PBR & PBU PANELS. Technical/Installation Information
|
|
- Fay Boone
- 6 years ago
- Views:
Transcription
1 PBR & PBU PANELS Technical/Installation Information
2 IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE Retro-R PANELS. THE MANUFACTURER DETAILS MUST BE FOLLOWED AS A MINIMUM TO INSURE APPROPRIATE WARRANTIES WILL BE ISSUED. ALWAYS INSPECT EACH AND EVERY PANEL AND ALL ACCESSORIES BEFORE INSTALLATION. NEVER INSTALL ANY PRODUCT IF ITS QUALITY IS IN QUESTION. NOTIFY MBCI IMMEDIATELY IF ANY PRODUCT IS BELIEVED TO BE OUT OF TOLERANCE, SPECIFICATION OR HAS BEEN DAMAGED DURING SHIPMENT. IF THERE IS A CONFLICT BETWEEN PROJECT INSTALLATION DRAWINGS PROVIDED OR APPROVED BY THE MANUFACTURER AND DETAILS IN THIS MANUAL, PROJECT INSTALLATION DRAWINGS WILL TAKE PRECEDENCE. Copyright NCI Group, Inc All Rights Reserved The Engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommended that the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed Steel Structural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria for coldformed steel components. Along with the Specification, the designer should reference the most current building code applicable to the project jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired, please contact the manufacturer. Descriptions and specifications contained herein were in effect at the time this publication was approved for printing. In a continuing effort to refine and improve products, MBCI reserves the right to discontinue products at any time or change specifications and/ or designs without incurring obligations. To ensure you have the latest information available, please inquire or visit our website at Application details are for illustration purposes only and may not be appropriate for all environmental conditions, building designs, or panel profiles. Projects should be engineered to conform to applicable building codes, regulations, and accepted industry practices. Insulation is not shown in these details for clarity. For complete performance specifications, product limitations, and disclaimers, please consult MBCI s Paint and Galvalume Plus warranties. Upon receipt of payment in full, these warranties are available upon request for all painted or Galvalume Plus prime products. Sample copies can be found at or contact your local MBCI Sales Representative.
3 TABLE OF CONTENTS PBR PANEL PRODUCT INFORMATION Architect/Engineer Information....PB-2 PBR Panel UL 90 Requirements...PB-3 General Discription...PB-4 Product Selection Chart...PB-4 PBR Panel Section Properties....PB-5 PBR Panel Allowable Uniform Roof Loads...PB-6 PBR Panel Allowable Uniform Wall Loads....PB-7 PBR Panel Product Checklist... PB-8 - PB-9 PBR Panel Fastener Locations....PB-10 PBR Panel Attachment...PB-11 PBR Panel UL 90 Light Transmitting Panel Installation.... PB-12 - PB-13 PBU PANEL PRODUCT INFORMATION Architect/Engineer Information....PB-14 PBU Panel UL 90 Requirements...PB-15 General Discription...PB-16 Product Selection Chart...PB-16 PBU Panel Section Properties....PB-17 PBU Panel Allowable Uniform Roof Loads...PB-18 PBU Panel Allowable Uniform Wall Loads....PB-19 PBU Panel Product Checklist... PB-20 - PB-21 PBU Panel Fastener Locations....PB-22 PBU Panel Attachment...PB-23 PBU Panel UL 90 Light Transmitting Panel Installation.... PB-24 - PB-25 DETAILS Installation Guidelines...PB-26 Ridge...PB-27 High Side Eave...PB-28 Hip....PB-29 Valley...PB-30 Gutter...PB-31 Eave Trim....PB-32 Rake...PB-33 Parapet High Side Eave...PB-34 Parapet Rake...PB-35 Corner...PB-36 Corner Box....PB-37 Base...PB-38 Head Jamb....PB-39 SUBJECT TO CHANGE WITHOUT NOTICE SEE FOR CURRENT INFORMATION REV PB-1
4 PRODUCT INFORMATION PBR PANEL ARCHITECT/ENGINEER INFORMATION 1. PBR panel is a structural roof and wall panel. This panel can be installed directly over purlins or joists. Several different UL 90 construction numbers are available for this panel. 2. PBR panel is recommended for ½:12 or greater roof slopes. 3. Field applied tape sealant is required at panel sidelaps and endlaps. 4. PBR panel is a through-fastened panel. For proper fastener application, see page 9 and page The information in this manual is believed to be correct and accurate. It should not be used for any specific application without being reviewed by a registered professional engineer. 6. Galvalume material must not come in contact with concrete or pressure treated lumber. RATING PROFILE NOTES: 1 All roofs are Class Fastener #1E. 11 Fastener #4. WIDTH (IN) GAUGE FACTORY MUTUAL APPROVALS PURLIN SPACING PURLIN GA. FASTENER TYPE NUMBER OF FASTENERS PBR '-3 1/ 16 1/4-14 X 1 1/4 ZAC PBR '-3 1/ 16 1/4-14 X 1 1/4 ZAC3 6 STITCH FASTENER 1/4-14 X 7/8 ZAC11 1/4-14 X 7/8 ZAC11 STITCH FASTENER SPACING 20" o.c. 20" o.c. State of Florida Approval Numbers: FL (roof), FL (wall), FL5222 (light transmitting panels). Miami Dade County NOA: (roof), (wall), see special installation instructions, PB-2 REV SEE FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE
5 PBR PANEL PRODUCT INFORMATION UL 90 REQUIREMENTS PBR PANEL Construction #30 26 MSG Min. Gauge PBR Panel over Purlins at 5'- 0 ¼" O.C. 1. For Class 90 - Panel to purlin connections to be #14 Hex Head with a 5/8" O.D. washer in a in. pattern. Panel to panel connection to be 20" O.C. with fastener located over each purlin. 2. Purlins - No. 14 MSG min. gauge steel, (55,000 psi min. yield strength.) Construction #79 26 MSG Min. Gauge PBR Panel over Purlins at 5'- 0 ¼" O.C. 1. Panel Fasteners - Panel to purlin connections to be #14 Hex Head with a ⅝" O.D. washer, 6" O.C. in in. pattern. Endlap spacing to be 6 in. O.C. Spacing for panel to panel connection to be 20" O.C. 2. Purlins - No. 16 MSG min. gauge steel. (55,000 psi min. yield strength); or min. H series open web steel joists. Construction # MSG Min. Gauge PBR Panel over Purlins at 5'- 0 ¼" O.C. 1. Panel Fasteners - Panel to purlin connections to be x 1" self-drilling Hex Head with a ⅝" O.D. washer, 12" O.C. Spacing at endlap to be in a in. patterns. Spacing for panel to panel connection to be 20" O.C. with a fastener located over each purlin. 2. Purlins - No. 14 MSG min. gauge steel, (55,000 psi min. yield strength.) Construction # MSG Min. Gauge PBR Panel over Purlins at 5'- 0 ³ " O.C. 1. Panel Fasteners - Panel to purlin connections to be 12-14x1" self-drilling Hex Head with a ⅝" O.D. washer,12" O.C. Spacing at endlap to be in a in. pattern. Spacing for panel to panel connection to be 20" O.C. with a fastener located over each purlin. 2. Building Units - Translucent Panels. 3. Translucent Panel Rib and Purlin Reinforcement - See UL 90 light transmitting panel installation instructions. 4. Purlins - No. 16 MSG min. gauge steel. (55,000 psi min. yield strength). IMPACT RESISTANCE PBU panels carry a Class 4 rating under UL-2218 "Test Standard For Impact Resistance" FIRE RESISTANCE RATING 1. Deck: NC Class A Incline: Unlimited The panel qualifies for a Class A Fire Rating in compliance with Underwriters Laboratories Standard UL-263 when installed over a non-combustible substrate. A Class C Fire Rating will be qualified for over a combustible substrate. Look for classification marking on product. CAUTION The above listings are summaries of Construction Numbers. For UL 90 rated roof requirements and complete design information, see the Underwriters Laboratories Building Materials Directory. If you have any questions, call MBCI before proceeding. SUBJECT TO CHANGE WITHOUT NOTICE SEE FOR CURRENT INFORMATION REV PB-3
6 PBR PANEL 12" PRODUCT INFORMATION GENERAL DESCRIPTION 36" 1¹ ₄" PBR PANEL Coverage Width - 36" Minimum Slope - ½:12 Panel Attachment - See page 8 Panel Substrate - Galvalume Gauge - 26 standard - 29, 24 and 22 also available Coatings - Galvalume Plus, Signature 200* and Signature 300* PRODUCT SELECTION CHART GAUGE GALVALUME PLUS SIGNATURE 200* SIGNATURE 300* 22 gauge 24 gauge 26 gauge 29 gauge - Available in any quantity. - Minimum quantity may be required. *See Commercial/Industrial color chart for available colors. Signature is a registered trademark of Metal Building Components, L.P. Galvalume Plus is a registered and protected trademark of BIEC International, Inc. v The Galvalume Plus coating is subject to variances in spangle from coil to coil which may result in noticeable shade variation ininstalled panels.the Galvalume Plus coating is also subject to differential weathering after panel installation. Panels may appear to be different shades due to this weathering characteristic. If a consistent appearance is required, MBCI recommends that pre-painted panels be used in lieu of Galvalume Plus. Shade variation in panels manufactured from Galvalume Plus coated material do not diminish the structural integrity of the product. These shade variations should be anticipated and are not a cause for rejection. PB-4 REV SEE FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE
7 PBR PANEL 12" PRODUCT INFORMATION PBR PANEL 36" 1¹ ₄" SECTION PROPERTIES NEGATIVE BENDING POSITIVE BENDING PANEL Fy WEIGHT Ixe Sxe Maxo Ixe Sxe Maxo GAUGE (KSI) (PSF) (IN.4/FT.) (IN.3/FT.) (KIP-IN.) (IN.4/FT.) (IN.3/FT.) (KIP-IN.) 29 60* * * Fy is 80-ksireduced to 60-ksi in accordance with the 2012 edition of the North American Specification For Design Of Cold-Formed Steel Structural Members - A NOTES: 1. All calculations for the properties of PBR Roof panels are calculated in accordance with the 2012 edition of the North American Specification For Design Of Cold-Formed Steel Structural Members. 2. Ixe is for deflection determination. 3. Sxe is for bending. 4. Maxo is allowable bending moment. 5. All values are for one foot of panel width. The Engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommended that the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed Steel Structural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria for cold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to the project jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired, please contact the manufacturer. SUBJECT TO CHANGE WITHOUT NOTICE SEE FOR CURRENT INFORMATION REV PB-5
8 PRODUCT INFORMATION PBR ROOF PANEL ALLOWABLE UNIFORM LOADS IN POUNDS PER SQUARE FOOT PBR PANEL 29 Gauge (0.0133"), Fy = 60 ksi, Fu = 61.5 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Gauge (0.0181"), Fy = 60 ksi, Fu = 61.5 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Gauge (0.0223"), Fy = 50 ksi, Fu = 60 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Gauge (0.0286"), Fy = 50 ksi, Fu = 60 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Notes: 1. Strength calculations based on the 2012 AISI Standard "North American Specification for the Design of Cold-formed Steel Structural Members. 2. Allowable loads are applicable for uniform loading and spans without overhangs 3. LIVE LOAD/DEFLECTION load capacities are for those loads that push the panel against its supports. The applicable limit states are flexure shear, combined shear and flexure, web crippling at end and interior supports, and a deflection limit of L/180 under strength-level loads 4. NEGATIVE WIND LOAD capacities are for those loads that pull the panel away from its supports. The applicable limit states are flexure shear, combined shear and flexure, and a deflection limit of L/60 under 10-year wind loading 5. Panel pullover and Screw pullout capacity must be checked separately using the screws employed for each particular application whe utilizing this load chart. 6. Effective yield strength has been determined in accordance with section A2.3.2 of the 2012 NAS specification. 7. The use of any accessories other than those provided by the manufacturer may damage panels, void all warranties and will void all engineering data. 8. This material is subject to change without notice. Please contact MBCI for most current data The Engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommended that the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed Steel Structural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria for cold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to the project jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired, please contact the manufacturer. PB-6 REV SEE FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE
9 PBR PANEL PRODUCT INFORMATION PBR WALL PANEL ALLOWABLE UNIFORM LOADS IN POUNDS PER SQUARE FOOT 29 Gauge (0.0133"), Fy = 60 ksi, Fu = 61.5 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Gauge (0.0181"), Fy = 60 ksi, Fu = 61.5 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Gauge (0.0223"), Fy = 50 ksi, Fu = 60 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Gauge (0.0286"), Fy = 50 ksi, Fu = 60 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Notes: 1. Strength calculations based on the 2012 AISI Standard "North American Specification for the Design of Cold-formed Steel Structural Members. 2. Allowable loads are applicable for uniform loading and spans without overhangs 3. LIVE LOAD/DEFLECTION load capacities are for those loads that push the panel against its supports. The applicable limit states are flexure shear, combined shear and flexure, web crippling at end and interior supports, and a deflection limit of L/60 under 10-year wind loading 4. NEGATIVE WIND LOAD capacities are for those loads that pull the panel away from its supports. The applicable limit states are flexure shear, combined shear and flexure, and a deflection limit of L/60 under 10-year wind loading 5. Panel pullover and Screw pullout capacity must be checked separately using the screws employed for each particular application whe utilizing this load chart. 6. Effective yield strength has been determined in accordance with section A2.3.2 of the 2012 NAS specification. 7. The use of any accessories other than those provided by the manufacturer may damage panels, void all warranties and will void all engineering data 8. This material is subject to change without notice. Please contact MBCI for most current data The Engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommended that the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed Steel Structural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria for cold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to the project jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired, please contact the manufacturer. SUBJECT TO CHANGE WITHOUT NOTICE SEE FOR CURRENT INFORMATION REV PB-7
10 ⁵ ₈" PRODUCT INFORMATION PBR PANEL PBR Panel PRODUCT CHECKLIST Ridge Cap Sculptered High Side Eave 8" 12" 36" 1¹ ₄" PBR Panel Maximum Roof Pitch 5:12 Specify Pitch FL-49 2'-6" FL-51 3'-0" Specify Roof Slope 2" 1³ ₄" FL-17 Flat Ridge/Hip Flashing Valley Flashing SPECIFY ANGLE 2" Sculptered Rake 5" 1³ ₄" 11¹ ₂" SPECIFY ANGLE 11¹ ₂" Standard S PECIFY ANGLE 18³ ₄" 11" 2" 11" 45 FL ³ ₄" 2" 1³ ₄" 1¹ ₄" FL-38A Extended 45 FL-558 FL-16 Parapet High Eave Parapet Rake Eave Trim 6" 5" 6" 1³ ₄" 3¹ ₂" 5" 5¹ ₂" ³ ₄" Specify Roof Slope FL-874 FL-952 Specify Roof Slope FL-19 Sculptured Hang-On Gutter Sculptured Eave Gutter Gutter Strap 1" ³ ₄" 90 - OF ROOF PITCH DIM. A 1" 3¹ ₂" DIM. A 90 + of ROOF SLOPE Gutter End FL-893 Specify Roof Slope 90 + OF ROOF SLOPE FL-18C Specify Roof Slope 90 + of ROOF SLOPE FL-18 Specify Left or Right Specify Gutter part no. FL-18A PB-8 REV SEE FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE
11 PBR PANEL PRODUCT INFORMATION PRODUCT CHECKLIST Inside Corner Trim 4Z\x" C\v" 1C\v" Downspouts 3Z\x" 3Z\x" Corner Trim - Outside 3⁵\₁₆" 1C\v" 4Z\x" FL-31 - Straight 3⁵\₁₆" C\v" C\v" 1C\v" FL-800 Base Trim (With Sheeting Notch) FL-31A - With Kick-Out Base Trim (Without Sheeting Notch) 1C\v" Jamb Trim C\v" FL-830 3¹ ₄" 1³ ₄" 2" 1³ ₄" 2" ⁵ ₈ " 45 1" Z\x" 2¹ ₂" Fasteners 135 FL-72 ¹ ₂" FL-530 1Z\v" FL-23 #17A X 1¼" Driller LTP Head Trim #12A # x 1" Pancake Head Driller X 1¼" Long Life Driller High Strength Fiberglass High Strength Fiberglass U.V. Resistant 1Z\v" 1C\₈" 2Z\x" FL-26 #4 ¼"-14 X ⅞" Long Life Lap Tek Sealant ½" X ³ " HW-507 1" X ³ " HW-506 Closures Inside HW-455 #43L #44L #14 ¼"-14 X 1¼" Long Life Driller with 1⅛" O.D. washer ¼"-14 X ⅞" Long Life Lap Tek with 1⅛" O.D. Washer ⅛ X 3/16" Stainless Steel Pop Rivet TRIPLE BEAD TR URETHANE SEALANT 11 OZ. NOTE: 25' Per tube at ¼" bead Triple Bead HW-502 Color Part No. White HW-540 Gray HW-540 Almond HW-540 Bronze HW-540 Outside HW-456 Beveled Inside* Beveled Outside* *Special order - requires two-week lead time Note: It is the users responsibility to ensure that the installation and use of all light transmitting panels comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding all light transmitting panels with screens, fixed standard railings, or other acceptable safety controls that prevent fall-through. SUBJECT TO CHANGE WITHOUT NOTICE SEE FOR CURRENT INFORMATION REV PB-9
