University of Central Florida Main Campus. Domestic Water. Service and Meter Installations Requirements. Issued January 26 th, 2017.
|
|
- Eustace Denis Neal
- 6 years ago
- Views:
Transcription
1 University of Central Florida Main Campus Domestic Water Service and Meter Installations Requirements Issued January 26 th, P a g e
2 Table of Contents 1. GENERAL INFORMATION DEFINITIONS TYPICAL REQUIREMENTS METERING PLAN REVIEW AND COORDINATION WITH UCF UES... 7 DW - FIGURE 00: GENERAL NOTES RELATED TO DOMESTIC WATER DISTRIBUTION & METERING DW - FIGURE 01A: WATER METER MATRIX DW - FIGURE 01B: WATER METER RESPONSIBILITY TABLE DW - FIGURE 02: STANDARD ROADWAY OPEN CUT DETAIL DW - FIGURE 03: LOCATING WIRE TERMINAL DW - FIGURE 04: VALVE & VALVE BOX DETAIL DW - FIGURE 05: DOMESTIC WATER REMOTE PRESSURE SAMPLING POINT DW - FIGURE 06: WATER MAIN WET TAP DW - FIGURE 07: BLOW-OFF/END WITH NO FUTURE EXTENSION POSSIBLE DW - FIGURE 08: 3" AND LARGER DOMESTIC WATER METER DW - FIGURE 09: GAUGE DIAPHRAGM ASSEMBLY 2 P a g e
3 1. GENERAL INFORMATION 1.1. UCF Utilities & Energy Services (UES) is responsible for managing Domestic Water throughout the UCF Main Campus. These UCF Construction Standards are intended to identify any items that must exceed industry and/or Code required minimums Water meters are utilized for utility billing, savings calculations, demand profiling, and performance monitoring. Essential to these functions are an accurate and properly selected and installed system For ease of use, this section of the construction standards provides multiple 8.5 x11 details or Figures. These details are used to convey critical information to the designer, track the designers progress and verify the contractor s installation. These details or Figures are provided in the table below and are intended to be incorporated into the construction documents, by the designer, as applicable, after confirming they meet all current Code and design intent requirements. ALL Projects As Applicable DW - Figure 00, 01A, 01B DW - Figure 02, 03, 04, 05, 06, 07, 08, DEFINITIONS 2.1. Placeholder for future definitions. 3. TYPICAL REQUIREMENTS 3.1. System Size Computation The allowable minimum service pressure must not be less than 20 pounds per square inch Normal Flow Flow demands must be based on the output capacity of the water plant. Design of water systems must account for peak flow rates for the entire campus Fire Flow Fire hydrant flow tests shall be witnessed by UCF UES. The results of the tests shall be provided to UCF UES for record keeping Fire Hydrant Locations Hydrants must be served by a valve stub not less than 6" IPS, and must connect to a main not less than 8" IPS. UCF UES shall be consulted in all cases where the existing main servicing the site is 6" IPS or less Fire Hydrants - Approved Manufacturers Mueller Super Centurian A423 with 5-1/4 barrel Hydrants must be equipped with a minimum of one (1) pumper outlet nozzle 4-1/2 inches in diameter and two (2) hose nozzles 2-1/2 inches in diameter. 3 P a g e
4 Threads, nozzle caps, operating nuts, and cap color must conform to UCF UES Standards. Barrel color must be yellow Prepare and prime all surfaces prior to painting Fire Hydrant body shall be painted using "RUST-OLEUM" Fire Hydrant Enamel Yellow Part # Cap colors shall be selected according to class and corresponding GPM Units must be traffic type with breakable safety coupling located below barrel break line to preclude valve opening Valve must be compression type with 5-1/4 inches minimum valve opening and shoe inlet connection to be 6-inches minimum Hydrants must be secured with restraining assemblies All units must be designed and installed to be self-draining Gravel or crushed stone for the drain sump must be provided Valve Locations Valves must be provided for all branch connections, main ends, fire hydrant stubs, or other locations Distribution loops must have the ability of being isolated Valves are to be placed so that the maximum allowable length of water main required to be shut-down for repair work must be two-hundred (200) feet in high density or five-hundred (500) feet in other areas. High density is defined as any building 20,000 sqft or greater Water main materials must be ductile iron pressure water pipe or PVC pressure pipe. Gate valves, Mueller 2360 or UCF UES approved equal, must be provided at all new branches, fire hydrants, backflow prevention devices, and meters Water lines will be disinfected according to AWWA Standard C-601 and must be witnessed by the UCF UES All pipes must be tested for leakage by filling with water to a pressure 150 lbs. The pipes must withstand this test for 2 hours without any decrease in pressure All pipe leakage testing must be witnessed by UCF UES. The testing contractor shall notify UCF UES at least 48 hours prior to starting the test Any leaks identified by pressure testing shall be repaired by the contractor at no additional cost to UCF Pipes and Pipe Fittings Installation Materials must be cleaned and maintained clean, with all coatings protected from damage. The interior of the pipe must be free of dirt and debris, and when work is not in progress, all open ends must be plugged. 4 P a g e
