SECTION REINFORCING STEEL. 1. Reinforcing Steel for Cast-In-Place Concrete Structures
|
|
- Logan Baldwin
- 5 years ago
- Views:
Transcription
1 SECTION REINFORCING STEEL PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes the following: 1. Reinforcing Steel for Cast-In-Place Concrete Structures PART 2- PRODUCTS 2.1 MATERIALS A. Reinforcing Steel for Concrete Structures shall be in accordance with section of the MoDOT Standard Spec. All reinforcement shall be uncoated. PART 3- EXECUTION 3.1 CONSTRUCTION A. Furnishing and placement of Reinforcing Steel for Concrete Structures shall be in accordance with section 706 of the MoDOT Standard Spec. 1. Any reference to method of measurement and basis of payment included in the MoDOT Standard Spec. DOES NOT apply to this section. END OF SECTION
2 THIS PAGE INTENTIONALLY LEFT BLANK
3 SECTION CAST-IN-PLACE CONCRETE PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes the following: 1. Concrete for existing substructure modifications to the abutments and piers 2. Concrete for Approach Rail Piers 3. New substructure concrete 4. Adhesives for concrete anchorage or rebar anchorage 1.3 ACTION SUBMITTALS A. Mix Design B. Concrete Work Plan which includes concrete placement methods, provisions for hot and cold weather concreting and curing. PART 2- PRODUCTS 2.1 MATERIALS A. Concrete shall be in accordance with section 501 of the MoDOT Standard Spec. Concrete shall be class B-1 Concrete with f' c = 4,000 psi unless otherwise noted. Concrete shall be class A-1 Concrete with f'c = 4,000 psi for the pier repair details on the following sheets: 1. S S S S
4 B. Adhesives for Rebar Dowels, and Threaded Rod Anchors: 1. Shall be an injectable, two component, epoxy based anchoring adhesive formula. 2. Shall be approved for exterior use. 3. Shall be code listed for cracked and uncracked concrete per an ICC-ES report. 4. Shall meet the requirements of ACI with a minimum characteristic bond stress in cracked concrete of 750 psi for a 5/8" anchor using 2,500 psi concrete evaluated at a maximum short term temperature of 130 F and maximum long term temperature of ll0 F. 5. Shall be one of the following or an approved equal meeting the requirements of sections 1 through 3 directly above: A. Hit HY-200 Hilti, Inc South 122nd East A venue Tulsa, OK B. SET-XP Simpson Strong-Tie PO Box Pleasanton, CA C. AClOO+Gold Powers Fasteners, Iric. 2 Powers Lane Brewster, NY PART 3-EXECUTION 3.1 CONSTRUCTION A. Concrete construction shall be in accordance with section 703 of the MoDOT Standard Spec. 1. Any reference to method of measurement and basis of payment included in the MoDOT Standard Spec. DOES NOT apply to this section. B. Where new concrete is to be placed against existing concrete surfaces, the existing concrete shall be thoroughly cleaned. Surface cleaning shall remove all foreign matter, laitance, efflorescence and dirt by pressure washing with a minimum of 3,000 psi. C. Field Drilled Anchors 1. Adhesives shall be installed in accordance with manufacturer's recommendations. Holes shall be THOROUGHLY CLEANED in accordance with manufacturer's recommendations. 2. If reinforcement is encountered during drilling operations contractor shall cut or core the reinforcement encountered. END OF SECTION
5 SECTION PRECASTSTRUCTURALCONCRETEPANELS PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes the performance criteria, materials, design, production, and erection of precast structural concrete for the entire project. The work performed under this Section includes all labor, material, equipment, related services, and supervision required for the manufacture and erection of the precast structural concrete work shown on the Contract Drawings. B. This Section includes the following: 1. Precast Deck Panels 2. Neoprene between bottom of deck panels and structural steel. 3. Epoxy Adhesive used to adhere deck panels to neoprene. 4. Non-Shrink Grout for transverse shear keys on bridge Water Reactive Crystalline Admixture used in shear keys on bridge Penetrating Crystalline Cementitious Coating used in shear keys on bridge C. Related Sections include the following: 1. Section "Structural Steel for Bridges" material properties of embeds and hardware. D. Any reference to method of measurement and basis of payment included in the MoDOT Standard Spec. DOES NOT apply to this section. 1.3 ACTION SUBMITTALS A. Concrete Mix Design
6 B. Shop Drawings: 1. Detail fabrication of precast structural concrete units including connections at member ends and to each adjoining member. 2. Indicate locations, plan views, elevations, dimensions, tolerances, shapes, and cross sections of each unit, support conditions and types of reinforcement, including special reinforcement. 3. Indicate aesthetic intent including joints, rustications or reveals, and extent and location of each surface finish. 4. Indicate welded connections by AWS standard symbols. Show size, length, and type of each weld. 5. Detail loose and cast-in hardware, lifting and erection inserts, connections, and joints. Include Catalog Cut Sheets for any aftermarket products or the appropriate design calculations. 6. Indicate locations, tolerances and details of anchorage devices to be embedded in or attached to structure or other construction. 7. Indicate location of each precast structural concrete member by same identification mark placed on unit. 8. Indicate relationship of precast structural concrete members to adjacent materials, and adjacent memebers. 9. Indicate locations and details of joint treatment. 10. Design Modifications: If design modifications are proposed to meet performance requirements and field conditions, notify the Engineer and submit Shop Drawings. Do not affect the appearance, durability or strength of members when modifying details or materials. Maintain the general design concept when altering size of members and alignment. 11. No work or ordering of materials for this item shall be done until the submittal has been approved by the engineer. C. Deck Panel Erection Plan: refer to Deck Panel Erection Notes and Tolerances on sheet G-1 01 of the plans for a general discussion of minimum requirements for the Deck Panel Erection Plan. 1. No work or ordering of materials for this item shall be done until the submittal has been approved by the engineer. D. Non-shrink grout technical data sheet E. Water Reactive Crystalline Admixture technical data sheet F. Penetrating Crystalline Cementitious Coating technical data sheet G. Neoprene Technical Data Sheet H. Epoxy Adhesive Technical Data Sheet 2
