TEST REPORT. Rendered to: ALL WEATHER INSULATED PANELS Vacaville, California. PRODUCT TYPE: Wall Panels SERIES/MODEL: DM45 Series
|
|
- Austen Parrish
- 5 years ago
- Views:
Transcription
1 Architectural Testing TEST REPORT Report No.: D Rendered to: ALL WEATHER INSULATED PANELS Vacaville, California PRODUCT TYPE: Wall Panels SERIES/MODEL: DM45 Series Title Summary of Results Air psf <0.01 cfm/ft 2 Water Penetration Resistance Test Pressure psf Reference must be made to Report No. D dated 02/14/14 for complete test specimen description and detailed test results.
2 Page 1 of Report Issued To: All Weather Insulated Panels 929 Aldridge Road Vacaville, California Test Laboratory: Architectural Testing, Inc East Jensen Avenue Fresno, California (559) Project Summary: 3.1 Product Type: Wall Panels 3.2 Series/Model: DM Compliance Statement: Results obtained are tested values and were secured by using the designated test methods. Test specimen description and results are reported herein. 3.4 Test Date: 01/30/ Test Record Retention End Date: All test records for this report will be retained until January 30, Test Location: Architectural Testing, Inc. test facility in Fresno, California. 3.7 Test Sample Source: The test specimen was provided by the client. Representative samples of the test specimen will be retained by Architectural Testing for a minimum of four years from the test completion date. 3.8 Drawing Reference: The test specimen drawings have been reviewed by Architectural Testing and are representative of the test specimen reported herein. Test specimen construction was verified by Architectural Testing per the drawings located in Appendix A. Any deviations are documented herein or on the drawings. 3.9 List of Official Observers: Name Company Brian Ng Tyler Westerling All Weather Insulated Panels Architectural Testing, Inc.
3 Page 2 of Test Methods: ASTM E , Test Method for Determining Rate of Airflow Through Exterior Windows, Curtain Walls and Doors Under Specified Pressure Differences Across the Specimen. ASTM E , Test Method for Water Penetration of Exterior Windows, Curtain Walls and Doors by Uniform Static Air Pressure Difference. 5.0 Test Specimen Description: 5.1 Product Sizes: Overall Area: Width Height 7.43 m² (80.0 ft 2 ) millimeters inches millimeters inches Overall size Construction: The SR Series foam insulated sheet metal wall panels measured 4-0" thick. The mockup consisted of two (2) full-sized roof panels measuring 96" long by 40" wide and two (2) half-sized panels cut in two pieces approximately 20" in width mounted at each edge of the assembly. A test buck was constructed of nominal 2 x 10 Douglas fir lumber. Two (2) 2 x 4 supports were attached to the test buck, one at each end. The top lip of each panel joint was sealed with a 1/2" bead of Schnee-Morehead SM5430 and pushed together. The perimeter of the mock-up was sealed to the wood test buck with Dow Corning 791 sealant.
4 Page 3 of Test Results: The temperature during testing was 11 C (71 F). The results are tabulated as follows: Title of Test Air Leakage per ASTM E 1680, at 1.57 psf at 6.27 psf at psf Water Penetration per ASTM E 1646, at psf at psf Results <0.1 L/s/m 2 (<0.01 cfm/ft 2 ) <0.1 L/s/m 2 (<0.01 cfm/ft 2 ) <0.1 L/s/m 2 (<0.01 cfm/ft 2 ) Pass Pass General Note: All testing was performed in accordance with the referenced standard(s). Wall panels were tested in the vertical position. Architectural Testing will service this report for the entire test record retention period. Test records that are retained such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation will be retained by Architectural Testing, Inc. for the entire test record retention period. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, Inc. Dennis Janzen Technician Tyler Westerling, P.E. Senior Project Engineer DJ:TW: ss Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Drawings (2) This report produced from controlled document template ATI 00479, issued 01/27/12.
