SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: -

Similar documents
SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS:

MGVCL/MM/1043/13-14/11 KV Disc Insulators (Porcelain)

PART-II SPECIFICATION OF 22KV PIN INSULATORS. This specification covers 22KV Pin Type Insulators for 22KV H.T. over head power lines.

Date: TECHNICAL SPECIFICATION FOR (LT,11KV, 33KV) PORCELAIN PIN INSULATORS

Maharashtra State Electricity Distribution Co. Ltd.

Maharashtra State Electricity Distribution Co. Ltd.

SPECIFICATION OF HT-LT STAY (GUY) INSULATORS:

SPECIFICATION FOR HT-LT STAY (GUY) INSULATORS:

Specification No. CSC- XXIX/DH/UH/P&D/

11KV PORCELAIN INSULATORS AND FITTINGS

Maharashtra State Electricity Distribution Co. Ltd.

ANNEXURE - ' D ' TECHNICAL SPECIFICATION FOR INSULATOR PINS ( PINS FOR 11,22 AND 33 kv INSULATORS )

SPECIFICATION FOR DISC INSULATORS (Standard Type)

MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO. Ltd. (MUMBAI) SCHEDULE 'A' TECHNICAL SPECIFICATION FOR. 11 kv, 22 kv & 33 kv HORN GAP FUSES FOR

TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS

TECHNICAL SPECIFICATION FOR CONDUCTOR HARDWARE FITTING FOR 11/22/33 kv OVERHEAD POWER LINES

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA

9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA

TECHNICAL SPECIFICATION FOR 11 POST INSULATORS, 11 KV & 33 KV PIN INSULATORS AND 11 KV, B&S TYPE 45 KN & 70 KN DISC INSULATORS.

TECHNICAL SPECIFICATION FOR 11 KV & 33 KV POST INSULATORS, 11 KV & 33 KV PIN INSULATORS AND 11 KV, B&S TYPE 45 KN & 70 KN DISC INSULATORS.

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS

SPECIFICATION FOR STAY INSULATORS (PORCELAIN)

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS Insulators & Lightening Arrestor GROUP K & L

TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1

SPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type

SPECIFICATION OF LT AERIAL BUNCHED (AB) CABLES (Size: 3C x 35mm² +1C x mm²) FOR LT LINES (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY)

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

TECHNICAL SPECIFICATION OF UNARMOURED FLAT 1100 VOLTS L.T. PVC INSULATED TWIN CORE 4.0mm² CABLE WITH ROUND ALUMINIUM CONDUCTOR BLACK SHEATHED.

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS. Insulators & Lightening Arrestors GROUP A

SEAL & SIGNATURE OF THE TENDERER

CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS

2. RATED VOLTAGE: The rated voltage of the AB cables shall be 1100 volts

General Requirements. Technical Specifications for Insulators of Transmission Lines

TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1

TECHNICAL SPECIFICATION OF 70KN & 45KNDISC INSULATOR (B & S)

TECHNICAL SPECIFICATION OF LONG ROD PORCELAIN INSULATORS FOR TRANSMISSION LINES

TECHNICAL SPECIFICATION

a) Temperature Variation : 5ºC to 55ºC b) Relative humidity : Upto 95% c) Altitude : 0 to 1000 Mtrs. d) No.of tropical monsoon months : 3 (Three)

POST AND DISC INSULATOR

TURKISH ELECTRICITY DISTRIBUTION CO. TECHNICAL SPECIFICATION FOR POST (SUPPORT) INSULATORS FOR MEDIUM VOLTAGE SYSTEMS

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv)

TECHNICAL SPECIFICATION OF ACCESSORIES SUITABLE FOR 7/3.15 mm G.I. EARTH WIRE

Technical Specification for 11 KV, 5KN, 340 Creepage Distance Pin type Composite (Polymer) Insulator with rod

APDRP SCHEME, WESCO. Technical Specification for 33KV Air Break Switch PART 1: SCOPE AND CONDITIONS

TECHNICAL SPECIFICATION FOR 11KV COMPOSITE INSULATORS (SILICON RUBBER HOUSED)

1. 8mtr 200Kg PSC Pole 2. 9mtr 300Kg PSC Pole

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

No: PUR/IMP/JPL/UVIT/ISO/39 July 29, 2008

PART-II. TECHNICAL SPECIFICATIONS FOR 11 KV, 45KN, 320 Creepage Distance, Long rod (B&S) type Composite (Polymer) Insulator.

