ACOUSTICAL PANEL CEILINGS
|
|
- Blanche Cross
- 6 years ago
- Views:
Transcription
1 SECTION ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.01 SUMMARY A. This Section includes acoustical panels and exposed suspension systems for ceilings SUBMITTALS A. Product Data: For each type of product indicated. B. Coordination Drawings: Drawn to scale and coordinating acoustical panel ceiling installation with hanger attachment to building structure and ceiling mounted items: C. Samples: For each exposed finish. D. Product test reports. E. Maintenance data QUALITY ASSURANCE A. Fire-Test-Response Characteristics: 1. Fire-Resistance Characteristics: Where indicated, provide acoustical panel ceilings identical to those of assemblies tested for fire resistance per ASTM E 119 by UL or another testing and inspecting agency acceptable to authorities having jurisdiction. a. Identify materials with appropriate markings of applicable testing and inspecting agency. 2. Surface-Burning Characteristics: Acoustical panels complying with ASTM E 1264 for Class A materials, when tested per ASTM E EXTRA MATERIALS A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Acoustical Ceiling Panels: Full-size panels equal to 2.0 percent of quantity installed. 2. Suspension System Components: Quantity of each exposed component equal to 2.0 percent of quantity installed. PART 2 - PRODUCTS 2.01 ACOUSTICAL PANEL CEILINGS, GENERAL A. Acoustical Panel Standard: Comply with ASTM E B. Metal Suspension System Standard: Comply with ASTM C 635. C. Attachment Devices: Size for five times the design load indicated in ASTM C 635, Table 1, "Direct Hung," unless otherwise indicated. Comply with seismic design requirements. 1. Anchors in Concrete: Expansion anchors fabricated from corrosionresistant materials, with holes or loops for attaching hangers of type indicated and with capability to sustain, without failure, a load equal to five times that imposed by ceiling construction, as determined by testing per ASTM E 488 or ASTM E 1512 as applicable. 2. Power-Actuated Fasteners in Concrete: Fastener system of type suitable ACOUSTICAL PANEL CEILINGS
2 for application indicated, fabricated from corrosion-resistant materials, with clips or other accessory devices for attaching hangers of type indicated, and with capability to sustain, without failure, a load equal to 10 times that imposed by ceiling construction, as determined by testing per ASTM E D. Wire Hangers, Braces, and Ties: Zinc-coated carbon-steel wire; ASTM A 641/A 641M, Class 1 zinc coating, soft temper. 1. Size: Select wire diameter so its stress at 3 times hanger design load (ASTM C 635, Table 1, "Direct Hung") will be less than yield stress of wire, but provide not less than inch- (2.69-mm-) diameter wire. E. Metal Edge Moldings and Trim: Type and profile indicated or, if not indicated, manufacturer's standard moldings for edges and penetrations that comply with seismic design requirements; formed from sheet metal of same material, finish, and color as that used for exposed flanges of suspension system runners ACOUSTICAL PANELS FOR ACOUSTICAL PANEL CEILING A. Available Products: Subject to compliance with requirements, products that may be incorporated into the Work include, but are not limited to, the following: Armstrong Kitchen Zone, 24 x 24. B. Products: Subject to compliance with requirements, provide one of the following: 1. Armstrong World Industries, Inc. 2. BPB USA. 3. Chicago Metallic Corporation 4. Ecophon CertainTeed, Inc. 5. Tectum Inc. 6. USG Interiors, Inc METAL SUSPENSION SYSTEM FOR ACOUSTICAL PANEL CEILING A. Available Products: Subject to compliance with requirements, products that may be incorporated into the Work include, but are not limited to, the following: 1. Armstrong World Industries, Inc. Prelude 15/ BPB USA. 3. Chicago Metallic Corporation. 4. Ecophon CertainTeed, Inc.. 5. USG Interiors, Inc. PART 3 - EXECUTION 3.01 INSTALLATION A. Comply with ASTM C 636 and seismic design requirements indicated, per manufacturer's written instructions and CISCA's "Ceiling Systems Handbook." B. Measure each ceiling area and establish layout of acoustical panels to balance border widths at opposite edges of each ceiling. Avoid using less-than-halfwidth panels at borders. C. Suspend ceiling hangers from building's structural members, plumb and free from contact with insulation or other objects within ceiling plenum. Splay hangers only where required to miss obstructions; offset resulting horizontal forces by bracing, countersplaying, or other equally effective means. Where width of ducts and other construction within ceiling plenum produces hanger spacings that interfere with location of hangers, use trapezes or equivalent ACOUSTICAL PANEL CEILINGS
3 END OF SECTION devices. When steel framing does not permit installation of hanger wires at spacing required, install carrying channels or other supplemental support for attachment of hanger wires. 1. Do not support ceilings directly from permanent metal forms or floor deck; anchor into concrete slabs. 2. Do not attach hangers to steel deck tabs or to steel roof deck. D. Install edge moldings and trim of type indicated at perimeter of acoustical ceiling area and where necessary to conceal edges of acoustical panels. Screw attach moldings to substrate at intervals not more than 16 inches (400 mm) o.c. and not more than 3 inches (75 mm) from ends, leveling with ceiling suspension system to a tolerance of 1/8 inch in 12 feet (3.2 mm in 3.6 m). Miter corners accurately and connect securely. E. Install suspension system runners so they are square and securely interlocked with one another. Remove and replace dented, bent, or kinked members. F. Install acoustical panels with undamaged edges and fit accurately into suspension system runners and edge moldings. Scribe and cut panels at borders and penetrations to provide a neat, precise fit. ACOUSTICAL PANEL CEILINGS
4 SECTION RESILIENT BASE AND ACCESSORIES PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Resilient base. 2. Resilient stair accessories. 3. Resilient molding accessories SUBMITTALS A. Product Data: For each type of product indicated. B. Samples: For each type of product indicated, in manufacturer's standard-size Samples but not less than 12 inches (300 mm) long, of each resilient product color, texture, and pattern required QUALITY ASSURANCE A. Fire-Test-Response Characteristics: As determined by testing identical products according to ASTM E 648 or NFPA 253 by a qualified testing agency. 1. Critical Radiant Flux Classification: Class I, not less than 0.45 W/sq. cm PROJECT CONDITIONS A. Maintain ambient temperatures within range recommended by manufacturer in spaces to receive resilient products. B. Until Substantial Completion, maintain ambient temperatures within range recommended by manufacturer. C. Install resilient products after other finishing operations, including painting, have been completed. PART 2 - PRODUCTS 2.01 RESILIENT BASE A. Resilient Base: 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. Allstate Rubber Corp.; Stoler Industries. b. Armstrong World Industries, Inc. c. Burke Mercer Flooring Products; Division of Burke Industries, Inc. d. Endura Rubber Flooring; Division of Burke Industries, Inc. e. Estrie Products International; American Biltrite (Canada) Ltd. f. Flexco, Inc. g. Johnsonite. h. Mondo Rubber International, Inc. i. Musson, R. C. Rubber Co. j. Nora Rubber Flooring; Freudenberg Building Systems, Inc. k. PRF USA, Inc. l. Roppe Corporation, USA. m. VPI, LLC; Floor Products Division. RESILIENT BASE AND ACCESSORIES
