1 EIFS Inspection Report Property Address: 417 Palace Cir. Trussville, AL Inspection ordered by: Joshua Bollinger PH: (205) (866) FA: (205) Southland Drive, Ste. 134, Hoover, AL Produced Using ReportMakerPro Copyright
2 I. INTRODUCTION 1.1 PURPOSE: Enclosed is your Stucco Inspection. The purpose of this moisture inspection is to help assess the condition of the stucco system by looking for visible installation flaws, inadequate water diversion and sealant failures and conduct random moisture readings using electronic moisture scan devices. Please note that the provision of a scope of work for remedial repairs is not the purpose of this inspection. Further investigation may be needed to determine the extent of water damage, if any, and how best to modify your home to address any moisture problems that may be indicated by this inspection. 1.2 SCOPE OF INSPECTION: This is a basic, stucco inspection limited to the following: A visual examination of the condition of the stucco, exterior sealants, flashing, windows, doors, roof-to-stucco transitions, parapets, gutters, deck-to-building connections, stucco terminations and any penetrations through the stucco. Conducting of random electronic moisture scanning of the building envelope. Preparing a report of our observations of potential problem areas and recording any high readings found. Providing detailed information on typical moisture-related problems in stucco homes to assist you in maintaining the value of your home. 1.3 LIMITATIONS OF LIABILITY: Because this is a limited inspection, we can make no guarantee, express or implied, that our observations and random moisture readings offer conclusive evidence that no installation or moisture problems exist, or that problems found are all-inclusive. This inspection company, its employees and any divisions shall not be liable for non-visual defects, unseen defects, unspecified defects or hidden damage and conditions existing on the subject property and hereby disclaims any liability or responsibility thereof. All parties concerned agree to hold harmless and indemnify this inspection company involving any liabilities that may result. Any disputes arising from this report are limited to the party that ordered the EIFS/Stucco inspection. Acceptance of this report by party validates their agreement with the contents contained in this report. Party agrees to waive their rights to a jury trial and agrees to abide by binding arbitration by the laws of the State of Alabama. All fees involving arbitration will be paid by the party ordering the report. 1.4 FURTHER TESTING / INVESTIGATION: Our policy is to rely on moisture meter readings as an indicator of relative moisture values between different test spots, not as an absolute value of water content in the substrate. It is difficult to determine if the structural wood of your home has been damaged in areas of high readings without 'probing' and/or removing a core sample of the stucco to allow for visual inspection. Should we feel that further investigation is needed this will be indicated in the summary section of the report. 1.5 REPAIR FOLLOW-UP AND ANNUAL INSPECTIONS: A repair follow-up inspection should be conducted within three months after completion of the repairs to assess the effectiveness of the moisture modifications. This is extremely important. Annual inspections should also be scheduled to ensure that your stucco system remains dry. This way any sealant failures, stucco cracks, etc. can be caught and repaired promptly. Testing and maintaining your home on a regular basis is the best way to prevent costly repairs associated with moisture damage. Also, should you decide to sell your home, annual inspections and maintenance documentation will be a valuable selling tool, providing evidence to show that your home has been inspected and maintained on a regular basis by a reputable and qualified firm. Page 1 of 14
3 Project Information OWNER INFORMATION HOME INFORMATION Owners Builder Property Address 417 Palace Cir Builder's Address Property City Trussville, AL City, State, ZIP Phone Owners Realtor Realty Company Phone FA Phone EIFS Applicator Applicator's Address Phone FA PROPERTY INFORMATION INSPECTION INFORMATION Type of Exterior EIFS Date of Inspection 7/1/2013 Substrate (if known) OSB/plywood Last rainfall W/in last week Age of Property 20 yrs Temp. & Humidity 84º & 45% humidity EIFS Square Footage 8,000 sq ft Weather Conditions Partly Cloudy Stories 2 Inspector Chuck Marion Type of Windows Wood AL. Licenses HI-#2083; EIFS- #41 Inspection Test Equipment Test Equipment Description Test Range Setting Low Medium High A Tramex Interior Encounter B Tramex Exterior Wet Wall Detector C Delmorst Probe Meter D Structural Resistance Tester (SRT) >44 = Pass <44 = Fail Higher is better Important Note: The test equipment is used to help locate problem areas. It must be understood that the test equipment is not an exact science but rather good tools used as indicators of possible problems. At times, because of hidden construction within the wall cavity, the meters get false readings or no readings at all. Some meters will pick up on metals, wiring, unique wall finishes, etc. Positive readings do not always mean there is a problem, nor do negative readings necessarily mean there is not a problem. We do not use the equipment to obtain exact moisture content, but rather to obtain relative readings between suspected problem areas and non problem areas. This information is then used to help determine potential problem areas which may warrant more investigation. Page 2 of 14
