CONDENSING TEMPERATURE CONTROL THROUGH ENERGY MANAGEMENT SYSTEM SIMULATON FOR A LARGE OFFICE BUILDING

Similar documents
Whole Building Energy Performance Evaluation through. Similar Control Strategies

Application of a cooling tower model for optimizing energy use

ENERGY MODELING TOOLS: SOLUTIONS FOR CREATING A HIGH PERFORMANCE BUILDING. Presented by Neil Maldeis Energy Solutions Engineering Leader, Trane

Optimized System for Your Bottom Line. Trane Training Class 1 Dec, 2017

Energy Modeling Tools Solutions for Creating an Intelligent Building

RETRO-COMMISSIONING OF A HEAT SOURCE SYSTEM IN A DISTRICT HEATING AND COOLING SYSTEM Eikichi Ono 1*, Harunori Yoshida 2, Fulin Wang 3 KEYWORDS

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

Sample Reports. for. HAP v4.80 Example Problem

Coupling of Building Data Analysis and Building Simulation - Case Study in Large-scale Complex Building -

POTENTIAL FOR THE ENERGY EFFICIENCY ADVANCEMENT IN DISTRICT HEATING AND COOLING PLANT BY RENOVATION

Technical Assignment 2 Building and Plant Energy Analysis

Building Commissioning for Energy Efficiency and Comfort, Vol.VI-8-4

9/13/2011. Mark Hanicits, Director of Facilities and Safety, MetroSouth Medical Center. Terry Malloy P.E., Cxa, Project Manager, Teng & Associates

OPTIMIZATION OF ICE THERMAL STORAGE SYSTEM DESIGN FOR HVAC SYSTEMS

The Biggest Loser REDUCING HIGHER EDUCATION COSTS BY 50%

SURNA Grow Facility: Systems Comparison - IEA

Sample Reports. for. HAP v4.90 Example Problem

VERIFICATION OF OPTIMUM OPERATION METHOD BY SIMULATION FOR THE HVAC SYSTEM WITH A THERMAL STORAGE TANK IN AN ACTUAL BUILDING

Strategies for Persistence: Measurement and Verification. Ryan Hughes PE, CEM, LEED AP Eaton Energy Solutions

Section 2: Estimating Energy Savings and Incentives

Year-round Energy Saving Potential for a Stratum Ventilated Subtropical Office. C.K. Lee Zhang Lin K.F. Fong

CASE STUDY OF APPLYING DIFFERENT ENERGY USE MODELING METHODS TO AN EXISTING BUILDING

ENERGY EVALUATION BY SIMULATION FOR EFFECTIVE USE OF SEWAGE HEAT

A Method for On-Going Commissioning of VRV Package Systems Using a. Simulation Model

ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA

Dharam V. Punwani Avalon Consulting, Inc. Tom L. Pierson Turbine Air Systems, Ltd.

LIBRARY ENERGY WALK- THROUGH. Andy Robinson, Training and Education, SEDAC

Building performance based on measured data

Analysis and System Design of a Large Chiller Plant for Korea, with or without Thermal Storage

Using Annual Building Energy Analysis for the Sizing of Cooling Tower for Optimal Chiller-Cooling Tower Energy Performance

Retro-commissioning and on-going commissioning 23 November 2016

Economic Estimation of Heat Storage Type Geothermal Source Heat Pump System Applied in K-Ward Office Building


Evaluation of reduced energy use resulting from a DHC network in the Shinjuku DHC area

Energy Consumption Analysis and Energy Conservation Evaluation of a. Commercial Building in Shanghai

OPTIMAL OPERATING METHOD FOR A HEAT SOURCE SYSTEM CONSIST OF CENTRIFUGAL CHILLERS

Timmins and District Hospital

Condenser Water Heat Recovery"

Evidence based calibration of a building energy simulation model: Application to an office building in Belgium

AUTOMATION ZONE BUILDER

THERMAL CHARACTERISTICS AND ENERGY CONSERVATION MEASURES IN AN INDOOR SPEED-SKATING ARENA

Retrocommissioning Investigation Study of the Sheraton Chicago Hotel

EMD SERONO RESEARCH CENTER EXISTING

National Indian Gaming Association 2005 Certification: Energy Management for Cost Savings Larry Kinney Synertech Systems Corporation On behalf of