5 B. Resilient Base Standard: ASTM F C. Minimum Thickness: inch (3.2 mm). D. Height: 4 inches (102 mm). E. Lengths: Coils in manufacturer's standard length. F. Outside Corners: Preformed. G. Inside Corners: Job formed. H. Finish: As selected by Architect from manufacturer's full range. I. Colors and Patterns: As selected by Architect from full range of industry colors RESILIENT MOLDING ACCESSORY A. Resilient Molding Accessory: 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. Burke Mercer Flooring Products; Division of Burke Industries, Inc. b. Flexco, Inc. c. Johnsonite. d. R.C.A. Rubber Company (The). e. Roppe Corporation, USA. f. VPI, LLC; Floor Products Division. B. Description: Nosing for carpet, nosing for resilient floor covering, reducer strip for resilient floor covering, joiner for tile and carpet, transition strips, and as shown on drawings. C. Material: Vinyl. D. Profile and Dimensions: As indicated. E. Colors and Patterns: As selected by Architect from full range of industry colors INSTALLATION MATERIALS A. Trowelable Leveling and Patching Compounds: Latex-modified, portland cement based or blended hydraulic-cement-based formulation provided or approved by manufacturer for applications indicated. B. Adhesives: Water-resistant type recommended by manufacturer to suit resilient products and substrate conditions indicated. 1. Use adhesives that comply with the following limits for VOC content when calculated according to 40 CFR 59, Subpart D (EPA Method 24): a. Cove Base Adhesives: Not more than 50 g/l. b. Rubber Floor Adhesives: Not more than 60 g/l. PART 3 - EXECUTION 3.01 PREPARATION A. Prepare substrates according to manufacturer's written instructions to ensure adhesion of resilient products. B. Fill cracks, holes, and depressions in substrates with trowelable leveling and patching compound and remove bumps and ridges to produce a uniform and smooth substrate. C. Do not install resilient products until they are same temperature as the space where they are to be installed. 1. Move resilient products and installation materials into spaces where they will be installed at least 48 hours in advance of installation. D. Sweep and vacuum clean substrates to be covered by resilient products RESILIENT BASE AND ACCESSORIES
6 immediately before installation RESILIENT BASE INSTALLATION A. Comply with manufacturer's written instructions for installing resilient base. B. Apply resilient base to walls, columns, pilasters, casework and cabinets in toe spaces, and other permanent fixtures in rooms and areas where base is required. C. Install resilient base in lengths as long as practicable without gaps at seams and with tops of adjacent pieces aligned. D. Tightly adhere resilient base to substrate throughout length of each piece, with base in continuous contact with horizontal and vertical substrates. E. Do not stretch resilient base during installation RESILIENT ACCESSORY INSTALLATION A. Comply with manufacturer's written instructions for installing resilient accessories. B. Resilient Molding Accessories: Butt to adjacent materials and tightly adhere to substrates throughout length of each piece. Install reducer strips at edges of carpet or resilient floor covering that would otherwise be exposed CLEANING AND PROTECTION A. Comply with manufacturer's written instructions for cleaning and protection of resilient products. B. Cover resilient products until Substantial Completion. END OF SECTION RESILIENT BASE AND ACCESSORIES
7 SECTION RESILIENT TILE FLOORING PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Vinyl composition floor tile SUBMITTALS A. Product Data: For each type of product indicated. B. Shop Drawings: For each type of floor tile. Include floor tile layouts, edges, columns, doorways, enclosing partitions, built-in furniture, cabinets, and cutouts. C. Samples: Full-size units of each color and pattern of floor tile required. D. Maintenance data QUALITY ASSURANCE A. Fire-Test-Response Characteristics: As determined by testing identical products according to ASTM E 648 or NFPA 253 by a qualified testing agency. 1. Critical Radiant Flux Classification: Class I, not less than 0.45 W/sq. cm PROJECT CONDITIONS A. Maintain ambient temperatures within range recommended by manufacturer in spaces to receive floor tile. B. Until Substantial Completion, maintain ambient temperatures within range recommended by manufacturer. C. Close spaces to traffic during floor tile installation. D. Close spaces to traffic for 48 hours after floor tile installation. E. Install floor tile after other finishing operations, including painting, have been completed. PART 2 - PRODUCTS 2.01 VINYL COMPOSITION FLOOR TILE A. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: 1. AB ColorPlus, American Biltrite (Canada) Ltd. 2. Armstrong World Industries, Inc. 3. Congoleum Corporation. 4. Mannington Mills, Inc. 5. Tarkett, Inc. 6. Vinylasa Tile, Distributed by American Tile Inc. B. Tile Standard: ASTM F See color selection on the drawings. C. Wearing Surface: Smooth. D. Thickness: inch (3.2 mm). E. Size: 12 by 12 inches (305 by 305 mm). F. Colors and Patterns: Match product indicated on finish schedule index on drawings INSTALLATION MATERIALS A. Trowelable Leveling and Patching Compounds: Latex-modified, portland RESILIENT TILE FLOORING
8 PART 3 - EXECUTION cement based or blended hydraulic-cement-based formulation provided or approved by manufacturer for applications indicated. B. Adhesives: Water-resistant type recommended by manufacturer to suit floor tile `and substrate conditions indicated. 1. Use adhesives that comply with the following limits for VOC content when calculated according to 40 CFR 59, Subpart D (EPA Method 24): a. VCT Tile Adhesives: Not more than 50 g/l. C. Floor Polish: Provide protective liquid floor polish products as recommended by manufacturer PREPARATION A. Prepare substrates according to manufacturer's written instructions to ensure adhesion of resilient products. B. Concrete Substrates: Prepare according to ASTM F Verify that substrates are dry and free of curing compounds, sealers, and hardeners. 2. Remove substrate coatings and other substances that are incompatible with adhesives and that contain soap, wax, oil, or silicone, using mechanical methods recommended by manufacturer. Do not use solvents. 3. Alkalinity and Adhesion Testing: Perform tests recommended by manufacturer. Proceed with installation only after substrates pass testing. 4. Moisture Testing: Perform tests recommended by floor covering manufacturer and as follows. Proceed with installation only after substrates pass testing. a. Perform anhydrous calcium chloride test, ASTM F Proceed with installation only after substrates have maximum moisture-vapor-emission rate of 3 lb of water/1000 sq. ft. (1.36 kg of water/92.9 sq. m) in 24 hours. b. Perform relative humidity test using in situ probes, ASTM F Proceed with installation only after substrates have a maximum 75% relative humidity level measurement. C. Fill cracks, holes, and depressions in substrates with trowelable leveling and patching compound and remove bumps and ridges to produce a uniform and smooth substrate. D. Do not install floor tiles until they are same temperature as space where they are to be installed. 1. Move resilient products and installation materials into spaces where they will be installed at least 48 hours in advance of installation. E. Sweep and vacuum clean substrates to be covered by resilient products immediately before installation FLOOR TILE INSTALLATION A. Comply with manufacturer's written instructions for installing floor tile. B. Lay out floor tiles from center marks established with principal walls, discounting minor offsets, so tiles at opposite edges of room are of equal width. Adjust as necessary to avoid using cut widths that equal less than one-half tile at perimeter. RESILIENT TILE FLOORING
9 1. Lay tiles square with room axis. C. Match floor tiles for color and pattern by selecting tiles from cartons in the same sequence as manufactured and packaged, if so numbered. Discard broken, cracked, chipped, or deformed tiles. 1. Lay tiles with grain direction alternating in adjacent tiles (basket-weave pattern). D. Scribe, cut, and fit floor tiles to butt neatly and tightly to vertical surfaces and permanent fixtures including built-in furniture, cabinets, pipes, outlets, and door frames. E. Extend floor tiles into toe spaces, door reveals, closets, and similar openings. Extend floor tiles to center of door openings. F. Maintain reference markers, holes, and openings that are in place or marked for future cutting by repeating on floor tiles as marked on substrates. Use chalk or other nonpermanent, nonstaining marking device. G. Adhere floor tiles to flooring substrates using a full spread of adhesive applied to substrate to produce a completed installation without open cracks, voids, raising and puckering at joints, telegraphing of adhesive spreader marks, and other surface imperfections CLEANING AND PROTECTION A. Comply with manufacturer's written instructions for cleaning and protection of floor tile. B. Floor Polish: Remove soil, visible adhesive, and surface blemishes from floor tile surfaces before applying liquid floor polish. 1. Apply two coat(s). C. Cover floor tile until Substantial Completion. END OF SECTION RESILIENT TILE FLOORING
