Natural Ventilation of Buildings through Light Shafts. Design-Based Solution Proposals

Size: px
Start display at page:

Download "Natural Ventilation of Buildings through Light Shafts. Design-Based Solution Proposals"

Transcription

1 IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Natural Ventilation of Buildings through Light Shafts. Design-Based Solution Proposals To cite this article: Miguel Ángel Padilla-Marcos et al 2017 IOP Conf. Ser.: Mater. Sci. Eng View the article online for updates and enhancements. Related content - Energy saving due to natural ventilation in housing blocks in Madrid RA González-Lezcano and S Hormigos- Jiménez - Experimental research on the indoor temperature and humidity fields in radiant ceiling air-conditioning system under natural ventilation Tao Huang, Yutong Xiang and Yonghong Wang - A mechanism to reduce energy waste in the post-execution of GPU applications Emmanuell D Carreño, Adiel S Sarates Jr and Philippe O A Navaux This content was downloaded from IP address on 15/08/2018 at 18:33

2 Natural Ventilation of Buildings through Light Shafts. Design- Based Solution Proposals Miguel Ángel Padilla-Marcos 1, Alberto Meiss 1, Jesús Feijó-Muñoz 1 1 Av. Salamanca, 18. Universidad de Valladolid Valladolid. Spain miguelangel.padilla@uva.es Abstract. This work analyses how the built environment affects the quality of the air to be introduced into buildings from light shafts. Several factors such as urban environment and building design intervene in the ability of the light shaft to produce its air change process. Urban areas continuously pollute the air in cities which affects the human health and the environment sustainability. Poor air quality outside buildings supposes a big energy waste to promote an acceptable air quality inside buildings. That requires a large flow rate to maintain the indoor air quality which is translated to an energy efficiency term. The main objective focuses on the impact of standardized architecture design in the quality of the indoor air dependent on the air change in the light shaft. The air change capacity of the outdoor space is numbered analysed using the concept of air change efficiency (ACE). ACE is determined by the built environment, the wind conditions and the design of the building containing light shafts. This concept is comparatively evaluated inside a control domain virtually defined to obtain the mean age of the air for a known air volume. The longer the light shaft in the wind direction is, the better the ACE is compared with other options. Light shafts up to 12 metres high are the most suitable in order to obtain acceptable efficiency results. Other studied cases verify that assumption. Different simplified tools for the technicians to evaluate the design of buildings containing light shafts are proposed. Some strategies of architectural design of buildings with light shafts to be used for ventilation are presented. 1. Introduction Population growth led to the uncontrolled urban development of cities in the 20th century. Peripheral expansion and urban centres have been constructed using architectural models that often do not improve the quality of life of their users. These shortcomings extent to various fields of architecture and are usually solved by the use of technologies that imply a high economic and energy expenditure (active measures). However, solutions related to architectural design (passive measures) can help to improve living conditions without requiring other resources. Thus, the criteria for the efficient design of buildings and their relationship with the environment can improve the behaviour of the outside air. Such improvements imply a greater airflow in outdoor spaces, which directly affects the safety, healthiness, comfort and energy consumption characteristics of indoor spaces with air conditioning. The urban configuration of buildings, empty spaces, courtyards and urban corridors [1,2] causes a moving air to become obstructed in the lower layers of the atmosphere and determines the airflow patterns in those areas [3 6], hindering the process of air exchange, particularly in confined outdoor Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI. Published under licence by Ltd 1

3 spaces between built volumes [2,3,7 9]. Accordingly, geometry has an influence on the quality of the air volume that constitutes the exterior space of buildings [3,10]. By analysing the behaviour of airflow patterns, one can relate the shape, orientation and composition of ideal building groups with their impact on air quality in confined outdoor spaces. The efficiency of these architectural designs can be numerically quantified by studying the process of change in air quality as a result of displacement. The shape of a building, volume of air, and wind exposure are fundamental factors that determine air patterns in exterior spaces [11,12]. The influence of the architectural form on the air exchange efficiency was already shown [13]. However, the impact of wind at different velocities on interior air circulation has not been analysed yet. Wind constitutes the primary aerodynamic phenomenon in urban areas [14,15], and buildings can alter its trajectory [4]. Air intake in outdoor spaces of buildings depends on their wind exposure, wind velocity [6], and the shape of the building. The building geometry affects air drag and displacement in such spaces [10]. In principle, outdoor air is considered to be of better quality than the air within buildings. This quality depends on multiple conditions [14,16], such as wind velocity and its predominant direction, presence of vegetable mass [17,18], and pollution due to factories or high traffic vehicular roadways [3,19,20]. In many cases, streets, urban corridors, and green spaces allow for a good exchange with atmospheric air (Figure 1), which facilitates obtaining interior air of acceptable quality [12]. However, confined spaces, such as light shafts, reduce access to the air for outdoor ventilation because there are less surfaces in contact with the atmospheric air [2,10]. Hence, it is necessary to guarantee a progressive, continual [21,22] exchange of air volume to obtain an acceptable quality that will be used in buildings indoor ventilation [3,11,12]. The objective of the present study is to analyse the air behaviour in different building dimensions containing confined spaces such as light shafts when the wind velocity is variable. The purpose is to create guidelines that define the relationship between wind velocity and exterior ventilation efficiency and quality in different urban architectural models [23,24]. The selected architectural forms match the types present in contemporary cities and whose designs are part of the architectural tradition of recent centuries [19,25]. The present study is also narrowly related with energy factors due to the increased repercussions of airflow exchange on electricity consumption in buildings [3,10,26 28]. It is advisable to obtain an optimal air quality in confined spaces that provide air for interior ventilation. This would allow for a reduction in airflow required to dilute interior contaminants, which would lower the energy impact involved in the air exchange process [11,23,29]. Energy term is not treated in this work. 2. Fundamentals: outdoors air change efficiency Boundary conditions allow linking the physical properties of the model with air parameters (internal friction, height of boundary layer, etc.) [30 32]. These parameters affect its movement in the free state and therefore, within the confined volume being studied [4], which allow, to a greater or lesser degree, for moving air to adhere, detach, or flow at higher or lower velocities along the surfaces that enclose the spaces [6,33 35]. Continuous variation of wind direction and velocity in short time periods makes it essentially impossible to exactly predict its behaviour [36,37]. Any study of outdoor air requires the assumption of several premises that significantly reduce the complexity of the physical model [5,38,39]. The simplification consists of reducing the random temporal variables to one variable dependent on the height over the earth s surface, which is constant in time. In this way, the physical definition of the contour conditions of the fluid is modelled through vertical profiles of wind speed, intensity, and turbulence dissipation [16,24,40 44] (Equations 1-5), 2

4 (1).. (2) (3).. if (4)... if (5) where U is the velocity (m/s) at height z (m); U* is the friction velocity (m/s); k is the von Karman dimensionless constant (k 0.41); d is the displacement height (m); z 0 is the roughness height of the physical medium (m); k nw is the near-wall turbulence (m 2 /s 2 ); U m is the mean velocity profile (m/s); α is the power profile equivalent index; ρ is the air density (1.204 kg/m 3 to K); h t is the total height of the simulated model (m); μ is the dynamic viscosity of air ( N s/m 2 to K); k e is the turbulent energy (m 2 /s 2 ); ε is the turbulence dissipation (m 2 /s 2 ); and Cμ is the dimensionless empirical constant (determined by Launder and Spalding (1974) [44] with an approximate value of 0.09). The wind profile defines the vertical distribution of speed and turbulence [6,31,41,45,46]. These profiles provide dynamic and kinetic energy for the distribution of non-uniform pressure over the constructed surfaces [5,16]. Turbulent phenomena produce chaotic air displacement, which facilitates vortex formation and air stagnation in the areas protected from the direct wind [1,10]. Airflow behaviour close to and in each space constitutes the efficiency pattern study. Ideal ventilation efficiency [47] is obtained from the minimum required atmospheric (clean) airflow to maintain optimal comfort and hygiene conditions in the space. The relationship between outdoor exchange efficiency and the design of outdoor spaces can be expressed by the geometric efficiency [2,10,35,48]. The age of the air concept is used to assess the average time that an air particle takes to travel from one point to another in a model. Each particle s trajectory originates in a succession of vector changes and different external parameters that intervene in the behavioural pattern [44]. A ventilation efficiency value for the volume is obtained from the residence time ratio (Equations 6 and 7). This ratio analyses the mean age of the air contained in a volume and the minimum exchange time obtained in the model s outflow (Equations 8) [47], (6) 2 (7) 1 (8), where τ e is the minimum exchange time; V is the volume of the analysed air; Q is the control volume balanced airflow; τ t is the mean age of outflow air (residence time of air in the control volume); τ is the mean age of the air volume; and ε a is the outdoor air exchange efficiency. 3

