EADQUARTERS. Thesis Revised Proposal. Stephanie Kunkel Mechanical Option

Similar documents
EADQUARTERS. Final Thesis Report. Stephanie Kunkel Mechanical Option

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Chilled Beams. The new system of choice?

Walter Reed National Military Medical Center Bethesda, MD

Thesis Proposal. Park. Findlay 12/10/2010. Connor Blood

David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option. Proposal

Element Z General Design Requirements Existing Facilities Information

McCarran International Airport Terminal 3

Energy modeling in IDA ICE according to ASHRAE , app. G

NASA Langley Research Center Administration Office Building One Hampton, VA. Project Proposal. Introduction to Proposed Design Alternatives Revision 1

Underf loor For Schools

Chilled Water Plant Redesign

THERMA-FUSER VARIABLE AIR VOLUME DIFFUSER SYSTEMS

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal

UC Berkeley Indoor Environmental Quality (IEQ)

COMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program

Energy Reduction Strategy Through 2020

Sustainable Building Operations & Upgrades

Evaluation of Energy Savings of the New Chinese Commercial Building Energy Standard

Planning for Biomed Facility Puts Energy Efficiency Under Microscope

Italcementi Center for Research and Innovation

Building Controls Strategies Conference. Retro-Commissioning with BAS Overview. 10 March Steve Brown, CAP ESD Controls Team Leader


THE KEMPER BUILDING 1 EAST WACKER DRIVE PHIL KEUHN SIEBEN ENERGY ASSOCIATES

Case Study for Fortune 500 Telecom: Retrofitting Pneumatic Controls for Energy Efficiency

Compliance Evaluation: ASHRAE Standard Ventilation for Acceptable Indoor Air Quality

Mission Critical Commissioning for Healthcare Facilities

Final Thesis Report Mechanical System Alternatives Analysis

Gaige. Thesis Project Proposal. The. December 13 th, 2013 Matthew Neal, Mechanical Option Stephan Treado, Advisor. Proposed System Changes

Technical Facility Management FACILITY CONSULTING SERVICES. The Facility Audit Program

Application of Advanced Energy Technologies

ASHRAE Standard 62.1 Ventilation Report

Recommissioning Energy Savings Persistence

Texas Hospital. Central Plant Redesign. Central Utility Plant SECOND PLACE HEALTH CARE FACILITIES, EXISTING 2013 ASHRAE TECHNOLOGY AWARD CASE STUDIES

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan

Principles of Ventilation and Air Conditioning Design & Installation

Building Automation Systems

Mechanical (HVAC)* * MasterFormat Specifications Division 23

Integration of Mechanical System Redesign. Geothermal Heat Pumps with DOAS

5/7/2012. Agenda. What is High Performance? Ensuring a Successful Transition to Sustainable, High-Performance Operations

Therma-Fuser Systems. Energy Modeling Guide for Therma-Fuser systems. Acutherm was spec d here

Walter Reed National Military Medical Center Bethesda, MD

FACILITY DESIGN PLAN FOR HARDING HALL RENOVATION AND ADDITION SOUTH DAKOTA STATE UNIVERSITY DATE: March 29, 2017

DesignTools Software Energy Analyzer User Manual

RETRO-COMMISSIONING: AN OWNER S LOOK AT THE TRUE COSTS AND RETURN ON INVESTMENT. Adam Renzi, PE

Condenser Water Heat Recovery"

Energy Trigger (A Existing Building Upgrade Mechanism Model)

ABSTRACT I. INTRODUCTION II. METHODS AND MATERIAL

Persistence Tracking in a Retro-commissioning Program

White Paper ENVELOPE-FIRST APPROACH TO NET-ZERO ENERGY BUILDINGS

PEARL RIVER TOWER GUANGZHOU, CHINA LUKE LEUNG

Modeling for LEED. Refer to Additional LEED credits on page 6 90 for a list of credits TRACE 700 may help to achieve.

Milwaukee, WI. Darron Rempel

Valent Packaged Rooftop Units A Fresh Choice for High-Percentage Outdoor Air Designs. Valent is a business of Unison Comfort Technologies.