10 SECTION EXTERIOR PAINTING PART 1 - GENERAL 1.1 SUMMARY A. Section includes surface preparation and the application of paint systems on the following exterior substrates: 1. Steel and iron except on PEMB red iron. 2. Wood indicated to be painted. B. No painting is required on shop-primed metal building framing, nor on wood framing for electric panels, nor on wood at horse stalls. 1.2 ACTION SUBMITTALS A. Product Data: For each type of product. Include preparation requirements and application instructions. 1. Include printout of current "MPI Approved Products List" for each product category specified, with the proposed product highlighted. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Products: Subject to compliance with requirements, provide product listed in the Exterior Painting Schedule for the paint category indicated or equal. 2.2 PAINT, GENERAL A. MPI Standards: Products shall comply with MPI standards indicated and shall be listed in its "MPI Approved Products Lists." B. Material Compatibility: 1. Materials for use within each paint system shall be compatible with one another and substrates indicated, under conditions of service and application as demonstrated by manufacturer, based on testing and field experience. 2. For each coat in a paint system, products shall be recommended in writing by topcoat manufacturers for use in paint system and on substrate indicated. C. Colors: As indicated in a color schedule. EXTERIOR PAINTING
11 PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates and conditions, with Applicator present, for compliance with requirements for maximum moisture content and other conditions affecting performance of the Work. B. Verify suitability of substrates, including surface conditions and compatibility with existing finishes and primers. C. Proceed with coating application only after unsatisfactory conditions have been corrected. 1. Application of coating indicates acceptance of surfaces and conditions. 3.2 PREPARATION A. Comply with manufacturer's written instructions and recommendations in "MPI Architectural Painting Specification Manual" applicable to substrates and paint systems indicated. B. Remove hardware, covers, plates, and similar items already in place that are removable and are not to be painted. If removal is impractical or impossible because of size or weight of item, provide surface-applied protection before surface preparation and painting. 1. After completing painting operations, use workers skilled in the trades involved to reinstall items that were removed. Remove surface-applied protection. 3.3 APPLICATION A. Apply paints according to manufacturer's written instructions and recommendations in "MPI Manual." B. Apply paints to produce surface films without cloudiness, spotting, holidays, laps, brush marks, roller tracking, runs, sags, ropiness, or other surface imperfections. Cut in sharp lines and color breaks. 3.4 CLEANING AND PROTECTION A. Protect work of other trades against damage from paint application. Correct damage to work of other trades by cleaning, repairing, replacing, and refinishing, as approved by Architect, and leave in an undamaged condition. B. At completion of construction activities of other trades, touch up and restore damaged or defaced painted surfaces. 3.5 EXTERIOR PAINTING SCHEDULE A. Steel and Iron Substrates: EXTERIOR PAINTING
12 1. Alkyd System MPI EXT 5.1D: a. Prime Coat: Shop primer specified in Section where substrate is specified. b. Intermediate Coat: Exterior, alkyd enamel, matching topcoat. c. Topcoat: Alkyd, exterior, semi-gloss (MPI Gloss Level 5), MPI #94. B. Wood Substrates: Plywood backboards. 1. Latex over Latex Primer System MPI EXT 6.3L: a. Prime Coat: Primer, latex for exterior wood, MPI #6. b. Intermediate Coat: Latex, exterior, matching topcoat. c. Topcoat: Latex, exterior, flat (MPI Gloss Level 1), MPI #10. C. No paint is required on wood at horse stalls. END OF SECTION EXTERIOR PAINTING
13 SECTION INTERIOR PAINTING PART 1 - GENERAL 1.01 SUMMARY A. This Section includes surface preparation and the application of paint systems on the following interior substrates: 1. Concrete masonry units (CMU). 2. Steel SUBMITTALS A. Product Data: For each type of product indicated on the Room Finish Schedule and Index shown on the drawings. B. Samples: For each finish and for each color and texture required. C. Product List: Printout of current "MPI Approved Products List" for each product category specified in Part 2, with the proposed product highlighted QUALITY ASSURANCE A. MPI Standards: 1. Products: Complying with MPI standards indicated and listed in "MPI Approved Products List." 2. Preparation and Workmanship: Comply with requirements in "MPI Architectural Painting Specification Manual" for products and paint systems indicated. B. Mockups: Apply benchmark samples of each paint system indicated and each color and finish selected to verify preliminary selections made under sample submittals and to demonstrate aesthetic effects and set quality standards for materials and execution. 1. Architect will select one surface to represent surfaces and conditions for application of each paint system specified in Part 3. a. Wall and Ceiling Surfaces: Provide samples of at least 100 sq. ft. (9 sq. m). b. Other Items: Architect will designate items or areas required. 2. Apply benchmark samples after permanent lighting and other environmental services have been activated. 3. Final approval of color selections will be based on benchmark samples. a. If preliminary color selections are not approved, apply additional benchmark samples of additional colors selected by Architect at no added cost to Owner EXTRA MATERIALS A. Furnish extra materials described below that are from same production run (batch mix) as materials applied and that are packaged for storage and identified with labels describing contents. 1. Quantity: Furnish an additional 1 gal. (3.8 L) of each material and color applied. INTERIOR PAINTING
14 PART 2 - PRODUCTS 2.01 PAINT, GENERAL A. Material Compatibility: 1. Provide materials for use within each paint system that are compatible with one another and substrates indicated, under conditions of service and application as demonstrated by manufacturer, based on testing and field experience. 2. For each coat in a paint system, provide products recommended in writing by manufacturers of topcoat for use in paint system and on substrate indicated. B. Chemical Components of Field-Applied Interior Paints and Coatings: Provide topcoat paints and anti-corrosive and anti-rust paints applied to ferrous metals that comply with the following chemical restrictions; these requirements do not apply to paints and coatings that are applied in a fabrication or finishing shop: 1. Aromatic Compounds: Paints and coatings shall not contain more than 1.0 percent by weight of total aromatic compounds (hydrocarbon compounds containing one or more benzene rings). 2. Restricted Components: Paints and coatings shall not contain any of the following: a. Acrolein. b. Acrylonitrile. c. Antimony. d. Benzene. e. Butyl benzyl phthalate. f. Cadmium. g. Di (2-ethylhexyl) phthalate. h. Di-n-butyl phthalate. i. Di-n-octyl phthalate. j. 1,2-dichlorobenzene. k. Diethyl phthalate. l. Dimethyl phthalate. m. Ethylbenzene. n. Formaldehyde. o. Hexavalent chromium. p. Isophorone. q. Lead. r. Mercury. s. Methyl ethyl ketone. t. Methyl isobutyl ketone. u. Methylene chloride. v. Naphthalene. w. Toluene (methylbenzene). x. 1,1,1-trichloroethane. y. Vinyl chloride. C. Colors: As indicated in a color schedule (see Index to Finish Schedule on the drawings) BLOCK FILLERS A. Interior/Exterior Latex Block Filler: MPI #4. INTERIOR PAINTING
15 2.03 PRIMERS/SEALERS A. Interior Latex Primer/Sealer: MPI #50. B. Interior Alkyd Primer/Sealer: MPI # METAL PRIMERS A. Alkyd Anticorrosive Metal Primer: MPI #79. B. Quick-Drying Alkyd Metal Primer: MPI #76. C. Rust-Inhibitive Primer (Water Based): MPI #107. D. Cementitious Galvanized-Metal Primer: MPI #26. E. Waterborne Galvanized-Metal Primer: MPI #134. F. Vinyl Wash Primer: MPI #80. G. Quick-Drying Primer for Aluminum: MPI # WOOD PRIMERS A. Interior Latex-Based Wood Primer: MPI # LATEX PAINTS A. Interior Latex (Flat): MPI #53 (Gloss Level 1). B. Interior Latex (Low Sheen): MPI #44 (Gloss Level 2). C. Interior Latex (Eggshell): MPI #52 (Gloss Level 3). D. Interior Latex (Satin): MPI #43 (Gloss Level 4). E. Interior Latex (Semigloss): MPI #54 (Gloss Level 5). F. Interior Latex (Gloss): MPI #114 (Gloss Level 6, except minimum gloss of 65 units at 60 deg). G. Institutional Low-Odor/VOC Latex (Flat): MPI #143 (Gloss Level 1). H. Institutional Low-Odor/VOC Latex (Low Sheen): MPI #144 (Gloss Level 2). I. Institutional Low-Odor/VOC Latex (Eggshell): MPI #145 (Gloss Level 3). J. Institutional Low-Odor/VOC Latex (Semigloss): MPI #147 (Gloss Level 5). K. High-Performance Architectural Latex (Low Sheen): MPI #138 (Gloss Level 2). L. High-Performance Architectural Latex (Eggshell): MPI #139 (Gloss Level 3). M. High-Performance Architectural Latex (Satin): MPI #140 (Gloss Level 4). N. High-Performance Architectural Latex (Semigloss): MPI #141 (Gloss Level 5). O. Exterior Latex (Flat): MPI #10 (Gloss Level 1). P. Exterior Latex (Semigloss): MPI #11 (Gloss Level 5). Q. Exterior Latex (Gloss): MPI #119 (Gloss Level 6, except minimum gloss of 65 units at 60 deg) ALKYD PAINTS A. Interior Alkyd (Flat): MPI #49 (Gloss Level 1). B. Interior Alkyd (Eggshell): MPI #51 (Gloss Level 3). C. Interior Alkyd (Semigloss): MPI #47 (Gloss Level 5). D. Interior Alkyd (Gloss): MPI #48 (Gloss Level 6) QUICK-DRYING ENAMELS A. Quick-Drying Enamel (Semigloss): MPI #81 (Gloss Level 5). B. Quick-Drying Enamel (High Gloss): MPI #96 (Gloss Level 7) DRY FOG/FALL COATINGS A. Latex Dry Fog/Fall: MPI #118. B. Waterborne Dry Fall: MPI #133. C. Interior Alkyd Dry Fog/Fall: MPI #55. INTERIOR PAINTING
