SECTION UNIT MASONRY
|
|
- Vincent Walsh
- 5 years ago
- Views:
Transcription
1 SECTION UNIT MASONRY PART 1 GENERAL 1.01 SUMMARY A. Furnish labor, materials, and equipment and perform functions required in the installation and maintenance of the work covered by this Section. 1. This work includes: a. Unit masonry work. b. Angles, sleeves, anchors, inserts, and ties required to be built into masonry work RELATED SECTIONS A. Steel reinforcement: Division - 3 B. Concrete: Division - 3 C. Mortar for Engineered Masonry: Division REFERENCES A. ACI 530, Specifications for Masonry Structures B. National Concrete Masonry Association: Standard Specifications for the Design and Construction of Load Bearing Concrete Masonry, NCMA TR-75B. C. Standard Building Code, latest edition QUALITY ASSURANCE A. Allowable Tolerances: 1. Plumb: ± 1/8 inch in 5-0, non-cumulative. 2. Horizontal Warp: ± 1/8 inch in 5-0, non-cumulative. 3. Level Courses in Wall Panels: ± 1/4 inch. SLID Stormwater Treatment Area Unit Masonry
2 1.05 SUBMITTALS A. Manufacturer s product data indicating compliance with specified requirements. PART 2 PRODUCTS 2.01 MATERIALS A. Portland Cement: ASTM C150-84, Type I, white or gray, as required. B. Masonry Cement: ASTM C91-83a, Type II. C. Sand: 100 percent passing a #8 sieve, and not more than 15 percent passing a #100 sieve, ASTM C D. Water: City potable water. E. Wall Reinforcement: Truss type welded wire masonry reinforcement, every second course, 9 gauge deformed wire, minimum weight for 8 inch wall 187lbs. per 1000 lineal feet,.048 sq. in. effective cross sectional steel area sized for width of block. 1. Comply with material requirements of ASTM Standard A 82 for high tensile steel. F. Anchors: Galvanized steel, minimum 12 inch long. G. Waterproofing: SEC #1, manufactured by SEC Manufacturing Co., or equivalent approved by Architect/ENGINEER. H. Concrete Block: Hollow load-bearing blocks, ASTM C-90, Grade N, Type I, moisture content requirements as stipulated in the guide specifications of the Florida Concrete and Products Assoc., Inc., weight of concrete more than 100 lbs. per cubic foot, compressive strength minimum 2000 p. s. i., nominal 8 inches by 8 inches by 16 inches. 1. Use standard blocks specially designed for use at jambs, beams, as required. PART 3 EXECUTION 3.01 MORTAR A. ASTM C270, Type S, with compressive strength of 1800 p. s. i. at twenty-eight (28) days, except that Type M with 2500 p. s. i. shall be used for reinforced masonry, when required by code and where indicated in the Drawings. 1. Ingredients: SLID Stormwater Treatment Area Unit Masonry
3 a. Portland cement, sand, hydrated lime and water, or masonry cement, sand, and water, with waterproofing added in accordance with the manufacturer s recommendations in mortar for exterior work. B. Mix mortar with minimum amount of water for satisfactory workability, and only in quantity needed for immediate use. 1. The mason may adjust the consistency. 2. Do not use mortar after the cement has begun its initial set. 3. Re-tempering will not be permitted. C. Pointing and Cleaning: On completion, point up exposed masonry, including joints at concrete columns and beams ERECTION 1. Fill holes and joints, remove loose mortar, cut out defective joints, and re-point only where necessary. 2. Masonry surfaces which are to be exposed, either painted or unpainted, shall be thoroughly cleaned free of mortar and stains and the joints pointed to obtain a level, smooth surface. A. Protect masonry work from damage, both in appearance and structural stability. 1. When rain is imminent and the work discontinued, cover the top of exposed masonry with a strong waterproof membrane, well secured in place. 2. Replace walls damaged during construction by wind action or failure to provide adequate protection and bracing, at no expense to the OWNER. B. Lay masonry in a common running bond, with vertical joints centered over masonry units below. C. Do not step back unfinished work for joining with new work. 1. Complete the last course laid between columns or walls before interrupting the day s work. 2. Toothing may be restored to only when specifically approved by the ENGINEER. 3. Remove loose mortar before new work is started, and wet the exposed joint thoroughly before laying new work. SLID Stormwater Treatment Area Unit Masonry
