FRP Floor Panels Standard Specification
|
|
- Cathleen Reynolds
- 1 years ago
- Views:
Transcription
1 1. Scope Furnish all labor, materials, equipment and incidentals necessary to install the fiberglass reinforced polymer (FRP) products as specified herein. The work covered by this section shall include (but shall not be limited to) materials and installation for the fiberglass reinforced plastic (FRP) Floor Panel System. 2. Design Criteria 3. Materials The design of FRP products including connections shall be in accordance with governing building codes and standards as applicable. Design live loads of FRP floor panels shall not be less than 100 PSF uniformly distributed unless specifically stated otherwise in drawings and/or supplementary conditions. Floor panel deflection at the center of a simple span not to exceed Structural members shall be designed to support all applied loads. Deflection in any direction shall not be more than L/180 of span for structural members. Connections shall be designed to transfer the loads. Materials used in the manufacture of the FRP products shall be raw materials in conformance with the specification. All materials shall be of the kind and quality specified. All FRP products shall be manufactured utilizing Polyester or Vinyl ester resin with flame retardant and ultraviolet (UV) inhibitor additives. A synthetic surface veil shall be the outermost layer covering the exterior surface. The flame retardant FRP shapes shall achieve a flame spread rating in accordance with ASTM test method E- 84. (Polyester resin is available without flame retardant and UV inhibitor additives.) If required, after fabrication, all cut ends, holes and abrasions of FRP shapes shall be sealed with a compatible resin coating. FRP products exposed to weather shall contain an ultraviolet inhibitor. Should additional ultraviolet protection be required, a one mil minimum UV coating shall be applied. All exposed surfaces shall be smooth and true to form.
2 4. Physical Properties, Electrical properties & Flammability Property at 70F Amount Test Method Ultimate Tensile Strength 26,500 psi ASTM D-638 Tensile Modulus 1.5 x 106 psi ASTM D 638 Flexural Strength 30,000 psi ASTM D 790 Flexural Modulus 1.5 x 106 psi ASTM D 790 Punch Shear 23,000 psi ASTM D-732 Barcol Hardness ASTM D 2583 Glass Content 45% ASTM D 2584 Table 1: Physical properties ELECTRICAL ASTM TEST METHOD UNITS/ VALUE Amount Arc Resistance, LW D495 seconds 120 Dielectric Strength, LW D149 KV/in 35 KV/mm 1.38 Dielectric Strength, PF D149 volts/mil 200 FLAMMABILITY ASTM TEST METHOD UNITS/ VALUE Amount Tunnel Test E Max NBS Smoke Chamber E (typical) Flammability UL Thermal Index D635 Generic Self Extinguishing o C 130 British Fire Test BS Class 1 Table 2: Electrical properties & Flammability
3 All values are minimum ultimate properties from coupon tests except as noted. ℵ This value is determined from full section simple beam bending of Edgeng structural shapes. R The Shear Modulus value has been determined from tests with full sections of Edgeng structural shapes. (See the EdgengDesign Manual for further information.) Plate compressive stress/modulus measured edgewise and flexural stress/modulus measured flatwise. Measured as a percentage maximum by weight. Typical values because these are shape and composite dependent tests. This is a typical value which varies with composite thickness. LW = Lengthwise CW = Crosswise PF = Perpendicular to laminate face N.T. = Not Tested 5. Submittals Submittals shall include, but not be limited to: A. Drawings including layouts; connection and framing details; fastener types and spacing; product description. B. Material certifications. C. Operation and maintenance data for the FRP Floor panel System. 6. Quality Assurance A. Qualifications: Five years successful experience in fabricating FRP Floor Panel Systems would be the minimum requirement for the manufacturer. FRP Floor Panel System manufacturer shall retain a registered professional engineer legally qualified to practice in same state as the Site. Responsibilities include: o FRP Floor Panel System performance and design criteria stated in the Contract Documents shall be reviewed. o Written requests should be prepared for clarifications or interpretations of performance or design criteria for submittal to engineer or contractor. o Preparation of design calculations verifying compliance of FRP Floor Panel System with requirements of the Contract Documents should be supervised. o Signing and sealing all calculations. o Design of FRP Floor Panel System was performed in accordance with performance and design criteria stated in the Contract Documents should be certified