16 PART 3 - EXECUTION 3.01 EXAMINATION A. Examine substrates and conditions, with Applicator present, for compliance with requirements for maximum moisture content and other conditions affecting performance of work. B. Maximum Moisture Content of Substrates: When measured with an electronic moisture meter as follows: 1. Concrete: 12 percent. 2. Masonry (Clay and CMU): 12 percent. 3. Wood: 15 percent. 4. Gypsum Board: 12 percent. 5. Plaster: 12 percent. C. Verify suitability of substrates, including surface conditions and compatibility with existing finishes and primers. D. Begin coating application only after unsatisfactory conditions have been corrected and surfaces are dry. 1. Beginning coating application constitutes Contractor's acceptance of substrates and conditions PREPARATION AND APPLICATION A. Comply with manufacturer's written instructions and recommendations in "MPI Architectural Painting Specification Manual" applicable to substrates indicated. B. Clean substrates of substances that could impair bond of paints, including dirt, oil, grease, and incompatible paints and encapsulants. 1. Remove incompatible primers and re-prime substrate with compatible primers as required to produce paint systems indicated. C. Apply paints to produce surface films without cloudiness, spotting, holidays, laps, brush marks, roller tracking, runs, sags, ropiness, or other surface imperfections. Cut in sharp lines and color breaks. D. Painting Mechanical and Electrical Work: Paint items exposed in equipment rooms and occupied spaces including, but not limited to, the following: 1. Mechanical Work: a. Uninsulated metal piping. b. Uninsulated plastic piping. c. Pipe hangers and supports. d. Tanks that do not have factory-applied final finishes. e. Visible portions of internal surfaces of metal ducts, without liner, behind air inlets and outlets. f. Duct, equipment, and pipe insulation having cotton or canvas insulation covering or other paintable jacket material. g. Mechanical equipment that is indicated to have a factory-primed finish for field painting. 2. Electrical Work: a. Switchgear. b. Panelboards. c. Electrical equipment that is indicated to have a factory-primed finish for field painting. E. Protect work of other trades against damage from paint application. Correct damage to work of other trades by cleaning, repairing, replacing, and refinishing, INTERIOR PAINTING
17 as approved by Architect, and leave in an undamaged condition. F. At completion of construction activities of other trades, touch up and restore damaged or defaced painted surfaces INTERIOR PAINTING SCHEDULE A. CMU Substrates: 1. Latex System: MPI INT 4.2A. a. Prime Coat: Interior/exterior latex block filler. b. Intermediate Coat: Interior latex matching topcoat. c. Topcoat: Interior latex (eggshell). B. Steel Substrates: 1. Alkyd System: MPI INT 5.1E. a. Prime Coat: Shop primer specified in Section where substrate is specified. b. Intermediate Coat: Alkyd, interior, matching topcoat. c. Topcoat: Alkyd, interior, semi-gloss (MPI Gloss Level 5), MPI #47. END OF SECTION INTERIOR PAINTING
18 SECTION HIGH PERFORMANCE COATINGS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Extent of painting work is shown on drawings and schedules (designated GLAZED or WALL GLAZE ) and as herein specified. B. The work includes painting and finishing of interior and exterior exposed items and surfaces throughout project except as otherwise indicated. Surface preparation, priming and coats of paint specified are in addition to any shop priming and surface treatment specified under other sections of work. C. The work includes preparation of surfaces for refinishing, and refinishing with coatings designated. D. Paint as used herein means all coating systems materials, including primers, emulsions, enamels, stains, sealers and fillers and other applied materials whether used as prime, intermediate or finish coats. E. Paint exposed surfaces whether or not colors are designated in schedules except where natural finish of material is specifically noted as a surface not to be painted. Where items or surfaces are not specifically mentioned, paint same as adjacent similar materials or areas. If color or finish is not designated, Architect will select these from standard colors available for materials systems specified. F. Following categories of work are not included as part of field applied finish work, or are included in other sections of these specifications: 1. Shop Priming: Unless otherwise specified, shop priming of ferrous metal items is included under various sections for structural steel, miscellaneous metal, hollow metal work and similar items. Also, for fabricated components such as architectural woodwork, wood casework and shop fabricated or factory built mechanical and electrical equipment or accessories. 2. Pre-Finished Items: Unless otherwise indicated, do not include painting when factory finishing or installer finishing is specified for such items as (but not limited to) prefinished doors, finished mechanical and electrical equipment including light fixtures and air diffusers, switchgear and distribution cabinets. 3. Operating Parts and Labels: Moving parts of operating units, mechanical and electrical parts, such as valve and damper operations, linkages, sinkages, sensing devices, motor and fan shafts will not require finish painting unless otherwise indicated. a. Do not paint over any code required labels such as Underwriters Laboratories and Factory Mutual, or any equipment dentification, performance rating, name or nomenclature plates SUBMITTALS A. Product Data Submit manufacturer s technical information, including paint label analysis and application instructions, for each material proposed to use B. Samples: Submit full range of standard color samples for Architect s review. HIGH PERFORMANCE COATINGS
19 1.03 DELIVERY AND STORAGE A. Deliver materials to job site in original, new and unopened packages and containers bearing manufacturer s name and label JOB CONDITIONS A. Apply water base paints only when temperature of surfaces to be painted and surrounding air temperatures are between 50 F (10 C) and 90 F (32 C), unless otherwise permitted by paint manufacturer s printed instructions. B. Apply solvent thinned paints only when temperature of surfaces to be painted and surrounding air temperatures are between 45 F (7 C) and 95 F (34 C), unless otherwise permitted by paint manufacturer s printed instructions. C. Do not apply paint in snow, rain, fog or mist, or when relative humidity exceeds 85%, or to damp or wet surfaces unless otherwise permitted by paint manufacturer s printed instructions. Painting may be continued during inclement weather if area and surfaces to be painted are enclosed and heated within temperature limits specified by paint manufacturer during application and drying periods. D. Apply paint only with minimum 50 FC light provided at all surfaces. E. Provide barriers to occupied portions of the facility during painting and curing operations. F. At all interior applications, provide ventilation of at least 6 air changes per hour during painting and curing operations. PART 2 - PRODUCT 2.01 COLORS AND FINISHES A. Surface treatments and finishes are indicated in the Finish Schedule of the contract documents. B. Prior to beginning work, Architect will make selection from manufacturer s complete range of colors for surfaces to be painted. C. Color Pigments 1. Pure, non-fading, application types to suit substrates and service indicated. a. Lead content in pigment, if any, is limited to contain not more than 0.6% lead as lead metal based on the total non-volatile(dry film) or paint by weight. D. Paint Coordination 1. Provide finish coats which are compatible with prime paint used. Review other sections of these specifications in which prime paint are to be provided to ensure compatibility of total coatings system for various substrates. Upon request from other trades, furnish information in characteristics of finish materials proposed for use, to ensure compatible prime coats are used. 2. Provide barrier coats over incompatible primers or remove and re-prime as required. Notify Architect in writing of any anticipated problems using specified coating systems with substrates primed by others MATERIAL QUALITY A. Provide best quality grade of various types of coatings as regularly manufactured HIGH PERFORMANCE COATINGS