4 D. Built-In metal frames, vent blocks, access doors, and anchor bolts required by other trades as the work progresses. 1. Check with other trades for these items. E. Bed each course solidly in mortar, under face shells and webs, with vertical joints, slushed full and breaking halfway over units in the course next below, unless stacked bond is specified or noted in the Drawings. 1. Terminate walls under soffits of existing beams or slab construction slightly below the soffit and fill the remaining space with mortar after roof dead loads have been brought to bear on the structure. 2. Fill cavities with mortar in walls or partitions supporting plumbing fixtures or other items, voids at door jambs, and other spaces requiring grout fill, so that anchoring devices are in a solid field not less than 8 inches in every direction from their center. 3. Reinforce exterior walls by placing wall reinforcement as indicated in the Drawings. 4. Lap reinforcing sufficiently at splices (24 inches min.) to ensure continuity. F. Where block walls abut the vertical surface of a concrete member, provide cast-in-place recessed reglets for dovetail, corrugated, galvanized, 1 inch wide by 1/8-inch thick anchors at the end of each wall reinforcement run. 1. Where new block walls abut existing or previously erected concrete or masonry walls, secure anchors to existing wall by breaking through the block or chipping a recess in concrete and filling the space with grout, to prevent horizontal movement. G. Where walls with concrete filled voids are indicated, use regular concrete with pea rock aggregate and a compressive strength of 3000 psi at twenty-eight (28) days. 1. Comply with the requirements of Division 3. H. Do not wet concrete masonry units before laying. 1. Erect masonry plumb, true to line, level, and accurately spaced, with each course breaking joints with course next below, unless a stacked pattern is indicated in the Drawings. 2. Keep bond pattern plumb throughout, and corners and reveals plumb and true. SLID Stormwater Treatment Area Unit Masonry
5 3. Use power drills and saws for penetration of plumbing and other pipes in exposed locations. 4. Fill chases and knockouts after other work is installed in them to restore the integrity of the wall. I. For Exposed Masonry Finishes 1. Do not use cracked, spalled, or chipped blocks. 2. Use extra care to set blocks plumb, with even, uniform tooled joints, and to keep mortar smears from the face of the block. 3. Set courses level and line up the face of the units to provide a flat surface without warpage or breaks at the joints. 4. Strike the excess mortar from the joints with a trowel run parallel to the joint to avoid smearing the block face. 5. Joint thickness: 3/8-inch. 6. Keep setting mortar from the face of the block and wipe excess away before it sets. a. The blocks will remain exposed and painted in the finished condition. b. Replace blocks defaced by excessive mortar smears that interfere with the uniform texture and color of the wall. END OF SECTION SLID Stormwater Treatment Area Unit Masonry
REINFORCED CONCRETE MASONRY SECTION
SECTION 04 22 02 - REINFORCED CONCRETE MASONRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 01 Specification
More informationA. Coordinate concrete unit masonry (also termed CMU and block ) work with work before and after, especially:
04222 CONCRETE UNIT MASONRY (UNREINFORCED ONLY) SPECIFIER: Use this section only for UNREINFORCED concrete masonry. Its only reinforcement is in the horizontal joints. It covers ONLY plain blockwork (no
More information1.02 STANDARD REFERENCES: The following standard specifications shall apply to the Work of this Section as indicated:
SECTION 04220 CONCRETE UNIT MASONRY PART 1 - GENERAL 1.01 SCOPE: A. The CONTRACTOR shall furnish all labor, materials and equipment necessary for the masonry construction as shown on the drawings or as
More informationSECTION UNIT MASONRY ASSEMBLIES
PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Concrete masonry units. 2. Decorative masonry units. 3. Mortar and grout. 4. Steel reinforcing bars. 5. Masonry joint reinforcement. 6. Ties and anchors.
More informationSECTION MORTAR
PART l - SCOPE SECTION 04100 - MORTAR A. This Section includes all labor, materials, equipment, and related items required for the work of mortar as shown on the Drawings and specified herein. The work
More informationParagraph Description Page No General Materials Concrete Masonry Work Altitude Valve Vault Cover 25-4
City of Columbia Engineering Regulations PART 25: SPECIFICATIONS FOR ALTITUDE VALVE VAULT Table of Contents Paragraph Description Page No. 25.1 General 25-1 25.2 Materials 25-1 25.3 Concrete Masonry Work
More informationSECTION BRICK MASONRY ASSEMBLIES
PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following: 1. Face brick. 2. Mortar and grout. 3. Ties and anchors. 4. Miscellaneous masonry accessories. 1.2 SUBMITTALS A. Product Data: For each type
More informationConditions of the Contract and Division 1 General Requirements are a part of this section.
