGE SUBSTATION GROUNDING AND BONDING. Approved by. /0 Rev Description Revision by Approved by Issue Date YYYY/MM/DD New Format Replaces 5322-0.0. T.C. 206/02/09 T.C. 206/03/02 206/03/02 2/0.0 PURPOSE This specification describes the minimum requirements

More information

EXTERNAL GROUNDING (EARTHING)

EXTERNAL GROUNDING (EARTHING) EXTERNAL GROUNDING (EARTHING) CHAPTER 4 This chapter provides requirements and guidelines for designing and installing the external grounding (earthing) electrode system at a communications site. This

More information

Grounding Enhancement Material Using Bentonite

Grounding Enhancement Material Using Bentonite Grounding Enhancement Material Using Bentonite N. H. Shuhada, N. A. Ahmad * and Z. Adzis Institute of High Voltage and High Current, Faculty of Electrical Engineering, Universiti Teknologi Malaysia, 81310

More information

VSS-2 ½ D HIGH HEAD SUMP PUMP FREE STANDING

VSS-2 ½ D HIGH HEAD SUMP PUMP FREE STANDING Flows to 200 GPM. TDH to 95 Feet at 1750 RPM Free Standing or Guide Rail Design. Available in Standard Submersible or Explosion Proof Design. Provided with 25 feet of submersible motor power cable. Cast

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Updated format, division title, and removed references to other sections. - mgl44 A. Summary This section contains design criteria for the

More information

EARTHING & LIGHTING PROTECTION

EARTHING & LIGHTING PROTECTION EARTHING & LIGHTING PROTECTION RELIABLE CONNECTION SOLUTIONS THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES Introduction Legrand Seico, an ISO certified and approved vendor in

More information

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING SECTION 16060 GROUNDING AND BONDING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 1.1. REFERENCE STANDARDS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification

More information

Ufer grounding. Ufer Ground - Wikipedia, the free encyclopedia https://en.wikipedia.org/wiki/ufer_ground

Ufer grounding. Ufer Ground - Wikipedia, the free encyclopedia https://en.wikipedia.org/wiki/ufer_ground Ufer grounding "Concrete Encased Electrode Grounding" by the NEC ( National Electrical Code ) 250-52 (A)(3) in 2005, is in many states the primary source of "Earth" ground in "all" remodel and new building

More information

Improvement of Substation Earthing

Improvement of Substation Earthing International Journal of Engineering and Advanced Technology (IJEAT) Improvement of Substation Earthing Mohammad Ali Adelian Abstract Designing a proper substation grounding system is quite complicated.

More information

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

GB Translated English of Chinese Standard: GB NATIONAL STANDARD OF THE PEOPLE S REPUBLIC OF CHINA

GB Translated English of Chinese Standard: GB NATIONAL STANDARD OF THE PEOPLE S REPUBLIC OF CHINA Translated English of Chinese Standard: GB50169-2016 www.chinesestandard.net Buy True-PDF Auto-delivery. Sales@ChineseStandard.net GB NATIONAL STANDARD OF THE PEOPLE S REPUBLIC OF CHINA UDC P GB 50169-2016

More information

GN7 Amendment 3-5 Agricultural and horticultural premises

GN7 Amendment 3-5 Agricultural and horticultural premises GN7 Amendment 3-5 Agricultural and horticultural premises 5.1Introduction Amendment No. 3 to the 17th Edition Sect 705 There are no significant changes introduced in Section 705by Amendment No. 3 to the

More information

CITY OF BRANSON MUNICIPLE CODE Chapter 18 BUILDINGS AND BUILDING REGULATIONS ARTICLE V. RESIDENTIAL CODE

CITY OF BRANSON MUNICIPLE CODE Chapter 18 BUILDINGS AND BUILDING REGULATIONS ARTICLE V. RESIDENTIAL CODE CITY OF BRANSON MUNICIPLE CODE Chapter 18 BUILDINGS AND BUILDING REGULATIONS ARTICLE V. RESIDENTIAL CODE Sec. 18-103. - International Residential Code. (a) Adopted. The International Residential Code,

More information

Bulletin Grounding and bonding of solar photovoltaic systems Rules , , , and

Bulletin Grounding and bonding of solar photovoltaic systems Rules , , , and Bulletin 64-2-0 Grounding and bonding of solar photovoltaic systems Rules 64-064, 64-066, 64-068, 64-070 and 64-222 Scope (1) Introduction (2) Grounding of solar photovoltaic system output, ac grounding

More information

COMPANY: Aplicaciones Tecnológicas, S.A.