5 The boundary of the model to be considered is based on previous studies and on the air volumes that warrant analysis [49]. The study of ventilation efficiencies in exterior spaces requires the definition of a simplified model of a turbulence simulation [50]. In this way, we can determine the averaged integration of the variables based on contour conditions [40 42], ignoring extreme values that could result from the chaotic, natural effect of the wind [22,50,51]. In this study, the RANS model (Reynoldsaveraged Navier-Stokes) is selected to obtain mean velocity values, turbulence coefficients, and age of the air parcels [52 55] as opposed to instantaneously calculating variables (for example, through the LES model large eddy simulation) [56,57]. 3. Methodology Previous research has validated the outdoor air change efficiency concept inside light shafts [35]. It is crucial to determine the field of action, choosing a specific domain, named control domain (CD). CD delimits the outdoor space at various levels of observation [43] into a bigger computational domain (CPD) that represents the experimental wind tunnel section. CPD covers a huge part of the urban environment around the building to be analysed. Dimensions of the CPD covers more than 5 H times around in the horizontal plane and up to 15 H times downstream from the centre of the light shaft. In the vertical dimension, CPD reaches up to 6 H as was already said by authors such as Sharples and Bensalem (2001) [58] and Li and Ward (2007) [36]. A proper choice for the CD, inside the CPD, ensures the correct representation of the air flow in the immediate vicinity of the building and its influence on the air distribution in the light shaft. The choice of an ideal CD based on proportions relative to a reference dimension of the building was investigated for the air change efficiency application [43]. For buildings with a light shaft, the building width (c r ) was chosen as the reference dimension (Figure 1). This choice allows the air change efficiency of the air volume contained in the light shaft to be evaluated, delimiting the surfaces through which the air enters and exits the domain. This CD reduces computational costs from the whole CPD and keeps the evaluation reliable. It was assumed that the flow equilibrium condition was satisfied (Figure 2). Figure 1. Dimensions of the control domain (CD) based on the light shaft geometry 4

6 Figure 2. Air behaviour of the control domain (CD) for the building and the light shaft geometry To evaluate the adequacy of a light shaft design in regard to air change, the flow field at the top of the light shaft must be determined [45,46]. This distribution provides information on the behaviour of the air at the top of the light shaft and the motion that will be generated in the space by means of the vertical flow. The vertical flow field at the top of the light shaft was obtained from the signs of the velocities, which are generated by the aerodynamics of the building when exposed to wind. The 175 evaluated cases assumed that the building centreline width (c r ) was 10 m. The horizontal dimensions L and W were varied between 2 m and 6 m, and the height H was varied between 6 m and 42 m (1 < H/L < 21). The used boundary conditions are included in Table 1. Table 1: Boundary conditions for the analysis air characteristics (fluid) boundary conditions of the inlet model height (H) m reference velocity m/s air density kg/m³ reference height m temperature K turbulence energy equations 2 and 3 Reynolds number kinetic viscosity dynamic viscosity 1.515E E- 06 turbulence dissipation equations 4 and 5 m²/s turbulence height m N s/m ² von Karman constant wall conditions isothermal boundary conditions for the floor roughness height m exponential law displacement height m friction velocity m/s temperature K roughness height m upper and lateral walls defined according to limits without symmetry displacement height m From the efficiency values obtained, it was determined that the greatest changes in efficiency were achieved by means of varying the longitudinal dimension. The complexity of the analysis makes it difficult to be represented with mathematical functions. The obtained results confirmed the effect of the 5

7 building and light shaft dimensions on the air quality distribution. However, the effects of parameters such as the wind velocity and the building width, which affect the tendency of the flow over the roof to follow the roof line, were not analysed. 4. Results and discussions The results indicate that the light shaft transverse dimension (W) has a negligible effect on the process efficiency (εª). The height (H) and the light shaft longitudinal dimension (L) significantly affect the air exchange, defining the H/L ratio, where the efficiency increases as the length increases and as the height decreases. Efficiency values between 1.06% and 42.62% were obtained; these were the extreme cases. The wind blowing over the top of the light shaft affects the movement of air and pollutants in the light shaft, affecting the air change process [2]. The wind velocity and the forces and viscous stresses facilitate the entrainment of air that has changed direction after colliding with an obstruction and allow the flow direction to return to the wind direction. When air in motion encounters a building, the flow is deflected. The change in the direction of the velocity vector of the air near the cornice line of the building is promoted by a predominantly ascending vertical component. The effect of the wind on the confined volume of air depends on the change in the flow over the building cornice. When the velocity of the air that interacts with the air in the light shaft changes, the flow field in the plane at the top of the light shaft is altered (Figure 3). This interaction entails a change in the distribution of the mass transfer that depends on the wind velocity [8]. The distance between the cornice and the opening of the light shaft affects the air change process. The light shaft axial length (L) regarding the region where the flow attachment occurs depends on the relationship between velocity and width. A vortex forms at the top of the light shaft that facilitates the change of the air volume dependant on the H/L ratio. The effects of the building shape, its location and the wind velocity on this vortex were investigated (Figure 3). Figure 3. Analysis of the air flow in the light shaft 6

8 The domain defined by the light shaft dimensions was evaluated as if it were an indoor space isolated from the ambient air. The influence of the air flow at the top of the light shaft affects the displacement of the air within the light shaft Effect of wind velocity Table 2 shows the air change efficiency for 9 light shaft sizes with 5 wind velocities that were analysed with the validated CFD models. The reference value was the air change efficiency for perfect mixing at 50 %. light shaft dimensions Table 2: Air change efficiency for W= 3 m H/L wind velocity 0.75 m/s 1.50 m/s 3.00 m/s 6.00 m/s 9.00 m/s 2x 3y 9, % 5.09% 3.69% 3.34% 2.77% 3x 3y 6,0 9.89% 5.13% 3.32% 3.27% 2.98% 4x 3y 4, % 6.08% 3.70% 3.75% 3.73% 5x 3y 3, % 8.13% 4.87% 4.48% 4.41% 6x 3y 3, % 11.62% 6.81% 6.15% 5.99% mean efficiency 11.89% 7.21% 4.48% 4.20% 3.98% mixing model efficiency 50.00% The air change efficiency decreased as the wind velocity increased. Furthermore, the air change efficiency increased as the longitudinal dimension (L) increased. However, when the light shaft length was fixed and the width (W) was varied (Table 3), the variation in the efficiency was sufficiently small that mean values could be calculated. Table 3: Air change efficiency for L= 3 m light shaft wind velocity H/L dimensions 0.75 m/s 1.50 m/s 3.00 m/s 6.00 m/s 9.00 m/s 3x 2y 10.52% 5.14% 2.91% 2.76% 2.45% 3x 3y 9.89% 5.13% 3.32% 3.27% 2.98% 3x 4y 6,0 9.63% 4.81% 3.54% 3.63% 3.40% 3x 5y 9.50% 5.36% 3.76% 3.94% 3.72% 3x 6y 9.39% 5.46% 4.13% 4.32% 4.06% mean efficiency 9.79% 5.18% 3.53% 3.58% 3.32% mixing model efficiency 50.00% As the wind velocity increases, the drag force from the deflection of the air next to the cornice increases, generating a curvilinear trajectory. The extent of this deflection and the effect that it has on the mixing of the air in the light shaft depends on the wind velocity, as shown in Figure 4. Turbulence and drag cause a partial return flow of the air that has already been mixed. The efficiency increased in those cases in which the formation of a vortex at the opening of the light shaft caused the air to flow toward the region that did not affect the quality of the light shaft air. The results indicate that the effect of the vortex decreases at higher wind velocities, reducing the renewal of air in the light shaft. The vertical flow at the cornice increases with the wind velocity so that the vector component remains proportional, resulting in a similar attachment in all cases. However, the resulting intensity depends on the wind velocity; i.e., the greater the horizontal component of wind velocity, the greater the airflow across the opening. 7

9 Figure 4. Influence of the wind on the air in the light shaft The air change increases as the wind velocity increases. However, the diffusion of the clean air is reduced because of its trajectory, reducing the ratio between the ideal and actual renewal times, thereby affecting the efficiency. Therefore, the mean age of the air in the light shaft decreases as the wind velocity increases and is independent of the calculated minimum air residence time. As expected, it can be observed from the age of the air distribution that there is a descending vertical gradient, with the maximum age of the air at the bottom of the light shaft and the minimum value at the top, verifying that the value decreases as the velocity increases. The trajectories followed by the stream lines in the interior of the light shaft reflect the air change caused by the dynamic influence of the wind. At higher velocities, the air change affects the age, but the mixing of young incoming fresh air from the flow into the city is hindered by the deflection effect. The results show the insignificant influence of the light shaft transverse dimension (W). Maximum errors of ± 0.34% were obtained in the analysis of the effect of velocity for a fixed length. The error for the various wind velocities was ± 5.69%, which implies a relative variation of ± 47.86% with respect to the maximum of the resulting mean efficiencies. Thus, it can be concluded that the mean efficiency approximately corresponds to the efficiency of a 3 m 3 m light shaft. In addition, since the light shaft has a square shape (1:1 ratio), the movement of air in the space can be evaluated regardless of the orientation of the wind what directly affects the design of the building Discussion of results and architectonic application The ratio between the height of the light shaft and the length in the wind direction (H/L) corresponds to the number of vortices which are generated inside. This non-dimensional parameter defined the ability of the air to penetrate from the top into the light shaft which is used to determine some design strategies. The rates selected for this study demonstrate that the larger this ratio is, the more difficult it is for the air to penetrate. These rates eventually affected the efficiency index. In general, large centreline widths joined to light shafts with small proportional ratios should be selected. Moreover, results also show the relationship between geometry and wind velocity, which would allow designers to compare some different hypothetical cases in several climate conditions. The 8