4 General Observation Checklist Item Description Yes No Improper Comments Sealants at window perimeters Existing sealants have failed and need replacing Mitre joints (bottom corners) of windows Suggest sealing the inside bottom corners of windows Alarm Sensor Penetrations at Window Sill Fixed window units and mullion joints Head flashing at top of windows Sealants around door perimeter Sealants at door threshold details Penetrations thru door threshold / tracks Head flashing at top of doors Penetrations through stucco sealed General appearance Cracking evident Expansion joints / Control joints Exposed mesh Impact damage Rusting aggregates Flat horizontal surfaces Delamination / Fasteners Terminations and Vinyl accessories Transition joints (stucco to brick, etc.) Termination below grade (ground level) Termination below or at slab levels Deck flashing Flashing at columns Any alarm sensors installed thru window bottoms-- seal properly Suggest to wet-glaze fixed units and mullion joints Some not checked--seal all as needed Head flashing not properly insalled All penetrations through EIFS should be properly sealed Fair general appearance Some cracking evident Some areas lack proper joints Few areas noted where mesh is visible through finish Few areas of small impact damage noted Bands have flat surfaces--suggest coating all with elastomeric Bottom edge of foam not sealed properly. Seal EIFS at slab grade. No visible deck flashing. Kick-out flashing Roof soffit terminations into stucco Missing kick out flashing. Page 3 of 14
5 Cut bushes away from home. Cut bushes away from home. EIFS sealed to stone. Seal EIFS at slab grade. Kick-out flashing. <10% under Seal all lamp penetrations. Grid Location F4 Observations Left Right Soft Substrate Test Equip. F6 Door Test G Tramex C5 NR Page 4 of 14
6 Front Elevation Detail Photos Door is sealed. Widow is sealed. Compression wrinkle. Re-seal expansion joint. Seal a slab grade. Window sash and sill are Repair window rot and seal. Window is loosing gas. Install missing kick out diverter flashing. EIFS terminates above grade. Seal all hose bib penetrations. Seal bottom edge of foam prope Page 5 of 14
7 Seal all downspout penetrations. Seal EIFS at slab grade. Repair EIFS crack properly. Repair and seal door jamb. Seal garage door head flashing Grid Location F7 G7 H7 F5 G5 Observations Garage Door Test Door Test Garage Door Test Left Right Soft Substrate Test Equip. Page 6 of 14
8 Right Elevation Detail Photos Repair EIFS crack properly. Repair EIFS crack properly. Seal all hose bib penetrations. Repair bird damage. Electrical panels have been sealed. Seal all penetrations to EIFS. Page 7 of 14
9 EIFS terminates at grade. Repair all bird damage. Repair all bird damage. Penetration has been sealed. No visible proper deck fla Grid Location E4 Door Test Observations Left Right Soft Substrate Test Equip. <10 <10 Delmhorst F4 Door Test G4 Page 8 of 14
10 Rear Elevation Detail Photos Repair all soft wood on windows and seal. Window has head flashing. Repair soft wood and seal. Repair damage to EIFS. Repair bird damage and seal windows. Repair window sill and seal. Repair soft wood on window Repair damage to EIFS. Repair all bird damage. Seal all lamp penetrations. Repair window sill. No visible deck flashing. Repair/seal EIFS at deck door. Page 9 of 14
11 Staining on side of chimney. Install missing kick out diverter flashing. Re-seal expansion joint. Install diverter flashing. Remove vine from downspout. Grid Location E4 Observations Left NR Right Soft Substrate Test Equip. D6 E6 Page 10 of 14
12 Left Elevation Detail Photos Seal windows. Install diverter flashing. Cut bushes away from home. Seal all attachments to EIFS. Page 11 of 14
13 EIFS Inspection Summary Overview: This residence is a two story residence clad with E.I.F.S. (Exterior Insulated Finish System). Random exteri moisture scans showed normal readings through-out most of the residence with a several areas registering above average on the Delmhorst moisture meter. Any specially noted areas and those that register above 30% should have a core sample taken to determine if substrate has wood rot or system failure. If substrate rot exists, replace with new framing and install new EIFS system. Windows & Doors: All of the doors, windows & penetrations should be properly sealed. There are several factors that generally can contribute to problems below windows. We suggest that all of the improperly sealed windows / doors and penetrations through the EIFS be professionally resealed using a quality sealant such as 'Dow Corning' and that adequate sealant be used to give long lasting protection. The 'miter' joint of the window casings track along with casing to casing joints and mullion joints of double window units and all elements of the fixed units should to be wet glazed. We als suggest that all alarm penetrations through the window sills be sealed (if any). Any cracks through the band should also be sealed. These areas should be rechecked and scanned 3-6 months after the new sealant work i completed. Repair all wood rot on windows and seal to EIFS. Deck Flashing: Repair deck flashing and remediate all damaged EIFS below deck. Penetrations: Seal all penetrations to the EIFS per manufacturers specifications. Damaged EIFS: Repair all woodpecker holes and damage to EIFS per manufacturers specifications. Chuck Marion EDI-AL # 41 Page 12 of 14