12 PBR PANEL PRODUCT INFORMATION PBR PANEL FASTENER LOCATIONS PANEL ENDS INTERIOR OF PANEL APPLICATION PREVAILING WIND NOTES: 1. The PBR panel has an unsymmetrical purlin bearing side lap leg. Panel side lap with extended foot to bear on frame. However, where possible, the panel should be lapped against prevailing wind. 2. The above are typical fastener spacings. However, they may not be appropriate for all applications. Consult a professional engineer for use on any specific application. 3. Minimum ½" x ³ " tape sealer required at panel side laps when used as roof panels. 4. Side lap fasteners are required. Typical spacing is 20" O.C. However, this spacing may not be appropriate for all applications. Consult a professional engineer for use on any specific application. PB-10 REV SEE FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE
13 PBR PANEL PRODUCT INFORMATION PBR PANEL ATTACHNENT ¹ ₄ - 14 X ⁷ ₈ LONG- LIFE LAPTEK W/WASHER 20 O.C. 6 EACH PER PANEL PBR PANEL ¹ ₂" X ³ ₃₂" PIGTAIL TO ENDLAP ¹ ₂" x ³ ₃₂" (CONTINUOUS@ ENDLAP) DETAIL "A" DETAIL "B" ¹ ₂" x ³ ₃₂" (TWO LAYERS) ENDLAP ATTACHMENT (SEE DETAIL B) HIGH SIDE ATTACHMENT (6 FASTENERS PER PANEL) SLOPE A A PBR PANEL EAVE ATTACHMENT (6 FASTENERS PER PANEL) INTERMEDIATE PURLIN ATTACHMENT (3 FASTENERS PER PANEL) PBR ROOF PANEL ¹ ₂" X ³ ₃₂" CONTINUOUS DOWN PANEL SIDE LAP (HW-507) ¹ ₂" X ³ ₃₂" PIGTAIL TO ENDLAP TAPE SEALANT (HW-507) ¹ ₂" X ³ ₃₂" (HW-507) (TWO LAYERS) NOTES: Sidelap 1. ½" X ³ " tape sealer must be installed between weather infiltration point and fastener. 2. Install Fastener #4 (¼"-14 X ⅞" Long Life Lap Tek) at 20" O.C. at roof panel side laps and 2 O.C. at wall panel side laps. 3. When possible, install panels such that sidelaps are nested away from prevailing winds. 4. Fastener #4A (¼"-14 X ⅞" Lap Tek) are available as an alternate when long life fasteners are not desired. Endlap 1. Stack 2 continuous layers of ½" X ³ " tape sealer on top of each other and must be installed between weather infiltration point and fastener. 2. Install a ½" X ³ " tape sealer pigtail to complete the seal between the side lap tape sealant and the end lap tape sealant. 3. Install Fastener #3 (12-14 X 1¼" Long Life driller) on each side of major ribs of panel (two fasteners per foot). 4. Fastener #17A (12-14 X 1¼" self-driller) are available as an alternate when long life fasteners are not desired. SUBJECT TO CHANGE WITHOUT NOTICE SEE FOR CURRENT INFORMATION REV PB-11
14 PRODUCT INFORMATION PBR PANEL SLOPE CONSTRUCTION NO. 542 UL 90 LIGHT TRANSMITTING PANEL INSTALLATION Install roof panels, leaving the light transmitting panel run open, except for lower light transmitting panel run metal panel. Install tape sealer to panel sidelaps and across panel width as normal. TRI-BEAD LOWER PANEL LIGHT TRANSMITTING PANEL PURLIN ¹ ₂" x ³ ₃₂" ¹ ₂" x ³ ₃₂" PIGTAIL ENDLAP TAPE SEALER TO SIDE LAP SEALER (HW-507) SLOPE TRI-BEAD PURLIN Attach light transmitting panels at the low and midslope connection to the purlin with nine Fastener #43L (¼ - 14 x 1¼" Long Life Driller with 1⅛" O.D. washer) per connection. LOWER PANEL 3L (18 MINIMUM) Install a Z\x" x C\cx" tape sealer pigtail to complete the seal between the side lap sealant and the end lap sealant. PB-12 REV SEE FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE
15 PBR PANEL PRODUCT INFORMATION CONSTRUCTION NO. 542 UL 90 LIGHT TRANSMITTING PANEL INSTALLATION (Continued) SLOPE ¼"-14 X ⅞" LONG LIFE LAP TEK #4 (9 PER PANEL) Be sure the light transmitting panel sidelaps have complete run of (½" x ³ ") tape sealer between the light transmitting panel and the PBR panel. PURLIN Fasten light transmitting panel with Fastener #44L (¼" - 14 x ⅞" Long Life Lap Tek with 1⅛" O.D. washer) at 10" O.C. down each side lap. LOWER PANEL 3L (18 MINIMUM) 4L 10" O.C. LIGHT TRANSMITTING PANEL Install upper metal panel in light transmitting panel run and fasten as at a normal endlap with nine Fastener #3 (12-14 X 1¼" Long Life driller). SUBJECT TO CHANGE WITHOUT NOTICE SEE FOR CURRENT INFORMATION REV PB-13
16 PBU PANEL PRODUCT INFORMATION ARCHITECT/ENGINEER INFORMATION 1. PBU panel is a structural roof and wall panel. This panel can be installed directly over purlins or joists. PBU panel is UL 90 rated per construction number PBU panel is recommended for 1:12 or greater roof slopes. 3. Field applied tape sealant is required at panel sidelaps and endlaps. 4. PBU panel is a through-fastened panel. For proper fastener application, see page 21 and page The information in this manual is believed to be correct and accurate. It should not be used for any specific application without being reviewed by a registered professional engineer. PB-14 REV SEE FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE
17 PBU PANEL PRODUCT INFORMATION UL 90 REQUIREMENTS PBU PANEL Construction #39 26 MSG Min. Gauge PBU Panel over Purlins at 5'- 0 ¼" O.C. 1. Panel Fasteners - Panel to purlin connections to be #14 self-drilling, Hex Head with a ⅝" O.D. washer, 6" O.C. Spacing at endlaps to be 6" O.C. Spacing for panel to panel connections to be 12" O.C. 2. Purlins - No. 16 MSG min gauge steel. (55,000 psi min. yield strength) IMPACT RESISTANCE PBU panels carry a Class 4 rating under UL-2218 "Test Standard For Impact Resistance" FIRE RESISTANCE RATING 1. Deck: NC Class A Incline: Unlimited The panel qualifies for a Class A Fire Rating in compliance with Underwriters Laboratories Standard UL-263 when installed over a non-combustible substrate. A Class C Fire Rating will be qualified for over a combustible substrate. Look for classification marking on product. CAUTION The above listings are summaries of Construction Numbers. For UL 90 rated roof requirements and complete design information, see the Underwriters Laboratories Building Materials Directory. If you have any questions, call MBCI before proceeding. SUBJECT TO CHANGE WITHOUT NOTICE SEE FOR CURRENT INFORMATION REV PB-15
18 PBU PANEL PRODUCT INFORMATION GENERAL DESCRIPTION 36" 6" ³ ₄" PBU PANEL Coverage Width - 36" Minimum Slope - 1:12 Panel Attachment - See page 17 Panel Substrate - Galvalume Gauge - 26 standard - 29, 24 and 22 also available Coatings- Galvalume Plus, Signature 200* and Signature 300* PRODUCT SELECTION CHART GAUGE GALVALUME PLUS SIGNATURE 200* SIGNATURE 300* 22 gauge 24 gauge 26 gauge 29 gauge - Available in any quantity. - Minimum quantity may be required. *See Commercial/Industrial color chart for available colors. Signature is a registered trademark of Metal Building Components, L.P. Galvalume Plus is a registered and protected trademark of BIEC International, Inc. v The Galvalume Plus coating is subject to variances in spangle from coil to coil which may result in noticeable shade variation ininstalled panels.the Galvalume Plus coating is also subject to differential weathering after panel installation. Panels may appear to be different shades due to this weathering characteristic. If a consistent appearance is required, MBCI recommends that pre-painted panels be used in lieu of Galvalume Plus. Shade variation in panels manufactured from Galvalume Plus coated material do not diminish the structural integrity of the product. These shade variations should be anticipated and are not a cause for rejection. PB-16 REV SEE FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE
19 PBU PANEL 6" PRODUCT INFORMATION PBU PANEL 36" ³ ₄" 29 Gauge (0.0133"), Fy = 60 ksi, Fu = 61.5 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Gauge (0.0181"), Fy = 60 ksi, Fu = 61.5 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Gauge (0.0223"), Fy = 50 ksi, Fu = 60 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Gauge (0.0286"), Fy = 50 ksi, Fu = 60 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Notes: 1. Strength calculations based on the 2012 AISI Standard "North American Specification for the Design of Cold-formed Steel Structural Members. 2. Allowable loads are applicable for uniform loading and spans without overhangs 3. LIVE LOAD/DEFLECTION load capacities are for those loads that push the panel against its supports. The applicable limit states are flexure shear, combined shear and flexure, web crippling at end and interior supports, and a deflection limit of L/180 under strength-level loads 4. NEGATIVE WIND LOAD capacities are for those loads that pull the panel away from its supports. The applicable limit states are flexure shear, combined shear and flexure, and a deflection limit of L/60 under 10-year wind loading 5. Panel pullover and Screw pullout capacity must be checked separately using the screws employed for each particular application whe utilizing this load chart. 6. Effective yield strength has been determined in accordance with section A2.3.2 of the 2012 NAS specification. 7. The use of any accessories other than those provided by the manufacturer may damage panels, void all warranties and will void all engineering data. 8. This material is subject to change without notice. Please contact MBCI for most current data SUBJECT TO CHANGE WITHOUT NOTICE SEE FOR CURRENT INFORMATION REV PB-17
20 PRODUCT INFORMATION PBU PANEL PBU ROOF PANEL ALLOWABLE UNIFORM LOADS IN POUNDS PER SQUARE FOOT 29 Gauge (0.0133"), Fy = 60 ksi, Fu = 61.5 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Gauge (0.0181"), Fy = 60 ksi, Fu = 61.5 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Gauge (0.0223"), Fy = 50 ksi, Fu = 60 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Gauge (0.0286"), Fy = 50 ksi, Fu = 60 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Notes: 1. Strength calculations based on the 2012 AISI Standard "North American Specification for the Design of Cold-formed Steel Structural Members. 2. Allowable loads are applicable for uniform loading and spans without overhangs 3. LIVE LOAD/DEFLECTION load capacities are for those loads that push the panel against its supports. The applicable limit states are flexure shear, combined shear and flexure, web crippling at end and interior supports, and a deflection limit of L/180 under strength-level loads 4. NEGATIVE WIND LOAD capacities are for those loads that pull the panel away from its supports. The applicable limit states are flexure shear, combined shear and flexure, and a deflection limit of L/60 under 10-year wind loading 5. Panel pullover and Screw pullout capacity must be checked separately using the screws employed for each particular application whe utilizing this load chart. 6. Effective yield strength has been determined in accordance with section A2.3.2 of the 2012 NAS specification. 7. The use of any accessories other than those provided by the manufacturer may damage panels, void all warranties and will void all engineering data. 8. This material is subject to change without notice. Please contact MBCI for most current data The Engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommended that the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed Steel Structural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria for cold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to the project jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired, please contact the manufacturer. PB-18 REV SEE FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE
21 PBU PANEL PRODUCT INFORMATION PBU WALL PANEL ALLOWABLE UNIFORM LOADS IN POUNDS PER SQUARE FOOT 29 Gauge (0.0133"), Fy = 60 ksi, Fu = 61.5 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Gauge (0.0181"), Fy = 60 ksi, Fu = 61.5 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Gauge (0.0223"), Fy = 50 ksi, Fu = 60 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Gauge (0.0286"), Fy = 50 ksi, Fu = 60 ksi SPAN SPAN IN FEET LOAD TYPE TYPE NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION NEGATIVE WIND LOAD span LIVE LOAD/DEFLECTION Notes: 1. Strength calculations based on the 2012 AISI Standard "North American Specification for the Design of Cold-formed Steel Structural Members. 2. Allowable loads are applicable for uniform loading and spans without overhangs 3. LIVE LOAD/DEFLECTION load capacities are for those loads that push the panel against its supports. The applicable limit states are flexure shear, combined shear and flexure, web crippling at end and interior supports, and a deflection limit of L/180 under strength-level loads 4. NEGATIVE WIND LOAD capacities are for those loads that pull the panel away from its supports. The applicable limit states are flexure shear, combined shear and flexure, and a deflection limit of L/60 under 10-year wind loading 5. Panel pullover and Screw pullout capacity must be checked separately using the screws employed for each particular application whe utilizing this load chart. 6. Effective yield strength has been determined in accordance with section A2.3.2 of the 2012 NAS specification. 7. The use of any accessories other than those provided by the manufacturer may damage panels, void all warranties and will void all engineering data. 8. This material is subject to change without notice. Please contact MBCI for most current data The Engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommended that the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed Steel Structural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria for cold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to the project jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired, please contact the manufacturer. SUBJECT TO CHANGE WITHOUT NOTICE SEE FOR CURRENT INFORMATION REV PB-19
22 PRODUCT INFORMATION PBU PANEL PBU Panel PRODUCT CHECKLIST Ridge Cap Sculptered High Side Eave 8" 36" 6" ³ ₄" PBU Panel Maximum Roof Pitch 5:12 Specify Pitch FL-50 2'-6" FL-52 3'-0" Specify Roof Slope 2" 1³ ₄" FL-17 Flat Ridge/Hip Flashing Valley Flashing SPECIFY ANGLE 2" Sculptered Rake 5" 1¹ ₈" 11¹ ₂" SPECIFY ANGLE 11¹ ₂" FL-38 Standard S PECIFY ANGLE Extended 18³ ₄" 11" 2" 45 FL " 18³ ₄" FL-558 2" 1⁷ ₈" 1³ ₄" FL-15 Parapet High Eave 6" Parapet Rake 1¹ ₈" 4 ¹ ₂" 7 ¹ ₈" Eave Trim 3¹ ₂" 5" Specify Roof Slope 5¹ ₂" FL-874 ³ ₄" FL-954 Specify Roof Slope ⁵ ₈" FL-19 Sculptered Hang-On Gutter Sculptered Eave Gutter Gutter Strap 90 + of Roof Pitch 1" ³ ₄" DIM "A" 90 - of Roof Pitch 1" 90 + of Roof Pitch 3¹ ₂" DIM "A" Gutter End FL of Roof Pitch Specify Roof Slope FL-512B Specify Roof Slope FL-512 Specify Left or Right Specify Gutter part no. FL-18A PB-20 REV SEE FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE
23 PBU PANEL PRODUCT INFORMATION PRODUCT CHECKLIST Inside Corner Trim 3" 3" C\v" 1Z\₁₆" Downspouts 3Z\x" 3Z\x" FL-31 - Straight Corner Trim - Outside 3 ⁵\₁₆" 3 ⁵\₁₆" C\v" 1Z\₈" 1Z\₈" C\v" C\v" 1Z\₁₆" FL-810 FL-31A - With Kick-Out FL-840 Base Trim (With Sheeting Notch) Base Trim (Without Sheeting Notch) Jamb Trim 3Z\v" 2" 1C\v" 2" 135 1C\v" ⁵\₈" FL Z\x" 2Z\x" FL-530 1" 1Z\v" Z\x" FL-21 Fasteners LTP Head Trim #17A #12A X 1¼" Driller 2¹ ₂" x 1" Pancake Head Driller 1" # X 1¼" Long Life Driller High Strength Fiberglass High Strength Fiberglass U.V. Resistant 1" FL-514A #4 ¼"-14 X ⅞" Long Life Lap Tek Sealant ½" X ³ " HW-507 1" X ³ " HW-506 Closures Inside HW-459 #43L #44L #14 ¼"-14 X 1¼" Long Life Driller with 1⅛" O.D. washer ¼"-14 X ⅞" Long Life Lap Tek with 1⅛" O.D. Washer ⅛ X 3/16" Stainless Steel Pop Rivet TR TRIPLE BEAD URETHANE SEALANT 11 OZ. NOTE: 25' Per tube at ¼" bead Triple Bead HW-502 Color Part No. White HW-540 Gray HW-540 Almond HW-540 Bronze HW-540 Outside Beveled Inside* Beveled Outside* *Special order - requires two-week lead time HW-460 Note: It is the users responsibility to ensure that the installation and use of all light transmitting panels comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding all light transmitting panels with screens, fixed standard railings, or other acceptable safety controls that prevent fall-through. SUBJECT TO CHANGE WITHOUT NOTICE SEE FOR CURRENT INFORMATION REV PB-21