7 1.4 INFORMATIONAL SUBMITTALS A. Welding Certificates: Copies of certificates for Welding Procedure Specifications (WPS) with the supporting Procedure Qualification Record (PQR)( if required by AWS), and the appropriate AWS Welder Certifications. B. Fabricator Qualifications C. Concrete Break Test results shall be submitted to Owner. D. Reinforcement Certifications 1.5 QUALITY ASSURANCE A. Fabricator Qualifications: A firm that complies with the following requirements and is experienced in producing precast structural concrete units similar to those indicated for this Project and with a record of successful in-service performance. 1. Assumes responsibility for engineering precast structural concrete units to comply with performance requirements. This responsibility includes preparation of Shop Drawings. 2. Participates in PC I' s Plant Certification program at the time of bidding and is designated a PCI-certified plant for Group B, Category Bl -Precast Bridge Products (No Prestressed Reinforcement) 3. Has sufficient production capacity to produce required members without delaying the Work. 4. Certification shall be maintained throughout the production of the precast structural concrete units. Production shall immediately stop if at any time the fabricator's certification is revoked, regardless of the status of completion of contracted work. Production will not be allowed to re-start until the necessary corrections are made and certification has been re-established. In the event certification(s) can not be reestablished in a timely manner, causing project delays, the fabricator, at no additional cost, will contract out the remainder of the units to be manufactured at a PCI certified plant. B. Design Standards: Comply with ACI 318 (ACI 318M) and the design recommendations of PCI MNL 120, "PCI Design Handbook- Precast and Prestressed Concrete," applicable to types of structural precast concrete members indicated. C. Quality-Control Standard: For manufacturing procedures and testing requirements and quality control recommendations for types of members required, comply with PCI MNL 116, "Manual for Quality Control for Plants and Production of Structural Concrete Products." 3
8 H. Welding: Qualify procedures and personnel according to A WS D 1.1/D 1.1M, "Structural Welding Code - Steel" and A WS D 1.5/D 1.5M, "Bridge Welding Code". I. Preinstallation Conference: Conduct conference to comply with requirements in Section "Coordination." 1.6 DELIVERY, STORAGE, AND HANDLING A. Deliver all structural precast concrete members in such quantities and at such times to assure compliance with the agreed upon project schedule and setting sequence to ensure continuity of installation. B. Handle and transport members in a manner to avoid excessive stresses that could cause cracking or other damage. C. Store units with adequate dunnage and bracing, and protect units to prevent contact with soil, staining, and to control cracking, distortion, warping or other physical damage. D. Unless otherwise specified or shown on Shop Drawings, store members with dunnage across full width of each bearing point. E. Place stored members so identification marks are clearly visible, and units can be inspected. F. Place dunnage of even thickness between each member. G. Lift and support members only at designated points indicated on the Shop Drawings. 1.7 SEQUENCING A. Furnish loose connection hardware and anchorage items to be embedded in or attached to other construction without delaying the Work. Provide locations, setting diagrams, templates, instructions, and directions, as required, for installation. PART 2- PRODUCTS 2.1 FORM MATERIALS A. Forms: Rigid, dimensionally stable, nonabsorptive material, warp and buckle free, that will provide precast concrete surfaces within fabrication tolerances indicated; nonreactive with concrete and suitable for producing required surface finishes. 4
9 B. Form-Release Agent: Commercially produced form-release agent that will not bond with, stain or affect hardening of precast concrete surfaces and will not impair subsequent surface or joint treatments of precast concrete. 2.2 STEEL REINFORCEMENT MATERIALS A. Reinforcment shall be in accordance with section of the MoDOT standard Spec. All reinforcement shall be uncoated except as follows: a. Bridge 3153 reinforcing bar shall be epoxy coated in accordance with section of the MoDOT Standard Spec. B. Supports: Use bolsters, chairs, spacers, and other devices for spacing, supporting, and fastening reinforcing bars in place according to PCI MNL CONCRETE MATERIALS A. Concrete shall be in accordance with section and 501 of the MoDOT standard Spec. B. Concrete shall be Class A-1. C. Compressive Strength (28 Days): 6000 psi minimum. 2.4 EPOXY ADHESIVE A. Epoxy Adhesive for bonding Neoprene to Deck Panels: 1. Shall meet specification ASTM C-881 Types I and IV Class B. 2. Shall possess a minimum slant shear bond strength at 2 days of 1700 psi per ASTM C Shall be a two component epoxy approved by the manufacturer for bonding concrete to neoprene smfaces. 4. Shall be one of the following or an approved equal meeting the requirements of sections 1 through 3 directly above: A. Sikadur 31, Hi-Mod Gel Sika Corporation 201 Polito A venue B. Rezi-Weld Gel Paste State Lyndhurst, NJ W.R. Meadows, Inc. C. Pro-Poxy 200 P.O. Box 338 Hampshire, IL Dayton Superior Corporation 1125 Byers Road Miamisburg, OH
10 2.5 NEOPRENE AND OTHER ACCESSORIES A. Provide the neoprene pads between the precast deck panels and steel surface meeting the requirements of Shore A- 50 Durometer and in accordance with Section of the MoDOT Standard Spec. B. Erection Accessories: Provide clips, hangers, high density plastic or steel shims, and other accessories required to install structural precast concrete members. C. Welding Electrodes: E8018C3 Electrodes and comply with AWS standards for steel type and/or alloy being welded. 2.6 GROUTMATERIALS A. Nonshrink Grout: Premixed, prepackaged, non-ferrous aggregate grout containing selected silica sands, portland cement, shrinkage-compensating agents, plasticizing and water-reducing agents, complying with ASTM C 1107, Grade A for drypack and Grades B and C for flowable grout and of consistency suitable for application with a 30-minute working time. Water-soluable chloride ion content of grout less than 0.06 percent chloride ion by weight of cement when tested in accordance with ASTM C1218/C1218M. Non-shrink Grout shall be mixed with water and Water Reactive Crystalline Admixture in the dosage prescribed by the Water Reactive Crystalline Admixture manufacturer. 2.7 WATER REACTIVE CRYSTALLINE ADMIXTURE A. Shall be a hydrophilic crystalline permeability reducing admixture for concrete exposed to hydrostatic pressure (PRAH) in accordance with ACI212.3R-10. B. Shall have no leakage after 14 days when pressure tested at 150 psi (350ft. water head) in accordance with U.S. Almy Corp of Engineers CRD-C C. Shall be one of the following or an approved equal: 1. AQUAFIN-IC ADMIX Aquafin Inc. 505 Blue Ball Rd. #160 Elkton, MD XYPEX ADMIX C-500NF Xypex Chemical Corporation Mayfield Place Richmond, British Columbia V6V 2G9 Canada 3. Krystol Internal Membrane (KIM) KRYTON International Inc East Kent Avenue Vancouver, British Columbia, V5P 2S8 Canada 6