10 results classified by the evaluated parameter, which entailed the proposal for comparative building design strategies, can be summarized depending on its impact. It was shown that the efficiency varies inversely proportional with the wind velocity (Uref) and directly proportional with the centreline building width (cr) and the light shaft dimension parallel to the wind direction (L). 5. Conclusions The efficiency results prove numerically that the light shafts are generally heavily deficient in their air ventilation. The analysis of the residential light shaft cases in Spain, of sizes up to 6 m long, 6 m wide, and 42 meters high, values a bracket of efficiencies dependent on its dimensions. The analysis of design impact on the air renovation quality, along with the methodology and hypotheses applied make it possible to verify that its mean efficiency improves as the dimension on the wind s direction gets bigger and the height gets smaller. Independently of the mean efficiency in the whole light shaft, it is stated that air masses at its higher portion present a greater capacity of renovation. The mean efficiency in the lower third of the light shaft encompasses approximately half of the mean efficiency of the light shaft, which impacts negatively on the contained air quality. It can be graphically observed that the efficiency pattern on the horizontal planes at the light shafts keeps a regular tendency in approximately lineal strata. The efficiency varies co-directionally to the wind. Therefore, the efficiency analysis simplification of a vertical plane that encompasses the longitudinal computational domain is justified, which leads to the bi-dimensional simulation proposal. Although the obtained results of initial analysis suggest that the wind velocity has a negligible effect on the mixing process with outdoors incoming air, it has been verified that it has an impact on air renovation quality. It varies irregularly, enabling the definition of influence patterns as the efficiency gradient tends to stabilize at greater speeds. For a series of light shafts 3 meters wide and 18 meters high, a % mean efficiency is obtained, for a speed of 0.75 m/s and a 3.98 % mean efficiency for a speed of 9 m/s. Acknowledgment(s) This study has been developed with the technical support of the national research project The outdoor space of the DB HS3 "indoor air quality": development of alternative solutions (reference: VIVIENDA ) funded by the Ministry of Housing, whose endowment enabled the CFD simulations. This study represented part of the methodology developed by the Spanish national research project Energy impact of airtightness level in residential buildings in Spain: analysis and characterization of the air leakage. INFILES (reference: BIA R ) funded by the Spanish Ministry of Economy and Competitiveness, which is use to evaluate the impact of the outdoor air quality in the building airtightness. We are particularly grateful for the data and series of experimental results contributed by the Meteorological Institute of Universität Hamburg via the CEDVAL project for validation of the study. References [1] Salizzoni P, Soulhac L, Mejean P. Street canyon ventilation and atmospheric turbulence. Atmos Environ. 2009;43(32): [2] Hall DJ, Walker S, Spanton AM. Dispersion from courtyards and other enclosed spaces. Atmos Environ. 1999;33(8): [3] Ahmad Zaki S, Hagishima A, Tanimoto J. Experimental study of wind-induced ventilation in urban building of cube arrays with various layouts. J Wind Eng Ind Aerodyn. 2012;103: [4] Salizzoni P, Van Liefferinge R, Soulhac L, Mejean P, Perkins RJ. Influence of wall roughness on the dispersion of a passive scalar in a turbulent boundary layer. Atmos Environ. 2009;43(3):

11 [5] Theurer W, Baeehlin W, Plate EJ. Model Study of the Development of Boundary Layers Above Urban Areas. 1992;44:41 4. [6] Ahmad K, Khare M, Chaudhry KK. Wind tunnel simulation studies on dispersion at urban street canyons and intersections - A review. J Wind Eng Ind Aerodyn. 2005;93(9): [7] Blocken B, Carmeliet J, Stathopoulos T. CFD evaluation of wind speed conditions in passages between parallel buildings-effect of wall-function roughness modifications for the atmospheric boundary layer flow. J Wind Eng Ind Aerodyn. 2007;95(9 11): [8] Kubota T, Miura M, Tominaga Y, Mochida A. Wind tunnel tests on the relationship between building density and pedestrian-level wind velocity: Development of guidelines for realizing acceptable wind environment in residential neighborhoods. Build Environ. 2008;43(10): [9] Kastner-Klein P, Berkowicz R, Britter R. The influence of street architecture on flow and dispersion in street canyons. Meteorol Atmos Phys. 2004;87(1 3): [10] Vardoulakis S, Fisher BEA, Pericleous K, Gonzalez-Flesca N. Modelling air quality in street canyons: A review. Atmos Environ. 2003;37(2): [11] Yassin MF. Impact of height and shape of building roof on air quality in urban street canyons. Atmos Environ. 2011;45(29): [12] Padilla-Marcos MÁ, Feijó-Muñoz J, Meiss A. Confined-air quality based on the geometric efficiency of urban outdoor spaces. Cases study. Int J Vent. 2016;15(1): [13] Skote M, Sandberg M, Westerberg U, Claesson L, Johansson A V. Numerical and experimental studies of wind environment in an urban morphology. Atmos Environ. 2005;39(33): [14] Hang J, Sandberg M, Li Y. Effect of urban morphology on wind condition in idealized city models. Atmos Environ. 2009;43(4): [15] Eliasson I, Offerle B, Grimmond CSB, Lindqvist S. Wind fields and turbulence statistics in an urban street canyon. Atmos Environ. 2006;40(1):1 16. [16] Amorim JH, Rodrigues V, Tavares R, Valente J, Borrego C. CFD modelling of the aerodynamic effect of trees on urban air pollution dispersion. Sci Total Environ. 2013; : [17] Endalew AM, Hertog M, Delele MA, Baetens K, Persoons T, Baelmans M, et al. CFD modelling and wind tunnel validation of airflow through plant canopies using 3D canopy architecture. Int J Heat Fluid Flow. 2009;30(2): [18] Xiaomin X, Zhen H, Jiasong W. The impact of urban street layout on local atmospheric environment. Build Environ. 2006;41(10): [19] Leitl B, Meroney R. Car exhaust dispersion in a street canyon. Numerical critique of a wind tunnel experiment. J Wind Eng Ind Aerodyn. 1997;67 68: [20] Leitl BM, Kastner-Klein P, Rau M, Meroney RN. Concentration and flow distributions in the vicinity of U-shaped buildings: Wind-tunnel and computational data. J Wind Eng Ind Aerodyn. 1997;67 68: [21] Kim JJ, Baik JJ. A numerical study of the effects of ambient wind direction on flow and dispersion in urban street canyons using the RNG k-ε turbulence model. Atmos Environ. 2004;38(19): [22] Hang J, Sandberg M, Li Y. Age of air and air exchange efficiency in idealized city models. Build Environ. 2009;44(8): [23] DePaul FT, Sheih CM. Measurements of wind velocities in a street canyon. Atmos Environ. 1986;20(3): [24] Oke TR. Street design and urban canopy layer climate. Energy Build. 1988;11(1 3): [25] Memon RA, Leung DYC. On the heating environment in street canyon. Environ Fluid Mech. 2011;11(5): [26] Muhaisen AS. Shading simulation of the courtyard form in different climatic regions. Build Environ. 2006;41(12): [27] Yang X, Li Y, Yang L. Predicting and understanding temporal 3D exterior surface temperature distribution in an ideal courtyard. Build Environ. 2012;57:

12 [28] Firla g S, Murray S. Impacts of airflows, internal heat and moisture gains on accuracy of modeling energy consumption and indoor parameters in passive building. Energy Build. 2013;64: [29] Corke TC, Nagib HM. Flow near a building model in a family of surface layers. 1979;5: [30] Counihan J. Adiabatic atmospheric boundary layers: A review and analysis of data from the period Atmos Environ. 1975;9(10): [31] Paterson D a., Apelt CJ. Simulation of wind flow around three-dimensional buildings. Build Environ. 1989;24(1): [32] Montazeri H, Blocken B. CFD simulation of wind-induced pressure coefficients on buildings with and without balconies: Validation and sensitivity analysis. Build Environ. 2013;60: [33] Stathopoulos T, Baskaran A. Boundary treatment for the computation of three-dimensional wind flow conditions around a building. J Wind Eng Ind Aerodyn. 1990;35(1): [34] Byrne CEI, Holdo AE. Effects of increased geometric complexity on the comparison between computational and experimental simulations. J Wind Eng Ind Aerodyn. 1998;73: [35] Li J, Ward IC. Developing computational fluid dynamics conditions for urban natural ventilaiton study. School of Architecture, the University of Sheffield. 2007; [36] Baik J-J, Kim J-J, Fernando HJS. A CFD Model for Simulating Urban Flow and Dispersion. J Appl Meteorol. 2003;42(11): [37] van Hooff T, Blocken B. Coupled urban wind flow and indoor natural ventilation modelling on a high-resolution grid: A case study for the Amsterdam ArenA stadium. Environ Model Softw. 2010;25(1): [38] Castro IP, Apsley DD. Flow and dispersion over topography: A comparison between numerical and laboratory data for two-dimensional flows. Atmos Environ. 1997;31(6): [39] Hargreaves DM, Wright NG. On the use of the k-ε model in commercial CFD software to model the neutral atmospheric boundary layer. J Wind Eng Ind Aerodyn. 2007;95(5): [40] Richards PJ, Hoxey RP. Appropriate boundary conditions for computational wind engineering models using the k-ϵ turbulence model. J Wind Eng Ind Aerodyn. 1993;46 47(0): [41] Lien FS, Yee E, Cheng Y. Simulation of mean flow and turbulence over a 2D building array using high-resolution CFD and a distributed drag force approach. J Wind Eng Ind Aerodyn. 2004;92(2): [42] Yang Y, Gu M, Chen S, Jin X. New inflow boundary conditions for modelling the neutral equilibrium atmospheric boundary layer in computational wind engineering. J Wind Eng Ind Aerodyn. 2009;97(2): [43] Launder BE, Spalding DB. The numerical computation of turbulent flows. 1974;3: [44] Paterson DA, Apelt CJ. Computation of wind flows over three-dimensional buildings. J Wind Eng Ind Aerodyn. 1986;24(3): [45] Counehan J. Wind tunnel determination of the roughness length as a function of the fetch and the roughness density of three-dimensional roughness elements. Atmos Environ. 1971;5(8): [46] Sandberg M. What is ventilation efficiency? Build Environ. 1981;16(2): [47] Lin M, Hang J, Li Y, Luo Z, Sandberg M. Quantitative ventilation assessments of idealized urban canopy layers with various urban layouts and the same building packing density. Build Environ. 2014;79: [48] Padilla-Marcos MA, Feijó-Muñoz J, Meiss A. Confined-air quality based on the geometric efficiency of urban outdoor spaces. Cases study. Int J Vent. 2016;15(1). [49] Yakhot V, Orszag SA. Renormalization group analysis of turbulence. I. Basic theory. J Sci Comput. 1986;1(1):3 51. [50] Blocken B, Janssen WD, van Hooff T. CFD simulation for pedestrian wind comfort and wind safety in urban areas: General decision framework and case study for the Eindhoven University campus. Environ Model Softw. 2012;30: [51] Iaccarino G, Ooi A, Durbin PA, Behnia M. Reynolds averaged simulation of unsteady separated 11