5 Materials for domestic water systems including taps, repairs, etc., must be disinfected in compliance with American Water Works Association (AWWA) C601 and C Water from these pipes must not be used for any purpose prior to receipt of satisfactory test results Underground pressure piping system located in the traveled way or planned traveled way must be installed with five (5) feet of cover Exposed systems must be supported as necessary to hold the piping and appurtenances in a firm, substantial manner to the required lines and grades indicated, with no undue piping stresses transmitted to equipment or other items Pipe above ground and outside of buildings must be supported on concrete supports Pipes and Pipe Fittings All pipe and fittings must be clearly marked with the name or trademark of the manufacturer, the batch number, the location of the plant, and strength designation, as applicable All piping and fittings for water service must meet current ANSI/ASTM and AWWA standards Main distribution piping, over ten (10 ) inches shall be ductile iron. Service piping may be PVC Piping Not Permitted Galvanized not permitted Piping Permitted (UCF Design Standards 2012 page 77) and below shall use Schedule 80 PVC shall use C900 PVC Greater than 10 shall use Ductile Iron pipe shall NOT be used Polyvinyl Chloride (PVC) Connections for pipe three (3) inches in diameter and larger must be rubber compression ring type with restrained joints per AWWA guidelines Valves All valves must be American manufactured and the valve type, size rating, and flow direction arrow must be clearly marked on each unit All valves shall be fully ported Hand wheel valves are not permitted below grade Underground Service (General) All valves must be of American manufacturer. 5 P a g e
6 Valves must be iron body, epoxy-coated, bronze mounted, solid wedge (sewage) or double-disc (water), non-rising stem type, and must be equipped with two (2) inch square cast iron wrench nuts Above Ground Service (General) Valves must be iron body, bronze mounted gate valves, solid wedge (sewage), with the exception that valves must have an outside screw and yoke (OS&Y), rising stem type Valves must have cast iron hand wheels or chain operators with galvanized steel chains Backflow Preventers The assembly must be the reduced pressure type, with shut-off gate valves provided at each and must comply with the applicable provisions of AWWA Standard C506, "Backflow Prevention Devices--Reduced Pressure Principle and Double Check Valve Types" Backflow preventers must be manufactured by Wilkins Provide type RPZ, model 975 XL for 2" lines or smaller Provide model 375 for 3" lines or larger for building installations For 2" and smaller, the pipe supporting the device must be copper For 3" and larger, the pipe supporting the device must be ductile iron All backflow preventers must be installed with concrete pads and protected by yellow rounded top concrete bollards The lowest point of a backflow assembly must be at least 12 above concrete pad Hose-bibbs are not permitted on backflow preventers Backflow assembly must have a minimum of 3 feet of clearance on all sides. This includes landscaping All backflow preventers must be tested by a certified testing agency. Technician performing the testing must we certified through FSAWWA Results of backflow preventer testing and maintenance reports must be submitted to UCF UES Backflow preventers and their associated connections, piping, and fittings must be provided with a painted finish suitable for the application Domestic Water = Rust-Oleum Safety Blue 4. METERING 4.1. General Requirements All meters will be provided by the UCF UES. Both the meter and installation will be paid from project funds. The meter becomes property of the university after final certificate of occupancy is issued. 6 P a g e
7 5. PLAN REVIEW AND COORDINATION WITH UCF UES Coordination of domestic water service and metering requirements with UCF UES is important for the success of the project At the 50% Construction Document Phase the following shall be shown on plans and reviewed with UCF UES: Design flows, diversity factors and method of computation The design documents must provide the methodology for the diversity factors used Proposed routing of domestic water service from campus main distribution to the building Proposed location of meter Proposed metering configuration Designer shall submit all included Figures identified by UCF UES for the service type. Designer shall identify any aspects of the Figure that cannot or will not be provided All requested Figures shall be submitted to UCF UES, through UCF s project manager At the 100% Construction Document Phase the following shall be shown on plans and reviewed with UCF UES: Design flows, diversity factors and method of computation The design documents must provide the methodology for the diversity factors used Final location of meter Final metering configuration Designer shall submit all included Figures identified by UCF for the service type. Designer shall identify any aspects of the Figure that cannot or will not be provided All requested Figures shall be submitted to UCF UES, through UCF s project manager. 7 P a g e
8
9
10
11
12
13
14
15
16
17
18
University of Central Florida Main Campus. Chilled Water. Service and Meter Installations Requirements. Issued January 26 th, 2017.
University of Central Florida Main Campus Chilled Water Service and Meter Installations Requirements Issued January 26 th, 2017 1 P a g e Table of Contents 1. GENERAL INFORMATION... 3 2. DEFINITIONS...