A/E Design Deliverable Checklist

Presentation Outline. Project Information & Background. Project Information & Background. Project Team. Boston, Massachusetts

ENGINEERING UPDATE WHITE PAPER: BUILDING PERFORMANCE METRICS. price-hvac.com. May 2013 Vol. 10

Robert E. McMains Date Robert E. McMains Date

ADMINISTRATION CHAPTER 1

AHU Models Using Whole Building Cooling and Heating Energy Consumption Data

Target 100: Re-Envisioning Today s Hospital Prototype for Greatly Improved Energy Efficiency, Human Well-Being and Performance

B. System Design and Performance Requirements

KETTERING ICE ARENA STRUCTURAL & MEP STUDY

Achieving acoustical standards in the classroom Study of HVAC systems and classroom acoustics

Re: College of Lake County: AB Wing HVAC Remodeling Programming Mtg #3 Architect s Project Number: Meeting Minutes

Energy Efficiency in Multi-Tenant Office Buildings

Element D Services Heating, Ventilating, and Air Conditioning

Rhode Island Commercial Codes FAQs

Air Source Heat Pumps in the Commercial Market. Thursday, February 5, :00-10:30 a.m.

A/E Design Deliverable Checklist

Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619

Brown University Updated March 11, 2013 Facilities Design & Construction Standards

Commissioning for Energy Savings

THE NEW WAY TO PROVIDE COMFORT IN 4 PIPES SYSTEMS APPLICATIONS

IECC Commercial Significant Changes Summary Tier I

DISPLACEMENT VENTILATION

Beam? previous. 50% over our. to our. the competition. reducing. first cost of the. project. shown at same. water flow

Ceiling Radiant Cooling Panels

ENERY COST AND CONSUMPTION IN A LARGE ACUTE HOSPITAL

LEED Commissioning and Actual Energy Use. John Kokko, P.Eng. LEED A.P. Vice President Enermodal Engineering

Mechanical Product Overview

780 CMR: 9 th Edition Massachusetts State Building Code. Presented to: BSA Codes Committee. DATE: January 20, 2016

ACBC Floor Mounted Active Beam

NEWMOA June 30, Fran Boucher LEED AP, Certified Energy Manager Senior Energy Engineer

Can we feel safe in this building?

The Mirenda Center for Sports, Spirituality, and Character Development

The optimization of the mechanical night cooling system in the office building

Penn National Gaming Selects Daikin McQuay RoofPak and Magnitude HVAC Systems for LEED Certification

Industrial Retrofit Guide. Superior Solutions for Industrial Heating and Ventilating

Voyager kw rooftop units Plug and Play comfort in commercial applications

Ehsan Soltani. Date of Birth: 1 Sep, 1980 Nationality: Iranian Marital Status: Married Mobile :(+98)

REQUEST FOR PROPOSAL. Commissioning Services College of Pharmacy Building Construct New Facility University of Iowa #

LEED And Your Indoor Environment

Full-Scope Commissioning for High-Quality Buildings

Empire State Building Performance Year 4 M&V Report April 2, 2015

COOLIDGE SENIOR HIGH SCHOOL

Consolidating Systems for a Greener Future:

B. ASHRAE 1991 HVAC Applications Handbook: Chapter 34--Testing, Adjusting and Balancing.

The Art of Thermal Mass Modeling for Energy Conservation in Buildings, Part 2

Secondary loop chilled water in super high-rise

Transcription:

EADQUARTERS 707 N. Calvert St. Mechanical System Renovation Construction Management & Lighting/Electrical Breadths Stephanie Kunkel www.engr.psu.edu/ae/thesis/portfolios/2011/slk5061 Mechanical Option Dr. Bahnfleth January 14, 2011

K U N K E L 2 Table of Contents EXECUTIVE SUMMARY... 3 MECHANICAL SYSTEM SUMMARY... 3 OVERALL SYSTEM EVALUATION... 4 MECHANICAL SYSTEM DESIGN... 4 Current Design Objectives, Requirements & Influences... 4 PROPOSED SYSTEM ALTERNATIVES... 5 Active Chilled Beams (ACB s)... 5 Two-Pipe to Four-Pipe Replacement... 6 Additional Mechanical Systems Replacement... 7 Mechanical System Space Requirements... 7 BREADTH TOPICS... 7 Construction Management... 7 Lighting/Electrical... 8 TOOLS FOR ANALYSIS... 8 Building Loads... 8 Construction Management... 8 Lighting/Electrical... 8 REFERENCES... 9 APPENDIX A PRELIMINARY SPRING SCHEDULE... 10

