Kuhlman Electric Corporation Volt Instrument Transformers

Size: px
Start display at page:

Download "Kuhlman Electric Corporation Volt Instrument Transformers"

Transcription

1 Kuhlman Electric Corporation 5000 Volt Instrument Transformers

2 5000 Volt Table of Contents Description Model Page 3 ½ Window CT Single, Dual & Multi Ratio (High Accuracy Available) TD ½ Window CT Single, Dual & Multi Ratio (High Accuracy Available) RMB(X) Indoor, Wound, Dry-Type VT Y Burden U/VCD Indoor, Wound, Dry-Type CT Standard Range CID

3 TD 994 Current Transformer Indoor/Outdoor 5kV, 60kV BIL, Single, Dual & Multi Ratios Molded Resin, Window Type, Metering/Relaying application The TD-994 indoor/outdoor, window-type current transformer is rated for use on 5,000 volt systems with 60kV BIL. Primary current ratios are available from 50:5 to 4000:5 at 60 Hertz (Hz) with a of up to 4.0. This dry-type, solid-cast current transformer will operate with high accuracy for metering or relay applications Volt mechanical description The core and coil assembly is wound and encapsulated in a molded cast resin with a standard 3.44 window to provide high withstand capabilities. An optional primary bus bar with NEMA 4-hole pads can also be provided (4000A max). The secondary terminals are ¼ -20 copper studs with associated hardware located inside a removable terminal box with two (2) 1 NPT conduit hubs. accuracy performance The TD-994 will operate with 0.3 Class accuracy for metering with burdens of B0.1 to B1.8 and up to C400 for some relay applications. The transformer is accurate through its, and can be used continuously to this level. testing The unit is individually tested per the IEEE C57.13 standard, including applied and induced voltage, accuracy and polarity. Partial discharge testing is performed to guarantee the unit is free of partial discharge through 120% of the nominal system voltage. The unit is tested above operating voltage for traces of corona. A corona free label is bonded to the completed transformer as a guarantee of trouble-free service. mounting The TD is designed for mounting in an upright, underhung or cantilever position. Mounting slots are provided on the aluminum base. ORDERING INFO FOR TD-994 Ratio Catalog Number* Accuracy/Burden Metering Relay options The TD is available with a primary bus bar kit. The unit can be offered in single or dual core designs. Contact factory for other needs. HIGH ACCURACY N/A Catalog Number Burden Accuracy Range 100:5 B130100S1 0.3 B0.1 C :5 B130200S1 0.3 B0.2 C :5 B130300S1 0.3 B0.2 C :5 B130400S1 0.3 B0.5 C :5 B130500S1 0.3 B0.5 C :5 B130600S1 0.3 B0.5 C :5 B130800S1 0.3 B0.9 C :5 B131000S1 0.3 B1.8 C :5 B131200S1 0.3 B1.8 C :5 B131500S1 0.3 B1.8 C :5 B132000S1 0.3 B1.8 C :5 B132500S1 0.3 B1.8 C :5 B133000S1 0.3 B1.8 C :5 B134000S1 0.3 B1.8 C /400:5 B130200D1 0.3 B0.2/B0.5 C20/C40 2.0/ /600:5 B130300D1 0.3 B0.2/B0.5 C50/C / /800:5 B130400D1 0.3 B0.5/B0.9 C75/C / /1200:5 B130600D1 0.3 B0.5/B1.8 C100/C / /2000:5 B131000D1 0.3 B1.8/B1.8 C100/C / /3000:5 B131500D1 0.3 B1.8/B1.8 C100/C / /4000:5 B132000D1 0.3 B1.8/B1.8 C100/C / Available in multi-ratio designs (full tap ratings same as single ratio above). - 1 Second Thermal/Mechanical s: 60x full winding I nom / Unlimited mechanical. - Available with a primary bar kit (maximum 4000A). Change last digit of catalog from 1 to 3. * IC Approval AE-1335 is noted by bold catalog number. 3

4 5000 Volt TD 994 Current Transformer 4 NOTE: OUTLINES ARE FOR REFERENCE ONLY. CONTACT FACTORY FOR ACTUAL DESIGN DRAWINGS.