24 PBU PANEL PRODUCT INFORMATION PBU PANEL FASTENER LOCATIONS PANEL ENDS INTERIOR OF PANEL APPLICATION PREVAILING WIND NOTES: 1. The PBU panel has an unsymmetrical purlin bearing side lap leg. Panel side lap with extended foot to bear on frame. However, where possible, the panel should be lapped against prevailing wind. 2. The above are typical fastener spacings. However, they may not be appropriate for all applications. Consult a professional engineer for use on any specific application. 3. Minimum ½" X ³ " tape sealer required at panel side laps when used as roof panels. 4. Side lap fasteners are required. Typical spacing is 20 O.C. However, this spacing may not be appropriate for all applications. Consult a professional engineer for use on any specific application. PB-22 REV SEE FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE
25 PBU PANEL PRODUCT INFORMATION PBU PANEL ATTACHMENT ¹ ₄ - 14 X ⁷ ₈ LONG- LIFE LAPTEK W/WASHER 20 O.C. 6 EACH PER PANEL PBU PANEL ¹ ₂" X ³ ₃₂" PIGTAIL TO ENDLAP ¹ ₂" x ³ ₃₂" (CONTINUOUS@ ENDLAP) DETAIL "A" DETAIL "B" ¹ ₂" x ³ ₃₂" (TWO LAYERS) ENDLAP ATTACHMENT (SEE DETAIL B) HIGH SIDE ATTACHMENT (6 FASTENERS PER PANEL) SLOPE A A PBU PANEL EAVE ATTACHMENT (6 FASTENERS PER PANEL) INTERMEDIATE PURLIN ATTACHMENT (3 FASTENERS PER PANEL) PBU ROOF PANEL ¹ ₂" X ³ ₃₂" CONTINUOUS DOWN PANEL SIDE LAP (HW-507) ¹ ₂" X ³ ₃₂" PIGTAIL TO ENDLAP TAPE SEALANT (HW-507) ¹ ₂" X ³ ₃₂" (HW-507) (TWO LAYERS) NOTES: Sidelap 1. ½" X ³ " tape sealer must be installed between weather infiltration point and fastener. 2. Install Fastener #4 (¼"-14 X ⅞" Long Life Lap Tek) at 20" on center. 3. When possible, install panels such that sidelaps are nested away from prevailing winds. 4. Fastener #4A (¼"-14 X ⅞" Lap Tek) are available as an alternate when long life fasteners are not desired. Endlap 1. Stack 2 continuous layers of ½" X ³ " tape sealer on top of each other and must be installed between weather infiltration point and fastener. 2. Install Fastener #3 (12-14 X 1¼" Long Life driller) on each side of major ribs of panel (two fasteners per foot). 3. Fastener #17A (12-14 X 1¼" self-driller) are available as an alternate when long life fasteners are not desired. SUBJECT TO CHANGE WITHOUT NOTICE SEE FOR CURRENT INFORMATION REV PB-23
26 PRODUCT INFORMATION PBU PANEL LIGHT TRANSMITTING PANEL INSTALLATION SLOPE Install roof panels, leaving the light transmitting panel run open, except for lower light transmitting panel run metal panel. Install tape sealer to panel sidelaps and across panel width as normal. TRI-BEAD LOWER PANEL PURLIN ¹ ₂" x ³ ₃₂" LIGHT TRANSMITTING PANEL ¹ ₂" x ³ ₃₂" PIGTAIL ENDLAP TAPE SEALER TO SIDE LAP SEALER (HW-507) SLOPE TRI-BEAD PURLIN LOWER PANEL 3L (12 MINIMUM) Attach light transmitting panels at the low and midslope connection to the purlin with six Fastener #43L (¼ - 14 x 1¼" Long Life Driller with 1⅛" O.D. washer) per connection. Install a Z\x" x C\cx" tape sealer pigtail to complete the seal between the side lap sealant and the end lap sealant. PB-24 REV SEE FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE
27 PBU PANEL PRODUCT INFORMATION LIGHT TRANSMITTING PANEL INSTALLATION (Continued) Be sure the light transmitting panel sidelaps have complete run of (½" x ³ ") tape sealer between the light transmitting panel and the PBU panel. SLOPE ¼"-14 X ⅞" LONG LIFE LAP TEK #4 (6 PER PANEL) Fasten light transmitting panel with Fastener #44L (¼" - 14 x ⅞" Long Life Lap Tek with 1⅛" O.D. washer) at 10" O.C. down each side lap. PURLIN LOWER PANEL 3L (12 MINIMUM) 4L 10" O.C. LIGHT TRANSMITTING PANEL Install upper metal panel in light transmitting panel run and fasten as at a normal endlap with six Fastener #3 (12-14 X 1¼" Long Life driller). SUBJECT TO CHANGE WITHOUT NOTICE SEE FOR CURRENT INFORMATION REV PB-25
PBR & PBU PANELS. Technical/Installation Information
PBR & PBU PANELS Technical/Installation Information IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE PANEL S. THE MANUFACTURER DETAILS MUST BE FOLLOWED AS A MINIMUM
More informationPBR & PBU Panels. Technical/Installation Information
PBR & PBU Panels Technical/Installation Information TABLE OF CONTENTS A. PBR Panel 1. General Description..................................................................... 2 2. Architect/Engineer Information............................................................
More information5V Crimp DESIGN/INSTALLATION INFORMATION
5V Crimp DESIGN/INSTALLATION INFORMATION IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE SYSTEM. METAL DEPOTS DETAILS MUST BE FOLLOWED AS A MINIMUM TO INSURE APPROPRIATE
More informationRetro-R DESIGN/INSTALLATION INFORMATION
Retro-R DESIGN/INSTALLATION INFORMATION IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE Retro-R PANELS. THE MANUFACTURER DETAILS MUST BE FOLLOWED AS A MINIMUM TO
More information5V CRIMP. Technical/Installation Information
5V CRIMP Technical/Installation Information IMPORTANT NOTICE READ THIS MANUAL OCMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE SYSTEM. ALWAYS INSPECT EACH AND EVERY PANEL AND ALL ACCESSORIES BEFORE
More informationBattenLok HS. Technical/Installation Information
BattenLok HS Technical/Installation Information IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE ROOFING SYSTEM. THE MANUFACTURER DETAILS MUST BE FOLLOWED AS A MINIMUM
More informationRichmond, VA 800/ Rome, NY 800/ Salt Lake City, UT 800/ San Antonio, TX 800/ COMMERCIAL / INDUSTRIAL PRICING
TABLE OF CONTENTS A. Panels 1. PBR.........................................................................CP-2-3 2. PBU.........................................................................CP-2-3 3.
More informationResidential Pricing Guide
Guide TABLE OF CONTENTS Panels 5V Crimp Slimline 2 4 Accessories Flat Sheets Coils V-Groove Soffit Ridge Caps Roof Jacks Touch-up Paint Insulation Slimline Rib Cover Closure Strips Tube Sealant 6 6 7
More informationLokSeam. Design/Installation Information
Design/Installation Information IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE ROOFING SYSTEM. MBCI DETAILS MUST BE FOLLOWED AS A MINIMUM TO INSURE APPROPRIATE
More informationTable of Contents. Notes to Designer/User Map of Typical Roof Conditions...3 Fastener Placement...4 Fastener Selection...5
Table of Contents Section Page Notes to Designer/User...................1-2 Map of Typical Roof Conditions..............3 Fastener Placement........................4 Fastener Selection.........................5
More informationa division of NCI Standing Seam Roof Systems
a division of NCI Standing Seam Roof Systems Building Benefits You Can Expect From A&S Materials Standing Seam roof panels weigh a relatively modest 11/2 pounds per square foot. When long life is required
More informationLokSeam. Design/Installation Information. This booklet includes: Trims and Accessories Design and Installation Information
LokSeam Design/Installation Information This booklet includes: Trims and Accessories Design and Installation Information IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION
More informationAgricultural Pricing Guide
Guide TABLE OF CONTENTS Panels Rain Guard Perma-Clad, WeatherSafe and Stormproof Stormproof with Drip Stop Corrugated 2 4 6 7 Accessories Flat Sheets Coils Roof Jacks Ventilators Light Transmitting Panels
More information29 Gauge. Technical/Installation Information
Technical/Installation Information IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE 29 GAUGE LOW PROFILE PANELS PANELS. THE MANUFACTURER DETAILS MUST BE FOLLOWED
More informationSTILE. Panel Information. Design/Installation Considerations. Flashing Profiles. Detail Conditions. Notes. Accessory Profiles. Testing Information
Table of ontents Product Page No. Product Page No. Panel Information Profile...PST-2 Panel Overview...PST-2 Flashing Profiles Eave...PST- Extended Eave...PST- leat...pst- Stile Starter...PST- Box Gutter...PST-
More informationCentral Seam Plus. Central-Loc
Central Seam Plus Central-Loc Product Guide HELPFUL INFORMATION ON PANELS, TRIMS, GUTTERS AND ACCESSORIES 3" 3" " or 18" COVERAGE " or 18" COVERAGE Central Seam Plus Field seamed Central-Loc Snaps together
More information* Other widths available upon request. 24 Gauge Galvalume - Standard Surface. Other gauges and aluminium available upon request.
is a concealed fastener architectural standing seam roof panel. The panels are easily installed over decking, utilizing metal clips. panels are ideally suited for decorative mansard, fascia and roofs.