K U N K E L 3 EXECUTIVE SUMMARY The Maryland State Highway Administration (SHA) Headquarters is located in downtown Baltimore and occupies two office buildings, 707 and 211, which were both originally built in 1959. This report s focus is on the 707 N. Calvert Street building, a 6 story office building with two levels of parking in the Basement and Subbasement; the Basement level also includes a print shop as well as some office space. With each floor approximately 29,000 square feet, the total renovation cost is $4,435,500. Over the past semester, this thesis has been dedicated to the research and analysis of The Maryland State Highway Administration (SHA) Headquarters 707 Building s existing mechanical system. In Technical Report I, the building was analyzed and found that it exceeded the minimum ventilation requirements set forth in ASHRAE Standards 62.1 and 90.1. Trane TRACE 700 was used in Technical Report II to provide a building load and energy analysis of the current system; thus allowing heating and cooling loads to be calculated and annual energy consumption and operating cost to be estimated. The existing conditions of the complete HVAC systems that were installed in the 707 Building and a LEED analysis were performed in Technical Report III. The objective of this Thesis Proposal is to explore design alternatives, ultimately applying changes that would, in some way, enhance the present system. A critique of the renovated system can be found later in this report. Active chilled beams were determined to be the best replacement of the current 534 perimeter induction units since they themselves are modern induction units. Interchanging the active chilled beams in the office space will lead to an increase in building usable square footage. Two breadth topics were also evaluated based off of the implementation of this redesign. A lighting/electrical breadth will examine the benefits of multiservice integration within the chilled beams in the office space. The other breadth, construction management, will evaluate the potential cost and schedule savings of integrating the lighting and/or sprinkler systems into the one single active chilled beam. MECHANICAL SYSTEM SUMMARY The 707 building s mechanical system is comprised of two low pressure central station air handling units (AHUs) serving the central core of the building and one high pressure central station AHU serving the central core of the building. Cooling is provided by a chilled water plant, utilizing a centrifugal chiller and an updraft cooling tower, while heating is provided by two low pressure steam boilers and a steamto-hot water heat exchanger. Overall, the components of the system include 3 constant volume built-up AHUs, 534 perimeter induction units with no operating fans on the 6 office levels, 18 VAV boxes that serve individual areas, a chilled water/hot water indoor unit, and a chilled water/steam indoor unit. An expansive description about the mechanical system design can be found in the following section.

K U N K E L 4 OVERALL SYSTEM EVALUATION In Technical Report III, a complete system evaluation was performed. Evaluations of the existing and renovated design systems in the areas of construction cost, maintainability, operating cost, and mechanical space requirements, were made. With each floor approximately 29,000 square feet and the total usable square footage occupied by mechanical systems comes to be about 1,500 square feet, the total renovation cost is $4,435,500. The 707 building meets, and in some cases, exceeds the minimum ventilation requirements based upon Section 6. When determining the population density, the conference rooms were left empty so that the block load would be more accurate. The 707 building was mostly compatible with Standard 90.1 2007. The non-compliant fields only make up a fraction of the total building system. ASHRAE Standards 62.1 and 90.1 are necessary items to improve upon when striving towards an energy efficient, healthy building. Overall, 707 should be evaluated as adequate, but definitely needs enhancement, in both Standards. Consistent with these Standards, through more renovations and efficient equipment choices, the 707 building could advance its current condition to one that features commendable indoor air quality and energy efficiency. According to the energy analysis results from Technical Report II, the 707 building consumes 1,743,765 kwh of energy annually. Knowing the monthly energy usages, an annual building operating cost analysis was performed in Technical Report II. Utility rates for both electricity and natural gas, from the Baltimore Gas and Electric Company (BGE) website were manually inserted into TRACE in the form of utility schedules, so that the energy consumption could be calculated in a yearlong energy simulation. The total annual utility cost that was totaled for the consumed electricity and natural gas is $200,808 or 1.17 $/sf. Areas of improvement may produce hefty savings in energy and renovation costs. From increasing building usable square footage, to quickening the construction schedule, there are many opportunities for improvement of this 51 year-old building. These, and more, design modifications will be studied during this, and following, reports. MECHANICAL SYSTEM DESIGN This section describes the current renovation plans including what is presently unsuitable within the 707 Building s mechanical system. Current Design Objectives, Requirements & Influences The intent of renovating the 707 Building is to improve system reliability, energy efficiency and occupant safety and comfort. The options for renovation were compared using the following criteria: disturbance to Operations (during construction), maintenance requirements of the proposed system, simplicity of the system control strategy, robustness (system resistance to failure may be in conflict with maintainability). The winning bid for the following renovation plans totaled at $4,435,500, or about $18.90/sf.