20 PART 3 - EXECUTION by acceptable paint materials manufacturer. Materials not displaying manufacturer s identification as a standard, best grade product will not be acceptable. 1. Proprietary names used to designate colors or materials are for the intended purpose of establishing a minimum standard of quality. 2. Provide undercoat paint produced by same manufacturer as finish coats. Use only thinners approved by paint manufacturer, and use only within recommended limits. B. Acceptable Manufacturers: 1. Tnemec Company, Inc., Kansas City, MO, ( ) 2. Architect-approved equivalent INSPECTION A. Applicator must examine areas and conditions under which painting work is to be applied, and notify Contractor in writing of any conditions detrimental to proper and timely completion of work. Do not proceed with work until unsatisfactory conditions have been corrected in a manner acceptable to Applicator. B. Starting of painting work will be construed as Applicator s acceptance of surfaces and other conditions within any particular area. C. Do not paint over dirt, rust, scale, grease, moisture, scuffed surfaces or conditions otherwise detrimental to formation of a durable paint film SURFACE PREPARATION A. General 1. Perform preparation and cleaning procedures in accordance with paint manufacturer s instructions and as herein specified for each particular substrate condition. a. Remove hardware, hardware accessories, machined surfaces, plates, lighting fixtures and similar items in place and not to be finish painted, or provide surface applied protection prior to surface preparation and painting operations. Remove, if necessary, for complete painting of items and adjacent surfaces. Following completion of painting of each space or area, reinstall removed items. b. Clean surfaces to be painted before applying paint or surface treatments. Remove oil and grease prior to mechanical cleaning. Program cleaning and painting so that contaminants from cleaning process will not fall onto wet, newly painted surfaces. c. Wash all existing surfaces with solution of trisodium phosphate or equal cleaner, followed by a wash with clear water. B. Cementitious Materials 1. Prepare cementitious surfaces of concrete and concrete block to be painted by removing efflorescence, chalk, dust, dirt, grease, oils and by roughening as required to remove glaze. 2. Determine alkalinity and moisture content of surfaces to be painted by performing appropriate tests. If surfaces are found to be sufficiently alkaline to cause blistering and burning of finish paint, correct this condition before application of paint. Do not paint over surfaces where HIGH PERFORMANCE COATINGS
21 moisture content exceeds that permitted in manufacturer s printed directions. 3. Clean concrete floor surfaces scheduled to be painted with a commercial solution of muriatic acid or other etching cleaner. Flush floor with clean water to neutralize acid, and allow to dry before painting. Follow manufacturer s preparation instructions for surfaces if different from above. C. Ferrous Metals 1. Clean ferrous surfaces which are not galvanized or shop coated of oil, grease, dirt, loose mill scale and other foreign substances by solvent or mechanical clean. a. Touch-up shop applied prime coats wherever damaged or bare, where required by other sections of these specifications. Clean and touch-up with same type shop primer. D. Galvanized Surfaces 1. Clean surfaces per ASTM D (2005) as a minimum. Follow manufacturer s written recommendations. Remove all passivators MATERIAL PREPARATION A. Mix and prepare painting materials in accordance with manufacturer s directions. B. Store materials not in actual use in tightly covered containers. Maintain containers used in storage, mixing and application of paint in a clean condition, free of foreign materials and residue. Maintain limited storage quantities as acceptable to the Fire Department. C. Stir materials before application to produce a mixture of uniform density, and stir as required during application. Do not stir surface film into material. Remove film, and if necessary, strain material before using APPLICATION A. General 1. Apply paint in accordance with manufacturer s directions. Use applicators and techniques best suited for substrate and type of material being applied. a. Apply additional coats when undercoats, stains or other conditions show through final coat of paint, until paint film is of uniform finish, color and appearance. Give special attention to ensure that surfaces, including edges, corners, crevices, weld and exposed fasteners receive a dry film thickness equivalent to that of flat surfaces. b. Paint surfaces behind movable equipment and furniture same as similar exposed surfaces. Paint surfaces behind permanently fixed equipment or furniture with prime coat only before final installation of equipment. c. Finish exterior doors on tops, bottoms and side edges same as exterior faces unless otherwise indicated. d. Sand lightly between each succeeding enamel coat. e. Omit first coat (primer) on metal surfaces which have been shop primed and touch-up painted unless otherwise indicated. HIGH PERFORMANCE COATINGS
22 B. Scheduling Painting 1. Apply first coat material to surfaces that have been cleaned, pretreated or otherwise prepared for painting as soon as practicable after preparation and before subsequent surface deterioration. a. Allow sufficient time between successive coatings to permit proper drying. Do not recoat until paint has dried to where it feels firm, does not deform or feel sticky under moderate thumb pressure, and application of another coat of paint does not cause lifting or loss of adhesion of the undercoat. C. Minimum Coating Thickness 1. Apply materials at not less than manufacturer s recommended spreading rate to establish a total dry film thickness as recommended by coating manufacturer. D. Mechanical and Electrical Work 1. Painting of mechanical and electrical work is limited to those items exposed in occupied spaces. E. Prime Coats 1. Apply prime coat of material which is required to be painted or finished, and which has not been prime coated by others. a. Recoat primed and sealed surfaces where there is evidence of suction spots or unsealed areas in first coat, to assure a finish coat with no burn-through or other defects due to insufficient sealing. F. Pigmented (Opaque) Finishes 1. Completely cover to provide an opaque, smooth surface of uniform finish, color, appearance and coverage. Cloudiness, spotting, holidays, laps, brush marks, runs, sags, ropiness or other surface imperfections will not be acceptable CLEAN-UP AND PROTECTION A. Clean-Up 1. During progress of work, remove from site discarded paint materials, rubbish, cans and rags at end of each work day. a. Upon completion of painting work, clean window glass and other paint spattered surfaces. Remove spattered paint by proper methods of washing and scraping, using care not to scratch or otherwise damage finished surfaces. B. Protection 1. Protect work of other trades, whether to be painted or not, against damage by painting and finishing work. Correct any damage by cleaning, repairing or replacing, and repainting as acceptable to Architect. a. At the completion of work of other trades, touch-up and restore all damaged or defaced painted surfaces FINISH PAINTING SCHEDULE A. The following finish systems refer to products of Tnemec Company, Inc., unless indicated otherwise. HIGH PERFORMANCE COATINGS
23 1. CONCRETE AND CMU (Epoxy/Polyurethane System) Coat 1: Tnemec Series 130 Envirofill at 80 sq. ft. per gallon Coat 2: Tnemec Series 280 Tneme-Glaze at 8.0 mils DFT Coat 3: Tnemec Series 297 Enviro-Glaze at 2.5 mils DFT 2. FERROUS METAL, Interior of Metal Doors and Frames of space receiving finish under this section (Surface Preparation: touch up prime coat) Coat 1: Tnemec Series Primer Coat 2 & 3: Tnemec Series 287 at 3.0 mils DFT 3. CONCRETE FLOORS (cover floor finish 6 up wall to form base) Coat 1: Tnemec Series 237 broadcast to refusal at 1/16 Coat 2: Tnemec Series 280 Tneme-Glaze at 10.0 mils DFT Coat 3: Tnemec Series 291 CRU at mils DFT END OF SECTION HIGH PERFORMANCE COATINGS
SECTION RESILIENT TILE FLOORING. A. Section includes vinyl composition floor tile and accessories indicated and as specified.