COMPANY: Aplicaciones Tecnológicas, S.A. COMPANY: Aplicaciones Tecnológicas, S.A. AREA: Lightning Protection PRODUCT: CONDUCTIVER PLUS REFERENCE: AT 10L AT-10L CONDUCTIVER PLUS 1 / 12 AT-10L CONDUCTIVER PLUS CONDUCTIVER PLUS is a non-corrosive

More information

Practical Checklists of Best Practices Frank Donovan, W3LPL

Practical Checklists of Best Practices Frank Donovan, W3LPL Design, Construction and Maintenance of Antennas and Towers for Storm Survival and Long Term Reliability Practical Checklists of Best Practices Frank Donovan, W3LPL Typical A Typical Guyed Guyed Tower

More information

Substation Grounding. Presented by: Bruce Kayser, PE Assisted by Danny Seele

Substation Grounding. Presented by: Bruce Kayser, PE Assisted by Danny Seele Substation Grounding Presented by: Bruce Kayser, PE 785-633-5756 Assisted by Danny Seele Introduction Bruce Kayser, PE BSEE from KSU in 1989 Licensed Professional Engineer in KS Employed by ElectriComm,

More information

PARTICULAR SPECIFICATION E11: GENERAL ELECTRICAL EARTHING AND LIGHTNING PROTECTION

PARTICULAR SPECIFICATION E11: GENERAL ELECTRICAL EARTHING AND LIGHTNING PROTECTION E11 : General Electrical Earthing and LIGHTNING Protection PARTICULAR SPECIFICATION E11: GENERAL ELECTRICAL EARTHING AND LIGHTNING PROTECTION 1 2009-05-12 Review of Mechanical / Electrical and Control

More information

SECTION EARTHING AND EARTH FAULT PROTECTION

SECTION EARTHING AND EARTH FAULT PROTECTION SECTION 16660 PART 1 - GENERAL 1.01 DESCRIPTION A. The work to be performed includes, but is not necessarily limited to, all work involved with the construction and assembly of a complete electrical earthing

More information

STANDARDIZED STRUCTURES

STANDARDIZED STRUCTURES Q, QH & QL TOWERS 16.1 Q, QH, and QL Towers General Description The series includes three and four leg angle towers, which are suited for a variety of antenna mounting positions and load conditions. The

More information

OVERHEAD SERVICES - SECONDARY

OVERHEAD SERVICES - SECONDARY OVERHEAD SERVICES - SECONDARY Contents - Overhead Services... O-1 General Requirements for Overhead Service... O-2 Names of Parts for Overhead Service... O-3 Service Attachment on an Unguyed Service Mast...

More information

SECTION 24 GROUNDING SYSTEMS

SECTION 24 GROUNDING SYSTEMS Page 1 of 50 Source : Standard Handbook for Electrical Engineers, Fifteenth Edition 24_1 SECTION 24 GROUNDING SYSTEMS David R. Stockin Manager of Engineering, E&S Grounding Solutions Michael A. Esparza

More information

STABILIZATION OF SOIL RESISTANCE IN NEW INSTALLATION IN THE COASTAL SOIL IN NIGER DELTA

STABILIZATION OF SOIL RESISTANCE IN NEW INSTALLATION IN THE COASTAL SOIL IN NIGER DELTA STABILIZATION OF SOIL RESISTANCE IN NEW INSTALLATION IN THE COASTAL SOIL IN NIGER DELTA John Tarilanyo Afa Department of Electrical/Electronic Engineering, Niger Delta University, Wilberforce Island, Bayelsa

More information

Tender No.:- RITES/CO/B&A/EE/CUK- Gulbarga/External/E-2/2012.