4 Installer Qualifications o Retain a single installer trained and with record of successful experience in installing FRP Floor Panel Systems. o Installer shall have record of successfully installing F FRP Floor Panel Systems in accordance with recommendations and requirements of manufacturer, or shall provide evidence of being acceptable to the manufacturer. o Installer shall employ only tradesmen with specific skill and successful experience in the type of Work required. o When requested by the engineer, submit name and qualifications of installer with the following information for at least three successful, completed projects: o Names and telephone numbers of owner and architect or engineer responsible for each project. o Approximate contract cost of the FRP Baffle Wall Systems for which installer was responsible. B. System Manufacture 1. EDGENG 2. If Contractor wished to furnish an alternate system manufacturer, Contractor shall first make written application to Engineer for acceptance thereof, certifying that the proposed substitute will perform adequately the functions and achieve the results called for by the general design, be similar in substance to that specified and be suited to the same use as that specified. The application will also contain an itemized estimate of all costs or credits that will result directly or indirectly from acceptance of such substitute, including costs of redesign and claims of other contractors affected by the resulting change, all of which will be considered by Engineer in evaluating the proposed substitute. C. Source Quality Control: FRP Floor Panel System manufacturer shall prepare all Shop Drawings and other submittals (except for delegated design submittals, when professional engineer is retained by other than FRP Floor Panel System manufacturer) for all components furnished under this Section. Components shall be specifically constructed for specified service conditions and shall be integrated into overall assembly by FRP Floor Panel Systems. 7. Warranty Minimum of one year for the materials and for the workmanship of the fabricated product, after the installation with a maximum of eighteen months would be the general warranty for these FRP Floor Panels.
5 8. Material Handling At the time of delivery, all materials shall be inspected for shipping damage. The freight company and the Manufacturer shall be notified immediately of any damage or quantity shortages. The Contractor shall protect FRP materials from cuts, scratches, gouges, abrasions, and impacts. When lifting FRP materials, spreader bars shall be used (not wire slings unless materials are fully protected). FRP components shall not be dragged across one another unless separated by a non-scratching spacer. 9. Installation Before placing and attaching components, the contractor shall confirm the alignment and location of FRP Floor Panels and its base structure. All bearing surfaces must be level, flat, clean and free of debris. Erection shall proceed according to sequence shown on the approved drawings. Contractor shall install pads, curbs or piers to modify uneven or sloped concrete surfaces to create a flat, level surface for FRP Floor Panel System attachment. Contractor shall field cut materials as required and shown on the Manufacturer's drawings. Contractor shall seal field cut edges with NSF approved material. Contractor shall install Panels and connections as shown on the approved layout drawings. Field modifications (cuts, copes, holes, etc.) unless shown on the drawings are not allowed without the manufacturer's written approval. Before placement of Floor panels, contractor shall check alignment and location of framing members and existing structure. Contractor shall adjust FRP Floor Panels for proper bearing and alignment.
FRP Specifications. Section Fiberglass Reinforced Polymer (FRP) Structural Shapes/Plate and Fabrications REVISED
FRP Specifications Section 06 71 00 Fiberglass Reinforced Polymer (FRP) Structural Shapes/Plate and Fabrications REVISED 11.2016 BRISTOL FACILITY 400 Commonwealth Ave., P. O. Box 580, Bristol, VA 24203-0580
FRP Baffle Wall Standard Specification-Section 11350
-Section 11350 1. General Information The work covered by this section shall include (but shall not be limited to) materials and installation for the fiberglass reinforced plastic (FRP) Baffle Wall System.
FRP Specifications. Section Fiberglass Reinforced Polymer (FRP) Hollow Core Building Panels Products and Fabrications REVISED 11.
FRP Specifications Section 06 70 00 Fiberglass Reinforced Polymer (FRP) Hollow Core Building Panels Products and Fabrications REVISED 11.2016 BRISTOL FACILITY 400 Commonwealth Ave., P. O. Box 580, Bristol,
FRP Specifications. Section Fiberglass Reinforced Polymer (FRP) Baffle Wall Panel Products and Fabrications REVISED 11.
FRP Specifications Section 06 70 00 Fiberglass Reinforced Polymer (FRP) Baffle Wall Panel Products and Fabrications REVISED 11.2016 BRISTOL FACILITY 400 Commonwealth Ave., P. O. Box 580, Bristol, VA 24203-0580
FRP Specifications. Section Fiberglass Reinforced Polymer (FRP) Molded Grating and Treads Products and Fabrications REVISED 11.