A Case Study of a Commissioning Process for Demand Side Energy Conservation of the Large Heat Source Plant in Kyoto Station Building

Chapter 4. Analysis of Building Energy Performance

Practical research on effective use of simulation for HVAC systems in the retro-commissioning process H. Tanaka 1, S. Ito 2, Y. Morikawa 3, Y. Akashi

EnergyPro Building Energy Analysis. Nine-story Office Building

PROJECT NAME CLEVELAND CLINIC PROJECT #

A HYBRID MONITORING-MODELING PROCEDURE FOR ANALYZING THE PERFORMANCE OF LARGE CENTRAL CHILLING PLANTS

DEVELOPMENT OF A HIGH-PERFORMANCE OFFICE BUILDING SIMULATION MODEL FOR A HOT AND HUMID CLIMATE

UNDERFLOOR AIR DISTRIBUTION INTEGRATED WITH AN INDIRECT AND DIRECT EVAPORATIVE COOLING ASSISTED 100% OUTDOOR AIR SYSTEM

COMPUTER SIMULATION AND EXPERIMENTAL VALIDATION OF A MODERN HOTEL ON BUILDING ENERGY CONSERVATION

Xavier University of Louisiana

Sound HVAC Choices for Sustainable Design. Julian de Bullet

Technical Report Two: Building and Plant Energy Analysis Report

Building Load and Energy Estimates Analysis. Instructor: Dr. Mumma. October 28, Thesis Building Sponsor s: INOVA Fairfax Hospital

Retro-Commissioning for Energy Efficiency

DEVELOPMENT OF NEW SELF-COMPARISON TEST SUITES FOR ENERGYPLUS

Building Control Strategies That Work to Improve Your Energy Bottom Line

ENERGY SAVING OF AIR-CONDITIONING IN MASS MERCHANDISERS BY OPERATIONAL CHANGE OF AIR-CONDITIONING SYSTEM

INCENTIVE ESTIMATOR HVAC USER GUIDE CONTENTS FLORIDA CUSTOM INCENTIVE PROGRAM

Giuseppe Giordano Founder & CEO

EVALUATION OF DISTRIBUTION SYSTEM PERFORMANCE IN DISTRICT HEATING AND COOLING SYSTEM

Energy Efficiency in Building Active Design Part II

A survey on energy consumption status and characteristics of hotel buildings in Guangzhou

The energy benefits of View Dynamic Glass

Modeling and analyzing solar cooling systems in Polysun

Building Energy Efficiency Analysis for a High School

AEE Technical Roundtable Measurement and Verification. Alec Stevens, PE April 8, 2014

Great Ocean Rd Ice Creamery

Project : Power & Fuel consumption - an engineering initiative. VPS Rockland, Dwarka.

NORTH AMERICAN MONITORING OF A HOTEL WITH ROOM SIZE GSHPS

Water Bottling Facility

*Corresponding authors. Tel.: x415, address: (N. Zhu)

Green Building Parameters & Case Studies

Ground-Coupled Heat Pump And Energy Storage

2/17/2017. Energy Accounting & Education. Topics (Electricity) Creating Electricity

Energy Simulation of a Heat Pump System with Thermal Storage according to Control Strategies

Chilled Water System Optimization

Acknowledgements 4. Executive Summary 5

EnergyPro Building Energy Analysis. Single-story School Building

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

Continuous Commissioning Leading Energy Project Process - An Industry Approach

Retrocommissioning Investigation Report

The correct citation for this paper is:

Does Evaporative Cooling Make Sense in Arid Climates?

METHODOLOGY The process starts with a collection of available information, continued by an audit in loco, it is

CASE STUDIES ON HVAC SYSTEM PERFORMANCE USING A WHOLE BUILDING SIMULATION BASED REAL-TIME ENERGY EVALUATION APPROACH WITH BEMS

ctbuh.org/papers The Evaluation of Performance for the Application of a Heat Recovery Ventilator to High-rise Apartments Title:

Concentrating solar power in sustainable tourism

Proceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28

DISTRICT HEAT DRIVEN ABSORPTION COOLING OF DISTRICT COOLING PLANTS IN TRONDHEIM, NORWAY

BEYOND O&M. Shawn Maurer SEDAC Building Energy Specialist. Smart Energy Design Assistance Center (SEDAC), University of Illinois at Urbana Champaign

