1 September 29, 2017 TO: REF: CONDITION OF PROPERTY SURVEY Structural Integrity of Framing. Dear Ms. : HEDDERMAN ENGINEERING, INC. performed an inspection today on the property located at, Houston, Texas. The purpose of the inspection was to view the evidences of water penetration, and give our professional opinion on the structural integrity of the framing members of the house that were affected by the flood. Observations were made at both the interior and exterior of the structure. The scope of the inspection was limited to only those items that were readily visible and accessible at the time of the inspection. Any items causing visual obstruction, including, but not limited to, furniture, furnishings, floor or wall coverings, foliage, soil, appliances, insulation, etc., were not moved. The basis of our opinions will be the apparent performance of that portion of the property actually visible at the time of the inspection. Disassembly or removal of any portion of the structure is beyond the scope of this inspection. There is no warranty or guarantee, either expressed or implied, regarding the habitability, future performance, life, merchantability, workmanship, and/or need for repair of any item inspected. We make no representation regarding the condition of this property other than as contained in this written report. Any verbal discussions concerning this property that were made at the time of the inspection, and not contained in this written report, are not to be relied upon.
2 Excluded from the scope of the inspection are any and all items related to mold and/or all microbial substances. Due to the current limitations of coverage on most homes by the insurance industry in Texas, where damages due to mold and/or other microbial substances may not be covered, we recommend that you have a mold inspection by a qualified professional if mold is a concern. Observations 1. It was observed that the flood water has entered the house, and the water level was approximately three feet above the first floor. The floor coverings were removed along with the sheetrock on the interior walls on the first floor. The exterior wall sheathing in the flood affected area has been partially removed from the exterior wall.
3
4 2. We checked the moisture levels of the exposed framing members and structural sheathing on the walls and found
5
6
7
8 3. We observed evidence that the wood floors have swelled in the flood water and expanded, and have moved the exterior wall off the foundation at seven locations around the house. The damaged walls need to be restored to their original position on the foundation and to do so will require removal of most, if not all, of the brick veneer around the house to expose the damaged framing members, and to move them back into place. In addition, the damaged and missing exterior gypboard sheathing needs to be replaced. Further investigation with a contractor is recommended concerning these extensive repairs and to obtain a cost estimate for the repairs. Obtain Cost Estimate a. Front wall of Living Room The front wall of the living room has been pushed outwards approximately 1-3/4 inch by the wood floors in the house, causing extensive damage to the brick veneer. The original chalk line from when the house was built was visible on the concrete foundation.
9
10
11 b. Front wall of Dining Room The front bay window area of the dining room has been pushed outwards approximately 1-1/4 inches by the flood waters, causing extensive damage to the brick veneer and window assembly. It is our opinion that the entire bay window area needs to be rebuilt.
12 c. Exterior wall of Front Bedroom d. Exterior wall of Master Bedroom
13 e. Other Exterior wall of Master Bedroom at Closet The exterior wall at the master bedroom closet area has been pushed outwards approximately ¾ inch, causing the bottom plate to crack. The movement of the wall was reflected in the siding shown below being pushed out.
14 f. Rear wall of Family Room
15 g. Rear wall of Breakfast Room
16 Structural Integrity Conclusions Based upon the above observations, it is our opinion that the structural integrity of the first floor wall framing members has compromised by the flood waters, with the exterior load bearing walls being moved out of their original position. Extensive repairs will be needed to move the walls back to their original position, along with replacing the damaged gypboard sheathing behind the brick veneer. Further investigation with your insurance adjuster and/or a contractor is recommended to obtain a cost estimate to make all the needed repairs. CLOSE Thank you for asking HEDDERMAN ENGINEERING, INC. to perform this important inspection work for you. If you have any questions after reviewing this report, please feel free to call me at my office. At your service, Tim Hedderman Registered Professional Engineer #51501 Texas Firm Number: 7942
PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX HOUSTON, TEXAS (713)
PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX 271492 HOUSTON, TEXAS 77277 http://www.profengineering.com (713) 664-1264 June 19, 2000 Mr. Samuel Underdog 329 Castle Dr. Houston TX 77018 Dear Mr.
More informationGeneral Summary. inspectorroy.com Lake Austin Blvd #10104 Austin, TX Customer Jason Woosley
General Summary 2600 Lake Austin Blvd #10104 Austin, TX 78703 Customer Jason Address 3431 Guadalajara Street Round Rock TX 78665 The following items or discoveries indicate that these systems or components
More informationInfrared Inspection Report
Infrared Inspection Report 1234 Sample St, Anywhere Inspection Date/Time: 3/12/2007-11:00 AM Prepared For: Dave Smith Prepared By: Norton Inspection Co. 6632 Telegraph Rd, #346 Bloomfield Hills, MI 48301
More informationHedderman Stucco. A Division of Hedderman Engineering Inc. Phone:
Hedderman Stucco A Division of Hedderman Engineering Inc. www.heddermanengineering.com Email:office@heddermanengineering.com Phone: 281-355-9944 Prepared For: CLIENT NAME Address: PROPERTY ADDRESS Produced
More informationLighthouse Engineering, L.L.C.
Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: Office@LighthouseEng.com Thursday, September 04, 2014 TO: Our Client RE: Initial Engineering
More informationExcellence in Experts, Efficiency and Service
Excellence in Experts, Efficiency and Service February 12, 2009 Insurance Company P.O. Box 1209 Horse Canyon, California 92808 RE: Insured: Mr. and Mrs. Insured 1669 Wild Horse Ranch Tobiano Paint, California
More informationInspection Report Summary
Inspection Report Summary Prepared for: Property Location: XXXXXXXXXXXXXXXX XXXXXXXXXXXXX Dallas, Texas 75XXX Contact Info: Home Phone: XXXXXXXXXXXX E-mail: XXXXXXXXXXXXXXXX Date of Inspection: October
More informationOwner Builder Inspection Report
www.sherspec.com Owner Builder Inspection Report PREPARED FOR USE IN ASSESSING A PROPOSAL FOR WARRANTY INSURANCE TO BE ISSUED UNDER SECTION 137B (2)(a) OF THE BUILDING ACT 1993 INSPECTION DETAILS Registered
More informationInfrared Inspection Report
Infrared Inspection Report 716 Glen Oaks Dr., Franklin, TN. David A. Andersen & Associates Building Science Thermographer #33784 TN HI Lic#40 4772 Chester Harris Rd Woodlawn Tennessee 37191 (615)406-6808
More informationSparks Engineering, Inc. S T R U C T U R A L E V A L U A T I O N, D E S I G N A N D T E S T I N G
Sparks Engineering, Inc. S T R U C T U R A L E V A L U A T I O N, D E S I G N A N D T E S T I N G February 29, 2008 Ms. Leslie Wolfenden Save Austin's Cemeteries PO Box 41814 Austin, TX 78704 (512) 917-1666
More informationKORA_Req._for_Eng._Studies_on_Stouffer_Apts. KU Reference No
000130 1 PURPOSE: Professional Engineering Consultants, P.A. (PEC) was engaged by University of Kansas Design & Construction Management to perform an assessment of Stouffer Place Apartment Building 20
More informationThermal Evaluation Report
1234 Madison Rd. Anywhere, US, 12345 Prepared for: John Smith Prepared by: Your Company Name Here 1234 Any Street Anywhere, US 12345 Visual report of findings. Energy losses and moisture infiltration.
More informationThermal Imaging Report
Thermal Imaging Report 123 Renovation Street Manalapan, NJ 07726 Prepared for: Mr. and Mrs. Homeowner Prepared by: A Full House Inspection Co. LLC 530 Prospect Avenue Little Silver, NJ 07739 Prepared by
More informationMain Floor Plan Scale: 1/8"=1'-0"
16'-0" 1 6'-6" 1 36'-0" Future Deck 10'-6" 4'-11" 4'-11" 10'-6" 36'-0" Future Deck 1 6'-6" 1 16'-0" 6068 3030 3030 6068 1 20'-9 1/2" 20'-9 1/2" 1 D/W D/W 26'-4" 24'-8" 2'-0" '-4" '-4" '- 1/2" 20'-10 1/2"
More informationSummary. Inspect It Like A Girl. P.O. Box 2283 Madison, MS Customer Happy Home. Address 123 Happy Home Road Jackson MS 39157
Summary P.O. Box 2283 Madison, MS 39110 Customer Happy Address 123 Happy Road Jackson MS 39157 The following items or discoveries indicate that these systems or components do not function as intended or
More informationInspection Report. Prepared for: Gil Turiel. Property Address: 545 Briar Run Court Loganville, GA Date: July 17, 2011
Inspection Report Prepared for: Gil Turiel Property Address: Loganville, GA 30052 Date: July 17, 2011 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT
More informationHOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS This guide is intended to provide the homeowner or contractor with the
More informationChris Nowling Inspection Services 6608 Wolfcreek Pass Austin, TX (512)
Chris Nowling Inspection Services 6608 Wolfcreek Pass Austin, T 78749 (512) 288-0288 PROPERTY INSPECTION REPORT Prepared For: Craig Hawes (Name of Client) Concerning: 1005 FM 2571 Smithville, T 78957 (Address
More informationDavid A. Andersen & Associates
Cover Page David A. Andersen & Associates Infrared Thermal Inspection Report 7044 Bridgeport Dr., Nashville TN, 37221 Inspection prepared for: Christopher Hahn & Angela Hahn Inspection Date: 2/28/2009
More informationCopyrighted Home Plan 2011 Natural Element Homes, LLC
29'-0" SQUARE FOOTAGE 6'-0" PORCH 3'-0" 6'-0" 2'-0" 3'-6" 8'-0" 2'-4" 3'-8" 6'-7" 3'-11" BCD3756-2 BCA2420T 3-0 9LITE BATH WOOD STOVE 10'-0" 2-4 15'-10 1/2" 3'-11" 6'-0" 11'-9 1/2" 15 R. @ 7 5/8" 14 T.