5 APPENDIX A Drawings
6
7
TEST REPORT. Rendered to: All Weather Insulated Panels Vacaville, California. PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series
Architectural Testing TEST REPORT Report No.: C6304.01-301-44 Rendered to: All Weather Insulated Panels Vacaville, California PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series Title Summary of Results
More informationPERFORMANCE TEST REPORT. Rendered to: ALL-WEATHER INSULATED PANELS. SERIES/MODEL: SM40 PRODUCT TYPE: Insulated Sandwich Wall Panel
PERFORMANCE TEST REPORT Rendered to: ALL-WEATHER INSULATED PANELS SERIES/MODEL: SM40 PRODUCT TYPE: Insulated Sandwich Wall Panel Title Summary of Results Air Infiltration
More informationTEST REPORT. Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California. SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window
TEST REPORT Report No.: D8932.01-301-44 Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window SPECIFICATION: AAMA/WDMA/CSA 101/I.S.2/A440-08,
More informationArchitectural Testing TEST REPORT. Rendered to: COEUR D'ALENE WINDOW Spokane Valley, Washington. PRODUCT TYPE: PVC Fixed Window SERIES/MODEL: 3310
Architectural Testing TEST REPORT Report No.: E2257.01-901-44 Rendered to: COEUR D'ALENE WINDOW Spokane Valley, Washington PRODUCT TYPE: PVC Fixed Window SERIES/MODEL: 3310 SPECIFICATIONS: AAMA/WDMA/CSA
More informationTEST REPORT. Report No.: G Rendered to: CR LAURENCE CO., INC. Vernon, California
TEST REPORT Report No.: G9949.01-303-47 Rendered to: CR LAURENCE CO., INC. Vernon, California PRODUCT TYPE: Fixed Lite Storefront System SERIES/MODEL: IT451 Title Summary of Results Design Pressure ±1440
More informationPERFORMANCE TEST REPORT. Report No.: H Rendered to: VELUX America LLC Greenwood, South Carolina
PERFORMANCE TEST REPORT Report No.: H0140.01-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Curb Mounted Skylight SERIES/MODEL: Specials Dome Skylight 0.118 Thickness PC
More informationTEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana
Architectural Testing TEST REPORT Report No.: D0162.01-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite
More informationTEST REPORT. ASSOCIATED MATERIALS, INCORPORATED Cuyahoga Falls, Ohio. Rendered to: PRODUCT TYPE: Fixed Window SERIES/MODEL: A780 SPECIFICATIONS:
Architectural Testing TEST REPORT Report No.: D7201.01-901-44 Rendered to: ASSOCIATED MATERIALS, INCORPORATED Cuyahoga Falls, Ohio PRODUCT TYPE: Fixed Window SERIES/MODEL: A780 SPECIFICATIONS: AAMA/WDMA/CSA
More informationTEST REPORT ASTM E331. Report No.: E Rendered to: IMISON USA Houston, Texas
TEST REPORT ASTM E331 Report No.: E2907.01-801-42 Rendered to: IMISON USA Houston, Texas PRODUCT TYPE: Foam and Plaster Wall System SERIES/MODEL: Fibrecote Title Water Penetration Resistance Test Pressure
More informationTEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey
TEST REPORT Report No.: F399.01-109-44 Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey PRODUCT TYPE: ACP Panel System (Dry Seal) SERIES/MODEL: Dry Econect-RS Title Design Pressure Air Infiltration
More informationTEST REPORT. Report No.: A Rendered to: TUBELITE, INC. Walker, Michigan
Architectural Testing TEST REPORT Report No.: A2941.01 109 44 Rendered to: TUBELITE, INC. Walker, Michigan PRODUCT TYPE: Aluminum Side Hinge Door SERIES/MODEL: Thermal=Block Summary of Results Title Test
More informationTEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio
TEST REPORT Report No.: E9891.01-501-47 Rendered to: TREMCO, INCORPORATED Beachwood, Ohio PRODUCT TYPE: Wall Panel System SERIES/MODEL: Vulkem 116 Illmod 600 Acrytec Panel SPECIFICATION: ASTM E 330, Standard
More informationAAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS
AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS SERIES/MODEL: 800MD Signature PRODUCT TYPE: Fixed Plastic Glazed Skylight Title Summary
More informationTEST REPORT. Report No.: F Rendered to: MI WINDOWS AND DOORS, LLC Gratz, Pennsylvania