11 2.8 PENETRATING CRYSTALLINE CEMENTITIOUS COATING A. Shall be a hydrophilic crystalline cementitious surface applied waterproofing which reacts with un-hydrated cement particles in the base concrete to produce crystals that grow into capillary voids and minor cracks within the base concrete. B. Shall seal static cracks up to 1/64" in width that occur after application of the coating and when exposed to water. C. Shall resist hydrostatic pressure of at least 71 psi (164ft. water head) when tested to DIN 1048 Part-5 direct water penetration test. D. Shall be one of the following or an approved equal: 1. AQUAFIN-IC Aquafin Inc. 505 Blue Ball Rd. #160 Elkton, MD XYPEX CONCENTRATE Xypex Chemical Corporation Mayfield Place Richmond, British Columbia V 6V 2G9 Canada 3. Krystol T1 & T2 KRYTON International Inc East Kent A venue Vancouver, British Columbia, V5P 2S8 Canada 2.9 FORM FABRICATION A. Form: Accurately construct forms, mortar tight, of sufficient strength to withstand pressures due to concrete placement, vibration operations, and temperature changes. Coat contact smfaces of forms with release agent before reinforcement is placed. Avoid contamination of reinforcement by release agent. B. Maintain forms to provide completed structural precast concrete members of shapes, lines, and dimensions indicated in Contract Documents, within fabrication tolerances specified. 1. Edge and Corner Treatment: Uniformly chamfered or as built-in on standard forms FABRICATION A. Cast-in Anchors, Inserts, Plates, Angles, and Other Anchorage Hardware: Fabricate anchorage hardware with sufficient anchorage and embedment to comply with design requirements. Accurately position for attachment of loose hardware and secure in place during precasting operations. Locate anchorage hardware where it does not affect position of main reinforcement or concrete placement. Do not relocate embeds in members unless approved by Engineer. 7
12 1. Weld headed stud anchors used for anchorage according to AWS Dl.l/Dl.lM and AWS C5.4, "Recommended Practices for Stud Welding." B. Furnish loose hardware items including steel plates, clip angles, seat angles, anchors, dowels, hangers, and other hardware shapes for securing precast concrete members to supporting and adjacent construction. C. Cast-in reglets, slots, and other accessories in structural precast concrete members as indicated on Contract Drawings. D. Reinforcement: Comply with recommendations in PCI MNL 116 for fabricating, placing, and supporting reinforcement. 1. Clean reinforcement of loose rust and mill scale, earth, and other materials that reduce or destroy the bond with concrete. When damage to epoxy coated reinforcing exceeds limits specified in ASTM A 775/A 775M, repair with patching material compatible with coating material and epoxy coat bar ends after cutting. 2. Accurately position, support, and secure reinforcement against displacement during concrete-placement and consolidation operations. Locate and support reinforcement by plastic tipped or corrosion resistant metal or plastic chairs, runners, bolsters, spacers, hangers, and other devices for spacing, supporting, and fastening reinforcing bars and welded wire reinforcement in place according to PCI MNL Place reinforcing steel to maintain at least% in. (19 mm) minimum concrete cover, or minimum cover as shown on the plans. Provide cover requirements in accordance with ACI 318 (ACI 318M) when units are exposed to corrosive environment or severe exposure conditions. Arrange, space, and securely tie bars and bar supports to hold reinforcement in position while placing concrete. E. Comply with requirements in PCI MNL 116 and in this Section for measuring, mixing, transporting, and placing concrete. After concrete hatching, no additional water may be added. F. Place concrete in a continuous operation to prevent cold joints or planes of weakness from forming in precast concrete members. G. Thoroughly consolidate placed concrete by vibration without dislocating or damaging reinforcement and built-in items, and minimize pour lines, honeycombing or entrapped air voids on surfaces. Use equipment and procedures complying with PCI MNL 116. H. Comply with PCI MNL 116 procedures for hot and cold-weather concrete placement. I. Identify pickup points of precast concrete members and orientation in structure with permanent markings, complying with markings indicated on Shop Drawings. Imprint or permanently mark casting date on each precast concrete member on a surface that will not show in finished structure. 8
13 J. Cure concrete, according to requirements in PCI MNL 116, by moisture retention without heat or by accelerated heat curing using live steam or radiant heat and moisture. Cure members until compressive strength is high enough to ensure that stripping does not have an effect on the performance or appearance of final product FABRICATION TOLERANCES A. Fabricate structural precast concrete members of shapes, lines and dimensions indicated, so each finished member complies with PCI MNL 135 product tolerances as well as position tolerances for cast-in items. Dimensional tolerances shall be according to "Bridge Deck Units" except as modified below: 1. b =Width (measured longitudinal to bridge) ±Ys" 2. c = Depth ±W' 3. Location of embed Bottom Plate Assembly ±W' longitudinal and transverse 4. Location of Side Plate and Embedded Rod Hf' longitudinal and vertical 5. Concrete Blackouts ± 1.4" transverse B. Panels will be rejected at the job site if found to be out of tolerance by the inspector FINISHES A. Concrete shall be struck off and thoroughly vibrated until concrete of a uniform and satisfactory density is attained. B. After surface irregularities have been removed, top surface of panels shall be tined transversely to bridge with a wire comb. Wire comb and texturing shall be in accordance with sections and of the MoDOT Standard Spec SOURCE QUALITY CONTROL A. Quality-Control Testing: Test and inspect precast concrete according to PCI MNL 116 requirements. B. Concrete Break Test results shall be submitted to Owner. PART 3- EXECUTION 3.1 PREPARATION A. Furnish loose connection hardware and anchorage devices for precast concrete members to be embedded in or attached to the structural steel before starting that Work. Provide locations, setting diagrams, templates and instructions for the proper installation of each anchorage device. 9