13 flow. Int J Heat Fluid Flow. 2003;24(2): [52] Jeong SJ, Andrews MJ. Application of the k-ε turbulence model to the high Reynolds number skimming flow field of an urban street canyon. Atmos Environ. 2002;36(7): [53] Moonen P, Dorer V, Carmeliet J. Evaluation of the ventilation potential of courtyards and urban street canyons using RANS and LES. J Wind Eng Ind Aerodyn. 2011;99(4): [54] Hertwig D, Efthimiou GC, Bartzis JG, Leitl B. CFD-RANS model validation of turbulent flow in a semi-idealized urban canopy. J Wind Eng Ind Aerodyn. 2012;111: [55] Murakami S, Mochida A, Hayashi Y. Examining the k-e model by means of a wind tunnel test and large-eddy simulation of the turbulence structure around a cube. J Wind Eng Ind Aerodyn. 1990;35: [56] Hertwig D, Leitl B, Schatzmann M. Organized turbulent structures-link between experimental data and LES. J Wind Eng Ind Aerodyn. 2011;99(4): [57] Sharples S, Bensalem R. Airflow in courtyard and atrium buildings in the urban environment: A win tunnel study. Sol Energy. 2001;70(3):

Riccardo Buccolieri 1, Mats Sandberg 2

Riccardo Buccolieri 1, Mats Sandberg 2 STUDY OF TE EFFECTS OF BUILDING DENSITY AND OVERALL SAPE OF A CITY ON POLLUTANT DISPERSION BY COMBINATION OF WIND TUNNEL EXPERIMENTS AND CFD SIMULATIONS Riccardo Buccolieri 1, Mats Sandberg 2 1 Dipartimento

More information

H POLLUTANT DISPERSION OVER TWO-DIMENSIONAL IDEALIZED STREET CANYONS: A LARGE-EDDY SIMULATION APPROACH. Colman C.C. Wong and Chun-Ho Liu*

H POLLUTANT DISPERSION OVER TWO-DIMENSIONAL IDEALIZED STREET CANYONS: A LARGE-EDDY SIMULATION APPROACH. Colman C.C. Wong and Chun-Ho Liu* H14-117 POLLUTANT DISPERSION OVER TWO-DIMENSIONAL IDEALIZED STREET CANYONS: A LARGE-EDDY SIMULATION APPROACH Colman C.C. Wong and Chun-Ho Liu* Department of Mechanical Engineering, The University of Hong

More information

Large eddy simulation of natural ventilation for idealized terrace houses due to the effect of setback distance

Large eddy simulation of natural ventilation for idealized terrace houses due to the effect of setback distance IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Large eddy simulation of natural ventilation for idealized terrace houses due to the effect of setback distance To cite this article:

More information

Fluctuating Inlet Flow Conditions for Use in Urban Air Quality CFD Studies

Fluctuating Inlet Flow Conditions for Use in Urban Air Quality CFD Studies Proceedings of the World Congress on Engineering Vol II, WCE, July -,, London, U.K. Fluctuating Inlet Flow Conditions for Use in Urban Air Quality CFD Studies S. M. Kwa, S. M. Salim Abstract Fluctuating

More information

TREES IN URBAN STREET CANYONS AND THEIR IMPACT ON THE DISPERSION OF AUTOMOBILE EXHAUSTS. Christof Gromke*, Bodo Ruck

TREES IN URBAN STREET CANYONS AND THEIR IMPACT ON THE DISPERSION OF AUTOMOBILE EXHAUSTS. Christof Gromke*, Bodo Ruck TREES IN URBAN STREET CANYONS AND THEIR IMPACT ON THE DISPERSION OF AUTOMOBILE EXHAUSTS Christof Gromke*, Bodo Ruck Laboratory of Building- and Environmental Aerodynamics Institute for Hydromechanics,

More information

SCIENCE & TECHNOLOGY

SCIENCE & TECHNOLOGY Pertanika J. Sci. & Technol. 25 (S): 277-286 (2017) SCIENCE & TECHNOLOGY Journal homepage: http://www.pertanika.upm.edu.my/ Effect of Upstream Building Configurations on Mean Wind Speed Ratio at Urban

More information

ASSESSMENT OF AIR CHANGE RATE AND CONTRIBUTION RATIO IN IDEALIZED URBAN CANOPY LAYERS BY TRACER GAS SIMULATIONS

ASSESSMENT OF AIR CHANGE RATE AND CONTRIBUTION RATIO IN IDEALIZED URBAN CANOPY LAYERS BY TRACER GAS SIMULATIONS Topic B4: Ventilation ASSESSMENT OF AIR CHANGE RATE AND CONTRIBUTION RATIO IN IDEALIZED URBAN CANOPY LAYERS BY TRACER GAS SIMULATIONS Qun WANG 1, Mats SANDBERG 2, Jian HANG 1* 1 Department of Atmospheric

More information

On Plume Dispersion over Two-Dimensional Urban-like Idealized Roughness Elements with Height Variation

On Plume Dispersion over Two-Dimensional Urban-like Idealized Roughness Elements with Height Variation On Plume Dispersion over Two-Dimensional Urban-like Idealized Roughness Elements with Height Variation Colman C.C. Wong and Chun-Ho Liu Department of Mechanical Engineering, The University of Hong Kong,

More information

Urban Physics: towards sustainable buildings and cities

Urban Physics: towards sustainable buildings and cities Inauguration Event & Mini-Symposium for Prof.dr. Alexey Voinov: SYSTEMS AND SUSTAINABILITY IN TIME AND SPACE Urban Physics: towards sustainable buildings and cities Prof.dr.ir. Bert Blocken Eindhoven University

More information

On The Effect Of Various Design Factors On Wind-Induced Natural Ventilation Of Residential Buildings In Malaysia M. F. Mohamad 1,2*, A. Hagishima 2, J

On The Effect Of Various Design Factors On Wind-Induced Natural Ventilation Of Residential Buildings In Malaysia M. F. Mohamad 1,2*, A. Hagishima 2, J On The Effect Of Various Design Factors On Wind-Induced Natural Ventilation Of Residential Buildings In Malaysia M. F. Mohamad 1,2*, A. Hagishima 2, J. Tanimoto 2, N. Ikegaya 2, and A. R. Omar 1 1 Faculty

More information

Numerical analysis of eccentric orifice plate using ANSYS Fluent software

Numerical analysis of eccentric orifice plate using ANSYS Fluent software IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Numerical analysis of eccentric orifice plate using ANSYS Fluent software To cite this article: D Zahariea 2016 IOP Conf. Ser.:

More information

Influence of Building Aspect Ratio and Traffic Volume on Reactive Pollutant Dispersion in Urban-like Street Canyons during Direct Ground Heating

Influence of Building Aspect Ratio and Traffic Volume on Reactive Pollutant Dispersion in Urban-like Street Canyons during Direct Ground Heating Department of Mechanical Engineering University of Hong Kong Influence of Building Aspect Ratio and Traffic Volume on Reactive Pollutant Dispersion in Urban-like Street Canyons during Direct Ground Heating

More information

u and Yoshie (2013) investigate the effect of building geometry and they revealed that the ventilation efficiency strongly depended on the level of bu

u and Yoshie (2013) investigate the effect of building geometry and they revealed that the ventilation efficiency strongly depended on the level of bu Effect of upstream building arrangement and setback distance on air flow around idealized cubical building arrays A. Abd Razak 1*, R.. usam 1, T. Liyana 1, S. A. Zaki 2 and A. F. Mohammad 2 1 Faculty of