More information160.F1 PROPERTY INSPECTION REPORT 6 Vitoria St, Sebastopol, 3356 INSPECTION DETAILS Registered Practitioners Signature:
www.sherspec.com 6 Vitoria St, Sebastopol, 3356 160.F1 PROPERTY INSPECTION REPORT INSPECTION DETAILS Registered Practitioners Name: Rudolf Venema Registered Practitioners Signature: Practitioners Registration
More informationEXTERIOR SIDING CONDITION SURVEY
EXTERIOR SIDING CONDITION SURVEY FOR FARRWOOD 2 CONDOMINIUMS 49-176 FARRWOOD DRIVE HAVERHILL, MA APRIL 2016 c/o PROPERTY MANAGEMENT OF ANDOVER, INC. P.O. BOX 488 ANDOVER, MA 01810 213 WEST STREET, MILFORD,
More informationMy Home Was Built In What Can I Expect To See On My Report?
My Home Was Built In 1956. What Can I Expect To See On My Report? Common Issues in 40 70 Year Old Homes Evidence of foundation settlement Older roof, limited service life remaining Older electrical system
More informationDATE: 4/1/2014 SCALE: 3/16"=1'- 0" SHEET:
Terrace Level First Floor Second Floor Total Back Porch Front Porch Finished NA 1397 SF 743 SF 2140 SF 63 SF 195 SF Unfinished NOTES: All dimensions are framing dimensions, NOT finished dimensions Exterior
More informationHomeTeam Inspection Service 6550 Concord Beaumont, Texas (fax) Defective Drywall Inspection Report
HomeTeam Inspection Service 6550 Concord Beaumont, Texas 77708 409-838-5440 409-838-5464 (fax) Defective Drywall Inspection Report Client: XXXXXXXXXX Property Address: XXXXXXXXXXXXXXX Inspection Date:
More informationRSH ENGINEERING, INC. END OF BUILDERS WARRANTY INSPECTION REPORT INSP#: K00001 DATE: 00/00/11 PAGE #: 1
PAGE : 1 1 2 3 4 LEFT SIDE OF HOUSE: SEE. 3 TO. 10 FOR DETAILS. LEF T SIDE OF HOUSE: GENERAL NOTE: SOFFIT VENTS ARE MISSING AND/OR IS INADEQUATE ADD SOFFIT VENTS. PROVIDE ADEQUATE OF SOFFIT VENTS TO MEET
More informationHoly Trinity Construction Project Sanctuary Repairs Transepts Social Hall General Assembly Presentation May 29, 2016
Holy Trinity -- 2016 Construction Project Sanctuary Repairs Transepts Social Hall General Assembly Presentation May 29, 2016 The 2016 Construction Project contractual start date was on April 4, 2016. The
More informationStructural Condition Assessment
108 6 th Street, Garland, Texas Engineering Report Date: September 29, 2016 RLG No. : 16729 Prepared for: Mr. Jeff D. Bulls III AIA 3030 LBJ Freeway, Suite 1220 Dallas, TX 75234 PM: Harold F. Phillips
More informationAlabama Home Inspections
Cover Page Property Inspection Report 1000 Sample Dr., Sampletown USA Inspection prepared for: Report Sample Inspection Date: 1/21/2010 Time: 400pm Size: Approx. 2,200sf Weather: Cloudy 62 Inspector: Bobby
More informationStorm Damage Assessment Report For: 1234 Example Street., Houston, TX 77002
Storm Damage Assessment Report For: 1234 Example Street., Houston, TX 77002 Prepared For: Miriam Saliba nspection Date: 9/6/2017 Prepared By: Adam Wells TREC License # 21140 105 E Spreading Oaks Ave, Friendswood,
More informationInterNACHI. Advanced Inspection of Crawlspaces for home inspectors
CRAWLSPACE INACCESSIBLE Crawlspace conditions which in the Inspector s opinion posed a personal safety hazard limited examination of the crawlspace to only those home systems and their components visible