14 3.2 EXAMINATION A. Examine supporting structural steel and conditions for compliance with requirements for installation tolerances, bearing surface tolerances, and other conditions affecting precast concrete performance. B. Proceed with precast concrete installation only after unsatisfactory conditions have been corrected. 3.3 ERECTION A. Install loose clips, hangers, bearing pads, and other accessories required for connecting structural precast concrete members to supporting members and backup materials. B. Erect precast structural concrete level, plumb and square within the specified allowable erection tolerances. Provide temporary structural framing, shoring and bracing as required to maintain position, stability, and alignment of members until permanent connections are completed. 1. Install temporary steel or plastic spacing shims or bearing pads as precast concrete members are being erected. Surface weld steel shims to each other to prevent shims from separating. 2. Maintain horizontal and vertical joint alignment and uniform joint width as erection progresses. 3. Remove projecting lifting devices and use plastic patchcaps or sand-cement grout to fill voids within recessed lifting devices flush with surface of adjacent precast concrete surfaces when recess is exposed. C. Connect structural precast concrete members in position by bolting, welding, grouting, or as otherwise indicated on approved Shop (Erection) Drawings. Remove temporary shims, wedges, and spacers as soon as practical after connecting and/or grouting activities are completed. D. Welding: Comply with applicable A WS D 1.5/D 1.5M requirements for welding, welding electrodes, appearance of welds, quality of welds, and methods used in correcting welding work. 1. Protect structural precast concrete members and bearing pads from damage during field welding or cutting operations and provide noncombustible shields as required. 2. Welds not specified shall be continuous fillet welds, using not less than the minimum fillet as specified by A WS D 1.5/D 1.5M. 3. Visually inspect all welds critical to precast structural concrete connections. Visually check all welds for completion and remove, reweld or repair all defective welds, if services of A WS-certified welding inspector are not furnished by Owner. 10
15 E. At bolted connections, use upset threads, thread locking compound or other approved means to prevent loosening of nuts after final adjustment. 1. Where slotted connections are used, verify bolt position and tightness at installation. For sliding connections, properly secure bolt but allow bolt to move within connection slot. 2. Grouting or Dry-Packing Connections and Joints: Indicate joints to be grouted and any critical grouting sequences on Shop (Erection) Drawings. Grout open spaces at keyways, connections and joints where required or indicated. Provide reinforcing steel where indicated. Retain flowable grout in place until it gains sufficient strength to support itself. Fill joints completely without seepage to other surfaces. Alternatively, pack spaces with stiff dry pack grout material, tamping until voids are completely filled. Place grout and finish smooth, level, and plumb with adjacent concrete surfaces. Promptly remove grout material from exposed surfaces before it affects finishes or hardens. Keep grouted joints damp for at least 24 hours after initial set. F. Field cutting of precast, prestressed concrete members is not permitted without approval of the Engineer. G. Fasteners: Do not use drilled or power-actuated fasteners for attaching accessory items to precast, prestressed concrete members unless approved by Precast Engineer and Engineer of Record. 3.4 ERECTION TOLERANCES A. Erect structural precast concrete members level, plumb, square, and in alignment without exceeding the noncumulative erection tolerances ofpci MNL 135 except as modified below: d =Joint Width 1 /.t" ± W' 3.5 REPAIRS A. Repairs will be permitted provided structural adequacy, serviceability and durability of members and appearance are not impaired. B. Remove and replace damaged precast structural concrete members when repairs do not comply with specified requirements. 11
16 3.6 CLEANING A. Clean exposed smfaces of precast concrete members after erection and completion of joint treatment to remove weld marks, other markings, dirt, and stains. 1. Perform cleaning procedures, if necessary, according to precast concrete fabricator's recommendations. Protect adjacent work from staining or damage due to cleaning operations. 2. Do not use cleaning materials or processes that could change the appearance of exposed concrete finishes or damage adjacent materials. END OF SECTION
SECTION ARCHITECTURAL PRECAST CONCRETE. A. American Society for Testing and Materials (ASTM):
SECTION 03450 ARCHITECTURAL PRECAST CONCRETE PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 03100 - Concrete Formwork 2. 03200 - Concrete Reinforcement 3. 03300 - Cast-in-Place Concrete 4. 03600 -
More information***************************************************************************************************************
03450 ARCHITECTURAL PRECAST CONCRETE *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 03 45 13 ***************************************************************************************************************
More informationSECTION STRUCTURAL PRECAST HOLLOW CORE SLABS
PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish all labor, materials, equipment and incidentals to provide a complete structural precast hollow core slab system as shown on the Contract
More informationSTRUCTURAL PRECAST CONCRETE
SECTION 03410 STRUCTURAL PRECAST CONCRETE PART 1 GENERAL 1.01 SUMMARY A. Provide labor, materials, necessary equipment, services and included, but not limited to, related work to complete the structural
More informationGUIDE SPECIFICATIONS For STRUCTURAL PRECAST HOLLOW CORE SLABS SECTION 03410
GUIDE SPECIFICATIONS For STRUCTURAL PRECAST HOLLOW CORE SLABS SECTION 03410 Note to user: These guide specifications are provided by Mid- States Concrete Products as a service to you; they are NOT specific
More information***************************************************************************************************************
03410 STRUCTURAL PRECAST CONCRETE *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 03 41 00 ***************************************************************************************************************
More informationDesign Reference Sample: Sample of approved precast structural concrete color, finish, and texture, preapproved by Architect.
