1 Building Control Strategies That Work to Improve Your Energy Bottom Line William D. (Skip) Milton MBA, CEM, CEA Assistant Director of Facilities Operations Texas Children s Hospital

2 Objective: Learn how to implement no cost/low cost measures to reduce your facilities energy cost.

3 Definitions: Baseline: Facility energy cost prior to implementation of any ECM s. Balance Point: Theoretical OAT that building does not require heating or cooling. Benchmark: Comparison of performance to an industry standard. Delta (Δ): Change in a measured or controlled process variable. Energy Conservation Measure (ECM): Measures that reduce energy usage or cost. Energy Use Index (EUI): BTU s per Square Foot of Gross Space (Benchmark Value) Dollars per Square Foot of Gross Area (Baseline Value) Measurement and Verification (M&V): Process of validating the performance of implemented ECM s Reset Ratio: The slope of a variable medium set-point based upon a measured vairable.

4 Before You Start! 1. Gather your facilities most update design documents (MEP) drawings and schedules. 2. Check, and record, current settings and sequences against the design documents. 3. Use this information as your reference base for future changes.

5 Establishing a Baseline This is simple. Just total a years cost of energy for a facility and device by the facility's gross square footage. You may desire to baseline individual months cost.

6 Example of yearly energy cost compared to gross area 7.00 TCH Energy Cost vs. Campus Square Footage FY07 FY08 FY09 FY10 FY11 FY12 $/SF SF 1,000,000 Note that the baseline was established in 2007

7 Benchmarking Use the Portfolio Manager located at: IT IS FREE!

8 ECM #1 Audit Monthly Utility Bills. Electric bills are clear as mud!

9 ECM #1 Audit Monthly Utility Bills. 1. Check invoice to determine if meter was read or if the charges are for an estimated reading. If estimated ask utility why the meter was not read and how the estimate was determined. 2. Compare pervious month s ending meter reading with this month s beginning meter reading. They should be the same. 3. Apply the current rate schedule to the measured commodity. The results should match the billed amounts. 4. Verify that the proper taxes are charged. 5. Compare month s usage to usage for the same month last year. 6. Document errors and notify the utility, in writing, of the errors.

10 ECM #2 Yearly Inspect Calibrate and/or Replace Equipment Sensors: Temperature, Relative Humidity, Pressure, Flow, (Air and Liquid) Kwh, KW, BTU,

11 ECM #2 Yearly Inspect Calibrate and/or Replace Equipment Sensors: 1. Establish a sensor replacement parameter. i.e. specified % offset requires replacement instead of calibration. 2. Insure sensor is correct for the application and is located in the correct position to measure the sensed variable. 3. Verify current sensed value against a separate calibrated instrument value. 4. If values are different calibrate or replace faulty sensor. 5. Flow sensors require annual cleaning.

12 ECM #3 Establish and Implement Room Temperature Set Points.

13 ECM #3 Establish and Implement Room Temperature Set Points. 1. Start out with public areas and commercial spaces. 2. Establish reasonable cooling and heating limits for your facility. 3. For electro mechanical thermostats use set-point limits and T-stat guards. 4. For electronic thermostats use programmable settings. 5. For BAS space sensors with or without set-point adjustment install limits in controllers. AHU, Terminal units, VAV boxes 6. Regularly inspect values to insure continued compliance.

14 ECM #4 Schedule occupied/unoccupied operation of equipment: Space temperature set points, Lighting, AHU s, Chiller/s, Boilers, and

15 ECM #4 Schedule occupied/unoccupied operation of equipment: 1. Meet with staff to develop agreed upon occupied/unoccupied schedules. 2. Consider EVS after hours cleaning schedules. 3. HVAC and lighting schedules for the same space may be different. 4. Consider installing timed override capabilities for some area/s. 5. Consider using daylight harvesting where possible. 6. Insure and communicate measures to alter schedules for special use requirements. 7. Communicate schedules to entire O&M staff. 8. Get ready to address questions.

16 ECM #5 Control Chilled Water Δ-T

17 ECM #5 Control Chilled Water Δ-T Calculating Savings: ΔT = (CHWR Temp CHWS Temp) Deg. F BtuH = (GPM x 8.34) X ΔT TonH = BtuH/12,000

18 ECM #5 Control Chilled Water Δ-T 1. Research CHW Low Delta-T Syndrome on Internet. 2. Consider controlling ΔT from 13F to 18F. 3. Determine sweet spot for your facility. 4. Control ΔT values manually or automatically. 5. Outside air temperature drives ΔT values. 6. Monitor AHU SA temperatures for positive cold deck temperature droop. 7. Check final filters for any condensation. 8. Check ΔT values at least daily.

19 ECM #6 Control Heating Medium Temperatures. Consider Outdoor Air Temperature Reset for Hot Water

20 ECM #6 Control Heating and Cooling Medium Temperatures. Consider Outdoor Air Temperature Reset for Hot Water. 1. Base HVAC heating water temperature on OAT. 2. Colder OAT requires warmer water and warmer OAT requires cooler water. 3. Set lower water temperature value at, or near, building balance point. 4. Set upper temperature limit at OAT value requiring significant cooling. 5. Heating water example: HW-T= 110F when OAT = 55F HW-T= 60F when OAT = 85F (The values are dependent on the building and HVAC system capabilities)

21 ECM #7 Control Heating and Cooling AHU Deck Temperatures. Consider Outdoor Air Temperature Reset

22 ECM #7 Control Heating and Cooling AHU Deck Temperatures. Consider Outdoor Air Temperature Reset This is the same concept as the previous reset tactic Cooling example: AHU Cooling SA-T = 55F when OAT = 85F AHU Cooling SA-T = 58F when OAT = 55F (The values are dependent on the building and HVAC system capabilities)

23 ECM #8 Adjust Air Flows to Meet Code Minimums. Reference ASHRAE 62.2 Ventilation Standards

24 ECM #8 Adjust Air Flows to Meet Code Minimums. Reference ASHRAE 62.2 Ventilation Standards (Most AHJ use ASHRAE 62 as their standard) 1. Physically measure space volume to determine required supply CFM requirements. 2. Adjust air flow settings to comply with your AHJ s minimum requirements. Most AHJ s follow ASHRAE standards. 3. Monitor performance monthly to insure compliance.