TEST REPORT Report No.: F7299.01-109-47 Rendered to: MI WINDOWS AND DOORS, LLC Gratz, Pennsylvania PRODUCT TYPE: Polyvinyl Chloride (PVC) Picture Window SERIES/MODEL: HM155 SPECIFICATION(S): AAMA/WDMA/CSA
More informationTEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California
TEST REPORT Report No.: G8680.01-303-47 Rendered to: C.R. LAURENCE CO., INC. Vernon, California PRODUCT TYPE: Double Side Hinged Door - Outswing SERIES/MODEL: 925 Title Summary of Results Design Pressure
More informationTEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio
TEST REPORT Report No.: E9792.01-501-47 Rendered to: TREMCO, INCORPORATED Beachwood, Ohio PRODUCT TYPE: Wall Panel System SERIES/MODEL: ExoAir 230, Dymonic 100 SPECIFICATION: ASTM E 331, Standard Test
More informationStructural Performance Certification Authorization Report
Document Title: Doc No: FRM B1-02 Rev No: Page: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-113.0 Issue Date: Revision Date:
More informationTEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California
TEST REPORT Report No.: E5562.01-301-44 Rendered to: INTERNATIONAL WINDOW Fullerton, California PRODUCT TYPE: Sliding Glass Door (XO) SERIES/MODEL: 8920 SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,
More informationTEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California
TEST REPORT Report No.: E5467.01-301-44 Rendered to: INTERNATIONAL WINDOW Fullerton, California PRODUCT TYPE: Sliding Glass Door (OXO) SERIES/MODEL: 8920 SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,
More informationTEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California
TEST REPORT Report No.: E5564.01-301-44 Rendered to: INTERNATIONAL WINDOW Fullerton, California PRODUCT TYPE: Sliding Glass Door (XXO) SERIES/MODEL: 8880 SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,
More informationTEST REPORT. Report No.: F Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia
TEST REPORT Report No.: F7657.01-550-44 Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia PRODUCT TYPE: Metal Wall Panel System SERIES/MODEL: Low Profile Accu-Trac System ES with Stiffeners
More informationTEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California
TEST REPORT Report No.: E5468.01-301-44 Rendered to: INTERNATIONAL WINDOW Fullerton, California PRODUCT TYPE: Sliding Glass Door (OXXO) SERIES/MODEL: 8920 SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,
More informationTEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio
Architectural Testing TEST REPORT Report No.: B2739.02-501-47 Rendered to: TREMCO, INCORPORATED Beachwood, Ohio PRODUCT TYPE: Air Barrier System SERIES/MODEL: ExoAir 230, ProGlaze ETA System 1, Spectrem
More informationPERFORMANCE TEST REPORT. Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly
PERFORMANCE TEST REPORT Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly Title Summary of Results Air Infiltration
More informationTEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11
TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11 REPORT NO.: 1391.02-106-11 RENDERED TO: PRODUCT TYPE: GAMCO CORPORATION Flushing, New York Aluminum fixed window SERIES / MODEL: W250C Test Summary of Results
More informationTEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California
TEST REPORT Report No.: G6910.01-303-47 Rendered to: C.R. LAURENCE CO., INC. Vernon, California PRODUCT TYPE: Side Hinged Door - Outswing SERIES/MODEL: 925 Title Summary of Results Design Pressure ±2640
More informationTEST REPORT. Report No.: B Rendered to: MI WINDOWS AND DOORS, INC. Gratz, Pennsylvania
Architectural Testing TEST REPORT Report No.: B2133.01-109-47 Rendered to: MI WINDOWS AND DOORS, INC. Gratz, Pennsylvania PRODUCT TYPE: PVC Single Hung Window (Fin) SERIES/MODEL: 3540 SPECIFICATION: AAMA/WDMA/CSA
More informationTEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11
TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11 REPORT NO.: 1391.04-106-11 RENDERED TO: PRODUCT TYPE: GAMCO CORPORATION Flushing, New York Aluminum Outswing Casement Window SERIES / MODEL: W250C Test Summary
More informationMIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: FLEETWOOD WINDOWS & DOORS. SERIES/MODEL: Norwood 3070HI OOX PRODUCT TYPE: Sliding Glass Door
MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Rendered to: FLEETWOOD WINDOWS & DOORS SERIES/MODEL: Norwood 3070HI OOX PRODUCT TYPE: Sliding Glass Door This report contains in its entirety: Cover Page: 1 page
More informationStructural Performance Certification Authorization Report
Document Title: Doc No: FRM B1-02 Rev No: Pa ge: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-115.0 Issue Date: Revision Date:
More informationMOCK-UP TEST REPORT. Rendered to: TUBELITE INC. PROJECT: 300 ES Interior Glazed Curtain Wall
Architectural Testing MOCK-UP TEST REPORT Rendered to: TUBELITE INC PROJECT: 300 ES Interior Glazed Curtain Wall Report No: 94346.01-602-32 Test Completion Date: 09/10/09 Report Date: 09/14/09 Record Retention
More informationTEST REPORT. Rendered to: EARTHWISE GROUP, LLC Liberty Township, Ohio
TEST REPORT Report No.: E6273.02-501-47 Rendered to: EARTHWISE GROUP, LLC Liberty Township, Ohio PRODUCT TYPE: PVC Single Hung Window SERIES/MODEL: 143.095 Single Hung SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,
More informationASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Solar Gard Armorcoat 8-mil Film PRODUCT TYPE: Fixed Window with Applied
More informationStructural Performance Certification Authorization Report
Document Title: Doc No: FRM B1-02 Rev No: Page: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-105.0 Issue Date: Revision Date:
More informationTEST REPORT. Report No.: A Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina
Architectural Testing TEST REPORT Report No.: A6303.08-250-44 Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina PRODUCT TYPE: Double Hung Window SERIES/MODEL: VictorBilt Palmetto
More informationPERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test
More informationPERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors/Round Top Double PRODUCT TYPE: In-swing Round Top Double Door LH-4-5/8 Title Uniform Load Deflection
More informationASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A7795.01 109 44 Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut INSULPANE OF CT INC. Hamden, Connecticut PRODUCT
More informationINTERNATIONAL WINDOW TEST REPORT
INTERNATIONAL WINDOW TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-08 AND -11 TESTING ON 7223 O/X AWNING WINDOW REPORT NUMBER H5789.01-301-44 R1 TEST DATE(S) 09/13/17-09/18/17 ISSUE DATE REVISION
More informationAAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: BUILDERS ACCESSORIES, INC.
AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: BUILDERS ACCESSORIES, INC. SERIES/MODEL: 6490 PRODUCT TYPE: Polyvinyl Chloride (PVC) Casement Window Title Summary of Results Primary Product Designator
More informationAAMA 506 TEST REPORT. Report No.: G Rendered to: VEKA INC. Fombell, Pennsylvania
AAMA 506 TEST REPORT Report No.: G0434.01-501-44 Rendered to: VEKA INC. Fombell, Pennsylvania PRODUCT TYPE: PVC Double Hung Window SERIES/MODEL: DH57WW/AL-Insert Test Date(s): 06/28/16 Test Record Retention
More informationAAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: ALUMIL US. SERIES/MODEL: M300 Falcon PRODUCT TYPE: Aluminum Horizontal Sliding Window (XO)
AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: ALUMIL US SERIES/MODEL: M300 Falcon PRODUCT TYPE: Aluminum Horizontal Sliding Window (XO) Title Summary of Results Primary Product Designator HS-C30
More informationStructural Performance Certification Authorization Report
Document Title: Doc No: FRM B1-02 Rev No: Page: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-109.0 Issue Date: Revision Date:
More informationArchitectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT. Report Number: C Rendered to: Tubelite Inc.
Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT Report Number: C0271.01-450-44 Rendered to: Tubelite Inc. Walker, Michigan MODEL DESIGNATION: 400 Series Curtainwall with 4 Sided SSG PRODUCT
More informationTEST REPORT. Rendered to: UNIVERSAL PULTRUSIONS, LLC Marshall, Arkansas. Cycles 2,000,000. Summary of Results
Architectural Testing TEST REPORT Report No.: C0231.01-201-44 Rendered to: UNIVERSAL PULTRUSIONS, LLC Marshall, Arkansas PRODUCT TYPE: Side-Hinged Door SERIES/MODEL: 3070 Fiberglass Door SPECIFICATION:
More informationTEST REPORT. Report No.: G Rendered to: CR LAURENCE CO., INC. Vernon, California
TEST REPORT Report No.: G7972.01-303-44 Rendered to: CR LAURENCE CO., INC. Vernon, California PRODUCT TYPE: Woven Stainless Steel Screen Type III Infill SERIES/MODEL: 316 SS Black Powder Coat Summary of
More informationTEST REPORT. Report No.: H Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia
TEST REPORT Report No.: H3615.01-550-44 Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia PRODUCT TYPE: EIFS Panel Systems SERIES/MODEL: GP ForceField Air & Water Barrier Sheathing with
More informationASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: MGM WINDOW COMPANY Hendersonville, Tennessee
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A7921.02 501 44 Rendered to: MGM WINDOW COMPANY Hendersonville, Tennessee PRODUCT TYPE: PVC Double Hung Window SERIES/MODEL: 4650DH
More informationTEST REPORT. Report No.: F Rendered to: VELUX America LLC Greenwood, South Carolina
TEST REPORT Report No.: F8969.01-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Skylight SERIES/MODEL: Dynamic Double Dome Skylight 100% IMA Smooth/50% IMA Prismatic (5'
More informationMIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: BRICK-IT. SERIES/MODEL: Brick Veneer Panel Systems PRODUCT TYPE: Wall Panel Systems
This report contains in its entirety: Cover Page: 1 page Report Body: 15 pages Sketches: 7 pages Drawing: 1 page MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Rendered to: BRICK-IT SERIES/MODEL: Brick Veneer
More informationMIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama
Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT This report contains in its entirety: Cover Page: 1 page Report Body: 10 pages Sketches: 2 pages Photographs: 4 pages Drawings: 7 pages Report
More informationASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A2653.02 401 44 Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama PRODUCT TYPE: Curtain Wall SERIES/MODEL: PW257 Captured
More informationTEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina
TEST REPORT Report No.: G4210.01-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Skylight with Curb SERIES/MODEL: Specials Dome Skylight 0.150 thickness 100% IMA smooth/0.118
More informationAAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built)
AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: GAMCO CORPORATION SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built) Summary of Results Thermal Transmittance (U-Factor) 0.47 Condensation
More informationDennis Fassnacht Jr :59:35-04'00'
Document Title: Doc No: FRM B1-02 Rev No: Page: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-103.0 Issue Date: Revision Date:
More informationTEST REPORT. Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania. PRODUCT TYPE: Drywall Clip
Architectural Testing TEST REPORT Report No.: C2155.02-109-44 Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania PRODUCT TYPE: Drywall Clip Reference must be made to Report No. C2155.02-109-44, dated 04/05/13
More informationAAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A AAMA TEST REPORT SUMMARY
AAMA/WDMA/CSA 101/I.S.2/A440-08 AAMA/WDMA/CSA 101/I.S.2/A440-05 AAMA 910-93 TEST REPORT SUMMARY Rendered to: GIESSE NORTH AMERICA 2014 Holston Industrial Drive Blountville, TN 37617 PRODUCT TYPE: XO Sliding
More informationAAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: COASTAL INNOVATIVE PRODUCTS
Architectural Testing AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: COASTAL INNOVATIVE PRODUCTS SERIES/MODEL: Outswing Aluminum Bi-Folding System TYPE: Swinging Door with Frame Summary of Results
More informationAAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT SUMMARY. Rendered to:
AAMA/WDMA/CSA 101/I.S.2/A440-08 AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT SUMMARY Rendered to: AluminTechno LLC. 12 Selitskog Street, Room 211 FEZ Minsk, Minsk District, Minsk Region 220075 Republic
