Verification of Chiller Performance Promotion and Energy Saving

Similar documents
A Comparison of Methods to Verify Energy-Saving Benefits for Chillers

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

Energy Saving Report. Frigi-Tech Oil Additive. Application. In HKU Central Plant. Chiller No. 3

VERIFICATION OF OPTIMUM OPERATION METHOD BY SIMULATION FOR THE HVAC SYSTEM WITH A THERMAL STORAGE TANK IN AN ACTUAL BUILDING

COPs, EERs, and SEERs

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

Sustainable Design for Hospitals in Taiwan

Year-round Energy Saving Potential for a Stratum Ventilated Subtropical Office. C.K. Lee Zhang Lin K.F. Fong

Central Chiller Plants

RETRO-COMMISSIONING OF A HEAT SOURCE SYSTEM IN A DISTRICT HEATING AND COOLING SYSTEM Eikichi Ono 1*, Harunori Yoshida 2, Fulin Wang 3 KEYWORDS

HEATING SYSTEM RETURN TEMPERATURE EFFECT ON HEAT PUMP PERFORMANCE

Normalized Effect Of Condenser Fouling And Refrigerant Charge On Performance Of Vapor Compression Air Conditioning Systems

Heat Pump Technology Applies on Air-conditioners Impact on Electric Power

Government Office Buildings Energy Consumption Index Research - by Means of Comparing Simulation and Real Energy Consumption WANG Yichao 1, YAN Da, 1

ENERGY EVALUATION BY SIMULATION FOR EFFECTIVE USE OF SEWAGE HEAT

Using Annual Building Energy Analysis for the Sizing of Cooling Tower for Optimal Chiller-Cooling Tower Energy Performance

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

INCENTIVE ESTIMATOR HVAC USER GUIDE CONTENTS FLORIDA CUSTOM INCENTIVE PROGRAM

An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors

D DAVID PUBLISHING. Optimizing Thermal Energy Storage Systems in the Hospitality Industry. 1. Introduction

Deployment of a New Series of Eco Turbo ETI Chillers

DISTRICT HEATING AND COOLING WITH LARGE CENTRIFUGAL CHILLER-HEAT PUMPS

ENERY COST AND CONSUMPTION IN A LARGE ACUTE HOSPITAL

New Suggestions for Centrifugal Chiller Technologies to Realize High Efficiency and High Functionality

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

FRIGI-TECH OIL SUPPLEMENT TEST GAMMA BIOLOGICALS, INC MANGUM ROAD HOUSTON, TEXAS. performed by:

Chilled Water Loop Optimization. Kazimir Gasljevic Richard Dewey Sandro Sanchez

Performance Characteristics and Mapping for a Variable-Speed Ductless Heat Pump

Energy Efficient Solar Milk Chiller

Large University Central Chiller Plant Design Considerations

Chapter 9: Applications of the Laws of Thermodynamics

Simulation and Design of Fuzzy Temperature Control for Heating and Cooling Water System

*Corresponding authors. Tel.: x415, address: (N. Zhu)

Trane Engineering News Multi-pipe unit for heating and cooling buildings

Performance of Variable Speed Centrifugal Chillers

Heat Pump Hot Water Supply Systems

The impact of the work under partial load on the energy efficiency of an air-to-water heat pump

Japanese Energy Efficient Technologies

A NEW METHOD FOR THE OPTIMAL CHILLER SEQUENCING CONTROL

Performance Mapping for Variable Ductless Heat Pump Systems in Heating, Cooling and Defrost Operation

Research on Green Energy Technology for the Innovation Park of Wuhan National Bioindustry Base

ME HVAC Systems, Topic 14, Cooling Equipment

Using Water-Cooled Chillers to Exceed ASHRAE Minimum Efficiency Standard by > 50%

State of the Art of Air-source Heat Pump for Cold Regions

Intelligent System Design

Thesis Proposal. Kristen Shehab. Mechanical Option Thesis Proposal. Instructor: Dr. Srebric Building Sponsor: CCG Facilities Integration

EnergyPro Building Energy Analysis. Nine-story Office Building

Energy Efficiency in Building Active Design Part II

Intelligent. Powerful. Proven. usa.siemens.com/demandflow

york yvwa variable-speed, water-cooled, screw chillers Infinite chiller configurations to help you achieve your goals

- Operating hours. - Average kw/ton.