LESSONS LEARNED IN MODELING UNDERFLOOR AIR DISTRIBUTION SYSTEM

Existing Building Cx: Processes & Results A Cultural Journey. Barry Abramson Senior Vice President Servidyne

Italcementi Center for Research and Innovation

Introduction Table of Contents

SIMULATION VERSUS REALITY 4 CASE STUDIES. Anthony Calderone Aurecon, Melbourne, Australia

Building Operator Certification Level I

Transcription:

CONDENSING TEMPERATURE CONTROL THROUGH ENERGY MANAGEMENT SYSTEM SIMULATON FOR A LARGE OFFICE BUILDING Young-Hoon Kwak 1, Dong-Seok Kong 1, Se-Hwan Cheon 1, Ro-Yeul Kwak 2, and Jung-Ho Huh 3 1 Department of Architectural Engineering, University of Seoul, Seoul, Korea 2 School of Architecture, Hannam University, Daejeon, Korea 3 School of Architecture & Architectural Engineering, University of Seoul, Seoul, Korea ABSTRACT For the efficient energy use, the study analyzed the outdoor wet bulb temperature in a large office building, which is operated by several chillers and cooling towers in a hot and humid weather condition. This simulation study modelled and calibrated the target building through the measured energy consumption data. Condensing water supply temperature of the cooling tower was controled as an energy efficient measure. The result showed that by controlling the condensing water supply temperature based on the monthly wet bulb temperature change, the energy consumption in the cooling season could be saved by 1.4%. If the control of hourly condensing water supply temperature is possible, up to 6.6% of energy can be saved. INTRODUCTION Plant equipment that cover the basic cooling/heating load consumes a lot of energy. Particularly, the energy consumed by chillers, cooling towers, and circulation pumps that cover cooling/heating load take large part of the total energy consumption. Thus, any efficient energy use requires an energy control of plant equipment. This study plans to reduce energy consumption by controlling the reset temperature of condensing water based on the outdoor temperature (wet bulb temperature) among the elements of the plant equipment. The previous study has shown that the COP of a chiller may increase by 12.1 to 110.4% by dynamically operating the cooling tower fan, and controlling the condensing water temperature according to outdoor temperature and the partial load of the chiller(yu and Chan, 2006). Also, another study showed that the COP of the chiller can be increased by 2.3 to 110.4% by coding a model, which was verified by TRNSYS, with FORTRAN subroutines and by resetting the condensing water temperature based on outdoor temperature(chan and Yu, 2006). Under a subtropical climate, another study could also reduce the compressor power by 8.6 to 40.2% by controlling the condensing temperature(yu and Chan, 2005). Furthermore, they calculated the potential electricity reduction in hotel A by 18.2%, and the potential energy reduction in hotel B by 29% by controlling head pressure and condensing temperature(chan and Yu, 2002). These studies analyzed the increase in the COP of chillers and corresponding energy reduction by controlling condensing temperature. But these studies mostly focused on air-cooled chillers and analyzed the energy reduction by a simulation under a subtropic climate based on TRNSYS. In a building, like the target building for this study, the absorption chiller and the centrifugal water chiller are dynamically operated together. The study determined that a new energy saving method could be proposed by controlling condensing water temperature using the climate data that change in a real time. Meanwhile, controlling the condensing water temperature is normally performed by bypass and automatic control. Generally, the temperature for the condensing water is set during the installation, and is rarely reset or adjusted. But this study assumed that the condensing water temperature would be easily adjustable. The study analyzed the outdoor wet bulb temperature in a large office building that is operated by several chillers and cooling towers in a hot and humid weather condition, and also analyzed the potential energy saved by modeling the target building using the energy simulation, adjusting its energy consumption based on the measured energy usage, and controlling the condensing water supply temperature of the cooling towers. BACKGROUND Cooling Tower A cooling tower cools down the condensing water used in the condenser of the chiller. The condensing water that completed its mission at the condenser of the chiller and returned to the cooling tower at a higher temperature falls down from the top of the cooling tower gradually, and as it contacts the uprising outdoor air, some of it is vaporized and the temperature of the rest is reduced(lee et al., 2002). Such a principle can be easily explained as the heat exchange between the condensing water and outdoor air, and the temperature of the condensing water affects the performance of the chiller considerably. The temperature of the condensing water is determined by how much heat it emits. The amount - 2619 -