14 About Us We have 20 + years of Residential Inspection & Remodeling experience and outstanding customer service in Central Alabama. We ser home owners, home builders, general contractors, insurance companies, interior decorators and real estate agents using professiona craftsmanship and quality materials. Contact us today! We are happy to answer your questions and provide free estimates for both large and small residential and light commercial construction projects. When you need residential remodeling or construction service you will want our expertise on your side. From start to finish, you will find our residential remodeling services professional and affordable. Alabama Licensed Home Builder Alabama Licensed Home Inspector Alabama Licensed EIFS Inspector Certified Mold Inspector & Remediator Alabama Certified Asbestos Inspector Alabama Licensed G.C. Subcontractor Alabama Licensed Real Estate Broker General Liability Insurance Workman s Comp. Insurance QUALITY & PERFORMANCE From minor alterations, to large, complex build outs, and high end residential projects, Specialty Building Contractors has the necess skills to complete your project in a timely, affordable and efficient manner. We have the knowledge, craftsmen, and subcontractor resources to provide a supreme level of quality. Any construction project, no matter how small, represents a significant owner investment. Every client should enjoy a completed project with their expectations met or exceeded. Specialty Building Consultants prides itself on service, quality and performance. We start the project when we say we will and are devoted to stay on task until it is finished and you, the customer are satisfied. We are committed to providing necessary resources to complete the project on time and within budget. Consistent communication is key to the process. We return our clients telephone ca promptly and keep the lines of communication open. Specialty Building Consultants partners with customers and subcontractors from the beginning to ensure their timelines and budgets are met. We provide competitive pricing on projects of various types and sizes. If a client has a budget to meet, we will endeavor to provide alternatives and recommendations to reduce cost and stay within the budget. OUR COMMITMENT Specialty Building Consultants primary concerns are customer service, quality and integrity comes first. Customer satisfaction is our number one priority. Request a FREE written estimate today. Our mission is to provide dependable, high quality service to all our customers. We work hard to meet this commitment so that the true value & potential of each finished project is reached. When it comes to customer service, no one is better than Specialty Buildin Contractors. We demand nothing but the best from ourselves and employees so that it shows in all of our completed projects. We ta pride in our work. And you will, too. You can count on us for dependable, professional and affordable service. When you need contract maintenance, construction, remodeling or repairs, you will want Specialty Building Consultants on your team. Page 13 of 14
15 Qualifications 1,500+ EIFS/Stucco/Home inspections completed 25 years experience in residential & commercial construction. Certified by (EDI) Exterior Design Institute Member No. AL 41 Certified by Exterior Design Institute and Warranty Corporation to inspect Exterior Insulation and Finish Systems (EIFS) and Hard Coat stucco, architectural stone, vinyl siding, fiber cement cladding, and asphalt shingle roof for proper installation during construction and moisture intrusion problems on existing structures Certified MWC Free Certified Roof Inspector State of Alabama Certified Lead Inspector & Remediator. State of Alabama Certified Asbestos Inspector. State of Alabama Home Builders License #8829 State of Alabama Home Inspector License #HI 2083 State of Alabama EIFS/Stucco License #EIFS 0878 State of Alabama G.C. Subcontractor License #S State of Alabama Real Estate Broker License #64273 B.A. University of Alabama 1985 Page 14 of 14
Stucco Moisture Inspection Report
Website:www.ibgoodinspector.com E-Mail:support@ibgoodinspector.com January 11, 2006 Stucco Moisture Inspection Report Property Address 123 Our Street OurTown, USA 12345 Report Ordered By: Mr. & Mrs. Client
More informationStucco Inspection Report
Website:www.moistureconsultantsinc.com E-Mail:support@moistureconsultantsinc.com March 14, 2007 Stucco Inspection Report Property Address 5605 Village Lake Dr. Pace FL. 32571 Report Ordered By: Ken Dezarn
More informationSAMPLE REPORT Location:
Stucco Check Inspections, LLC Invasive Stucco Inspection Prepared for: SAMPLE REPORT Location: Sample Houston, TX PHONE: 713.319.5751 EMAIL: Info@stuccocheck.com I. INTRODUCTION 1.1 PURPOSE: Enclosed is
More informationStucco Moisture Testing Report
Stucco Moisture Testing Report 0 Property Address: ABC St. Anywhere, LA Ordered by: Seller or Purchaser Inspection Connection, Egret St., Covington, LA 0 Bus: 9-- Cell: (9) - Email: chrissavoie@bellsouth.net
More informationMoisture Survey Inspection Report
Moisture Survey Inspection Report Date of Inspection: January 1, 2017 For the property located at: 123 Pleasant Lane Pleasantville, Washington, 98999 Report prepared for: John and Jane Doe Professional
More informationMoisture Free Inspection Report
Moisture Free Inspection Report For the Property Located At: 123 Our Street ThisTown, USA 12345 Report Prepared For: Mr. & Mrs. Client 4255 Old Danielsville Rd.,Athens, GA 30601 PH: 706-248-3596 : HomeandStuccoInspectionsofGa.com
More informationINSPECTION TYPE EIFS system, Visual, Tramex & Delmhorst probe moisture readings