More informationTEST REPORT. Rendered to: THE NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS Glen Ellyn, Illinois
TEST REPORT Report No.: E5190.02-301-41 Rendered to: THE NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS Glen Ellyn, Illinois TYPE: Sunshade in the Horizontal Position above a dual glazed clear
More informationOSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX AMERICA INC. SERIES/MODEL: CAP-1 PRODUCT TYPE: Fixed Acrylic Glazed Skylight
OSHA FALL PROTECTION TEST REPORT Rendered to: VELUX AMERICA INC. SERIES/MODEL: CAP-1 PRODUCT TYPE: Fixed Acrylic Glazed Skylight Report No: Test Date: 04/01/09 Report Date: 10/20/09 Record Retention Date:
More informationPERFORMANCE TEST REPORT. Rendered to: HILTI CORPORATION. PRODUCT: Extreme Weather Window & Door Insulating Foam Sealant
PERFORMANCE TEST REPORT Rendered to: HILTI CORPORATION PRODUCT: Extreme Weather Window & Door Insulating Foam Sealant Report No.: G1169.02-106-31 Report Date: 11/16/16 Test Record Retention Date: 10/25/20
More informationCR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT
CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK AAMA 1801 TESTING ON IT451, STOREFRONT WINDOW REPORT NUMBER H7645.03-303-11 R0 TEST DATE 11/03/17 ISSUE DATE 11/17/17 RECORD RETENTION
More informationCR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT
CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK AAMA 1801 TESTING ON IT451, STOREFRONT WINDOW REPORT NUMBER H7645.02-303-11 R0 TEST DATE 11/03/17 ISSUE DATE 11/17/17 RECORD RETENTION
More informationAAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window
AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP TYPE: Picture Window ATI Data File No. 71965.01A 71965.01B Summary of Test Results Glazing
More informationANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC.
ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT Rendered to: MASTER WINDOW SYSTEMS, INC. SERIES/MODEL: Master 1000 Sliding Window PRODUCT: PVC Horizontal Sliding Window Summary of Results Title Test Specimen
More informationOSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America LLC. SERIES/MODEL: FCM B PRODUCT TYPE: Fixed Glass Glazed Curb Mount Skylight
OSHA FALL PROTECTION TEST REPORT Rendered to: VELUX America LLC SERIES/MODEL: FCM 4646 0004B PRODUCT TYPE: Fixed Glass Glazed Curb Mount Skylight Report No: 90752.03-109-44 Test Date: 07/27/09 Report Date:
More informationKNOTWOOD, A DIVISION OF OMNIMAX INTERNATIONAL MIAMI-DADE TEST REPORT
KNOTWOOD, A DIVISION OF OMNIMAX INTERNATIONAL MIAMI-DADE TEST REPORT SCOPE OF WORK TAS 201, TAS 202, AND TAS 203 TESTING ON KNOTWOOD, ALUMINUM POWDER-COATED CLADDING REPORT NUMBER I6115.01-109-18 TEST
More informationTEST REPORT. Rendered to: AD SKYLIGHTS, INC. Algonquin, Illinois. AD Skylight without Guard
TEST REPORT Report No.: E6827.01-602-47 Rendered to: AD SKYLIGHTS, INC. Algonquin, Illinois PRODUCT TYPE: Fixed Curb Mount Skylight SERIES/MODEL: AD Skylight with guard AD Skylight without Guard SPECIFICATION:
More informationAAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: W250C Awning TYPE: Projecting (Awning)
AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: GAMCO CORPORATION SERIES/MODEL: W250C Awning TYPE: Projecting (Awning) Summary of Results Thermal Transmittance (U-Factor) 0.48 Condensation Resistance
More informationOSHA FALL PROTECTION TEST REPORT. Rendered to: SERIES/MODEL: FS S PRODUCT TYPE: Fixed Deck Mounted Skylight
OSHA FALL PROTECTION TEST REPORT Rendered to: VELUX America LLC SERIES/MODEL: FS S06 2004 PRODUCT TYPE: Fixed Deck Mounted Skylight Report No: 96238.02-109-44 Test Date: 01/06/10 Report Date: 01/09/18
More informationTEST REPORT. Report No.: C Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania. PRODUCT TYPE: Drywall Clip
Architectural Testing TEST REPORT Report No.: C2155.01-109-44 Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania PRODUCT TYPE: Drywall Clip Summary of Results Drywall Size 6" Kick-Out 8' x 4' x 1/2" 425
More informationTEST REPORT. Report No.: G Rendered to: TREMCO, INCORPORATED Beachwood, Ohio
TEST REPORT Report No.: G1700.01-501-47 Rendered to: TREMCO, INCORPORATED Beachwood, Ohio PRODUCT TYPE: Steel Stud Wall with Three Coat Stucco System SERIES/MODEL: Multiple Refer to product matrix SPECIFICATION:
More informationAAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.