NATIONAL ELECTRIC POWER COMPANY (NEPCO) TENDERNO. 9/2013 FOR THE SUPPLY OF INSULATORS AND FITTINGS FOR DOUBLE AND QUADRUPLE CIRCUITS 132 kv OHTL's

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

Specification No. CSC-70/DH/UH/P&D/

11 KV, 45KN, 320 Creepage Distance, Long rod (B&S) type Composite (Polymer) Insulator

ASSAM POWER DISTRIBUTION COMPANY LIMITED. OFFICE OF THE CHIEF GENERAL MANAGER (HQ),APDCL BIJULEE BHAWAN, PALTANBAZAR, GUWAHATI

Technical Specification for Steel Forged Fittings

5.2 The phase conductors shall be provided with one, two & three ridges for easy identification.

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

Technical Specifications for 11 KV, 45KN, 320 mm. Creepage Distance, Long rod, (B&S) type Composite (Polymer) Insulator

TECHNICAL SPECIFICATION FOR G.I. BARBED WIRE. (SPECIFICATION NO.MM/I/G.I.BARBED WIRE/2006) (Dt )

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA

TECHNICAL SPECIFICATION FOR RATE CONTRACT OF INSULATING MATS

Technical Specification for Helical Fittings for Overhead Power Lines

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara:

Technical Specification for. Insulators. Part 1. Insulators for High and Extra-High Voltage Overhead Lines

NEPAL ELECTRICITY AUTHORITY (An Undertaking of Government of Nepal) Distribution and Consumer Services Butwal Regional Office

8. Hydrophobicity classification guide STRI guide 1.92/1 9. Radio interference characteristics of overhead power lines and high-voltage equipment

SECTION-II (VOLUME-II) PAGE 1

COMPOSITE INSULATORS

MGVCL/MM/ 3Cx240 mm 2 XLPE Cables/2077 TECHNICAL SPECIFICATION FOR 11 KV XLPE POWER CABLE (CROSS LINKED POLYTHELENE DRY GAS CURED) SECTION I

TECHNICAL SPECIFICATIONS FOR. 11 KV, 45 KN, 320 mm. Creepage Distance, Long rod (B&S) type Composite (Polymer) Insulators

TECHNICAL SPECIFICATION FOR CONDUCTORS

Standard. Extra High Voltage (EHV) Post Insulators Standard R Version 1.0, June Tasmanian Networks Pty Ltd (ABN )

TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATION FOR FRP FENCING AROUND DISTRIBUTION TRANSFORMER STATIONS

Technical Specification for Outdoor Porcelain Station Post Insulators

SPECIFICATION FOR POLYMER DISC INSULATOR

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES

10-SDMS-02 SPECIFICATIONS FOR BARE COPPER CONDUCTORS

TECHNICAL SPECIFICATION OF SILICON RUBBER HOUSED COMPOSITE INSULATORS FOR TRANSMISSION LINES

TECHNICAL SPECIFICATION FOR 3-PH SMC BOXES MADE FROM THERMOSETTING PLASTIC FOR 3-PH ENERGY METER.

