1 SECTION INDOOR AIR QUALITY REQUIREMENTS PART 1 - GENERAL 1.1 SUMMARY OF WORK A. This section includes the indoor air quality requirements and identifies methods of implementation and documentation to achieve the IAQ management objectives. B. Related Sections: 1. Division 01 Section Sustainable Design Requirements 2. Division 01 Section Construction Waste Management and Disposal Plan. 1.2 REFERENCES A. LEED Green Interior Design and Construction v2009 Reference Guide. Indoor Environmental Quality Credit 4.1, 4.2, 4.3, 4.4, 4.5: Low-Emitting Materials B. ASHRAE. ANSI/ASHRAE : Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size. C. EPA. EPA Protocol for Environmental Requirements, Testing for Indoor Air Quality Baseline IAQ. D. State of California. South Coast Air Quality Management District (SCAQMD) Rules October 2003 (as amended). E. State of California. South Coast Air Quality Management District (SCAQMD) Rules November 1996 (as amended). F. Green Seal. Paints (GS-11). January May G. Green Seal. Anti-Corrosive Paints (GC-03). January H. U.S. Green Building Council. Indoor Environmental Quality Credit 3: Construction IAQ Management Plan and Credit 4: Low-Emitting Materials Leadership in Energy and Environmental Design Reference Guide for Green Interior Design and Construction (LEED- ID&C) Version LEED CONSTRUCTION COORDINATOR A. The LEED Construction Coordinator shall be responsible for: 1. Supervising on-site indoor air quality management activities on a daily basis 2. Coordinating indoor air quality management tasks with subcontractors to ensure timely and orderly progress of the work 3. Preparing indoor air quality management documentation and submittals 4. Reporting indoor air quality management progress to the Contracting Officer INDOOR AIR QUALITY

2 B. LEED Kick-Off Meeting, Review: 1. Indoor Air Quality Management Objectives 2. Indoor Air Quality Management Description of Work 3. Indoor Air Quality Management Postings and Submittals C. LEED Orientation Meeting; Review: 1. Indoor Air Quality Management Objectives 2. Indoor Air Quality Protection Measures 1.4 SUBMITTALS A. Product VOC Identification Schedules: 1. Complete schedule and collect supporting documentation (MSDSs, product data sheets, letter from manufacturers, etc.) to document VOC emission rates for all adhesives, sealants, paints and coatings that are applied onsite and fall within the building weather barrier. 2. Complete schedule to document the quantities of all adhesives, sealants, paints and coatings that are applied onsite and fall within the building weather barrier. 3. Submit completed schedules and supporting product literature to the Contracting Officer for review at least 14 days prior to ordering. B. CRI Green Label Carpet Schedules: 1. Complete schedule and collect supporting documentation (letters from manufacturers, product literature, etc.) for all carpet products used in the project. 2. Submit completed schedules and supporting product literature to the Contracting Officer for review at least 14 days prior to ordering. C. No-Added Urea-Formaldehyde Schedules: 1. Complete schedule and collect supporting documentation (letters from manufacturers, product literature, etc.) for all composite wood and agrifiber products used in the project. 2. Submit completed schedules and supporting product literature to the Contracting Officer for review at least 14 days prior to ordering. D. Greenguard Indoor Air Quality Certified: 1. Complete schedule and collect supporting documentation (letters from manufacturers, product literature, etc.) for all systems furniture used in the project. 2. Submit completed schedules and supporting product literature to the Contracting Officer for review at least 14 days prior to ordering. E. IAQ Management Inspection Log 1. Complete the log on a weekly basis. The log shall commence when the building is enclosed and carry through to building turnover. 2. The inspection log shall be completed for each weekly inspection and must document: a. Indoor air quality management measures implemented onsite INDOOR AIR QUALITY

3 b. Deficiencies related to those measures and, c. Corrective actions taken to remedy the deficiencies 3. Each deficiency must be initialed and each log signed after all corrective measures have been completed and documented. 4. Submit an up-to-date copy of the IAQ Management Inspection Log to the Contracting Officer on a monthly basis. 5. Submit a compilation of the completed logs to the Contracting Officer after construction and prior to Contractor demobilization. F. Photographs: 1. Provide photographs as specified in the IAQ Management Plan, attached to the end of this section. 2. Photographs must be taken on three different occasions during construction to prove sustained compliance. 3. Photographs must be date stamped, and a description of the indoor air quality management measure depicted. 4. Coordinate with photo requirements as indicated in Division 01 Section Sustainable Design Requirements. G. Final Report 1. Submit the IAQ Final Report to the Government and Contracting Officer that includes all IAQ Management Schedules and documentation, and all required photographs. 2. Submit report with the application for Substantial Performance 3. All Schedules are to be completed and signed by the General Contractor and Sub- Contractors. INDOOR AIR QUALITY

4 1.5 MAXIMUM VOC (VOLATILE ORGANIC COMPUND) PRODUCT LIMITS A. VOC Levels for Adhesives and Sealants EQ Credit 4.1 EQc4.1: Adhesives and Sealants Used on the interior of the building (inside the waterproofing system and applied on site) Classification of Material VOC Limit (g/l less water) Applicable Standard Architectural Applications Indoor Carpet Adhesives 50 g/l SCAQMD Rule #1168 Carpet Pad Adhesives 50 g/l SCAQMD Rule #1168 Wood Flooring Adhesive 100 g/l SCAQMD Rule #1168 Rubber Floor Adhesives 60 g/l SCAQMD Rule #1168 Subfloor Adhesives 50 g/l SCAQMD Rule #1168 Ceramic Tile Adhesives 65 g/l SCAQMD Rule #1168 VCT & Asphalt Adhesives 50 g/l SCAQMD Rule #1168 Drywall and Panel Adhesives 50 g/l SCAQMD Rule #1168 Cove Base Adhesives 50 g/l SCAQMD Rule #1168 Multipurpose Construction Adhesives 70 g/l SCAQMD Rule #1168 Structural Glazing Adhesives 100 g/l SCAQMD Rule #1168 Specialty Applications PVC Welding 510 g/l SCAQMD Rule #1168 CPVC Welding 490 g/l SCAQMD Rule #1168 ABS Welding 325 g/l SCAQMD Rule #1168 Plastic Cement Welding 250 g/l SCAQMD Rule #1168 Adhesive Primer for Plastic 550 g/l SCAQMD Rule #1168 Contact Adhesive 80 g/l SCAQMD Rule #1168 Special Purpose Contact Adhesive 250 g/l SCAQMD Rule #1168 Structural Wood Member Adhesive 140 g/l SCAQMD Rule #1168 Sheet Applied Rubber Lining Operations 850 g/l SCAQMD Rule #1168 Top & Trim Adhesive 250 g/l SCAQMD Rule #1168 Substrate Specific Applications Metal to Metal 30 g/l SCAQMD Rule #1168 Plastic Foams 50 g/l SCAQMD Rule #1168 Porous Material (except wood) 50 g/l SCAQMD Rule #1168 Wood 30 g/l SCAQMD Rule #1168 Fiberglass 80 g/l SCAQMD Rule #1168 Sealants Architectural 250 g/l SCAQMD Rule #1168 Nonmembrane Roof 300 g/l SCAQMD Rule #1168 Roadway 250 g/l SCAQMD Rule #1168 Single-Ply Roof Membrane 450 g/l SCAQMD Rule #1168 Other 420 g/l SCAQMD Rule #1168 Sealant Primers Architectural Non Porous 250 g/l SCAQMD Rule #1168 Architectural Porous 775 g/l SCAQMD Rule #1168 Other 750 g/l SCAQMD Rule #1168 Aerosol Adhesives General Purpose Mist Spray 65% VOC's by weight Green Seal GS-36 General Purpose Web Spray 55% VOC's by weight Green Seal GS-36 Special Purpose Aerosol Adhesives (all types) 70% VOC's by weight Green Seal GS-36 INDOOR AIR QUALITY