25 ECM #9 Reduce Simultaneous Heating and Cooling for Dual Duct VAV Boxes.

26 ECM #9 Reduce Simultaneous Heating and Cooling for Dual Duct VAV Boxes. 1. Program a dead band, range of temperature that requires no mechanical HVAC, into space controller set points. 2. Establish and set heating, cooling, and standby airflows. 3. Observe the performance of the box including the cooling and heating valves. Verify that the box reaches and maintains set points. 4. Make sure the control valves fully close.

27 ECM #10 Establish Occupied/Unoccupied set points for VAV Boxes.

28 ECM #10 Establish Occupied/Unoccupied set points for VAV Boxes. In unoccupied control the VAV Box will modulate to maintain the temperature set point of 78 degrees except that the minimum airflow set point is zero (0) CFM so there will never be the need for reheat in unoccupied mode to maintain the cooling set point.

29 ECM #11 Measure Flow Differential Pressures at the Correct Place.

30 ECM #11 Measure Flow Differential Pressures at the Correct Location. Locate the differential pressure sensor at the hydraulically most remote point in the piping system.

31 ECM #12 Utilize Measurement and Verification Activities to Insure Continuous Compliance. Monthly, Daily

32 ECM #12 Utilize Measurement and Verification Activities to Insure Continuous Compliance. Use at least one year s baseline energy usage data and weather data (HHD/CDD) to develop a simple predictive regression for reference. Microsoft Excel has an easy to use regression tool.

33 KtonH ECM #12 Utilize Measurement and Verification Activities to Insure Continuous Compliance WT CW Degree Day Correlation y = x Cooling Degree Days

34 TonH ECM #12 Utilize Measurement and Verification Activities to Insure Continuous Compliance WT TonH Degree Day Regression TonH = 1.31(CDD) Regression Actual 0 Month

35 Questions William D. (Skip) Milton

Reducing Hospital Energy Use and Maintaining Savings. Glen Anderson, PE

Reducing Hospital Energy Use and Maintaining Savings. Glen Anderson, PE Reducing Hospital Energy Use and Maintaining Savings Glen Anderson, PE AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The American Institute of Architects Continuing

More information

Retro-Commissioning in Hospitals

Retro-Commissioning in Hospitals Retro-Commissioning in Hospitals American Society of Healthcare Engineering () Introduction Elements of the Health Facility Retro-Cx Process Retro-Cx Case Studies Hospital Hospital Oklahoma Heart Hospital

More information

Strategies for Persistence: Measurement and Verification. Ryan Hughes PE, CEM, LEED AP Eaton Energy Solutions

Strategies for Persistence: Measurement and Verification. Ryan Hughes PE, CEM, LEED AP Eaton Energy Solutions Strategies for Persistence: Measurement and Verification Ryan Hughes PE, CEM, LEED AP Eaton Energy Solutions AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The

More information

Retro-Commissioning for Existing Facilities

Retro-Commissioning for Existing Facilities Retro-Commissioning for Existing Facilities Tom Meyer Director, Technical Programs National Environmental Balancing Bureau 8575 Grovemont Circle Gaithersburg, Maryland 20877 (301) 977-3698 www.nebb.org

More information

NEBBinar: Retro-Commissioning for Comfort and Energy Efficiency. August 21, 2013

NEBBinar: Retro-Commissioning for Comfort and Energy Efficiency. August 21, 2013 NEBBinar: Retro-Commissioning for Comfort and Energy Efficiency August 21, 2013 0 Moderator Jim Huber, NEBB Vice President and President of Complete Commissioning Jim Huber is the President of Complete

More information

Retrocommissioning Investigation Report

Retrocommissioning Investigation Report Continuous Optimization for Commercial Buildings Program Retrocommissioning Investigation Report March 22, 2013 Prepared for: Thompson Rivers University International Building BC Hydro #:COP10-353 Prism

More information

Project Information. Measure Description

Project Information. Measure Description Project Information Project ID#: CE07M016 Measure: Multiple Electric : 452,593 kwh, 8.84 kw, 39.26 kw Facility Type School Technology: Multiple Measure Description CH-1 - Chiller Plant Optimization and

More information

Characteristics of Energy Consumption by building type of a U.S. Navy Installation in Hot and Humid Climate

Characteristics of Energy Consumption by building type of a U.S. Navy Installation in Hot and Humid Climate Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 216 Characteristics of Energy Consumption by building type of a U.S. Navy Installation

More information

Xavier Energy Initiative

Xavier Energy Initiative Xavier Energy Initiative By Ron Perkins Report of August Site Visit To paraphrase Blaise Pascal, if I had more time I would have written a shorter report. In deference to those who do not share my enthusiasm

More information

5/7/2012. Agenda. What is High Performance? Ensuring a Successful Transition to Sustainable, High-Performance Operations

5/7/2012. Agenda. What is High Performance? Ensuring a Successful Transition to Sustainable, High-Performance Operations Ensuring a Successful Transition to Sustainable, High-Performance Operations Ed Tinsley, PE, LEED AP, HFDP, CHFM, CHC Managing Principal, TME, Inc. Agenda What is High Performance Operations? High Performance

More information

Retro-Commissioning for Energy Efficiency

Retro-Commissioning for Energy Efficiency High Performance Buildings 2006 AABC Commissioning Group (ACG) April 6, 2006 Retro-Commissioning for Energy Efficiency Making buildings work. Better. Tom Poeling, P.E., CEM, LEED AP E M C Engineers, Inc.