More informationSECTION CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION
SECTION 22 11 16.13 CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION PART 1: GENERAL 1.01 SUMMARY A. This Section includes water-distribution backflow prevention products and installation specifications.
More information4 1 /2 MARK 73-5 AMERICAN FLOW CONTROL. It s What We Know. AMERICAN-DARLING FIRE HYDRANT AMERICAN-DARLING 4 1 /2 MARK 73-5 FIRE HYDRANT
AMERICAN-DARLING FIRE HYDRANT AMERICAN-DARLING FIRE HYDRANT AMERICAN FLOW CONTROL It s What We Know. CONSTRUCTION AMERICAN-DARLING FIRE HYDRANT OPERATING NUT Cast one-piece bronze operating nut. Design
More informationSERVICE LINES, METERS AND APPURTENANCES
AUGUST02 SECTION 02646 SERVICE LINES, METERS AND APPURTENANCES PART 1 - GENERAL 1.1 DESCRIPTION A. This section concerns materials and installation of corporation stops, curb stops, service lines, meters,
More informationSECTION WATER DISTRIBUTION
SECTION 33 10 00 WATER DISTRIBUTION PART 1 GENERAL 1.01 SUMMARY 1.02 CODES A. Section Includes: 1. Underground water service piping, watermains and appurtenances. A. All work shall comply with the most
More informationSPECIFICATIONS FOR THE INSTALLATION OF REDUCED PRESSURE BACKFLOW PREVENTERS AND CONCRETE VAULTS FOR METERS 4 AND LARGER
SPECIFICATIONS FOR THE INSTALLATION OF REDUCED PRESSURE BACKFLOW PREVENTERS AND CONCRETE VAULTS FOR METERS 4 AND LARGER Updated January 2018 RP-2 Installation Specifications 1. In W.H.U.D s service area
More information2. A preconstruction meeting with the TWA s staff is required prior to initiating construction.
General: 1. Construct utilities in accordance to TWA approved plans and shop drawings. Any deviation from the approved plans shall be approved by the DEVELOPER S ENGINEER and TWA 2. A preconstruction meeting
More informationSECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE)
SECTION 02623 HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE) PART 1 - GENERAL 1.1 SCOPE OF WORK A. Furnish all labor, materials, equipment and incidentals required and install high density
More informationSECTION WATER DISTRIBUTION SYSTEM
PART 1 GENERAL 1.1 SCOPE SECTION 02660 WATER DISTRIBUTION SYSTEM A. The Contractor shall furnish all labor, equipment, and materials and perform all operations necessary to construct a complete, functioning
More informationTECHNICAL SPECIFICATIONS WATER MAINS & MATERIALS
WATER MAINS & MATERIALS Scope of Work Work to be performed under this contract shall consist of furnishing and installing, complete and ready for service, the water mains with various appurtenances as
More informationDUKE UNIVERSITY CONSTRUCTION STANDARDS
1 33 11 00 Water Utility Distribution Piping 1. Introduction A. Duke University owns and operates the water distribution system throughout the campus boundaries; however, water is supplied by the City
More informationSECTION POLYVINYL CHLORIDE (PVC) WATERLINE
SECTION 02632 POLYVINYL CHLORIDE (PVC) WATERLINE PART 1 - GENERAL 1.01 SCOPE OF WORK A. Furnish all labor, materials, equipment, and incidentals required, and install polyvinyl chloride (PVC) waterline,
More informationSECTION 2 MATERIALS 1. GENERAL
SECTION 2 MATERIALS 1. GENERAL All materials to be incorporated in the project shall be first quality, new and undamaged material conforming to all applicable portions of these specifications. 2. CONCRETE
More informationUnderground Piping for Private Hydrants & Sprinkler Supply Line
City of Brea Brea Fire Department Fire Prevention 1 Civic Center Circle Phone: (714) 990-7655 Underground Piping for Private Hydrants & Sprinkler Supply Line PURPOSE The provision of adequate water supplies
More informationEL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD Fire Water Supply without a Purveyor Residential & Commercial STANDARD #D-003 EFFECTIVE 01-04-2016 1. PURPOSE 1.1. The California Fire Code (CFC) requires
More informationAll service lines shall conform to the following requirements:
505 WATER SERVICE INSTALLATION 505.1 DEFINITION A service line is comprised of the piping and related appurtenances including the connection installed from the Des Moines Water Works water main to the
More informationC. ASSE 1013 Performance Requirements for Reduced Pressure Principle Backflow Preventers.