FRP Specifications Section 06 74 13 Fiberglass Reinforced Polymer (FRP) Molded Grating and Treads Products and Fabrications REVISED 11.2016 BRISTOL FACILITY 400 Commonwealth Ave., P. O. Box 580, Bristol,
FRP Specifications. Section Fiberglass Reinforced Polymer (FRP) Pultruded Grating/Treads and Fabrications REVISED
FRP Specifications Section 06 74 13 Fiberglass Reinforced Polymer (FRP) Pultruded Grating/Treads and Fabrications REVISED 11.2016 BRISTOL FACILITY 400 Commonwealth Ave., P. O. Box 580, Bristol, VA 24203-0580
ENGINEERING SPECIFICATION PULTRUDED DYNAFORM FIBERGLASS STRUCTURAL SHAPES. March 16,
ENGINEERING SPECIFICATION PULTRUDED DYNAFORM FIBERGLASS STRUCTURAL SHAPES March 16, 2015 06610-1 SECTION 06610 FIBERGLASS REINFORCED PLASTICS (FRP) FABRICATIONS PULTRUDED FIBERGLASS STRUCTURAL SHAPES PART
PROForms. Specifications SECTION FIBERGLASS REINFORCED POLYMER (FRP) PULTRUDED PRODUCTS
PROForms Specifications SECTION 06600 FIBERGLASS REINFORCED POLYMER (FRP) PULTRUDED PRODUCTS Disclaimer BEDFORD REINFORCED PLASTICS INC. disclaims liability for any personal injury, property or other damages
ENGINEERING SPECIFICATION. PULTRUDED PEDESTRIAN FIBERGLASS GRATING SAFE-T-SPAN T1210 VINYL ESTER and ISOPHTHALIC. October 25, 2004 Revision 1
ENGINEERING SPECIFICATION PULTRUDED PEDESTRIAN FIBERGLASS GRATING SAFE-T-SPAN T1210 VINYL ESTER and ISOPHTHALIC 1 PART 1 - GENERAL 1.1 SCOPE OF WORK SECTION 06610 FIBERGLASS REINFORCED PLASTICS (FRP) FABRICATIONS
WEIR PLATES & SCUM BAFFLES
WEIR PLATES & SCUM BAFFLES Bedford Reinforced Plastics Weir Plates and Scum Baffles are available in any SIZE, any LENGTH and any CONFIGURATION Benefits Corrosion Resistant Maintenance Free Strong Easy
Dynaform Structural Shapes
CELEBRATING 50YEARS High Performance Composite Solutions Dynaform Structural Shapes Products Brochure Dynaform Structural Shapes Square Tube Channel Angle Wide Flange Beam Concrete Embedment Angles Custom
Dynaform Structural Shapes
CELEBRATING 50YEARS Building the World to Last HIGH PERFORMANCE COMPOSITE SOLUTIONS Dynaform Structural Shapes SI Units Dynaform Structural Shapes Square Tube Channel Angle Wide Flange Beam Concrete Embedment
SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM
PART 1- GENERAL 1.1 SUMMARY A. Section Includes: SECTION 084523 - SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 1. Flat factory prefabricated structural insulated translucent sandwich panels; with glazed endwalls.
ENGINEERING SPECIFICATION PULTRUDED DYNAFORM FIBERGLASS STRUCTURAL SHAPES FIBERGRATE MOLDED GRATING WITH GRATING PEDESTALS. January 24,
ENGINEERING SPECIFICATION PULTRUDED DYNAFORM FIBERGLASS STRUCTURAL SHAPES FIBERGRATE MOLDED GRATING WITH GRATING PEDESTALS January 24, 2014 06600-1 SECTION 06610 FIBERGLASS REINFORCED PLASTICS (FRP) FABRICATIONS
ENGINEERING SPECIFICATION FIBERTRED MOLDED STAIR TREADS SECTION 06610
ENGINEERING SPECIFICATION FIBERTRED MOLDED STAIR TREADS SECTION 06610 PART 1 - GENERAL 1.1 SCOPE OF WORK FIBERGLASS REINFORCED PLASTICS (FRP) FABRICATIONS MOLDED STAIR TREADS A. The CONTRACTOR shall furnish,
Introduction. Strongwell's 398,000 sq. ft. Bristol, Virginia facility is the world's largest pultrusion operation.