Tender No.:- RITES/CO/B&A/EE/CUK- Gulbarga/External/E-2/2012. Amendment No. 1. Sub. : Tender: Supply, Erection, Testing & Commissioning of 11kV/440 V substation, Transformers, DG Sets, HT/ LT panels, HT/LT Cables, Street Lighting etc at University Campus at Khadaganchki

More information

Lightning Protection Practice for Large-Extended Photovoltaic Installations

Lightning Protection Practice for Large-Extended Photovoltaic Installations 202 International Conference on ightning Protection (ICP), Vienna, Austria ightning Protection Practice for arge-extended Photovoltaic Installations Dr. Nikolaos Kokkinos Research and Development Department

More information

Water Quality Specification for Power Supplies

Water Quality Specification for Power Supplies Technical Note #6 Water Quality Specification for Power Supplies Introduction The cooling water for Alpha Scientific Power Supplies must meet certain minimum specifications in regard to quality and flow

More information

Refining Corrosion Technologist NACE-RCT-001

Refining Corrosion Technologist NACE-RCT-001 Refining Corrosion Technologist NACE-RCT-001 NACE Cathodic Protection Specialist (CP 4) Essay Exam Exam Preparation Guide March 2018 Copyright 2016 by NACE International Institute. All rights reserved.

More information

SECTION GROUNDING

SECTION GROUNDING SECTION 16450 GROUNDING PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies general grounding and bonding requirements of electrical and telecommunication installations for personnel safety, equipment

More information

Galvanic Anodes Period 3 Intermediate Corrosion Course 2017

Galvanic Anodes Period 3 Intermediate Corrosion Course 2017 Galvanic Anodes Period 3 Intermediate Corrosion Course 2017 February 21-23, 2017 Eric Langelund Piping & Corrosion Specialties, Inc. 1 Overview Definitions and Terminology Galvanic Anodes An Overview Magnesium

More information

Petroleum Production and Disposal Facility Static and Lightning Mitigation

Petroleum Production and Disposal Facility Static and Lightning Mitigation Overview Petroleum Production and Disposal Facility Static and Lightning Mitigation Over the years, there have been an inordinately high number of ignitions caused by lightning and static at petroleum

More information

ROOF OWNER'S OPERATION AND MAINTENANCE MANUAL

ROOF OWNER'S OPERATION AND MAINTENANCE MANUAL ROOF OWNER'S OPERATION AND MAINTENANCE MANUAL Table of Contents Section Title Page Section 1.0 General Maintenance Statement 2 Section 2.0 Safety 2 Section 3.0 Inspections 2-4 Section 4.0 Repairs 4 Section

More information

Corrosion in Reinforced Concrete

Corrosion in Reinforced Concrete Corrosion in Reinforced Concrete Chris Atkins CED Working Day What is concrete? 1. Cement Clay and limestone heated in a furnace to drive off water, some can be replaced with slag / pfa 2. Crushed Rock

More information

A. This Section includes the following sump pumps and accessories, inside the building, for building storm drainage systems:

A. This Section includes the following sump pumps and accessories, inside the building, for building storm drainage systems: SECTION 221429 - SUMP PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

a: potential difference before direct current is applied b: potential difference after the application of current

a: potential difference before direct current is applied b: potential difference after the application of current CATHODIC PROTECTION Cathodic protection is a proven corrosion control method for protection of underground and undersea metallic structures, such as oil and gas pipelines, cables, utility lines and structural

More information

USER MANUAL DIGITAL CORROSION TESTER PROFESSIONAL MODEL

USER MANUAL DIGITAL CORROSION TESTER PROFESSIONAL MODEL USER MANUAL DIGITAL CORROSION TESTER PROFESSIONAL MODEL USER MANUAL SEAGUARD DIGITAL CORROSION TESTER PROFESSIONAL MODEL 2017 Canada Metal (Pacific) Ltd. All rights reserved. The information contained

More information

Substation Design Volume X

Substation Design Volume X PDHonline Course E477 (4 PDH) Substation Design Volume X Grounding Instructor: Lee Layton, P.E 2015 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org

More information

Wiring Investigation, for Stray Voltage MPSC U17897 Szymanski Farm 1375 Argyle Rd. Snover, MI

Wiring Investigation, for Stray Voltage MPSC U17897 Szymanski Farm 1375 Argyle Rd. Snover, MI Wiring Investigation, for Stray Voltage MPSC U17897 Szymanski Farm 1375 Argyle Rd. Snover, MI Prepared by Brian Prokuda, P.E.* Hartland, MI www.kpspq.com December 3, 2015 *Registered Engineer in Michigan

More information

Materials of Engineering ENGR 151 CORROSION ELECTRICAL PROPERTIES

Materials of Engineering ENGR 151 CORROSION ELECTRICAL PROPERTIES Materials of Engineering ENGR 151 CORROSION ELECTRICAL PROPERTIES more anodic (active) more cathodic (inert) GALVANIC SERIES Ranking of the reactivity of metals/alloys in seawater Platinum Gold Graphite