K U N K E L 5 Many options were considered for the HVAC renovation of the 707 Building. The current plan is to have nine total phases that will be performed so that work can be completed while maintaining building operations. Due to limited relocation space, a maximum of 20 people can be removed from their areas at a time during the renovation. The contractor will be responsible for submitting a phasing plan and coordinated schedule which will achieve this goal. To prevent system failure and improve the current levels of building comfort, system reliability and operating efficiency, much of the outdated and dilapidated mechanical system will be replaced. This option is intended to improve comfort to occupants and system efficiency, and lessen maintenance costs as the equipment will be new. Since much of the equipment at the 707 Building has exceeded its expected service life, it will be replaced to maintain reliable building operation. The following equipment should be replaced with similar equipment: AHU s, the original boiler and pumps. The new AHU s will be equipped with supply fan and return fan VFD s; adding return fans and VFD s will allow proper control of building pressurization and ventilation. The induction unit secondary water system will be modified to only provide reheat water. Also, the existing building automation system will be replaced. Once there are supply fan VFD s and a new controls system, zone dampers can be added for each half of a floor. The current option for the perimeter spaces replacement is for the 534 induction units to be replaced, in kind. This requires installation of new floor mounted induction units, cleaning the vertical ducts, adding new branch ducts from the existing verticals, and all new dual temp piping, control valves, and thermostats and tie into BAS. Advantages of this option include limited building operation disturbance, little architectural work needed, and increased system efficiency. The main disadvantage is that this option does not provide any increase in usable floor area. Other impacts of these interior improvements are the cause of the occupant relocation (2 weeks per floor), and system outages of approximately 1 week during equipment replacement. PROPOSED SYSTEM ALTERNATIVES After analyzing the problems that have emerged in the existing system, research was performed to examine potential alternatives. The alternatives that are described in the following section may aid in decreasing maintainability issues, while increasing the thermal comfort of the occupants and overall indoor air quality. Active Chilled Beams (ACB s) Due to the various design options, the current 534 perimeter induction units can be replaced by active chilled beams (ACB s) because they use forced air induction to both heat and cool a room. Since the induction principle causes a secondary air flow through the heat exchanger, induction units don t require an additional fan. As seen in Figure 1, the operation of ACB s occurs when primary/ventilation air supply is introduced into the beam through a series of nozzles. This process induces room air to rise to the ceiling and into the ACB, which in turn pulls the air through a secondary water coil. Induced room air is cooled

K U N K E L 6 and/or heated by the water coil to the extent needed to control the room temperature. Induced room air is then mixed with the primary/ventilation air and discharged into the space through a diffuser. This ACB induction is less noisy than traditional induction units and also requires less maintenance. Figure 1: Active Chilled Beams in Cooling and Heating Modes (Courtesy of SmithGroup) ACB s are the 3 rd generation of chilled beam technology and can take care of both the sensible and latent heat gains of a room in a single package and can be operated singly or grouped for zone control. While the room still requires air ducts and the ventilation must be hooked up to the beam, all HVAC requirements can be handled in a single unit. Two-Pipe to Four-Pipe Replacement There are two types of water distribution systems which serve the climate control equipment in a building the two-pipe and four-pipe. The current system in 707 is a two-pipe system which includes only one supply line and one return line to the unit so that only heating or only cooling is performed at any given time. This system is much less flexible than a four-pipe system. A four-pipe system includes a distribution system that contains both hot and chilled water supplies with respective return lines. This system is able to supply cooling to one room or zone while heating