Introduction Strongwell's 398,000 sq. ft. Bristol, Virginia facility is the world's largest pultrusion operation. What you see below is not the erection of a steel structure. Rather, it is a structure
ENGINEERING SPECIFICATION FIBERGRATE MOLDED GRATING
ENGINEERING SPECIFICATION FIBERGRATE MOLDED GRATING 1 PART 1 - GENERAL 1.1 SCOPE OF WORK SECTION 06610 FIBERGLASS REINFORCED PLASTICS (FRP) FABRICATIONS MOLDED GRATING A. The CONTRACTOR shall furnish,
SECTION FIBERGLASS REINFORCED POLYMER (FRP) PANELS
SECTION 07 44 50 FIBERGLASS REINFORCED POLYMER (FRP) PANELS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Design, Engineering, manufacturing and erection of fiberglass reinforced panels. Delegated Design of
SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.
SECTION 06 12 00 STRUCTURAL INSULATED PANELS ------------------------------------------------------------------------------------------------------------ PART 1- GENERAL ----------------------------- 1.1
CS-100 Guide Specifications
MANUFACTURER CUSTOM-BILT METALS 1333 Corporate Drive, Suite 103 Irving, Texas 75038-2520 (800) 826-7813 or info@custombiltmetals.com www.custombiltmetals.com CS-100 Guide Specifications This Guide Specification
FIBERGLASS STRUCTURAL SHAPES AND PLATE
FIBERGLASS STRUCTURAL SHAPES AND PLATE Introduction Strongwell's 350,000 sq. ft. Bristol, Virginia facility is the world's largest pultrusion operation. What you see below is not the erection of a steel
Lamit Industries, Inc. 710 Marion Road Columbus, Ohio P-(614) F-(614)
Lamit Industries, Inc. 710 Marion Road Columbus, Ohio 43207 P-(614)444-3010 F-(614)444-4264 info@lamitindustries.com www.lamitindustries.com SECTION 06120 STRUCTURAL INSULATED PANELS PART 1 GENERAL 1.01
The Pultex Pultrusion Design Manual
The Pultex Pultrusion Design Manual of Standard and Custom Fiber Reinforced Polymer Structural Profiles Imperial Version Volume 5 Revision 6 Featuring Pultex Standard Structural Profiles Pultex SuperStructural
Product Guide Specification
April 2014 6840 SW 81 Terrace Miami, Florida 33143 Phone 305-666-6676 Fax 305-666-7675 Website www.trimstonepanels.com E-mail stoneworks@stoneworksofart.com Product Guide Specification Specifier Notes:
SPECIFICATION GUIDELINE
Environmental StoneWorks specification guideline should be used to assist design professionals in the preparation of projects. Edit and delete items that may not be applicable. Verify all referenced section
SPECIFICATION GUIDELINE
SPECIFICATION GUIDELINE Environmental Stoneworks Corporate Office 6300 East Stapleton Drive South Denver, CO 80216 Phone (303) 309-3040 Fax (303) 309-3059 www.estoneworks.com Environmental Stoneworks specification
Section [ ] Stormwater Catch Basin Filtration Device
PART 1 GENERAL Section [ ] Stormwater Catch Basin Filtration Device 01.01.00 Purpose The purpose of this specification is to establish generally acceptable criteria for devices used for filtration of stormwater
PRODUCT SPECIFICATIONS
PART 1 GENERAL 1.01 SUMMARY A. Section Includes: High density cast resin architectural products, including columns, panels, caps, bases, trim elements and balustrade systems. Specifier Note: Article below
SECTION EXPANSION CONTROL
SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
SECTION EXPANSION CONTROL
SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-06 71 33 (February 2015) ----------------------------- Preparing Activity: NASA Superseding UFGS-06 71 33 (May 2012) UNIFIED FACILITIES GUIDE SPECIFICATIONS References
First Class Building Products, Inc.
PART 1- GENERAL 1.01 SUMMARY First Class Building Products, Inc. A. Related sections: 1.02 REFERENCES GLASS-FIBER REINFORCED GYPSUM (GRG) 1. Division 5, Metal Stud Framing 2. Division 7, Sealants 3. Division
SECTION WINDOW FILM. Display hidden notes to specifier. (Don't know how? Click Here) Copyright ARCAT, Inc. - All rights reserved
SECTION 08 87 13 WINDOW FILM Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2008-2010 ARCAT, Inc. - All rights reserved PART 1 GENERAL 1.1 SECTION INCLUDES A. Safety and Security
Section PANEL SIGNAGE
Section 10 14 23 PANEL SIGNAGE PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including FDOT DIVISION I GENERAL REQUIREMENTS & COVENANTS Specification Sections,
SPECIFICATIONS FOR BRIDGE CONSTRUCTION SECTION 5 REINFORCING STEEL. 5.1 General Certification Fabrication...