FINEGAN INSPECTION SERVICES, INC. 27 Laurelwood Drive Milford Ohio, 45150 513 683-0733 RESIDENCE LOCATION INSPECTION TYPE EIFS system, Visual, Tramex & Delmhorst probe moisture readings OVERVIEW The report
More informationHedderman Stucco. A Division of Hedderman Engineering Inc. Phone:
Hedderman Stucco A Division of Hedderman Engineering Inc. www.heddermanengineering.com Email:office@heddermanengineering.com Phone: 281-355-9944 Prepared For: CLIENT NAME Address: PROPERTY ADDRESS Produced
More informationFor The Home Of: Mr. & Mrs. Sam A. Sample 123 Main Street Our Town, USA 12345
For The Home Of: Mr. & Mrs. 123 Main Street Our Town, USA 12345 Project Information PROPERTY INFORMATION INSPECTION INFORMATION Owners Mr. Owner Rust ID Number 12345678 Property Address Claims Form ID
More informationMOISTUREFREE WARRANTY INSPECTION PROTOCOL
MOISTUREFREE WARRANTY INSPECTION PROTOCOL MODIFIED 6/8/2006 Introduction In order to qualify for a MoistureFree Warranty, a moisture inspection must be performed on the property following the guidelines
More informationEXTERIOR INSULATION & FINISH SYSTEMS PRELIMINARY INFORMATION
EXTERIOR INSULATION & FINISH SYSTEMS PRELIMINARY INFORMATION Style of Structure: Two Story. Estimate age of Structure: The house is 5-10 years old. Foundation: Utility Basement. Finished into living space
More informationStucco Moisture Report
Stucco Moisture Report For the Property Located At: 401 Woodale Drive Kennett Square Pa. 19348 Report Prepared For: Mr.Patrick Duffy ADVANCED STUCCO SYSTEMS INC. Phone Number 484-894 - 9665 www.stuccorepairswaterproofingcom.com
More informationStucco Moisture Testing Report
Stucco Moisture Testing Report For the Property Located At: 225 Hockessin Circle Hockessin Delaware Report Prepared For: Brian Burgess Hillendale Road, Avondale Pa. 19311 Ph: 484-894-9665 Fax: Website:
More informationChapter 2 Understanding The Problem
Chapter 2 Understanding The Problem What Causes Most Of The Problems With Stucco? EIFS was originally intended to seal and insulate the exterior of the home from the elements. Problems occur when poorly
More informationPrimary Concerns and Defects
Primary Concerns and Defects Primary Concerns and Defects: Home Inspector Observations: Where to Look. What to Look For. What Observed condition may mean. Primary Concerns The points to be inspected per
More informationLimited Leak Assessment
Website:www.moistureconsultantsinc.com E-Mail:support@moistureconsultantsinc.com December 2th, 2005 Limited Leak Assessment Property Address US Naval Facility Building 484 Panama City Beach, Florida Report
More informationSenturion TM I Wall System
Senturion TM I Wall System TYPICAL DETAILS 1017662 1. Senturion I Wall System Application (Plan VIew) 2. Senturion I Wall System Application (Isometric View) 3. Aesthetic Groove (Plan View) 4. Insulation
More informationSenturion TM III Wall System
Senturion TM III Wall System TYPICAL DETAILS 1017666 1. Senturion III Wall System Application (Plan VIew) 2. Senturion III Wall System Application (Isometric View) 3. Aesthetic Groove (Plan VIew) 4. Insulation
More informationAccent is cracked with stains Accent is sloped away from the home Flat accent is not sealed to window
Glossary of Terms Accent Bands/Trim Bands An accent band is decorative stucco trim constructed over a wood or EIFS foam attachment. Trim bands are decorative bands constructed of wood or other material.
More information2019 IAQA Annual Meeting
Daniel Stih, CMC. CIEC Healthy Living Spaces Stanley Yeskolski CIEC, CMC Investigative Inspection Services Inc. 2 Purpose The presentation will provide a over view of: Installation Details Problem Areas
More informationStucco Moisture Inspection Report Prepared For: Mr. & Mrs. Kevin Abrahams. Providing Peace of Mind One home at a time Since 1989
Real Estate Inspections Infrared Thermography Stucco Inspections Diagnostic Inspections and more INSPECTION GROUP FIG Services LLC d/b/a FOX INSPECTION GROUP Property Inspection Report # 130416JMsi 11227
More informationPROPERTY PRESERVATION AND CAPITAL PLANNING
PROPERTY PRESERVATION AND CAPITAL PLANNING Overview What am I looking for Remaining Useful Life Estimating Planning TERMINOLOGY Shake Siding Service Head Barge Board Soffit / Overhang Belly Band Knee Brace
More informationBuilding Moisture Survey
Home Inspections - Thermal Imaging - Building Envelope Forensics Building Moisture Survey Prepared For: Robin 797 Merrimac Ln Kennett Square PA 19348 Table of Contents Cover Page...1 Table of Contents...2
More informationEIFS Inspection Report
EIFS Inspection Report PREPARED FOR: Hampton Court Townhome Association 220 Hampton Avenue Highwood, IL 60050 EVALUATION INFORMATION: Date of Inspections: September 28, 2007 Weather/Temp: Age of EIF System:
More informationSC-01 Cross-Section. Cement Board Substrate Master Wall Mesh and Base Coat Superior Finish
Master Wall Mesh and Base Coat Plastic Control Joint Accessory, Plastic Components 22027-16 or equal. See notes for placement recommendations Notes: Control joints are required and should be located by
More informationNational Property Inspections
Monday, August 22, 2011 Inspector Joe Smith 548-254-3658 Page 1 of 33 GENERAL INFORMATION GENERAL CONDITIONS AT TIME OF INSPECTION : No Property Occupied : Property Faces : North South East þ West Year(s)
More informationDiscussion of the Stucco Identification of All Panels
Discussion of the Stucco Identification of All Panels Mock-Up Stucco Identification Review: Review of Home Inspector Observations by Mock-Up: What type of system is Mock-Up Number and why? Where did you
More informationBUILDING SUCCESSFULLY WITH DRYVIT RESIDENTIAL SYSTEMS.