SECTION 034100 - PART 1 - GENERAL 1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this
More informationSECTION STRUCTURAL STEEL
SECTION 05120 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this
More information- PRECAST CONCRETE POTABLE WATER STORAGE TANKS
PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2
More informationSECTION ARCHITECTURAL PRECAST CONCRETE. C. Section Joint Sealers: Perimeter joints with sealant and backing.
SECTION 03451 ARCHITECTURAL PRECAST CONCRETE PART 1 GENERAL 1.01 SECTION INCLUDES A. Architectural precast concrete wall panels; with integral insulation. B. Supports, anchors, and attachments. C. Intermediate
More informationMezzanines By Design Page 1
SECTION 05120 STRUCTURAL STEEL PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions and Division 1 apply to this Section. 1.2 SUMMARY
More informationSECTION PRECAST STRUCTURAL PRETENSIONED CONCRETE
PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 03 41 33 PRECAST STRUCTURAL PRETENSIONED CONCRETE SPEC WRITER NOTE: Delete between //--// if not applicable to project. Also delete any other item or paragraph
More informationSECTION PRECAST CONCRETE COVER SYSTEM
SECTION 13500 PRECAST CONCRETE COVER SYSTEM PART 1 GENERAL 1.1 SYSTEM DESCRIPTION A. Design Criteria: 1. Precast manufacturer shall be responsible for structural design of individual precast components,
More informationSECTION COLD-FORMED METAL TRUSSES
SECTION 054400 COLD-FORMED METAL TRUSSES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More information1. Base plates, setting plates and anchor rods for columns. 8. Lintels if connected to structural steel columns.
PAGE 051200-1 SECTION 051200 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification sections,
More informationSECTION STRUCTURAL PRECAST CONCRETE
SECTION 03500 STRUCTURAL PRECAST CONCRETE PART 1 GENERAL 1.01 SUMMARY A. Section Includes. This section covers Prestressed or Precast concrete member construction, including product design not shown on
More information1. Cast-in place structural concrete including footers, foundations, and other non-slab applications. 2. Formwork 3. Reinforcement
SECTION 03 31 00 - CAST-IN-PLACE STRUCTURAL CONCRETE PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Cast-in place structural concrete including footers, foundations, and other non-slab applications.
More informationSPECIAL SPECIFICATION 2043 Brick Veneer on MSE Wall
2004 Specifications CSJ 0196-02-120 SPECIAL SPECIFICATION 2043 Brick Veneer on MSE Wall 1. Description. This Item shall govern for the furnishing of the materials and construction of brick veneers on abutment
More informationSTRUCTURAL STEEL FRAMING Section
PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Structural steel. 2. Grout. 1.2 DEFINITIONS A. Structural Steel: Elements of the structural frame indicated on Drawings and as described in AISC 303,
More information***************************************************************************************************************
03365 POST-TENSIONED CONCRETE *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 03 38 00. ***************************************************************************************************************
More informationSECTION COLD-FORMED METAL FRAMING
SECTION 05400 PART I - GENERAL 1.01 DESCRIPTION A. Scope: Work of this Section shall include all materials and installation necessary to provide all cold formed metal framing. B. This Section includes:
More informationCommission No Section
Commission No. 1511 Section 05120-1 PART ONE - GENERAL 1.1 DESCRIPTION A. Work Included: Structural steel and grout. Furnish, fabricate, mark for erection identification, pack, crate, or otherwise properly
More informationUPRR INDUSTRIAL LEAD BRIDGE T-WALL RETAINING WALL SYSTEM 5.0 x 7.5 UNITS DESIGN UNIT 018 WORK PACKAGE 04
UPRR INDUSTRIAL LEAD BRIDGE T-WALL RETAINING WALL SYSTEM 5.0 x 7.5 UNITS DESIGN UNIT 018 WORK PACKAGE 04 1. Description This work shall consist of the design, manufacture and construction of a T-WALL structure
More informationSECTION ARCHITECTURAL CAST STONE
PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 047200 ARCHITECTURAL CAST STONE A. RELATED DRAWINGS All drawings, to include supplemental drawings, instructions and conditions of this contract. B. RELATED
More informationSECTION METAL FABRICATIONS FOR STEAM UTILITY DISTRIBUTION
PAGE 055015-1 SECTION 055015 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification sections,
More informationSTRUCTURAL STEEL FRAMING
SECTION 05 12 00 - STRUCTURAL STEEL FRAMING PART 1 - GENERAL 1.1 SUMMARY A. Section includes 1. Structural steel framing 2. Structural steel framing required for support and framing of rooftop mechanical
More informationHARVEY MUDD COLLEGE TEACHING AND LEARNING CENTER SECTION Page 1 of 6 VOIDED CONCRETE SLAB
030111 Page 1 of 6 PART 1 - GENERAL 1.1 SUMMARY A. This Section specifies: 1. Voided concrete floor and roof slab system consisting of structural reinforced concrete containing hollow (bubbles) spherical
More informationA. Structural Steel: Elements of structural-steel frame, as classified by AISC 303, "Code of Standard Practice for Steel Buildings and Bridges.
SECTION 05 12 00 - STRUCTURAL STEEL FRAMING PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationADDENDUM NUMBER 3 AUGUST 18, Jackson County Utility Authority Project No Pascagoula/Moss Point WWTP Escatawpa WWTP Repairs
ADDENDUM NUMBER 3 AUGUST 18, 2016 Jackson County Utility Authority Project No. 20150619124 Pascagoula/Moss Point WWTP Escatawpa WWTP Repairs FROM: BURK-KLEINPETER, INC. ENGINEERS, ARCHITECTS, PLANNERS,
More informationTILT-UP PRECAST CONCRETE SANDWICH PANELS. A. Work includes, but is not limited to, the following:
PART 1 GENERAL 1.01 SUMMARY SECTION 03460 TILT-UP PRECAST CONCRETE SANDWICH PANELS A. Work includes, but is not limited to, the following: 1. Architectural precast concrete sandwich wall panels. 2. Integral
More information1. Cast-in-place concrete is specified in Section
SECTION 03 38 00 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section describes the requirements for furnishing and installing post-tensioned slabs, jacks, jacking and anchors at Parking Structure, and record
More informationSection REINFORCING STEEL
Section 03210 PART 1 GENERAL 1.01 SUMMARY This Section includes the furnishing and subsequent placing of reinforcing steel, deformed and smooth, chairs, ties, splicing devices, and other reinforcing accessory
More informationA. Section includes cast-in-place concrete, including reinforcement, concrete materials, mixture design, placement procedures, and finishes.