More information

Lungs of the city of Eindhoven

Lungs of the city of Eindhoven Lungs of the city of Eindhoven ir. Rob Vervoort (r.p.m.vervoort@tue.nl), Eindhoven University of Technology, PDEng-trainee Smart Buildings & Cities, Department of the Built Environment, Building Physics

More information

APPLYING COMPUTATIONAL FLUID DYNAMICS TO ARCHITEC- TURAL DESIGN DEVELOPMENT

APPLYING COMPUTATIONAL FLUID DYNAMICS TO ARCHITEC- TURAL DESIGN DEVELOPMENT APPLYING COMPUTATIONAL FLUID DYNAMICS TO ARCHITEC- TURAL DESIGN DEVELOPMENT Strategy and Implementation JIN-YEU TSOU Department of Architecture, Chinese University of Hong Kong Sha Tin, New Territories,

More information

18th International Conference on Harmonisation within Atmospheric Dispersion Modelling for Regulatory Purposes 9-12 October 2017, Bologna, Italy

18th International Conference on Harmonisation within Atmospheric Dispersion Modelling for Regulatory Purposes 9-12 October 2017, Bologna, Italy 18th International Conference on Harmonisation within Atmospheric Dispersion Modelling for Regulatory Purposes 9-12 October 2017, Bologna, Italy COMBINING GAUSSIAN AND CFD MODELLING TO ASSESS THE IMPACT

More information

Comparison of RANS, URANS and LES in the Prediction of Airflow and Pollutant Dispersion

Comparison of RANS, URANS and LES in the Prediction of Airflow and Pollutant Dispersion Comparison of RANS, URANS and LES in the Prediction of Airflow and Pollutant Dispersion S. M. Salim, K. C. Ong, S. C. Cheah Abstract The performance of three different numerical techniques, i.e. RANS,

More information

Modelling urban pollution dispersion by using MISKAM

Modelling urban pollution dispersion by using MISKAM Modelling urban pollution dispersion by using MISKAM Márton Balczó 1, Tamás Faragó 2, Tamás Lajos 3 PhD Student 1, Student 2, Professor 3 Budapest University of Technology and Economics, Department of

More information

H AIR QUALITY MODELLING OF ROAD PROJECTS USING A 3D COMPUTATIONAL FLUID DYNAMICS (CFD) MODEL. Malo Le Guellec, Lobnat Ait Hamou, Amita Tripathi

H AIR QUALITY MODELLING OF ROAD PROJECTS USING A 3D COMPUTATIONAL FLUID DYNAMICS (CFD) MODEL. Malo Le Guellec, Lobnat Ait Hamou, Amita Tripathi H13-198 AIR QUALITY MODELLING OF ROAD PROJECTS USING A 3D COMPUTATIONAL FLUID DYNAMICS (CFD) MODEL Malo Le Guellec, Lobnat Ait Hamou, Amita Tripathi FLUIDYN France, Saint-Denis, France Abstract: The air

More information

Numerical simulation of inter-flat pollutant dispersion routes and cross-contamination risk in high-rise residential buildings Di Mu, Naiping Gao* Ins

Numerical simulation of inter-flat pollutant dispersion routes and cross-contamination risk in high-rise residential buildings Di Mu, Naiping Gao* Ins Numerical simulation of inter-flat pollutant dispersion routes and cross-contamination risk in high-rise residential buildings Di Mu, Naiping Gao* Institute of Thermal and Environment Engineering, School

More information

Modeling of pollutant dispersion in street canyon by means of CFD

Modeling of pollutant dispersion in street canyon by means of CFD Modeling of pollutant dispersion in street canyon by means of CFD Davide Meschini a, Valentina Busini * a, Sjoerd W. van Ratingen b, Renato Rota a a Department of Chemistry, Materials and Chemical Engineering

More information

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building Shafqat Hussain and Patrick H. Oosthuizen Department of Mechanical and Materials Engineering, Queen s

More information

Modelling of air pollution on urban buildings: a wind tunnel study

Modelling of air pollution on urban buildings: a wind tunnel study Modelling of air pollution on urban buildings: a wind tunnel study A. M. Mfula 1,2, V. Kukadia 1, R. F. Griffiths 2 & D. J. Hall 3 1 Building Research Establishment Ltd (BRE), UK 2 Environmental Technology

More information

CFD Modelling of an Aerosol Exposure Chamber for Medical Studies G. Manenti, M. Derudi, G. Nano, R. Rota

CFD Modelling of an Aerosol Exposure Chamber for Medical Studies G. Manenti, M. Derudi, G. Nano, R. Rota CFD Modelling of an Aerosol Exposure Chamber for Medical Studies G. Manenti, M. Derudi, G. Nano, R. Rota Dip. di Chimica, Materiali e Ingegneria Chimica G. Natta, Politecnico di Milano, via Mancinelli

More information

WIND FLOW IN THE RECESSED CAVITIES OF A TALL

WIND FLOW IN THE RECESSED CAVITIES OF A TALL The Seventh Asia-Pacific Conference on Wind Engineering, November 8-12, 2009, Taipei, Taiwan WIND FLOW IN THE RECESSED CAVITIES OF A TALL BUILDING Charles C.K. Cheng 1, K.M. Lam 2 and Andrew Y.T. Leung

More information

A three-dimensional numerical model of air pollutant dispersion

A three-dimensional numerical model of air pollutant dispersion Air Pollution XIII 39 A three-dimensional numerical model of air pollutant dispersion K. Kaminski, W. Kaminski & J. Petera Faculty of Process and Environmental Engineering, Technical University of Lodz,

More information

Published in: CleanTech for Sustainable Buildings: From Nano to Urban Scale (CISBAT), Lausanne, September 2011

Published in: CleanTech for Sustainable Buildings: From Nano to Urban Scale (CISBAT), Lausanne, September 2011 Evaluation of wind-driven ventilation in building energy simulation: sensitivity to pressure coefficients Ramponi, R.; Costola, D.; Angelotti, A.; Blocken, B.; Hensen, J.L.M. Published in: CleanTech for

More information

A study of single-sided ventilation and provision of balconies in the context of high-rise residential buildings

A study of single-sided ventilation and provision of balconies in the context of high-rise residential buildings A study of single-sided ventilation and provision of balconies in the context of high-rise residential buildings Mohamed M. F. 1,2,*, King S. 2, Behnia M. 3, Prasad D. 2 1 Faculty of Engineering and Built

More information

CFD Modeling of Reactive Pollutants in an Urban Street Canyon using Different Chemical Mechanisms

CFD Modeling of Reactive Pollutants in an Urban Street Canyon using Different Chemical Mechanisms CFD Modeling of Reactive Pollutants in an Urban Street Canyon using Different Chemical Mechanisms B Sanchez a,b, JL Santiago a, A Martilli a, M Palacios a, F Kirchner c a Center for Energy, Environment

More information

Numerical Simulation of Dispersion in an Urban Street Canyon: Comparison between Steady and Fluctuating Boundary Conditions

Numerical Simulation of Dispersion in an Urban Street Canyon: Comparison between Steady and Fluctuating Boundary Conditions Numerical Simulation of Dispersion in an Urban Street Canyon: Comparison between Steady and Fluctuating Boundary Conditions S. M. Kwa, S. M. Salim Abstract Over the years, the reliance on CFD to investigate

More information

A study on the effect of the airflow rate of the ceiling type air-conditioner on the ventilation performance

A study on the effect of the airflow rate of the ceiling type air-conditioner on the ventilation performance A study on the effect of the airflow rate of the ceiling type air-conditioner on the ventilation performance Kwang-Chul Noh 1, Chang-Woo Han 2 and Myung-Do Oh 2 1 Institute of Industrial Technology, University

More information

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1692 1697 The 7 th International Conference on Applied Energy ICAE2015 CFD and Wind Tunnel Study of the Performance of

More information

CFD/FEM Based Analysis Framework for Wind Effects on Tall Buildings in Urban Areas

CFD/FEM Based Analysis Framework for Wind Effects on Tall Buildings in Urban Areas 2017 2nd International Conference on Industrial Aerodynamics (ICIA 2017) ISBN: 978-1-60595-481-3 CFD/FEM Based Analysis Framework for Wind Effects on Tall Buildings in Urban Areas Qiao Yan, Dalong Li,

More information

Numerical Analysis of Ventilation Effectiveness in Occupied Zones for Various Industrial Ventilation Systems

Numerical Analysis of Ventilation Effectiveness in Occupied Zones for Various Industrial Ventilation Systems Numerical Analysis of Ventilation Effectiveness in Occupied Zones for Various Industrial Ventilation Systems Seohiro Kikuchi a *, Kazuhide Ito b, Nobuyuki Kobayashi c a Graduate Student, Tokyo Polytechnic

More information

Flow and heat distribution analysis of different transformer sub-stations

Flow and heat distribution analysis of different transformer sub-stations IOP Conference Series: Materials Science and Engineering OPEN ACCESS Flow and heat distribution analysis of different transformer sub-stations To cite this article: H Hasini et al 2013 IOP Conf. Ser.:

More information

Thermal comfort study of a hawker center in Singapore

Thermal comfort study of a hawker center in Singapore September 004 Page of 6 Thermal comfort study of a hawker center in Singapore Song Jiafang, Wong Nyuk Hien, Agustinus Djoko Istiadji Department of Building, School of Design and Environment, National University