More informationR PANEL / PBR PANEL. Installation, Flashings & Shop Drawing Detail Guide.
R PANEL / PBR PANEL Installation, Flashings & Shop Drawing Detail Guide 901 W. Watkins Street Phoenix, AZ 85007 Phone: (877) 787-5467 (855) 426-7836 Email: sales@cortenroofing.com sales@metalforroofing.com
More informationWestern States 7/8 Corrugated
Western States 7/8 Corrugated Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer / Installers..1 Fastener Placement and Selection.2-3 Key
More informationWESTERN RIB. Installation, Flashings & Shop Drawing Detail Guide.
WESTERN RIB Installation, Flashings & Shop Drawing Detail Guide 901 W. Watkins Street Phoenix, AZ 85007 Phone: (877) 787-5467 (855) 426-7836 Email: sales@cortenroofing.com sales@metalforroofing.com For
More informationLokSeam. Technical/Installation Information
Technical/Installation Information IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE ROOFING SYSTEM. MBCI DETAILS MUST BE FOLLOWED AS A MINIMUM TO INSURE APPROPRIATE
More informationMIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590
More informationShadowRib. Design/Installation Information
ShadowRib Design/Installation Information IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE ROOFING SYSTEM. THE MANUFACTURER DETAILS MUST BE FOLLOWED AS A MINIMUM
More informationNuRoof Retrofit Systems. Technical/Installation Information
Retrofit Systems Technical/Installation Information INTRODUCTION If your roof is causing problems due to leaks, high maintenance costs and low energy efficiency, the MBCI NuRoof Retrofit System is the
More informationSuperior Structural Standing Seam Roof Systems
07 61 00/MBC BuyLine 3903 Superior Structural Standing Seam Roof Systems OUR PANELS MAKE THE difference www.mbci.com Superior Structural Standing Seam Roof Systems Illustrious Standing Seam Roof Systems
More informationML200 Panel Technical Data Guide
Description ML200 is a mechanical seamed standing seam roofing panel used on low to steep sloped commercial applications. The panel is factory formed in continuous lengths up to 60-0 long. Attachment to
More informationTable of Contents. 3. Exposed Fastener Panels
Table of Contents 895 North Parkway 3. Exposed Fastener Panels Exposed Fastener Panels Table of Contents... PE1-2 PBR... PE3-4 PBA... PE5-6 AVP... PE7-8 PBU... PE9-10 PBC... PE11-12 PBD... PE13-14 7.2...
More informationDouble-Lok. Technical/Installation Information
Technical/Installation Information IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE DOUBLE-LOK ROOFING SYSTEM. MBCI DETAILS MUST BE FOLLOWED AS A MINIMUM TO ENSURE
More informationIMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE WEATHER GUARD PANEL.
IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE WEATHER GUARD PANEL. IF THERE IS A CONFLICT BETWEEN PROJECT ERECTION DRAWINGS PROVIDED OR APPROVED BY WHIRLWIND BUILDING
More informationSL-16. Design/Installation Information
SL-16 Design/Installation Information IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE SL Series ROOFING SYSTEM. ALWAYS INSPECT EACH AND EVERY PANEL AND ALL ACCESSORIES
More informationCentral Texas Metal Roofing Supply Co., Inc 36" SHEET WIDTH 38 ¼ 40 ¼ 38 ¼ 40 ¼ 38 ¼ 40 ¼ 40 ¼ 40 ¼ NET COVERAGE
3 4 " 9" 36" GAUGE PANEL FINISH 26 26 26 26 24 24 24 24 FRONTIER RIB LAP GUARD FRONTIER RIB LAP GUARD FRONTIER RIB LAP GUARD LAP GUARD LAP GUARD GALVALUME GALVALUME SMP SMP GALVALUME GALVALUME KYNAR500
More informationCentral Texas Metal Roofing Supply Co., Inc SHEET WIDTH 38 ¼ 40 ¼ 38 ¼ 40 ¼ 38 ¼ 40 ¼ 38 ¼ 40 ¼ 38 ¼ 40 ¼
GAUGE PANEL FINISH NET COVERAGE 26 26 26 26 U PBU U PBU GALVALUME GALVALUME SMP SMP (NOTE 1) SHEET WIDTH 38 ¼ 40 ¼ 38 ¼ 40 ¼ WEIGHT PER SQ. 95.00 95.00 95.00 95.00 24 24 24 24 24 24 U PBU U PBU U PBU GALVALUME
More informationTECHNICAL ERECTION MANUAL SUPER SEAM II
8234 Hansen Road Houston, TX 77075 (800) 324 9992 Toll Free (713) 946 7140 (832) 553 4992 Fax www.whirlwindsteel.com Subject to change without notice IMPORTANT NOTICE PLEASE READ THIS MANUAL COMPLETELY
More informationMIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590
More informationCOMMERCIAL & INDUSTRIAL CI-CFR-INDEX SHEET INDEX CI-CFR-INDEX SHEET INDEX CI-CFR-INFO C & I DISCLAIMER
CI-CFR-INDEX SHEET INDEX CI-CFR-INFO C & I DISCLAIMER CI-CFR-LG LEGEND CI-CFR-JT-01 PANEL JOINT CI-CFR-JT-02 PANEL JOINT SEQUENCE CI-CFR-JT-03 PANEL JOINT LAYOUT CI-CFR-SQ-01 PANEL INSTALLATION SEQUENCE
More informationCentral Texas Metal Roofing Supply Co., Inc 36" NET COVERAGE SHEET WIDTH 38 ¼ 40 ¼ 38 ¼ 40 ¼ 38 ¼ 40 ¼ 40 ¼ 40 ¼
36" 1 2 " 6" GAUGE PANEL FINISH NET COVERAGE SHEET WIDTH WEIGHT PER SQ. 26 26 26 26 24 24 24 24 TEXAS RIB CHANNEL GUARD TEXAS RIB CHANNEL GUARD TEXAS RIB CHANNEL GUARD CHANNEL GUARD CHANNEL GUARD GALVALUME
More informationTABLE OF CONTENTS PRODUCT CATALOGUE fax OVERVIEW PBR 7.2 LONGSPAN ECONORIB
PRODUCT CATALOGUE www.metroll.us sales@fontana.metroll.com ph. 909.823.7663 fax 909.693.5153 TABLE OF CONTENTS OVERVIEW PBR Product Overview and Color Charts Panel Information and Trim 7.2 LONGSPAN ECONORIB
More informationSuperior Structural Standing Seam Roof Systems
07 61 00/MBC BuyLine 386 Superior Structural Standing Seam Roof Systems OUR PANELS MAKE THE difference www.mbci.com Superior Structural Standing Seam Roof Systems The Strongest Standing Seam Roof System
More informationENERGY STAR PARTNER. PBR & R Panel
ENERGY STAR PARTNER 1 Table of Contents Important Information Installation Information Technical Information Trims and Flashings Illustration Roo ng Installation Details Eave Flashing (EF-3) Eave Flashing
More information900 SERIES PANEL SHEET INDEX ENDLAP INSTALLATION SEQUENCE L.E. W/ GUTTER VAPOR BARRIER CS-RK-01B-900
CS-PJ-01-900 CS-DS-01-900 CS-PJ-02-900 CS-EL-01-900 CS-EL-02-900 CS-EL-03-900 CS-EL-04-900 CS-RD-01-900 CS-RD-02-900 CS-RD-03-900 CS-EV-01A-900 CS-EV-01B-900 CS-EV-02A-900 CS-EV-02B-900 CS-EV-03A-900 CS-EV-03B-900
More informationProduct Guide HELPFUL INFORMATION ON PANELS, TRIMS, GUTTERS AND ACCESSORIES
5V Product Guide HELPFUL INFORMATION ON PANELS, TRIMS, GUTTERS AND ACCESSORIES ½" 24" COVERAGE Copyright 2018, Central States Manufacturing, Inc., All Rights Reserved. D C GUID_PROD_5V_180201 The men
More informationDIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: METAL SALES MANUFACTURING CORPORATION
0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (0) 3-87 (562) 699-03 www.icc-es.org ESR-23 Reissued 08/2017 This report is subject to renewal 08/2019. DIVISION: 07 00 00 THERMAL
More informationSHURLOC 150 STANDARD DETAILS
OVER WOOD DECK STANDARD DETAILS Austin - Headquarters/Sales Office 830 Sagebrush Drive Austin, TX 78758 (512) 452-1515 (800) 428-7412 Fax (512) 833-7499 www.ctmrs.com email: info@ctmrs.com Seguin - Plant/Sales
More informationTYPICAL ROOF CONDITION LAYOUT
FIXED POINTS TYPICAL ROOF CONDITION LAYOUT 15 17 9 16 29 12 14 11 3 7 35 20 6 23 30 31 24 13 18 Typical Roof Condition Layout... 1 Low Eave Isometric View - Fixed/ Floating... 2 Low Eave Section - Fixed/
More informationTRIAD CORRUGATED METAL, INC.