More informationPROPERTY OVERVIEW PROPERTY HIGHLIGHTS. 2,340 SF Convenience Store. 3,508 SF Three Unit Strip Center. U-Haul Business. Sunoco Branded Gas Station
RETAIL FOR SALE 5990 Asheville Highway, Hendersonville, NC 28791 OFFERING SUMMARY SALE PRICE: $1,350,000 LOT SIZE: 0.75 Acres YEAR BUILT: 1980 BUILDING SIZE: 5,848 SF RENOVATED: 2018 C-2 Commercial ZONING:
More informationLimited Leak Assessment
Website:www.moistureconsultantsinc.com E-Mail:support@moistureconsultantsinc.com December 2th, 2005 Limited Leak Assessment Property Address US Naval Facility Building 484 Panama City Beach, Florida Report
More informationSAMPLE REPORT Location:
Stucco Check Inspections, LLC Invasive Stucco Inspection Prepared for: SAMPLE REPORT Location: Sample Houston, TX PHONE: 713.319.5751 EMAIL: Info@stuccocheck.com I. INTRODUCTION 1.1 PURPOSE: Enclosed is
More informationInfrared Energy Report
Infrared Energy Report John Jones 5 Anytown Rd. Anytown, NJ 08892 Prepared by: www.njamerispec.com Richard Roshak 3 Derbyshire Lane Somerset, NJ 08873 njamerispec@verizon.net 732-356-6840 Sunday, September
More informationBrick Walls MTI. Rainscreen Retrofit for. Flood Recovery Hurricane Recovery Restoration Flood Resilient Retrofit. Guide to Wet Flood-Proofing
Rainscreen Retrofit for Brick Walls Flood Recovery Hurricane Recovery Restoration Flood Resilient Retrofit Revised 1/14/19 Guide to Wet Flood-Proofing MTI MASONRY TECHNOLOGY INCORPORATED Note: The retrofit
More informationProperty Inspection Report
DAVID A. MEACHAM Professional Inspection & Construction Services Property Inspection Report Prepared for David Smith Property Address 1154 Gulf View Drive Tampa Bay, Florida Inspection Date Friday, October
More informationInspection Report. Prepared for: Tonia Mann. Property Address: 2557 Briar Valley Way Dacula, GA Date: March 01, 2012
Inspection Report Prepared for: Tonia Mann Property Address: Dacula, GA 30019 Date: March 01, 2012 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT
More informationCity of Washburn Building Assessment
City of Washburn Building Assessment Structural Assessment Report 204 W. Bayfield St. September 30, 2016 KOA No. 162078.01 Prepared For: City of Washburn 119 Washington Ave. Washburn, WI 54891 Prepared
More informationKEVIN BURNS BUILDING INSPECTIONS REGISTERED BUILDER PRE-PURCHASE VISUAL STRUCTURAL INSPECTION REPORT No. 822
KEVIN BURNS BUILDING INSPECTIONS REGISTERED BUILDER 6163 PRE-PURCHASE VISUAL STRUCTURAL INSPECTION REPORT No. 822 CLIENT: Talavera PROPERTY ADDRESS: Mindarie DATE: 20 April 2017 TIME: 9.00am WEATHER: Fine
More informationMadison's Home Inspections
Cover Page Madison's Home Inspections Property Inspection Report my street, Clarksville TN, 37043 Inspection prepared for: Gary Mann Agent: gary mann - Madison's Inspection Date: 0/4/2009 Time: 12 pm Age:
More informationTown of Enfield. Parks & Recreation P.O. Box 699 Enfield NC (252) telephone (252) fax
Town of Enfield Parks & Recreation P.O. Box 699 Enfield NC 27823 (252) 445-3146-telephone (252) 445-1019-fax www.enfieldnc.org Request for Proposals for the Renovation and/or Construction of the Recreation
More informationNew Homes Forestbrook Road. Yes, it s INCLUDED!