SECTION 07 TECHNICAL SPECIFICATIONS 11KV OUTDOOR TYPE SINGLE PHASE METAL OXIDE (ZNO) GAPLESS LIGHTNING ARRESTER (LA)

FIJI ELECTRICITY AUTHORITY BIDDING DOCUMENT

6C-001 High-Voltage Pin-Type Insulator

SPECIFICATION FOR FRLS POWER CABLES

TABLE OF CONTENTS. Page FOREWORD INTRODUCTION SCOPE NORMATIVE REFERENCES

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION

33-SDMS-02 SPECIFICATIONS FOR

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION

TECHNICAL SPECIFICATION OF SILICON RUBBER HOUSED COMPOSITE INSULATORS FOR TRANSMISSION LINES

TECHNICAL SPECIFICATION FOR SUPPLY OF WEDGE CONNECTOR TO BE USED IN POWER DISTRIBUTION SYSTEM

660 Volts 630 & 800AMP

11-SDMS-01 REV. 03 ( )

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

P.V.C. INSULATED UNARMOURED COPPER CABLES

SPECIFICATION OF NEOPRENE RUBBER SEALS

ACCELARATED POWER DEVELOPMENT AND REFORM PROGRAMME. Technical Specification (T.S)

FOREWORD SCOPE NORMATIVE REFERENCES DEFINITIONS REQUIREMENTS... 4

Transcription:

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: - 1. SCOPE: - This specification covers 11KV Disc Type & 11KV/ 22KV Pin Type Insulators for 11/22KV H.T. over head power lines. 2. APPLICABLE STANDARDS: - Except when they conflict with specific requirement in this specification, the insulators shall comply with the Indian Standard specification, IS-731/1971and the latest version thereof. The insulators fittings shall comply with the Indian Standard specification IS-2486/Part-I/1993, IS-2486/Part.II/ 1989 or the latest version thereof. 3. DESCRIPTION: - 3.1 DISC INSULATORS. :- 11KV Brown Glazed 'Disc' insulators conforming to IS-731/71 and subsequent amendment No. 1 to 5 for suspension or tension strings, ball and socket type having ball shank dia.16mm and minimum failing load of 70 KN along with phospher bronze 'W' clips. 3.2 PIN INSULATORS:- 11/22KV Brown Glazed pin insulators confirming to IS-731/1971 and subsequent amendment No.1 to 5 to give rigid support to an over-head line and intended to be mounted vertically on supporting structure by GI Pin passing up inside this insulator with minimum failing loads 10 KN. 4. GENERAL REQUIREMENT: - i) The porcelain shall be sound and free from defects, thoroughly vitrified and smoothly glazed. ii) The glaze shall be brown in colour. The glaze shall cover all the porcelain parts of the insulator except those areas which serve as 1

support during fixing or are left unglazed for the Purpose of assembly. iii) The design of the insulators shall be such that stresses due to expansion and contraction in any part of the insulator shall not lead to deterioration. The porcelain shall not engage directly with hard metal. iv) Cement used in the construction of the insulators shall not cause fracture by expansion or lessen by contraction and proper care shall be taken to locate the individual parts correctly during cementing. The cement shall not give rise to chemical reaction with metal fitting and its thickness shall be as uniform as possible. 5. ELECTRICAL AND MECHANICAL CHARACTERISTICS : - The electrical and mechanical particulars of 11KV Disc and 11/22KV Pin insulators shall be as per the Guaranteed Technical Particulars shown in Annexture-A & B attached herewith, measured at the following standard atmospheric conditions. 1. Ambient temperature 20 Deg. C 2. Barometric pressure 1013 millibars 3. Absolute Humidity 11 Grams of water per cubic mtrs. Corresponding to 63% relative humidity at 20 Deg.C. 6. BASIC INSULATION LEVELS: - 6.1 The test voltage of Disc. And Pin insulators shall be as per the values given in Guaranteed Technical Particulars shown in Annexure-A & attached. 6.2 In this specification power frequency voltages are expressed as peak values divided by 2 and impulse voltages are expressed as peak values. 6.3 The withstand flashover voltages are referred to the reference atmospheric conditions. 7. Ferrous parts of Disc. Insulators as per IS-2108/1977 shall be hot dip galvanized as per IS-2633/1986. 2