More information

Galvanic and Stray Current Corrosion

Galvanic and Stray Current Corrosion Chapter 5 Galvanic and Stray Current Corrosion MElec-Ch5-1 Overview Galvanic Corrosion Understanding Galvanic Corrosion Controlling Galvanic Corrosion Stray Current Corrosion Understanding Stray Current

More information

Refining Corrosion Technologist NACE-RCT-001

Refining Corrosion Technologist NACE-RCT-001 Refining Corrosion Technologist NACE-RCT-001 NACE Cathodic Protection Technologist (CP3) Essay Exam Exam Preparation Guide March 2018 Copyright 2016 by NACE International Institute. All rights reserved.

More information

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS SECTION 26 05 26 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

GLENWOOD PLACE 2 MAR 2015

GLENWOOD PLACE 2 MAR 2015 PART 1 - GENERAL 1.01 SUMMARY: SECTION 16110 RACEWAYS A. Description: 1. Provide continuous conduit systems - beginning at the service point, to all distribution equipment and to every outlet and piece

More information

SECTION 2831 ITEM F-162 CHAIN-LINK FENCES

SECTION 2831 ITEM F-162 CHAIN-LINK FENCES SECTION 2831 ITEM F-162 CHAIN-LINK FENCES PART 1 - GENERAL 1.1 DESCRIPTION. This item shall consist of furnishing and erecting a chain-link fence in accordance with these specifications and the details

More information

ABSTRACT EXECUTIVE SUMMARY

ABSTRACT EXECUTIVE SUMMARY MIE TALK August 2016 Compiled by: Schalk J. P. Kruger ABSTRACT Corrosion is a major issue in industrial plant processes especially where any part of the structure is submerged in ground or water. The management

More information

How To Construct a Ferro Cement Tank

How To Construct a Ferro Cement Tank How To Construct a Ferro Cement Tank Be Advised The following power point presentation assumes that individuals using it to construct ferro-cement tanks have a basic knowledge of geometry and calculating

More information

DESIGN OF IMPRESSED CURRENT CATHODIC PROTECTION SYSTEMS

DESIGN OF IMPRESSED CURRENT CATHODIC PROTECTION SYSTEMS DESIGN OF IMPRESSED CURRENT CATHODIC PROTECTION SYSTEMS Advanced Corrosion Course 2017 February 21-23, 2017 Keith Boswell, National Pipeline Services, LLC. 1 OBJECTIVES To Provide Corrosion Control Personnel

More information

Heating Cables DATASHEET

Heating Cables DATASHEET Heating Cables DATASHEET JUNHO 2013 M PSBL system Heating cable PSBL Features Self-limiting Can be used in explosive athmospheres without temperature limiter Can be cut to any length due to parallel power

More information

RESIDENTIAL QUICK REFERENCE

RESIDENTIAL QUICK REFERENCE RESIDENTIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR

More information

C&G 2382 BS7671: th Edition IEE Wiring Regulations. 25 Questions

C&G 2382 BS7671: th Edition IEE Wiring Regulations. 25 Questions C&G 2382 BS7671:2008 17 th Edition IEE Wiring Regulations 25 Questions 1. BS7671 states that installation design must take into account a. current copper prices b. the effects of climate change c. a comparison

More information

Technical Seminar for Cathodic Protection to GOGC Design Unit Specialists. Dr. Nick Kioupis, Cathodic & Lightning Protection Section Head, DESFA

Technical Seminar for Cathodic Protection to GOGC Design Unit Specialists. Dr. Nick Kioupis, Cathodic & Lightning Protection Section Head, DESFA Technical Seminar for Cathodic Protection to GOGC Design Unit Specialists Dr. Nick Kioupis, Cathodic & Lightning Protection Section Head, DESFA Cathodic protection of complex structures is protection applicable

More information

Lightning Conduction Ground Rods: Configurations & Testing For Tree Protection

Lightning Conduction Ground Rods: Configurations & Testing For Tree Protection Lightning Conduction Ground Rods: Configurations & Testing For Tree Protection Dr. Kim D. Coder, Professor of Tree Biology & Health Care, Warnell School, UGA Grounding resistance can be reduced by increasing

More information

Investigation of leakage current flow through wooden poles structures on overhead distribution system