Architectural Testing AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: 300ES Curtainwall (8" System) TYPE: Glazed Wall Systems (Site-built) Summary of Results Thermal
More informationASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: WIRE-BOND. SERIES/MODEL: Masonry Tie Thermal Evaluations (2x6 Steel Stud Wall)
ASTM C 1363-11 THERMAL PERFORMANCE TEST REPORT Rendered to: WIRE-BOND SERIES/MODEL: Masonry Tie Thermal Evaluations (2x6 Steel Stud Wall) TYPE: Masonry Wall Assembly Summary of Results Test Unit R-Value
More informationMOCK-UP TEST REPORT NCTL ACURLITE STRUCTURAL SKYLIGHTS MOCKUP TEST UNIT TEST DATES 03/13/17, 03/21/17 03/23/17 REPORT DATE 04/03/17
MOCK-UP TEST REPORT NCTL-110-19973-1 ACURLITE STRUCTURAL SKYLIGHTS MOCKUP TEST UNIT TEST DATES 03/13/17, 03/21/17 03/23/17 REPORT DATE 04/03/17 1 of 18 Report Number NCTL-110-19973-1 Report Date 04/03/17
More informationOSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America Inc. SERIES/MODEL: VCM/VCE B PRODUCT TYPE: Venting Curb Mounted Skylight
OSHA FALL PROTECTION TEST REPORT Rendered to: VELUX America Inc. SERIES/MODEL: VCM/VCE 4646 2004B PRODUCT TYPE: Venting Curb Mounted Skylight Report No: Test Date: 01/06/10 Report Date: 03/15/10 Expiration
More informationPERFORMANCE TEST REPORT. Rendered to: DOW CORNING CORPORATION. PRODUCTS: Dow Corning 790 Silicone
PERFORMANCE TEST REPORT Rendered to: DOW CORNING CORPORATION PRODUCTS: Dow Corning 790 Silicone Report No.: F6923.03-106-31 Report Date: 09/19/16 Test Record Retention Date: 09/07/21 130 Derry Court York,
More informationConstruction Consulting Laboratory, International
Construction Consulting Laboratory, International Test Report CCLI-14-060 Client MI Windows and Doors, LLC. 1001 West Crosby Road Carrollton, TX 75006 Product Type: Aluminum Fixed Window Series / Model:
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: GAMCO CORPORATION. Series/Model: CW250
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: GAMCO CORPORATION Series/Model: CW250 Type: Two-Lite Curtain Wall System Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC
More informationTEST REPORT AAMA 501.5
TEST REPORT AAMA 501.5 REPORT NO.: RENDERED TO: PRODUCT TYPE: 1517.02-106-11-R0 DESANA PARTNERS Cranston, Rhode Island Back Drained and Ventilated Wall System SERIES / MODEL: Tru-Brix Rainscreen System
More informationNFRC SOLAR HEAT GAIN COEFFICIENT TEST REPORT. Rendered to: CLEAR FOCUS IMAGING
NFRC 201-2004 SOLAR HEAT GAIN COEFFICIENT TEST REPORT Rendered to: CLEAR FOCUS IMAGING SERIES/MODEL: ImageVue BASE WINDOW: 3/16" Clear Single Glazed PRODUCT TYPE: Window Film on the Exterior of Clear 3/16"
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: S80 Monterey. TYPE: Bi-fold Door
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: S80 Monterey TYPE: Bi-fold Door Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC
More informationNFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. (Revised) Rendered to: CUSTOM VINYL PRODUCTS, LLC
NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT (Revised) Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: DHA4 Double Hung Report Number: Original Report Date: Revised
More informationNFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: TUBELITE, INC.
