COMPARISON OF THE SPECIFIC SURFACE CONDUCTIVITY AND ESDD APPROACHES TO ASSESSMENT OF SALT DEPOSITS ON NATURALLY POLLUTED INSULATORS. 1.

Size: px
Start display at page:

Download "COMPARISON OF THE SPECIFIC SURFACE CONDUCTIVITY AND ESDD APPROACHES TO ASSESSMENT OF SALT DEPOSITS ON NATURALLY POLLUTED INSULATORS. 1."

Transcription

1 E. A. Solomonik 36-WG11/Nberg/158 19/06/03 L. L. Vladimirsky, E. A. Solomonik HVDC Power Transmission Research Institute (NIIPT) COMPARISON OF THE SPECIFIC SURFACE CONDUCTIVITY AND ESDD APPROACHES TO ASSESSMENT OF SALT DEPOSITS ON NATURALLY POLLUTED INSULATORS 1. General The recent IEC draft submitted by the WG11 TC36 for revision comprises a number of statements which, in our opinion, should be further discussed. Presented below is a comparison of assessment of the natural polluting deposit s characteristics using the specific surface conductivity ρ techniques and the equivalent salt deposit density (ESDD/NSDD) method. These two parameters, along with some others that are not considered here, are used widely as the standard pollution level (PL) criterion of areas for which external insulation must be selected. In Russia and ex-ussr, a wealth of ρ and, to a smaller degree, ESDD/NSDD measurement data for naturally and artificially polluted (NP and AP, respectively) insulators have been accumulated over four decades since the 1960s. These comments are based on generalized data reported in [1-6] and in some other NIIPT publications. Both ρ and ESDD/NSDD were measured during the following studies: - selection of insulation levels (creepage distances) on the basis of breakdown (flashover) characteristics and parameters of the pollution layer of NP insulators taken out of service; - determination of flashover voltages of NP insulators by indirect methods (from characteristics of the pollution layer); - flashover studies of AP insulators of various configurations; - flashover studies of non-uniformly AP insulators; - selection of a pollutant for AP tests of external insulation. By way of illustration, Figs. 1 and 2 give NIIPT s findings of insulation level studies for 132 to 500 kv transmission lines in saline soil areas of Egypt. Back in 1969, the specific surface conductivity ρ of the polluting deposit was substantiated to be the principal criterion of assessing the pollution level of AP and NP insulators by a USSR national conference on polluted insulation research. Since that time, methods of determining ρ and its values for various PL areas were standardized by many Russian mandatory documents dealing with tests, selection, and operation of external insulation and used for practical applications. The operational experience of insulation selected with the help of this criterion proved the decision to be totally correct. As for the ESDD/NSDD method, which is also recognized in Russia, it is considered but a supplementary technique of evaluating the artificial and natural pollution level and used for selection of insulation quite seldom. Long-term field and laboratory polluted insulation studies of various territories provided basis for a number of standards and methodological documents, still in force in Russia, related to measurements of pollution layer parameters of naturally polluted porcelain and glass insulators [7-11]. Similar Russian guidelines have been developed for composite (polymer) insulators as well, with, however, a limited bank of measured data. The standards specify the scope, times, and procedures of natural pollution measurements. The most accurate, although time-consuming, method of selection of insulators for natural pollution conditions is through use of data on their wet flashover (breakdown) voltages, which are most often in artificial pollution tests. Specific surface conductivity inputs make insulator selection less accurate while facilitating it considerably. Additional insulator selection criteria that are also used in Russia for natural pollution conditions are density of salt deposits and properties of precipitation-carried pollutants accumulated in special collectors.

2 2. Selection of insulation levels by breakdown voltage and specific surface conductivity of NP insulators Russian requirements on selection of outdoor insulation by breakdown voltages and specific surface conductivity of wet polluted insulators in natural and industrial pollution areas at low values of specific conductivity of atmospheric precipitation (ρ v under 0.5 ms/cm) are shown in Table 1. Similar criteria are also available for areas with a high conductivity of atmospheric precipitation (ρ v from 0.5 to 10 ms/cm). Table 1 Russian standards for determining the specific effective creepage distance of electrical insulation λ e in natural and industrial pollution areas (ρ v under 0.5 ms/cm), based on measurements of λ e-bd and æ at NP λ e-bd, cm/kv ρ, µs Minimum λ e, cm/kv for 110 kv and above PL according to [11] over 1.2 to 1.5 over 1 to over 1.5 to 1.9 over 3 to over 1.9 to 2.3 over 6 to over 2.3 to 2.7 over 12 to over 2.7 to 3.3 over 20 to over 4 Designations used in Table 1 are as follows: L λ e-bd = specific effective breakdown creepage distance, cm/kv; λe-bd =, where: U bd K L = creepage distance of the test object (insulator or insulating structure), cm; U bd = average breakdown voltage of the test object over a period of time when it remains steady (varying within 10%), kv; К = creepage distance efficiency factor for the test object according to [11]; ρ = test time-averaged specific surface conductivity of the polluting deposit, µs; ρ = К / R, where: К f = form factor of the test object; R s = test-time averaged surface resistance of the moisturesaturated polluting deposit, MOhm. λ e = specific effective creepage distance for outdoor insulators, cm/kv, as specified by Russian standards [12]; Those individual measured values of λ e-bd that are more than 20% below the average λ e-bd are disregarded. Likewise ignored are those test values of ρ that differ from the average æ by more than 50% at ρ 15 µs and more than 30% at ρ >15 µs. λ e-bd for each field station is the larger of two values, viz. the test- Taken as the design value of time average or the maximum for abnormally adverse pollution or precipitation conditions, such as exhibited during large-scale blackouts. The same approach is taken in determining the design value of the specific surface conductivity ρ. f s 2