NOTES TO SPECIFIER General notes about the specifications and the reasons for them are listed here in general statements. Use this as a guide when choosing the correct selection of statements that apply
More information04221 CONCRETE UNIT MASONRY
04221 CONCRETE UNIT MASONRY ****************************************** SPECIFIER: This section replaces 04230. It is MDCPS s more comprehensive block masonry section. It covers reinforced blockwork with
More information1. Section , Concrete Reinforcement and Embedded Assemblies. B. ACI 530/ASCE 5 - Building Code Requirements for Masonry Structures
SECTION 04 22 00 CONCRETE MASONRY UNIT PART 1 - GENERAL 1.1 SUMMARY A. Work Includes: This Section includes the furnishing and installation of concrete masonry units, reinforcing steel, miscellaneous masonry
More informationTechnical Notes 11B - Guide Specifications for Brick Masonry, Part 3 Rev [Feb. 1972] (Reissued Sept. 1988) INTRODUCTION
Technical Notes 11B - Guide Specifications for Brick Masonry, Part 3 Rev [Feb. 1972] (Reissued Sept. 1988) INTRODUCTION This Technical Notes contains the guide specifications in CSI format for Part III
More informationSECTION ARCHITECTURAL CONCRETE UNIT MASONRY
SECTION 04 2223 PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Split-face concrete unit masonry, burnished concrete unit masonry, and polished concrete unit masonry. 2. Split-face concrete unit masonry.
More informationSECTION INSTALLATION AND/OR REPLACEMENT OF MASONRY UNITS AND REPOINTING
SECTION 04210 INSTALLATION AND/OR REPLACEMENT OF MASONRY UNITS AND REPOINTING PART I GENERAL 1.1 SUMMARY A. Provide installation of new or replacement of masonry units and/or repointing of masonry units
More informationSECTION GLASS UNIT MASONRY ASSEMBLIES
PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish and install all materials, labor, equipment and incidentals required to install glass unit masonry as shown on the contract drawings and
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MORTAR AND MASONRY GROUT
SECTION 04110 MORTAR AND MASONRY GROUT PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. In the absence of other information, the methods and recommendations of the National Concrete Masonry Association
More informationDivision 04 - Masonry Section New Westminster Multi-Use Civic Facility & Office Building Project No Page 1
Project No. 210022 Page 1 1 GENERAL 1.1 REQUIREMENTS INCLUDED.1 Furnish all labour, material, services and equipment necessary for the supply, delivery and erection of concrete block masonry and reinforced
More informationSECTION PRECAST CONCRETE COVER SYSTEM
SECTION 13500 PRECAST CONCRETE COVER SYSTEM PART 1 GENERAL 1.1 SYSTEM DESCRIPTION A. Design Criteria: 1. Precast manufacturer shall be responsible for structural design of individual precast components,
More informationSECTION UNIT MASONRY
SECTION 04200 UNIT MASONRY A. ACCEPTABLE MANUFACTURERS 1. Sound Absorptive Masonry Units: 12 inch wide Soundblox type RSC/RF as manufactured by the Proudfoot Company, Monroe, CT. 2. Concrete Masonry Units:
More informationBanyan Air Service November 18, 2011 AVE Aviation and Commerce Center Building 1 Miami, FL
SECTION 04810 - UNIT MASONRY ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply to this Section.