5 B. VOC Levels For Paints EQc4.2 EQc4.2: Paints & Coatings Used on the interior of the building (inside the waterproofing system and applied on site) Classification of Material VOC Limit (g/l less water) Applicable Standard Architectural Paints, coatings and primers applied to interior walls and ceilings Flat 50 g/l Green Seal GS-11, 1993 Non-Flat 150 g/l Green Seal GS-11, 1993 Ferrous Metal Paints Anti-corrosive Paint 250 g/l Green Seal GS-03, 2nd Addition, 1997 Anti-rust paint 250 g/l Green Seal GS-03, 2nd Addition, 1997 Clear wood finishes, floor coatings, stains, sealers, and shellacs Clear Wood Varnish 350 g/l SCAQMD Rule #1113, 2004 Clear Wood Lacquer 550 g/l SCAQMD Rule #1113, 2004 Clear Brushing Lacquer 680 g/l SCAQMD Rule #1113, 2004 Pigmented Lacquer 550 g/l SCAQMD Rule #1113, 2004 Concrete curing compounds 350 g/l SCAQMD Rule #1113, 2004 Japans/Faux Finishing Coatings 350 g/l SCAQMD Rule #1113, 2004 Magnesite Cement Coatings 450 g/l SCAQMD Rule #1113, 2004 Waterproofing Concrete/Masonry Sealers 400 g/l SCAQMD Rule #1113, 2004 Wood Preservatives 350 g/l SCAQMD Rule #1113, 2004 Low Solids Coatings 120 g/l* SCAQMD Rule #1113, 2004 Floor Coatings 100 g/l SCAQMD Rule #1113, 2004 Waterproofing Sealers 250 g/l SCAQMD Rule #1113, 2004 Sealers and Undercoaters 200 g/l SCAQMD Rule #1113, 2004 Shellac: Clear 730 g/l SCAQMD Rule #1113, 2004 Shellac: Pigmented 550 g/l SCAQMD Rule #1113, 2004 Sanding Sealers 350 g/l SCAQMD Rule #1113, 2004 All Other Sealers 200 g/l SCAQMD Rule #1113, 2004 Stains 250 g/l SCAQMD Rule #1113, 2004 *Note: VOC lev els for Low-Solids Coatings are measured in grams of VOC per liter of material, 1.6 FLOORING SYSTEM REQUIREMENTS EQc4.3 A. The following chart illustrates maximum allowable carpet emissions from the Green Label Testing Program Carpet and Carpet Cushion Criteria INDOOR AIR QUALITY

6 EQc4.3: Flooring Systems Installed in the building interior Classification Requirement Applicable Standard Option 1: Carpet Green Label Plus CRI Green Label Plus Carpet Cushion Green Label CRI Green Label Carpet Adhesive VOC Limit 50 g/l SCAQMD Rule #1168 *Hard Surface Flooring FloorScore std compliant or a more stringent version by independent 3rd-party Concrete, wood, bamboo, cork flooring finmeet Sealer and StaSCAQMD Rule 1113 Tile setting adhesives and grout Meet VOC Limits SCAQMD Rule 1168 *FloorScore products include vinyl, linoleum, laminate, wood, ceramic and rubber flooring and wall base An alternative compliance path using FloorScore is acceptable for credit achievement: 100% of the non-carpet finished flooring must be FloorScore certified and must constitute 25% of the finished floor area (examples include mechanical electrical and elevator service rooms) OR Option 2: All flooring elements installed must meet the requirements of the California Dept of Health Services Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers, including 2004 Addenda. B. All hard surface flooring must be certified as compliant with FloorScore standard by an independent third party and/or meet the requirements of South Coast Air Quality Management District Rule 1113, Architectural Coatings. 1.7 COMPOSITE WOOD, AGRIFIBER PRODUCTS & LAMINATES EQc4.4 A. All composite wood, Agrifiber products, and laminating adhesives to contain no added urea formaldehyde (UF) resins. EQc4.4 Composite Wood & Agrifiber Products Used on the interior of the building (inside the waterproofing system and applied on site) Classification Particleboard Medium Density Fiberboard (MDF) Plywood Wheatboard Strawboard Panel Substrates Door Cores Other Composite Wood Products Other Agrifiber Products Requirement 1.8 SYSTEMS FURNITURE & SEATING REQUIREMENTS EQc4.5 A. All systems furniture and seating that was manufactured, refurbished or refinished within one year prior to occupancy must meet one of the options below. INDOOR AIR QUALITY

7 EQc4.5 Systems Furniture & Seating Systems furniture is defined as either a panel-based workstation comprised of modular interconnection panels, hang-on components and drawer/filing components, or a freestanding grouping of furniture items and their components that have been designed to work in concert. Furniture other than systems furniture and task and guest chairs used with systems furniture is defined as occasional furniture and is excluded from credit requirements. Classification Applicable Standard Option 1: Furniture and Seating Greenguard Indoor Air Quality Option 2: Calculated indoor air concentrations that are less than or equal to those listed below for furniture systems and seating determined by a procedure based on ANSI/BIFMA M and ANSI/BIFMA X testing protocol conducted in an indepndent third party air quality testing laboratory Maximum Indoor Air Concentrations Chemical Contaminant Systems Furniture Seating Total VOCs 0.5 mg/m mg/m3 Formaldehyde 50 parts per billion 25 parts per billion Total Aldehydes 100 parts per billion 50 parts per billion 4-phenylcyclohexene (4-PCH) mg/m mg/m3 1.9 FILTRATION MEDIA REQUIREMENTS A. Refer to Section 3.7 HVAC PROTECTION MEASURES B. Air handling equipment not used during construction: 1. Protect all HVAC equipment and ductwork from collecting dust, water and odors. This is accomplished by sealing all openings into the HVAC systems with plastic. This includes all supply and return openings and duct installation in progress during ALL phases of installation. C. Air handling equipment used during construction: 1. Install new filters with a MERV = 8 (or higher) at all return/exhaust grilles/inlets before any HVAC system is operated. 2. Install new filters with a MERV = 13 (or higher) at all return/exhaust grilles/inlets before building is occupied. PART 2 - PRODUCTS (NOT USED) PART 3 - EXECUTION 3.1 SITE ASSESSMENT A. Conduct a thorough site assessment to determine areas of concern from an Indoor Air Quality management perspective. Implement IAQ Management measures and document with the appropriate IAQ Management schedules. INDOOR AIR QUALITY