Sugar Mill is a Covenant Restricted Community. New Homes Forestbrook Road Yes, it s INCLUDED! Granite Countertops Ceramic Tile Kitchen Floors Front Brick Accents Upgraded Kitchen Cabinets Ceramic Tile
More informationSTRUCTURAL INSPECTION EDUCATION BUILDING AND PLAYGROUND Memorial Drive Houston, Texas 77079
STRUCTURAL INSPECTION EDUCATION BUILDING AND PLAYGROUND 15015 Memorial Drive Houston, Texas 77079 Prepared for: Emanuel Episcopal Church c/o Ms. Alice Busch Prepared by: Criterium Farrell Yancy Engineers
More informationEidem Farm Brooklyn Park, MN
Eidem Farm Brooklyn Park, MN East Farm House Structural Condition Assessment Prepared By 1 0 0 P O R T L A N D A V E N U E S O U T H, S U I T E 1 0 0 M I N N E A P O L I S, M I N N E S O T A 5 5 4 0 1
More informationRESIDENTIAL BASEMENT ALTERATIONS GUIDE
RESIDENTIAL BASEMENT ALTERATIONS GUIDE THIS IS A GUIDE ONLY! FOR DETAILED INFORMATION, CONTACT THE BUILDING INSPECTOR OR TOWNSHIP AS ADDITIONAL REQUIREMENTS MAY PERTAIN TO YOUR PROJECT. November 2018 WHITEHALL
More informationDECK GUIDE PERMIT FEES
DECK GUIDE PERMIT FEES Deck (over 48 above grade): $ 130.00 * Deck (any portion under 48 above grade): $ 190.00 * (Pursuant to Contracted Agent fee schedule) * Plus PA Act 13 Surcharge: $ 4.50 Note: Fees
More informationWhite Rock Creek Trail
White Rock Creek Trail 7333 Valley View Lane, Dallas TX 75240 Price range: $275s-450s The perfect blend of Modern and Traditional Architecture for a Timeless appeal Choose between 2 or 3 bedrooms, and
More informationTermite Protection: Building Code Provisions & Recommended Improvements
Termite Protection: Building Code Provisions & Recommended Improvements Educational Overview Revised 6/13/2017 Introduction Termites cause serious damage in the United States around $2.5 billion yearly,
More informationDRAFT REPORT STRUCTURAL EVALUATION SINGLE FAMILY RESIDENCE 1 SILVERTHORNE LANE BELLE MEAD, NEW JERSEY PREPARED FOR: MS.
DRAFT REPORT STRUCTURAL EVALUATION SINGLE FAMILY RESIDENCE 1 SILVERTHORNE LANE BELLE MEAD, NEW JERSEY PREPARED FOR: MS. ELLEN NEVINS PREPARED BY: JOHN T. DALESSIO, P.E., P.P. LIC. NO. 19628 51 MT. BETHEL
More informationStucco Moisture Inspection Report
Website:www.ibgoodinspector.com E-Mail:support@ibgoodinspector.com January 11, 2006 Stucco Moisture Inspection Report Property Address 123 Our Street OurTown, USA 12345 Report Ordered By: Mr. & Mrs. Client
More information2019 IAQA Annual Meeting
Daniel Stih, CMC. CIEC Healthy Living Spaces Stanley Yeskolski CIEC, CMC Investigative Inspection Services Inc. 2 Purpose The presentation will provide a over view of: Installation Details Problem Areas
More informationNational Property Inspections
Monday, August 22, 2011 Inspector Joe Smith 548-254-3658 Page 1 of 33 GENERAL INFORMATION GENERAL CONDITIONS AT TIME OF INSPECTION : No Property Occupied : Property Faces : North South East þ West Year(s)
More informationOne and Two Family Additions
One and Two Family Additions An addition to a house, duplex, garage, or an accessory structure requires a building permit prior to performing any construction. Building Department & Permit Office Mon-Fri
More informationMoonlight Architecture, Inc. Architecture Interior Design Site Planning
Moonlight Architecture, Inc. Architecture Interior Design Site Planning 22 May 2018 18057 Mr. Michael J. Petit de Mange, County Administrator Kent County Levy Court 555 Bay Road Dover, DE 19901 RE: Facilities
More informationQuality Inspection 8618 London Heights San Antonio, TX Phone: (210)
Quality Inspection 8618 London Heights San Antonio, TX 78254 Phone: (210) 240-0476 PRE DRYWALL INSPECTION REPORT Prepared For: DELETED (Name of Client) Concerning: DELETED, San Antonio, TX 78258 (Address
More informationThe Inspection Process. Waxhaw N.C.
The Inspection Process In Waxhaw N.C. This information is provided by the Waxhaw Enforcement Division to assist you in the progression of your project. Nothing in this document should be considered "Code"
More informationAlder Circle Alder Circle Price range: $795K - $1M. For More Information. Bill Conrad Sales Consultant
Alder Circle 5409 Alder Circle Price range: $795K - $1M Bellaire High School Centrally located- just minutes from the Galleria and Medical Center A total of 15 Classical Designed homes with all the new
More informationREPAIR OF WOOD FRAMED STRUCTURES WITH BRICK MASONRY VENEERS. Prepared for FEMA
REPAIR OF WOOD FRAMED STRUCTURES WITH BRICK MASONRY VENEERS Prepared for FEMA 09 When the flooding of buildings consisting of wood frame construction and brick veneer occurs, complete demolition is not
More informationROME ART AND COMMUNITY CENTER
ROME ART AND COMMUNITY CENTER 308 W. Bloomfield St. Rome, NY 13440 INSULATION AND SLATE ROOFING REPAIRS SCOPE OF WORK: A. SPRAY FOAM INSULATE ATTIC AREA B. FRONT ROOF REPAIR C. REAR ROOF REPAIRS D. INTERIOR
More informationBRENTWOOD CALL JESSI KELLY TODAY FOR MORE INFORMATION! BEAUTIFUL, UNIQUE BRAND NEW HOMES IN CHINA SPRING ISD
BRENTWOOD BEAUTIFUL, UNIQUE BRAND NEW HOMES IN CHINA SPRING ISD The greatest in family and recreational amenities to hit the north side of Waco is Brentwood! Homes available now in this kidapproved neighborhood!