More informationSECTION UNIT MASONRY
PART 1 GENERAL 1.01 SECTION INCLUDES A. Concrete Masonry Units. B. Mortar and Grout. C. Accessories. 1.02 RELATED REQUIREMENTS 1.03 REFERENCE STANDARDS SECTION 042000 UNIT MASONRY A. Unless otherwise noted
More informationGUIDE SPECIFICATIONS For STRUCTURAL PRECAST HOLLOW CORE SLABS SECTION 03410
GUIDE SPECIFICATIONS For STRUCTURAL PRECAST HOLLOW CORE SLABS SECTION 03410 Note to user: These guide specifications are provided by Mid- States Concrete Products as a service to you; they are NOT specific
More informationBRICKWORK 3.5 BRICKWORK 1 GENERAL
BRICKWORK 1 GENERAL 1.1 INSPECTION Notice Give sufficient notice so that inspection may be made of the following: - Set out of brickwork to lintels, arches and other architectural features. - Damp-proof
More informationPRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS
PRODUCTION SPECIFICATIONS SECTION 03135 INSULATED CONCRETE FORMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Insulated panel permanent concrete form system for: 1. Exterior structural wall panels. 2. Interior
More informationPRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS
PRODUCTION SPECIFICATIONS SECTION 03135 INSULATED CONCRETE FORMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Insulated panel permanent concrete form system for: 1. Exterior structural wall panels. 2. Interior
More informationA. Types of lightgauge metal framing units include the following: 1. C-shaped structural steel studs Uniform Building Code.
SECTION 05400 COLD-FORMED METAL FRAMING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSELECT APPROPRIATE SECTIONS FOR BELOW; DELETE OTHERS
Master Specifications 03440-1 SECTION 03440 REINFORCED AUTOCLAVED AERATED CONCRETE PANELS Date: 04-19-07 SECTION REQUIRES EDITOR TO MAKE SELECTIONS - GENERALLY SELECTIONS ARE PRECEDED BY **. SPEC EDITOR
More informationSECTION CONCRETE FORMWORK AND ACCESSORIES
SECTION 03100 CONCRETE FORMWORK AND ACCESSORIES Part 1 GENERAL 1.01 SUMMARY A. Furnish equipment, materials, and labor required for construction and removal of forms for the containment of concrete to
More informationSECTION STRUCTURAL PRECAST HOLLOW CORE SLABS
PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish all labor, materials, equipment and incidentals to provide a complete structural precast hollow core slab system as shown on the Contract
More informationSECTION UNIT MASONRY CONSTRUCTION
PART 1 GENERAL 1.01 SCOPE OF WORK A. Contractor shall furnish all labor, materials, equipment and incidentals required to provide unit masonry construction as shown and specified herein. The work shall
More informationSECTION UNIT MASONRY SYSTEM
SECTION 04320 UNIT MASONRY SYSTEM PART 1 GENERAL 1.01 SECTION INCLUDES A. Concrete masonry and face brick units. B. Reinforcement, anchorage, and accessories. 1.03 SUBMITTALS A. Submit product data under
More informationDURRELL DESIGN GROUP, PLLC ROOF REPLACEMENT BARR ELEMENTARY SCHOOL JACKSON PUBLIC SCHOOL DISTRICT JACKSON, MISSISSIPPI.
DURRELL DESIGN GROUP, PLLC 500-G E. WOODROW WILSON AVENUE JACKSON, MISSISSIPPI 39216 PHONE: 601.708.4788 FAX: 601.488.4717 ROOF REPLACEMENT BARR ELEMENTARY SCHOOL JACKSON PUBLIC SCHOOL DISTRICT JACKSON,
More informationSECTION UNIT PAVERS
PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following: 1. Concrete pavers. 2. Detectable warning pavers. 3. Warning stripe pavers. 1.2 SUBMITTALS A. Product Data: For the following: 1. Pavers.
More informationA. MASONRY MASONRY SECTION General Requirements: Division One is applicable in full hereto.
PHJN1010CU SECTION 0400 MASONRY A. MASONRY 1. General Requirements: Division One is applicable in full hereto. 2. General: Workmanship shall be first class, with horizontal courses level, vertical joints
More information0331 Brick and block construction
0331 BRICK AND BLOCK CONSTRUCTION 1 GENERAL 1.1 STANDARDS Materials and construction: To AS 4773.1 and AS 4773.2. 2 PRODUCTS 2.1 DURABILITY Exposure environment: [complete/delete] Exposure locations: To
More informationConcrete Block Machines Typical Fixed Block Machine
SEAOG 2016 Masonry Workshop Concrete Masonry Units and Terminology Concrete Masonry in Georgia Georgia World Congress Center Reference: Inspector s Handbook Masonry Institute of America Roy Keck, FACI
More informationStone and Masonry Veneer
Stone and Masonry Veneer R703.7 Stone and masonry veneer, general. Stone and masonry veneer shall be installed in accordance with this chapter, Table R703.4 and Figure R703.7. These veneers installed over
More informationDIVISION 03 CONCRETE SPECIFICATION : FORMS AND FORMWORK
DIVISION 03 CONCRETE SPECIFICATION 031000: FORMS AND FORMWORK PART 1.0 GENERAL 1.1 DESCRIPTION The work of this specification includes furnishing of all labor, materials, equipment and incidentals to install,
More informationSECTION Specification for Building Limes Specification For Building Sands from Natural Sources Methods of Tests for Paints.