SPECIFICATIONS FOR BRIDGE CONSTRUCTION SECTION 5 REINFORCING STEEL TABLE OF CONTENTS 5.1 General...5-1 5.2 Certification...5-1 5.3 Fabrication...5-1 5.4 Handling and Storage...5-1 5.5 Field Repair of Epoxy
SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM
Page 1 of 6 SECTION 08 32 20 LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS SLIDING DOORS. SECTION INCLUDES OVERHEAD SLIDING TUBE ASSEMBLY, MOUNTING
Section Glass Wall Cladding
OPACI-COAT-300 GLASS WALL CLADDING SUGGESTED SPECIFICATION PART 1 - GENERAL 1.01 DESCRIPTION A. General Information 1. The other contract documents complement the requirements of this section. 2. Requirements
Section BUILDINGS, SHELTERS, ENCLOSURES
Section 13121 BUILDINGS, SHELTERS, ENCLOSURES Part 1 GENERAL 1.1 SECTION INCLUDES 1.2 A. Pre-engineered buildings. B. Pre-engineered shelters. C. Pre-engineered enclosures. D. Electrical wiring and devices
and FIBERGLASS FOAM AND HOLLOW CORE BUILDING PANELS
and FIBERGLASS FOAM AND HOLLOW CORE BUILDING PANELS DURASHIELD Fiberglass Foam Core Building Panels Features The DURASHIELD panel is a tongue-and-groove fiberglass pultruded panel comprised of a pultruded
ThermalShell Modular Insulated Pre-Cast Panels
412 N. California St. Building #2 Sycamore IL, 60178 Phone: 815.899.0224 Fax: 815.899.0226 E-mail: info@thermalshell.com Web: www.thermalshell.com ThermalShell Modular Insulated Pre-Cast Panels Construction
PLASTERFORM GLASSFIBER REINFORCED GYPSUM (GRG) REV: 4/11
Plasterform Inc. 1180 Lakeshore Road East, Mississauga, Ontario Canada L5E 1E9 t 905.891.9500 1.800.268.4534 f 905.891.2232 plasterform.com SECTION 09285 PLASTERFORM GLASSFIBER REINFORCED GYPSUM (GRG)
SECTION COMPOSITE METAL WALL PANEL SYSTEM (Accu-Trac Low Profile DS)
SECTION 07412 COMPOSITE METAL WALL PANEL SYSTEM (Accu-Trac Low Profile DS) PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
Florock Seamless Flooring Systems
Architectural Specification FloroBuild PT/ HT Epoxy Mortar ¼ Power Trowel or Hand Trowel Flooring System Part 1: General 1.01 System Description A. Roller-applied 100% solids, penetrating epoxy primer
STATE UNIVERSITY CONSTRUCTION FUND. UNIVERSITY CON DIRECTIVE 5-1 Issue date: October 2014
STATE STRUCTION FUND DIRECTIVE 5-1 Issue date: October 2014 STRUCTURAL STEEL 1. General: It is the Fund's policy that the design of the structural steel is the prime responsibility of the project's Structural
SECTION WINDOW FILM. Display hidden notes to specifier. (Don't know how? Click Here) Copyright ARCAT, Inc. - All rights reserved
SECTION 08 87 13 WINDOW FILM Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2008-2010 ARCAT, Inc. - All rights reserved PART 1 GENERAL 1.1 SECTION INCLUDES A. Safety and Security
FRP REBAR: MDOT APPROVED
FRP REBAR: MDOT APPROVED MDOT SPECIAL SPEC 12DS802(K075) ALLOWS BASALT FRP RUST-FREE REBAR THAT EXTENDS THE LIFESPAN OF CONCRETE. QUINCY STREET, HANCOCK, MI GATORBAR PILOT PROJECT = SUCCESS #3 GatorBar
(Project Location) (your firm's name)
SECTION 07 21 00 THERMAL INSULATION PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including the Conditions of the Contract and Division 01 Specification Sections
SECTION RESINOUS FLOORING or SECTION QUARTZ FLOORING
SECTION 09 67 23 RESINOUS FLOORING or SECTION 09 67 26 QUARTZ FLOORING PART 1 - GENERAL 1.1 SUMMARY (Specification writer shall add, delete or amend, as deemed necessary) A. Provide all labor, materials,
Section HIGH-TENSION Stretched-Fabric Wall Systems SoftWalls, Inc.