SECTION 09 65 19 RESILIENT TILE FLOORING PART 1 - GENERAL 1.1 SUMMARY A. Section includes vinyl composition floor tile and accessories indicated and as specified. 1.2 SUBMITTALS A. Product Data: Submit
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 096519 - RESILIENT TILE FLOORING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationA. Section includes surface preparation and the application of paint systems on interior substrates.
SECTION 09 91 23 - INTERIOR PAINTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationB. Store products in dry spaces protected from the weather, with ambient temperatures maintained between 50 and 90 deg F (10 and 32 deg C).
SECTION 09651 - RESILIENT TILE FLOORING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationD. Maintenance data for resilient floor tile to include in Operating and Maintenance Manual specified in Division 1.
SECTION 09660 RESILIENT TILE FLOORING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationDAYTONA BEACH PIER BUILDING RESTORATION 06/10
SECTION 099113 - EXTERIOR PAINTING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes surface preparation and the application of paint systems on the following exterior substrates: 1. Steel. 2. Galvanized
More informationMASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 09 - FINISHES
SECTION 099113 - EXTERIOR PAINTING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes surface preparation and the application of paint systems on the following exterior substrates: 1. Concrete. 2. Concrete
More informationSECTION ACOUSTICAL PANEL CEILINGS
SECTION 095113 ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationConstruction Standards PAGE
Construction Standards PAGE 095113-1 SECTION 095113 - PART 1 - GENERAL 1.1 M.S.U. ISSUES 1. It the intent of MSU that all joint sealants used on its projects will comply with LEED NC 3 Credit Requirements
More informationA. Section includes surface preparation and application of wood finishes[.]
SECTION 09 93 00 - STAINING AND TRANSPARENT FINISHING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationThis Section includes surface preparation and field application of anti-graffiti coating systems for the following vertical and horizontal surfaces:
0 0 0 0 0 0 SECTION 0 ANTI- GRAFFITI COATINGS PART - GENERAL RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division Specification
More informationBanyan Air Service November 18, 2011 AVE Aviation and Commerce Center Building 1 Miami, FL
SECTION 09511 - ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 099600 - HIGH PERFORMANCE COATINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO
SECTION 09 65 16 - RESILIENT SHEET FLOORING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationA. Section includes surface preparation and the application of high-performance coating systems on the following substrates:
ILLINOIS STATE UNIVERSITY CORDOGAN, CLARK & ASSOCIATES, INC. WATTERSON DINING EXPANSION PROJECT 960 RIDGEWAY AVENUE NORMAL, ILLINOIS AURORA, ILLINOIS CCA PROJECT NUMBER: 14362 630-896-4678 BID SET JULY
More informationPRESTON HEALTH SERVICES ARCHITECT'S NO. 2700
SECTION 09 5113 - ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 095113 - ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationUNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:
SECTION 095113 - ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 DEFINITIONS A. AC: Articulation
More information1.1 This Section includes surface preparation and the application of base coats, intermediate and topcoats.
PAINTING GENERAL INFORMATION 1.1 This Section includes surface preparation and the application of base coats, intermediate and topcoats. DESIGN REQUIREMENTS 2.1 Material Compatibility: a. Provide materials
More informationA. This Section includes acoustical panel ceilings installed with exposed suspension systems.
SECTION 09511 ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification
More informationA. Product Data: Submit manufacturer's descriptive literature, and recommendations and instructions for installation.
SECTION 09512 - ACOUSTICAL TILECEILINGS (ACT-01 and ACT-02) PART 1 - GENERAL 1.01 SUMMARY A. Section includes ceilings consisting of acoustical panels and exposed suspension systems. This ceiling system
More informationStore No MAY 13 Addendum No. 1 SECTION ACOUSTICAL PANEL CEILINGS
SECTION 09511 ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationStudent Services & Classroom Addition
SECTION 096813 - TILE CARPETING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSection GYPSUM DRYWALL
Section 09250 GYPSUM DRYWALL 1.00 GENERAL: A. Gypsum Association Specification GA216 and manufacturer's instruction (whichever is more stringent). 2.00 DRYWALL MATERIALS: A. Exposed Gypsum Board: ASTM
More informationARCHITECTURAL GUIDE SPECIFICATIONS - DESCRIPTIVE
ARCHITECTURAL GUIDE SPECIFICATIONS - DESCRIPTIVE MANNINGTON COLORFIELDS SHEET RUBBER FLOORING Section 09 65 16 Sheet rubber Flooring (Thermoset Rubber) Created May 2012 Mannington Mills, Inc. P. O. Box
More informationB. Samples: For each exposed product and for each color and pattern specified.
SECTION 096519 - RESILIENT TILE FLOORING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Vinyl composition floor tile. 2. Vinyl composition floor tile (VCT) shall be installed in each Unit at / in
More informationSECTION GYPSUM BOARD ASSEMBLIES
SECTION 09260 GYPSUM BOARD ASSEMBLIES PART 1 GENERAL 1.1 SUMMARY A. Provide gypsum board assemblies. 1.2 SUBMITTALS A. Product Data: Submit manufacturer's product data and installation instructions for
More informationSECTION RESILIENT FLOORING ACCESSORIES
SECTION 09653 PART I - GENERAL 1.01 DESCRIPTION A. Scope: Work of this Section shall include all materials and installation necessary to provide Resilient Wall Base and Accessories, including resilient
More informationSECTION RESILIENT ATHLETIC SURFACING. B. Related Sections: Section(s) related to this section include:
CONNOR PowerDrop Page 1 SECTION 09624 RESILIENT ATHLETIC SURFACING PART 1 - GENERAL 1.01 SUMMARY A. Section includes: Resilient athletic surfacing, including [recycled] [virgin] rubber flooring B. Related
More informationSTUDIO 2LR ARCHITECTURE + INTERIORS
STUDIO 2LR ARCHITECTURE + INTERIORS 6University of South Carolina, School of Medicine USC SOM #28 Sim II 6311 Garners Ferry Road, Columbia, South Carolina State Project Number: H27-Z325 September 27, 2018
More informationSECTION LINEAR METAL CEILINGS
SECTION 09 5423 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections, apply
More informationSECTION EXTERIOR PAINTING PART 1 - GENERAL 1.1 SUMMARY
SECTION 099113- EXTERIOR PAINTING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes sutface preparation and the application of paint systems on the following exterior substrates: 1. Clay masonry. 2.
More informationPART 1 GENERAL RESILIENT ACCESSORIES
SECTION 09 65 13.33 (09655) PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Resilient Base 2. Transition Edges 3. Stair Nosings 1.2 REFERENCES A. ASTM International Publications: 1. C241 Standard Test
More informationBuildingName The Description of the Project P DOCUMENTS
ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION
More informationPART 1 GENERAL RESILIENT SHEET FLOORING
SECTION 09 65 16 (09652) PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Resilient Sheet Flooring a. All seams heat-welded. 1.2 REFERENCES A. Americans with Disabilities Act (ADA) II Public Accommodations
More informationEnd of Addendum No. 3
ADDENDUM NO. 3 DATE: May 5, 2017 PROJECT: OWNER: BID DATE: Jail Renovations Monday, May 8, 2017 at 2:00 pm The following shall be incorporated into the Contract Documents dated 19 APR 2017. PROJECT MANUAL
More informationSECTION ACOUSTICAL PANEL CEILINGS. A. Section includes acoustical panels and exposed suspension systems for ceilings.