SECTION 09200 PART 1 - GENERAL 1.01 DESCRIPTION A. Extent of Work: The extent of lath and plaster work is shown on the drawings and in schedules and includes interior and exterior plaster work, and fibreglass
More information2002 Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine TEL: ; FAX: ; WEBSITE:
SECTION 07651 FLEXIBLE COPPER SHEET FLASHINGS Advanced Building Products, Inc. manufacturer many types of flexible copper sheet flashings. Due to their ductility, high tensile strength, and resistance
More informationSPECIFICATIONS MODERRA MORTARLESS MASONRY VENEER
SPECIFICATIONS MODERRA MORTARLESS MASONRY VENEER PART 1: GENERAL 1.01 Section Includes A. Product description and definitions. B. Constructing base ledge for concrete wall units. C. Installing modular
More informationINSULATED CONCRETE MASONRY UNITS Section 04220
INSULATED CONCRETE MASONRY UNITS Section 04220 PART 1 GENERAL 1.01 Summary A. Section Includes 1. Insulated masonry wall units (CMU's) 2. Decorative insulated masonry wall units 1.02 SUBMITTALS A. Samples:
More informationEditing notes to assist users are separated from specification text by rows of asterisks. Delete these notes prior to final printing.
SECTION 09635 LIMESTONE FLOORING This guide specification has been prepared by TexaStone Quarries LLC to assist design professionals in the preparation of a specification section covering cut limestone
More informationSECTION PRECAST CONCRETE MANHOLES
SECTION 02601 PRECAST CONCRETE MANHOLES PART 1 GENERAL 1.1 The work specified in this section shall include the furnishing, hauling, and placing of all precast manholes shown on the drawings and as specified
More informationSECTION ALUMINUM HANDRAIL SYSTEMS
SECTION 05520 ALUMINUM HANDRAIL SYSTEMS PART 1 - GENERAL 1.01 SUMMARY A. Section includes aluminum handrails and railings. B. Related Work: 1. Section 03300 - Cast-in-Place Concrete C. References: 1. American
More informationThe following specification refers to the Stepstone, Inc. product known as: Steptreads
The following specification refers to the Stepstone, Inc. product known as: Steptreads If you need any additional information please call Stepstone, Inc. at 800-572-9029 or visit our website www.stepstoneinc.com
More informationSpec Master 5/7/ For each product requiring color and texture selection, provide full size samples.
SECTION 04812 (042012) MECHANICALLY ATTACHED BRICK PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-04 21 26 (November 2009) ----------------------------- Preparing Activity: USACE Superseding UFGS-04 21 26 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS References
More informationUnit Masonry
04 00 00 Unit Masonry This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 092216 - NON-STRUCTURAL METAL FRAMING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION CAST-IN-PLACE CONCRETE
SECTION 03300 CAST-IN-PLACE CONCRETE PART 1 GENERAL 1.01 SECTION INCLUDES A. The Contractor shall furnish all work and materials, including cement, sand and coarse aggregate, water, admixtures, curing
More informationSECTION BRICKWORK PART I GENERAL
SECTION 04210 BRICKWORK PART I GENERAL 101 Scope General: supply and build the brickwork shown on the drawings or needed to complete the brickwork, including but not limited to the following: Provide all
More informationSECTION BRICKWORK
SECTION 04210 BRICKWORK THERE ARE NOTES AND CLAUSES IN THE SUSTAINABILITY GUIDE ON THIS TRADE. THIS TRADE SECTION DEPENDS ON COORDINATION BETWEEN THIS SPECIFICATION AND THE FINISHES SCHEDULE AS WELL AS
More informationMaster Specifications for Microcotta November 2017
SECTION 042130 - MICROCOTTA PART 1 - GENERAL 1.1 SUMMARY A. Provide Architectural Microcotta, cast architectural polymer resin units manufactured in accordance with the Contract Documents. 1.2 WORK INCLUDED
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-04 23 00 (November 2009) ----------------------------- Preparing Activity: USACE Nontechnical Title Revision (August 2015) UNIFIED FACILITIES GUIDE SPECIFICATIONS References
More information1 Exam Prep Concrete Masonry Handbook Questions and Answers
1 Exam Prep Concrete Masonry Handbook Questions and Answers 1. According to Concrete Masonry Handbook, a masonry unit is considered as normal weight if it has a density or unit weight of more than pounds
More informationSECTION CONCRETE UNIT MASONRY. A. Section Includes: Concrete unit masonry construction as shown on Drawings and as specified.