More information

KCAHE 2011 ANNUAL CONFERENCE LOW ENERGY HEALTHCARE DESIGN

KCAHE 2011 ANNUAL CONFERENCE LOW ENERGY HEALTHCARE DESIGN KCAHE 2011 ANNUAL CONFERENCE LOW ENERGY HEALTHCARE DESIGN Benchmarking energy usage - How hospitals use energy? - Why some facilities use more? - What should you be using? - Are you operating efficiently?

More information

Figure 26.5 Potential fan energy savings using fan speed limiting 16.

Figure 26.5 Potential fan energy savings using fan speed limiting 16. COMMISSIONING FOR ENERGY MANAGEMENT 685 Figure 26.5 Potential fan energy savings using fan speed limiting 16. 26.4.2.2. Set Minimum Outside Air Intake Correctly Outside air intake rates are often significantly

More information

Energy Management Journey

Energy Management Journey Energy Management Journey Arnold Granger, P.E., CEM Director of Energy Management Dr. Yeqiao Zhu, P.E., MBA Director of Facilities Patient Care and Prevention Facilities Patient Treatment Research Facilities

More information

9/13/2011. Mark Hanicits, Director of Facilities and Safety, MetroSouth Medical Center. Terry Malloy P.E., Cxa, Project Manager, Teng & Associates

9/13/2011. Mark Hanicits, Director of Facilities and Safety, MetroSouth Medical Center. Terry Malloy P.E., Cxa, Project Manager, Teng & Associates Mark Hanicits, Director of Facilities and Safety, MetroSouth Medical Center September 21 st, 2011 4:15pm 5:15pm Terry Malloy P.E., Cxa, Project Manager, Teng & Associates Energy consumption (BTU/SF) in

More information

The baseline building system for compliance with Senate Bill 668 is defined by Appendix G,

The baseline building system for compliance with Senate Bill 668 is defined by Appendix G, Project: North Carolina A&T State University New Student Health Center SCO #: 08-08109-01A 1.0 Heating, Ventilating and Air Conditioning (HVAC) Baseline Building Systems Senate Bill 668 Compliance The

More information

Introduction to Building Analytics

Introduction to Building Analytics INNOVATION INNOVATION Introduction to Building Analytics www.ecosave.com.au INNOVATION INNOVATION Lunch + Analytics = Sleep www.ecosave.com.au INNOVATION What? Why? How? www.ecosave.com.au Who is Watching?

More information

Retro-commissioning and on-going commissioning 23 November 2016

Retro-commissioning and on-going commissioning 23 November 2016 Retro-commissioning and on-going commissioning 23 November 2016 1 CONTENTS 1. Needs for Retro-Commissioning (RCx) 2. Retro-Commissioning (RCx) Definition and Scope 3. Briefing of RCx Process 4. Alternative

More information

SMART HVAC & LIGHTING SYSTEMS. Savings From Two Major C&I End Uses

SMART HVAC & LIGHTING SYSTEMS. Savings From Two Major C&I End Uses SMART HVAC & LIGHTING SYSTEMS Savings From Two Major C&I End Uses September 21, 2016 PRESENTATION OVERVIEW Why this focus? Significant savings potential Smart controls coupled with more efficient technologies

More information

Success with MEASUREMENT & VERIFICATION

Success with MEASUREMENT & VERIFICATION 2016 Success with MEASUREMENT & VERIFICATION Prepared for the North Carolina Department of Environmental Quality. Project funded by the U.S. Department of Energy, Office of Energy Efficiency and Renewable

More information

Energy Modeling Applications for Existing Buildings

Energy Modeling Applications for Existing Buildings Energy Modeling Applications for Existing Buildings Presented by: Clark Denson PE, CEM, BEMP, LEED AP BD+C 4/27/12 Learning Objectives 1. List available methods and tools for energy modeling 2. Explain

More information

Three Case Studies of the Application of Energy Systems Optimization Best Practices for Automatic Demand Response

Three Case Studies of the Application of Energy Systems Optimization Best Practices for Automatic Demand Response Three Case Studies of the Application of Energy Systems Optimization Best Practices for Automatic Demand Response Yifu Shi Kelly Guiberteau Carlos Yagua, P.E. James Watt, P.E. Energy Systems Laboratory,

More information

Georgetown University New Science Center

Georgetown University New Science Center Georgetown University New Science Center Final Thesis Proposal PENN STATE UNIVERSITY Prepared For: Dr. William P. Bahnfleth Department of Architectural Engineering Prepared By: Kevin M Edstrom Mechanical

More information

Energy Savings Audit

Energy Savings Audit Energy Savings Audit PREPARED FOR Steve Bennett Eileen Horn City of Lawrence ASSESSMENT SITE City of Lawrence Arts Center 940 new Hampshire St. Lawrence, KS 66044 ASSESSMENT PERFORMED BY P1 Group Inc 16210

More information

Technical Retro-Commissioning of Existing Buildings

Technical Retro-Commissioning of Existing Buildings Standard S0 0 0 Technical Retro-Commissioning of Existing Buildings Review Draft (--) This draft has been recommended for public review by the responsible project committee. To submit a comment on this

More information

BEYOND O&M. Shawn Maurer SEDAC Building Energy Specialist. Smart Energy Design Assistance Center (SEDAC), University of Illinois at Urbana Champaign

BEYOND O&M. Shawn Maurer SEDAC Building Energy Specialist. Smart Energy Design Assistance Center (SEDAC), University of Illinois at Urbana Champaign BEYOND O&M Shawn Maurer SEDAC Building Specialist Smart Design Assistance Center (SEDAC), University of Illinois at Urbana Champaign PRESENTATION OVERVIEW and Take away: Regular costs less over the long

More information

CONTINUOUS COMMISSIONING OF SALT LAKE COMMUNITY COLLEGE SOUTH CITY CAMPUS

CONTINUOUS COMMISSIONING OF SALT LAKE COMMUNITY COLLEGE SOUTH CITY CAMPUS CONTINUOUS COMMISSIONING OF SALT LAKE COMMUNITY COLLEGE SOUTH CITY CAMPUS Song Deng, P.E. and Dan Turner, P.E., Ph.D., Energy Systems Laboratory, Texas A&M University System, College Station, Texas Jim

More information

Chilled Beams. The new system of choice?