3 Owing to a fairly large scatter of the measured breakdown voltage and specific surface conductivity values, reliable data for each location can be obtained only from a sufficiently large number of measurements, which must be continue for at least two years, so as to cover the worst-case pollution conditions for the study area. With both λ e-bd and æ data available, the value of λ e should be found from λ e-bd. The standard values quoted in Table 1 cover insulator strings and pin insulators of overhead transmission lines with steel and reinforced concrete supports or towers, as well as external insulation of electric apparatus and insulators of outdoor switchgear. The standards were based on and substantiated by generalized NP measurements and apparatus service records for areas with various environmental conditions. NP breakdown voltage values were used for plotting dozens of insulation level maps for a majority of ex-ussr areas featuring natural and/or industrial pollution. Such maps are generally divided into local and regional categories covering part or totality of the power system service area. Breakdown voltage values were also applied for selection of insulation levels of many planned or upgraded electric power facilities. In the latter case, the breakdown voltage approach to selection of insulators and determination of pollution level exhibits only one disadvantage of being highly labor-intensive: it involves time-consuming operations of mounting, removing, transporting and testing large numbers of insulators, to say nothing about the need for purpose-oriented test equipment, such as a powerful test transformer, an artificial wetting system, and some other items. Tests call for at least two years; in order to take off the insulators, the field pollution standard must be de-energized. The ρ approach to insulator selection is not as time-consuming and calls for a smaller number of test insulators. However, the ρ test duration is the same as in the breakdown voltage case. 3. Comparison of parameters of insulator polluting deposit Numerous natural pollution studies, which were carried out by NIIPT in compliance with respective mandatory procedures, made it possible to correlate the breakdown voltage of insulators to both ρ and ESDD/NSDD for specific environment conditions. By way of illustration, quoted below are conclusive experimental findings for two test cases. Here breakdown voltages are expressed via the L specific breakdown effective creepage distance λ e-bd (see above, λe-bd = ). U bd K Case 1 deals with a dry tropical climate, saline soil area featuring abundant dew condensation. For several years, both breakdown voltage and polluting deposit measurements were recorded simultaneously on a large number of regular cap-and-pin porcelain insulators. The range of ρ, ESDD, and λ e-bd was found to be 2-50 µs, mg/cm, and cm/kv, respectively. Case 2, dealing with a humid tropical climate, sea coast area, involved long-term studies of regular cap-and-pin porcelain and glass insulators. The averaged findings are summarized in Table 2. These and many other findings by NIIPT permit the following conclusions: - averaged breakdown voltage values for a specific area or areas with similar environmental conditions can be deduced from both ρ and ESDD; - the scatter of measured values of both ρ and ESDD remains within the characteristics of a single PL; - even with a considerable scatter of experimental findings, the breakdown voltage/ρ relationships for different types and intensities of natural pollution make possible establishment of reliable regularities for insulators of an identical configuration; however, similar data on ESDD are unavailable. 3

4 Table 2 Averaged field-study findings for cap-and-pin insulators exposed to saline sea pollution λ e-bd, cm/kv over 1.1 to 1.3 over 1.3 to 1.6 over 1.6 to 1.9 æ, µs over 3 to 6 SDD, mg/cm 2 over to 0.05 ESDD, mg/cm 2 over to 0.04 Overall density of pollutant, mg/cm 2 PL over 0.08 to over 6 to 10 over 0.05 to 0.10 over 0.04 to 0.06 over 0.18 to over 10 to 18 over 0.10 to 0.18 over 0.06 to 0.10 over 0.30 to Besides, it is shown by available data that use of the insulator-type-averaged polluting deposit parameters yields ρ/esdd ratios that range widely depending on pollution type and level. By way of illustration, Table 3 shows such averaged ρ/esdd (µs cm 2 /mg) ratios for regular porcelain cap-andpin insulators versus PL and some pollution varieties. Table 3 Ratios of polluting deposit parameters of cap-and-pin insulators for some natural pollution varieties PL Pollution type ρ/esdd Pollution type ρ/esdd Pollution type ρ/esdd Fly ash of coalburning 50 ther Sea salt Soil salt mal power plants Results of similar measurements in different operating environments show that the ρ/esdd ratio depends heavily on the natural pollution variety and level, the insulator type, non-uniformity of pollution, climatic conditions of the study area, as well as some other factors. Thus selection of insulation levels with the help of such general-purpose parameters as ρ or ESDD can very often lead to very different results. It is shown by NIIPT s experience that the ρ-based insulation selection procedure should be further improved through developing recommendations for reference insulators, separately at least for marine, soil, and industrial pollution. 4. Comparison of insulation selection approaches Summarized in Table 4 are pros and contras for using the ρ and ESDD/NSDD polluting deposit characteristics in selection of outdoor insulation. The data available at NIIPT permit the following conclusions: - use of polluting deposit parameters for selection of insulation levels dictates application of simple insulator shapes, as suggested by IEC WG11 TC36 in revision of IEC standard 60815; - selection of insulation levels by a common criterion for different pollution varieties, which is based on polluting deposit parameters, whether ЕSDD, as in the IEС under revision, or ρ, as in many other cases, can result in serious errors; - available Russian NP research findings generally give preference to the ρ-based approach to selection of insulation levels; use of the ESDD/NSDD approach calls for further data acquisition; 4

5 Comparison of insulation selection approaches Table 4 ρ Proved to be good with a majority of pollutants Comparatively easy to determine Quite often the test insulator must not be taken out of service Used widely in a number of countries Acceptable for any insulator materials Applicable for all kinds of pollution and wetting conditions More accurate when used to determine needed insulation level by a uniform standard for areas with different pollutant deposits Parameter ESDD/NSDD Proved to be good with marine and soil salt pollutants Fairly hard to determine As a rule, the test insulator must be taken out of service Used widely in a number of countries Unacceptable for composite insulators Non-applicable for chemical pollutants and industrial/natural conducting wetting media Less accurate when used to determine needed insulation level by a uniform standard for areas with different pollutant deposits - under a specific set of pollution conditions, some insulator configurations can be proved superior by the ESDD/NSDD criterion and others, by the ρ method; - insulation levels can be selected on the basis of both ρ and ESDD/NSDD data with appropriate experimental data available for an area with similar pollution and wetting conditions; - at the present stage of development of an international guide on selection of outdoor insulation in polluted areas, it is believed necessary to keep using both polluting deposit parameters because PL is traditionally determined in many countries, including Russia, with the help of ρ, while in others preference is given to ESDD; - it is thought practical to generalize and analyze, under auspices of IEC WG11 TC36, all available data obtained by various researchers in order to derive reference PL vs. ρ and PL vs. ESDD/NSDD relationships for a wide range of marine, soil, industry and other pollution varieties; it is suggested also that further NP research be carried out for identification of most appropriate application areas for each polluting deposit parameter. However, some suggestions on the issue under discussion are deemed possible even now. 5. Preliminary recommendations on application of ρ and ESDD/NSDD criteria under different conditions Because it is unlikely that breakdown strength test data for field-polluted insulators would be used on a large scale in selection of external insulation, the approach followed in revision of IEC and suggesting that PL be determined from parameters of the natural polluting deposit on the insulator surface is highly commendable. Table 5 summarizes NIIPT s vision of using polluting deposit parameters for selection of insulation levels. With respect to composite insulators, the IEC standard should specify, regardless of pollution sources, the breakdown voltage of wet polluted units as the principal insulation selection parameter, to be supplemented by the criterion of specific surface conductivity of the polluting deposit on the units. 5