BUILDING SUCCESSFULLY WITH DRYVIT RESIDENTIAL SYSTEMS. DS504 THE FOLLOWING IS A LIST OF MAJOR CONSIDERATIONS THAT WILL HELP ENSURE A QUALITY DRYVIT INSTALLATION. SUBSTRATES (INSPECTION/WALK-AROUND) Prior
More informationGLOBAL PROPERTY INSPECTIONS TECHNICAL BULLETIN
GLOBAL PROPERTY INSPECTIONS TECHNICAL BULLETIN TM June 1, 2002 TOPIC: Exterior Coverings This is the sixth in a series of technical bulletins in which an over-all examination of the home will be discussed
More informationTechnical Bulletin. Corporate: P.O. Box 397 Fortson Georgia FAX Technical:
MW# 112-010112 Topic: Owner s Responsibilities for Cleaning and Maintenance of Wall Systems Related Technical Bulletins Repairing Master Wall EIFS Sealant Use Window Considerations EIFS Inspection Guidelines
More information3. Aesthetic Groove. 5. Window Head (Flush) 6. Window Head (Recessed) 7. Window Jamb Detail (Flush) 8. Window Jamb Detail (Recessed)
TYPICAL DETAILS Pebbletex-D10 System 1. Pebbletex-D10 Application (Plan VIew) 2. Pebbletex-D10 Design (Isometric View) 3. Aesthetic Groove 4. Insulation Boards / Reinforcing Mesh Application at Openings
More informationForensics Engineering 8th Congress Forging Forensic Frontiers November 29 December 2, 2018, Austin, TX
This paper was published at the Forensic Engineering 8th Congress, held November 29-December 2, 2018 in Austin, TX. The published version of this paper is available for purchase and download at: https://ascelibrary.org/doi/book/10.1061/9780784482018
More informationAcroWall-ES System. Class PB Exterior Insulation and Finish System providing a primary moisture barrier. Typical Details
Typical Details AcroWall-ES System Class PB Exterior Insulation and Finish System providing a primary moisture barrier 1. Typical AcroWall-ES System Application 2. Typical Aesthetic Reveal 3. Typical Window
More informationBUILDING EXTERIOR SHELL TRAINING
BUILDING EXTERIOR SHELL TRAINING Course Handout Part 1 Background and Insurance Issues (19min) Causes of Building Exterior Shell Problems Bad Design Poor Planning Failure to Follow Manufacturer s Recommendations
More informationPROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX HOUSTON, TEXAS (713)
PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX 271492 HOUSTON, TEXAS 77277 http://www.profengineering.com (713) 664-1264 June 19, 2000 Mr. Samuel Underdog 329 Castle Dr. Houston TX 77018 Dear Mr.
More informationINSTALLING WATER-RESISTIVE BARRIERS & FLASHING
INSTALLING WATER-RESISTIVE BARRIERS & FLASHING IN A TWO-LAYER STUCCO APPLICATION Fortifiber Building Systems Group provides this guide to assist installers by demonstrating a two-layer installation of
More informationInspection Report. Prepared for: Yossi Berg. Property Address: 4925 Diggers Way Sugar Hill, GA. Date: July 20, 2011
Inspection Report Prepared for: Yossi Berg Property Address: Sugar Hill, GA. Date: July 20, 2011 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT &
More informationWeatherSmart Air Barrier Installation Guide
WeatherSmart Air Barrier Installation Guide 1 The intent of this document is to provide a guide for the installation of WeatherSmart as both a Weather Resistive Barrier (W.R.B.) and an Air Barrier Material
More informationBWA ENVIRONMENTAL CONTROL BOARD (ECB) APPLICATION
BWA ENVIRONMENTAL CONTROL BOARD (ECB) APPLICATION To: The Environmental Control Board I propose to: (please check all that apply) * Repaint my home/garage. Color samples are submitted herewith and are
More informationR E S I D E N T I A L B U I L D E R S R E F E R E N C E G U I D E
DRYVIT SYSTEMS CANADA DSC504 R E S I D E N T I A L B U I L D E R S R E F E R E N C E G U I D E BUILDING SUCCESSFULLY WITH DRYVIT OUTSULATION RESIDENTIAL SYSTEMS INTRODUCTION Building Successfully with
More informationAcrocrete Platinum CI Stucco Typical details for an impact resistant cement plaster stucco system featuring Neopor rigid insulation board
Acrocrete Platinum CI Stucco Typical details for an impact resistant cement plaster stucco system featuring Neopor rigid insulation board Acrocrete Platinum CI Stucco Typical details for an impact resistant
More informationInspection Fundamentals: Stucco & EIFS
Inspection Fundamentals: Stucco & EIFS By Ben Gromicko To be able to identify the stucco system you must understand system components. You should understand the basic components of the most common stucco
More informationWEATHERTIGHTNESS (INVASIVE MOISTURE TESTING) ASSESSMENT
WEATHERTIGHTNESS (INVASIVE MOISTURE TESTING) ASSESSMENT 1 INTRODUCTION Inspection Date: 24 TH August 2016 Job No:47126 Property Inspected: 1-51 Watford Street Christchurch Weather Conditions: Fine Prepared
More informationDifferences between EnCon Insulated Precast and EIFS
Differences between EnCon Cover Differences between EnCon EnCon produces a number of different insulated precast concrete products. They range from Insulated Wall panels, Styrocore Insulated Wall Panels,
More informationProperty Inspection Report
DAVID A. MEACHAM Professional Inspection & Construction Services Property Inspection Report Prepared for David Smith Property Address 1154 Gulf View Drive Tampa Bay, Florida Inspection Date Friday, October
More informationFirstEnergy Program Overview
FirstEnergy Program Overview Builder incentives $400 per unit + $0.10/kWh in projected savings Eligibility Located in service area of a FirstEnergy Utility Certificate of Occupancy Dates: FirstEnergy Ohio
More informationFinestone Platinum CI Stucco Typical details for an impact resistant cement plaster stucco system featuring Neopor rigid insulation board
Finestone Platinum CI Stucco Typical details for an impact resistant cement plaster stucco system featuring Neopor rigid insulation board Finestone Platinum CI Stucco Typical details for an impact resistant
More informationCascade Thermal Imaging, Inc. ~ Infrared Imaging The Non-Invasive Truth ~ Thermography Report
TM Thermography Report Completed for: Mr. John Smith 2242 Greenwood Ave - Seattle, WA 98102 Thermography date: 1-26 & 1-29-16 Outdoor temperature: 54 F Indoor temperature: 68 F Temp diff In-Out Δ T : 14
More informationGAF EnergyGuard Polyiso Wall Sheathing
From: Technical Services May 15, 2013 GAF EnergyGuard Polyiso Wall Sheathing GAF s EnergyGuard Polyiso Wall Sheathing is intended to be installed on residential construction only. Application types include:
More informationApplication Instructions for Dryvit Backstop NT For Use Beneath Claddings Other Than Dryvit EIFS
Application Instructions for Dryvit Backstop NT For Use Beneath Claddings Other Than Dryvit EIFS CHECKLIST PRIOR TO THE INSTALLATION OF BACKSTOP NT - SMOOTH AND TEXTURE Project Conditions Maximum storage
More informationMagnum Board Coatings
Master Wall Mesh and Base Coat Plastic Control Joint Accessory, Plastic Components 22027-16 or equal. See notes for placement recommendations Notes: Control joints are required and should be located by
More informationInspection Report. Prepared for: Gil Turiel. Property Address: 545 Briar Run Court Loganville, GA Date: July 17, 2011
Inspection Report Prepared for: Gil Turiel Property Address: Loganville, GA 30052 Date: July 17, 2011 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT
More informationREPORT OF FINDINGS AND RECOMMENDATIONS BUILDING ENVELOPE REPAIRS AND RENOVATIONS RIVER RIDGE CONDOMINIUM NEWMARKET NEW HAMPSHIRE
REPORT OF FINDINGS AND RECOMMENDATIONS BUILDING ENVELOPE REPAIRS AND RENOVATIONS NEWMARKET NEW HAMPSHIRE Per the request of the Board of Directors of River Ridge Condominium Association (RRC), Newmarket,
More informationSenershield -R / Senershield -VB
Senershield -R / Senershield -VB Air / Water-Resistive Barrier Typical Details 1. Termination at Grade - Sheathing Overlapping Foundation 2. Termination at Grade - Sheathing Overlapping Foundation with
More informationDetermination 2010/052 Refusal to issue a code compliance certificate for a 6-year old house at 103 Karewa Parade, Papamoa
Determination 2010/052 Refusal to issue a code compliance certificate for a 6-year old house at 103 Karewa Parade, Papamoa 1. The matters to be determined 1.1 This is a determination under Part 3 Subpart
More informationProperty Condition Assessment
Property Condition Assessment Pewaukee, WI 53072 Inspection Date: 1/6/15 Prepared For: Report Number: Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar Dr. Pewaukee, WI 53072
More informationREPAIR STANDARDS AND OPTIONS
Chapter 4 Repair Standards and Options REPAIR STANDARDS AND OPTIONS NOTICE MOISTURE WARRANTY CORPORATION OFFERS THIS FREE INFORMATION AS A SERVICE TO REPAIR CONTRACTORS AND HOMEOWNERS TO ASSIST IN THEIR
More informationEXTERIOR SIDING CONDITION SURVEY
EXTERIOR SIDING CONDITION SURVEY FOR FARRWOOD 2 CONDOMINIUMS 49-176 FARRWOOD DRIVE HAVERHILL, MA APRIL 2016 c/o PROPERTY MANAGEMENT OF ANDOVER, INC. P.O. BOX 488 ANDOVER, MA 01810 213 WEST STREET, MILFORD,
More informationAcrocrete Platinum CI Stucco Ultra Typical details for a premium impact and puncture resistant rain screen design cement plaster stucco system
Acrocrete Platinum CI Stucco Ultra Typical details for a premium impact and puncture resistant rain screen design cement plaster stucco system featuring Neopor rigid insulation board and Acrostop R Acrocrete
More informationBuilding Construction and Water Intrusion
Building Construction and Water Intrusion RAY CHOY-MARSHALL GOVAN ASSOCIATES an architectural corporation ray_choy-marshall@sbcglobal.net 2930 camino diablo, suite 210, walnut creek, ca 94597 2004 Design
More informationCommercial Roof Cover Maintenance and Repair Risk Engineering Your Business Insurance Specialists
Commercial Roof Cover Maintenance and Repair Risk Engineering Your Business Insurance Specialists With information provided by the Insurance Institute for Business & Home Safety Protection from the top
More informationInspection Report. Property Address:
Inspection Report provided by: Safe Side Home Inspection Inspector: Corey Stuart TN License # 778 434 Margaret Circle McMinnville, TN 37110 safesideinspection@blomand.net Property Address: 1234 Anywhere
More informationInsulation. First Revison October DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS
Insulation First Revison October 2016 DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS 1. General Information This Guide describes the use of Kingspan GreenGuard DC14 Drainage
More informationBUILDING A NEW HOME. Construction Permit Tips For Home Owners
BUILDING A NEW HOME Construction Permit Tips For Home Owners This publication provides guidelines for constructing a detached singlefamily home. The code requirements herein are not all inclusive and should
More informationTOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ FAX
TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ 08014 856-467-3626--- FAX 856-467-9260 Application for Certificate of Occupancy for Change of Occupancy Pursuant to Chapter 119 of the Township
More information80201R StoColor Acryl Flat Acrylic-Based, Vertical Above-Grade Exterior Wall Coating for Recoating Prepared, Previously Painted Surfaces
Sto Corp. 3800 Camp Creek Parkway Building 1400, Suite 120 Atlanta, GA 30331 Tel: 404-346-3666 Toll Free: 1-800-221-2397 Fax: 404-346-3119 www.stocorp.com 80201R StoColor Acryl Flat Acrylic-Based, Vertical
More informationWater Management & Damage Prevention: A Guide for Homeowners
Water Management & Damage Prevention: A Guide for Homeowners This article provides homeowners with basic information to make these decisions and take the appropriate actions to keep their homes dry and
More informationREPORT OF ROOF CONDITION STUDY. YOUR FACILITY Your Facilities Location. Date YOUR FACILITY S IDENTIFICATION. Prepared for Your Company
REPORT OF ROOF CONDITION STUDY YOUR FACILITY Your Facilities Location YOUR FACILITY S IDENTIFICATION Date Prepared for Your Company 1114 Grindstone, Union, Kentucky 41091 (859) 657-6677 [Report Date] [Client]
More informationReCote Finish System over Concrete
Part 1 General 1.01 GENERAL A. The Master Wall ReCote Finish System for smooth precast and cast in place concrete consists of an acrylic primer and ReCote acrylic finish. When needed an acrylic modified
More informationBuilding Permit Application
Submittal Date: Permit #: PROPERTY INFORMATION: Site Address: Parcel #: Subdivision: Block: Lot: Square Footage of Property: PROPERTY OWNER INFORMATION: Owner s Name: Phone: Mailing Address: Email: CONTRACTOR
More information19 East Ave. Mullica Hill, N.J Phone: Fax: ARCHITECTURAL FOAM FABRICATORS, LLC.