Chilled Beams. The new system of choice? Chilled Beams The new system of choice? Presented By: Kevin M. Pope P.E. Jason Leffingwell Hammel Green And Abrahamson, Inc. and Ken Bauer, P.E., LEED AP Butters-Fetting Co., Inc. History of Chilled Beams

More information

University of Minnesota Duluth Civil Engineering Building

University of Minnesota Duluth Civil Engineering Building Energy Data Attachment University of Minnesota Duluth Civil Engineering Building LEED Energy Modeling The energy modeling for LEED NC 2.2 was performed against ASHRAE 9.1-24 Appendix using equest version

More information

Monitoring-Based Commissioning (MBCx) Plan Template

Monitoring-Based Commissioning (MBCx) Plan Template Monitoring-Based Commissioning (MBCx) Plan Template Hannah Kramer Eliot Crowe Jessica Granderson Building Technology and Urban Systems Division Lawrence Berkeley National Laboratory Prepared for Amy Jiron

More information

Teague Research Center

Teague Research Center Continuous Commissioning Report for the Teague Research Center Building #445 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

NEBBinar: Managing Building Performance through Commissioning. March 28, 2013

NEBBinar: Managing Building Performance through Commissioning. March 28, 2013 NEBBinar: Managing Building Performance through Commissioning March 28, 2013 0 Moderator Jim Huber, NEBB Vice President and President of Complete Commissioning Jim Huber is the President of Complete Commissioning.

More information

Cornell University Energy and Sustainability: ECI Campus Energy Metrics Fiscal Year 2014 Annual Analysis Purpose and Methodology. ECI Campus Summary:

Cornell University Energy and Sustainability: ECI Campus Energy Metrics Fiscal Year 2014 Annual Analysis Purpose and Methodology. ECI Campus Summary: Purpose and Methodology ECI Campus Summary: Starting in the 2011/2012 fiscal year, a yearly energy metrics analysis is being performed. This analysis supports creating Facilities Metrics and evaluation

More information

How LEED & The Retro-Commissioning Credits Produce Energy Savings. James Vallort Vice President Environmental Systems Design, Inc.

How LEED & The Retro-Commissioning Credits Produce Energy Savings. James Vallort Vice President Environmental Systems Design, Inc. How LEED & The Retro-Commissioning Credits Produce Energy Savings James Vallort Vice President Environmental Systems Design, Inc. Retro-Commissioning Today s session will focus on the following items:

More information

Appendix D Example M&V Plans

Appendix D Example M&V Plans Appendix D: Example M&V Plans Appendix D Example M&V Plans 1 California s 2000 LNSPC Program Procedures Manual Example M&V Plans Several example M&V Plans are included in this Appendix for further guidance.

More information

Commercial Retro-Commissioning Program Manual for 2015 SECTION 1

Commercial Retro-Commissioning Program Manual for 2015 SECTION 1 Commercial Retro-Commissioning Program Manual for 2015 SECTION 1 Introduction The Commercial Retro-Commissioning Program (RCx) is designed to achieve demand and energy savings in commercial facilities.

More information

Cornell University Energy and Sustainability: ECI Campus Energy Metrics Fiscal Year 2015 Annual Analysis Purpose and Methodology. ECI Campus Summary:

Cornell University Energy and Sustainability: ECI Campus Energy Metrics Fiscal Year 2015 Annual Analysis Purpose and Methodology. ECI Campus Summary: Purpose and Methodology ECI Campus Summary: Starting in the 2011/2012 fiscal year, a yearly energy metrics analysis is being performed. This analysis supports creating Facilities Metrics and evaluation

More information

Use of Building Automation Systems for (Retro)Commissioning

Use of Building Automation Systems for (Retro)Commissioning Center for Energy and Environment Use of Building Automation Systems for (Retro)Commissioning Neal Ray, Center for Energy and Environment Gustav Brändström, Center for Energy and Environment January 17,

More information

Ventilation. Commercial Kitchen. What We Learned From MGM Grand Fire Airtight Buildings Benchmarking Building Energy Use Resetting Setpoints

Ventilation. Commercial Kitchen. What We Learned From MGM Grand Fire Airtight Buildings Benchmarking Building Energy Use Resetting Setpoints NOVEMBER 2015 ASHRAE JOURNAL THE MAGAZINE OF HVAC&R TECHNOLOGY AND APPLICATIONS ASHRAE.ORG Commercial Kitchen Ventilation What We Learned From MGM Grand Fire Airtight Buildings Benchmarking Building Energy

More information

Cornell University Energy and Sustainability: ECI Campus Energy Metrics Fiscal Year 2017 Annual Analysis Purpose and Methodology. ECI Campus Summary:

Cornell University Energy and Sustainability: ECI Campus Energy Metrics Fiscal Year 2017 Annual Analysis Purpose and Methodology. ECI Campus Summary: Purpose and Methodology ECI Campus Summary: Starting in the 2011/2012 fiscal year, a yearly energy metrics analysis is being performed. This analysis supports creating Facilities Metrics and evaluation