8. As the insulators are to be used anywhere in Gujarat State including the coastal area, the Creepage distances of specified in GTP are minimum. However, the firm may offer insulators of higher creepage distance, but the mechanical and electrical parameters of their product shall be as per the mechanical and electrical requirement given in Appendix-A & B attached. 9. TESTS: - i) All the tenderers must submit copies of type test certificates along with laboratory approved drawings for the products offered by them. The Certificates shall be from CPRI, ERDA, and Indian Institute of Science, Bangalore or any other Govt. recognized laboratory, but not more than 5 years old as on date of opening the tender. ii) Copy of type test certificate of each type offered must be submitted. iii) The type test certificate shall be final and complete for all the tests as per the list of type tests given in specification Cl.No.9.1of the specification. iv) Failure to submit the type test certificates as described above shall be liable for rejection of tender offer. v) Routine test shall be carried out on every insulator as specified in IS-731/71 with amendment No.1 to 5 and certificate issued with each batch. Details of test result on each of the insulator supplied, has to be submitted to inspector for his perusal and verification. vi) The insulators shall comply with the type tests as per IS- 731/1971with latest amendment 1 to 5 and as mentioned in Cl.No.9.1 below. 9.1 TYPE TESTS: - The following shall constitute the type tests (Cl.No.10.1.1 of IS- 731/1971). However, the test voltage value shall be as per GTP enclosed. 3

a) Visual examination. b) Verification of dimensions. c) Visible discharge test. d) Impulse voltage withstand test (+ve wave & -ve wave) e) Impulse voltage flashover test (+ve wave & -ve wave) f) Dry and wet power frequency voltage withstands test. g) Dry and wet power frequency flashover voltage test. h) Temperature Cycle test. i) 24 Hours mechanical failing load test (for Disc insulators only) or mechanical performance test. j) Electro mechanical failing load test (for Disc insulators only) k) Mechanical failing load test (for Pin insulators only) l) Puncture test. m) Porosity test. n) Galvanizing test (for Disc Insulators only) The tests shall be carried out on the two samples in the order mentioned in the Cl.10.1.1 of IS-731/1971. All the tests shall be carried out in the same laboratory. 9.2. ACCEPTANCE TESTS: - From the offered lot, samples shall be drawn randomly as per the criteria given. The firm has to arrange for carrying out all following acceptance tests at firms works only at firm's cost in presence of inspector deputed by MGVCL. a) Verification of dimensions and Visual examination. b) Temperature cycle tests. c) 24 Hours mechanical failing load test or mechanical performance test. (For disc. insulators only) d) Electro mechanical failing load test (for disc. insulators only) e) Mechanical failing load test (for pin insulators only) f) Puncture test. g) Porosity test. h) Galvanizing test (for disc. insulators only) 9.3. ROUTINE TESTS: - The following tests shall be carried out as routine tests by firm on each insulator before offering the lot for inspection. a) Visual examination. b) Mechanical routine test (for type 'B' string insulators units only) c) Electrical routine test (for type 'B' string insulators and rigid insulators). 4

10. DRAWING AND CATALOGUES: - The tenderer shall furnish catalogues, literature and detailed dimensional drawing of insulators offered showing section of the insulators to show the method of construction connecting arrangement, length and type of threads etc. The drawing shall be got approved by the User Department prior to commencing the bulk supply. 11. MARKING: - 11.1. Each insulator shall be legibly and indelibly marked to show the following. a) Name or trade mark of the manufacturer. b) Month and year of manufacturer. c) Minimum failing load. d) Country of manufacture. e) ISI Certification mark, if any. f) Word 'MGVCL' marked stickers to be provided on each insulator. 11.2. Marking on porcelain shall be printed and shall be applied before firing. 12. PACKING:- i) All insulators (without fittings) shall be packed in wooden crates suitable for easy but rough handling suitable for rail/road transport. Where more than one insulator is packed in a crate, wooden separators shall be fixed between the insulators to keep individual insulator in position, without movement within the crates. Disc. Insulators however, may be assembled in a string and then packed inside a crate, in above fashion. ii) The wooden crates shall be provided with steel hoop and bends for strength and durability to withstand rough handling. The bends shall have descriptive marking of the firm thereon. 5