More informationProperty Inspection Report
Property Inspection Report Cover Page 12345 Inspection prepared for: Happy Homebuyer Date of Inspection: 11/1/2012 Time: 9:00 Age of Home: 1961 Size: 1830 sqft Weather: 65º - No Rain in the Last Week Inspector:
More informationEXECUTIVE SUMMARY INTRODUCTION Terms of Reference Building Description Documents Reviewed SUMMARY OF FIELD DATA 4
Abbott Place Wood Framed Window Condition Assessment May 30, 2012 TABLE OF CONTENTS EXECUTIVE SUMMARY 1 1.0 INTRODUCTION 2 1.1 Terms of Reference 2 1.2 Building Description 3 1.3 Documents Reviewed 3 2.0
More informationBUILDING REPORT. 123 Anywhere Street Suburb City. Prepared for: Client NON INVASIVE
0 NON INVASIVE BUILDING REPORT 123 Anywhere Street Suburb City Prepared for: Client 1 Following your instructions we visited the above property on the 11/06/12 to carry out a non-invasive building inspection
More informationThe Inspector. Property Inspection Report
Cover Page The Inspector Property Inspection Report Inspection prepared for: ******** ******* Date of Inspection: 11/18/2013 Time: 12PM Age of Home: unknown Size: 2000sf Weather: overcast / 40 Inspector:
More informationSUMMARY 1234 Main St.Fall Branch Tennessee Buyer Name 02/23/2018 9:00AM
SUMMARY 1234 Main St.Fall Branch Tennessee 37656 Buyer Name 02/23/2018 9:00AM KC Bartley Certified Master Inspector - TN Lic. #1244 Professional Home Inspections (423) 306-0508 kc@prohitn.com These summary
More informationKEVIN BURNS HOMES PRACTICAL COMPLETION REPORT VISUAL BUILDING INSPECTION REPORT
KEVIN BURNS HOMES PRACTICAL COMPLETION REPORT VISUAL BUILDING INSPECTION REPORT No. 764 CLIENT: PROPERTY ADDRESS: Jindalee DATE: 25 November 2016 WEATHER: Fine ARRIVAL TIME: 8.15am DEPARTURE TIME: 10.30am
More informationRESPONSIBILITY OF THE BUILDER/OWNER
NOTE: 1 2'-5" 1'-4" 19'-4" 1'-4" 2'-5" 1 1) ALL REPRESENTATIONS OF FIXTURES, EQUIPMENT, MATERIALS, ELECTRICAL, PLUMBING, FASTENERS, ETC. ON CLIENTS DESIGN ARE NOT INCLUDED WITH CLIENT'S PACKAGE PURCHASED
More informationSUMMARY OF AREAS REQUIRING FURTHER EVALUATION
January 24, 2011 RE: ABC Lane Surprise, AZ 85374 Dear Mr. Sample: At your request, a visual inspection of the above referenced property was conducted January 24, 2011. An earnest effort was made on your
More informationJAY E. BUTLER, being first duly sworn deposes and states as follows: 1. I am a Professional Engineer licensed in the State of New York.
SUPREME COURT OF THE STATE OF NEW YORK COUNTY OF NEW YORK In the Matter of DEVELOP DON T DESTROY BROOKLYN; Index No. DANIEL GOLDSTEIN; ATLANTIC AVENUE BETTERMENT ASSOCIATION; RJI No. FORT GREENE ASSOCIATION;
More informationHome Inspection Report Report Number: For The Property Located On:
Home Inspection Report Report Number: 416-129 For The Property Located On: Some Place Dr Prepared For Exclusive Use By: John and Jane Doe Report Prepared By: Adam Duncan; License No.: 3533 Inspector Signature:
More informationBuilding Guide. Colorado Chapter of the International Conference of Building Officials. Building Guide
12/29/16 Building Guide Colorado Chapter of the International Conference of Building Officials Building Guide Colorado Chapter of the International Code Council Single Family Residential Enclosing Existing
More informationWoodshire Village Estates
Woodshire Village Estates 9002 Stella Link, Houston, TX 77025 Price range: $475K to $659K Zoned to Bellaire High School Features ample additional parking for you and your guests Anti-Cookie Cutter exteriors,
More informationFlood Resistant Construction Using Closed-Cell SPF
Flood Resistant Construction Using Closed-Cell SPF The 2017 U.S. hurricane season, the worst in more than a decade, has taken its toll on millions living in the southeastern US. It is not only the destructive
More informationThe Home Doctor, Inc.