of the chiller heat emitted can be calculated, as in Eq. (1), by the log mean temperature difference between the total heat transfer coefficient of the cooling tower and the ambient outdoor wet bulb temperature (Chan and Yu, 2002; Chan and Yu, 2006; Yu and Chan, 2005; Yu and Chan, 2006). Meanwhile, Figure 1 shows the temperature distribution between the condensing water and outdoor air. A -(minus) B value is called Range, and D -(minus) C value is called Approach. Here, air temperature refers to the outdoor wet bulb temperature. Range and Approach become key factors in determining the capacity of the cooling tower(ashrae, 2008; KENCA, 2008; Jayamaha, 2006; Lee et al., 2002; McQuiston et al., 2000). P Expansion device Condenser Evaporator Decrease in condenser water temperature Compressor Reduction in pressure differential due to decrease in condensing pressure Figure 2 Pressure-enthalpy(P-h) diagram showing effect of reducing condenser water temperature on chiller efficiency MODELING AND CALIBRATION Building modeling The target building is G building located in Seoul. Table 1 shows overview of the target building and shown in Figure 3 are the overall plant equipment and the air-conditioning system diagram of the target building(kwak, R. et al., 2011; Kwak, Y. et al., 2011). h Table 1 Overview of the target building Figure 1 Temperature relationships between water and air in counterflow cooling tower Condenser temperature and energy savings The temperature of Range and Approach in the cooling tower affects the energy consumption made by the cooling tower and chiller. The larger the Range, and the smaller the Approach, the higher the energy reduction can become(jayamaha, 2006; KARSE, 2004; Wulfinghoff, 1999). The typical Approach temperature is 5 C and for the absorption chiller, it is between 6 ~ 9 C(KENCA, 2008). As shown in Figure 2, the lower the condensing water supply temperature, the more improved the efficiency of the chiller can become. The control of the condensing water supply temperature can increase the efficiency of the chiller and save the operating cost(jayamaha, 2006). Theoretically, the condensing water supply temperature can cool down the outdoor wet bulb temperature so as to allow the condenser water whose temperature is lower than the dry bulb temperature of the ambient air. But it requires a larger surface area and a larger air circulation rate, and therefore, it is practically impossible (KENCA, 2008). CATEGORIES CONTENTS Target building G building in Seoul Stories B6 ~ 38F Floor area 141,551 Main facilities Office, Arcade, Parking lot Absorption chiller heater: 1,200 RT x 3EA Absorption chiller:310 RT x 2 EA Plant equipment Centrifugal water chiller: 310 RT x 1 EA Boiler: 4,000 kg/h x 1 EA, 2,000 kg/h x 1 EA Office: single duct CAV or VAV(Fan Power Unit) HVAC B2F ~ B4F: CAV Basement, Arcade: CAV or VAV 1,400 kw x 3 EA Generator Type: Gas Engine, Co-generator EA OA Natural Gas AHU RA Co-generator Chilled water SA RA Hot water Absorption Chiller Heat Exchanger Centrifugal Chiller Heat Exchanger Boiler Figure 3 The overview of plant equipment and airconditioning system FPU SA Cooling Tower Indoor Absorption Chiller Heater Steam - 2620 -