More information

Evaluation of a CFD modeling approach by means of an intensive experimental campaign using passive samplers in an urban area of Madrid

Evaluation of a CFD modeling approach by means of an intensive experimental campaign using passive samplers in an urban area of Madrid Evaluation of a CFD modeling approach by means of an intensive experimental campaign using passive samplers in an urban area of Madrid Jose Luis Santiago 1, Rafael Borge 2, Fernando Martin 1, David de

More information

Effects of shaft supporting structure on performance test of axial flow fan

Effects of shaft supporting structure on performance test of axial flow fan IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Effects of shaft supporting structure on performance test of axial flow fan To cite this article: R Ma et al 2016 IOP Conf. Ser.:

More information

An Analytical Solution for Steady Temperature Profiles in a Vertically Stratified Environment

An Analytical Solution for Steady Temperature Profiles in a Vertically Stratified Environment Modern Applied Science; Vol. 8, No. 4; 2014 ISSN 1913-1844 E-ISSN 1913-1852 Published by Canadian Center of Science and Education An Analytical Solution for Steady Temperature Profiles in a Vertically

More information

Natural ventilation assessment in typical open an semi open urban environments under various wind directions

Natural ventilation assessment in typical open an semi open urban environments under various wind directions Natural ventilation assessment in typical open an semi open urban environments under various wind directions Article Accepted Version Hang, J., Luo, Z., Sandberg, M. and Jian, G. (2013) Natural ventilation

More information

Performance Improvement Analysis for a Negative-pressurized Biosafety Level Laboratory

Performance Improvement Analysis for a Negative-pressurized Biosafety Level Laboratory Performance Improvement Analysis for a Negative-pressurized Biosafety Level Laboratory F.J. Wang* and J.S. Huang 1 Department of Refrigeration, Air Conditioning and Energy Engineering, National Chin-Yi

More information

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at  ScienceDirect. Procedia Engineering 121 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 1449 1453 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International

More information

Current Studies on Air Distributions in Commercial Airliner Cabins

Current Studies on Air Distributions in Commercial Airliner Cabins Liu, W. and Chen, Q. 2013. Current studies on air distributions in commercial airliner cabins. Accepted by Theoretical & Applied Mechanics Letters. Current Studies on Air Distributions in Commercial Airliner

More information

A Modelling-Mapping Approach for Fine-Scale Natural Ventilation Evaluation in High Density Cities

A Modelling-Mapping Approach for Fine-Scale Natural Ventilation Evaluation in High Density Cities A Modelling-Mapping Approach for Fine-Scale Natural Ventilation Evaluation in High Density Cities Chao Yuan 1, 2, Leslie Norford 3, Rex Britter 4, Steve Yim 5, Edward Ng 6, 1 Massachusetts Institute of

More information

putational domain contained 8 blocks surrounding the central one. All 9 blocks had the same arrangement. Each block comprised a total of 72 residentia

putational domain contained 8 blocks surrounding the central one. All 9 blocks had the same arrangement. Each block comprised a total of 72 residentia The Seventh International Colloquium on Bluff Body Aerodynamics and Applications (BBAA7) Shanghai, China; September 2-6, 2012 Ventilation efficiency indices for evaluating ventilation performance of newly-built

More information

Air Pollutant Dispersion from a Large Semi- Enclosed Stadium in an Urban Area: High- Resolution CFD Modeling versus Full-Scale Measurements

Air Pollutant Dispersion from a Large Semi- Enclosed Stadium in an Urban Area: High- Resolution CFD Modeling versus Full-Scale Measurements International Congress on Environmental Modelling and Software Brigham Young University BYU ScholarsArchive 6th International Congress on Environmental Modelling and Software - Leipzig, Germany - July

More information

CFD Modelling and Analysis of Different Plate Heat Exchangers

CFD Modelling and Analysis of Different Plate Heat Exchangers CFD Modelling and Analysis of Different Plate Heat Exchangers Ahmed Y Taha Al-Zubaydi a *, Guang Hong b and W. John Dartnall c Faculty of Engineering and Information Technology, UTS, Sydney, Australia

More information

Influence of trees on the dispersion of pollutants in an urban street canyon Experimental investigation of the flow and concentration field

Influence of trees on the dispersion of pollutants in an urban street canyon Experimental investigation of the flow and concentration field First published in: Atmospheric Environment 41 (2007) 3287 3302 www.elsevier.com/locate/atmosenv Influence of trees on the dispersion of pollutants in an urban street canyon Experimental investigation

More information

EFFECTS OF BUILDINGS ASPECT RATIO, WIND SPEED AND WIND DIRECTION ON FLOW STRUCTURE AND POLLUTANT DISPERSION IN SYMMETRIC STREET CANYONS: A REVIEW

EFFECTS OF BUILDINGS ASPECT RATIO, WIND SPEED AND WIND DIRECTION ON FLOW STRUCTURE AND POLLUTANT DISPERSION IN SYMMETRIC STREET CANYONS: A REVIEW International Journal of Mechanical and Materials Engineering (IJMME), Vol. 7 (2012), No. 2, 158-165. EFFECTS OF BUILDINGS ASPECT RATIO, WIND SPEED AND WIND DIRECTION ON FLOW STRUCTURE AND POLLUTANT DISPERSION

More information

Research on the cavitation characteristic of Kaplan turbine under sediment flow condition

Research on the cavitation characteristic of Kaplan turbine under sediment flow condition IOP Conference Series: Earth and Environmental Science Research on the cavitation characteristic of Kaplan turbine under sediment flow condition To cite this article: L Weili et al 2010 IOP Conf. Ser.:

More information

768 SIMULATING WIND POWER DENSITY AROUND BUILDINGS FOR SITING BUILDING INTEGRATED WIND TURBINES

768 SIMULATING WIND POWER DENSITY AROUND BUILDINGS FOR SITING BUILDING INTEGRATED WIND TURBINES 768 SIMULATING WIND POWER DENSITY AROUND BUILDINGS FOR SITING BUILDING INTEGRATED WIND TURBINES Sue Ellen Haupt 1,2, Susan W. Stewart 2, Julia A. Cole 2, Frank J. Zajaczkowski, and Kerrie J. Schmehl 2

More information

Document Version Publisher s PDF, also known as Version of Record (includes final page, issue and volume numbers)

Document Version Publisher s PDF, also known as Version of Record (includes final page, issue and volume numbers) Air pollutant dispersion from a large semi-enclosed stadium in an urban area: high-resolution CFD modeling versus full-scale measurements van Hooff, T.; Blocken, B. Published in: Proceedings of the International

More information

6.5 THE INFLUENCE OF OBSTACLES ON THE FLOW AND POLLUTANT DISPERSION IN AN URBAN ENVIRONMENT

6.5 THE INFLUENCE OF OBSTACLES ON THE FLOW AND POLLUTANT DISPERSION IN AN URBAN ENVIRONMENT 6.5 THE NFLUENCE OF OBSTACLES ON THE FLOW AND POLLUTANT DSPERSON N AN URBAN ENVRONMENT Mohamed F. Yassin a, *, Masaaki Ohba b, Hideyuki Tanaka b a Faculty of Engineering, Assiut University, Assiut, Egypt

More information

CODASC: A DATABASE FOR THE VALIDATION OF STREET CANYON DISPERSION MODELS. Christof Gromke

CODASC: A DATABASE FOR THE VALIDATION OF STREET CANYON DISPERSION MODELS. Christof Gromke CODASC: A DATABASE FOR THE VALIDATION OF STREET CANYON DISPERSION MODELS Christof Gromke Building Physics and Services, Department of the Built Environment, Eindhoven University of Technology, Eindhoven,

More information

Dr. J. Wolters. FZJ-ZAT-379 January Forschungszentrum Jülich GmbH, FZJ

Dr. J. Wolters. FZJ-ZAT-379 January Forschungszentrum Jülich GmbH, FZJ Forschungszentrum Jülich GmbH, FZJ ZAT-Report FZJ-ZAT-379 January 2003 Benchmark Activity on Natural Convection Heat Transfer Enhancement in Mercury with Gas Injection authors Dr. J. Wolters abstract A

More information

Experimental Validation of a Computational Fluid Dynamics Model for IAQ applications in Ice Rink Arenas

Experimental Validation of a Computational Fluid Dynamics Model for IAQ applications in Ice Rink Arenas Yang, C., Demokritou, P., Chen Q., and Spengler, J. 2001. Experimental validation of a computational fluid dynamics model for IAQ applications in ice rink arenas, Indoor Air, 11(2), 120-126. Experimental

More information

To whom it may concern

To whom it may concern Department of the Built Environment Building Physics and Services Den Dolech 2, 5612 AZ Eindhoven Postbus 513, 5600 MB Eindhoven Internal address: Vertigo 6.B14 www.urbanphysics.net To whom it may concern

More information

MODELLING BUOYANCY INDUCED FLOWS OF PASSIVE COOLING SYSTEMS Pedro Correia da Silva 1, Vítor Leal 1 and J. Correia da Silva 2