8 3.2 VOC PRODUCTS AND MATERIALS IDENTIFICATION A. Provide a list of adhesives, sealants, paints, coatings, carpeting, and wood composite materials and products that shall be installed within the building vapor barrier. B. The sub-contractor shall provide documentation (MSDS or other product literature) that clearly states the amount of VOC s in grams per liter. 3.3 SOURCES OF POLLUTANTS A. Any construction activity that produces odor and/or dust is considered a source of air pollutants. Typical sources of pollutants include: 1. Disturbing materials during demolition, repair or construction. 2. Materials that produce detectable odor. 3. Materials that create dust. 4. Equipment that emits products of combustion or creates odor and/or dust. 5. Construction activities that disrupt pollutants that have settled. B. Possible sources of pollutants include: BUILDING MATERIALS WET PRODUCTS FURNISHINGS SOLUTIONS GASOLINE / DIESEL POWERED LPG and OTHER GASES OTHER SOURCES Concrete Drywall Engineered wood products Cove base Paint and stains Sealants and coatings Adhesives Acid finish Carpeting Wood flooring Furniture Solvents Cleaning products Generators Compressors Portable heaters Epoxy flooring Roofing Insulation Ceiling tiles Glazing Caulking Grouting Wall coverings Cabinets Partitions Fuels Pesticides Heavy equipment Vehicles Welder Cutting torch Standing water/moisture causing mold growth Tobacco smoking within the building Exterior work adjacent to building openings Soldering gun 1. List all potential sources of indoor air pollutants on the construction site. Refer to Source Control Plan Schedule B to be provided by LEED consultant in Excel format at construction kick-off. 2. Do not permit smoking inside the building where porous materials are installed (drywall, ceiling tiles, carpet, etc.). 3. Do not burn garbage. 4. Do not fuel up equipment inside the building. 5. Do not store gasoline or solvents inside the building. 6. Do not allow lubricants to spill within the building (e.g. pipe threading oil). 7. Promptly clean all spills (fuels, lubricants, paints, adhesives, etc.). 8. Restrict outdoor vehicular/equipment traffic and operation where emissions can be drawn into building. INDOOR AIR QUALITY

9 9. Reduce on-site emissions by using equipment that burns propane/natural gas instead of gasoline. Electric equipment eliminates combustion emissions. 10. Exhaust pollution sources directly to the outside using temporary or permanent ventilation equipment (refer to HVAC Protection Measures). 11. Where exhaust is not feasible and ventilation is required, locally re-circulate air through a portable air cleaner. 12. Collect and bag sawdust from woodworking tools. 13. Cover and/or seal all indoor sources of odor and dust. 14. Use painting techniques that minimize odor (roller instead of spraying) 15. Use cleaning practices that minimize dust (vacuum instead of sweeping). 16. Use cleaning products that minimize pollution, fumes, VOC s, chemicals. 3.4 CONTAINMENT IAQ POLLUTANT MEASURES A. Prevent the movement of pollutants from the source to other areas in the building as follows: B. Erect dust curtains/doors/barriers C. Use portable fans to exhaust pollutants (e.g. gas engine exhaust) to the exterior through windows, doors, etc. Ensure that other windows or doors will not let pollutants back into building. D. Close windows and doors close to exterior work do not allow exterior pollutants to enter the building (dust, vehicle emissions, etc.). If windows and doors are not yet installed, temporarily seal openings with plastic, wood, etc. E. Move equipment or pollutant-causing work to locations where IAQ impact is minimized: 1. Avoid high draft or large open areas 2. Use shields and curtains to contain work 3. Locate in small, contained areas 4. Locate outside the building 5. Depressurize the work area using temporary or permanent ventilation equipment (refer to HVAC Protection Measures). 6. Pressurize occupied or completed areas using temporary or permanent ventilation equipment (refer to HVAC Protection Measures). 3.5 HOUSEKEEPING MEASURES A. Clean frequently to collect dust. B. Minimize creation of dust during cleaning by using wetting agents, sweeping compounds, damp rags, wet mop. C. Use vacuum equipment with HEPA filtration and/or a wet scrubber. D. Clean spills promptly. E. Clean or remove excess application of solvent-containing products. F. Remove accumulated water and keep the building interior as dry as possible. INDOOR AIR QUALITY

10 G. Close windows and doors close to exterior moisture or provide temporary enclosures of plastic or wood H. Use ventilation/dehumidification to reduce interior humidity if necessary. I. Cover, seal and protect materials stored and installed on-site from moisture, dust and dirt accumulation. J. Do not install any materials with evidence of moisture damage or excessive moisture content. K. Do not place materials directly on the ground. Always elevate materials off the ground to protect from moisture and dirt. 3.6 SCHEDULING MEASURES A. Schedule construction activities to reduce absorption of VOC s, odors and fumes by porous materials. B. Complete applications of wet and odorous materials such as paints, sealants, and coatings before installing absorbent sink materials such as ceiling tiles, carpets, and fabric-covered furnishings. C. Allow for Testing, Adjusting and Balancing to be carried out following construction and before occupancy (refer to HVAC Protection Measures). D. Allow for corrective work related to general deficiencies, Testing, Adjusting and Balancing, and Commissioning to be carried out following construction and before occupancy. 3.7 HVAC PROTECTION MEASURES A. General 1. Protect all HVAC equipment and ductwork from collecting dust, water and odors. 2. Protect acoustic lining, and insulation as well as pre-lined and insulated ductwork from moisture accumulation and damage. This applies both to stored material and installed systems. 3. Cover ALL equipment and stockpiled ducts and fittings with plastic during construction. Close and cover all hatches and access doors when the equipment is not being worked on. 4. Do not use the mechanical room to store or collect construction waste materials. 5. Install ceiling tiles prior to final cleaning to prevent dust accumulation in ceiling plenum. 6. HVAC protection measures will be reviewed by the Engineer during each site visit. 7. Correct HVAC protection deficiencies identified by the engineer within 48 hours of notification 8. Clean or replace any equipment or materials that is incorrectly stored or improperly protected at no extra cost to the contract. 9. Air filter MERV (minimum efficiency reporting value ) ratings shall be determined by ASHRAE B. Select either OPTION 1 or OPTION 2 for each ventilation system: 1. OPTION 1 Ventilation Equipment NOT Used During Construction (RECOMMENDED) If INDOOR AIR QUALITY

11 the Contractor does not intend to operate ventilation equipment during construction the following measures MUST be implemented at the Contractor s expense. a. Do not operate any permanent HVAC equipment or systems during construction. b. Seal all openings into the HVAC systems with plastic. While ductwork installation is proceeding, seal all duct openings (open ends) that are not under immediate work. As ductwork installation is completed, seal all supply, return and exhaust openings. c. Seal all equipment openings (inlets and outlets on air handlers, fans, VAV boxes, etc.) with plastic until ductwork is connected. Seal ductwork as described above. d. For ceiling plenums, install ceilings and seal all openings into plenum with plastic. e. If the HVAC system protection measures do not meet this specification or if the system is operated during construction, the contractor must provide duct cleaning, plus all necessary access doors, at no extra cost to the contract. f. When all construction work is complete: 1) Remove plastic from system openings. 2) Install new filters with a MERV = 13 (or higher) in all air handling equipment (package and built-up equipment). Coordinate with the filtration requirements of Division 23 Sections. 3) Start-up systems. 4) Prepare systems for Testing, Adjusting and Balancing Contractor and Commissioning Agent. 2. OPTION 2 - Ventilation Equipment Used During Construction: If intended to operate any ventilation equipment during construction the following measures MUST be implemented at the Contractor s expense. a. Install filters with a MERV 8 (or higher) at all return/exhaust grilles. If return/exhaust grilles are not specified with filters, provide temporary filters as required. (Filter requirements apply to all system types: re-circulating, 100% outside air, and exhaust-only.) b. Temporarily shut down the return/exhaust side of the system during heavy construction/demolition. c. Permanently close off the return/exhaust side of the system in areas with high dust levels. Cover duct openings with plastic in these areas. d. If the HVAC system is operated during construction without proper protection (as outlined in this specification) the contractor must provide duct cleaning, plus all necessary access doors, at no extra cost to the contract. e. When all construction work is complete: 1) Install new filters with a MERV = 13 (or higher) in all air handling equipment (package and built-up equipment). Coordinate with the filtration requirements of Division 23 Sections. 2) Remove all temporary filters at grilles. 3) Prepare systems for Testing, Adjusting and Balancing Contractor and Commissioning Agent. 3.8 INSTALLATION OF PRODUCTS A. All filters, plastic and other protection measures shall be properly installed, and installation shall be reviewed by Consultant to ensure compliance. INDOOR AIR QUALITY