More information

Energy Reduction in Hospitals

Energy Reduction in Hospitals Energy Reduction in Hospitals OSBORN ENGINEERING DAVE CHOUINARD, CBCP, LEED AP, DIRECTOR HEALTHCARE CARL SCHULTZ, PE, DIRECTOR ENERGY AND FACILITY SYSTEMS MARK WUTZ, PE, DIRECTOR ENERGY & COMMISSIONING

More information

Chilled Water Energy Savings Study

Chilled Water Energy Savings Study 1 Chilled Water Energy Savings Study Pressure Dependent Valve Sizing and Valve Authority Pressure Independent Valves (Mechanical and Electronic) Chilled Water System Design MIT Beta Site Study-Correcting

More information

Getting Started with Your First Project: Considering Rules

Getting Started with Your First Project: Considering Rules Getting Started with Your First Project: Considering Rules to Deploy So you re ready to start a pilot project with a new customer. You have identified what data is available and where it is and how you

More information

Indiana University Glick Eye Institute. LEED Measurement & Verification Plan

Indiana University Glick Eye Institute. LEED Measurement & Verification Plan Indiana University Glick Eye Institute LEED Measurement & Verification Plan April 10, 2012 1 Table of Contents General Introduction... 3 Facility Description... 4 M&V Objectives... 4 M&V Approach/Option...

More information

Rowan University Energy Management Optimization of our Central Chilled Water System

Rowan University Energy Management Optimization of our Central Chilled Water System Rowan University Energy Management Optimization of our Central Chilled Water System Presented at the 2014 IDEA Annual Campus Energy Conference Atlanta, GA FOUR PILLARS OF ROWAN ENERGY MANAGEMENT: GENERATION

More information

Karl Helmink, P.E., CEM Retrocommissioning Manager University of Illinois. Retrocommissioning Saving the Planet One Building at a Time

Karl Helmink, P.E., CEM Retrocommissioning Manager University of Illinois. Retrocommissioning Saving the Planet One Building at a Time Karl Helmink, P.E., CEM Retrocommissioning Manager University of Illinois Retrocommissioning Saving the Planet One Building at a Time AIA Quality Assurance Portland Energy Conservation, Inc is a registered

More information

The Duke Endowment. Duke Facilities Fall Campus Sustainability Summit. Facilities Discussion. September 14, Management

The Duke Endowment. Duke Facilities Fall Campus Sustainability Summit. Facilities Discussion. September 14, Management The Duke Endowment 2011 Fall Campus Sustainability Summit Facilities Discussion September 14, 2011 Agenda Overview of Duke s Facility Portfolio & Organization Climate Action Plan Creating a Coal Free Duke

More information

UCSF Mission Bay Campus Arthur and Toni Rembe Rock Hall th Street San Francisco, California

UCSF Mission Bay Campus Arthur and Toni Rembe Rock Hall th Street San Francisco, California UCSF Mission Bay Campus Arthur and Toni Rembe Rock Hall 1550 4th Street San Francisco, California Monitoring Based Recommissioning Project Project Implementation: June 2005 to December 2005 Funded by a

More information

Army Exceeds Energy Goal Ahead of Mandate (Actual Energy Reduction of 38% vs 30% and Achieved in 2010 vs 2015)

Army Exceeds Energy Goal Ahead of Mandate (Actual Energy Reduction of 38% vs 30% and Achieved in 2010 vs 2015) Army Exceeds Energy Goal Ahead of Mandate (Actual Energy Reduction of 38% vs 30% and Achieved in 2010 vs 2015) NDIA E 2 S 2 May 9-12, 2011 New Orleans, LA Overview Background Energy Conservation Measures

More information

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal The following documentation provides an example submittal for the LEED-NC v2.1 Energy & Atmosphere Credit 1 (EAc1). This sample EAc1 submittal

More information

Can You Afford Not To Retro-Commission Your Facility In These Lean Times? Wednesday, October 3, :00pm 2:15pm

Can You Afford Not To Retro-Commission Your Facility In These Lean Times? Wednesday, October 3, :00pm 2:15pm Can You Afford Not To Retro-Commission Your Facility In These Lean Times? Wednesday, October 3, 2012 1:00pm 2:15pm Presenters Bruce Pitts bpitts@woodharbinger.com Len Rozek lrozek@ecube.com Mark Howe cmarkhowe@yahoo.com

More information

Persistence Tracking in a Retro-commissioning Program

Persistence Tracking in a Retro-commissioning Program Persistence Tracking in a Retro-commissioning Program Mike Eardley Architectural Energy Corporation Synopsis The persistence of energy savings and electrical demand reductions created by retrocommissioning

More information

SURNA Grow Facility: Systems Comparison - IEA

SURNA Grow Facility: Systems Comparison - IEA SURNA Grow Facility: Systems Comparison - IEA May 2016 SURNA Grow Facility This analysis provides the projected energy and associated cost comparison between the Surna proposed facility in comparison to

More information

ANALYSIS OF THE POTENTIAL ENERGY SAVINGS FOR 14 OFFICE BUILDINGS WITH VAV SYSTEMS

ANALYSIS OF THE POTENTIAL ENERGY SAVINGS FOR 14 OFFICE BUILDINGS WITH VAV SYSTEMS ANALYSIS OF THE POTENTIAL ENERGY SAVINGS FOR 14 OFFICE BUILDINGS WITH VAV SYSTEMS Jingjing Liu Graduate Research Assistant Juan-Carlos Baltazar, Ph.D. Associate Research Engineer David E. Claridge, Ph.D.,

More information

Outline Chilled Water T Study AHU Coil Overview Cooling Overview Test Setup Data Analysis Findings Summary

Outline Chilled Water T Study AHU Coil Overview Cooling Overview Test Setup Data Analysis Findings Summary Improved Chilled Water Plant Performance with New Energy Valve (EV) Outline Chilled Water T Study AHU Coil Overview Cooling Overview Test Setup Data Analysis Findings Summary 6 December 2012 Boston Hotels