TRIAD CORRUGATED METAL, INC. COMMERCIAL RESIDENTIAL AGRICULTURAL MS-216 MS-218 Panel Guide This guide describes the design and performance characteristics of the MS-216 and MS-218 Roof panel system. The
More informationTRIAD CORRUGATED METAL, INC.
TRIAD CORRUGATED METAL, INC. C O M M E R C I A L R E S I D E N T I A L A G R I C U L T U R A L Snap Loc Panel Guide Snap Loc metal panels are a perfect fit for residential, architectural and commercial
More informationS BI COM P ON E NT CA T ALOG
SBI METAL BUILDINGS & COMPONENTS S BI COM P ON E NT CA T ALOG Date: 03 / 16 / 2017 COMMERCIAL PRODUCTS Commercial Panels and Trim Cee, Zee, Eave Struts, Angle, Channel, and Clips Accessories FT 0 1 2 3
More informationTrusted Tested Tough Kalaeloa Blvd, Kapolei, Hawaii Phone (808) Fax (808) Neighbor Islands (800)
MAC 200 STRUCTURAL STANDING SEAM METAL ROOF SYSTEM Trusted Tested Tough 91-104 Kalaeloa Blvd, Kapolei, Hawaii 96707 Phone (808) 682-3000 Fax (808) 682-3636 Neighbor Islands (800) 352-3920 www.kloecknermetals.com
More informationEVALUATION REPORT OF CENTRAL STATES MANUFACTURING, INC. 'CENTRAL-LOC PANEL' FLORIDA BUILDING CODE 5TH EDITION (2014) FLORIDA PRODUCT APPROVAL
- EVALUATION REPORT OF CENTRAL STATES MANUFACTURING, INC. 'CENTRAL-LOC PANEL' FLORIDA BUILDING CODE 5TH EDITION (2014) FLORIDA PRODUCT APPROVAL FL 14016.2-R2 STRUCTURAL COMPONENTS ROOF DECK Prepared For:
More informationCentral Texas Metal Roofing Supply Co., Inc NET COVERAGE SHEET WIDTH
1 2 " 1 24" GAUGE PANEL FINISH NET COVERAGE SHEET WIDTH WEIGHT PER SQ. 26 5 Vee GALVALUME 24 26 3/8 95.00 PRICE PER SQ. PRICE PER LINEAR FOOT PANEL PRICING: 1. Price per Square is based on 26 3/8 sheet
More informationLokSeam DESIGN/INSTALLATION INFORMATION
LokSeam DESIGN/INSTALLATION INFORMATION IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE LokSeam ROOFING SYSTEM. METAL DEPOTS DETAILS MUST BE FOLLOWED AS A MINIMUM
More informationSECTION METAL ROOF PANELS
SECTION 07 41 13 PART 1 GENERAL 1.1 SECTION INCLUDES A. Standing-seam roof panels. B. Metal roofing accessories. 1.2 RELATED SECTIONS A. Section 07 62 00 - Sheet Metal Flashing. B. Section 07 72 00 - Roof
More informationPIPE. Central Texas Largest Distributor. Structural Steel, Pipe and Metal Building Components
Central Texas Largest Distributor Structural Steel, Pipe and Metal Building Components PIPE Waco Location P.O. Box 154485 913 South Loop Dr. Waco Texas 76705 Local - 254-754-2611 Bryan Location 9401 E.
More informationNUCOR VR 16 II STANDING SEAM ROOF SYSTEM TABLE OF CONTENTS
NUCOR VR 16 II STANDING SEAM ROOF SYSTEM TABLE OF CONTENTS Nucor VR16 II Vertical Rib Standing Seam Roof System...2 Nucor VR16 II Property and Span Tables...3 Standard Details...5 ED3010PE - Gutter...5
More informationDesigner Series. Technical/Installation Information
Technical/Installation Information IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE Designer Series WALL SYSTEM. MBCI MUST BE FOLLOWED AS A MINIMUM TO INSURE APPROPRIATE
More informationTECHNICAL ERECTION MANUAL SUPER SEAM PLUS
8234 Hansen Road Houston, TX 77075 (800) 324 9992 Toll Free (713) 946 7140 Phone (832) 553 4992 Fax www.whirlwindsteel.com Subject to change without notice IMPORTANT NOTICE PLEASE READ THIS MANUAL COMPLETELY
More informationClassic Rib Roofing Panels DETAIL MANUAL
Metal Roofing Wholesalers Classic Rib Roofing Panels DETAIL MANUAL www.metalroofingwholesalers.com 1170 Topside Rd Louisville, TN 37777 The Classic Rib Roofing Panel Figure 1 House With Classic Rib Metal
More information2120 SW Poma Drive; Palm City, Florida Phone Fax
2120 SW Poma Drive; Palm City, Florida 34990 772-223-4055 Phone 772-781-7492 Fax www.sunlastmetal.com sales@sunlastmetal.com IMPORTANT NOTICE READ THIS MANUAL COMPLETELY BEFORE BEGINNING INSTALLATION OF
More informationShadowRib Metal Wall Panel INSTALLATION GUIDE
Metal Wall Panel INSTALLATION GUIDE IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE ROOFING SYSTEM. THE MANUFACTURER DETAILS MUST BE FOLLOWED AS A MINIMUM TO INSURE
More informationSECTION PRE-ENGINEERED METAL BUILDING
SECTION 13121 PRE-ENGINEERED METAL BUILDING PART 1 GENERAL 1.01 SCOPE OF WORK A. Furnish all labor, materials, equipment and incidentals required to design, fabricate, deliver to project site, and erect
More informationPRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590
More informationSL175 Panel Technical Data Guide
Description SL175 is a integral snap-lock standing seam roofing panel used on commercial and residential applications. The panel is factory formed in continuous lengths up to 60-0 long. Attachment to either
More information2120 SW Poma Drive; Palm City, Florida Phone Fax
2120 SW Poma Drive; Palm City, Florida 34990 772-223-4055 Phone 772-781-7492 Fax www.sunlastmetal.com sales@sunlastmetal.com IMPORTANT NOTICE READ THIS MANUAL COMPLETELY BEFORE BEGINNING INSTALLATION OF
More information238T and 138T Panel and Accessories Price List 9/29/2017 (price good for shipments through 11/31/2017) Customer Job Date Sales Rep 238T PANEL ITEM #
238T and 138T Panel and Accessories Price List 9/29/2017 (price good for shipments through 11/31/2017) Customer Job Date Sales Rep 238T PANEL ITEM # DESCRIPTION SELLING PRICE UOM 238T 238T Seam Cap 24
More informationMIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 NOTICE OF ACCEPTANCE
More informationUltra-Dek. Technical/Installation Information
Technical/Installation Information IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE Ultra-Dek ROOFING SYSTEM. IF THERE IS A CONFLICT BETWEEN PROJECT ERECTION DRAWINGS
More informationIMAGE II. Panel Information. Detail Conditions. Flashing Profiles. Accessory Profiles. Testing Information. Design/Installation Considerations PIM-1
Table of ontents Product Page No. Product Page No. Panel Information Profiles... PIM-2 Panel Overview...PIM-2 Flashing Profiles Eave...PIM-3 Extended Eave...PIM-3 leat...pim-3 Offset leat...pim-3 5K Gutter...PIM-3
More informationPRE-ENGINEERED METAL BUILDING SYSTEM
PRE-ENGINEERED METAL BUILDING SYSTEM PART 1 GENERAL 1.1 SUMMARY A. The building shall include all primary and secondary structural framing members, connection bolts, roof and wall covering, flashing, gutter,
More informationMIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590
More informationSECTION STANDING SEAM METAL ROOFING
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 41 13 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Use for roofing sloped 1 in 4 (3 in/ft) or greater. 3. Delete between // // if not applicable
More information5V and CORRUGATED Accessory Detail Manual
5V and CORRUGATED Accessory Detail Manual NOA # 06-0921.07 Miami Dade Approved - 5V Only Site Specific Engineering Required Thompson Architectural Metal Roofing is proud to be a partner of the Energy Star
More informationSECTION METAL ROOF AND SOFFIT PANELS
Metal Panel Systems, Inc. 11506 Reading Road Cincinnati, Ohio 45241-2512 Telephone: 800-554-6126 or 513-554-6120 Fax: 513-554-6121 www.metalpanelsystems.com info@metalpanelsystems.com Specifications for