12 3.9 SCHEDULING A. Schedule construction activities to minimize the amount of VOC s, odors and fumes absorbed by porous materials (e.g. ceiling tiles, carpet, etc.). B. Complete applications of wet and odorous materials such as paints, sealants, and coatings before installing absorbent sink materials such as ceiling tiles, carpets, and fabric-covered furnishings. C. Allow for Testing, Adjusting and Balancing to be carried out following construction and before occupancy (refer to HVAC Protection Measures). D. Allow for corrective work related to general deficiencies, Testing, Adjusting and Balancing, and Commissioning to be carried out following construction and before occupancy INSPECTIONS AND MAINTENANCE A. All indoor air quality management measures shall be inspected on a weekly basis and any deficiencies shall be remedied. B. Inspections shall be photographed and documented in the IAQ Management log and shall denote any deficiencies as well as corrective action taken during the weekly inspections. C. The IAQ Management Inspection Log shall be provided to the Contracting Officer for review if requested. This log shall be started when the building is enclosed, and shall carry through to building turnover to the Government. D. All Pollutant Containment, Housekeeping and HVAC protection measures will be reviewed by the Contracting Officer during each site visit. E. After building turn-over a complete copy of the IAQ logs for the duration of the project to be provided to the Contracting Officer for documentation purposes. F. The Contractor shall clean or replace any equipment or materials that is incorrectly stored or improperly protected at no extra cost to the contract REMOVAL OF PRODUCTS A. All products installed, as a part of the indoor air quality program s temporary measures shall be removed prior to building turnover. Any remedial work required as a result of removing the control measures shall be the responsibility of the contractor. PART 4 - CLOSE OUT 4.1 Final Report A. Submit the IAQ Final Report to the LEED consultant that includes all IAQ Management Schedules and documentation, and all required photographs. B. Submit report with the application for Substantial Performance C. All Schedules are to be completed and signed by the General Contractor and Sub-Contractors. INDOOR AIR QUALITY

13 END OF SECTION INDOOR AIR QUALITY

SECTION Indoor Air Quality Management - LEED for Schools CONSTRUCTION MANAGER EDITION

SECTION Indoor Air Quality Management - LEED for Schools CONSTRUCTION MANAGER EDITION SECTION 01811 - Indoor Air Quality Management - LEED for Schools CONSTRUCTION MANAGER EDITION PART 1 GENERAL 1.1 Summary: A. Construction activities shall be controlled to avoid causing detectable odor,

More information

CAMP BLANDING JOINT TRAINING CENTER CONSTRUCTION AND FACILITY MANAGEMENT OFFICE ARCHITECT S PROJECT # CFMO PROJECT #

CAMP BLANDING JOINT TRAINING CENTER CONSTRUCTION AND FACILITY MANAGEMENT OFFICE ARCHITECT S PROJECT # CFMO PROJECT # SECTION 018113.13 - PART 1 - GENERAL 1.1 SUMMARY A. Section includes general requirements and procedures for compliance with certain USGBC LEED prerequisites and credits needed for Project to obtain LEED

More information

SECTION INDOOR AIR QUALITY MANAGEMENT PLAN. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION INDOOR AIR QUALITY MANAGEMENT PLAN. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 018119 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

SECTION SUSTAINABLE DESIGN REQUIREMENTS LEED FOR NEW CONSTRUCTION AND MAJOR RENOVATIONS

SECTION SUSTAINABLE DESIGN REQUIREMENTS LEED FOR NEW CONSTRUCTION AND MAJOR RENOVATIONS SECTION 018113.13 - SUSTAINABLE DESIGN REQUIREMENTS LEED FOR NEW CONSTRUCTION AND MAJOR RENOVATIONS PART 1 - GENERAL 1.1 SUMMARY A. Section includes general requirements and procedures for compliance with

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 01 8113.53 - SUSTAINABLE DESIGN REQUIREMENTS - GREEN GLOBES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Note year for Reference as Specified in the LEED V Manual.

Note year for Reference as Specified in the LEED V Manual. PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Sustainable design Project goals. 2. Sustainable design product requirements. B. Related Sections: 1. Section 01810 - Commissioning: General commissioning

More information

Low Emitting Materials

Low Emitting Materials Low Emitting Materials LEED v4 Requirements This credit covers volatile organic compound (VOC) emissions into indoor air and the VOC content of materials, as well as the testing methods by which indoor

More information

Indoor Air Quality Management Plan for LEED

Indoor Air Quality Management Plan for LEED Terminal Development Program Contract 1: 201301B San Diego Airport Terminal 2 West Expansion Indoor Air Quality Management Plan for LEED Prepared by HVAC Design Builder: California Comfort Systems USA

More information

Indoor Air Quality (IAQ) Requirements

Indoor Air Quality (IAQ) Requirements University of New Hampshire University of New Hampshire Scholars' Repository Division 01 General Requirements Chapter 5 Technical Construction and Renovation Standards 1-25-2013 013560 - Indoor Air Quality

More information

UNIVERSITY OF ROCHESTER DIVISION 01 SPECIFICATIONS November 4, 2013 SECTION SUSTAINABLE DESIGN REQUIREMENTS - LEED FOR NEW

UNIVERSITY OF ROCHESTER DIVISION 01 SPECIFICATIONS November 4, 2013 SECTION SUSTAINABLE DESIGN REQUIREMENTS - LEED FOR NEW SECTION 018113.13 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,

More information

Construction Indoor Air Quality (IAQ) Management Plan

Construction Indoor Air Quality (IAQ) Management Plan Denver School of Science & Technology Middle School 2000 Valentia Street Denver, CO 80238 Telephone: 303-643-5775 Main Fax: 303-673-5776 Construction Indoor Air Quality (IAQ) Management Plan Denver School

More information

SECTION GREEN BUILDING POLICY IMPLEMENTATION

SECTION GREEN BUILDING POLICY IMPLEMENTATION SECTION 01390 [Note: The intent of this section is to identify Contractor specific work required for achievement of the University Green Building Policy. The policy applies to all new facilities, and partially

More information

New Montgomery County Elementary School. Construction Indoor Air Quality Management Plan IEQc3.1 IAQ Plan During Construction

New Montgomery County Elementary School. Construction Indoor Air Quality Management Plan IEQc3.1 IAQ Plan During Construction New Montgomery County Elementary School Construction Indoor Air Quality Management Plan IEQc3.1 IAQ Plan During Construction LEED certification promotes environmentally friendly buildings and sites through

More information

Chapter 8: Indoor Environmental Quality

Chapter 8: Indoor Environmental Quality Chapter 8: Indoor Environmental Quality 1 Learning Objectives Minimum indoor air quality performance Environmental tobacco smoke control Enhanced indoor air quality strategies Low-emitting materials Construction