Proceedings of Building Simulation 2011: There are various types of chillers in the target building because the operation time and the usage of each chiller depends on the energy policy. The main chillers are three absorption chiller heaters, which cover the most of the weekly cooling load. Two absorption chillers use the waste heat of the cogenerator, and supplement the main chillers. The centrifugal water chiller is operated normally at night, and sometimes during daylight if necessary. Shown in Figure 4 is the operation plan for the actual chillers on a week day in August, 2009(Kwak, R. et al., 2011). Collect Information about the Building (Site-visit, Drawings, Weather Data, Utility Bills, etc..) Adjust Input Values Create Input File Identify Possible Reasons for The Mismatch Between Simulated Results and Measured Data Obtain Results from Simulation Models Collect Measured Data Compare Simulated Results to Measured Data (Graphical and/or Statistical Methods) No Determine If Simulated Results and Measured Data Match Yes Calibration is Complete Figure 5 Model calibration procedure Electricity Energy Consumption[MWh] 2,000 Figure 4 Chiller operation time (a week day in August) Model Calibration The target building was modeled by collecting related drawings, interviews with operators, and climate data. Later, the model was revised by comparing the measured energy consumption in 2009 and the simulated energy consumption. As in Eq. (2), (3) and (4), the model was revised by reviewing the error using the monthly data calibration equation(m&v Guideline, 2002). If the model does not satisfy the value of acceptance, the causes for the error are analyzed to adjust the input value. Then the input file is adjusted and the error is compared again. Shown in Figure 5 is the process explained above(krarti, 2000). The calibrated model is determined as the baseline model, which is used to calculate the energy savings. Measured Simulated 1,800 1,600 1,400 1,200 1,000 800 600 400 200 0 Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Month Figure 6 Comparison of measured and simulated energy consumption Table 2 Acceptable tolerance for monthly data calibration INDEX ACCEPTABLE VALUE CALCULATED VALUE Shown in Figure 6 is the comparison between the electricity consumption of the the measured and simulation model. Table 2 is the result of the calculated errors ( ) based on the Eq. (2), (3), and (4). The percentage difference of between the measured and simulation energy consumption are less than, respectively. Since the - 2621 -

error value is within the acceptance value, it is determined that the model calibration was successful (M&V Guideline, 2002). The total electricity consumption can be categorized by the type of use, as in Lighting/Elec. Equip.(46%) > Plant (26%) > HVAC (22%) > Power (6%) in the order of the electricity consumption(refer to Figure 7). Since the measured energy consumption by element and the simulated energy consumption were determined to have been calibrated well, the study excludes the analysis of each element of plant equipment, and compares and analyzes the total energy consumption. However, this study analyzed only the electricity consumption and excluded the analysis of gas consumption. Electricity consumption [%] 50 45 40 35 30 25 20 15 10 5 0 Measured(%) Simulated(%) Measured[kWh] Simulated[kWh] 26.0226.26 22.3122.86 45.9345.22 Plant HVAC Lighting/Elec. Equip. Each element Figure 7 Comparison between the measured and simulated electricity consumption of the target building each element RESULT AND DISCUSSION 5.67 5.61 Power 9,000 8,000 7,000 6,000 5,000 4,000 3,000 2,000 1,000 Control of the condensing water supply temperature related to the chillers As has been mentioned, lowering the condensing water supply temperature can reduce energy consumption. But, once it exceeds the permissible range, lowing the condensing water supply temperature can in fact result in consuming more energy. Also, shown in Figure 8, controlling the condensing water supply temperature requires to find the optimal temperature point by considering the efficiency of the overall system that includes both the cooling towers and chillers(jayamaha, 2006). Therefore, comparing the energy consumption based on the control of condensing water supply temperature should not compare the each energy consumption of the facility; rather, it should consider both the plant equipment, such as the chillers and cooling towers, and the energy consumption of the circulation pump. Since this refers to the electricity consumption of the previously categorized Plant (refer to Figure 7), the study will compare not the total energy consumption of the building, but compare the electricity consumption of the plant. - Electricity consumption [MWh] Also, the study focuses on the cooling energy consumption in cooling seasons, and therefore, compares the electricity consumption of the plant from June to September. Figure 8 Effect of condenser water temperature on chiller and cooling tower efficiency Cooling tower design conditions in Korea Due to the hot and humid summer climate in Korea, the design temperature of the cooling tower is somewhat higher than that in the USA. Shown in Table 3 is the comparison between the cooling tower design temperature of Korea and USA(KENCA, 2008; Jayamaha, 2006). Table 4 is the cooling tower design conditions and specifications of the target building, which are identical to the usual cooling tower design temperature in Korea. (Kwak, R. et al., 2011). Table 3 Comparison between the cooling tower design temperature of Korea and USA TEMPERATURE KOREA USA Condensing water return temperature Condensing water supply temperature Outdoor wet bulb temperature 37 C 35 C (95 F) 32 C 29.4 C (85 F) 27 C 26.7 C (80 F) Table 4 Design conditions for the cooling tower of the target building CATEGORIES CONTENTS Flow rate 200 /s Fan motor Pump head Condensing water return temperature Condensing water supply temperature Outdoor wet bulb temperature 44 kw 60.43 kpa 37.5 C 32 C 27 C - 2622 -