P a g e 1 PART I. GENERAL 1.01 Scope A. Furnish and install SoftWalls HIGH-TENSION Acoustical & Tackable Stretch Fabric Systems B. Related Work Specified Elsewhere: 1.Preparation of a smooth, flat and
SPECIFICATIONS FOR AluSystems Aluminum Composite Panels Series 20 Dry Joint 1.00 GENERAL 1.01 RANGE OF WORK Section includes: Laminated panels and attachment systems for use as exterior cladding. A. Provide
Alply CLASSIC WALL Architectural Insulated Panel Wall System
SECTION 07 42 13 INSULATED METAL WALL PANELS ALPLY Insulated Panels Alply CLASSIC WALL Architectural Insulated Panel Wall System PART 1 / GENERAL 1.1 SYSTEM DESCRIPTION A. Smooth, non-embossed steel, insulated
SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT
Page 220529-1 SECTION 220529 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
SECTION STAY-IN-PLACE INSULATED CONCRETE FORMING SYSTEM
ARCHITECTURAL SPECIFICATIONS MANUFACTURER: InterBlock LLC PO Box 1123, Sheboygan, WI 53082 Phone Number 920-207-7234 SECTION 03100 STAY-IN-PLACE INSULATED CONCRETE FORMING SYSTEM PART 1 GENERAL 1.01 Summary
SL150 Guide Specification
SL150 Guide Specification This is a suggested guide specification for metal roofing projects where the SL150 panel system is applicable. Questions regarding applicability should be discussed with Union
SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and
COMPOSOLITE FIBERGLASS BUILDING PANEL SYSTEM
COMPOSOLITE FIBERGLASS BUILDING PANEL SYSTEM COMPOSOLITE Building Panel System Odor control covers at the Trinity River Waste Water Treatment Plant in Dallas, Texas, utilize COMPOSOLITE panels because
SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS
SECTION 08 32 20 CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS Page 1 of 6 USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,
CSI GUIDE Countertops
CSI GUIDE Countertops Part 1 General 1.0 RELATED DOCUMENTS A. Drawings and general provisions of the contract, including general and supplementary conditions and Division 1 Specification Sections, apply
09/07/07 GLASSFIBER REINFORCED GYPSUM (GRG) C. S. I Spec Master Spec Page 1
Page 1 PART 1 - GENERAL 1.01 SUMMARY:.01 Provide special glassfiber reinforced gypsum (GRG) shapes in accordance with the requirements of the contract documents..02 The installing contractor shall be responsible
SECTION HANGERS AND SUPPORTS FOR PLUMBING
SECTION 22 05 29 HANGERS AND SUPPORTS FOR PLUMBING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
SECTION PRE-ENGINEERED MEMBRANE STRUCTURE
SECTION 13125 PART 1 - GENERAL 1.1 SUMMARY A. Section includes the design, engineering, fabrication and erection of a frame-supported, tensilemembrane structure complete with entrance and exit doors and
SECTION Structured Polycarbonate Panel Assemblies. Series 3500 BPC System with 40mm Tongue and Groove
Duo-Gard Industries Inc. 40442 Koppernick Road Canton, Michigan 48187 Phone (734) 207-9700 Fax (734) 207-7995 www.duo-gard.com SECTION 08 45 13 Structured Polycarbonate Panel Assemblies Series 3500 BPC
ST. JOHNS COUNTY ARCH. PROJ. NO SECTION PREFABRICATED ALUMINUM CANOPIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS
SECTION 10530 PREFABRICATED ALUMINUM CANOPIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
SECTION WINDOW FILM. A. Section Windows; windows to receive architectural window film.
SECTION 08870 WINDOW FILM PART 1 GENERAL 1.1 SECTION INCLUDES A. Safety and security films. 1.2 RELATED SECTIONS A. Section 08500 - Windows; windows to receive architectural window film. B. Section 08600
The Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers.