More information

Existing Building Commissioning (or Retro-Commissioning)

Existing Building Commissioning (or Retro-Commissioning) SOUTHEAST REGION Existing Building Commissioning (or Retro-Commissioning) SERBCA Annual Meeting Covington, KY December 6, 2013 Session Learning Objectives o Definition of Existing Building Cx / RetroCx

More information

Existing Building Cx: Processes & Results A Cultural Journey. Barry Abramson Senior Vice President Servidyne

Existing Building Cx: Processes & Results A Cultural Journey. Barry Abramson Senior Vice President Servidyne Existing Building Cx: Processes & Results A Cultural Journey Barry Abramson Senior Vice President Servidyne AIA Quality Assurance Learning Objectives 1. Define the key steps in the process of retrocommissioning

More information

City of Fort Collins Building Automation Systems Enhances Savings and Commissioning Efficiency Works Training

City of Fort Collins Building Automation Systems Enhances Savings and Commissioning Efficiency Works Training City of Fort Collins Building Automation Systems Enhances Savings and Commissioning Efficiency Works Training November 18, 2015 Agenda Commissioning Monitoring Based Commissioning Building Tune up Case

More information

Sustainable Maintenance Best Practice: Energy Efficiency in the Carbon Free World. Michel Abi Saab. Team Leader, Energy Efficiency LEED AP, CEM, CMVP

Sustainable Maintenance Best Practice: Energy Efficiency in the Carbon Free World. Michel Abi Saab. Team Leader, Energy Efficiency LEED AP, CEM, CMVP Sustainable Maintenance Best Practice: Energy Efficiency in the Carbon Free World Michel Abi Saab Team Leader, Energy Efficiency LEED AP, CEM, CMVP Masdar Insert Date3rd Here September 2015 ABSTRACT A

More information

Application of Advanced Energy Technologies

Application of Advanced Energy Technologies GLOBALCON 2002 Philadelphia, Pennsylvania March 27, 2002 Application of Advanced Energy Technologies Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting, Inc. www.advantekinc.com

More information

FRIGI-TECH OIL SUPPLEMENT TEST GAMMA BIOLOGICALS, INC MANGUM ROAD HOUSTON, TEXAS. performed by:

FRIGI-TECH OIL SUPPLEMENT TEST GAMMA BIOLOGICALS, INC MANGUM ROAD HOUSTON, TEXAS. performed by: FRIGI-TECH OIL SUPPLEMENT TEST GAMMA BIOLOGICALS, INC. 3700 MANGUM ROAD HOUSTON, TEXAS performed by: ADAMS MECHANICAL SERVICES, INC. 235 CORTLANDT HOUSTON, TEXAS TEST DATES: JUNE 16, 1989 - SEPTEMBER 10,

More information

Energy & Climate Action

Energy & Climate Action Energy & Climate Action John Onderdonk Matthew Berbee Manager for Sustainability Programs Energy & LEED Manager June 11, 2010 0 Overview Energy Conservation Initiatives & Projects Alternative Energy Climate

More information

Energy Auditing for Schools. Maryland Energy Administration Eric Oliver, EMO Energy Solutions, LLC May 10, 2007

Energy Auditing for Schools. Maryland Energy Administration Eric Oliver, EMO Energy Solutions, LLC May 10, 2007 Energy Auditing for Schools Maryland Energy Administration Eric Oliver, EMO Energy Solutions, LLC May 10, 2007 Schools Consumption breakdown 19% 6% 9% Space Heating 46% Water Heating Lighting Cooling 20%

More information

Steps to Making Existing Commercial Buildings Become High Performance. Jim Bochat

Steps to Making Existing Commercial Buildings Become High Performance. Jim Bochat Steps to Making Existing Commercial Buildings Become High Performance Jim Bochat Steps to Advanced Existing Building Energy Performance Presentation s Reference Documents ASHRAE s Energy Efficiency Guides

More information

Converting CAV to VAV in Florida: What does this really mean?

Converting CAV to VAV in Florida: What does this really mean? AABC Commissioning Group AIA Provider Number 50111116 Converting CAV to VAV in Florida: What does this really mean? Course Number: CXENERGY1707 Steve Harrell, CxA, CEM, SSRCx April 26, 2017 Credit(s) earned

More information

LOGO. Trivium Level II Energy Audit

LOGO. Trivium Level II Energy Audit LOGO Trivium Level II Energy Audit Submission Date: 9/16/2016 Table of Contents 1.0 EXECUTIVE SUMMARY 3 2.0 SITE ENERGY CONSUMPTION 5 3.0 BACKGROUND INFORMATION 6 3.1 Description of the Client 6 3.2 Description

More information

Building Operator Certification Level I

Building Operator Certification Level I Building Operator Certification Level I A Partnership of the CUNY Institute for Urban Systems Building Performance Lab, the CUNY School of Professional Studies, and the New York State Energy Research &

More information

SGM Engineering, Inc.

SGM Engineering, Inc. SGM Engineering, Inc. 1. What is a typical Central Energy Plant consists of? BAS controls, chillers, pumps, cooling towers, electrical distribution, piping, chemicals, heating systems, and generators.

More information

CONTINUOUS COMMISSIONING OF THE MATHESON COURTHOUSE IN SALT LAKE CITY, UTAH. William D. Turner, P.E., Ph.D. Song Deng, P.E.