K U N K E L 7 another. Therefore, the four-pipe system could be well utilized in 707 especially with perimeter zones being warmer than the core zone due to fenestration. Additional Mechanical Systems Replacement With the replacements of the perimeter wall induction units, a resize of the chiller and boiler is inevitable. As previously mentioned, the AHU s have surpassed their expected life and will also need to be replaced. Mechanical System Space Requirements The total space that was allocated for mechanical system components is outlined in Table 1, below. The 707 Building s mechanical system renovation requires the replacement of 534 induction units, in kind. This involves the installation of new floor mounted induction units; the main disadvantage of this act is that it does not provide any increase in usable floor area. The area occupied by the VAV boxes and ceiling ductwork was not taken into account during this takeoff. Since most of the mechanical equipment is located in the Penthouse, usable floor area taken up by these systems is minimal for such a large building. Summing the information from the table below, the total square footage occupied by mechanical systems comes to be roughly 1,500 ft 2. With a redesign using ceiling mounted ACB s, the usable square footage will certainly increase. Table 1: Mechanical Space Requirements Area (ft 2 ) Induction Units 1,112.5 Basement AHU s 130 Vertical Shafts 256 BREADTH TOPICS When implemented, any mechanical system redesign will consequently alter other building systems. After feedback from design engineers, the following construction management and lighting/electrical breadths will be analyzed during the Spring 2011 Semester. Construction Management This construction management breadth will investigate the potential savings in construction costs and installation schedule. With the design engineer s current prediction of a lengthy 9 phases being implemented in the 707 Building systems renovation, a more rapid installation schedule will be examined. Items on the schedule s critical path will also be examined. Specific research will be gathered for the cost (including those related to changes in schedule), schedule, and commissioning for any change to the mechanical system. Designing a system with chilled beams leads to the ability to combine several services in a single integrated unit. Aside from known HVAC services, a full range of building services such as fully addressable lighting solutions, fire alarms, and sprinkler heads can be incorporated into the beam. A decrease in costs and on-site installation time is nearly guaranteed by incorporating fire protection and/or lighting features into the beam.

K U N K E L 8 Lighting/Electrical A lighting/electrical breadth will examine the benefits of multiservice integration within the chilled beams in the office space. A reduction in the cooling load is also plausible with this renovation. With the resizing of the chiller and boiler, an alteration in electric load will most likely occur. Design loads for the building s current electrical distribution system will be compared to the redesigned system. An electrical study will be performed comparing the current electric load output to the renovated one by a redesign representation of the circuit/breaker or panel board. TOOLS FOR ANALYSIS The following is a description of tools and methods that will be used to substantiate and ensure the work that will be put forth throughout the redesign of the 707 Building. Building Loads Trane TRACE 700 will be used to model the new systems and calculate new building loads. The loads, along with the output energy usage and utility cost will then be able to be compared to the original design. If needed, this information will help to resize equipment such as the boilers and chillers. Early research is required in order to accurately model the active chilled beams since they are still an emerging technology. To determine the legitimacy of the results, they will be compared to building energy data found in the Commercial Building Energy Consumption Survey (CBECS). Construction Management Any cost information needed that cannot be obtained from the project manager, design engineer, or approved submittals will be referenced from RS Means. Once the scheduling data is supplied by JMT, Microsoft Project will most likely be used to rework the renovation schedule. Lighting/Electrical An electrical analysis will be run using TRACE to determine the overall effect in reducing the cooling load by implementing active chilled beams. Data sheets in Microsoft Excel will also be utilized to compare and contrast the differences between the systems.

K U N K E L 9 REFERENCES Designing Chilled Beams for Thermal Comfort. ASHRAE Journal, October 2009. The article that appeared in the 2009 October issue of the ASHRAE Journal describes how ACB s are both an in-room space conditioning device and the room air diffusion device. ASHRAE Standard 55-2004 for thermal comfort is used to help sizing and locating the beams for acceptable levels of occupant thermal comfort. Design Considerations for Active Chilled Beams. ASHRAE Journal, September 2008. The article that appeared in the 2008 September issue of the ASHRAE Journal describes how ACB s are gaining popularity in managing large sensible cooling loads while using as little as only the required ventilation air. It also describes the various ceiling installation applications that can be utilized. Active Chilled Beams Frequently Asked Questions. DADANCO LLC, July 2009. This document includes information on comparing ACB s to other alternatives, air and water-side application considerations, heating, installation, controls, commissioning and maintenance. Induction Units Frequently Asked Questions. DADANCO LLC, December 2007. This document includes information on improving existing induction systems, air and water-side application considerations, controls, commissioning and maintenance.

K U N K E L 10 APPENDIX A PRELIMINARY SPRING SCHEDULE