MODELLING BUOYANCY INDUCED FLOWS OF PASSIVE COOLING SYSTEMS Pedro Correia da Silva 1, Vítor Leal 1 and J. Correia da Silva 2 Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 MODELLING BUOYANCY INDUCED FLOWS OF PASSIVE COOLING SYSTEMS Pedro Correia da Silva 1, Vítor Leal 1 and J. Correia da Silva 2 1

More information

Accepted for publication in Environmental Pollution

Accepted for publication in Environmental Pollution Influence of avenue trees on air quality at the urban neighborhood scale. Part II: Traffic pollutant concentrations at pedestrian level Graphical abstract Accepted for publication in Environmental Pollution

More information

Analysis of Uniformity and Energy Consumption in. Supermarket installed DurkeeSox Air Dispersion System. with PE Air Dispersion Model

Analysis of Uniformity and Energy Consumption in. Supermarket installed DurkeeSox Air Dispersion System. with PE Air Dispersion Model Analysis of Uniformity and Energy Consumption in Supermarket installed DurkeeSox Air Dispersion System with PE Air Dispersion Model Summary: Taking partial area of a large supermarket for example, to simulate

More information

CFD Study on Inter-Action between NonIsothermal Airflow and Buoyancy Plume in an AirConditioned Space

CFD Study on Inter-Action between NonIsothermal Airflow and Buoyancy Plume in an AirConditioned Space Wang et al. CFD Letters www.cfdl.issres.net Vol. 2(3) 2010 Vol. 2(3) September 2010 CFD Study on Inter-Action between NonIsothermal Airflow and Buoyancy Plume in an AirConditioned Space Xin. Wang1C and

More information

CFD SIMULATION OF A NOVEL VENTILATION SYSTEM OF SUBWAY STATION IN HARBIN

CFD SIMULATION OF A NOVEL VENTILATION SYSTEM OF SUBWAY STATION IN HARBIN CFD SIMULATION OF A NOVEL VENTILATION SYSTEM OF SUBWAY STATION IN HARBIN Xiyan Guan 1, Yiqiang Jiang 1,and Yang Yao 1 1 School of Municipal & Environmental Engineering, Harbin Institute of Technology,

More information

Scott Reynolds, PE M/E Engineering Syracuse NY

Scott Reynolds, PE M/E Engineering Syracuse NY Scott Reynolds, PE M/E Engineering Syracuse NY What is Wind Modeling? Wind modeling studies are used to determine: The flow of pollutants from exhaust stacks on buildings. The determination of pollutant

More information

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at   ScienceDirect. Procedia Engineering 121 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 225 231 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International

More information

CFD evaluation of natural ventilation of indoor environments. by the concentration decay method: CO 2 gas dispersion. from a semi-enclosed stadium

CFD evaluation of natural ventilation of indoor environments. by the concentration decay method: CO 2 gas dispersion. from a semi-enclosed stadium van Hooff T, Blocken B, 2013. CFD evaluation of natural ventilation of indoor environments by the concentration decay method: CO 2 gas dispersion from a semi-enclosed stadium. Building and Environment

More information

Reliability verification of an assessment tool for outdoor thermal environment

Reliability verification of an assessment tool for outdoor thermal environment IOP Conference Series: Materials Science and Engineering Reliability verification of an assessment tool for outdoor thermal environment To cite this article: Y S Jee et al 2010 IOP Conf. Ser.: Mater. Sci.

More information

CFD Analysis on Capture Efficiency in Commercial Kitchen using Low Radiative Cooking Equipment with Concentrated Exhaust Chimney

CFD Analysis on Capture Efficiency in Commercial Kitchen using Low Radiative Cooking Equipment with Concentrated Exhaust Chimney CFD Analysis on Capture Efficiency in Commercial Kitchen using Low Radiative Cooking Equipment with Concentrated Exhaust Chimney Koki TOYOMURA 1, Hisashi KOTANI 1, Toshio YAMANAKA 1, Yoshihisa MOMOI 1,

More information

Design of a new wind tunnel facility at Industrial Engineering School in Badajoz (Spain)

Design of a new wind tunnel facility at Industrial Engineering School in Badajoz (Spain) Design of a new wind tunnel facility at Industrial Engineering School in Badajoz (Spain) F. Zayas Hinojosa Department of Electronics and Electromechanical Engineering, University of Extremadura, Spain

More information

Thermal and Fluid-dynamical Optimisation of Passengers Comfort in a Touring Bus Cabin

Thermal and Fluid-dynamical Optimisation of Passengers Comfort in a Touring Bus Cabin Excerpt from the Proceedings of the COMSOL Conference 2008 Hannover hermal and Fluid-dynamical Optimisation of Passengers Comfort in a ouring Bus Cabin Petrone G. (*), Fichera G. (**), Scionti M. (*) (*)

More information

COMPARISON OF WIND TUNNEL MEASUREMENT AND NUMERICAL SIMULATION OF DISPERSION OF POLLUTANTS IN URBAN ENVIRONMENT

COMPARISON OF WIND TUNNEL MEASUREMENT AND NUMERICAL SIMULATION OF DISPERSION OF POLLUTANTS IN URBAN ENVIRONMENT COMPARISON OF WIND TUNNEL MEASUREMENT AND NUMERICAL SIMULATION OF DISPERSION OF POLLUTANTS IN URBAN ENVIRONMENT I. Goricsán Department of Fluid Mechanics Budapest University of Technology and Economics

More information

Changing the geometry of the Wind Tower and its Influence on Aerodynamic Behavior and Natural Ventilation

Changing the geometry of the Wind Tower and its Influence on Aerodynamic Behavior and Natural Ventilation IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 13, Issue 4 Ver. I (Jul. - Aug. 2016), PP 13-19 www.iosrjournals.org Changing the geometry of the

More information

NUMERICAL STUDY ON FILM COOLING AND CONVECTIVE HEAT TRANSFER CHARACTERISTICS IN THE CUTBACK REGION OF TURBINE BLADE TRAILING EDGE

NUMERICAL STUDY ON FILM COOLING AND CONVECTIVE HEAT TRANSFER CHARACTERISTICS IN THE CUTBACK REGION OF TURBINE BLADE TRAILING EDGE S643 NUMERICAL STUDY ON FILM COOLING AND CONVECTIVE HEAT TRANSFER CHARACTERISTICS IN THE CUTBACK REGION OF TURBINE BLADE TRAILING EDGE by Yong-Hui XIE *, Dong-Ting YE, and Zhong-Yang SHEN School of Energy

More information

MODELLING THE URBAN MICROCLIMATE AND ITS INFLUENCE ON BUILDING ENERGY DEMANDS OF AN URBAN NEIGHBOURHOOD

MODELLING THE URBAN MICROCLIMATE AND ITS INFLUENCE ON BUILDING ENERGY DEMANDS OF AN URBAN NEIGHBOURHOOD MODELLING THE URBAN MICROCLIMATE AND ITS INFLUENCE ON BUILDING ENERGY DEMANDS OF AN URBAN NEIGHBOURHOOD J. Allegrini 1,2 ; J. Kämpf 3 ; V. Dorer 1 ; J. Carmeliet 1,2 1: Empa, Laboratory for Building Science

More information

Incorporation of Computational Fluid Dynamics into the Effect of Building Layout on the Wind Environment-A Case Study of Shezi Island in Taipei

Incorporation of Computational Fluid Dynamics into the Effect of Building Layout on the Wind Environment-A Case Study of Shezi Island in Taipei , July 3-5, 013, London, U.K. Incorporation of Computational Fluid Dynamics into the Effect of Building Layout on the Wind Environment-A Case Study of Shezi Island in Taipei Ying-Ming Su Abstract Building

More information

Flow and Pollutant Transport in Urban Street Canyons of Different Aspect Ratios with Ground Heating: Large-Eddy Simulation

Flow and Pollutant Transport in Urban Street Canyons of Different Aspect Ratios with Ground Heating: Large-Eddy Simulation Flow and Pollutant Transport in Urban Street Canyons of Different Aspect Ratios with Ground Heating: Large-Eddy Simulation The MIT Faculty has made this article openly available. Please share how this

More information

EXAMINATION OF TRAFFIC POLLUTION DISTRIBUTION IN A STREET CANYON USING THE NANTES 99 EXPERIMENTAL DATA AND COMPARISON WITH MODEL RESULTS

EXAMINATION OF TRAFFIC POLLUTION DISTRIBUTION IN A STREET CANYON USING THE NANTES 99 EXPERIMENTAL DATA AND COMPARISON WITH MODEL RESULTS EXAMINATION OF TRAFFIC POLLUTION DISTRIBUTION IN A STREET CANYON USING THE NANTES 99 EXPERIMENTAL DATA AND COMPARISON WITH MODEL RESULTS R. BERKOWICZ 1, M. KETZEL 1, G. VACHON 2, P. LOUKA 2, J.-M. ROSANT

More information

Hydraulic performance of a low specific speed centrifugal pump with Spanwise-Slotted Blades

Hydraulic performance of a low specific speed centrifugal pump with Spanwise-Slotted Blades IOP Conference Series: Materials Science and Engineering OPEN ACCESS Hydraulic performance of a low specific speed centrifugal pump with Spanwise-Slotted Blades To cite this article: D X Ye et al 2013