CONTINUOUS COMMISSIONING OF THE MATHESON COURTHOUSE IN SALT LAKE CITY, UTAH. William D. Turner, P.E., Ph.D. Song Deng, P.E. CONTINUOUS COMMISSIONING OF THE MATHESON COURTHOUSE IN SALT LAKE CITY, UTAH William D. Turner, P.E., Ph.D. Song Deng, P.E. Director Assistant Director Energy Systems Laboratory Texas A&M University System

More information

CREDIT COMPLIANCE (Please complete the color coded criteria(s) based on the option path selected)

CREDIT COMPLIANCE (Please complete the color coded criteria(s) based on the option path selected) (Responsible Individual) (Company Name) I,, from verify that the information provided below is accurate, to the best of my knowledge. CREDIT COMPLIANCE (Please complete the color coded criteria(s) based

More information

Technical Report Three Mechanical Systems Existing Conditions Evaluation

Technical Report Three Mechanical Systems Existing Conditions Evaluation 09 10 Technical Report Three Mechanical Systems Existing Conditions Evaluation WESTINGHOUSE ELECTRIC CO. NUCLEAR ENGINEERING HEADQUARTERS CAMPUS Pittsburgh, PA Daniel P. Aughenbaugh Mechanical Dr. Bahnfleth

More information

The Milton S. Hershey Medical Center Academic Support Building. AE Senior Thesis Kari Anne Donovan Mechanical Option

The Milton S. Hershey Medical Center Academic Support Building. AE Senior Thesis Kari Anne Donovan Mechanical Option The Milton S. Hershey Medical Center Academic Support Building AE Senior Thesis Kari Anne Donovan Mechanical Option Presentation Outline Existing Conditions Distributed Chilled Water Feasibility Study

More information

Xavier University of Louisiana

Xavier University of Louisiana Annual Savings Report Year 2 May 1, 2012 to April 30, 2013 July 2013 For Marion Bracy Vice President Xavier University Facilities Planning 1 Drexel Drive New Orleans LA 70125 (504) 520 1056 Submitted By

More information

You Can t Afford Discomfort. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

You Can t Afford Discomfort. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas You Can t Afford Discomfort Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Where We Are Today: So You Want To Save Money? Things to consider: 1. First Cost 2. Energy cost 3. Occupant Salary costs

More information

Practical M&V for Recommissioning Projects

Practical M&V for Recommissioning Projects Practical M&V for Recommissioning Projects Russ Chitwood May 4, 2007 Role of M&V in Recommissioning Case Study RCx Projects M&V Methods M&V Results Conclusions Overview 2 Role of M&V in Recommissioning

More information

Wakulla Chamber of Commerce July Place your cover photo here. Size and crop it to 4 high x 9.6 wide. Presented by Derick Farfan

Wakulla Chamber of Commerce July Place your cover photo here. Size and crop it to 4 high x 9.6 wide. Presented by Derick Farfan Wakulla Chamber of Commerce July 2017 Commercial Energy Efficiency Programs Place your cover photo here. Size and crop it to 4 high x 9.6 wide. Presented by Derick Farfan Energy Efficiency Incentives Question:

More information

Every building needs an Energy Efficiency Platform.

Every building needs an Energy Efficiency Platform. Every building needs an Energy Efficiency Platform. Persistent commissioning Rule-based controls Advanced analytics Cut energy costs Reduced downtime Optimize energy usage Other Systems Monitor Manage

More information

Variable Frequency Drive Retrofit Opportunities. Michael Kuk CERx Solutions LLC

Variable Frequency Drive Retrofit Opportunities. Michael Kuk CERx Solutions LLC Variable Frequency Drive Retrofit Opportunities Michael Kuk CERx Solutions LLC Speaker Introduction» Founder / owner of CERx Solutions LLC» Veteran Owned Small Business Enterprise founded in 2013» 27+

More information

Universal Translator 3: A free software tool to support your data processing needs

Universal Translator 3: A free software tool to support your data processing needs Session: Tools and Resources: Your Knowledge Center Universal Translator 3: A free software tool to support your data processing needs Ryan Stroupe PG&E Pacific Energy Center August 11, 2016 Rhode Island

More information

Energy Efficiency Analysis for a Multi-Story Research Office Building (LG Multi V Water IV Heat Recovery VRF System)

Energy Efficiency Analysis for a Multi-Story Research Office Building (LG Multi V Water IV Heat Recovery VRF System) Energy Efficiency Analysis for a Multi-Story Research Office Building (LG Multi V Water IV Heat VRF System) (* Source: http://kr.lgeaircon.com/) Commercial Air-Conditioning Engineering Study ES-MultiVWaterIV_EnergyAnalysis-08-14

More information

Intelligent. Powerful. Proven. usa.siemens.com/demandflow

Intelligent. Powerful. Proven. usa.siemens.com/demandflow Demand Flow Chilled Water System Optimization Intelligent. Powerful. Proven. usa.siemens.com/demandflow Demand Flow CHW Building Technologies A powerful solution to reduce energy consumption and improve

More information

OPTION 1: PERFORMANCE RATING METHOD

OPTION 1: PERFORMANCE RATING METHOD OPTION 1: PERFORMANCE RATING METHOD I confirm that the energy simulation software used for this project has all capabilities described in EITHER section `G2 Simulation General Requirements' in Appendix

More information

Benchmarking EPA Portfolio Manager and Energy Star Certification

Benchmarking EPA Portfolio Manager and Energy Star Certification Benchmarking EPA Portfolio Manager and Energy Star Certification 1 What is Benchmarking? Energy Benchmarking is the practice of comparing any given building to similar buildings for the purpose of evaluating

More information

Energy Strategies That Work Case Studies

Energy Strategies That Work Case Studies Energy Strategies That Work Case Studies Jean Ascoli, Architect, CEM, Program Director for New Construction Smart Energy Design Assistance Center University of Illinois, Urbana Champaign of Homeland Security

More information

Retrocommissioning: A Persistence Study

Retrocommissioning: A Persistence Study Retrocommissioning: A Persistence Study Umamaheswar Krishnan and Aniruddha Duttagupta, Nexant, Inc Alan Ahrens, CenterPoint Energy ABSTRACT Retrocommissioning (RCx) projects have become more commonplace

More information

Improving the efficiency, occupant comfort, and financial well-being of campus buildings