Table of Contents Trims...1-17 Sills...18-21 Frieze Boards...22-23 Cornices...24-28 Bands...29-32 Keystones...33-35 Pilasters...36 Columns...37-39 Quoins...40 Arches & Circles...41-42 4 1/2 Trims 7 6 14
More informationAll Pro Home Inspection. Home Report South Your Town
Home Report 9999 South Your Town Page 1 of 22 Not Inspected Summary This summary is not the entire report. The complete report may include additional information of concern to the client. It is recommended
More informationDetermination 2012/010
Determination 2012/010 Regarding the refusal of code compliance certificates for a 12-year-old house with monolithic cladding and a 7-year-old pergola addition at 12 Diana Avenue, Gisborne 1. The matter
More informationInspection Report. Prepared for: Tonia Mann. Property Address: 2557 Briar Valley Way Dacula, GA Date: March 01, 2012
Inspection Report Prepared for: Tonia Mann Property Address: Dacula, GA 30019 Date: March 01, 2012 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT
More informationTRUMAN STATE UNIVERSITY GREENWOOD SCHOOL WINDOW REPLACEMENT
SECTION 085200 - WOOD WINDOWS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationRG180 FIBERED ELASTOMERIC 15yr System/ Metal Roofs
RG180 FIBERED ELASTOMERIC 15yr System/ Metal Roofs PART 1 - GENERAL 1.01 Description of Work A. This general specification is for the application of a Roof Guardian Technologies (RGT) Elastomeric Coating
More informationBUILDING SUCCESSFULLY WITH DRYVIT RESIDENTIAL SYSTEMS.
BUILDING SUCCESSFULLY WITH RESIDENTIAL S. DS504 THE FOLLOWING IS A LIST OF MAJOR CONSIDERATIONS THAT WILL HELP ENSURE A QUALITY INSTALLATION. SUBSTRATES (INSPECTION/WALK-AROUND) Prior to starting a job,
More informationARCHITECTURAL REVIEW CHECKLIST ARCHITECTURAL REVIEW SUBMITTAL REQUIREMENTS SINGLE MODEL
9500 Civic Center Drive Thornton, CO 80229 CITY DEVELOPMENT DEPARTMENT ARCHITECTURAL REVIEW CHECKLIST 303-538-7295 Single-Family Detached and Single-Family Attached Homes developmentsubmittals@cityofthornton.net
More informationSUMMARY 1234 Main St.Loudon TN Buyer Name 08/28/2018 9:00AM
SUMMARY 1234 Main St.Loudon TN 37774 Buyer Name 08/28/2018 9:00AM Dusty Jameson TN Home Inspector License #00123, TN WDI License #104158 Inspector Cluseau's Home Inspection Service 865-691-6158 dustyjameson@gmail.com
More informationFinestone Stucco System
Typical Details Finestone Stucco System Cement Plaster Stucco 1. Typical Finestone Stucco System with Steel Framing 2. Typical Finestone Stucco System with Wood Framing 3. Typical Finestone Stucco System
More informationSentry Stucco Ultra Wall System
Typical Details Sentry Stucco Ultra Wall System Premium impact and puncture resistant, rain screen design cement plaster stucco system with enhanced water management 1. Typical Sentry Stucco Ultra Wall
More informationCommercial Flashing Details
This technical note illustrates many of the most common flashing details for commercial buildings. The purpose for flashing is to direct moisture to the exterior and in so doing, prevent moisture from
More informationInspection Report. Prepared for: Tonia Mann. Property Address: 56 Riverview Place Douglasville, GA Date: September 19, 2012
Inspection Report Prepared for: Tonia Mann Property Address: Douglasville, GA 30134 Date: September 19, 2012 Inspector: Charles Mann Edifice Inspections, Inc. (770) 594-2222 www.edificeinspections.com
More informationDryScan Limited was engaged to complete a Pre-Purchase Scan only moisture ingress thermal imaging inspection for Joe Blogs at 8 Anywhere, Auckland.