iii) The firm shall provide at his cost, lead seal and wire on each wooden crate to facilitate sealing by the inspector of MGVCL after acceptance of the lot. 13. INSPECTION: - Party has to offer the materials for inspection duly packed in crates as mentioned in GTP. The inspection approval is valid for a period of 15 days from the date of inspection to enable the firm to dispatch the materials by arranging transportation at destination allotted thereof within the said period. After this period of 15 days, the validity of the inspection will lapse. Thereafter, the inspection approval will be revalidated by competent authority on furnishing written application explaining therein the valid reasons for delay in affecting dispatches. 14. The firm shall not dispatch the offered lot unless the same is inspected by the inspector of MGVCL & accepted by him after passing in all acceptance tests, and/or receipt of waival of inspection in writing from competent authority of MGVCL. Manufacturer's Name and Address. 6

Schedule for requirement of 11/22KV Pin & Disc Insulators. Sr. Description of materials No 1 11KV Pin Insulators Brown Glazed porcelain Insulator confirming to IS-731/1971 Ammendment 1 to 5 Type-B with 320mm minimum creepage distance and with lead/zinc thimble suitable for use with G.I.Forged pin having small steel heads as per IS-2486 (P.I)/1993 & IS-2486 (P.II)/1989 and revision with latest ammendment if any. - Confirming to REC Specification. - With minimum failing load of 10 KN. -Confirming to MGVCL specification attached herewith. 2 11KV Disc Insulators Brown Glazed porcelain Insulator confirming to IS-731/1971 and subsequent ammendment 1 to 5 for suspension and tension strings ball and socket type having pin ball. The minimum creepage distance shall be 320 mm. shank dia of 16 mm and minimum failing load of 7140 Kgs (70 KN) confirming to Board's specification attached herewith. The insulators shall have 'W' type phospher Bronze security clips for ball sockets portion of insulators confirming to IS-2486 (P- III/1974). The insulators shall also confirm to MGVCL specifications attached herewith. 3 22KV Pin Insulators Brown Glazed porcelain Pin Insulators confirming to IS-731/1971 Ammendment 1 to 5 Type-B with 560mm minimum creepage distance and with lead/zinc thimble suitable for use with G.I.Forged pin having large steel head as per IS-2486 (P.I)/1993 & IS-2486 (P.II)/1989-second revision and conforming REC specification. Quantity required. Type Test:- 1. The offers without type test certificate and certified drawing by Government approved laboratory will not be considered. 2. Party should submit his own design drawing with all dimensional details to be supported by type test certificate and attested drawings. 7

Manufacturer's Name and Address. PART-A MGVCL/MM/1017/TATKAL/11 KV Pin & Disc Insulators ANNEXURE-'A' TECHNICAL INFORMATION AND GUARANTEED TECHNICAL PARTICULARS: BIDDER HAS TO CONFIRM FOLLOWING IMPORTANT REQUIREMENT: Sr. No. Particulars 11KV Pin Insulator 11KV Disc. Insulator 1 Insulator shall be manufactured as per IS-731/1971 and subsequent amendment 1 to 5 or latest amendment of it. 2 Brown colour glazed 3 320mm (Min) creepage distance. 4 Mechanical failing load (Min) i) 10 KN (1020KG for Pin Insulator) ii) 70KN (7140KG for Disc. Insulator) -- -- 5 Lead/Zinc thimble suitable for fixing with 11KV G.I.Pin as per IS-2486 (Part-I)/1993 & IS-2486 (Part-II)/1989 with latest amendment (small steel head) 6 Melleable cast iron as per IS-2108/1977 & hot dip galvanized socket as per IS-2633/1986. -- -- 7 High tensile forged steel hardened and tampered duly hot dip galvanized BALL Pin. -- 8 Phospher bronze 'W' clips -- 9 Ball & Socket size 16mm -- 10 Impulse withstands test voltage. a) 1.2/50 micro sec. +ve wave - 110 KV b) 1.2/50 Micro sec. ve Wave - 110 KV. 11. Impulse flashover test voltage. a) 1.2/50 micro sec. +ve wave - 120 KV b) 1.2/50 Micro sec. -ve Wave - 130 KV. 12. Power frequency withstand test voltage a) Dry - 70 KV b) Wet - 45 KV 13. Power frequency flashover test voltage. a) Dry - 80 KV b) Wet -50 KV 8