February 7, 2013 The Home Doctor, Inc. Property: 26147 HUNTER GATES RD. LESTER, AL 35647 Client: JOHN DOE HOME INSPECTIONS With over 10,000 since 1994 1-800-246-4362 SUMMARY PAGE CLIENT(S): JOHN DOE ADDRESS:
More informationINSPECTOR GROUP PTY LTD
Website: http://www.inspectorgroup.com.au Inspector's email: peter@inspectorgroup.com.au Inspector: Peter Hopfinger Building Surveyor & Timber Pest Inspector Registration Number: 2194 Mob: 0414 607 240
More informationI. Process. Table of Contents. I. Process. II. Additional Information
INSTRUCTIONS KEEP FOR YOUR RECORDS The following must occur prior to beginning any on-site work: 1) A Building Permit must be posted in a visible location onsite Table of Contents I. Process II. Additional
More informationWOOD FLOORING WOOD FLOORING
09550 - WOOD FLOORING 09550-1 PART ONE: GENERAL 1.1 Description WOOD FLOORING 1.1.1 Work in this Section, as shown or specified, shall be provided by the Interior Contractor and shall be in accordance
More informationSUMMARY 1234 Main St.Severn Buyer Name 02/20/2018 9:00AM
SUMMARY 1234 Main St.Severn 21144 Buyer Name 02/20/2018 9:00AM Henry Toman MD License 32391 1st American Home Inspection, LLC 443-685-4062 henrytoman61@gmail.com The summary is meant to organize the defects
More informationInspection Report. Prepared for: Yossi Berg. Property Address: 4925 Diggers Way Sugar Hill, GA. Date: July 20, 2011
Inspection Report Prepared for: Yossi Berg Property Address: Sugar Hill, GA. Date: July 20, 2011 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT &
More informationApplications for building permits will not be reviewed until all of the required information has been submitted.
NOTICE: Applications for building permits will not be reviewed until all of the required information has been submitted. Once all items are submitted a minimum of ten (10) working days are required to
More informationSTRUCTURAL INSPECTION SANCTUARY/ OFFICE BUILDING Memorial Drive Houston, Texas 77079
STRUCTURAL INSPECTION SANCTUARY/ OFFICE BUILDING 15015 Memorial Drive Houston, Texas 77079 Prepared for: Emanuel Episcopal Church c/o Ms. Alice Busch Prepared by: Criterium Farrell Yancy Engineers Texas
More informationA Sample Report On The Conditions At:
HomeInfo, LLC Information You Deserve 3620 McCurdy Street Montgomery, AL 36111-2148 334-303-4284 Office 334-264-7755 Fax A Sample Report On The Conditions At: 123 Main Street Anytown, Alabama 36101-1101
More informationMOLD INSPECTION REPORT Block Home Inspections LLC
Block Home Inspections LLC David Block - 913-220-7762 MOLD INSPECTION REPORT Block Home Inspections LLC David M. Block Certified Mold Inspector #CMI-06-2024 INSPECTION AGREEMENT Mold screening is intended
More information9'-2 1/2" 72" Whirlpool Tub Unit 6'-0" 9'-2" x 11'-6" Bathroom. 66" Vanity. 60" Shower 5'-0" 5'-8" Laundry Room 9'-2" x 5'-7" 5'-7 1/2"
37'-0" 1 '-" 18'-" 18'-" 2030 11'-1" 8'-1" 11'-7" 7'-2 1/2" 0" Tub/Shower '-0" Bedroom #2 11'-0" x 11'-0" 7'-1" x 1'-11" Linen 48" Vanity 28 Bedroom #3 11'-0" x 11'-" 3'-7" 42" Archway 011 3535 Dining
More informationMAJOR DEFECTS BUILDING SURVEY REPORT
MAJOR DEFECTS BUILDING SURVEY REPORT XXXXXX Road Bedminster Bristol BS3 XXX Prepared for Mr XXXXXXX July 2017 T J Maggs MRICS MAGGS AND ALLEN 22 Richmond Hill Clifton Bristol BS8 1BA 0117 973 4049 survey@maggsandallen.co.uk
More informationCartwright Street Waterford at The Willows
13 602 Cartwright Street Waterford at The Willows This 2,579 square foot bungalow is the first Mike Holmes approved home in Saskatchewan. Every stage of this stunning home was inspected and approved by
More informationCastle Court Terrace B Castle Court, Price range: $624,900 - $724,900. For More Information. Richard Fowler Sales Consultant
Castle Court Terrace 1306-B Castle Court, 77006 Price range: $624,900 - $724,900 Gated community of 10 luxury 4 story homes Conveniently located within minutes of the Museum District, Texas Medical Center,
More informationINSPECTION TYPE EIFS system, Visual, Tramex & Delmhorst probe moisture readings
FINEGAN INSPECTION SERVICES, INC. 27 Laurelwood Drive Milford Ohio, 45150 513 683-0733 RESIDENCE LOCATION INSPECTION TYPE EIFS system, Visual, Tramex & Delmhorst probe moisture readings OVERVIEW The report
More informationAlexandria Property Inspections Inc.