SECTION 05 31 13 STEEL FLOOR DECKING PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the contract, including General and Supplementary Conditions and Division 01 - Specification
FIBERGLASS HANDRAIL & LADDER SYSTEMS
FIBERGLASS HANDRAIL & LADDER SYSTEMS Fiberglass Handrail Systems SAFRAIL system in a chemical plant. Internal connections make circular handrail systems such as these possible around tanks. SAFRAIL fiberglass
Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1
Louis Armstrong New Orleans International Airport NOAB Project # 8910-01233 PART 1 - GENERAL SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS 1.1 RELATED DOCUMENTS A. Drawings and general provisions
Architectural Single-Hung Aluminum Window Series L701T SH-AW130 GUIDE SPECIFICATION
Architectural Single-Hung Aluminum Window Series L701T SH-AW130 GUIDE SPECIFICATION Section 08520 Aluminum Windows PART 1: WORK INCLUDED A. The conditions of the contract and applicable sections of Division
Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi
STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel
Architectural Specifications, Section Phenolic Lockers
Architectural Specifications, Section 10500 Phenolic Lockers Hollman, Inc., 1825 W. Walnut Hill Lane, Irving, TX 75038, (972) 815-4000, www.hollman.com 1.0 GENERAL 1.1 SECTION INCLUDES A. Phenolic Lockers.
Floor Insulation Underlayment Section Sound Control Matting
Floor Insulation Underlayment Section 09618 Sound Control Matting Part I General 1.1 Summary A. Section includes a sound control material for achieving an STC and IIC rating in excess of 50 to meet building
02800 SHADE STRUCTURES
02800 SHADE STRUCTURES for PLAY AREAS ****************************************** SPECIFIER: The shade structure shall utilize a four point hypar system with four columns located a minimum of 10 feet from
STANDARD SPECIFICATIONS RTPV100 PLAS-TANKS INDUSTRIES, INC. 39 STANDEN DRIVE HAMILTON, OH TELEPHONE (513) FACSIMILE (513)
STANDARD SPECIFICATIONS RTPV100 PLAS-TANKS INDUSTRIES, INC. 39 STANDEN DRIVE HAMILTON, OH 45015 TELEPHONE (513) 942-3800 FACSIMILE (513) 942-3993 Filament Wound and Contact Molded Reinforced Thermoset
Product Specifications
Product Specifications Bedford Standard Ladders Disclaimer BEDFORD REINFORCED PLASTICS INC. disclaims liability for any personal injury, property or other damages of any nature whatsoever, whether special,
Broadcast Parking Garage System
AIA Specification Part 1 General Broadcast Parking Garage System 1.01 Work Included A. All work to be provided in this section shall include material, labor, and equipment necessary to furnish the complete
FIBERGLASS ROUND CONTROL DAMPERS. Model K-RD INTRODUCTION M.K. PLASTICS PROVIDES FOUR DAMPER MODELS K-RD SUGGESTED SPECIFICATION
INTRODUCTION The M.K. Plastics series K-RD are manufactured to meet the needs of the odor control and corrosive HVAC industries by providing a corrosion-resistant FRP Damper that is used to regulate an
SECTION EXTERIOR GRILLS AND SCREENS
SECTION 10 82 13 PART 1 GENERAL PART 1 1 SUMMARY A. Section Includes: 1. Exterior perforated aluminum screen wall system with Ombrae TM Optical Tile imaging technology. 2. Accessories including attachments,
ENKASONIC FLOOR UNDERLAYMENT 9110
ENKASONIC FLOOR UNDERLAYMENT 9110 GS1197 Section 13080 SECTION 09618 SOUND CONTROL MATTING Part I General 1.1 Summary A. Section includes a sound control material for achieving an STC and IIC rating in
1. Cast-in-place concrete is specified in Section
SECTION 03 38 00 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section describes the requirements for furnishing and installing post-tensioned slabs, jacks, jacking and anchors at Parking Structure, and record
COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100
COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100 Part 1 General 1.01 Work Included A. The work under this section shall include the furnishing of all items shown on the drawings and as specified,
SECTION WINDOW FILM. Display hidden notes to specifier. (Don't know how? Click Here) Copyright ARCAT, Inc. - All rights reserved
SECTION 08 87 13 WINDOW FILM Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2008-2010 ARCAT, Inc. - All rights reserved PART 1 GENERAL 1.1 SECTION INCLUDES A. Safety and Security
SECTION METAL FLOOR PLATE STAIRS
SECTION 05513 - METAL FLOOR PLATE STAIRS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
RAY-CORE Structural Insulated Roof and Wall Panels
SUBMITTAL 20180101 RAY-CORE Structural Insulated Roof and Wall Panels Closed Cell Polyurethane Foam Insulation Douglas Fir Studs STANDARD FEATURES Insulation, Framing and Wrap in a 4 wide panel Available
Daytona Beach Pier Building Renovation Jun 2010
SECTION 15060 - HANGERS AND SUPPORTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
GUIDE SPECIFICATIONS CURA ADJUSTABLE REROOF FRAMING SYSTEMS SECTION REROOFING ADJUSTABLE FRAMING SYSTEM
- --- -- ----..-------~------------------------------------ GUIDE SPECIFICATIONS CURA ADJUSTABLE REROOF FRAMING SYSTEMS SECTION 07415 REROOFING ADJUSTABLE FRAMING SYSTEM PART 1 - GENERAL 1.01 SCOPE A.