Infrared Inspections DryScan Limited PO Box 869, Whangaparoa, Auckland 0943 Free phone: 0800-DRYSCAN ~ Mobile: 021 892 056 ~ Fax: 0064 9 421 1792 Email: bryce@dryscan.co.nz 6 th March 2012 Joe Blogs 8
More informationFINEGAN INSPECTION SERVICES, INC. 76 WEST FOSTER MAINEVILLE ROAD MAINEVILLE, OHIO PHONE FAX
FINEGAN INSPECTION SERVICES, INC. 76 WEST FOSTER MAINEVILLE ROAD MAINEVILLE, OHIO 45039 683-0733-PHONE 697-0163-FAX HOME INSPECTION REPORT 2/15/05 CLIENT: Mr. and Ms. RESIDENCE LOCATION: McJunkin Road,
More informationExterior structures (fences, sheds, decks, retaining walls, detached garages) in good condition, no evidence of termite damage or rotted wood
Please Note: This checklist should not be relied upon as a home inspection report, nor should it be considered a substitute for a home inspection. This list is representative, but NOT exhaustive. If you
More informationI. Process. Table of Contents. I. Process. II. Additional Information
INSTRUCTIONS KEEP FOR YOUR RECORDS The following must occur prior to beginning any on-site work: 1) A Building Permit must be posted in a visible location onsite Table of Contents I. Process II. Additional
More informationBuilding Envelope Enclosures That Work, What Owners Want!
WEBINAR February 23, 2017 Building Envelope Enclosures That Work, What Owners Want! Will Ikerd, P.E. (TX), LEED AP Webinar Speakers Karl Strand President of Vertical Solutions Consulting Will Ikerd, PE
More informationForm CITY OF SILVER BAY BUILDING PERMIT APPLICATION INFORMATION SHEET
CITY OF SILVER BAY BUILDING PERMIT APPLICATION INFORMATION SHEET 1. Building permits are required for any construction, erection, enlargement, alteration, remodeling, repair, moving or conversion of occupancy
More informationStorm Damage Repair Requirements
Storm Damage Repair Requirements A Guide to Navigating the Existing Building Code 1st Edition 516.621.2900 info@jsheld.com jsheld.com Overview When performing inspections of buildings or structures after
More informationSUMMARY 1234 Main St.Fall Branch Tennessee Buyer Name 02/23/2018 9:00AM
SUMMARY 1234 Main St.Fall Branch Tennessee 37656 Buyer Name 02/23/2018 9:00AM KC Bartley Certified Master Inspector - TN Lic. #1244 Professional Home Inspections (423) 306-0508 kc@prohitn.com These summary
More informationSECTION BID PROPOSAL FORM. Telephone NO: ( ) Facsimile NO: ( ) Oklahoma License NO:
ISSUE DATE: MARCH 21, 2012 (REVISION 2-08/31/12) PROJECT: CNB BUILDINGS 2 AND 3 CATOOSA, OKLAHOMA OWNER: BID TO: (Mail & Fax) CHEROKEE NATION BUSINESSES 777 WEST CHEROKEE STREET CATOOSA, OKLAHOMA 74015
More informationOCS ONE COAT STUCCO A custom blend of Portland cement, sand, extenders, fiber reinforcement and modifiers.
OCS ONE COAT STUCCO A custom blend of Portland cement, sand, extenders, fiber reinforcement and modifiers. Designed to save material by functioning as an exterior cladding in thicknesses ranging from 3/8
More informationTOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit:
TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION 355-7575 Ext. 395 Needed to Obtain Permit: 1. Building Permit Application, and/or residential plumbing permit application, as applicable, to be
More informationRG-170 Elastomeric 15yr System/ Metal Roofs
RG-170 Elastomeric 15yr System/ Metal Roofs PART 1 - GENERAL 1.01 Description of Work A. This general specification is for the application of a Roof Guardian Technologies (RGT) Elastomeric Coating system
More informationRSH ENGINEERING, INC. END OF BUILDERS WARRANTY INSPECTION REPORT INSP#: K00001 DATE: 00/00/11 PAGE #: 1
PAGE : 1 1 2 3 4 LEFT SIDE OF HOUSE: SEE. 3 TO. 10 FOR DETAILS. LEF T SIDE OF HOUSE: GENERAL NOTE: SOFFIT VENTS ARE MISSING AND/OR IS INADEQUATE ADD SOFFIT VENTS. PROVIDE ADEQUATE OF SOFFIT VENTS TO MEET
More informationapplication instructions
application instructions FOUNDATIONS 76 & 120 SERIES PRIMED PANEL SIDING ARCHITECTURAL COLLECTION REVERSE BOARD & BATTEN AND STUCCO PANEL SIDING General At the time of manufacture, siding meets or exceeds
More informationProperty Condition Assessment. Summary Report
www.real-estate-inspections.com Property Condition Assessment Summary Report Subject Property Prepared for: Client in Detroit File Number: 05-15-005 Inspector: Craig Milliken, PE CPM Real Estate Inspections,
More informationCITY OF VINE GROVE BUILDING PERMIT APPLICATION
CITY OF VINE GROVE BUILDING PERMIT APPLICATION DATE PERMIT NUMBER NAME of OWNER LAST FIRST MI STREET CITY STATE ZIP CODE PHONE NUMBER CELL PHONE NUMBER PROJECT LOCATION: SUBDIVISION LOT NO. SECTION STREET
More information