More information

I. CONSTRUCTION WASTE MANAGEMENT PLAN II. CONSTRUCTION INDOOR AIR QUALITY MANAGEMENT PLAN

I. CONSTRUCTION WASTE MANAGEMENT PLAN II. CONSTRUCTION INDOOR AIR QUALITY MANAGEMENT PLAN RECOMMENDED TENANT CONSTRUCTION PLANS June 2015 I. CONSTRUCTION WASTE MANAGEMENT PLAN II. CONSTRUCTION INDOOR AIR QUALITY MANAGEMENT PLAN To learn more please visit the sustainability section of our website:

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 083.3 - SUSTAINABLE DESIGN REQUIREMENTS - LEED 2009 FOR PART - GENERAL. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Contractor's Letter of Assurance

Contractor's Letter of Assurance Contractor's Letter of Assurance Instructions WELL Certification is determined by onsite Performance Verification and documentation, including Letters of Assurance from the appropriate professionals overseeing

More information

GREEN GUIDELINES FOR RENOVATIONS UNIVERSITY OF PENNSYLVANIA

GREEN GUIDELINES FOR RENOVATIONS UNIVERSITY OF PENNSYLVANIA GREEN GUIDELINES FOR RENOVATIONS UNIVERSITY OF PENNSYLVANIA January 2015 GREEN GUIDELINES FOR RENOVATIONS Purpose of these guidelines: The intent of these guidelines is to improve environmental practices

More information

Where Green Turns into Gold Improving Indoor Environmental Quality with LEED

Where Green Turns into Gold Improving Indoor Environmental Quality with LEED Eastern Illinois Safety Network January 2011 Where Green Turns into Gold Improving Indoor Environmental Quality with LEED Jean Ascoli, LEED AP BD+C Architect, Energy Specialist Building Research Council,

More information

Contractor's Letter of Assurance

Contractor's Letter of Assurance Contractor's Letter of Assurance Instructions WELL Certification and WELL Core and Shell Compliance are determined by onsite Performance Verification and Documentation, including Letters of Assurance from

More information

LEED v4 Building Design and Construction Quiz #8 EQ

LEED v4 Building Design and Construction Quiz #8 EQ LEED v4 Building Design and Construction Quiz #8 EQ 1. Which of these is considered an unoccupied space? [Choose three] A. School classroom B. Mechanical room C. Meeting room D. Locker room E. Restroom

More information

ATTACHMENT N LEED PROJECT PROCEDURES

ATTACHMENT N LEED PROJECT PROCEDURES ATTACHMENT N LEED PROJECT PROCEDURES 1. All subcontractors, sub-subcontractors and suppliers at all tiers are to include the following items in their trade scope of work: a. Submit data and documentation

More information

LEED And Your Indoor Environment

LEED And Your Indoor Environment LEED And Your Indoor Environment An overview of LEED v3 and Indoor Air Quality David McCauley, CIE Council Certified Indoor Environmentalist ACAC CIE #1008005 USGBC's Mission To transform the way buildings

More information

Read Health Canada s Tools for schools Action Kit s Introduction, Backgrounder and pages 14-3 to

Read Health Canada s Tools for schools Action Kit s Introduction, Backgrounder and pages 14-3 to DRAFT Renovation and Repair Checklist Excerpted from Tools for Schools Action Kit, Health Canada. Date: To be completed by: Facilities maintenance staff School Custodial staff Contract service providers

More information

Component Goal Performance Measurement Unit. meet the sustainability criteria. described below. described below. from landfills.

Component Goal Performance Measurement Unit. meet the sustainability criteria. described below. described below. from landfills. Facility Maintenance and Renovation Policy for Merchandise Mart Effective date: May 1, 2018 i. Scope This policy applies to any ongoing facility maintenance activities and any facility renovations that

More information

SECTION SUSTAINABLE CONSTRUCTION REQUIREMENTS

SECTION SUSTAINABLE CONSTRUCTION REQUIREMENTS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 01 81 13 SUSTAINABLE CONSTRUCTION REQUIREMENTS A. This Section describes general requirements and procedures to comply with federal mandates and U.S. Department

More information

Indoor Environmental Quality Policy

Indoor Environmental Quality Policy University of Florida Indoor Environmental Quality Policy For New Construction and Renovation Environmental Health and Safety Division June 2009 Introduction Effective management of the indoor environmental

More information

PROPOSED CRITERION REVISION: GS-8, GS-34, GS-36, GS-37, GS-40, GS-41, GS-52, GS-53 Volatile Organic Compound Content Section Revisions.

PROPOSED CRITERION REVISION: GS-8, GS-34, GS-36, GS-37, GS-40, GS-41, GS-52, GS-53 Volatile Organic Compound Content Section Revisions. December 4, 2012 PROPOSED CRITERION REVISION: GS-8, GS-34, GS-36, GS-37, GS-40, GS-41, GS-52, GS-53 Volatile Organic Compound Content Section Revisions. Green Seal is proposing revisions to the criterion

More information

DIVISION 9 FINISHES. This Article on Codes, Regulation and Standards shall apply to all Divisions of the Building Standards

DIVISION 9 FINISHES. This Article on Codes, Regulation and Standards shall apply to all Divisions of the Building Standards DIVISION 9 FINISHES This Article on Codes, Regulation and Standards shall apply to all Divisions of the Building Standards 1 Table of Contents SECTION 09 05 13 COMMON FINISHES 2 SECTION 09 51 23 ACOUSTICAL

More information

SECTION SUSTAINABILITY CERTIFICATION REQUIREMENTS LEED HC V3

SECTION SUSTAINABILITY CERTIFICATION REQUIREMENTS LEED HC V3 PART 1 - GENERAL 1.1 DESCRIPTION SECTION 01 81 13.11 SUSTAINABILITY CERTIFICATION REQUIREMENTS LEED HC V3 A. This section describes requirements and procedures which are additive to and compatible with

More information

Organic Chemistry Lab Renovation SECTION SUSTAINABLE DESIGN REQUIREMENTS CAL GREEN

Organic Chemistry Lab Renovation SECTION SUSTAINABLE DESIGN REQUIREMENTS CAL GREEN SECTION 01 81 13 - SUSTAINABLE DESIGN REQUIREMENTS CAL GREEN PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Standard for the Design of High-Performance Green Buildings Except Low-Rise Residential Buildings

Standard for the Design of High-Performance Green Buildings Except Low-Rise Residential Buildings Public Review Draft Proposed Addendum n to Standard 189.1-2017 Standard for the Design of High-Performance Green Buildings Except Low-Rise Residential Buildings First Public Review (December 2018) (Draft

More information

SECTION (SECTION 09650) - RESILIENT FLOORING SPECIFIER NOTE:

SECTION (SECTION 09650) - RESILIENT FLOORING SPECIFIER NOTE: This is a guidance document with sample specification language intended to be inserted into project specifications on this subject as appropriate to the agency's environmental goals. Certain provisions,

More information

DESIGN AND CONSTRUCTION STANDARDS November 2010

DESIGN AND CONSTRUCTION STANDARDS November 2010 09 00 03 GENERAL PROVISIONS A. For renovation projects, consider the building s character and existing finishes. All material patches should blend as closely as possible. Some buildings on campus have

More information

DESIGN AND CONSTRUCTION STANDARDS April 2011

DESIGN AND CONSTRUCTION STANDARDS April 2011 09 00 03 GENERAL PROVISIONS A. For renovation projects, consider the building s character and existing finishes. All material patches should blend as closely as possible. Some buildings on campus have

More information

CE Option 1 and 2 - Provide the pre-development site run -off rate (cfs) CE Option 1 and 2 - Provide the pre-development site run -off quantity (cf)