SECTION 09 51 13 ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 SUMMARY A. Section includes acoustical panels and exposed suspension systems for ceilings. 1.2 SUBMITTALS A. Product Data: For each type
More informationStudent Services & Classroom Addition
SECTION 095133 - ACOUSTICAL METAL PAN CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationUniversity of Missouri St. Louis UMSL Project No. S Thomas Jefferson Library Elevator R&B Project No: Renovation & Repairs
SECTION 092116.23 - GYPSUM BOARD SHAFT WALL ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSECTION (09620) - RESILIENT ATHLETIC FLOORING
PART 1 GENERAL 1.01 SUMMARY SECTION 09 65 66 (09620) - RESILIENT ATHLETIC FLOORING A. Section Includes: 1. Resilient Athletic Flooring a. Adhesive and Accessories B. Related Sections: 1.02 REFERENCES 1.
More informationSECTION ACOUSTICAL PANEL CEILINGS
SECTION 09511 - ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION TILE CARPETING
SECTION 096813 TILE CARPETING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationA. This Section includes ceilings consisting of acoustical panels and exposed suspension systems.
SECTION 09 51 13 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationARCHITECTURAL GUIDE SPECIFICATIONS
ARCHITECTURAL GUIDE SPECIFICATIONS MANNINGTON COLORSCAPE, COLORSPEC, & ONE-STEP STAIR TREADS Section 09 65 13.23 Resilient Stair Treads [Thermoset Rubber Type TS] Created November, 2008 Mannington Mills,
More informationSECTION RESILIENT TILE FLOORING
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 09 65 19 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable
More informationSection STATIC DISSIPATIVE RESILIENT FLOORING
THIS DOCUMENT IS INTENDED AS A SUGGESTED GUIDE FOR CREATING, MODIFYING, OR EDITING YOUR CSI FORMATTED 3-PART ARCHITECTURAL GUIDE SPECIFICATIONS. TARKETT WILL NOT BE LIABLE FOR ANY DAMAGES ARISING OUT OF
More informationLOWER MACUNGIE TOWNSHIP COMMUNITY CENTER ADDITIONS AND RENOVATIONS
0 0 0 SECTION 0. - ACOUSTICAL PANEL CEILINGS PART - GENERAL. SUMMARY A. This Section includes the following work:. Acoustical panels and exposed suspension systems for ceilings.. Patching of existing acoustical
More information1. Acoustical panels. 2. Exposed suspension systems for ceilings. 3. Wire hangers, fasteners, main runners, cross tees, and wall angle moldings.
SECTION 095113 - ACOUSTICAL PANEL WALLS & CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSPECIFICATIONS - CARPET TILE 09681
SPECIFICATIONS - CARPET TILE 09681 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 092216 - NON-STRUCTURAL METAL FRAMING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationBid No. B14-09 Building 900 Cafeteria, Multi-Purpose Room Renovation Flooring
Bid No. B14-09 Cafeteria, Multi-Purpose Room Renovation Flooring Addendum No. 1 This Addendum No. 1 sets forth modifications to portions of the bid and contract documents for the above-referenced work
More informationSECTION RESILIENT SHEET FLOORING
SECTION 09 65 16 RESILIENT SHEET FLOORING SPEC WRITER NOTE: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1.
More informationSECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection
SECTION 13090 RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13090-1 LOW INTENSITY RADIATION PROTECTION
More information1. Material:Galvanized or aluminum-coated steel sheet or rolled zinc. 2. Shapes:
SECTION 092900 - GYPSUM BOARD PART 1- GENERAL 1.1 SUMMARY Section Includes: 1. Interior gypsum board. 1.2 ACTION SUBMITTALS Product Data: For each type of product. PART 2 -PRODUCTS 2.1 GYPSUM BOARD, GENERAL
More informationSection RESILIENT TILE FLOORING INCLUDING VINYL COMPOSITION TILE
THIS DOCUMENT IS INTENDED AS A SUGGESTED GUIDE FOR CREATING, MODIFYING, OR EDITING YOUR CSI FORMATTED 3-PART ARCHITECTURAL GUIDE SPECIFICATIONS. TARKETT WILL NOT BE LIABLE FOR ANY DAMAGES ARISING OUT OF
More informationSECTION ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL
SECTION 09511 - ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.01 DESCRIPTION: A. Work under this section is subject to requirements of the Contract Documents including the General Conditions and Supplementary
More informationDIVISION 5 METALS SECTION COLD-FORMED METAL FRAMING
DIVISION 5 METALS SECTION 05 40 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 095423 - LINEAR METAL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION WOOD STRIP FLOORING
SECTION 096429 WOOD STRIP FLOORING PART 1 GENERAL 1.1 GENERAL REQUIREMENTS A. Work of this Section, as shown or specified, shall be in accordance with the requirements of the Contract Documents. 1.2 SECTION
More informationLINEAR METAL CEILINGS Section
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
More informationC. Samples: For each door face material, at least 3 by 5 inches (75 by 125 mm) in size, in specified finish.
SECTION 083113 - ACCESS DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION RESILIENT SHEET FLOORING
SECTION 09665 RESILIENT SHEET FLOORING PART 1 - GENERAL 1.1 DESCRIPTION A. This Section specifies the installation of sheet flooring with backing and integral cove base. 1.2 RELATED WORK A. Color and pattern:
More informationSECTION PAINTING
SECTION 09 91 00 PAINTING PART 1 GENERAL 1.01 SUMMARY A. Provide: 1. Paint: a. Interior Substrates: 1) Concrete masonry units. 2) Precast concrete. 3) Gypsum drywall. 4) Ferrous and zinc-coated metal.
More informationCONDUCTIVE RESILIENT FLOORING
THIS DOCUMENT IS INTENDED AS A SUGGESTED GUIDE FOR CREATING, MODIFYING, OR EDITING YOUR CSI FORMATTED 3-PART ARCHITECTURAL GUIDE SPECIFICATIONS. JOHNSONITE WILL NOT BE LIABLE FOR ANY DAMAGES ARISING OUT
More informationRESILIENT TILE FLOORING
SECTION 09660 RESILIENT TILE FLOORING PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 03300 - Cast-In-Place Concrete. 2. 09665 - Sheet Vinyl Floor System. 3. 08710 - Finish Hardware. 4. 15421 - Drains
More informationSECTION RESILIENT FLOORING
PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 09 65 00 RESILIENT FLOORING A. Resilient sheet and tile flooring B. Resilient base C. Resilient stair nosing, treads, risers and skirting 1.2 REFERENCES A. ASTM
More informationSECTION PORTLAND CEMENT PLASTER (STUCCO) WITH ACRYLIC FINISH
SECTION 09 24 23 - PORTLAND CEMENT PLASTER (STUCCO) WITH ACRYLIC FINISH PART I - GENERAL 1.01 SECTION INCLUDES A. Building paper B. Lath and accessories C. Plaster materials D. Acrylic finish E. Exterior
More informationCONDUCTIVE RESILIENT FLOORING
THIS DOCUMENT IS INTENDED AS A SUGGESTED GUIDE FOR CREATING, MODIFYING, OR EDITING YOUR CSI FORMATTED 3-PART ARCHITECTURAL GUIDE SPECIFICATIONS. JOHNSONITE WILL NOT BE LIABLE FOR ANY DAMAGES ARISING OUT
More informationSection RESILIENT SAFE-T VINYL SHEET FLOORING
RESILIENT SAFE-T VINYL SHEET FLOORING THIS DOCUMENT IS INTENDED AS A SUGGESTED GUIDE FOR CREATING, MODIFYING, OR EDITING YOUR CSI FORMATTED 3-PART ARCHITECTURAL GUIDE SPECIFICATIONS. TARKETT WILL NOT BE
More information1. Gypsum drywall including screw-type metal support system. 2. Drywall finishing (joint tape and compound treatment).