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationNORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS
PART 1 GENERAL 1.01 SUMMARY Section 15140 PIPE HANGERS, This Section includes the furnishing and subsequent installation of: A. Pipe and equipment hangers, supports, and associated anchors B. Equipment
More informationPROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA
The following standard specification is intended to be edited according to the specifics of the project. Brackets [ ] and areas shaded in gray [e.g. format] indicate requirements that are optional depending
More informationPART 5 WATER SYSTEMS
PART 5 WATER SYSTEMS Abbreviations and Symbols Plan 501 Abbreviations and symbols for water... 205 Concrete Boxes and Hardware 502 27" Frame and cover... 207 503 38" Frame and cover... 209 505 Concrete
More informationSECTION STORM UTILITY DRAINAGE PIPING PART 1 - GENERAL 1.1 SUMMARY 1.2 SUBMITTALS 1.3 PROJECT CONDITIONS
SECTION 334100 - STORM UTILITY DRAINAGE PIPING PART 1 - GENERAL 1.1 SUMMARY Section Includes: 1. Pipe and fittings. 2. Drain Basin. 3. De-chlorination tablet feeder. 4. Non-pressure transition couplings.
More informationSECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL
SECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL This section covers the furnishing and installation of ductile iron water pipe, fittings, thrust restraint and pipe disinfection. Ductile Iron Pipe MATERIALS
More informationTown of Fortville Utility Street Standards
SECTION 02660 - WATER MAINS Town of Fortville PART 1 - GENERAL 1.1 DESCRIPTION A. Scope: Furnish and install pipe, fittings, valves, hydrant and appurtenances necessary to complete work shown or specified.
More informationA. Codes and Standards that are Standard at the University: 1. AGA Compliance: LC 1-91 Interior Fuel Gas Piping Systems
PART 1: GENERAL 1.01 Purpose: This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is to
More informationRESIDENTIAL FIRE SERVICE METERS Addendum #1
109 WATER METERS (Addendum #1) 109.1 GENERAL All meters to be used for billing purposes shall be provided by the Water Utility. The Water Utility reserves the right to read, inspect, test or replace the
More informationD-1 FIRE PROTECTION PRODUCTS TAPPING VALVE. MUELLER Tapping Valves. MUELLER Tapping Sleeves and Crosses. MUELLER Stainless Steel Tapping Sleeves
TAPPING VALVE MUELLER Tapping Sleeves and Crosses Full range of Tapping Sleeves and Crosses to fit most types of pipe including cast iron, ductile iron, A-C, and cast iron O.D. PVC--Also outlet sealed
More informationCity of Flowery Branch Standard and Specifications Chapter WM
Section One Water Mains and Accessories City of Flowery Branch Chapter WM Part 1- General 1.01 Scope A. The Contractor shall furnish all equipment, labor and materials (unless otherwise agreed upon in
More informationDESIGN CRITERIA AND SPECIFICATIONS FOR WATER MAINS AND APPURTENANCES BOARD OF PUBLIC UTILITIES CITY OF TULLAHOMA, TENNESSEE
DESIGN CRITERIA AND SPECIFICATIONS FOR WATER MAINS AND APPURTENANCES BOARD OF PUBLIC UTILITIES CITY OF TULLAHOMA, TENNESSEE SPECIFICATIONS NO. TUB-W-287 REV. VIII JANUARY 2010 FORWARD It is intended that
More informationMASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING
SECTION 221316 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following soil and waste, sanitary drainage and vent piping inside the building: 1. Pipe, tube,
More informationCW 3530 MANUAL IRRIGATION SYSTEM TABLE OF CONTENTS
October 1990 CW 3530 MANUAL IRRIGATION SYSTEM TABLE OF CONTENTS 1. GENERAL CONDITIONS...1 3. DESCRIPTION...1 5. MATERIALS...1 5.1 General...1 5.2 Testing and Approval...1 5.3 Irrigation Pipe and Fittings...1
More informationARTICLE 29 SANITARY SEWER FORCE MAINS
SANITARY SEWER FORCE MAINS Index 29.01 GENERAL 29.02 DESIGN CRITERIA 29.03 MATERIALS 29.04 VALVES 29.05 INSTALLATION 29.06 IDENTIFICATION 29.07 HYDROSTATIC TESTING BACK TO TABLE OF CONTENTS Section 29.01
More informationLATHAM WATER DISTRICT
LATHAM WATER DISTRICT TOWN OF COLONIE STANDARD SPECIFICATIONS FOR WATER DISTRIBUTION SYSTEMS ADOPTED JUNE 24, 1993 REVISED FEBRUARY 29, 1996 LATHAM WATER DISTRICT 347 OLD NISKAYUNA ROAD LATHAM, NEW YORK
More informationUL / FM D-1 FIRE PROTECTION PRODUCTS TAPPING VALVE. MUELLER Tapping Sleeves and Crosses. MUELLER Tapping Valves
UL / FM TAPPING VALVE SECTION Rev. 2-15 MUELLER Tapping Sleeves and Crosses Full range of Tapping Sleeves and Crosses to fit most types of pipe including cast iron, ductile iron, A-C, and cast iron O.D.