CE Option 1 and 2 - Provide the pre-development site run -off rate (cfs) CE Option 1 and 2 - Provide the pre-development site run -off quantity (cf) LEED - 2009 for Retail - New and Major Renovations HINESBURG, VERMONT DPM Des.Proj.Mngr Mech., Elect., Plumbing Issued: 12-17-2010 Civil Eng. GC-S General Contractor - Site Revised: 4-9-12 Tasklist for

More information

APPENDIX 01: SAMPLE PRODUCT SUBMITTAL FORM (3 pages) URBAN ARTS ARCHITECTURE Abbott St, Vancouver, BC V6B 2K4 (604)

APPENDIX 01: SAMPLE PRODUCT SUBMITTAL FORM (3 pages) URBAN ARTS ARCHITECTURE Abbott St, Vancouver, BC V6B 2K4 (604) APPENDIX 01: SAMPLE PRODUCT SUBMITTAL FORM (3 pages) LEED-NC 2009 Material Submittal Form To be completed by Subcontractor/Installer Must be included in each product/material submittal Materials will not

More information

SECTION SUSTAINABILITY CERTIFICATION REQUIREMENTS LEED NC V3

SECTION SUSTAINABILITY CERTIFICATION REQUIREMENTS LEED NC V3 PART 1 - GENERAL 1.1 DESCRIPTION SECTION 01 81 13.01 SUSTAINABILITY CERTIFICATION REQUIREMENTS LEED NC V3 A. This section describes requirements and procedures which are additive to and compatible with

More information

SECTION RESILIENT STAIR TREADS CSI 3-PART SHORT-FORM GUIDE SPECIFICATION USE FOR OUTLINE OR DD SPECIFICATION ISSUES. EDIT TO SUIT PROJECT

SECTION RESILIENT STAIR TREADS CSI 3-PART SHORT-FORM GUIDE SPECIFICATION USE FOR OUTLINE OR DD SPECIFICATION ISSUES. EDIT TO SUIT PROJECT SECTION 09 6 13 RESILIENT STAIR TREADS CSI 3-PART SHORT-FORM GUIDE SPECIFICATION USE FOR OUTLINE OR DD SPECIFICATION ISSUES. PART 1 - GENERAL 1.1 SUMMARY EDIT TO SUIT PROJECT A. Work of this Section consists

More information

LEED 2009 Green Building Rating Systems Information Sheet 06/03/2009

LEED 2009 Green Building Rating Systems Information Sheet 06/03/2009 ENVIRONMENTAL HEALTH & SAFETY SERVICES LEED 2009 Green Building Rating Systems Information Sheet 06/03/2009 LEED is an acronym for Leadership in Energy and Environmental Design. It is a program developed

More information

Procedure for Department Managed Repair and Renewal Projects Under $15,000

Procedure for Department Managed Repair and Renewal Projects Under $15,000 Applies to: All Medical School Departments GUIDELINES: Issued: March 28, 2012 Revised: February 8, 2016 PURPOSE: To provide guidance to departments for repair and renewal projects with an estimated budget

More information

CITY OF ORANGE BUILDING DIVISION 2016 Green Building Code Requirements For Residential Construction

CITY OF ORANGE BUILDING DIVISION 2016 Green Building Code Requirements For Residential Construction CITY OF ORANGE BUILDING DIVISION 2016 Green Building Code Requirements For Residential Construction In order to facilitate sustainable construction practices, all new projects* must comply with the State

More information

A. Section includes surface preparation and application of wood finishes[.]

A. Section includes surface preparation and application of wood finishes[.] SECTION 09 93 00 - STAINING AND TRANSPARENT FINISHING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Produkt Declaration - LEED 2009 New Construction And Major Renovations NC & CS

Produkt Declaration - LEED 2009 New Construction And Major Renovations NC & CS OL REFLECT 2K- Product Rating The product fulfills the requirements for adhesives and sealants and contribute to achieve one LEED credit within IEQ Credit 4.1. The product fulfills the requirements for

More information

Indoor Environmental Quality

Indoor Environmental Quality Indoor Environmental Quality Factors that affect IEQ Air Quality IEQ Materials Connectivity 1 Fresh Air Ventilation Enhance indoor air quality Comfort Performance Well-being of the occupants Good IEQ can

More information

SECTION INDOOR AIR QUALITY (IAQ) MANAGEMENT

SECTION INDOOR AIR QUALITY (IAQ) MANAGEMENT SECTION 01 57 19 INDOOR AIR QUALITY (IAQ) MANAGEMENT 1 GENERAL 1.1 SUMMARY A. This Section includes special requirements for Indoor Air Quality (IAQ) management during construction operations. 1. Control

More information

Specification and Installation

Specification and Installation SHAW 5100 SPECIFICATION ADHESIVE FOR SHAW CARPET TILE Any variance from these procedures will become the responsibility of the installer and not the manufacturer. See Shaw s Modular Installation Guidelines

More information

STC MANUFACTURER STEEL DOOR WITH PLYWOOD 3/4

STC MANUFACTURER STEEL DOOR WITH PLYWOOD 3/4 FICHE TECHNIQUE LEED STC MANUFACTURER Among the leaders in manufacturers of steel doors and frames, STC Manufacturer was founded in 1993. He is characterized by non-standard production and quick deadline

More information

PROCUREMENT AND CONTRACTING DOCUMENTS GROUP

PROCUREMENT AND CONTRACTING DOCUMENTS GROUP PROCUREMENT AND CONTRACTING DOCUMENTS GROUP DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS 00 11 00 Notice To Bidders 00 21 00 Instructions To Bidders 00 22 00 Supplementary Instructions To Bidders

More information

Napa County Building Officials Coalition

Napa County Building Officials Coalition Napa County Building Officials Coalition Striving to provide clear and consistent building code information and handouts for all Napa County jursidictions. (Please check with each jursidiction for any

More information

TEXAS FACILITIES COMMISSION Edit Date: 4/13/2012 ARCHITECTURAL/ENGINEERING GUIDELINES

TEXAS FACILITIES COMMISSION Edit Date: 4/13/2012 ARCHITECTURAL/ENGINEERING GUIDELINES General The following guidelines must be met by both the Architect/Engineer (A/E) consultant and the contractor to assure indoor air quality of the building being provided. At the direction of the Project

More information

Residential 1 to 3 Story CALGreen (CGBSC) Correction List (To be inserted within the body of the Residential Plan Check Correction List)

Residential 1 to 3 Story CALGreen (CGBSC) Correction List (To be inserted within the body of the Residential Plan Check Correction List) Residential 1 to 3 Story CALGreen (CGBSC) Correction List (To be inserted within the body of the Residential Plan Check Correction List) 1. Because of special conditions, the City is requiring the construction

More information

GENERAL PROVISIONS

GENERAL PROVISIONS 09 00 03 GENERAL PROVISIONS A. For renovation projects, consider the building s character and existing finishes. All material patches should blend as closely as possible. Some buildings on campus have

More information

LEED Best Practices Save $$$

LEED Best Practices Save $$$ 16 Savings result where LEED has been applied to improve IAQ! LEED Best Practices Save $$$ A growing body of green building case studies document the benefits of healthy IAQ in the workplace Learn More

More information

GENERAL PROVISIONS

GENERAL PROVISIONS 09 00 03 GENERAL PROVISIONS A. For renovation projects, consider the building s character and existing finishes. All material patches should blend as closely as possible. Some buildings on campus have