5 RMB(X) 631 Current Transformer Indoor/Outdoor 5kV, 60kV BIL, Single, Dual & Multi Ratios Molded Resin, Window Type, Metering/Relaying application The RMB(X)-631 indoor/outdoor, window-type current transformer is rated for use on 5,000 volt systems with 60kV BIL. Primary current ratios are available from 200:5 to 4000:5 at 60 Hertz (Hz) with a of up to 4.0. This dry-type, solid-cast current transformer will operate with high accuracy for metering or relay applications Volt mechanical description The core and coil assembly is wound and encapsulated in a molded cast resin with a standard 3 ½ window (other sizes from 2 to 6 ) to provide high withstand capabilities. An optional primary bus bar with NEMA 4-hole pads can also be provided (4000A max). The secondary terminals are ¼ -20 copper studs with associated hardware located inside a removable terminal box with two (2) 1 NPT conduit hubs. accuracy performance The RMB-631 will operate with 0.3 Class accuracy for metering with burdens of B0.1 to B1.8 and up to C800 for some relay applications. The transformer is accurate through its, and can be used continuously to this level. The RMBX-631 will operate with 0.15 Class high accuracy for metering applications with burdens of B0.1 to B1.8. The transformer maintains 0.3 accuracy from 1% of I nom through its, and can be used continuously to this level (for 0.15 accuracy range, see ratings specifi c to each ratio). mounting The RMB is designed for mounting in an upright, underhung or cantilever position. Open end slots are provided on the aluminum mounting legs. ORDERING INFO FOR RMB-631 Catalog Accuracy/Burden (3.5 ID) Ratio* Number* Metering Relay* testing The unit is individually tested per the IEEE C57.13 standard, including applied and induced voltage, accuracy and polarity. Partial discharge testing is performed to guarantee the unit is free of partial discharge through 120% of the nominal system voltage. The unit is tested above operating voltage for traces of corona. A corona free label is bonded to the completed transformer as a guarantee of trouble-free service. options The RMB is available with a primary bus bar kit. Contact factory for other needs. HIGH ACCURACY RMBX-631 Catalog Number Burden 0.15/0.3 Acc Range 200:5 B180200S1 0.3 B0.2 C :5 B180300S1 0.3 B0.5 C :5 B180400S1 0.3 B0.9 C B180400X1 B0.5/B /4 to 1200A :5 B180500S1 0.3 B1.8 C B180500X1 B0.5/B /5 to 2000A :5 B180600S1 0.3 B1.8 C B180600X1 B0.9/B /6 to 2400A :5 B180800S1 0.3 B1.8 C B180800X1 B0.9/B /8 to 3200A :5 B181000S1 0.3 B1.8 C B181000X1 B to 4000A :5 B181200S1 0.3 B1.8 C B181200X1 B to 4800A :5 B181500S1 0.3 B1.8 C B181500X1 B to 4500A :5 B182000S1 0.3 B1.8 C B182000X1 B to 4000A :5 B182500S1 0.3 B1.8 C :5 B183000S1 0.3 B1.8 C :5 B184000S1 0.3 B1.8 C :5 MR B180600M1 0.3 B1.8 C :5 MR B181200M1 0.3 B1.8 C :5 MR B182000M1 0.3 B1.8 C :5 MR B183000M1 0.3 B1.8 C :5 MR B184000M1 0.3 B1.8 C Available in dual-ratio designs (ratings same as single ratio above, change catalog digit S to D ). * Units can also be supplied with C800 ratings (add -512 to the end of the catalog number). - 1 Second Thermal/Mechanical s: 80x full winding I nom / Unlimited mechanical. - Available with a primary bar kit (maximum 4000A). Change last digit of catalog from 1 to 3. 5

6 5000 Volt RMB(X) 631 Current Transformer 6 NOTE: OUTLINES ARE FOR REFERENCE ONLY. CONTACT FACTORY FOR ACTUAL DESIGN DRAWINGS.

7 U/VCD 7 Voltage Transformer Indoor 5kV, 60kV BIL, Single Ratios Molded Epoxy, Wound Type, Metering/Relaying application The U/VCD-7 indoor voltage transformer is rated for use on 5,000 volt systems with 60kV BIL. Primary voltage ratios are available from 20:1 to 40:1 for use on 5,000 volt systems, at 60 Hertz (Hz). This dry-type, solid-cast voltage transformer will operate with high accuracy for metering or relay applications Volt mechanical description The core and coil assembly is wound and encapsulated in a high dielectric strength epoxy resin to provide high withstand capabilities. The primary terminal(s) are screw-type, tin-plated, for #12 to #8 AWG conductors. The clamp-type post secondary terminals have ¼ -20 slotted screws and associated hardware embedded in epoxy resin on the front side of the transformer. In addition, a ground terminal is provided near the secondary terminals on the base plate. accuracy performance The U/VCD-7 will operate with 0.3 Class accuracy for metering and relay applications with burdens of 0, W, X, M and Y. The transformer is accurate from 90% to 110% of rated primary voltage. mounting The U/VCD is designed for mounting inside switchgear or other indoor applications in an upright, underhung or cantilever position. testing The unit is individually tested per the IEEE C57.13 standard, including applied and induced voltage, accuracy and polarity. Partial discharge testing is performed to guarantee the unit is free of partial discharge through 120% of the nominal system voltage. options Units are available in single or double bushing models. Primary terminal(s) can be equipped with fuse clip(s) and fuse(s). The unit can be offered in switchgear format with primary terminal(s) toward the back. Contact factory for other needs. ORDERING INFO FOR U/VCD-7 Ratio Primary Secondary HIGH ACCURACY N/A Catalog Number* Accuracy/ Catalog Number Accuracy/ 1 Bushing 2 Bushing Burden 2 Bushing Only Burden 20: B916G020S0 B916020S ,W,X,M,Y : B916030S ,W,X,M,Y : B916035S ,W,X,M,Y : B916040S ,W,X,M,Y Thermal Burden (Typical): 750VA. - Overvoltage : 1.1x cont. - For fuse clips, add a C per clip needed at the end of the catalog. - For fuses, add an F per fuse needed at the end of the catalog. * IC Approval AE-1378 noted by bold catalog number. 7

8 5000 Volt U/VCD 7 Voltage Transformer 8 NOTE: OUTLINES ARE FOR REFERENCE ONLY. CONTACT FACTORY FOR ACTUAL DESIGN DRAWINGS.