More informationAMERICAN FLOW CONTROL 2"-12" SERIES 2500 RESILIENT WEDGE GATE VALVE
AMERICAN FLOW CONTROL 2"-12" SERIES 2500 RESILIENT WEDGE GATE VALVE CONSTRUCTION DUCTILE IRON OPERATING NUT Provides strength and durability. UPPER O-RING SEALS Helps isolate the lubrication chamber as
More informationCONDUITS AND FITTINGS
CONDUIT AND FITTINGS Rigid Steel Conduit 3801 Rigid PVC Conduit 3803 HDPE Conduit 3803 Flexible Non Metallic Liquid Tight Conduit Type LFNC-B 3804 PVC Coated Urethane Lined Galvanized Rigid Steel Conduit
More informationSECTION WATER SYSTEMS
SECTION 02660 WATER SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. A complete underground domestic/fire water supply system, with all necessary accessories indicated on drawings or specified
More informationPART VII - WATER SYSTEM DESIGN CRITERIA
PART VII - WATER SYSTEM DESIGN CRITERIA A. Water Distribution, General 1. The water system layout shall be approved by the City Engineer. The fire hydrant layout shall be approved by the Redwood City Fire
More informationSECTION LAYING AND JOINTING BURIED PIPELINES
SECTION 02650 LINES PART 1 GENERAL 1.1 SUMMARY A. Section Includes: Installation of all underground pipelines. Provide pipeline materials, coatings and linings as specified and pipe of the types, sizes
More informationCULINARY WATER SYSTEMS
CULINARY WATER SYSTEMS I. Water system size determination A. The minimum water line size is 8 inch for distribution lines in a residential subdivision. 1. Subdivisions that have a school or church will
More informationSPECIFICATIONS - DETAILED PROVISIONS Section Stainless Steel Sluice Gates C O N T E N T S
SPECIFICATIONS - DETAILED PROVISIONS Section 11294 - Stainless Steel Sluice Gates C O N T E N T S PART 1 - GENERAL... 1 1.01 SUMMARY... 1 1.02 REFERENCES... 1 1.03 DEFINITIONS... 1 1.04 DESIGN REQUIREMENTS...
More informationPASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017
SECTION 02630 - STORM DRAINAGE PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSECTION ALUMINUM GATES
P.O. Box 1058 370 South Athol Rd. Athol, Massachusetts 01331 Phone: (978) 249-7924 Fax: (978) 249-3072 SECTION ALUMINUM GATES PART 1 GENERAL 1.01 SCOPE OF WORK A. The CONTRACTOR shall furnish all labor,
More informationSPECIAL SPECIFICATION 3504 Septic Tank System
1993 Specifications CSJ s 3136-01-126, etc. & 0683-01-070, etc. SPECIAL SPECIFICATION 3504 Septic Tank System 1. Description. This Item shall govern for all materials, equipment and labor necessary for
More information1. B16.1 Cast Iron Pipe Flanges and Flanged Fittings, Class C 111 Rubber Gasket Joints for Ductile Iron Pressure Pipe and Fittings
SECTION 33 34 00 SANITARY FORCE MAIN PART 1 GENERAL 1.1 SCOPE OF WORK A. This section specifies the requirements for furnishing and installing sanitary force main and appurtenances. The pipe shall be of
More information12.1 MUELLER TAPPING MATERIALS AND SPECIALTY VALVES. MUELLER Tapping Sleeves and Crosses. MUELLER Tapping Valves. MUELLER Stainless Steel Tapping
MUELLER TAPPING MATERIALS AND SPECIALTY VALVES 12.1 Shaded area indicates change Rev. 7-16 MUELLER Tapping Sleeves and Crosses Full range of Tapping Sleeves and Crosses to fit most types of pipe including
More informationSECTION PIPE & PIPE FITTINGS PART 1 GENERAL
SECTION 02610 PIPE & PIPE FITTINGS PART 1 GENERAL 1.01 DESCRIPTION A. This Section includes the material and bedding requirements for all pipe and pipe fittings for underground pressure and non-pressure
More informationSECTION 3900 WATER MAINS CITY OF BLUE SPRINGS, MISSOURI CONSTRUCTION SPECIFICATIONS
SECTION 3900 WATER MAINS CITY OF BLUE SPRINGS, MISSOURI CONSTRUCTION SPECIFICATIONS 3901 MATERIALS... 2 A. General... 2 B. Pipe and Fittings for Water Mains... 2 C. Ductile Iron Pipe and Fittings... 3
More informationSECTION TAPPING SLEEVES AND VALVES
SECTION 33 12 16.17 TAPPING SLEEVES AND VALVES PART 1: GENERAL 1.01 SCOPE Furnish, install and test all tapping sleeves, tapping valves, and tapping saddles as shown on the Drawings. 1.02 RELATED WORK
More informationCHAPTER 11 CONDUITS AND FITTINGS
CONDUITS AND FITTINGS CHAPTER 11 CONDUITS AND FITTINGS The standards and requirements for conduits and fittings used for traffic control signal and lighting systems are presented in this chapter. 11.1
More informationSPECIFICATIONS - DETAILED PROVISIONS Section Horizontal Centrifugal Water Pumps C O N T E N T S
SPECIFICATIONS - DETAILED PROVISIONS Section 11931 - Horizontal Centrifugal Water Pumps C O N T E N T S PART 1 - GENERAL... 1 1.01 PUMP - GENERAL... 1 1.02 CERTIFIED PUMP CURVES... 1 1.03 NPSH REQUIREMENTS...