A. Submit the following in addition to the standard requirements.
SECTION [13120] OMNIFLEX 300 MODULAR WALL SYSTEM SECTION 1 GENERAL 1.01 SECTION INCLUDES A. This Section specifies all requirements necessary to furnish and install a complete modular wall system including,
SECTION PANEL AND POST AND PYLON SIGNAGE. 1. Non-illuminated Panel and Post signs. 2. Internal illumination Pylon (Cabinet and Post) signs.
PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Non-illuminated Panel and Post signs. 2. Internal illumination Pylon (Cabinet and Post) signs. 1.2 PERFORMANCE REQUIREMENTS A. Structural
May 8, 2017 ADDENDUM #1. IFB Resin Floor System For Highway Department Central District Building
May 8, 2017 ADDENDUM #1 IFB 17-082 Resin Floor System For Highway Department Central District Building Addendum #1 is being issued to offer an alternate resin flooring system. 096700 FLUID-APPLIED FLOORING
SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS
SECTION 075423 - THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Division 00 Bidding Requirements and other Division
Guideline Specifications
Page 1 of 7 PART 1 Guideline Specifications Exterior Aluminum/Composite Wall Panels GENERAL ARROWHEAD 508 SYSTEM Pressure Equalized Rainscreen SECTION 07410 1.01 SUMMARY A. Work of this section included
Product Guide Specification
Norplex-Micarta March 2011 665 Lybrand Street Postville, Iowa 52162 Toll Free (800) 848-4431 Phone (563) 864-7321 Fax (563) 864-4231 Website www.norplex-micarta.com E-mail info@norplex-micarta.com Product
SECTION WINDOW FILM. Display hidden notes to specifier. (Don't know how? Click Here) Copyright ARCAT, Inc. - All rights reserved
SECTION 08 87 13 WINDOW FILM Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2008-2010 ARCAT, Inc. - All rights reserved PART 1 GENERAL 1.1 SECTION INCLUDES A. Safety and Security
MODEL SPECIFICATIONS: Hydraulically Driven Steel Underpinning Pile Specifications
MODEL SPECIFICATIONS: Hydraulically Driven Steel Underpinning Pile Specifications Mar/2008 v1.0 SECTION 02255 HYDRAULICLY DRIVEN STEEL UNDERPINNING PILES PART 1 GENERAL 1.01 SCOPE OF WORK The work shall
SECTION PERMANENT FORMS Insulating Concrete Forms Rev
SECTION 03 11 19 PERMANENT FORMS Insulating Concrete Forms Rev 5.20.14 PART 1 GENERAL 1.01 SUMMARY A. Supply and installation of permanent insulating concrete forms as formwork, placement of steel reinforcement
Re-Grate Pultruded Grating
RE-GRATE GRP Pultruded grating is made up of a 70% glass to 30% resin ratio, and encompasses twice the stiffness of RE-GRID Moulded Grating as it allows it to span greater distances. The uni-directional
Proudly Made in the U.S.A.
5-Year Warranty Proudly Made in the U.S.A. Cast-In-Place (wet-set) 2 Cast-In-Place (wet-set) Tactile Proudly Made in the U.S.A. In stock colors White 37875 Brick Red 20109 Yellow 33538 Blue 15187 Safety
PRODUCT GUIDE SPECIFICATION
PRODUCT GUIDE SPECIFICATION Specifier Notes: This product guide specification is written according to the Construction Specifications Institute (CSI) 3-Part Format, including MasterFormat, SectionFormat,
DIVISION 03 CONCRETE SPECIFICATION : FORMS AND FORMWORK
DIVISION 03 CONCRETE SPECIFICATION 031000: FORMS AND FORMWORK PART 1.0 GENERAL 1.1 DESCRIPTION The work of this specification includes furnishing of all labor, materials, equipment and incidentals to install,
OptiLiner Banded Liner System, Thermal, Metal Building
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.