14 Power frequency puncture voltage - 110 KV. 15 Visible discharge -9KV voltage. 16 Marking on Insulator as per Clause No. 12.1 and 12.2 of MGVCL Specification. 17 Insulator shall be packed in wooden crates as per Cl.No.13(i),13(ii) & 13 (iii) of MGVCL Specification. PART-'B': (Both for 11KV Pin Insulator & 11KV Disc. Insulator) BIDDER HAS TO FURNISH BELOW DETAILS ABOUT MATERIAL. 1. No. Of Insulator to be Packed in one crate. a) For 11KV Pin Insulator: b) For 11KV Disc Insulator: 2. Drawing Number/Product Number. a) For 11KV Pin Insulator: b) For 11KV Disc Insulator. PART-'C': ENCLOSURES: (Both for 11KV Pin Insulator and 11KV Disc. Insulator) Bidder has to enclose following documents and has to confirm for the same. Sr. No. Particulars Confirmatio n 1. Drawing with detailed dimension duly signed & stamped 2 Type test certificate covering all the tests as per Cl. No. 9.1 along with attested drawing from Govt. approved laboratory. 3 List of Plant & Machinery at firms works. 4 List of Testing equipments at firms works. 5 List of orders pending/executed at least for past two years for the items offered a) With GUVNL/MGVCL/DISCOM. b) With the purchases other than GUVNL/MGVCL/DISCOM 9

PART-'D' :- Bidder has to mention below deviation if any, Quoting relevant clause of specification. Signature & Seal of Tenderer. Manufacturer's Name and Address. TECHNICAL INFORMATION AND GUARANTEED TECHNICAL PARTICULARS (GTP) FOR SUPPLY OF 22KV PIN INSULATOR Sr. Particulars Confirmation No. 1 Insulator shall be manufactured as per IS- 731/1971 and subsequent amendment 1 to 5 or latest amendment of it. 2 Brown color glazed 3 560mm (Min) creepage distance. 4 Mechanical failing load 10 KN(Min) 5 Lead/Zinc large thimble suitable for fixing with 22KV G.I.Pin as per IS-2486 (P 1&2) with latest amendment (large steel head) 6 Visible discharge 18KV 7 Impulses withstand test voltage. a) 1.2/50 micro sec. +ve wave - 150 KV b) 1.2/50 Micro sec. ve Wave - 200 KV. 8 Impulse flashover test voltage a) 1.2/50 micro sec. +ve wave - 160 KV b) 1.2/50 Micro sec. ve Wave - 220 KV. 9 Power frequency withstands test. a) Dry - 95 KV b) Wet - 60 KV 10 Power frequency flashover test voltage. a) Dry - 110 KV b) Wet - 70 KV 11 Puncture withstand voltage 145 KV 12 Marking on Insulator as per Cl.No. 12.1 & 12.2 13. Insulator shall be packed in wooden crates as per Cl.No. 13 (i) (ii) & (iii) 10

PART-'B' :- BIDDER HAS TO FURNISH BELOW DETAILS ABOUT MATERIALS. 1. No.of Insulator to be packed in : One crate. 2. Drawing Number/Product Number: PART-'C':- ENCLOSURES: Bidder has to enclose following documents and has to confirm for the same. Sr. Particulars Confirmation No 1. Drawing with detailed dimension duly signed & stamped 2 Type test certificate covering all the tests as per Cl. No. 9.1 along with attested drawing from Govt. approved laboratory. 3 List of Plant & Machinery at firms works. 4 List of Testing equipments at firms works. 5 List of orders pending/executed at least for past two years for the items offered a) With GUVNL/MGVCL/DISCOM. b) With the purchases other than GUVNL/MGVCL/DISCOM PART-'D' :- Bidder has to mention below deviation if any, Quoting relevant clause of specification. Signature & seal of Tenderer. 11