9 CID 7 Current Transformer Indoor 5kV, 60kV BIL, Single Ratios Molded Epoxy, Wound Type, Metering/Relaying application The CID-7 indoor current transformer is rated for use on 5,000 volt systems with 60kV BIL. Primary current ratios are available from 5:5 to 600:5 at 60 Hertz (Hz) with a of up to 1.5. This dry-type, solid-cast current transformer will operate with high accuracy for metering or relay applications Volt mechanical description The core and coil assembly is wound and encapsulated in a high dielectric strength epoxy resin to provide high withstand capabilities. The primary terminals are fl at, tin-plated copper with standard NEMA 2-hole pattern suitable for various size conductors. The clamp-type post secondary terminals have ¼ - 20 slotted screws and associated hardware embedded in epoxy resin on the front side of the transformer. The ground terminal is provided near the secondary terminals on the base plate. accuracy performance The CID-7 will operate with 0.3 Class accuracy for metering with burdens of B0.1 to B0.5 and C50 for relay applications. The transformer is accurate through its, and can be used continuously to this level. mounting The CID is designed for mounting inside switchgear or other indoor applications in an upright, underhung or cantilever position. testing The unit is individually tested per the IEEE C57.13 standard, including applied and induced voltage, accuracy and polarity. Partial discharge testing is performed to guarantee the unit is free of partial discharge through 120% of the nominal system voltage. options Contact factory for other needs. ORDERING INFO FOR CID-7 Catalog Ratio Number* Accuracy/Burden Metering Relay HIGH ACCURACY N/A Catalog Number Accuracy/ Burden 5:5 B S0 0.3 B0.5 C :5 B S0 0.3 B0.5 C :5 B S0 0.3 B0.5 C :5 B S0 0.3 B0.5 C :5 B S0 0.3 B0.5 C :5 B S0 0.3 B0.5 C :5 B S0 0.3 B0.5 C :5 B S0 0.3 B0.5 C :5 B S0 0.3 B0.5 C :5 B S0 0.3 B0.5 C :5 B S0 0.3 B0.5 C :5 B S0 0.3 B0.5 C :5 B S0 0.3 B0.5 C :5 B S0 0.3 B0.5 C :5 B S0 0.3 B0.5 C :5 B S0 0.3 B0.5 C Second Thermal/Mechanical Minimum: 69x/186x I nom (37.8kA/102kA for above 300:5). Contact factory for actuals. * IC Approval AE-1392 noted by bold catalog number. 9

10 5000 Volt CID 7 Current Transformer 10 NOTE: OUTLINES ARE FOR REFERENCE ONLY. CONTACT FACTORY FOR ACTUAL DESIGN DRAWINGS.

SECTION HIGH EFFICIENCY DISTRIBUTION TRANSFORMERS

SECTION HIGH EFFICIENCY DISTRIBUTION TRANSFORMERS SECTION 26 22 13 HIGH EFFICIENCY DISTRIBUTION TRANSFORMERS PART 1 GENERAL 1.1 WORK INCLUDED A. Dry-type, low-voltage, distribution transformers meeting US Department of Energy proposed Candidate Standard

More information

Standard of Practice - Campus Electrical Distribution System

Standard of Practice - Campus Electrical Distribution System A26.3 Standard of Practice - Campus Electrical Distribution System NOTE: Significant revisions or additions to the previous standards are highlighted in italics. GENERAL Designers shall verify that all

More information

SECTION MEDIUM VOLTAGE TRANSFORMERS

SECTION MEDIUM VOLTAGE TRANSFORMERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC Van Dam Street Long Island City, NY ELECTRIC METER SHOP DEPARTMENT

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC Van Dam Street Long Island City, NY ELECTRIC METER SHOP DEPARTMENT CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 48-05 Van Dam Street Long Island City, NY 11101 ELECTRIC METER SHOP DEPARTMENT METER ENGINEERING SPECIFICATION MES-350 REVISION 3 June 2016 EFFECTIVE DATE

More information

DISTRIBUTION TRANSFORMER SPECIFICATION #

DISTRIBUTION TRANSFORMER SPECIFICATION # DISTRIBUTION TRANSFORMER SPECIFICATION #1212.03 15kV Single Phase Submersible Transformer Stainless Steel 12/2/2011 Page 1 of 8 1. SCOPE This specification covers single-phase submersible transformers

More information

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

B. Provide liquid-filled secondary substation transformers as indicated on drawings. SECTION 26 12 13 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 26 05 00. B. Provide liquid-filled secondary substation transformers as indicated on drawings. 1.02 RELATED

More information

2/2 % ) Direct Acting Subminiature Solenoid Valves. 1/8" and 1/4" NPT. Features. Construction. Electrical

2/2 % ) Direct Acting Subminiature Solenoid Valves. 1/8 and 1/4 NPT. Features. Construction. Electrical ANSI Accredited Program PRODUCT CERTIFICATION 4 Direct Acting Subminiature Solenoid Valves /8" and /4" NPT / 856 -WAY Features -way normally closed operation Compact design Brass and 6 stainless steel

More information

roduct Scope: Substation

roduct Scope: Substation roduct Scope: Substation Three Phase or Single Phase, 50 or 60 Hz, 55ºC, 65ºC, 75ºC, 55ºC/65ºC, 55ºC/75ºC, 65ºC/75ºC Envirotemp FR3 fluid or Mineral Oil Three Phase: 300 12,000 kva Single Phase: 167 6,667

More information

Unit Price Labor. INSTALL 138KV DISCONNECT SWITCH WITH MOTOR OPERATOR AND AUXILIARY SWITCHES ON EXISTING STRUCTURE 1 ea.