6 Tentative suggestions for IEC on application of ρ and ESDD/NSDD for porcelain and glass insulators under different conditions Table 5 Pollution type Principal IEC Additional IEC parameter parameter Saline soil ESDD, ρ NSDD Rural and non-industrial urban ρ ESDD/NSDD Sea spray without conducting wetting ESDD, ρ NSDD Sea spray with conducting wetting ρ ESDD/NSDD Solid industrial cementing pollution, pollution from coal/shale-burning thermal power plants ESDD, ρ NSDD Pollution from oil-burning thermal power plants ρ Chemical industry pollution ρ Petrochemical industry pollution ρ ESDD/NSDD Recommendations on determining PL from ρ are given in Table 1. As for the PL versus ESDD/NSDD relationship, the recommendations of the draft IEC WG11 TC36 document appear to be acceptable, with the exception of cases shown in Table 5. References 1. Merkhalev S. D., Solomonik E. A., Line and Substation Insulation in Polluted Atmosphere Areas. Leningrad, Energiya Publishers, 1973, 158 p. (in Russian) 2. Merkhalev S. D.. Solomonik E. A., Selection and Maintenance of Insulation in Polluted Atmosphere Areas. Energoatomizdat Publishers, Leningrad, 1983, 119 с. (in Russian) 3. Vladimirsky L. L.,. Chernevich L. V., Yakovleva T. V., Polluted line insulation studies on routes of planned long-distance power transmission lines. NIIPT Proceedings Insulation of Overhead Lines and Switchgear in Polluted Atmosphere Areas. 1983, pp (in Russian). 4. Merkhalev S. D., Vladimirsky L. L., Insulation of HVDC Overhead Lines. In HVDC Power Transmission, Energoatomizdat Publishers, Moscow, 1985, pp (in Russian). 5. Vladimirsky L. L., Selection of external insulation on the basis of field studies of soil pollution areas. NIIPT Proceedings Insulation of 110 to 1150 kv Overhead Power Transmission Lines, Leningrad, 1989, pp (in Russian). 6. Gurgenidze A. M., Solomonik E. A., Studies of polluting deposit parameters and breakdown characteristics of insulators in industrial areas. NIIPT Proceedings Insulation of 110 to 1150 kv Overhead Power Transmission Lines, Leningrad, 1989, pp (in Russian). 7. Instructions on Determination of Breakdown Characteristics of Naturally Polluted Insulators. Soyuztekhenergo, Moscow, 1977, 29 p. (in Russian). 8. Instructions on Determination of Characteristics of the Natural Pollution Layer of Insulators. Soyuztekhenergo, Moscow, p. (in Russian) 9. Instructions on Plotting of Overhead Line and Switchgear Insulation Level Maps of Polluted Atmosphere Areas. Soyuztekhenergo, Moscow, p. (in Russian). 10. National Standard GOST Electric Equipment rated at 3 kv and above. Test Procedures for Polluted External Insulation. Moscow, 1986, 23 p. (in Russian). 11. Regulations on Electric Installations. 7 th edition. Chapter 1.9 Insulation of Electric Installations. Moscow, 2002 (in Russian). 12. L. L. Vladimirsky. E. A. Solomonik. Russian Guidelines for Selection of Outdoor Insulation. 36 to WG11/Cavtat/147 6

7 1,6 Eh, kv/cm Fig. 2. String height-related flashover voltage of a string of PFE-11 insulators versus ESDD of NP deposit. 1,4 1,2 1 0,8 0,6 0,4 0,2 0 ESDD, mg/sm 2 0 0,02 0,04 0,06 0,08 0,1 0,12 0,14 0,16 0,18 0,2

8 2 Eh, kv/cm Fig. 1. String height-related flashover voltage of a string of PFE-11 insulators versus specific surface conductivity of NP deposit. 1,8 1,6 1,4 1,2 1 0,8 0,6 0,4 0,2 0 X, µsm

The Reliability Study of the Statistical Method on Insulator Dimensioning of (U)HVDC Lines with Regard to Pollution Conditions

The Reliability Study of the Statistical Method on Insulator Dimensioning of (U)HVDC Lines with Regard to Pollution Conditions 1 The Reliability Study of the Statistical Method on Insulator Dimensioning of (U)HVDC Lines with Regard to Pollution Conditions Ying Long 1, Yan Xiao 1, Zhiyi Su 2, Dong Wu 3, Urban Astrom 3 Abstract--The

More information

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions Volume 114 No. 9 217, 1-9 ISSN: 1311-88 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various

More information

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators HIGH VOLTAGE INSULATORS By JP Holtzhausen The principal dielectric used on overhead power lines is air at atmospheric pressure. The air, surrounding the bare high voltage aluminium or steel- cored aluminium

More information

Mapping HV Insulators Pollution in the Mediterranean Island of Crete

Mapping HV Insulators Pollution in the Mediterranean Island of Crete 1 Mapping HV Insulators Pollution in the Mediterranean Island of Crete D. Pylarinos, K. Siderakis, N. Mavrikakis, E. Thalassinakis Abstract The reliability of High Voltage insulators is rather important

More information

Investigation of leakage current flow through wooden poles structures on overhead distribution system

Investigation of leakage current flow through wooden poles structures on overhead distribution system Proceedings of the 7th WSEAS International Conference on Power Systems, Beijing, China, September 15-17, 2007 120 Investigation of leakage current flow through wooden poles structures on overhead distribution

More information

Instruction guide Medium Voltage equipment on sites exposed to high humidity and/or heavy pollution. Recommendations for installation and use

Instruction guide Medium Voltage equipment on sites exposed to high humidity and/or heavy pollution. Recommendations for installation and use Medium Voltage equipment on sites exposed to high humidity and/or heavy pollution Recommendations for installation and use Contents Introduction 2 Use of MV equipment 2 Normal service conditions for indoor

More information

Pins Insulator. Composite/Polymers Insulators

Pins Insulator. Composite/Polymers Insulators Composite/Polymers Insulators Electric network in India operates under very harsh environments. Industrial pollution, marshy land, hilly and unfriendly terrain, extreme weather, coastal region etc. make

More information

Si-COAT 570 RTV Silicone HVIC. Reliability & Beyond. Seminar Presentation

Si-COAT 570 RTV Silicone HVIC. Reliability & Beyond. Seminar Presentation Si-COAT 570 RTV Silicone HVIC Reliability & Beyond Seminar Presentation Overview Background & industry pressures Early validation of Si-COAT HVIC The science of Si-COAT Q&A Si-COAT HVIC : The Background