More information

SECTION SUSTAINABLILITY CERTIFICATION REQUIREMENTS - GREEN GLOBES

SECTION SUSTAINABLILITY CERTIFICATION REQUIREMENTS - GREEN GLOBES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 01 81 13.21 SUSTAINABLILITY CERTIFICATION REQUIREMENTS - GREEN GLOBES A. This section describes general requirements and procedures to comply with the Green Building

More information

E. Popcorn or other spray applied textures on ceiling or walls are not acceptable.

E. Popcorn or other spray applied textures on ceiling or walls are not acceptable. DIVISION 9 09 2000 GYPSUM BOARD ASSEMBLIES A. Drywall finish: Drywall finishing to conform to Level 5 finish in accordance with Association of Wall and Ceiling Industries (AWCI). Drywall MUST continue

More information

Carboline Fireproofing Products

Carboline Fireproofing Products Carboline Fireproofing Products Credit Contributions for Leadership in Energy and Environmental Design (LEED v2009) Carboline Company 800-848-4645 1/6/2014 Background Carboline fireproofing products can

More information

CALGREEN NON-RESIDENTIAL BUILDING Checklist

CALGREEN NON-RESIDENTIAL BUILDING Checklist CALGREEN NON-RESIDENTIAL BUILDING Checklist REVISED 11/18/14 New non-residential buildings shall be designed to include the green building mandatory measures specified in this checklist. This checklist

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Notice to Bidders

More information

Health Impacts of the Built Environment. Duane Woik, Green Building Consultant Earth Advantage Institute

Health Impacts of the Built Environment. Duane Woik, Green Building Consultant Earth Advantage Institute Health Impacts of the Built Environment Duane Woik, Green Building Consultant Earth Advantage Institute Importance of Indoor Air Quality 90% of our time is spent indoors EPA ranks IAQ as one of the top

More information

RIVER VALE BOARD OF EDUCATION PROPERTY Page 1 of Indoor Air Quality Standards 7421 INDOOR AIR QUALITY STANDARDS

RIVER VALE BOARD OF EDUCATION PROPERTY Page 1 of Indoor Air Quality Standards 7421 INDOOR AIR QUALITY STANDARDS POLICY GUIDE RIVER VALE BOARD OF EDUCATION PROPERTY Page 1 of 6 Policy and Administration 7421 INDOOR AIR QUALITY STANDARDS This notice is to inform employees that our agency complies with the Public Employees

More information

The 411 on emitting materials Designing Healthy Interiors A. Costello, P.E., LEED-AP

The 411 on emitting materials Designing Healthy Interiors A. Costello, P.E., LEED-AP The 411 on emitting materials Designing Healthy Interiors A. Costello, P.E., LEED-AP September 21, 2011 Learning Objectives 1. Understand low emitting materials (Volatile Organic Compounds) and associated

More information

Sugen Building 3 LEED-CI Pilot Project

Sugen Building 3 LEED-CI Pilot Project Sugen Building 3 LEED-CI Pilot Project Winner San Mateo County Sustainability Award 2006 SAMCEDA Award of Excellence, Environmental Action Category 2005 LEEDing Lab Completed in 2003, Sugen s Building

More information

In the design development phase, submit finish and material selections to Facilities Management Planning Group for review.

In the design development phase, submit finish and material selections to Facilities Management Planning Group for review. 09 00 00 FINISHES 09 01 00 Maintenance of Finishes 09 01 20 Maintenance of Plaster and Gypsum Board 09 01 20.91 Plaster Restoration 09 01 30 Maintenance of Tiling 09 01 30.91 Tile Restoration 09 01 50

More information

INDDOR ENVIRONMENTAL QUALITY

INDDOR ENVIRONMENTAL QUALITY INDDOR ENVIRONMENTAL QUALITY IEQ- P1: MINIMUM INDOOR AIR QUALITY PERFORMANCE To establish minimum indoor air quality (IAQ) performance to enhance indoor air quality in buildings, thus contributing to the

More information

MILETTE DOORS BIFOLD PANEL DOORS

MILETTE DOORS BIFOLD PANEL DOORS CONTRIBUTION LEED FICHE TECHNICAL TECHNIQUE DATA LEED SHEET ENTREPRISE MILETTE DOORS The Client First! Since the creation of our company in 1967, we never stopped innovating, growing and adapting ourselves

More information

A. The project is intended to achieve LEED Certification at the Silver Level per the U.S. Green Building Council LEED for Schools 2007 rating system.

A. The project is intended to achieve LEED Certification at the Silver Level per the U.S. Green Building Council LEED for Schools 2007 rating system. SECTION 23 01 01 HVAC LEED REQUIREMENTS PART 1 -GENERAL 1.1 WORK INCLUDES A. Compliance with LEED project requirements. B. Coordination of LEED construction phase activities. C. Data gathering of construction

More information

TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS

TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS AIA General Conditions... GC-1 to GC-44 Amendments to General Conditions... AM-1 to AM-2 Supplements to General Conditions... SU-1 to SU-7 00200 Instructions To Bidders... 1 3 00201 Contractor s Bidding

More information

LEED TECHNICAL DATA SHEET

LEED TECHNICAL DATA SHEET LEED TECHNICAL DATA SHEET COMPANY An innovator by means of rigorous procedures/standard and a committed team of experts, Parquets Alexandra offers hi-tech products of the highest quality. CONSISTENT, PROVEN

More information

NORTH CAROLINA ENERGY STAR CONFERENCE

NORTH CAROLINA ENERGY STAR CONFERENCE NORTH CAROLINA ENERGY STAR CONFERENCE NOVEMBER 16, 2007 ENERGY STAR INDOOR AIR PACKAGE OUTLINE What s so important about IAQ? What is the Indoor Air Package? How does it work? WHAT ARE BUILDINGS FOR? People

More information

Mold Remediation. Containment guidelines: based on the size of the infected area.

Mold Remediation. Containment guidelines: based on the size of the infected area. Mold Remediation Containment guidelines: based on the size of the infected area. Level 1 (10 sq. ft. or less): e.g. ceiling tiles, small areas on walls Moldy materials that can be cleaned should be cleaned

More information

Procedure for Department Managed Repair and Renewal Projects Under $15,000

Procedure for Department Managed Repair and Renewal Projects Under $15,000 Applies to: All Medical School Departments GUIDELINES: Issued: March 28, 2012 Revised: April 13, 2015 PURPOSE: To provide guidance to departments for repair and renewal projects with an estimated budget

More information

ADDENDUM 2 - JULY 14, 2015

ADDENDUM 2 - JULY 14, 2015 7/9/2015 The Professional(s) of Record above has signed for the following specification sections: DIVISION 1 GENERAL REQUIREMENTS Section 01 10 00 Summary of Work Section 01 25 00 Substitution Procedures

More information

Indoor Air Quality Program

Indoor Air Quality Program Indoor Air Quality Program Tabernacle Twp. School District Olson Middle School 132 New Rd. Tabernacle, NJ 08088 Tabernacle Elementary School 141 New Rd. Tabernacle, NJ 08088 Original Date: February 2,

More information

DIVISION 9 FINISHES. The Consultant shall consider the use of the space and long-term maintenance requirements in the selection of finishes

DIVISION 9 FINISHES. The Consultant shall consider the use of the space and long-term maintenance requirements in the selection of finishes DIVISION 9 FINISHES GENERAL The Consultant shall consider the use of the space and long-term maintenance requirements in the selection of finishes D.C. Building Code and National Fire Protection Association

More information

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS INDIANA UNIVERSITY BIDDING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 (REVISED 2005) MINORITY,