Unit Price Labor. INSTALL 138KV DISCONNECT SWITCH WITH MOTOR OPERATOR AND AUXILIARY SWITCHES ON EXISTING STRUCTURE 1 ea. SUBSTATION B UPGRADE CONSTRUCTION MAJOR MATERIAL NOTES: Contractor to fill in line item column "Est. Qty." for items left blank. Construction Unit No. Description Est. Qty. Unit Labor 100 INSTALL 138KV

More information

Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008

Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008 Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008 (Above 1000V and up to 38kV for Surface Mining) Key Components of Specification:

More information

UNDERGROUND SERVICES SECONDARY

UNDERGROUND SERVICES SECONDARY Reference UNDERGROUND SERVICES SECONDARY Underground services secondary... U- 1 General requirements for underground service... U- 2 Name of parts for underground service... U- 3 Conduit layouts... U-

More information

SECTION HEAT TRACING FOR PLUMBING PIPING

SECTION HEAT TRACING FOR PLUMBING PIPING SECTION 22 05 33 HEAT TRACING FOR PLUMBING PIPING PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph not

More information

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

S. C. Electric Cooperative s Specification for a Single-Phase, Two Bushing Overhead Distribution Transformer (Revised 10/2013)

S. C. Electric Cooperative s Specification for a Single-Phase, Two Bushing Overhead Distribution Transformer (Revised 10/2013) S. C. Electric Cooperative s Specification for a Single-Phase, Two Bushing Overhead Distribution Transformer (Revised 10/2013) 1.0 GENERAL 1.1 This specification covers the electrical and mechanical characteristics

More information

Point Eight Power, Inc. Switchgear Specification Low Voltage UL 1558 Metal-Enclosed Switchgear

Point Eight Power, Inc. Switchgear Specification Low Voltage UL 1558 Metal-Enclosed Switchgear Table of Content 1.0 General... 2 2.0 Scope... 2 3.0 Applicable Codes, Standards and Qualifications... 2 4.0 Service and Environmental Conditions... 3 5.0 Construction... 3 6.0 Front Breaker Compartment

More information

Narayan Group. Supplying to in countries. Blue- Manufacturing units Green- Supply countries. Export business & Total Business

Narayan Group. Supplying to in countries. Blue- Manufacturing units Green- Supply countries. Export business & Total Business Narayan Group Supplying to in 55 53 countries 20 15 10 5 0 Export business & Total Business 17 14 10 11 12.3 10.08 8.1 5.83 7.2 7.92 2011 2012 2013 2014 2015 Blue- Manufacturing units Green- Supply countries

More information

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6.2 OVERHEAD SERVICES Wiring of any premises for connection

More information

Details of technical leaflets/write-up on various pieces of equipment.

Details of technical leaflets/write-up on various pieces of equipment. Details of technical leaflets/write-up on various pieces of equipment. (1) Insulator Designs: The insulators are provided in one, two, three, or four insulator designs per location and spaced to provide

More information

Metering Requirements 750 Volts or Less

Metering Requirements 750 Volts or Less SECTION 1 - SCOPE 1.1 Toronto Hydro Requirements 1.2 Ontario Electrical Safety Code SECTION 2 - PURPOSE Metering Requirements 750 Volts or Less INDEX SECTION 3 - DEFINITIONS, PUBLICATIONS AND THE INTERNATIONAL

More information

Switch Rack Assemblies

Switch Rack Assemblies Switch Rack Assemblies Applications: Free-standing switch rack assemblies are used: To provide a complete motor control center in one integrated package Outdoors and indoors In damp, wet or corrosive locations

More information

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS SINGLE-PHASE PADMOUNTED TRANSFORMERS

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS SINGLE-PHASE PADMOUNTED TRANSFORMERS CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS SINGLE-PHASE PADMOUNTED TRANSFORMERS Original Issue 1/84 Revised 1/91 Revised 6/02 Revised 11/05 Revised 11/09 Revised 1/12 Revised 11/12 Revised 5/14 Revised

More information

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

thermoweld The Contractors Choice GREAT PRODUCTS GREAT SERVICE GREAT PEOPLE

thermoweld The Contractors Choice GREAT PRODUCTS GREAT SERVICE GREAT PEOPLE The Contractors Choice the Contractors Choice Founded in 1958, with locations in Tulsa and Broken Arrow, Oklahoma. is part of the Quality Brands of Continental Industries. TABLE OF CONTENTS THE PROCESS...4

More information

INDUSTRIAL TEMPERATURE SENSORS

INDUSTRIAL TEMPERATURE SENSORS Temperature s INDUSTRIAL TEMPERATURE SENSORS Temperature s APPLIED SENSOR TECHNOLOGIES A DIVISION OF UNITED ELECTRIC CONTROLS T E M P S E N S O R - B - 0 2 Temperature s Temperature s index Subject Page

More information

ELECTRICAL INSPECTION BULLETIN (Effective )

ELECTRICAL INSPECTION BULLETIN (Effective ) ELECTRICAL INSPECTION BULLETIN (Effective 2009-02-01) Rule 36-000 Customer Owned High Voltage Installations With the increase in customer own high voltage equipment there appears to be confusion over which

More information

Customer Owned Meter Enclosures for Self-Contained Watthour Meters

Customer Owned Meter Enclosures for Self-Contained Watthour Meters Revision No. 4 Page 1 of 15 SPECIFICATION Page 2 of 15 RECORD OF SPECIFICATION APPROVALS: This Specification is approved for the inclusion of subject products on the Florida Meter Group s Approved Metering

More information

OPERATING TEMP RANGE: -40 TO 80 C -40 TO 105 C with optional UL2722 lead wires

OPERATING TEMP RANGE: -40 TO 80 C -40 TO 105 C with optional UL2722 lead wires PRODUCT DATA SPECIFICATIONS NTC THERMISTORS SERIES 10J / 11J OPERATING TEMP RANGE: -40 TO 80 C -40 TO 105 C with optional UL2722 lead wires CONSTRUCTION: 10J: Fully molded polypropylene or PBT plastic

More information

UFGS (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 35 33.00 40 (August 2013) --------------------------------- Preparing Activity: NASA Superseding UFGS-26 35 33.00 40 (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

OPERATING PROCEDURE NO. 310

OPERATING PROCEDURE NO. 310 OPERATING PROCEDURE NO. 310 Related Operating Procedures: 310A; 310B; 310C; 310D SUBJECT: Conditions of Service Issued: February 10, 2014 Revised: March 28, 2016 OBJECTIVE: To establish the rules, regulations