More information

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA 094: 2000 CEB STANDARD MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA Specification for MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEB Standard

More information

Polymer Cutout Testing Recommendations

Polymer Cutout Testing Recommendations 1 Polymer Cutout Testing Recommendations High Voltage Fuse Subcommittee May 2012 Frank Lambert Recommended Tests 1. Water Diffusion Tests (CAN/CSA 310 09 7.3) 2. DyePenetration (ANSI C29.13 Section 7.3)

More information

Porcelain Insulator Performance under Different Condition of Installation around Aligarh

Porcelain Insulator Performance under Different Condition of Installation around Aligarh Porcelain Insulator Performance under Different Condition of Installation around Aligarh Asfar Ali Khan and Ekram Husain Abstract Modern Society is strongly dependent on a reliable power supply. The availability

More information

Energy Division Insulators

Energy Division  Insulators Energy Division http://energy.tycoelectronics.com Insulators R Insulators Tyco Electronics Energy Division covers a wide range of polymeric, hybrid and porcelain insulators. For decades all these products

More information

General Requirements. Technical Specifications for Insulators of Transmission Lines

General Requirements. Technical Specifications for Insulators of Transmission Lines Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Insulators of Transmission

More information

Comparative Investigation of Silicone Rubber Composite and RTV Coated Glass Insulators Installed in Coastal Overhead Transmission Lines

Comparative Investigation of Silicone Rubber Composite and RTV Coated Glass Insulators Installed in Coastal Overhead Transmission Lines Comparative Investigation of Silicone Rubber Composite and RTV Coated Glass Insulators Installed in Coastal Overhead Transmission Lines Key words: glass insulators, RTV coated, leakage current, silicone

More information

Polymer Insulators and Coatings in the Cretan Power System. The Transmission Line Case

Polymer Insulators and Coatings in the Cretan Power System. The Transmission Line Case Polymer Insulators and Coatings in the Cretan Power System. The Transmission Line Case D. Pylarinos Hellenic Electricity Distribution Network Operator dpylarinos@yahoo.com K. Siderakis Technological Educational

More information

Study on the dc flashover performance of standard suspension insulator with ringshaped non-uniform pollution

Study on the dc flashover performance of standard suspension insulator with ringshaped non-uniform pollution High Voltage Research Article Study on the dc flashover performance of standard suspension insulator with ringshaped non-uniform pollution ISSN 2397-7264 Received on 28th June 2017 Revised 1st October

More information

Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester

Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester W. Payakcho, J. Grasaesom, S. Thong-om and B. Marungsri* Abstract This paper presents the experimental results

More information

TRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv

TRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv K-LINE INSULATORS LIMITED Catalogue TD-IPS TORONTO, ONTARIO, CANADA TRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission &

More information

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators Version:- 3.1 Date of Issue:- June 2014 Page 1 of 13 NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators 1. Purpose This document is the technical specification for 33kV, 66kV

More information

Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators

Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators N. Mavrikakis Faculty of Engineering Aristotle University of Thessaloniki nmavrika@auth.gr K. Siderakis

More information

Optimum Return Period of an Overhead Line Considering Reliability, Security and Availability with Respect to Extreme Icing Events

Optimum Return Period of an Overhead Line Considering Reliability, Security and Availability with Respect to Extreme Icing Events IWAIS XIV, China, May 0 Optimum Return Period of an Overhead Line Considering Reliability, Security and Availability with Respect to Extreme Icing Events Asim Haldar, Ph.D, P.Eng. ahaldar@nalcorenergy.com

More information

MOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL. GE Energy

MOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL. GE Energy MOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL Jacques Aubin GE Energy Brian D Sparling Abstract Moisture content of solid insulation is a persistent concern for power transformer

More information

Chemical analysis of insulator contaminants and Reliability improvement of T&D line for smart operation of grid under chemically polluted environment

Chemical analysis of insulator contaminants and Reliability improvement of T&D line for smart operation of grid under chemically polluted environment Chennai and Dr.MGR University Second International Conference on Sustainable Energy and Intelligent System (SEISCON 2011), Dr. M.G.R. University, Maduravoyal, Chennai, Tamil Nadu, India. July. 20-22, 2011.

More information

A Proper Design of Wind Turbine Grounding Systems under Lightning

A Proper Design of Wind Turbine Grounding Systems under Lightning A Proper Design of Wind Turbine Grounding Systems under Lightning M. A. Abd-Allah, Mahmoud N. Ali, A. Said Abstract Lightning protection systems (LPS) for wind power generation is becoming an important

More information

Study of Pre-polluting Methods on Artificial Icing Flashover Characteristics of Composite Insulators

Study of Pre-polluting Methods on Artificial Icing Flashover Characteristics of Composite Insulators IWAIS XIII, Andermatt, September 8 to 11, 2009 Study of Pre-polluting Methods on Artificial Icing Flashover Characteristics of Composite Insulators Lichun Shu 1, Xiaolin Li 2, Xingliang Jiang 1, Jianlin

More information

COASTAL INDIA. Supply & Application of: Epsilon Midsun 570 Gen-4 RTV HVIC (High Voltage Insulator Coating) and

COASTAL INDIA. Supply & Application of: Epsilon Midsun 570 Gen-4 RTV HVIC (High Voltage Insulator Coating) and Supply & Application of: Epsilon Midsun 570 Gen-4 RTV HVIC (High Voltage Insulator Coating) and Epsilon Midsun 579 RTV Anti-Corrosion Coating In COASTAL INDIA Supply & Application of 8,000kg of Epsilon

More information

Measurement of Leakage Current for Monitoring the Performance of Outdoor Insulators in Polluted Environments

Measurement of Leakage Current for Monitoring the Performance of Outdoor Insulators in Polluted Environments F E A T U R E A R T I C L E Measurement of Leakage Current for Monitoring the Performance of Outdoor Insulators in Polluted Environments Key words: insulators, pollution, leakage current, diagnostic techniques,

More information

Durability Predictions Using Early-Age Durability Index Testing

Durability Predictions Using Early-Age Durability Index Testing Durability Predictions Using Early-Age Durability Index Testing JR Mackechnie & MG Alexander Summary: Durability of reinforced concrete structures is often dependent on the corrosion of reinforcement due

More information

High Quality Porcelain Insulators for Transmission Lines

High Quality Porcelain Insulators for Transmission Lines Our Customers World Wide High Quality Porcelain Insulators for Transmission Lines 765kV KEPCO / KOREA Tangjin - Sin Ansomg 735kV H-Q / CANADA Manic - Churchill, James Bay 765kV PGCI / INDIA Kishenpur -

More information

Withlacoochee River Electric Cooperative, Inc. P.O. Box 278 Dade City, FL Billy E. Brown, Executive V.P.