SECTION 033053 - CONCRETE PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSECTION STRUCTURAL REINFORCED POLYMER COMPOSITE PEDESTRIAN BRIDGE DECK
SECTION 06610 STRUCTURAL REINFORCED POLYMER COMPOSITE PEDESTRIAN BRIDGE DECK PART 1 GENERAL 1.1 SUMMARY A. A. This Section includes the requirements for furnishing and installing all Structural Reinforced
More informationSUNY GENESEO RED JACKET DINING HALL RENOVATION SECTION STRUCTURAL STEEL FRAMING
SUNY GENESEO 051200-1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationSECTION GLASS-FIBER-REINFORCED PRECAST CONCRETE
SECTION 03490 GLASS-FIBER-REINFORCED PRECAST CONCRETE PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSECTION TILT-UP PRECAST CONCRETE SANDWICH PANELS. A. Work includes, but is not limited to, the following:
PART 1 GENERAL 1.01 SUMMARY SECTION 03460 TILT-UP PRECAST CONCRETE SANDWICH PANELS A. Work includes, but is not limited to, the following: 1. Architectural precast concrete sandwich wall panels. 2. Integral
More informationSECTION (03410) - PRECAST STRUCTURAL CONCRETE
SECTION 03 45 00 (03410) - PRECAST STRUCTURAL CONCRETE PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Plant-Precast Structural Concrete Units, Including the Following: a. Hollow-Core Slab Units b.
More information5 Concrete Placement
5 Concrete Placement Testing Entrained Air Slump Strength Water/Cementitious Ratio Mixing Placing Concrete Compressive Test Specimens Curing De-Tensioning Multiple Strand Release Single Strand Release
More informationSECTION STRUCTURAL STEEL
SECTION 05120 PART I - GENERAL 1.01 DESCRIPTION A. Scope: Work under this Section shall include all materials and installation necessary to provide Structural Steel as shown and detailed on the Drawings
More informationSECTION FABRICATED ENGINEERED STRUCTURES. A. Pre-engineered, shop-fabricated structural steel building with formed purlin framing.
PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 13 34 00 FABRICATED ENGINEERED STRUCTURES A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1
More informationFacility Repairs - MCAS Cherry Point - Tank Farm A SECTION STRUCTURAL STEEL 05/14
SECTION 05 12 00 STRUCTURAL STEEL 05/14 PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the
More informationCSI MASTERFORMAT SPECIFICATIONS. krystol internal membrane (kim ) Section 03 & 07 - Integral Crystalline Waterproofing of Concrete
Concrete Waterproofing Admixture 1 of 5 krystol internal membrane (kim ) Section 03 & 07 - Integral Crystalline Waterproofing of Concrete PART 1 GENERAL 1.01 SUMMARY Section Includes: Furnishing of all
More informationSECTION INTERIOR STONE INTERIOR STONE
SECTION 04401- INTERIOR STONE 04401-1 PART ONE: GENERAL 1.1 Description INTERIOR STONE 1.1.1 Work of this Section, as shown or specified, shall be provided by the Interior Contractor/Vendor and shall be
More informationJONES AIRWAY, LLC CLEVELAND REGIONAL JETPORT SECTION STRUCTURAL STEEL
CLEVELAND REGIONAL JETPORT 05 1200-1 PART 1 - GENERAL SECTION 05 1200 STRUCTURAL STEEL 1.1 RELATED SPECIFICATION SECTIONS: A. Bolting of wood to steel, steel anchors for work of other trades, concrete
More informationSECTION CAST-IN-PLACE CONCRETE
SECTION 03300 CAST-IN-PLACE CONCRETE PART 1 GENERAL 1.01 SECTION INCLUDES A. The Contractor shall furnish all work and materials, including cement, sand and coarse aggregate, water, admixtures, curing
More informationDIVISION 5 METALS SECTION STRUCTURAL STEEL
DIVISION 5 METALS SECTION 05 12 00 PART 1 GENERAL 1.01 SUMMARY A. Section Includes: All labor and materials required to furnish and install the structural steel shown on the Drawings and required by these
More informationSECTION STRUCTURAL STEEL FRAMING
SECTION 05 1200 STRUCTURAL STEEL FRAMING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationTnemec 394 Proprietary Long Form Coatings Schedule
1.1 PRIMER Tnemec 394 Proprietary Long Form Coatings Schedule A. Primer: Tnemec Series 394 PerimePrime Aromatic Polyurethane Mio/Zinc filled Primer applied @ 2.5-3.5 mils DFT and conforming to the following
More informationSECTION STRUCTURAL METAL FRAMING
SECTION 05100 STRUCTURAL METAL FRAMING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Structural steel framing including lintels, shelf angles, bearing plates, anchor bolts and other items as shown on
More informationA. Product Data: For each type of cold-formed steel framing product and accessory.
SECTION 05400 - COLD-FORMED METAL FRAMING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Exterior non-load-bearing wall framing. 1.2 ACTION SUBMITTALS A. Product Data: For each type of cold-formed
More informationA. Drawings and general provisions of the contract, including General and Supplementary Conditions, apply to this section.