More information

MPM 100 Monitor Product Description Guide

MPM 100 Monitor Product Description Guide MPM 100 Monitor Product Description Guide 3103 No. Andrews Ave. Ext. Pompano Beach, FL 33064 Tel: (954) 623 6660 Fax: (954) 623 6671 www.alber.com 4200 062 Rev 2.01 Copyright and Disclaimer MPM 100 Product

More information

Fusing Equipment. Capacitor Expulsion Fuse FUSE TUBE DESIGN FEATURES EJECTOR SPRING DESIGN FEATURES

Fusing Equipment. Capacitor Expulsion Fuse FUSE TUBE DESIGN FEATURES EJECTOR SPRING DESIGN FEATURES Fusing Equipment Capacitor Expulsion Fuse Electrical Apparatus 240-37 Cooper Power Systems offers a wide variety of fuse kv and amp ratings for use on both horizontal and vertical capacitor block bank

More information

PLCC Sockets Through Hole - M43 Series

PLCC Sockets Through Hole - M43 Series Through Hole - M43 Series PART NUMBER LEGEND M43X-XX-XX NUMBER OF CONTACTS 20, 28, 32, 44, 52, 68, 84, 100 (-10 Style) 44, 52, 68, 84 (-11 Style) STYLE -10 Standard wall thickness, through hole -11 Thin

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 6/15/16 Updated division section from 16124 to 2605 - mgl44 13, removed references to other section 10/17/14

More information

Welcome to Douglas County PUD

Welcome to Douglas County PUD Welcome to Douglas County PUD We are committed to providing the best possible utility services at the lowest possible cost consistent with sound business principles. To better serve you, please fill out

More information

4CS12 4CS-1/2 4X1-7/8D Handybox. Features. Dimensions and Weight. Long Description. Catalog Number

4CS12 4CS-1/2 4X1-7/8D Handybox. Features. Dimensions and Weight. Long Description. Catalog Number 3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 AllenWatson@elliottelectric.com 4CS12 4CS-1/2 4X1-7/8D Handybox Appleton/Oz Gedney Catalog Number 4CS12 Manufacturer Appleton/Oz

More information

SECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION

SECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION SECTION 16-372 SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION 1. GENERAL SPECIFICATIONS The work of this Section includes furnishing all labor, equipment, materials (unless specifically identified as Owner-furnished)

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Updated format, division title, and removed references to other sections. - mgl44 A. Summary This section contains design criteria for the

More information

DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv

DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv K-LINE INSULATORS LIMITED TORONTO, ONTARIO, CANADA Catalogue D-DS DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv ISO9001 SAI GLOBAL FILE No. 000117 Distribution Silicone Insulators

More information

MV Product Specifications

MV Product Specifications MODULAR VARIABLE SPEED BLOWER CABINET 2, 3, 4, and 5 TONS FEATURES Variable Speed modular blower Supports two-stage outdoor units Dehumidification Speed: 80% Airflow Efficient low continuous fan selection:

More information

A. This Section includes the following types of dry-type transformers rated 600 V and less, with capacities up to 1000 kva:

A. This Section includes the following types of dry-type transformers rated 600 V and less, with capacities up to 1000 kva: SECTION 16461 - LOW-VOLTAGE TRANSFORMERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION LOW-VOLTAGE SWITCHGEAR

SECTION LOW-VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 00 LOW-VOLTAGE SWITCHGEAR SPEC WRITER NOTE: This specification is not for general use. Use Section 26 24 13, DISTRIBUTION SWITCHBOARDS for most applications.

More information

Installation Instructions

Installation Instructions Installation Instructions AquaSnap 010-055 Chilled Water Storage Tank 50/60 Hz Part No: -900---001; -900---009; -900---010 CONTENTS INTRODUCTION.................................. 1 SAFETY CONSIDERATIONS......................

More information

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 1.1. REFERENCE STANDARDS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification

More information

Wall studs. Wall Studs

Wall studs. Wall Studs 15 Box To Stud Fastener Attaches with screws to metal studs. BB1 supports electrical box. BG series features Guide-Rite design. BP series features push-type design. 78101118145 BB1 Electrical Box 100 Support

More information

Moulded Case Current Transformers

Moulded Case Current Transformers Moulded Case Current 802 Series Instrument Model 802-943 * * Model 802-940 * * Generally for Ammeter use only 0.6 KV. BIL. 10 KV. full wave Manufactured to meet the requirements of UL 1244 and revisions

More information

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES Guidelines effective March 5, 2007 NES is committed to providing safe, reliable electric service at a reasonable price for all of our customers. These guidelines offer direction for activities relating

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Brugg Cables High Voltage Accessories. Swiss solutions for independent applications.

Brugg Cables High Voltage Accessories. Swiss solutions for independent applications. Brugg Cables High Voltage Accessories. Swiss solutions for independent applications. Fact Book High Voltage Accessories Brugg Cables Business Unit High Voltage Accessories Dr. Ruben Vogelsang Head of Product

More information

8.1.2 Under no circumstances shall a service entrance be left unmetered. Notify the Company if an unmetered service is encountered.

8.1.2 Under no circumstances shall a service entrance be left unmetered. Notify the Company if an unmetered service is encountered. 2012 Edition Redbook 8.0 REVENUE METERING 8.1 INTRODUCTION The purpose of this section is to outline requirements of the Customer, as set forth herein by LIPA, as they pertain to Electric Revenue Metering

More information

FAST POWER FACTOR REGULATOR. Computer-14df - xx - 144a INSTRUCTION MANUAL ( M / 00A ) (c) CIRCUTOR S.A.