More informationMetal Roof Certification & Listing Program
145 Limekiln Road, Suite 100B Issue Dated: 10/27/2017 New Cumberland, PA 17070 Revision Date: 10/27/2017 www.keystonecerts.com Expiration Date: 10/27/2022 Construction Specifications Institute (CSI) Category:
More informationPRODUCT SPECIFICATIONS
LokSeam LokSeam 12" One of the most versatile architectural metal panels available today, LokSeam by ABC, is a snap-together, concealed fastener, standing seam roof system with a 13/4" tall vertical rib,
More informationTable of Contents. 3. Standing Seam Panels
Table of Contents 895 North Parkway 3. Standing Seam Panels Standing Seam Panels Table of Contents... PS1-2 Double-Lok... PS3-8 Ultra-Dek... PS9-14 BattenLok HS... PS15-18 Curved BattenLok HS... PS19-20
More informationMIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 NOTICE OF ACCEPTANCE
More informationMultiLok-24 Guide Specifications conforming to C.S.I. standards. A Division of ASC Profiles
MultiLok-24 Guide Specifications conforming to C.S.I. standards A Division of ASC Profiles AEP SPAN MultiLok-24 Guide Spec i fi ca tions MANUFACTURER - AEP SPAN 5100 East Grand Avenue, Dallas, TX 75223,
More informationFACADES - ACM BASE AT OVERHANG (WITH BASE FLASHING) INDEX SHEET
KPH-DS-01-MTLV KPH-PJ-01-MTLV KPH-PJ-02-MTLV KPH-PJ-03-MTLV KPH-PJ-04-MTLV KPH-PJ-05-MTLV KPH-BS-01-MTLV KPH-BS-02-MTLV KPH-BS-03-MTLV KPH-BS-04-MTLV KPH-OC-01-MTLV KPH-IC-01-MTLV KPH-SF-01-MTLV KPH-SF-02-MTLV
More informationThe Experts in Retrofit Design. Retrofit Solutions. Retro-R SSR NuRoof NuWall
The Experts in Retrofit Design Retrofit Solutions Retro-R SSR NuRoof NuWall Retrofit Solutions by MBCI MBCI has experience in retrofitting existing buildings proven with millions of square feet of successfully
More informationThe Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers.
SECTION 05 31 23 - STEEL ROOF DECKING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the contract, including General and Supplementary Conditions and Division 01 - Specification
More informationFW-120 and ILPanels. Technical/Product Information
FW-120 and ILPanels Technical/Product Information IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE FW-120 AND IL PANELS. THE MANUFACTURER DETAILS MUST BE FOLLOWED
More informationFW-120. Technical/Installation Information
Technical/Installation Information IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE S. THE MANUFACTURER DETAILS MUST BE FOLLOWED AS A MINIMUM TO INSURE APPROPRIATE
More informationMIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590
More informationGENERAL SPECIFICATION FOR FIRE RATED APPLICATIONS
I N SULROCK FIRE RATED METAL PANELS GENERAL SPECIFICATION FOR FIRE RATED APPLICATIONS 1. GENERAL 1.1. Summary Fire-rated panels as shown on the drawings shall be INSULROCK brand panels as supplied by Green
More informationCentral Snap. Condition Details C SNAPDETAILS
Central Snap Condition Details D C SNAPDETAILS150612.2 The men and women at Central States Manufacturing, Inc. would like to welcome you. OUR MISSION Central States Manufacturing, Inc. is a 100% employee-owned
More informationMIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY AFFAIRS (PERA) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474
More informationSSL-175. Specifications
SSL-175 Specifications Everlast Metals 10 Enterprise Court Lebanon, PA 17042 Phone: (717) 270-6554 Fax: (717) 270-6569 www.everlastmetals.com 7410 Preformed Metal Roofing PART 1: GENERAL 1.01 SECTION INCLUDES
More informationPRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590
More informationDrexel Metals Inc. DMC 5V 26 Gauge min. Face-Fastening Metal Roof System over Plywood
Drexel Metals Inc. DMC 5V 26 Gauge min. Face-Fastening Metal Roof System over Plywood Section 07411 Metal Roof Panels Part 1 General 1.1 Summary A. This section includes the following: a. Factory-formed
More informationPanel Clip with (2) ¼ 14 x 2 Fasteners at Each Panel Joint. Base Angle. Fasteners to Concrete 24 O/C Base Z Flashing
EXTERIOR BASE DETAIL (FLUSH) EXTERIOR BASE DETAIL (OVERHANG) Base Trim with Panel Clip with (2) ¼ 14 x 2 Fasteners at Each Panel Joint Sealant Marriage Bead to Vertical Panel Joint Above and Below Z Flashing
More informationBUILDING COMPONENTS.
07 40 00/WHI BuyLine 5907 Over 10 Energy Star Rated Colors 40-Yr. warranty available on SMP paint systems and 35-Yr. for KYNAR paint systems Cool Metal Roofing Credit Opportunities Under USGBC LEED-NC
More informationPRODUCT DESCRIPTION ACCESSORIES. Canopies
An overhanging or projecting roof structure off the sidewall or endwall with the extreme end usually unsupported. Mainly used for aesthetic application or to cover entrance or walkway. Options: Face Panel
More informationSpan-Lok hp, Curved Span-Lok, & SpanSeam Guide Specifications
Span-Lok hp, Curved Span-Lok, & SpanSeam Guide Specifications MANUFACTURER - AEP SPAN 2141 Milwaukee Way, Tacoma, WA 98421, 800-733-4955 10905 Beech Avenue, Fontana, CA 92337 This Guide Specification is
More informationSECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM
PART 1- GENERAL 1.1 SUMMARY A. Section Includes: SECTION 084523 - SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 1. Flat factory prefabricated structural insulated translucent sandwich panels; with glazed endwalls.
More informationArchitectural. Technical/Installation Information
Technical/Installation Information IMPORTANT NOTICE This information is designed to assist you in product selection, detailing and application. MBCI is prepared and staffed to provide professional assistance
More informationSECTION STRUCTURAL RETROFIT ROOF SUB-FRAMING SYSTEM
SECTION 13 34 21 - STRUCTURAL RETROFIT ROOF SUB-FRAMING SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. The structural retrofit roof sub-framing system will provide support for a new metal roofing system constructed
More informationSECTION STEEL DECKING
SECTION 05 31 00 STEEL DECKING SPEC WRITER NOTE: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Refer to Section 05 36 00, COMPOSITE METAL DECKING for floor
More informationMetal Roof Certification & Listing Program
145 Limekiln Road, Suite 100B Issue Dated: 11/29/2017 New Cumberland, PA 17070 Revision Date: 12/07/2017 www.keystonecerts.com Expiration Date: 11/29/2022 Construction Specifications Institute (CSI) Category:
More informationSECTION STEEL BUILDING SYSTEMS
PART 1 - GENERAL 1.01 SECTION INCLUDES: SECTION 13120 - STEEL BUILDING SYSTEMS A. Pre-engineered building and components including the following: 1. Structural steel frame. 2. Roof covering system including
More information/CEC BuyLine 9109 C ECO B UILDING S YSTEMS
9/CEC BuyLine 909 C ECO B UILDING S YSTEMS A R C H I T E C T U R A L R E S O U R C E Rigid Frame Structural Systems Metal Roof Panels Rigid Frame Multi-Span (with Interior Column) Endpost End Frame (Bearing)
More information