More informationSECTION FACILITY SANITARY SEWERS
SECTION 22 13 13 FACILITY SANITARY SEWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationAmerican Flow control 2-12 Series 2500
American Flow control 2-12 Series 2500 Resilient wedge gate valve FLOW CONTROL Construction Ductile iron operating nut Provides strength and durability. Upper O-ring seals Can be replaced while the valve
More informationSECTION PLUMBING FIXTURES
SECTION 15440 - PLUMBING FIXTURES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, are a part of this Section. 1.02 SUMMARY A.
More informationSECTION SLUICE GATES
SECTION 11100 SLUICE GATES PART 1--GENERAL Fill in the blank with a short description of sluice gate usage, i.e., for isolation of wastewater, or for tank drainage, or for control of water surface. 1.01
More informationSection 2: Underground
Section 2: Underground GENERAL INSTALLATION REQUIREMENTS FOR UNDERGROUND FACILITIES Underground electric service and meter location will be established by NHEC upon site visit. In some instances the type,
More informationIvins City Standard Specifications for Design and Construction Part 2 Engineering and Design Standards
2.9. WATER SYSTEM DESIGN Ivins City Standard Specifications for Design and Construction All culinary water mains and appurtenances shall be designed to provide for adequate future service for all contiguous
More informationAmendment to OPSS 493 (Nov 2015) Construction Specification for Temporary Potable Water Supply Services
Engineering & Construction Services Division Standard Specifications for Sewers and Watermains TS 493 September 2017 Amendment to OPSS 493 (Nov 2015) Construction Specification for Temporary Potable Water
More informationWATER DISTRIBUTION AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)
WATER DISTRIBUTION 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation
More informationLINCOLN COUNTY STANDARD SPECIFICATIONS SECTION WATER LINES, VALVES, AND APPURTENANCES
LINCOLN COUNTY STANDARD SPECIFICATIONS SECTION 02665 WATER LINES, VALVES, AND APPURTENANCES 1. DESCRIPTION The CONTRACTOR shall furnish all labor, materials, equipment and supplies and shall perform all
More informationCISTERN & DRY-HYDRANTS
TOWN OF CHARLTON FIRE DEPARTMENT P.O. Box 114 Charlton City, MA 01508 Business Telephone: (508) 248-2299 Fax (508) 248-6190 CISTERN & DRY-HYDRANTS 1 Location and Construction 1.1 Fire protection cisterns
More informationTCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II
SECTION 221313 - FACILITY SANITARY SEWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationThis section includes materials and installation of ductile-iron pipe and fittings for potable and recycled water systems.
NORTH MARIN WATER DISTRICT STANDARD SPECIFICATIONS SECTION 15056 DUCTILE-IRON PIPE AND FITTINGS PART 1 GENERAL 1.01 DESCRIPTION This section includes materials and installation of ductile-iron pipe and
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 22 1316 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationSECTION MEASUREMENT AND PAYMENT
SECTION 01025 - MEASUREMENT AND PAYMENT PART 1 - GENERAL 1.01. BASIS FOR MEASUREMENT AND PAYMENT Measurement and Payment will be made for only those items included in the Schedule of Unit Prices or Contract
More informationEssex County College - West Essex Campus Addition And Renovations Dib # / SECTION DOMESTIC WATER PIPING SPECIALTIES
Essex County College - West Essex Campus Addition And Renovations Dib # 54292 / 11-14 SECTION 221119 - DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions
More informationRural Servicing Guidelines
Rural Servicing Guidelines for Low-Pressure Sanitary Sewer System and Trickle Feed Water Distribution System FOREWORD This manual is intended to provide information to Developers, Engineering and Geotechnical
More informationSECTION PACKAGE BOOSTER PUMP STATIONS
SECTION 331223 PACKAGE BOOSTER PUMP STATIONS Scope: The Contractor shall install a pump station at two locations to be determined by the Owner. These pump stations shall be designed to deliver flow to
More informationStainless Steel Aeration Equipment Specification
Section 15 Stainless Steel Aeration Equipment Specification Part 1 - General 1.01 Description A. Scope of Work 1. Furnish, install and test aeration system including air mains, drop pipes, valves, expansion