SECTION 04220 CONCRETE UNIT MASONRY PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Concrete unit masonry construction as shown on Drawings and as specified. 1.02 SYSTEM DESCRIPTION A. Performance Requirements:
More information104 References Comply with applicable portions of current editions of the following Australian Standards:
SECTION 04210 BRICKWORK THERE ARE NOTES AND CLAUSES IN THE SUSTAINABILITY GUIDE ON THIS TRADE. THIS TRADE SECTION DEPENDS ON COORDINATION BETWEEN THIS SPECIFICATION AND THE FINISHES SCHEDULE AS WELL AS
More informationSECTION PAVER TILE
SECTION 09340 PAVER TILE PART 1 - GENERAL 1.01 DESCRIPTION: A. This section specifies providing paver tiles, typically in patron areas as shown. These tiles are noted on Drawings as: 1. Paver tile. 2.
More informationDIVISION 5 - STRUCTURAL STEEL AND IRON WORK
DIVISION 5 - STRUCTURAL STEEL AND IRON WORK SECTION 05100 STRUCTURAL METAL FRAMING PART 1.00 GENERAL 1.01 SCOPE OF WORK A. Work Included: 1. 2. Structural steel complete in place. Steel joists complete
More informationA. JANDRIS & SONS Guide Specifications in CSI Format SECTION CONCRETE UNIT MASONRY
SECTION 042200 PART 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Work Included: Provide labor, materials and equipment necessary to complete the work of this Section, including but not limited to the following:
More informationICBO Evaluation Service, Inc Workman Mill Road, Whittier, California
Reissued June 1, 2002 ICBO Evaluation Service, Inc. 5360 Workman Mill Road, Whittier, California 90601 www.icboes.org Filing Category: DESIGN Concrete DURISOL WALL FORMS FOR CONCRETE CONSTRUCTION DURISOL
More informationSECTION BRICK FLOORING
SECTION 09 63 13 BRICK FLOORING SPEC WRITER NOTE: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Brick flooring
More informationSECTION ARCHITECTURAL PRECAST CONCRETE. C. Section Joint Sealers: Perimeter joints with sealant and backing.
SECTION 03451 ARCHITECTURAL PRECAST CONCRETE PART 1 GENERAL 1.01 SECTION INCLUDES A. Architectural precast concrete wall panels; with integral insulation. B. Supports, anchors, and attachments. C. Intermediate
More informationA. Section includes cast-in-place concrete, including reinforcement, concrete materials, mixture design, placement procedures, and finishes.
SECTION 033053 - CONCRETE PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSECTION EMBEDDED CMU/SPLIT FACE ARCHITECTURAL PRECAST/SITECAST CONCRETE. A. Site Cast or Tilt-Up CMU/Split Face Concrete Panels.
SECTION 03460 EMBEDDED CMU/SPLIT FACE ARCHITECTURAL PRECAST/SITECAST CONCRETE PART 1 GENERAL 1.1 SECTION INCLUDES A. Site Cast or Tilt-Up CMU/Split Face Concrete Panels. B. Shop/Plant Cast CMU/Split Face
More informationSECTION STEEL DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS
SECTION 08110 - STEEL DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General, Supplementary, and Special Conditions and Division 1 Specification
More informationTable 3. Detailed Comparison of Structural Provisions of IRC 2000 and 1997 NEHRP (Continued)
2000 IRC 1997 NEHRP Section Provision Section Provision Comments CHAPTER 3 BUILDING PLANNING R301 DESIGN CRITERIA R301.2.2 Seismic Provisions R301.2.2.1 Determination of Seismic Design Category R301.2.2.1.1
More informationSECTION Vitrified Clay Wall Coping 2014
SECTION 04220 2014 PART 1 GENERAL 1.1 DESCRIPTION A. SCOPE OF WORK 1. Provide new coping as indicated on Drawings. B. RELATED SECTIONS 1. Section 02050: Selective Demolition. 2. Section 07650: Metal Flashing.