FAST POWER FACTOR REGULATOR. Computer-14df - xx - 144a INSTRUCTION MANUAL ( M / 00A ) (c) CIRCUTOR S.A. FAST POWER FACTOR REGULATOR Computer-14df - xx - 144a INSTRUCTION MANUAL ( M 981 611 / 00A ) (c) CIRCUTOR S.A. -------- POWER FACTOR REGULATOR COMPUTER- 14f --------- Page 2 POWER FACTOR REGULATOR COMPUTER-

More information

ROLINX Laminated Busbar. Design Rules Version 01 (12/2015)

ROLINX Laminated Busbar. Design Rules Version 01 (12/2015) ROLINX Laminated Busbar Design Rules Version 01 (12/2015) Content 1. Introduction... 03 7. Features... 13 2. Configuration...03 8. Thermal parameters... 14 3. Products... 04 9. General parameters... 14

More information

3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series

3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series 3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series Data Sheet May 2014 Product Description 3M Cold Shrink Connector Insulators 8440 Series are open-ended, silicone rubber, tubular sleeves.

More information

ARC WELD STUDS & ARC STUD WELDING EQUIPEMENT

ARC WELD STUDS & ARC STUD WELDING EQUIPEMENT ARC WELD STUDS & ARC STUD WELDING EQUIPEMENT ARC STUDS GENERAL INFORMATION THE ARC STUDWELDING PROCESS ARC Studwelding is generally used to weld larger diameter studs to thick base metals. ARC Studs may

More information

OVERHEAD SERVICE. Table of Contents - Section 400

OVERHEAD SERVICE. Table of Contents - Section 400 OVERHEAD SERVICE Table of Contents - Section 400 PARAGRAPH 400.0 OVERHEAD SERVICES (0-600 VOLTS)... 1 400.1 GENERAL 1 400.2 IDENTIFICATION OF CONDUCTORS. 1 400.3 MAXIMUM SERVICE ENTRANCE CONDUCTOR SIZE

More information

Service Entrance Cable Fittings

Service Entrance Cable Fittings Suggested Specifications for Service Entrance Fittings All service fittings shall be approved for the purpose by a nationally recognized testing laboratory, inspection agency or product evaluation organization.

More information

CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH

CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH Rev. 1.3 HVAC Guide Specifications Chilled and Hot Water Universal Mount Fan Coil 2-Pipe Nominal Size: 60,000

More information

TABLE OF CONTENTS. Throughout the catalog you will notice blue highlighted items. These are the most frequently ordered BURNDY Products.

TABLE OF CONTENTS. Throughout the catalog you will notice blue highlighted items. These are the most frequently ordered BURNDY Products. H W U J B L T Substation Bolted TABLE OF CONTENTS COPPER SUBSTATION Introduction............... L-3 Type HFBW Bar Clamp............... L-13 Type NT Tube to Tube.............. L-4 Type HFB-P1 Bar Clamp...............

More information

Installation Instructions Self-Regulating (sr) roof and gutter

Installation Instructions Self-Regulating (sr) roof and gutter Installation Instructions Self-Regulating (sr) roof and gutter De-icing Cables Industrial and Commercial Series Contents page Section 1. Overview 1.1 Precautions... 2 1.2 Cable and components... 2 1.3

More information

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY ORANGE & ROCKLAND UTILITIES 390 WEST ROUTE 59 SPRING VALLEY, NY 10977

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY ORANGE & ROCKLAND UTILITIES 390 WEST ROUTE 59 SPRING VALLEY, NY 10977 CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 ORANGE & ROCKLAND UTILITIES 390 WEST ROUTE 59 SPRING VALLEY, NY 10977 DISTRIBUTION ENGINEERING DEPARTMENT SPECIFICATION EO-5015

More information

Power Zone Center. Your solution for power distribution and control systems

Power Zone Center. Your solution for power distribution and control systems Power Zone Center Your solution for power distribution and control systems The Strength of One Powerful When you need to install a new power distribution center in your facility, you need it done in fastest

More information

1-1/2 LB FM7 CND BD ELECTRO ZINC PLATED DICHROMATE EPOXY POWDER COATED

1-1/2 LB FM7 CND BD ELECTRO ZINC PLATED DICHROMATE EPOXY POWDER COATED LB57 1-1/2 LB FM7 CND BD Appleton/Oz Gedney Catalog Number Manufacturer Description Weight per unit Product Category LB57 Appleton/Oz Gedney Conduit Body, Electro Zinc Plated Dichromate Epoxy Powder Coated

More information

MGO INSULATED THERMOCOUPLES INDEX

MGO INSULATED THERMOCOUPLES INDEX MGO INSULATED THERMOCOUPLES INDEX PAGE General Information... M1 Part Numbering Examples... M4 Thermocouple Elements (MA)... M5 Leadwire Style Thermocouples (MB)... M6 Leadwire Style Thermocouples (MD,

More information

Phone: Fax:

Phone: Fax: SEPTEMBER 2007 www.nsiindustries.com Phone: 800.321.5847 Fax: 800.841.5566 Mechanical Connectors Dual Rated Single & Double Lugs........................ 1 Panelboard Lugs............................ 1

More information

TABLE OF CONTENTS. Type HFB-P1... A-22. Type HFB-N... A-23. Types KA-U, KKA-U... A-24. Type K2A-U... A-25. Types K3A-U, KK3A-U...

TABLE OF CONTENTS. Type HFB-P1... A-22. Type HFB-N... A-23. Types KA-U, KKA-U... A-24. Type K2A-U... A-25. Types K3A-U, KK3A-U... BURNDY Mechanical A-1 TABLE OF CONTENTS Types KS, KS-3 & SC... A-4 Type KSU............ A-5 Type KSA............ A-6 Types KVS, KVSU...... A-7 Types KVSW, KVS-A... A-8 Type QPX............ A-9 Type QPX-Y.........