Architectural Testing NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: 400 Series Curtain Wall (6" Standard Tube Backmember) - Fiberglass
More informationNFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: SPECIALTY WHOLESALE SUPPLY
NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT Rendered to: SPECIALTY WHOLESALE SUPPLY SERIES/MODEL: 4000 / 4500 DuraGard XT Double Hung Report Number: Report Date: E7526.09-116-45
More informationMILLENNIUM METALS, INC TEST REPORT
MILLENNIUM METALS, INC TEST REPORT SCOPE OF WORK WIND DRIVEN RAIN RESISTANCE TESTING OF MMI 26 GA OFF RIDGE VENT WITH DETACHABLE BAFFLE REPORT NUMBER H7685.03-450-18 R1 TEST DATE 11/29/17 ISSUE DATE 12/18/17
More informationAAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440. TYPE: Sliding Glass Door
Architectural Testing AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440 TYPE: Sliding Glass Door ATI Data File No. 71967.01 Summary of Test
More informationC R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Base 10
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to Series/Model: Base 10 Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results Data File Result
More informationASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB. TYPE: Acoustic Baffles
ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB TYPE: Acoustic Baffles Sample ID Number & Sample Description D9015.01 Series/Model 9100AB REVRB,
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: THERMA-TRU CORPORATION Series/Model: 3/0 x 6/8 Fiber-Classic/Smooth-Star, Full Lite Flush Glazed Type: Side-Hinged Single Door System Summary of
More informationASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: FabriSpan. TYPE: Ceiling System. Summary of Test Results
ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: FabriSpan TYPE: Ceiling System Summary of Test Results Sample ID Number & Sample Description C8714.01 Series/Model
More informationH R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR. Type: Office Partition
H0258.01-303-11-R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR Type: Office Partition Glazing: 1/4" Tempered Interior, 3-1/2" Air Space, 1/4" Tempered
More informationNFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: GAMCO CORPORATION
NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT Rendered to: GAMCO CORPORATION SERIES/MODEL: FG451T Flush Glaze Thermal Storefront Report Number: Report Date: G2028.02-116-45
More informationASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NOVAWALL SYSTEMS, INC. SERIES/MODEL: 3/4" Weltless. TYPE: Stretch Fabric Wall System
ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: NOVAWALL SYSTEMS, INC. SERIES/MODEL: 3/4" Weltless TYPE: Stretch Fabric Wall System Summary of Test Results Sample ID Number & Sample Description 1/3
More informationH R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR. Type: Office Partition
H0258.04-303-11-R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR Type: Office Partition Glazing: 1/4" Laminate Interior, 3-1/2" Air Space, 3/8" Laminate
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 8/0 Sliding Patio Door Summary of Test Results ATI Data File No. Glazing (Nominal Dimensions) STC
More informationG R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to NEW ENGLAND SOUNDPROOFING SERIES/MODEL: REVRB TRADITIONAL SERIES
ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423 Rendered to NEW ENGLAND SOUNDPROOFING SERIES/MODEL: REVRB TRADITIONAL SERIES TYPE: Acoustic Panels Summary of Test Results Data File No. 1/3 Octave Sound Absorption
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: THERMA-TRU CORPORATION Series/Model: 3/0 x 6/8 Fiber-Classic/Smooth-Star, Full Lite 1" IG Impact Glass with BTS Lite Frame Type: Side-Hinged Single
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390. TYPE: Sliding Glass Door
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390 TYPE: Sliding Glass Door Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC
More information