More information

ADVANCES in NATURAL and APPLIED SCIENCES

ADVANCES in NATURAL and APPLIED SCIENCES ADVANCES in NATURAL and APPLIED SCIENCES ISSN: 1995-0772 Published BYAENSI Publication EISSN: 1998-1090 http://www.aensiweb.com/anas 2017 May 11(7): pages 910-918 Open Access Journal Analysis Of Ventilation

More information

Heat transfer modelling of slot jet impinging on an inclined plate

Heat transfer modelling of slot jet impinging on an inclined plate Heat transfer modelling of slot jet impinging on an inclined plate A. Ramezanpour 1, H. Shirvani 1 & I. Mirzaee 2 1 School of Design and Communication Systems, APU University, UK 2 CFD Research Centre,

More information

Appendix A Emission Quantification Techniques

Appendix A Emission Quantification Techniques Appendix A Emission Quantification Techniques EMISSION QUANTIFICATION TECHNIQUES Fugitive dust emission rates and particle size distributions are difficult to quantify because of the diffuse and variable

More information

Volume 7 - Number 12 - November 2011 (29-34) Numerical Modeling of Wind Effect on Plume Dispersion from a Point Source around Buildings

Volume 7 - Number 12 - November 2011 (29-34) Numerical Modeling of Wind Effect on Plume Dispersion from a Point Source around Buildings ISESCO JOURNAL of Science and Technology Volume 7 - Number 12 - November 2011 (29-34) Abstract Dispersion from the polluted point source within the atmosphere is the major concern in the urban areas. The

More information

XVII th World Congress of the International Commission of Agricultural and Biosystems Engineering (CIGR)

XVII th World Congress of the International Commission of Agricultural and Biosystems Engineering (CIGR) XVII th World Congress of the International Commission of Agricultural and Biosystems Engineering (CIGR) Hosted by the Canadian Society for Bioengineering (CSBE/SCGAB) Québec City, Canada June 13-17, 2010

More information

Computer simulation of processes in the dead end furnace

Computer simulation of processes in the dead end furnace IOP Conference Series: Materials Science and Engineering OPEN ACCESS Computer simulation of processes in the dead end furnace To cite this article: A S Zavorin et al 2014 IOP Conf. Ser.: Mater. Sci. Eng.

More information

BOUNDARY SETTING IN SIMULATING GREENHOUSE VENTILATION BY FLUENT SOFTWARE

BOUNDARY SETTING IN SIMULATING GREENHOUSE VENTILATION BY FLUENT SOFTWARE BOUNDARY SETTING IN SIMULATING GREENHOUSE VENTILATION BY FLUENT SOFTWARE Cuiping Hou 1, 2, Chengwei Ma 1,2,* 1 College of Water Conservancy and Civil Engineering, China Agricultural University, Beijing,

More information

IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA

IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA H Han 1* and Y-I Kwon 2 1 Dept. Of Mechanical Engineering, Kookmin University, Korea 2 Dept. Of Building Mechanical Engineering,

More information

ACCEPTED MANUSCRIPT NUMERICAL MODELLING OF THE PASSIVE CONTROL OF AIR POLLUTION IN ASYMMETRICAL URBAN STREET CANYONS USING REFINED MESH

ACCEPTED MANUSCRIPT NUMERICAL MODELLING OF THE PASSIVE CONTROL OF AIR POLLUTION IN ASYMMETRICAL URBAN STREET CANYONS USING REFINED MESH Accepted Manuscript Numerical modelling of the passive control of air pollution in asymmetrical urban street canyons using refined mesh discretization schemes J. Gallagher, L.W. Gill, A. McNabola PII:

More information

Numerical Simulation of an Express Freight Train and a High-Speed Train Meeting in a Tunnel

Numerical Simulation of an Express Freight Train and a High-Speed Train Meeting in a Tunnel 2017 2nd International Conference on Industrial Aerodynamics (ICIA 2017) ISBN: 978-1-60595-481-3 Numerical Simulation of an Express Freight Train and a High-Speed Train Meeting in a Tunnel Kan He, Guang-Jun

More information

Numerical Investigation of the Integration of Heat Transfer Devices into Wind Towers

Numerical Investigation of the Integration of Heat Transfer Devices into Wind Towers A publication of CHEMICAL ENGINEERING TRANSACTIONS VOL. 34, 2013 Guest Editors: Neven Duić, Petar Sabev Varbanov Copyright 2013, AIDIC Servizi S.r.l., ISBN 978-88-95608-25-9; ISSN 1974-9791 The Italian

More information

Atmospheric boundary layer simulation in a short wind tunnel

Atmospheric boundary layer simulation in a short wind tunnel Int. J. Environ. Sci. Technol. (2014) 11:59 68 DOI 10.1007/s13762-013-0371-4 ORIGINAL PAPER Atmospheric boundary layer simulation in a short wind tunnel S. M. N. Shojaee O. Uzol Ö. Kurç Received: 11 September

More information

Numerical simulation of atmospheric boundary layer and wakes of horizontal-axis wind turbines

Numerical simulation of atmospheric boundary layer and wakes of horizontal-axis wind turbines Numerical simulation of atmospheric boundary layer and wakes of horizontal-axis wind turbines Ali M AbdelSalam Ramalingam Velraj Institute for Energy Studies, Anna University, Chennai, India Abstract Simulations

More information

FANROOMLESS VENTILATION SYSTEM FOR AN UNDERGROUND PARKING LOT

FANROOMLESS VENTILATION SYSTEM FOR AN UNDERGROUND PARKING LOT FANROOMLESS VENTILATION SYSTEM FOR AN UNDERGROUND PARKING LOT Eon Ku Rhee 1, Seong Hwan Yi 2,* 1Ph.D. Professor of Architecture, Chung-Ang University, Seoul, Korea 2 Ph.D. Candidate of Architecture, Chung-Ang

More information

Causes of Urban Heat Island in Singapore: An investigation using computational fluid dynamics (CFD)

Causes of Urban Heat Island in Singapore: An investigation using computational fluid dynamics (CFD) Causes of Urban Heat Island in Singapore: An investigation using computational fluid dynamics (CFD) RAJAGOPALAN PRIYADARSINI 1, WONG NYUK HIEN 2 1 School of Architecture & Building, Deakin University,

More information

Comparison of various types of k ɛ models for pollutant emissions around a two-building configuration

Comparison of various types of k ɛ models for pollutant emissions around a two-building configuration Comparison of various types of k ɛ models for pollutant emissions around a two-building configuration M. Lateb a,, C. Masson a, T. Stathopoulos b, C. Bédard a a Department of Mechanical Engineering, ÉTS

More information

Numerical Simulation of Airflow Organization and Temperature Distribution in Bulk Curing Barn Yong-qiao WANG, Yan-qiong LI, Yan ZHAO

Numerical Simulation of Airflow Organization and Temperature Distribution in Bulk Curing Barn Yong-qiao WANG, Yan-qiong LI, Yan ZHAO 5th International Conference on Advanced Materials and Computer Science (ICAMCS 2016) Numerical Simulation of Airflow Organization and Temperature Distribution in Bulk Curing Barn Yong-qiao WANG, Yan-qiong

More information

FAST EVALUATION OF SUSTAINABLE HEATING AND COOLING STRATEGIES FOR SOLAR HOMES WITH INTEGRATED ENERGY AND CFD MODELING

FAST EVALUATION OF SUSTAINABLE HEATING AND COOLING STRATEGIES FOR SOLAR HOMES WITH INTEGRATED ENERGY AND CFD MODELING FAST EVALUATION OF SUSTAINABLE HEATING AND COOLING STRATEGIES FOR SOLAR HOMES WITH INTEGRATED ENERGY AND CFD MODELING Justin Spencer 1 and Zhiqiang Zhai 1, * 1 Department of Civil, Environmental, and Architectural

More information

Evaluation of Gaussian Plume Model against CFD Simulations through the Estimation of CO and NO Concentrations in an Urban Area

Evaluation of Gaussian Plume Model against CFD Simulations through the Estimation of CO and NO Concentrations in an Urban Area American Journal of Environmental Sciences Original Research Paper Evaluation of Gaussian Plume Model against CFD Simulations through the Estimation of CO and NO Concentrations in an Urban Area 1,2 Mahmoud

More information

CFD simulation of near-field pollutant dispersion in the urban environment: A review of current modeling techniques

CFD simulation of near-field pollutant dispersion in the urban environment: A review of current modeling techniques Accepted on 15 July 2013 for publication in the Atmospheric Environment CFD simulation of near-field pollutant dispersion in the urban environment: A review of current modeling techniques Yoshihide Tominaga

More information

3D Simulation of a fire inside a river tunnel and optimisation of the ventilation using Computational Fluid Dynamics

3D Simulation of a fire inside a river tunnel and optimisation of the ventilation using Computational Fluid Dynamics 3D Simulation of a fire inside a river tunnel and optimisation of the ventilation using Computational Fluid Dynamics Authors: B. TRUCHOT, A. TRIPATHI Fluidyn-France Abstract CFD simulation is used to predict

More information

REPRESENTATIVENESS OF URBAN MONITORING STATIONS

REPRESENTATIVENESS OF URBAN MONITORING STATIONS REPRESENTATIVENESS OF URBAN MONITORING STATIONS JL Santiago, F Martín, A Martilli Atmospheric Pollution Division, Environmental Department, CIEMAT, Spain jl.santiago@ciemat.es fernando.martin@ciemat.es

More information