Improving the efficiency, occupant comfort, and financial well-being of campus buildings GHAUSI HALL ENERGY PROJECT REPORT Improving the efficiency, occupant comfort, and financial well-being of campus buildings ACE TEAM, ENERGY CONSERVATION OFFICE UC DAVIS FACILITIES MANAGEMENT Executive

More information

Management Committee December 3, Johnson County Community College Retrocommissioning Report

Management Committee December 3, Johnson County Community College Retrocommissioning Report Johnson County Community College Retrocommissioning Report Management Committee December 3, 2014 What is Retrocommissioning? Retrocommissioning is a systematic process to improve an existing building s

More information

OSU Richardson and Peavy Hall Energy Study: Energy Conservation Measure Analysis. January 25, 2012 {Revised April 30, 2012}

OSU Richardson and Peavy Hall Energy Study: Energy Conservation Measure Analysis. January 25, 2012 {Revised April 30, 2012} OSU Richardson and Peavy Hall Study: Conservation Measure Analysis January 25, 2012 OSU Richardson and Peavy Hall Study: Conservation Measure Analysis CONTENTS 1.0 Executive Summary... 1 2.0 Building

More information

The Biggest Loser REDUCING HIGHER EDUCATION COSTS BY 50%

The Biggest Loser REDUCING HIGHER EDUCATION COSTS BY 50% The Biggest Loser REDUCING HIGHER EDUCATION COSTS BY 50% Ian Hadden, PE, LEED AP BD+C, CEM Director, Energy Management Services University of Arkansas at Little Rock 501-313-9597 ithadden@ualr.edu.com

More information

Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY AHR Expo Innovation Award Winner in the Category of Building Automation

Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY AHR Expo Innovation Award Winner in the Category of Building Automation Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY 2014 AHR Expo Innovation Award Winner in the Category of Building Automation The Belimo Energy Valve won the Technical Innovation of

More information

Do-It-Yourself Energy Audit. Bob Furgeson, PE CEM CBCP GBE CEA Shive-Hattery Architects+Engineering

Do-It-Yourself Energy Audit. Bob Furgeson, PE CEM CBCP GBE CEA Shive-Hattery Architects+Engineering Do-It-Yourself Energy Audit Bob Furgeson, PE CEM CBCP GBE CEA Shive-Hattery Architects+Engineering Agenda» Basic Terminology» Background» Benchmarking» Audit Types/ASHRAE Standard» Building Audit Systems

More information

Monitoring-Based Commissioning: A Case Study in Higher Education. Janelle H. Griffin, PE, CCP, LEED AP

Monitoring-Based Commissioning: A Case Study in Higher Education. Janelle H. Griffin, PE, CCP, LEED AP Monitoring-Based Commissioning: A Case Study in Higher Education Janelle H. Griffin, PE, CCP, LEED AP AIA Quality Assurance The Commissioning Association is a Registered Provider with The American Institute

More information

Changes to the Minnesota Commercial Energy Code. Presented by: Andy Thielen, PE

Changes to the Minnesota Commercial Energy Code. Presented by: Andy Thielen, PE Changes to the Minnesota Commercial Energy Code Presented by: Andy Thielen, PE Warning! The following is an outline of proposed code changes. There is no guarantee that the final code adopted by the State

More information

Energy Management Report

Energy Management Report Energy Management Report November 2013 A. The extent to which the agency has met the percentage goal it established for reducing its usage of electricity, gasoline, and natural gas: Energy consumption

More information

Chilled Water Plant Statement of Capabilities

Chilled Water Plant Statement of Capabilities ENGINEERED ENERGY SOLUTIONS INC. 166 West Ed Avenue Somerville, NJ 08876 Phone: (908) 252-3800 Fax: (908) 252-3801 Chilled Water Plant Statement of Capabilities Table of Contents S E C T I O N 1 History

More information

AN INNOVATIVE DEDICATED OUTDOOR AIR APPLICATION FOR A GOVERNMENT OFFICE TOWER. MICHAEL HALLENBECK, PE, CEM Southland Industries

AN INNOVATIVE DEDICATED OUTDOOR AIR APPLICATION FOR A GOVERNMENT OFFICE TOWER. MICHAEL HALLENBECK, PE, CEM Southland Industries AN INNOVATIVE DEDICATED OUTDOOR AIR APPLICATION FOR A GOVERNMENT OFFICE TOWER MICHAEL HALLENBECK, PE, CEM Southland Industries BRAC 133 OVERVIEW PROJECT OVERVIEW FAN POWERED INDUCTION UNIT CENTRAL UTILITY

More information

Optimizing Central Chilled Water Systems

Optimizing Central Chilled Water Systems Optimizing Central Chilled Water Systems OPTIMIZING CENTRAL CHILLED WATER SYSTEMS kent.peterson@p2seng.com 1 O P T I M I Z I N G C E N T R A L C H I L L E D W A T E R S Y S T E M S Kent W. Peterson, PE,

More information

WHOLE BUILDING RETROFITS: A CONTRACTOR/SUPPLIER DEMONSTRATION

WHOLE BUILDING RETROFITS: A CONTRACTOR/SUPPLIER DEMONSTRATION 1 WHOLE BUILDING RETROFITS: A CONTRACTOR/SUPPLIER DEMONSTRATION Professor Kirk Alter Purdue University Fast Management, Inc. SESSION DESCRIPTION Whole Building Retrofits: A Contractor/Supplier Demonstration

More information

ENERGY MODELING GUIDELINES. D. Section Building Automation and Control System Guidelines

ENERGY MODELING GUIDELINES. D. Section Building Automation and Control System Guidelines 018130 ENERGY MODELING GUIDELINES PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 018110 Green Building Guidelines B. Section 230000 Basic HVAC Requirements C. Section 230540 Laboratories D. Section 230900

More information