Withlacoochee River Electric Cooperative, Inc. P.O. Box 278 Dade City, FL Billy E. Brown, Executive V.P. Wednesday, February 25, 2015 PSC 25 6.0343 Municipal Electric Utility and Rural Electric Cooperative Reporting Requirements Withlacoochee River Electric Cooperative, Inc. P.O. Box 278 Dade City, FL 33526-0278

More information

PRY-MOULD. High Voltage Accessories for Extruded Cables

PRY-MOULD. High Voltage Accessories for Extruded Cables PRY-MOULD High Voltage Accessories for Extruded Cables Linking the future As the worldwide leader in the cable industry, Prysmian Group believes in the effective, efficient and sustainable supply of energy

More information

Laboratory Investigation on Hydrophobicity of New Silicon Rubber Insulator under Different Environmental Conditions

Laboratory Investigation on Hydrophobicity of New Silicon Rubber Insulator under Different Environmental Conditions International Journal of Electrical & Computer Sciences IJECS-IJENS Vol: 12 No: 03 1 Laboratory Investigation on Hydrophobicity of New Silicon Rubber Insulator under Different Environmental Conditions

More information

TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS

TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS SEAL & SIGNATURE OF THE TENDERER PAGE 1 OF 11 TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS 1.0 Scope : The specification covers the manufacture,

More information

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.

More information

Technical Specification for LV ABC Fuse Switch Disconnectors

Technical Specification for LV ABC Fuse Switch Disconnectors Ergon Energy Corporation Limited Technical Specification for LV ABC Fuse ETS-06-02-02 Check this is the latest Process Zone version before use. Specification ETS 06-02-02 Ver 3 Contents 1. Purpose and

More information

9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA

9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA 9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA Technical specification for 9KV/18KV 5KA Metal oxide Lightning Arrestors without Gap. ----------------------------------------------------------------------------------------------------------------

More information

Information Document Service Proposals and Cost Estimating ID # R

Information Document Service Proposals and Cost Estimating ID # R Information Documents are not authoritative. Information Documents are for information purposes only and are intended to provide guidance. In the event of any discrepancy between an Information Document

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 220, 132 & 66 COMPOSITE SOLIDCORE STATION POST INSULATORS GETCO/E/2,1,6

More information

APEC 2016 Component Level Safety Certification in Systems- IEC /UL1577. MARK CANTRELL Senior Applications Engineer

APEC 2016 Component Level Safety Certification in Systems- IEC /UL1577. MARK CANTRELL Senior Applications Engineer APEC 2016 Component Level Safety Certification in Systems- IEC60747-17/UL1577 MARK CANTRELL Senior Applications Engineer 3/20/2016 Agenda What is safety isolation Isolation Concepts Regulatory Landscape

More information

Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing.

Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing. Midsun 570 Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing. Because the coating is highly water repellent, contaminant s cannot

More information

Understanding Extrusion

Understanding Extrusion Chris Rauwendaal Understanding Extrusion 2nd Edition Sample Chapter 2: Instrumentation and Control ISBNs 978-1-56990-453-4 1-56990-453-7 HANSER Hanser Publishers, Munich Hanser Publications, Cincinnati

More information

CIGRE C4 Colloquium on Lightning and Power System, Kuala Lumpur, May 2010

CIGRE C4 Colloquium on Lightning and Power System, Kuala Lumpur, May 2010 CIGRE C4 Colloquium on Lightning and Power System, Kuala Lumpur, 16-19 May 2010 LINE SURGE ARRESTERS ENERGY DUTY CONSIDERATIONS S. Sadovic *, D. Lepley **, E. Brocard **, J.M. George ** SUMMARY This Paper

More information

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: -

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: - SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: - 1. SCOPE: - This specification covers 11KV Disc Type & 11KV/ 22KV Pin Type Insulators for 11/22KV H.T. over head power lines. 2. APPLICABLE

More information

UNS 5kA Arrester. Certified Test Report IEC

UNS 5kA Arrester. Certified Test Report IEC CP No.: CP0504 Page 1 of 10 UNS 5kA Arrester Certified Test Report IEC 60099-4 2004 CERTIFICATION Statements made and data shown are, to the best of our knowledge and belief, correct and within the usual

More information

Substation Bus Design: Current Methods Compared with Field Results

Substation Bus Design: Current Methods Compared with Field Results Electrical Transmission and Substation Structures Conference 2009 ASCE 143 Substation Bus Design: Current Methods Compared with Field Results Keith Malmedal Ph.D. P.E. P.Eng. 1 and John Wendelburg P.E.

More information

Benchmarking and Control Indicators for Electrical Substation Projects

Benchmarking and Control Indicators for Electrical Substation Projects Benchmarking and Control Indicators for Electrical Substation Projects Submitted by: Justin R. Nettesheim A thesis submitted in partial fulfillment of the requirements for the degree of Master of Civil

More information

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008 Revisions Notes Changed note Date 1 (A) Changed template 09 / 07 / 2008 2 Changed template. Clause 12.5.4.1 hot-rolled steel added. Clause 12.5.4.2, 12.5.2.4, 12.5.3.4, 12.5.4.4, 12.5.5.4, 12.5.6.4, 12.5.7.4

More information

Evaluation of Environmental Degradation Factors for Service Life Prediction

Evaluation of Environmental Degradation Factors for Service Life Prediction Evaluation of Environmental Degradation Factors for Service Life Prediction Johann Mc Duling 1 Emile Horak Pr 2 Chris Cloete 3 T 32 ABSTRACT Evaluation of environmental degradation factors forms an integral

More information

DEPARTMENT OF DEFENSE TEST METHOD STANDARD METHOD 101, SALT ATMOSPHERE (CORROSION)

DEPARTMENT OF DEFENSE TEST METHOD STANDARD METHOD 101, SALT ATMOSPHERE (CORROSION) INCH-POUND MIL-STD-202-101 18 April 2015 SUPERSEDING MIL-STD-202G w/change 2 (IN PART) 28 June 2013 (see 6.1) DEPARTMENT OF DEFENSE TEST METHOD STANDARD METHOD 101, SALT ATMOSPHERE (CORROSION) AMSC N/A

More information

XXXXXXXXXXX Solar (XXX) Generation Interconnection

XXXXXXXXXXX Solar (XXX) Generation Interconnection Facility Study For XXXXXXXXXXX Solar (XXX) Generation Interconnection Prepared For: Randy Harlas, Substation Manager El Paso Electric Company El Paso, TX September 2010 Table of Contents 1. GENERAL...