More information

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property 2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical

More information

Permitting and Inspecting PV Systems. PV Codes and Standards 101. Photovoltaic System Basics

Permitting and Inspecting PV Systems. PV Codes and Standards 101. Photovoltaic System Basics Permitting and Inspecting PV Systems Presented by Bill Brooks, PE Brooks Engineering PV Codes and Standards 101 What are the applicable codes and standards for PV systems? Electrical codes - NEC Article

More information

(Condensed from National Electric Code)

(Condensed from National Electric Code) WIRING, SPECIFICATIONS, INSPECTION, AND METER INSTALLATION PROCEDURES FOR RESIDENTIAL CUSTOMERS SERVED BY SOUTHWEST ARKANSAS ELECTRIC COOPERATIVE CORPORATION Effective April 1, 1974 Revised February 3,

More information

NEC 2017 Code Changes Chapter 1 - General

NEC 2017 Code Changes Chapter 1 - General NEC 2017 Code Changes Chapter 1 - General Changes from the 2014 code are highlighted in yellow. ARTICLE 110 - Requirements for Electrical Installations Part I. General 110.1 Scope. This article covers

More information

Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE

Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE Commercial Products Type FLX TM Freezer Floor Frost Heave Protection DESIGN GUIDE Contents Introduction...2 Application Information... 2-3 Product

More information

nicrom e l e c t r o n i c

nicrom e l e c t r o n i c G E N E R A L High Performance Thick Film Resistors C A T A L O G 3 Nicrom Electronic Via Roncaglia CH - 6883 Novazzano SWITZERLAND Phone : ++4 () 9 68 99 86 Fax : ++4 () 9 68 99 86 info@nicrom-electronic.com

More information

The complete guide to transformers and packaged substations

The complete guide to transformers and packaged substations LAND LOGICAL POWER The complete guide to transformers and packaged substations Contents Land Logical Power transformers An introduction to the complete range of Land Logical Power transformers and package

More information

RoHS Compliant (6/6) according to Directive 2002/95/EC when ordered with 100% Sn solder.

RoHS Compliant (6/6) according to Directive 2002/95/EC when ordered with 100% Sn solder. Overview The KEMET Organic Capacitor (KO-CAP) is a tantalum capacitor with a Ta anode and Ta 2 O 5 dielectric. A conductive organic polymer replaces the traditionally used MnO 2 as the cathode plate of

More information

Fixed Demand (Block Demand) The utility company sends a signal to synchronize the start of the Maximum Demand period.

Fixed Demand (Block Demand) The utility company sends a signal to synchronize the start of the Maximum Demand period. Maximum demand control systems M 6 M.6.02 GB Maximum Demand Control There are three terms that appear on the majority of electric company bills: Active energy consumption (kw h) Reactive energy consumption

More information

About Matt Piantedosi

About Matt Piantedosi 2017 NFPA Conference & Expo Solar PV System Inspections Best Practices and Commonly Found Violations Presented by: Matt Piantedosi Manager of Solar Field Operations The Cadmus Group About Matt Piantedosi

More information

Install and commission high voltage (HV) electricity current transformer metering

Install and commission high voltage (HV) electricity current transformer metering Page 1 of 5 Install and commission high voltage (HV) electricity current transformer metering Level 4 Credits 10 Purpose People credited with this unit standard are able to: demonstrate knowledge of the

More information

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number PART 1 GENERAL 01 02 03 04 SCOPE Furnish and install Manual Transfer Switches (MTS) and

More information

MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 9,000 BTUH. Rev. 1.3

MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 9,000 BTUH. Rev. 1.3 MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil Heat / Cool Fan Coil 9,000 BTUH Rev. 1.3 HVAC Guide Specifications Chilled and Hot Water Hi-Wall Fan Coil 2-Pipe Nominal Size: 9,000 BTUH Multiaqua Model

More information

General Information, Industrial Thermocouple Section

General Information, Industrial Thermocouple Section INDUSTRIAL THERMOCOUPLES INDEX PAGE General Information... I1 Straight Base Metal Thermocouple Elements (IA)... I2 Angled Base Metal Thermocouple Elements (IB)... I3 Noble Metal Thermocouple Elements (IC,

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Medium Voltage Switchgear. Basis of Design.

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Medium Voltage Switchgear. Basis of Design. Basis of Design This section applies to the design and selection of medium voltage switchgear, primarily for use in substations. Design Criteria 13.8kV equipment shall be 15kV class, 4.16kV and 2.4kV equipment

More information

660 Volts 630 & 800AMP

660 Volts 630 & 800AMP Ergon Energy Corporation Limited Technical Specification for Switch- Disconnectors and Fuse-Switch- Disconnectors 660 Volts 630 & 800AMP ETS-06-02-01 Check this is the latest Process Zone version before

More information

Schmidthammer. 06 High current carbon brushes. Elektrokohle GmbH. Transmission systems with linear adjustable telescope holders p.

Schmidthammer. 06 High current carbon brushes. Elektrokohle GmbH. Transmission systems with linear adjustable telescope holders p. Schmidthammer Elektrokohle GmbH 06 High current carbon brushes 2012 Transmission systems with linear adjustable telescope holders p. 05 Transmission systems with Kombi holders p. 09 Further transmission

More information

Thermocouple Reference Table

Thermocouple Reference Table Thermocouple is the description for electrical feedthroughs that are commonly used for temperature measurement systems. A thermocouple feedthrough does not measure temperature, but rather it is used to

More information

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION LIST OF FIGURES...