More informationSECTION WATER DISTRIBUTION SYSTEM TABLE OF CONTENTS
06010 WATER DISTRIBUTION PIPE A. Design B. Materials C. Installation D. Pipe Identification and Marking SECTION 06000 WATER DISTRIBUTION SYSTEM TABLE OF CONTENTS 06020 FIRE PROTECTION A. Fire Hydrants
More informationCONSTRUCTION SPECIFICATION FOR WATERMAIN INSTALLATION IN OPEN CUT
ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS.PROV 441 APRIL 2017 (Formerly OPSS 441, November 2014 Note: The PROV implemented in April 2017 replaces OPSS 441 COMMON, November 2014 with no technical
More informationCHAPTER 3 - PRESSURE IRRIGATION
CHAPTER 3 - PRESSURE IRRIGATION 3.1 GENERAL This division covers furnishing and installing pressure pipe as shown on the Drawings or established in the field, and all flushing, testing, repairing, as required
More information4A General Information A. Concept... 1 B. Conditions... 1
Design Manual Chapter 4 - Water Mains Table of Contents TOC Table of Contents Chapter 4 - Water Mains 4A General Information 4A-1---------------------------------General Information A. Concept....... 1
More information452 Series Magnetic Drive Positive Displacement Disc Meters Size 1
Size 1 Features APPLICATIONS: Measurement of cold water for residential and small commercial applications where water volumes are low, and low flow sensitivity is important. CONFORMANCE TO STANDARDS: Hersey
More informationSECTION 12 - WATER DISTRIBUTION SYSTEM
SECTION 12 - WATER DISTRIBUTION SYSTEM 12.1 General. Work in this Section includes all water system piping including all valves, hydrants, fittings, anchors, air vents, and other allied equipment or material
More informationADDENDUM NO. 1. Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities
ADDENDUM NO. TO Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities Date of Addendum: December, 00 Hethcoat & Davis, Inc. 78 Franklin Road,
More informationPIPE OUTSIDE DIAMETER GUIDE
August 17, 2017-1 PIPE OUTSIDE DIAMETER GUIDE PIPE OUTSIDE DIAMETER GUIDE - SMALL DIAMETER PIPE SIZES NOMINAL PIPE SIZES 1 /2" 3 /4" 1" 1 1 /4" 1 1 /2" 2" 2 1 /2" THIS O.D. GUIDE IS FOR YOUR CONVENIENCE
More informationTable of Contents. Section Pipe and Fittings Section Includes Description of Work Submittals 1. 1.
Table of Contents Section 5010 - Pipe and Fittings Page No. Part 1 - General 1.01 Section Includes 1 1.02 Description of Work 1 1.03 Submittals 1 1.04 Substitutions 1 1.05 Delivery, Storage, and Handling
More informationSECTION 39 - MANHOLES TABLE OF CONTENTS 39-1 GENERAL PRECAST CONCRETE MANHOLES
Section SECTION 39 - MANHOLES TABLE OF CONTENTS 39-1 GENERAL... 39-1 39-2 PRECAST CONCRETE MANHOLES... 39-1 39-2.01 Precast Concrete Storm Drain Manholes... 39-1 39-3 SADDLE MANHOLES... 39-2 39-3.01 Saddle
More informationRULES AND REGULATIONS FOR WATER AND WASTEWATER SERVICE APPENDIX B WATER AND WASTEWATER SERVICE CONSTRUCTION SPECIFICATIONS
RULES AND REGULATIONS FOR WATER AND WASTEWATER SERVICE APPENDIX B WATER AND WASTEWATER SERVICE CONSTRUCTION SPECIFICATIONS Last Approved Revision: 3-23-2017 Page i TABLE OF CONTENTS SECTION I GENERAL...
More informationCW WATERMAINS TABLE OF CONTENTS
CW 2110 - WATERMAINS TABLE OF CONTENTS 1. DESCRIPTION...1 1.1 General...1 1.2 Definitions...1 1.3 Referenced Standard Construction Specifications...1 1.4 Referenced Standard Details...1 1.5 Referenced
More informationCONSTRUCTION SPECIFICATION FOR WATERMAIN INSTALLATION IN OPEN CUT
ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 441 NOVEMBER 2010 CONSTRUCTION SPECIFICATION FOR WATERMAIN INSTALLATION IN OPEN CUT TABLE OF CONTENTS 441.01 SCOPE 441.02 REFERENCES 441.03 DEFINITIONS
More informationEnvironmental Engineering-I
Environmental Engineering-I Prof. Dr. Muhammad Zulfiqar Ali Khan Engr. Muhammad Aboubakar Farooq Department of Civil Engineering The University of Lahore 1 Water Supply Pipes Valves Fire Hydrants 2 Water
More informationClay County Utility Authority Approved Materials " "
Clay County Utility Authority " "" Clay County Utility Authority "". "". " Clay County Utility Authority DESCRIPTION: Extruded sheets or panels with integral male/female sliding lock connection ends.