More information

1 Assessment of water tightness of reinforced concrete blocks with basalt plastic lining and secondary protection

1 Assessment of water tightness of reinforced concrete blocks with basalt plastic lining and secondary protection MATEC Web of Conferences 7, 00 (207) DOI: 0.05/ matecconf/207700 Raising of geo ecological safety of engineering collectors: the new method of assessment of water tightness of reinforced concrete blocks

More information

Calculation accuracy of high-temperature sag for ACSR in existing lines

Calculation accuracy of high-temperature sag for ACSR in existing lines Calculation accuracy of high-temperature sag for ACSR in existing lines D. Loudon, EFLA, Norway D.A. Douglass*, DPC, LLC, USA R.G. Stephen, ESKOM, South Africa G.C. Sibilant, EPRI/UKZN, USA Abstract According

More information

Analysis of Leakage Current to Predict Insulator Flashover Using Artificial Neural Network

Analysis of Leakage Current to Predict Insulator Flashover Using Artificial Neural Network Journal of Computer Science 7 (2): 167-172, 2011 ISSN 1549-3636 2011 Science Publications Analysis of Leakage Current to Predict Insulator Flashover Using Artificial Neural Network 1 N. Narmadhai and 2

More information

TECHNICAL SPECIFICATION FOR 11 POST INSULATORS, 11 KV & 33 KV PIN INSULATORS AND 11 KV, B&S TYPE 45 KN & 70 KN DISC INSULATORS.

TECHNICAL SPECIFICATION FOR 11 POST INSULATORS, 11 KV & 33 KV PIN INSULATORS AND 11 KV, B&S TYPE 45 KN & 70 KN DISC INSULATORS. Vidyut Bhavan( 4th Floor),Bidhannagar, Block-DJ Sector-II Kolkata-700 091 Phone No.033-2359-8397 Fax No.033-2359-1921 TECHNICAL SPECIFICATION FOR 11 POST INSULATORS, 11 KV & 33 KV PIN INSULATORS AND 11

More information

Lightning Protection Practice for Large-Extended Photovoltaic Installations

Lightning Protection Practice for Large-Extended Photovoltaic Installations 202 International Conference on ightning Protection (ICP), Vienna, Austria ightning Protection Practice for arge-extended Photovoltaic Installations Dr. Nikolaos Kokkinos Research and Development Department

More information

Facilities Study. For. XXXXXXXXXXXX Wind Park Interconnection Switching Station

Facilities Study. For. XXXXXXXXXXXX Wind Park Interconnection Switching Station Facilities Study For XXXXXXXXXXXX Wind Park Interconnection Switching Station Prepared For: Randy Harlas, Substation Manager El Paso Electric Company El Paso, TX September 2010 Table of Contents CERTIFICATION...

More information

Electrostatic Precipitators (ESPs)

Electrostatic Precipitators (ESPs) EVE 402 Air Pollution Generation and Control Chapter #5 Lectures (Part 7) Electrostatic Precipitators (ESPs) The process of electrostatic precipitation involves The ionization of contaminated air flowing

More information

DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv

DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv K-LINE INSULATORS LIMITED TORONTO, ONTARIO, CANADA Catalogue D-DS DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv ISO9001 SAI GLOBAL FILE No. 000117 Distribution Silicone Insulators

More information

ELECTRICAL RESISTIVITY AS A FUNCTION OF TEMPERATURE

ELECTRICAL RESISTIVITY AS A FUNCTION OF TEMPERATURE ELECTRICAL RESISTIVITY AS A FUNCTION OF TEMPERATURE Introduction The ability of materials to conduct electric charge gives us the means to invent an amazing array of electrical and electronic devices,

More information

QUALITY CONTROL Prepared: V. van Gastel / team TenneT Reviewed: M. Müller Approved: F. Wester BACKGROUND MATERIAL...

QUALITY CONTROL Prepared: V. van Gastel / team TenneT Reviewed: M. Müller Approved: F. Wester BACKGROUND MATERIAL... POSITION PAPER STAKE HOLDER CONSULTATION PROCESS OFFSHORE GRID NL Type: Position paper Work stream Technical Topic: T.1 Voltage level Filename ONL15-058-T1_Voltage level_pp_v1 Version 1 - release for Expert

More information

How to Estimate the Cost of Painting an Exterior Masonry Wall. December 2010 TABLE OF CONTENTS SECTION 1: INTRODUCTION... 3

How to Estimate the Cost of Painting an Exterior Masonry Wall. December 2010 TABLE OF CONTENTS SECTION 1: INTRODUCTION... 3 How to Estimate the Cost of Painting an Exterior Masonry Wall December 2010 TABLE OF CONTENTS SECTION 1: INTRODUCTION... 3 Main CSI Division... 3 Specific Sub-division... 3 Brief Description... 3 SECTION

More information

SYSTEM DEVELOPMENT EXTENSIVE RURAL ELECTRIFICATION PROGRAMS - EGYPT CASE

SYSTEM DEVELOPMENT EXTENSIVE RURAL ELECTRIFICATION PROGRAMS - EGYPT CASE SYSTEM DEVELOPMENT EXTENSIVE RURAL ELECTRIFICATION PROGRAMS - EGYPT CASE ENG. EL DESOUKI M. ALI ENG. AHMED HASSAN ENG. LAILA MOHY RURAL ELECTRIFICATION AUTHORITY MINISTRY OF ELECTRICITY & ENERGY Egyptian

More information

THE ITER HEAT REJECTION CHALLENGE.

THE ITER HEAT REJECTION CHALLENGE. THE ITER HEAT REJECTION CHALLENGE Steve Ployhar 1, Warren Curd 1, Ajith Kumar 2, Giovanni Dell Orco 1, Babulal Gopalapillai 1, Dinesh Gupta 2, Hiren Patel 2, Keun-Pack Chang 1, Fan Li 1, Fabio Somboli

More information

ATTACHMENT 13 NORTHEAST-POCONO RELIABILITY PROJECT PPL DESIGN CRITERIA AND SAFETY PRACTICES

ATTACHMENT 13 NORTHEAST-POCONO RELIABILITY PROJECT PPL DESIGN CRITERIA AND SAFETY PRACTICES ATTACHMENT 13 NORTHEAST-POCONO RELIABILITY PROJECT PPL DESIGN CRITERIA AND SAFETY PRACTICES The National Electrical Safety Code (NESC) is a set of rules to safeguard people during the installation, operation,

More information

Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols

Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols Ergon Energy Corporation Limited Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols ETS-01-05-01 Check this is the latest Process Zone version before use. Specification ETS 01-05-01