SECTION 03 01 30 MAINTENANCE OF CAST-IN-PLACE CONCRETE SECTION 03 01 40 MAINTENANCE OF PRECAST CONCRETE SECTION 03 01 50 MAINTENANCE OF CAST DECKS AND UNDERLAYMENT SECTION 03 01 60 MAINTENANCE OF GROUTING
More informationCONCRETE WORK CONCRETE WORK. Underground Electric Distribution Standards I. SCOPE APPLICABLE STANDARDS
Underground Electric Distribution Standards I. SCOPE This section includes the standards for concrete, reinforcing steel, formwork, concrete placement, curing, and construction joints. Concrete work for
More informationSECTION COLD-FORMED METAL FRAMING
SECTION 05 40 00 COLD-FORMED METAL FRAMING SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the
More informationSECTION COLD-FORMED METAL FRAMING
The Collective Voice of America s Steel Framing Industry The Steel Framing Industry Association (SFIA) is dedicated to expanding the market for cold-formed steel in construction through programs and initiatives
More informationSECTION Temperature Change: 120 deg F, ambient; 180 deg F, material surfaces.
PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following: 1. Handrails and guardrails. 1.2 PERFORMANCE REQUIREMENTS A. General: In engineering railings to withstand structural loads indicated, determine
More informationSection 708. PRESTRESSED CONCRETE
708.02 Section 708. PRESTRESSED CONCRETE 708.01. Description. This work consists of manufacturing and erecting prestressed concrete. 708.02. Materials. Provide materials in accordance with the following:
More informationPRESTON HEALTH SERVICES ARCHITECT'S NO MITCHELL-HOLLINGSWORTH NURSING & REHAB ADPH #B
SECTION 05 5213 - PIPE RAILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSECTION MISCELLANEOUS METALS
PART 1 GENERAL 1.1 WORK OF THIS SECTION A. Contractor shall provide all labor, materials, equipment and incidentals as shown, specified and required to furnish and install all miscellaneous metal fabrications
More informationMay 2017 Alterations to Buildings 1, 2, 3 & 9 Hudson County Prosecutor's Office Meadowview Campus Secaucus, New Jersey
SECTION 034100 - PRECAST STRUCTURAL CONCRETE PART 1 - GENERAL 1.1 SUMMARY A. Section is for precast structural concrete plank. 1.2 PERFORMANCE REQUIREMENTS A. Delegated Design: Design precast structural
More informationUNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:
SECTION 051200 - STRUCTURAL STEEL FRAMING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The provisions of the Contract and of the Contract documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Structural
More informationSECTION TILT-UP PRECAST CONCRETE. A. Work includes, but is not limited to, the following:
SECTION 03470 TILT-UP PRECAST CONCRETE PART 1 GENERAL 1.01 SUMMARY A. Work includes, but is not limited to, the following: 1. Precast wall panels. 2. Forms and casting beds. 3. Concrete. 4. Reinforcing
More informationMaster Specifications for Microcotta November 2017
SECTION 042130 - MICROCOTTA PART 1 - GENERAL 1.1 SUMMARY A. Provide Architectural Microcotta, cast architectural polymer resin units manufactured in accordance with the Contract Documents. 1.2 WORK INCLUDED
More informationSECTION ORNAMENTAL ALUMINUM RAILING
SECTION 05730 ORNAMENTAL ALUMINUM RAILING PART 1 GENERAL 1.1 SECTION INCLUDES A. Aluminum Pipe Railing 1.2 RELATED SECTIONS A. Section 03300 Cast-In-Place Concrete: Placement of sleeves cast in concrete.
More informationREINFORCED CONCRETE MASONRY SECTION
SECTION 04 22 02 - REINFORCED CONCRETE MASONRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 01 Specification
More informationCSI SPECIFICATIONS SURFACE-APPLIED CRYSTALLINE WATERPROOFING Section
SURFACE-APPLIED CRYSTALLINE WATERPROOFING Section 07 16 16 This section includes Krystol T1 crystalline waterproofing, applied to new or existing concrete substrates, above or below grade, on either dry
More informationSECTION VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT
SECTION 230548 - VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary
More informationSECTION SURFACE-APPLIED CRYSTALLINE WATERPROOFING AND CONCRETE REPAIR
SECTION PART 1 GENERAL 1.1 SECTION INCLUDES A. Surface-applied crystalline waterproofing treatment. B. Crystalline compounds for the repair of leaking cracks, holes and joints found in concrete. 1.2 RELATED
More informationBy CTS Cement Manufacturing Corp.
CSI SECTION 03 60 00 GROUTING 03 62 00 NON-SHRINK GROUTING 03 62 13 NON-METALLIC NON-SHRINK GROUTING High Flow, Non-Metallic, Multi-Purpose, Cementitious, Non-Shrink Grout EDITOR NOTE: The following guideline
More informationTCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II
SECTION 052100 - STEEL JOISTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections
More informationC. Miscellaneous Metal Fabricators are specified elsewhere in Division 5.
SECTION 05 1200 - STRUCTURAL STEEL FRAMING PART 1 - GENERAL 1.01 SUMMARY A. Extent of structural steel work is shown on drawings, including schedules, notes and details to show size and location of members,
More informationDIVISION 5 - STRUCTURAL STEEL AND IRON WORK
DIVISION 5 - STRUCTURAL STEEL AND IRON WORK SECTION 05100 STRUCTURAL METAL FRAMING PART 1.00 GENERAL 1.01 SCOPE OF WORK A. Work Included: 1. 2. Structural steel complete in place. Steel joists complete
More informationSECTION CONCRETE FORMWORK AND ACCESSORIES
SECTION 03100 CONCRETE FORMWORK AND ACCESSORIES Part 1 GENERAL 1.01 SUMMARY A. Furnish equipment, materials, and labor required for construction and removal of forms for the containment of concrete to
More informationHydrophilic Crystalline Waterproofing of Concrete-Admixture
Hydrophilic Crystalline Waterproofing of Concrete-Admixture Kryton International Inc. SECTION 03305 Hydrophilic Crystalline Waterproofing of Concrete Admixture PART 1 GENERAL 1.1 SECTION INCLUDES - A.
More informationDivision 03 Concrete Section includes various guidelines for general concrete use, curing, forming, reinforcing, finishing and concrete accessories.
Section includes various guidelines for general concrete use, curing, forming, reinforcing, finishing and concrete accessories. This design guideline is written to the designer of record (DOR). This guideline
More informationSPECIFICATION FOR REINFORCED SOIL WALL
SPECIFICATION FOR REINFORCED SOIL WALL 1.0 EXTENT OF WORK The work shall consist of Reinforced Soil walls built in accordance with this specification and in conformity with the lines, levels and details
More informationSection 708. PRESTRESSED CONCRETE BEAMS Description. Manufacture and erect prestressed concrete beams.