Alexandria Property Inspections Inc. 14421 Broadwinged Drive Gainesville, VA 20155 Prepared for: Prepared by: National Property Inspections 15 Canterbury Road Great Neck, NY 11021 08:00 July 19, 2012 Page
More informationRESIDENTIAL HARDWOOD WARRANTIES
RESIDENTIAL HARDWOOD WARRANTIES Limited Warranties for Pre finished Solid, Engineered and Longstrip Floors Manufacturing Defects Lifetime Floors ( Lifetime Floors ) hereby warrants to the original buyer
More informationBASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018)
BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018) PERMIT SUBMITTAL CHECKLIST: Signed and completed Building Permit application form. A separate Electrical permit is required from
More informationREQUEST FOR PROPOSALS March 4, 2010 PROJECT OVERVIEW:
Police Headquarters Project REQUEST FOR PROPOSALS March 4, 2010 PROJECT OVERVIEW: General description The objective is to renovate an approximately 18 x 24 section of the two-bay attached garage at Town
More informationVillage of Glen Ellyn Basement Remodeling Project Guidelines
Village of Glen Ellyn Basement Remodeling Project Guidelines Existing unfinished basement space is often remodeled to create more habitable (living, sleeping, eating, dining) space in a home. Building
More informationHPW Protocol Reference Manual
1 HPW Protocol Reference Manual Change Log: UPDATED BY DATE UPDATED VERSION UPDATE DETAILS 2 Table of Contents: HIGH PERFORMANCE WALL ASSEMBLY... 4 THERMAL SPECIFICATION... 4 REQUIREMENTS FOR HPW INSULATION...
More informationANTIQUE TERMITE, INC Stone Avenue, San Jose, CA Ph: (408) (408) Fax
WOOD DESTROYING PESTS AND ORGANISMS INSPECTION REPORT BUILDING NO. STREET, CITY, STATE, ZIP Date of Inspection No. of Pages 230 FORRESTER ROAD, LOS GATOS CA 95032 8/19/2010 5 ANTIQUE TERMITE, INC. 1913
More informationInsurance Risk Services 104 South Park Ave. Sanford, FL Phone Fax:
Access Home Insurance Company Inspector: Monica Angelette Agent: TRINTON INSURANCE GROUP LLC Completed: 4/20/2017 Insurance Risk Services 104 South Park Ave. Sanford, FL 32771 Phone 800-644-5112 Fax: 800-644-0567
More informationCopyrighted Home Plan 2011 Natural Element Homes, LLC
71'-3" 16'-7 1/2" 38'-7 1/2" 16'-0" NOTE: 52'-6" 6'-0" 6'-0" 29'-6" 3'-0" '-2" 17'-4" GLASS BLOCK 4'-3"x 3'-0" 4'-1 1/4" 4'-4 1/2" 6'-4 1/2" 14'-7 3/4" 6'-3 1/4" VSH2636T BCC2466+BCCP6066+BCC2466 5'-2
More informationGLOBAL PROPERTY INSPECTIONS TECHNICAL BULLETIN
GLOBAL PROPERTY INSPECTIONS TECHNICAL BULLETIN TM June 1, 2002 TOPIC: Exterior Coverings This is the sixth in a series of technical bulletins in which an over-all examination of the home will be discussed
More informationINFORMATIONAL HANDOUT FOR FINISHING A BASEMENT
7100 147 th Street West Telephone (952) 953-2588 Apple Valley, MN 55124-9016 Fax (952) 953-2515 www.cityofapplevalley.org INFORMATIONAL HANDOUT FOR FINISHING A BASEMENT 1. Submit plan showing the proposed
More information