SECTION 09250 GYPSUM DRYWALL PART 1 GENERAL 1.1 RELATED DOCUMENTS A. General provisions of contract, including General Conditions applicable to this section. 1.2 DESCRIPTION OF WORK A. Types of work include:
More informationB. Samples: For each exposed product and for each color and texture specified.
Copyright 201 0 AlA MasterSpec Short Form 02/10 SECTION 095113 -ACOUSTICAL PANEL CEILINGS PART 1- GENERAL 1.1 SUMMARY Section includes acoustical panels and exposed suspension systems for ceilings. 1.2
More informationSECTION (09941) - TEXTURED FINISHING
PART 1 GENERAL 1.01 SUMMARY A. Section Includes: SECTION 09 94 13 (09941) - TEXTURED FINISHING 1. Spray Applied Textured Finish and Primer a. Textured Finish for Ceilings. b. Textured Finish for Walls.
More informationSection RESILIENT TILE FLOORING INCLUDING ECONATURALS RUBBER FLOOR TILE
THIS DOCUMENT IS INTENDED AS A SUGGESTED GUIDE FOR CREATING, MODIFYING, OR EDITING YOUR CSI FORMATTED 3-PART ARCHITECTURAL GUIDE SPECIFICATIONS. TARKETT WILL NOT BE LIABLE FOR ANY DAMAGES ARISING OUT OF
More informationSECTION BROADLOOM CARPET
SECTION 09680 PART I - GENERAL 1.01 DESCRIPTION A. Scope: Work under this Section shall include all materials and installation necessary to provide Carpet as shown and detailed on the Drawings and specified
More informationSECTION STEEL DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS
SECTION 08110 - STEEL DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General, Supplementary, and Special Conditions and Division 1 Specification
More informationGeometrik Manufacturing Inc.
PRODUCT: GEOSQUARE WOOD TILES Page 1 PART I GENERAL 1.1 SECTION INCLUDES 1. GeoSquare wood [acoustical] ceiling tiles. 2. Coordination with other trades that have parts attached to, penetrate through or
More informationZONE 7 WATER AGENCY CWS 5 TURNOUT REPLACEMENT PROJECT # ADDENDUM NO. 3 April 02, 2019
ZONE 7 WATER AGENCY CWS 5 TURNOUT REPLACEMENT PROJECT # 275-18 ADDENDUM NO. 3 April 02, 2019 This Addendum No. 3 ( Addendum ) is dated the date set forth above and modifies certain Bidding Documents issued
More informationNortrax Section David Manchester Road, Ottawa NON-STRUCTURAL METAL FRAMING 16 May 2014 Page 1
16 May 2014 Page 1 PART 1 GENERAL 1.1 DESCRIPTION This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories
More informationSECTION POLYPROPYLENE FABRIC WALL COVERING
PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 09 72 31 POLYPROPYLENE FABRIC WALL COVERING SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. Also delete any other item or paragraph not
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 09 6816 - SHEET CARPETING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationOCALA INTERNATIONAL AIRPORT MBI PN: GENERAL AVIATION TERMINAL JANUARY 16, 2018 ADDENDUM-ISSUE
SECTION 09511 ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION RESINOUS FLOORING
SECTION 09705 PART I - GENERAL 1.01 DESCRIPTION A. Scope: Work of this Section includes all materials and installation necessary to provide resinous flooring system with integral cove base and top finish
More informationA. This section includes pre-finished Higuera Hardwoods bamboo flooring and accessories for floors and stairs.
SECTION PART 1 - GENERAL 1.1 SUMMARY A. This section includes pre-finished Higuera Hardwoods bamboo flooring and accessories for floors and stairs. 1.2 RELATED DOCUMENTS A. Related Sections include the
More informationELASTOFLEX ELASTOMERIC TEXTURED ACRYLIC WALL COATING SPECIFICATION
ELASTOFLEX ELASTOMERIC TEXTURED ACRYLIC WALL COATING SPECIFICATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions,
More informationB. Related Sections: The following Sections contain requirements that relate to this Section:
SECTION 08111 - STEEL DOOR FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION INTUMESCENT MASTIC FIREPROOFING
PART 1 GENERAL 1.01 SUMMARY SECTION 07 81 23 - INTUMESCENT MASTIC FIREPROOFING A. Section Includes: 1. Intumescent Mastic Fireproofing for Application to Exposed Steel 2. Protection of Adjacent Surfaces
More informationA. This Section includes traffic coatings for the following applications:
SECTION 071800 - TRAFFIC COATINGS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes traffic coatings for the following applications: 1. Interior and exterior, pedestrian traffic. 2. Vehicular traffic.
More informationSECTION NON-STRUCTURAL METAL FRAMING
SECTION 09 22 16 PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories
More informationSECTION INTUMESCENT FIREPROOFING
SECTION 078123 INTUMESCENT FIREPROOFING PART 1 GENERAL 1.1 GENERAL REQUIREMENTS A. Work of this Section, as shown or specified, shall be in accordance with the requirements of the Contract Documents. 1.2
More informationB. Samples for Initial Selection: Manufacturer's color charts showing the full range of colors and finishes available for wood flooring.
SECTION 096400- WOOD FLOORING PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationRESILIENT PHOTOLUMINESCENT STAIR TREADS
THIS DOCUMENT IS INTENDED AS A SUGGESTED GUIDE FOR CREATING, MODIFYING, OR EDITING YOUR CSI FORMATTED 3-PART ARCHITECTURAL GUIDE SPECIFICATIONS. JOHNSONITE WILL NOT BE LIABLE FOR ANY DAMAGES ARISING OUT
More informationA. Section includes hydraulic-cement-based, polymer-modified, self-leveling underlayment for application below interior floor coverings.
SECTION 03 54 16 - HYDRAULIC CEMENT UNDERLAYMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More information1.02 SUMMARY A. Section Includes: 1. Repair of two-coat historic exterior vertical plasterwork (stucco)
09 24 00-1 of 7 SECTION 09 24 00 HISTORIC STUCCO MAINTENANCE AND REPAIR PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationA. Product Data: For each type of product specified.
SECTION 09260 - GYPSUM BOARD ASSEMBLIES PART 1 - GENERAL.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION HIGH-PERFORMANCE COATINGS
SECTION 099600 - HIGH-PERFORMANCE COATINGS PART 1 - GENERAL 1.1 SUMMARY A. Section includes surface preparation and the application of high-performance coating systems on the following substrates: 1. Exterior
More informationGUIDE SPECIFICATION
GUIDE SPECIFICATION 09 64 33.01 Kährs Canvas Collection 940 Centre Circle, Suite 1000 Altamonte Springs, FL 32714 Tim Colgan Telephone: 407-492-2441 Fax: 407-260-9933 Tim.colgan@kahrs.com Web Site: http://www.kahrs.com
More informationLINOLEUM SHEET FLOORING
THIS DOCUMENT IS INTENDED AS A SUGGESTED GUIDE FOR CREATING, MODIFYING, OR EDITING YOUR CSI FORMATTED 3-PART ARCHITECTURAL GUIDE SPECIFICATIONS. JOHNSONITE WILL NOT BE LIABLE FOR ANY DAMAGES ARISING OUT
More informationLife Hall Renovation Issued: July 9, 2014 Montclair State University Addendum No. 1 Owner's Project No Cannon Design Project No
SECTION 078100 - APPLIED FIREPROOFING PART 1 - GENERAL 1.1 SUMMARY A. Section includes sprayed fire-resistive materials (SFRM). 1.2 PREINSTALLATION MEETINGS A. Preinstallation Conference: Conduct conference
More informationRD COATINGS -RD-ELASTOFLEX ELASTOMERIC ACRYLIC WALL COATING SPECIFICATION
RD COATINGS -RD-ELASTOFLEX ELASTOMERIC ACRYLIC WALL COATING SPECIFICATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions,
More information