708.0 Section 708. PRESTRESSED CONCRETE BEAMS 708.0 Description. Manufacture and erect prestressed concrete beams. 708.02 Materials. Use materials meeting the following. Mortar and Grout... 702 Cement...
More informationCSC SPECIFICATIONS SURFACE-APPLIED CRYSTALLINE WATERPROOFING Section
SURFACE-APPLIED CRYSTALLINE WATERPROOFING Section 07 16 16 This section includes Krystol T1 & T2 crystalline waterproofing, applied to new or existing concrete substrates, above or below grade, on either
More informationCSI SPECIFICATIONS SURFACE-APPLIED CRYSTALLINE WATERPROOFING Section
SURFACE-APPLIED CRYSTALLINE WATERPROOFING Section 07 16 16 This section includes Krystol T1 & T2 crystalline waterproofing, applied to new or existing concrete substrates, above or below grade, on either
More informationSECTION MISCELLANEOUS METAL FABRICATIONS
SECTION 05500 PART I - GENERAL 1.01 DESCRIPTION: A. Scope: Work under this Section shall include all material and installation necessary to provide Miscellaneous Metal Fabrications, as shown and detailed
More informationSECTION 1 TERMS, DEFINITIONS, ABBREVIATIONS, UNITS OF MEASURE, AND SYMBOLS 1-3 ABBREVIATIONS Common Usage.
SECTION 1 TERMS, DEFINITIONS, ABBREVIATIONS, UNITS OF MEASURE, AND SYMBOLS 1-3 ABBREVIATIONS. 1-3.2 Common Usage. Abbreviations Word or Words PAV.Pressure Aging Vessel PCC..Portland Cement Concrete PE.Polyethylene
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 096623 - RESINOUS MATRIX TERRAZZO FLOORING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSECTION BRICK MASONRY ASSEMBLIES
PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following: 1. Face brick. 2. Mortar and grout. 3. Ties and anchors. 4. Miscellaneous masonry accessories. 1.2 SUBMITTALS A. Product Data: For each type
More informationSECTION MISCELLANEOUS CAST-IN-PLACE CONCRETE
SECTION 033053- MISCELLANEOUS CAST-IN-PLACE CONCRETE PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationSECTION EMBEDDED CMU/SPLIT FACE ARCHITECTURAL PRECAST/SITECAST CONCRETE. A. Site Cast or Tilt-Up CMU/Split Face Concrete Panels.
SECTION 03460 EMBEDDED CMU/SPLIT FACE ARCHITECTURAL PRECAST/SITECAST CONCRETE PART 1 GENERAL 1.1 SECTION INCLUDES A. Site Cast or Tilt-Up CMU/Split Face Concrete Panels. B. Shop/Plant Cast CMU/Split Face
More informationTECHNICAL SPECIFICATION
TECHNICAL SPECIFICATION ITEM 03100 CONCRETE FORMWORK 1.0 GENERAL 1.1 DESCRIPTION This section defines requirements and limitations for design, construction, erection, and removal of concrete formwork for
More informationSPECIFICATIONS PRECAST PRESTRESSED CONCRETE PART 1 GENERAL 1.6.2.5 Openings, inserts and related reinforcement 1.6.3 Each drawing submitted to bear stamp of 1.1 Related Work qualified Professional Engineer
More informationMulti-Institutional Academic Health Science & Research Center Evansville, IN
SECTION 07 1616 - CRYSTALLINE WATERPROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION DRILLED CONCRETE PIERS AND SHAFTS
SECTION 31 63 29 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationSECTION 415 REINFORCING FOR CONCRETE
SECTION 415 REINFORCING FOR CONCRETE Module 5 August 2018 Release 10, Module 5 1 Release 10, August 2018 5-1 415 1 Description Furnish and place steel and fiber reinforced polymer (FRP) reinforcing of
More information1. Temperature Change: 120 deg F (67 deg C), ambient; 180 deg F (100 deg C), material surfaces.
SECTION 05500- METAL FABRICATIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION EXPANSION CONTROL
SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationSECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS
SECTION 260548 - VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Isolation pads. 2. Spring isolators. 3. Restrained spring isolators. 4. Channel
More informationK. ASTM F436- Standard Specification for Hardened Steel Washers; 2011.
DIVISION 05 METALS 05 12 00 STRUCTURAL STEEL FRAMING PART 1 GENERAL 1.1 SECTION INCLUDES A. Structural steel framing members, support members. 1.2 RELATED REQUIREMENTS A. Section 05 50 00 - Metal Fabrications:
More informationSECTION PRECAST STRUCTURAL PRETENSIONED CONCRETE
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 03 41 33 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // -- // if not applicable to project. Also delete any other item or paragraph
More informationColumbia Public Schools Shepard Elementary School Classroom Building Addition PWA I 1 CONCRETE REINFORCEMENT ~4 ASSURANCE
B. Supports and accessories for steel reinforcement. 1.02 SECTIONS A. Section 03300- Cast-in-Place Concrete. 1.03 SUBMITTALS A. See Section 01300- Administrative Requirements, for submittal procedures.
More informationSECTION CAST-IN-PLACE CONCRETE
McClellan Blakemore Architects New Warehouse Facility for SECTION 03300 CAST-IN-PLACE CONCRETE PART 1 GENERAL 1.01 SECTION INCLUDES A. Concrete formwork. B. Floors and slabs on grade. C. Concrete floor
More informationGUIDE SPECIFICATION SECTION CRYSTALLINE WATERPROOFING
GUIDE SPECIFICATION SECTION 071616 PART 1 - GENERAL CRYSTALLINE WATERPROOFING 1.1 SECTION INCLUDES A. Cementitious Crystalline Waterproofing on concrete structures and surfaces as shown on drawings and
More informationSECTION EXPANSION CONTROL
SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More information