Controlling condensing water supply temperature (Total) The study tried and controlled the condensing water supply temperature differently from the design condition by changing(increasing or decreasing) the design temperature by 1ºC and analyzing the corresponding energy consumption. Shown in Figure 9 is the total energy consumption by controlling the condensing water supply temperature. Here, the total energy consumption refers to the sum of the electricity usage from June to September in the plant. The comparison of the total energy consumption shows that as opposed to the design temperature (32ºC), the energy consumption was the smallest at 30ºC, 2ºC lower than the design temperature. This menas that by lowering the condensing water supply temperature by 2ºC from 32ºC, 11 MWh (0.3%) of the total energy consumption can be saved from 3,924 MWh to 3,913 MWh. Total Eenrgy Consumption[MWh] 4,300 4,200 4,100 4,000 3,900 3,800 3,700 4,222 4,013 3,938 3,913 3,915 3,924 3,937 4,009 4,022 27 28 29 30 31 32 33 34 35 Condenser Water Supply Temperture[ ] Total Figure 9 Total energy consumption by controlling condensing water supply temperature [MWh] Controlling condensing water supply temperature (monthly) The comparison of the total energy from June to September shows that as in Figure 9, the energy consumption was the lowest at 3,913 MWh when the condensing water supply temperature was at 30 C. However, the comparison of the energy consumption based on the control of the monthly condensing water supply temperature is shown in Figure 10 and Table 5. As shown in Figure 10 and Table 5, while the total energy consumption was lowest when the condensing water supply temperature was at 30 C, the temperature at which the monthly energy consumption was smallest was different each month: in June, it was 29 C; in July, it was 33 C; in August, it was 34ºC; and in September, it was 28 C. (refer to Table 5 shadow zone). Particularly in July and August, the smallest energy consumption was recorded while the measured condensing water supply temperature was higher than the design temperature. Since the target building mixes and uses the absorption chiller heaters, absorption chillers, and centrifugal water chiller, the energy consumption was smallest when the condensing water supply temperature was higher than the design temperature. For, as has been mentioned, the Approach temperature of the absorption chiller is set higher than that of the typical Approach. If the design condensing water supply temperature (32 C) is set to 29 C, 33 C, 34 C and 28 C from June to September, respectively, the total energy consumption will become 3,868 MWh (876 MWh + 1,079 MWh + 1,106 MWh + 807 MWh), which is smaller than 3,294 MWh at 32 C of the design temperature by 56 MWh (1.4%). Therefore, energy saving can be expected by controlling the condensing water supply temperature by each month. Energy Consumption[MWh] 1,400 1,200 1,000 800 600 400 200 0 27 28 29 30 31 32 33 34 35 Condenser Water Supply Temperature[ ] Figure 10 Monthly energy consumption based on the control of condensing water supply temperature [MWh] Table 5 Monthly energy consumption based on the control of condensing water supply temperature [MWh] TEMP. JUN JUL AUG SEP TOTAL 27 C 913 1,121 1,270 828 4,222 28 C 881 1,134 1,191 807 4,013 29 C 876 1,102 1,152 808 3,938 30 C 877 1,089 1,131 816 3,913 31 C 884 1,083 1,121 827 3,915 32 C 891 1,080 1,115 838 3,924 33 C 898 1,079 1,112 848 3,937 34 C 915 1,122 1,106 866 4,009 35 C 923 1,120 1,107 872 4,022 Controlling condensing water supply temperature (hourly) Controlling the condensing water supply temperature is based on the amount of heat transferred between the outdoor wet bulb temperature and condensing water Thus, it can be considered that the condensing water supply Jun Jul Aug Sep - 2623 -