More informationSECTION STORM DRAINAGE
SECTION 02720 STORM DRAINAGE PART 1 - GENERAL 1.01 WORK INCLUDED A. Trenching and other excavation. B. Ground water control. C. Pipe bedding. D. Installation of storm drains and appurtenances. E. Installation
More informationSECTION INSULATED CONCRETE FORMS - RASTRA 1.01 SUMMARY
SECTION 03135 INSULATED CONCRETE FORMS - RASTRA PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Insulated concrete forms for: NOTE TO SPECIFIER: Edit the following list as applicable to project requirements.
More informationDIVISION 04 MASONRY. Section Title Number MASONRY Maintenance of Masonry Masonry Mortaring Masonry Accessories
04 00 00 MASONRY 04 01 00 Maintenance of Masonry 04 01 20 Maintenance of Masonry 04 05 13 Masonry Mortaring 04 05 23 Masonry Accessories 04 20 00 UNIT MASONRY 04 21 00 Clay Unit and Brick Veneer 04 22
More informationSECTION CONCRETE PAVING
SECTION 32 13 13 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section describes the requirements for providing portland cement concrete work and all other incidental concrete improvements for the project
More informationSECTION WOOD FRAMING. A. Includes But Not Limited To 1. Furnish and install wood framing and blocking as described in Contract Documents.
SECTION 06110 WOOD FRAMING PART 1 GENERAL 1.1 SUMMARY A. Includes But Not Limited To 1. Furnish and install wood framing and blocking as described in Contract Documents. B. Products Installed But Not Supplied
More informationCity of Mesquite General Design Standards Revision Date:
SCREENING WALLS (Public and Private) Page 1 of 6 Section 1 General Design & Notes 1.1 Standards 1.1.1 All screening walls in the City of Mesquite and within its Extraterritorial Jurisdiction (ETJ), both
More informationSECTION PRE-ENGINEERED COLD-FORMED METAL ROOF AND FLOOR TRUSSES
SECTION 05440- PRE-ENGINEERED COLD-FORMED METAL ROOF AND FLOOR TRUSSES PART 1 GENERAL 1.01 SUMMARY A. Section includes pre-engineered, pre-fabricated cold formed steel framing elements. Work includes:
More informationSECTION 2831 ITEM F-162 CHAIN-LINK FENCES
SECTION 2831 ITEM F-162 CHAIN-LINK FENCES PART 1 - GENERAL 1.1 DESCRIPTION. This item shall consist of furnishing and erecting a chain-link fence in accordance with these specifications and the details
More informationTechnical Notes 24G - The Contemporary Bearing Wall - Detailing [Dec. 1968] (Reissued Feb. 1987) INTRODUCTION
Technical Notes 24G - The Contemporary Bearing Wall - Detailing [Dec. 1968] (Reissued Feb. 1987) INTRODUCTION The selection of a wall type and appropriate connection details is one of the most important
More information***************************************************************************************************************
03410 STRUCTURAL PRECAST CONCRETE *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 03 41 00 ***************************************************************************************************************
More informationSECTION NON-STRUCTURAL METAL FRAMING
SECTION 09 22 16 PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories
More informationSECTION TILT-UP PRECAST CONCRETE SANDWICH PANELS. A. Work includes, but is not limited to, the following:
PART 1 GENERAL 1.01 SUMMARY SECTION 03460 TILT-UP PRECAST CONCRETE SANDWICH PANELS A. Work includes, but is not limited to, the following: 1. Architectural precast concrete sandwich wall panels. 2. Integral
More informationMOUNTAIN STONE Products
MOUNTAIN STONE Products PRODUCT USERS GUIDE Mountain Stone Products P.O. Box 20308 42102 4301 Industrial Road Bowling Green, KY. 42101 (270) 796-6123 (270) 796-6131 (800) 781-0277 Local Fax Nationwide
More informationProposed Modification to the Florida Building Code
Proposed Modification to the Florida Building Code Name: Joseph D. Belcher Address: 41 Oak Village Blvd. Homosassa, Fl 34446 E-mail: Joe@jdbcodeservices.com Phone: 352-450-2631 FAX: (813) 925-4152 Fax:
More informationSTRUCTURAL PRECAST CONCRETE
SECTION 03410 STRUCTURAL PRECAST CONCRETE PART 1 GENERAL 1.01 SUMMARY A. Provide labor, materials, necessary equipment, services and included, but not limited to, related work to complete the structural
More informationSECTION CAST-IN-PLACE CONCRETE
McClellan Blakemore Architects New Warehouse Facility for SECTION 03300 CAST-IN-PLACE CONCRETE PART 1 GENERAL 1.01 SECTION INCLUDES A. Concrete formwork. B. Floors and slabs on grade. C. Concrete floor
More information.2 Provide for compartments in long cavity wall and at corners to achieve appropriate pressure equalization and drainage in cavity wall design.