More information

Sustainable Design Requirements

Sustainable Design Requirements University of New Hampshire University of New Hampshire Scholars' Repository Division 01 General Requirements Chapter 5 Technical Construction and Renovation Standards 1-25-2013 018113 - Sustainable Design

More information

Sustainable Design Requirements

Sustainable Design Requirements University of New Hampshire University of New Hampshire Scholars' Repository Division 01 General Requirements Chapter 5 Technical Construction and Renovation Standards 1-25-2013 018113 - Sustainable Design

More information

toxicity/ieq: Refer to Division 09 (9) for information on resilient flooring and carpeting. Refer to Division 05 (5) for information on metals.

toxicity/ieq: Refer to Division 09 (9) for information on resilient flooring and carpeting. Refer to Division 05 (5) for information on metals. This is a guidance document with sample specification language intended to be inserted into project specifications on this subject as appropriate to the agency's environmental goals. Certain provisions,

More information

LEED v4 Technical Bulletin Building Design + Construction

LEED v4 Technical Bulletin Building Design + Construction LEED v4 Technical Bulletin Building Design + Construction Background This document outlines Carboline s contributions towards available LEED v4 credits. Carboline is committed to developing and manufacturing

More information

ARDEX GUIDE SPECIFICATION ARDEX FEATHER FINISH Self-Drying, Cement-Based Finish Underlayment

ARDEX GUIDE SPECIFICATION ARDEX FEATHER FINISH Self-Drying, Cement-Based Finish Underlayment ARDEX GUIDE SPECIFICATION ARDEX FEATHER FINISH Self-Drying, Cement-Based Finish Underlayment SECTION 03 01 30 Maintenance of Cast-In-Place Concrete PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings, general

More information

City of Millbrae 2016 CALIFORNIA GREEN BUILDING CODE CHECKLIST FOR NEW NONRESIDENTIAL BUILDINGS

City of Millbrae 2016 CALIFORNIA GREEN BUILDING CODE CHECKLIST FOR NEW NONRESIDENTIAL BUILDINGS City of Millbrae 2016 CALIFORNIA GREEN BUILDING CODE CHECKLIST FOR NEW NONRESIDENTIAL BUILDINGS Building Permit Number: Site Address: In the column labeled Specify where each Measure can be found on the

More information

VICOSTONE QUARTZ SURFACES & LEED CERTIFICATION

VICOSTONE QUARTZ SURFACES & LEED CERTIFICATION VICOSTONE QUARTZ SURFACES & LEED CERTIFICATION CONTENTS I. BACKGROUND II. VICOSTONE QUARTZ SURFACES & LEED POINTS III. VICOSTONE ENVIRONMENTAL COMMITMENT I. BACKGROUND ABOUT VICOSTONE JOINT STOCK COMPANY

More information

How We Obtained LEED Certification pertaining to the Indoor Environmental Quality Category. Ron Fields, CAFS, NCT General Dynamics C4 Systems

How We Obtained LEED Certification pertaining to the Indoor Environmental Quality Category. Ron Fields, CAFS, NCT General Dynamics C4 Systems How We Obtained LEED Certification pertaining to the Indoor Environmental Quality Category Ron Fields, CAFS, NCT General Dynamics C4 Systems Outline What is LEED EB? GD LEED Costs and savings IEQ Prerequisites

More information

LEED v4 Technical Bulletin Building Design + Construction

LEED v4 Technical Bulletin Building Design + Construction LEED v4 Technical Bulletin Building Design + Construction Background This document outlines Carboline s contributions towards available LEED v4 credits. Carboline is committed to developing and manufacturing

More information

Green Remodeling Illustrations GREEN REMODELING ILLUSTRATIONS GREEN BUILDING GUIDELINES FOR HOME REMODELING

Green Remodeling Illustrations GREEN REMODELING ILLUSTRATIONS GREEN BUILDING GUIDELINES FOR HOME REMODELING Green Remodeling Illustrations GREEN REMODELING ILLUSTRATIONS GREEN BUILDING GUIDELINES FOR HOME REMODELING WWW.STOPWASTE.ORG New Addition Consider the following green remodeling options in a new addition.

More information

SANTA MONICA PLACE 395 Santa Monica Place, Santa Monica, CA 90401

SANTA MONICA PLACE 395 Santa Monica Place, Santa Monica, CA 90401 ENVIRONMENTAL MISSION STATEMENT Macerich is committed to planning, designing, constructing and operating Santa Monica Place in an environmentally sound manner. We will implement green-building strategies

More information

Work Plan for Window Removal and Remediation Rooms: 200 Wing classrooms, Cafeteria and Kitchen Thomas Prince School Princeton, Massachusetts

Work Plan for Window Removal and Remediation Rooms: 200 Wing classrooms, Cafeteria and Kitchen Thomas Prince School Princeton, Massachusetts 1) Introduction Work Plan for Window Removal and Remediation Rooms: 200 Wing classrooms, Cafeteria and Kitchen Thomas Prince School Princeton, Massachusetts Triumvirate Environmental Inc. (TEI) shall perform

More information

SECTION RESILIENT SHEET FLOORING

SECTION RESILIENT SHEET FLOORING SECTION 09 65 16 RESILIENT SHEET FLOORING SPEC WRITER NOTE: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1.

More information

DESIGN & CONSTRUCTION GUIDELINES

DESIGN & CONSTRUCTION GUIDELINES DESIGN & CONSTRUCTION GUIDELINES EDITION: USF FACILITIES MANAGEMENT - DC 5 DCG FACILITIES MANAGEMENT DESIGN & CONSTRUCTION PHONE: (813) 974-2845 4202 E. FOWLER AVENUE, OPM 1000 TAMPA, FLORIDA 33620-7550

More information

Suggested Specification for Tri-Patch Versatile Concrete Patching Compound

Suggested Specification for Tri-Patch Versatile Concrete Patching Compound Suggested Specification for Tri-Patch Versatile Concrete Patching Compound SURFACE PREPARATION for Interior and Exterior Floor-Covering Installations. (Vinyl Composition Tiles, Sheet Vinyl, Rubber, Indoor

More information

Ger-Eck, LLC SCRIBIL Dry Erase Clear Coat Section July 12, 2013 SECTION SCRIBIL Dry Erase Clear Coat

Ger-Eck, LLC SCRIBIL Dry Erase Clear Coat Section July 12, 2013 SECTION SCRIBIL Dry Erase Clear Coat SECTION 09 96 66 SCRIBIL Dry Erase Clear Coat PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General Conditions, Division 1 - GENERAL REQUIREMENTS,

More information

AirRenew Gypsum Board Products - Frequently Asked Questions

AirRenew Gypsum Board Products - Frequently Asked Questions AirRenew Gypsum Board Products - Frequently Asked Questions What is AirRenew? AirRenew is a family of innovative gypsum board products that helps clean the air and improve indoor air quality. The gypsum

More information

MILETTE DOORS FRENCH BIFOLD DOORS

MILETTE DOORS FRENCH BIFOLD DOORS LEED FICHE TECHNICAL TECHNIQUE DATA LEED SHEET ENTREPRISE MILETTE DOORS The Client First! Since the creation of our company in 1967, we never stopped innovating, growing and adapting ourselves to the needs

More information

BACT Determination Information

BACT Determination Information Number: Permit Number: Equipment Description: Unit Size/Rating/Capacity: Equipment Location: ROCs NOx SOx PM10 PM2.5 CO LEAD 24317 Standard: Technology Description: Basis: Standard: Technology Description:

More information