Proceedings of Building Simulation 2011: temperature is governed by the outdoor wet bulb temperature. Shown in Figure 11 is the measured climate data from June to September, 2009, which signifies that the amount of heat transfer of condensing water can differ by the hourly-changing outdoor wet bulb temperature. Also, because the monthly outdoor temperature distribution is different, the study categorized the outdoor wet bulb temperature. Figure 11 Coincidence outdoor temperature and humidity data for the site As in Figure 11, most of the measured outdoor wet bulb temperature in 2009 was lower than the design outdoor wet bulb temperature. Since the heat transfer with air in fact occurs not at the design outdoor wet bulb temperature, but at the measured outdoor wet bulb temperature, energy saving can be possible by lowering the condensing water supply temperature. The analysis of the frequency of the hourly wet bulb temperature shows that in June, the frequency of wet bulb temperature between 17 and 20 C occupied 54% (392) of the total frequency, and in July, the frequency of wet bulb temperature between 20 and 23 C occupied 82% (613) of the total frequency. Also, the frequency of wet bulb temperature at 21 to 24 C in August occupied 69% (515) of the total frequency in August, and in September, the frequency at 16~19 C occupied 71% (511) of the total frequency, all of which show that the wet bulb temperature was highest in August, followed by July, June and September. Dramatically, the energy consumption was in the same order as the wet bulb temperature, from August to July, June and September. As shown in Table 5, controlling the condensing water supply temperature at 29 C in June and 28 C in September reduced energy consumption. But, lowering the temperature increased the energy consumption in July and August because the outdoor wet bulb temperature in July and August is higher than that in June and September, which results in less heat transfer between condensing water and ambient air. It is typically known that when the outdoor wet bulb temperature is high, the air volume is small, the condensing water temperature is high, and the amount of condensing water is small, the cooling tower s heat transfer performance degrades(kenca, 2008). The Approach temperature shows the relation between the condensing water supply temperature and the outdoor wet bulb temperature. Considering the result of the previous studies, the monthly outdoor wet bulb temperature in June, July, August and September is 18 C, 22 C, 23 C, and 17 C, respectively. Meanwhile, the condensing water supply temperature at which the the energy consumption was smallest was 29 C in June, 33 C in July, 34 C in August, and 28 C in September. Of particular interest is that the Approach temperature of both the condensing water supply temperature and the monthly representative wet bulb temperature in from June to September is 11 C. While it was previously suggested that when the Approach temperature is low, energy can be saved. However, the target building mixes and uses various types of chillers and the outdoor dry bulb temperature is high, and thus, the Approach temperature is calculated high. If the correlation between the outdoor wet bulb temperature and energy consumption between June and September is to be analyzed, the calculation of the smallest energy consumption can be calculated by Eq. (5). But, as in Table 5, setting the condensing water supply temperature in June to 28 C does not result in the smallest energy consumption. The temperature was actually at 29 C. On the other hand, if the condensing water supply temperature in September is set from 28 C to 29 C, the difference in energy consumption is negligible. Thus, Eq. (5) is corrected by the energy consumption in June and September, which results in the following Eq. (6). Using Eq. (6), the study applied the EMS class by EnergyPlus to control the hourly condensing water supply temperature. The EMS class by EnergyPlus, as shown in Figure 12, consists of the H/W objects, such as Sensors and Actuators, and S/W objects, such as ProgramCallingManager, Program, Subroutine, and Variables(Ellis et al., 2007). - 2624 -

Figure 12 Objects of the EMS class by EnergyPlus Shown in Figure 13 is an example of coding Eq. (6) using ERL(EnergyPlus Runtime Language) by EnergyPlus at the program class of the EMS. Figure 13 Example of ERL code embedded in the EnergyManagementSystem:Program The total energy consumption between June and September was 3,665 MWh, which is 259 MWh (6.6%) lower than that under the design condensing water supply temperature(32 C). Shown in Figure 14 is the graph of the energy consumption based on the control of the condensing water supply temperature, as has been calculated by this study. Total Energy Consumption[MWh] EnergyManagementSystem:Program, T_CD_SetpointCalc,!- Name IF (T_WB < 18), SET T_CD_SetPoint_Resetting = 29, ELSEIF (T_WB >= 18) && (T_WB <= 23), SET T_CD_SetPoint_Resetting = T_WB + 11, ELSE, SET T_CD_SetPoint_Resetting = 34, ENDIF; 4,000 3,900 3,800 3,700 3,600 3,500 3,400 3,924 3,913 3,868 3,665 32 30 Monthly Hourly Condenser Water Supply Temperature Control Strategies Figure 14 Comparison of the total energy consumption by the control of condensing water supply temperature [MWh] As shown in the Figure 14, lowering the condensing water supply temperature below the design temperature results in energy reduction. Also, controlling the monthly or hourly condensing water supply temperature increases energy saved, because it allows detailed control of the temperature. But, in reality, it is almost impossible to control the hourly condensing water supply temperature. On the other hand, it is determined to be possible to control the monthly temperature. CONCLUSION Controlling the condensing water temperature is normally performed by bypass and automatic control. Generally, the temperature for the condensing water is set during the installation, and is rarely reset or adjusted. But this study assumed that the condensing water temperature would be easily adjustable. Due to the hot and humid summer climate in Korea, the study analyzed the outdoor wet bulb temperature in a large office building that is operated by several chillers and cooling towers, and also analyzed the potential energy saved by modeling the target building using the EMS class by EnergyPlus, adjusting its energy consumption based on the measured energy usage, and controlling the condensing water supply temperature of the cooling towers. Based on the design condensing water supply temperature as the basis, the study analyzed the total energy consumption between June and September, the cooling season by controlling either the total condensing water supply temperature, or the monthly and hourly temperature. The analysis resulted in the following energy savings: Under the design condensing water supply temperature: 3,924 MWh By controlling the total condensing water supply temperature: 3,913 MWh (0.3% savings to the design condensing water supply temperature) By controlling the monthly condensing water supply temperature: 3,868 MWh (1.4% savings to the design condensing water supply temperature) By controlling the hourly condensing water supply temperature: 3,665 MWh (6.6% savings to the design condensing water supply temperature) The result showed that by controlling the condensing water supply temperature based on the monthly wet bulb temperature change, the energy consumption in the cooling season (June to September) could be saved by 1.4%. If the control of the hourly condensing water supply temperature is possible, up to 6.6% of energy can be saved. NOMENCLATURE - 2625 -