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION LIST OF FIGURES... DIVISION 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN Contents 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION 13 00 60 LIST OF FIGURES... 6 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN 1. General Requirements

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 36 00.00 10 (October 2007) ---------------------------------- Preparing Activity: USACE Superseding UFGS-26 36 00.00 10 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Flexible Printed Circuits Design Guide

Flexible Printed Circuits Design Guide www.tech-etch.com/flex Flexible Printed Circuits Design Guide Multilayer SMT Assembly Selective Plating of Gold & Tin-Lead Fine Line Microvias Cantilevered & Windowed Leads 1 MATERIALS CONDUCTOR Copper

More information

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466 BUSWAY LOW VOLTAGE (POW-R-WAY III) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein

More information

Fixings, bonds and clamps

Fixings, bonds and clamps Square tape clamp Material 25 x 3mm Copper 0.12kg CT105-H 25 x 6mm Copper 0.30kg CT110-H 50 x 6mm Copper 0.60kg CT115-H Manufactured from high quality copper and aluminium alloys. Simple to install, providing

More information

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding.

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding. ALLIANT ENERGY CENTER PAVILIONS Project No. 2013 027 SECTION 27 11 00 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SnoTrace TM RGS TM Systems for Roof and Gutter Snow and Ice Melting

SnoTrace TM RGS TM Systems for Roof and Gutter Snow and Ice Melting SnoTrace TM RGS TM Systems for Roof and Gutter Snow and Ice Melting DESIGN GUIDE Commercial Products SnoTrace TM RGS TM Systems for Roof and Gutter Snow and Ice Melting design Guide Contents Introduction...

More information

Contents. SuperPlate. Tubes Technology. Through Holes Technology. Milled Channels Technology. Thermal Analysis. SuperPlate

Contents. SuperPlate. Tubes Technology. Through Holes Technology. Milled Channels Technology. Thermal Analysis. SuperPlate : an efficient way to manage complex electronic systems having high concentrated power. Water cooling is becoming more and more the solution to dissipate the high power of last generation power (IGBTs)

More information

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL). 16450 GROUNDING ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 26 An optional keynote to the

More information

product specifications e

product specifications e Wallbox The Wallbox controls up to six zones of light and will operate the following sources with a continuous Square Law dimming curve or on a full conduction non-dim basis: Incandescent LED, Tungsten

More information

Will accommodate up to 35 conductors while maintaining separation required to withstand instrumentation voltages

Will accommodate up to 35 conductors while maintaining separation required to withstand instrumentation voltages H.0 ACCESSORIES Introduction Technical Reference Accessories Pressure Viewport Isolator Thermocouple Coaxial Multipin Connector Feedthrough Description Accessories is the product classification given by

More information

DC-DC Converters MI-J00

DC-DC Converters MI-J00 DC-DC Converters MI-J00 10 to 50 Watts Features & Benefits Inputs: 28V DC per MIL-STD-704D/E/F 155V DC per MIL-STD-1399A 270V DC per MIL-STD-704D/E/F Single output: 2 48V DC Up to 23W/in 3 MIL-STD-810

More information

Specifications for Residential Overhead Electric Service Installation

Specifications for Residential Overhead Electric Service Installation Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be

More information

GENERAL USE VISE TYPE ALUMINUM SINGLE BOLT ALUMINUM TO ALUMINUM OR ALUMINUM TO COPPER

GENERAL USE VISE TYPE ALUMINUM SINGLE BOLT ALUMINUM TO ALUMINUM OR ALUMINUM TO COPPER GENERAL USE VISE TYPE ALUMINUM SINGLE BOLT ALUMINUM TO ALUMINUM OR ALUMINUM TO COPPER ALUMINUM GA9000 Recommended for aluminum or aluminum to copper distribution, service or tap connections. Add Suffix

More information

*** Supercedes: BECO E and COM , , & ***

*** Supercedes: BECO E and COM , , & *** 7/27/09 Page 1 of 9 R5 *** Supercedes: BECO E2.9-27.4 and COM 1-0696, 2-0196, & 5-0385 *** 1.0 Scope #2 AWG to 1000 KCMIL CONCENTRIC NEUTRAL JACKETED CABLES RATED 5-35 kv These Specifications cover single

More information

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING SECTION 16060 PART 1 GENERAL 1.01 DESCRIPTION A. Section includes requirements for an electrical grounding system, including electrodes, grounding rods, connectors, insulators, equipment grounding and

More information

TECHNICAL SPECIFICATION FOR 11KV INDOOR/OUTDOOR & 22KV/33KV OUTDOOR METERING CUBICLE SPEC NO.CE (DIST)/MM-IV/09/ INDEX

TECHNICAL SPECIFICATION FOR 11KV INDOOR/OUTDOOR & 22KV/33KV OUTDOOR METERING CUBICLE SPEC NO.CE (DIST)/MM-IV/09/ INDEX TECHNICAL SPECIFICATION FOR 11KV INDOOR/OUTDOOR & 22KV/33KV OUTDOOR METERING CUBICLE SPEC NO.CE (DIST)/MM-IV/09/ 23.10.2007 INDEX CLAUSE NO. CONTENTS PAGE NO. 1. SCOPE 2 2. SPARES 2 3. SERVICE CONDITIONS

More information

Minimum Transmission Design Standards f or Competitive Upgrades Rev 2

Minimum Transmission Design Standards f or Competitive Upgrades Rev 2 Minimum Transmission Design Standards f or Competitive Upgrades Rev 2 December, 2016 Minimum Design Standards Task Force Revision History Date or Version Number 12/17/2014 Revision IR Author Change Description

More information