More information

Plant Utilities and Energy Efficiency CH505

Plant Utilities and Energy Efficiency CH505 Plant Utilities and Energy Efficiency CH505 Teaching Scheme Course code CH505 Course Name Plant Utilities and Energy Efficiency Teaching scheme L T P Credit 3 0 0 3 Process Process is simply a method by

More information

INFLUENCE OF HEAT SOURCE LOCATION ON AIR TEMPERATURES IN SEALED MV SWITCHGEAR

INFLUENCE OF HEAT SOURCE LOCATION ON AIR TEMPERATURES IN SEALED MV SWITCHGEAR INFLUENCE OF HEAT SOURCE LOCATION ON AIR TEMPERATURES IN SEALED MV SWITCHGEAR Elin FJELD Wilhelm RONDEEL Knut VAAGSAETHER Univ.Coll. of Southeast Norway USN Norway USN - Norway elin.fjeld@usn.no wilhelm.rondeel@usn.no

More information

CCC Services for oil-filled- and XLPE-Cable Systems

CCC Services for oil-filled- and XLPE-Cable Systems sc CCC Services for oil-filled- and XLPE-Cable Systems Service Programme for Cable Systems As a supplier of MV- and HV-cable systems with several decades of experience, CCC GmbH Berlin offers the full

More information

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

SECTION N EQUIPMENT FOR SUBSTATION MAINTENANCE

SECTION N EQUIPMENT FOR SUBSTATION MAINTENANCE Page 89 SECTION N INDEX DESCRIPTION PAGE - INSULATED MODULAR RITZGLAS SCAFFOLD 90 - MODULAR RITZGLAS SCAFFOLD - MAIN PARTS 91 - TRUCK MOUNTED INSULATED LADDER FOR HOT LINES UP TO 500 kv WITH ROTATION SUPPORT

More information

Optimizing the Features of a Customizable Air-Cooled Chiller

Optimizing the Features of a Customizable Air-Cooled Chiller Carrier Engineering Newsletter Volume 5, Issue 2 Optimizing the Features of a Customizable Air-Cooled Chiller The use of air-cooled chillers in process and comfort cooling applications has been steadily

More information

Module 5 Measurement and Processing of Meteorological Data

Module 5 Measurement and Processing of Meteorological Data Module 5 Measurement and Processing of Meteorological Data 5.1 Evaporation and Evapotranspiration 5.1.1 Measurement of Evaporation 5.1.2 Pan Evaporimeters 5.1.3 Processing of Pan Evaporation Data 5.1.4

More information

Cooperation in the Energy Sector

Cooperation in the Energy Sector MINISTRY OF ENERGY AND INDUSTRY OF THE KYRGYZ REPUBLIC Cooperation in the Energy Sector Ministry of Energy and Industry of the Kyrgyz Republic Speaker: Aibek R. Kaliev, Deputy Minister Bishkek, 2014 Following

More information

ENVIRONMENTAL IMPACT ASSESSMENT AND YOU

ENVIRONMENTAL IMPACT ASSESSMENT AND YOU ENVIRONMENTAL IMPACT ASSESSMENT AND YOU PARTICIPATING IN PUBLIC CONSULTATIONS FOR: COAL FUELED THERMAL POWER PLANTS C A G Citizen consumer and civic Action Group 1. What are Thermal Power Plants? Electricity

More information

Main technical data for standard sizes of pit furnaces

Main technical data for standard sizes of pit furnaces Technological applications of pit furnaces Gas carburizing Hardening Bright Annealing Normalising Carbonitriding Typical load types Automotive industry: crankshafts, camshafts, pistons, pins, pumps, engine

More information

ACCR. More Amps. More Confidence. Glenmar E. Cambri, REE Senior Applications Engineer

ACCR. More Amps. More Confidence. Glenmar E. Cambri, REE Senior Applications Engineer TM ACCR More Amps More Confidence Glenmar E. Cambri, REE Senior Applications Engineer What is 3M ACCR? A high voltage, overhead transmission conductor designed as a drop-in replacement for ACSR and other

More information

Innovative Process for Comprehensive Treatment of Liquid Radioactive Waste

Innovative Process for Comprehensive Treatment of Liquid Radioactive Waste Innovative Process for Comprehensive Treatment of Liquid Radioactive Waste - 12551 R.A. Penzin, G.A. Sarychev All-Russia Scientific Research Institute of Chemical Technology (VNIIKHT), Moscow, Russia,

More information

Nip / Tuck Method A Solution to Providing Additional Conductor-to-Ground Clearances for Transmission Lines

Nip / Tuck Method A Solution to Providing Additional Conductor-to-Ground Clearances for Transmission Lines Nip / Tuck Method A Solution to Providing Additional Conductor-to-Ground Clearances for Transmission Lines Michael E Belanger, P.E., M.ASCE Garrett E Luszczki, E.I., A.M.ASCE TRC Augusta, Maine Presented

More information

Power Zone Center. Your solution for power distribution and control systems

Power Zone Center. Your solution for power distribution and control systems Power Zone Center Your solution for power distribution and control systems The Strength of One Powerful When you need to install a new power distribution center in your facility, you need it done in fastest

More information

Electric Field and Potential Distribution in a 420 kv Novel Unibody Composite Cross-Arm

Electric Field and Potential Distribution in a 420 kv Novel Unibody Composite Cross-Arm 4 th Nordic Insulation Symposium on Materials, Components and Diagnostics Electric Field and Potential Distribution in a 4 kv Novel Unibody Composite Cross-Arm Jahangiri, Tohid ; Bak, Claus Leth ; Faria

More information

PES ESSENTIAL. PES: Europe

PES ESSENTIAL. PES: Europe PES ESSENTIAL 96 PES: Europe The cost of wind Like other renewable energy technologies, wind is capital intensive, but has no fuel costs. The key parameters governing wind power economics are the investment

More information

EIGHT POINT WIND ENERGY CENTER

EIGHT POINT WIND ENERGY CENTER EIGHT POINT WIND ENERGY CENTER Case No. 16 F 0062 1001.11 Exhibit 11 Preliminary Design Drawings Contents Exhibit 11: Preliminary Design Drawings... 1 11(a) Site Plan... 1 11(b) Construction Operations

More information

Closed-Cell Spray Foam Insulation. Performance in Residential and Commercial Buildings During Adverse Weather

Closed-Cell Spray Foam Insulation. Performance in Residential and Commercial Buildings During Adverse Weather Closed-Cell Spray Foam Insulation Performance in Residential and Commercial Buildings During Adverse Weather July, 2006 Although all statements and information contained herein are believed to be accurate

More information

Brugg Cables High Voltage Accessories. Swiss solutions for independent applications.