More informationSECTION 4 - DESIGN STANDARDS FOR WATER DISTRIBUTION FACILITIES
SECTION 4 - DESIGN STANDARDS FOR WATER DISTRIBUTION FACILITIES 4.1 GENERAL REQUIREMENTS 4.1.1 Water and fire protection distribution facilities are to be provided solely for the purpose of supplying potable
More information2017 Material and Construction Specifications
2017 Material and Construction Specifications Water and Sewer Pre Construction Materials Standard Details Inspections & Testing Todd Marti, Director of Engineering South West, West Valley City, UT T: E:
More informationSECTION PLUMBING PIPING SYSTEMS
SECTION 15300 PLUMBING PIPING SYSTEMS PART 1 - GENERAL 1.01 SPECIAL NOTICE A. Each contractor shall read all relevant documents, become familiar with the job, the scope of work, type of general construction,
More informationDRAINS AND CLEANOUTS. 1. Division 7 - Thermal and Moisture Protection Piping (Plumbing).
SECTION 15421 DRAINS AND CLEANOUTS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. Division 7 - Thermal and Moisture Protection. 2. 15410 - Piping (Plumbing). 1.02 SUBMITTALS A. Product Data: Submit
More informationPOTABLE WATER MAINS. E. Section Water Distribution System Design Guidelines. F. Section Water Main Testing and Acceptance
PART 1 GENERAL 1.1 SECTION INCLUDES A. Furnishing of all plant, labor, equipment, appliances and materials, and in performing all operations in connection with the construction of the water mains, including
More informationCITY OF MARTINEZ STANDARD SPECIFICATIONS FOR WATER LINE WORK
CITY OF MARTINEZ STANDARD SPECIFICATIONS FOR WATER LINE WORK Engineering Division Community Development Department 525 Henrietta Street Martinez, CA 94553 (925) 372-3515 I. Water Pipe TABLE OF CONTENTS
More informationCITY OF WESTFIELD WATER RESOURCES DEPARTMENT PUBLIC DRINKING WATER DISTRIBUTION SYSTEM SPECIFICATIONS (REVISED 3/18/2013)
Page 1 of 23 CITY OF WESTFIELD WATER RESOURCES DEPARTMENT PUBLIC DRINKING WATER DISTRIBUTION SYSTEM SPECIFICATIONS (REVISED 3/18/2013) I. MATERIAL SPECIFICATIONS 1. PIPE 2. FITTINGS 3. COUPLINGS 4. GATE
More informationNFPA 24 May 2002 ROP Copyright 2001, NFPA
NFPA 24 (Log #CP2) 24-1 - (1-1 Scope): Accept SUBMITTER: Technical Committee on Private Water Supply Piping Systems RECOMMENDATION: Modify the scope to read as follows: 1.1 Scope. This standard establishes
More informationAll Prospective Bidders. SUBJECT: Addendum #2. DATE: April 8, Huntley High School Athletic Field Improvements Bid Release #2
TO: All Prospective Bidders SUBJECT: Addendum #2 DATE: April 8, 2013 PROJECT: Huntley High School Athletic Field Improvements Bid Release #2 OWNER: Consolidated School District #158 Algonquin, IL CONSTRUCTION
More informationContact Clark Public Utilities Construction Services department at (360) to initiate a request for service.
CHAPTER3 Clark Public Utilities Commercial Electric Service Handbook Commercial Underground Services Preparing for the installation The following checklist will assist in preparing a project for the installation
More informationSECTION REUSE WATER DISTRIBUTION SYSTEMS
SECTION 02661 REUSE WATER DISTRIBUTION SYSTEMS PART 1 GENERAL 1.01 SCOPE OF WORK A. WORK covered by this Section consists of furnishing and installing reuse water distribution pipes and appurtenances,
More informationNote to users of the online version of this document: The City of Mebane s Standard Specifications and Details are separated out to allow for easier
Note to users of the online version of this document: The City of Mebane s Standard Specifications and Details are separated out to allow for easier access and downloading from the City s website but the
More informationNOTICE OF INTENT TO USE THE GENERAL PERMIT FOR CONSTRUCTION OF WATER MAIN EXTENSIONS FOR PWSs
NOTICE OF INTENT TO USE THE GENERAL PERMIT FOR CONSTRUCTION OF WATER MAIN INSTRUCTIONS: This notice shall be completed and submitted by persons proposing to construct projects permitted under the "General
More informationKennedy Valve. A Division of McWane, Inc. AWWA PRODUCTS
Kennedy Valve A Division of McWane, Inc. AWWA PRODUCTS 1021 East Water Street Elmira, NY 14902 Phone: (607)734-2211 Fax: (607)734-3288 Fax: (800)952-4771 E-Mail: sales@kennedyvalve.com www.kennedyvalve.com
More information