City of Winnipeg Water Treatment Program Section 04051 Construction of Offices and Plant Interior Finishes Page 1 of 4 MASONRY PROCEDURES 1. GENERAL 1.1 Quality Control.1 Conform to requirements of CSA
More informationDesign and Construction Standards SECTION REINFORCED UNIT MASONRY
SECTION 04810 REINFORCED UNIT MASONRY PART 1 GENERAL 1.1 SECTION INCLUDES: A. Concrete masonry or brick units B. Reinforcement, anchorage, and accessories C. Parged masonry surfaces 1.2 REFERENCES A. ACI
More informationProduct Guide Specification
Product Guide Specification SECTION 04850 (04 40 00) NATURAL THIN VENEER STONE PART 1 GENERAL 1.1 SECTION INCLUDES Specifier Notes: Edit the following as required. A. Natural thin veneer stone for [exterior]
More information***************************************************************************************************************
03100 CONCRETE FORMWORK *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 03 11 00 ***************************************************************************************************************
More informationSECTION COLD-FORMED METAL FRAMING
SECTION 05 40 00 COLD-FORMED METAL FRAMING SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the
More informationDIVISION 5 METALS SECTION COLD-FORMED METAL FRAMING
DIVISION 5 METALS SECTION 05 40 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More information1.5-Hour Fire Rating. Assembly Information
1.5-Hour Fire Rating 6 C.M.U. Assembly Information 1. Preferred product 910350 c.m.u. 6" x 8" x 16" nominal 2. Portland cement stucco - 1/2" thick applied directly to C.M.U. 3. ASTM C-270 Masonry Mortar,
More informationUNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:
SECTION 321610 - CURBING PART 1 - GENERAL 1.1 DESCRIPTION A. This Section specifies requirements for furnishing and installing all types of curbing including the following: granite curb, concrete and bituminous
More informationPulaski County, Virginia
Pulaski County, Virginia Typical Retaining Wall Details Based on the 2009 International Residential Code CONTENTS Timber Retaining Wall... 2 General Requirements... 2 Wall Construction... 2 Deadmen...
More informationHOTEL SPECIFICATION SECTION 08100
Part 1 General HOTEL SPECIFICATION SECTION 08100 1.01 Work Included A. The work under this section shall include the furnishing of all items shown on the drawings and as specified including, but not limited
More informationBYU CITY FIRE STATION
SECTION 04810 - UNIT MASONRY ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION ARCHITECTURAL PRECAST CONCRETE. A. American Society for Testing and Materials (ASTM):
SECTION 03450 ARCHITECTURAL PRECAST CONCRETE PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 03100 - Concrete Formwork 2. 03200 - Concrete Reinforcement 3. 03300 - Cast-in-Place Concrete 4. 03600 -
More informationITEM 431 PNEUMATICALLY PLACED CONCRETE. All material shall conform to the pertinent requirements of the following items:
ITEM 431 PNEUMATICALLY PLACED CONCRETE 431.1. Description. This Item shall govern for furnishing and placing of "Pneumatically Placed Concrete" for encasement of designated structural steel members, the
More informationSECTION COLD-FORMED METAL FRAMING
The Collective Voice of America s Steel Framing Industry The Steel Framing Industry Association (SFIA) is dedicated to expanding the market for cold-formed steel in construction through programs and initiatives
More informationSECTION SPLIT FACE CONCRETE MASONRY UNITS
SECTION 04223 SPLIT FACE CONCRETE MASONRY UNITS ***** E. Dillon & Company manufactures the following high quality, custom produced, architectural concrete masonry units (CMU) using superior colored aggregates
More information