Investigation of leakage current flow through wooden poles structures on overhead distribution system Proceedings of the 7th WSEAS International Conference on Power Systems, Beijing, China, September 15-17, 2007 120 Investigation of leakage current flow through wooden poles structures on overhead distribution

More information

Parameters Effecting Substation Grounding Grid Resistance. Dwarka Prasad 1, Dr.H.C Sharma 2

Parameters Effecting Substation Grounding Grid Resistance. Dwarka Prasad 1, Dr.H.C Sharma 2 Parameters Effecting Substation Grounding Grid Resistance Dwarka Prasad 1, Research Scholar, Uttarakhand Technical University, Dehardun (Uttarakhand), India Department of Electrical Engineering Laxmi Devi

More information

Environmental concerns include the presence of oxygen, moisture (water), contact with dissimilar metals, and chemicals.

Environmental concerns include the presence of oxygen, moisture (water), contact with dissimilar metals, and chemicals. Construction Concern: Corrosion Article and photos by Gregory Havel May 9, 2018 Corrosion of a metal can be defined as its degrading from a reaction with its environment. This degradation can cause weakening

More information

The University of Texas at Austin September 30, 2011

The University of Texas at Austin September 30, 2011 SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATIONS PART 1 - GENERAL 1.1 SUMMARY A. This section governs the products and execution requirements relating to furnishing and installing grounding and

More information

Estimation of Corrosion Protection Condition on Buried Steel Pipeline under Cathodic Protection with IR-free Probe

Estimation of Corrosion Protection Condition on Buried Steel Pipeline under Cathodic Protection with IR-free Probe WP3-6 Estimation of Corrosion Protection Condition on Buried Steel Pipeline under Cathodic Protection with IR-free Probe Akinobu Nishikawa, Masahiro Sawai and Hidemasa Nonaka Osaka Gas Co., Ltd. JAPAN

More information

Cignal-owned Tower Sites Tower Operations & Rigging Policy

Cignal-owned Tower Sites Tower Operations & Rigging Policy Cignal-owned Tower Sites Tower Operations & Rigging Policy June 2016 Table of Contents 1 Introduction... 3 2 Process for Equipment Addition or Amendment... 4 2.1 Application for Equipment Addition or Amendment...

More information

Lightning Conduction System Design Concepts & Components For

Lightning Conduction System Design Concepts & Components For Lightning Conduction System Design Concepts & Components For Trees Dr. Kim D. Coder, Professor of Tree Biology & Health Care, Warnell School, UGA Trees have great value. The architectural, ecological,

More information

SECTION CHAIN LINK FENCING

SECTION CHAIN LINK FENCING SECTION 02835 - CHAIN LINK FENCING 1.0 GENERAL 1.1 Furnish and install chain link fencing complete in place with gates and accessories as specified herein and as shown on the Contract Drawings. 1.2 Reference

More information

Model T Professional Series 1/2HP 2 YEAR WARRANTY SUBMERSIBLE SUMP PUMP

Model T Professional Series 1/2HP 2 YEAR WARRANTY SUBMERSIBLE SUMP PUMP Model T00718 REPAIR PARTS REF. PART DESCRIPTION 1 310883 Upper casing 2 310885 Motor housing 3 310889 Stator 4 310887 Shaft / rotor 5 310895 Mechanical seal 6 310892 Impeller 7 310893 Strainer 8 310890

More information

(Condensed from National Electric Code)

(Condensed from National Electric Code) WIRING, SPECIFICATIONS, INSPECTION, AND METER INSTALLATION PROCEDURES FOR RESIDENTIAL CUSTOMERS SERVED BY SOUTHWEST ARKANSAS ELECTRIC COOPERATIVE CORPORATION Effective April 1, 1974 Revised February 3,

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 16060 Grounding and Bonding This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or

More information

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14 SECTION 270526 - GROUNDING AND BONDING FOR COMMUNICATIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Refining Corrosion Technologist NACE-RCT-001

Refining Corrosion Technologist NACE-RCT-001 Refining Corrosion Technologist NACE-RCT-001 NACE Cathodic Protection Tester Written Exam Exam Preparation Guide March 2018 Copyright 2017 by NACE International Institute. All rights reserved. Exam Preparation

More information

Corrosion Control and Cathodic Protection Data Sheet

Corrosion Control and Cathodic Protection Data Sheet Data Sheet CORROSION CONTROL Corrosion control is the application of engineering principles and procedures to minimise corrosion to an acceptable level by the most economical method. It is rarely practical

More information