Brugg Cables High Voltage Accessories. Swiss solutions for independent applications. Brugg Cables High Voltage Accessories. Swiss solutions for independent applications. Fact Book High Voltage Accessories Brugg Cables Business Unit High Voltage Accessories Dr. Ruben Vogelsang Head of Product

More information

The complete guide to transformers and packaged substations

The complete guide to transformers and packaged substations LAND LOGICAL POWER The complete guide to transformers and packaged substations Contents Land Logical Power transformers An introduction to the complete range of Land Logical Power transformers and package

More information

Renewable Energy Contribution to Energy Independency in Palestine. Eng. Emad Khader July 2016

Renewable Energy Contribution to Energy Independency in Palestine. Eng. Emad Khader July 2016 Renewable Energy Contribution to Energy Independency in Palestine Eng. Emad Khader July 2016 emad_khader@yahoo.com 1 Contents Part 1: Background : geography, climate, demography and economy. Part 2: Electric

More information

Japanese ODA Loan. Ex-Ante evaluation

Japanese ODA Loan. Ex-Ante evaluation Japanese ODA Loan Ex-Ante evaluation 1. Project Country: People's Republic of Bangladesh Name of the Project: Matarbari Ultra Super Critical Coal-Fired Power Project (I) Loan Agreement: June 16, 2014 Loan

More information

P.G student, Civil Engineering department, Saraswati College of Engineering, Maharashtra, India 1

P.G student, Civil Engineering department, Saraswati College of Engineering, Maharashtra, India 1 International Journal of Scientific & Engineering Research, Volume 6, Issue 1, December-15 145 Analysis and Design of kv transmission line tower with hot rolled and cold formed section Supriya Khedkar1,

More information

QUALITY ASSURANCE MANUAL FOR APPLICATORS OF ELASTOMERIC SHEET LININGS

QUALITY ASSURANCE MANUAL FOR APPLICATORS OF ELASTOMERIC SHEET LININGS QUALITY ASSURANCE MANUAL FOR APPLICATORS OF ELASTOMERIC SHEET LININGS 1.0 Purpose To establish a recommended quality assurance program for applicators of elastomeric sheet linings. 2.0 Scope This bulletin

More information

Studies of Mercury Capture on Fly Ash: Examples From Power Plants Burning Kentucky Coals

Studies of Mercury Capture on Fly Ash: Examples From Power Plants Burning Kentucky Coals Studies of Mercury Capture on Fly Ash: Examples From Power Plants Burning Kentucky Coals James C. Hower 1, Tanaporn Sakulpitakphon 1, Darrell N. Taulbee 1, and M. Mercedes Maroto-Valer 2 1 University of

More information

Research and Application Study on Accident-Based 3D Power Station Simulation Technology

Research and Application Study on Accident-Based 3D Power Station Simulation Technology International Conference on Electromechanical Control Technology and Transportation (ICECTT 2015) Research and Application Study on Accident-Based 3D Power Station Simulation Technology Tie Li, Xiaoming

More information

ENERGOCENTROMONTAZH INTERNATIONAL Ltd. (ECM Inter) Steam and GT power plants

ENERGOCENTROMONTAZH INTERNATIONAL Ltd. (ECM Inter) Steam and GT power plants ENERGOCENTROMONTAZH INTERNATIONAL Ltd. (ECM Inter) Steam and GT power plants 1 ECM Group overview Steam, GT & combined cycle power plants Design, consulting, supply of equipment, supervision, testing,

More information

Ontario ENGINEERING STANDARD SPECIFICATION 1/10 REV. ELECTRICAL DISTRIBUTION HIGH VOLTAGE SUBSTATION GROUNDING AND BONDING. Approved by.

Ontario ENGINEERING STANDARD SPECIFICATION 1/10 REV. ELECTRICAL DISTRIBUTION HIGH VOLTAGE SUBSTATION GROUNDING AND BONDING. Approved by. /0 Rev Description Revision by Approved by Issue Date YYYY/MM/DD New Format Replaces 5322-0.0. T.C. 206/02/09 T.C. 206/03/02 206/03/02 2/0.0 PURPOSE This specification describes the minimum requirements

More information

SULFATE AND CHLORIDE RESISTANCE PROPERTIES OF PORTLAND CEMENT BLENDS

SULFATE AND CHLORIDE RESISTANCE PROPERTIES OF PORTLAND CEMENT BLENDS Proceedings of the 4 th International Conference on Civil Engineering for Sustainable Development (ICCESD 2018), 9~11 February 2018, KUET, Khulna, Bangladesh (ISBN-978-984-34-3502-6) SULFATE AND CHLORIDE

More information

DECISION 1 SCOPE AND CONSIDERATIONS... 2

DECISION 1 SCOPE AND CONSIDERATIONS... 2 MEMORANDUM TO Windfarm developers FROM TenneT TSO SUBJECT Overplanting - version: Hollandse Kust (zuid) DECISION FOR INFORMATION ONLY QUALITY CONTROL Prepared: Daniël Vree Reviewed: Frank de Vries 19.09.2017

More information

EnergoFichtner. General Information. your reliable partner in power industry

EnergoFichtner. General Information. your reliable partner in power industry OOO EnergoFichtner Ul. Marksistskaya 3, str.2, Moscow, 109147, Russia Tеl./Fax: +7 (495) 661-5957 www.energofichtner.ru EnergoFichtner your reliable partner in power industry General Information The Group

More information

SCADA/EMS for Unified Power System of Russia

SCADA/EMS for Unified Power System of Russia 1 SCADA/EMS for Unified Power System of Russia Oxana Yakovleva Head of SCADA/EMS PIU, System Operator for UES of Russia Vladimir Calovic KEMA Consulting EPCC - les Diablerets, Switzerland, June 8, 2005

More information

General Plan OXYGEN SERVICE CONTAINER 2005 Version 1.02

General Plan OXYGEN SERVICE CONTAINER 2005 Version 1.02 - 1 - General Plan OXYGEN SERVICE CONTAINER 2005 Version 1.02 Laser Gas Author: Rauno Hakala Distribution: Printed: Document s state: version 1.02 Edited: 07.12.2003 - 2 - i) Version history Version Date

More information

Gas-insulated medium-voltage switchgear. for wind parks. Answers for energy.

Gas-insulated medium-voltage switchgear. for wind parks. Answers for energy. Gas-insulated medium-voltage switchgear for wind parks Answers for energy. Switchgear for wind turbines: 8DH10 up to 24 kv, up to 20 ka, up to 1,250 A up to 17.5 kv, up to 25 ka, up to 1,250 A Best performance

More information