REFERENCES ASHRAE. 2008. ASHRAE Handbook-HVAC Systems and Equipment. Chapter 39 COOLING TOWERS, American Society of Heating, Refrigerating and Air-Conditioning Engineers, USA. Chan K.T., and Yu F.W. 2002. Applying condensingtemperature control in air-cooled reciprocating water chillers for energy efficiency, Applied Energy, 72. Chan K.T., and Yu F.W. 2006. Thermodynamicbehaviour model for air-cooled screw chillers with a variable set-point condensing temperature, Applied Energy, 83. Ellis, P.G., Torcellini, P.A., and Crawley, D.B. 2007. Simulation of energy management system in EnergyPlus, Building Simulation 2007, China. EnergyPlus. Version 6.0 documentation. 2010, USA. Jayamaha L. 2006. Energy-Efficient Building System : green strategies for operation and maintenance, McGraw-Hill, USA. KARSE. 2004. KARSE Handbook-Enegy Saving for Building Services, Korea Association of Air Conditioning Refrigerating and Sanitary Engineers, Korea. KENCA. 2008. Heating Ventilation Air conditioning Design, Korea Engineering & Consulting Association, Korea. Krarti M. 2000. ENERGY AUDIT OF BUILDING SYSTEMS An Engineering Approach, CRC press, USA. Kwak Ro-Yeul et al. 2011. Feasibility study of BEMS applications, BSME lab internal technical report. Hannam University, Korea. Kwak Young-Hoon, Cheon Se-Hwan, Lee Sang- Moon, and Huh Jung-Ho. 2010. Application of an EMS Simulation for Building Energy Saving, Proceedings of the SAREK 2010 Summer Annual Conference, Korea. Kwak Young-Hoon, Kong Dong-Seok, Cheon Se- Hwan, Kwak Ro-Yeul, and Huh Jung-Ho. 2011. Analysis of Energy Potential Savings through Energy Management System Simulation for a Large Office Building, Proceedings of the KIAEBS 2011 Spring Annual Conference, Korea. Lee C., Bang S., and Ham H. 2002. Air-Conditioning Equipment, Sejinsa, Korea. McQuiston F.C, Parker J.D, and Spitler J.D. 2000. Heating, Ventilating, and Air Conditioning analysis and design, 5 th edition, John Wiley & Sons, USA. M&V Guidelines: Measurement and Verification for Federal Energy Project, 2002, Version 2.2. Wulfinghoff D.R. 1999. Energy efficiency manual, Energy Institute Press, USA. Yu F.W., and Chan K.T. 2005. Advanced control of condensing temperature for enhancing the operating efficiency of air-cooled chillers, Building and Environment, 40. Yu F.W., and Chan K.T. 2006. Tune up of the set point of condensing temperature for more energy efficient air cooled chillers, Energy Conversion and Management, 47. - 2626 -