OPTIMAL OPERATING METHOD FOR A HEAT SOURCE SYSTEM CONSIST OF CENTRIFUGAL CHILLERS

Project Measurement and Verification Procedures

Gregory W. Stevens and Ronald K. Ishii, Alternative Energy Systems Consulting, Inc.

Performance Analysis of a Solar Powered Adsorption Cooling System

7 Measurement and Verification for Generic Variable Loads

Simulation Studies on Performance of Solar Cooling System in UAE Conditions

Optimizing Central Chilled Water Systems

District Cooling Sustainable Design. Presented by George Berbari CEO of DC PRO Engineering

Application Center Equipment Guide. Product Type Category Name Product. Heating & Cooling Equipment Unitary Packaged Heating & Cooling Air Conditioner

In typical commercial buildings, water-cooled chilled water plants use a signifi cant amount of energy.

CONDENSING TEMPERATURE CONTROL THROUGH ENERGY MANAGEMENT SYSTEM SIMULATON FOR A LARGE OFFICE BUILDING

CCHP System with Interconnecting Cooling and Heating Network

NATIONAL CERTIFICATION EXAMINATION 2004 FOR ENERGY MANAGERS

Mechanical Systems Redesign Proposal. Thesis Proposal. Morton Hospital Expansion

JCM Proposed Methodology Form

Variable Frequency Drive Retrofit Opportunities. Michael Kuk CERx Solutions LLC

Study on Energy Saving Control of Electrical System in Office Building

Thesis Proposal. Clemson University Advanced Material Research Laboratory Anderson, SC. David Anderson Mechanical Option. Photo by Fred Martin

Enhanced Refrigeration Diagnostics for an Improved Air Conditioning Tune-Up Program

Section 2: Estimating Energy Savings and Incentives

Using Simulation Model to Reduce System Design Time and Cost

EFFECTIVENESS OF ENERGY CONSERVATION MEASURES IN RESIDENTIAL SECTOR OF JAPANESE CITIES

SOLAR COOLING WITH SMALL SIZE CHILLER: STATE OF THE ART

Cogeneration. Thermal Chillers. and. .. ASHRAE National Capital Chapter. Arlington, VA 10/10/2012

Appendix D Example M&V Plans

KAROLINA KOWAL. Warsaw University of Technology Student. Warsaw University of Technology Student

VRF V4+K Series 50Hz. Commercial Air Conditioners Commercial Air Conditioner Division Midea Group

THERMAL CHARACTERISTICS AND ENERGY CONSERVATION MEASURES IN AN INDOOR SPEED-SKATING ARENA

SorTech package solution description

Energy from the Earth. Geothermal Two very different methods Tides, waves, currents. Unit 12 Energy from the earth - Slide 1

Study on Water-Cooled Solar Semiconductor Air Conditioner

kw. Tetris W. High efficiency water cooled chillers and heat pumps. Bullet points. General. Configurations

ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD (I-P edition) Energy Standard for Buildings Except Low-Rise Residential Buildings.

This paper will discuss applications of an ice slurry generator that has been in production since The

COOLING EFFECTIVENESS OF MIST PRECOOLER FOR IMPROVING ENERGY PERFORMANCE OF AIR-COOLED CHILLER

Measurement and verification of load shifting interventions for a fridge plant system in South Africa

DEVELOPMENT OF NEW SELF-COMPARISON TEST SUITES FOR ENERGYPLUS

Conversion Factors for Comparing the Performance of Variable Refrigerant Flow Systems

ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD (I-P edition) Energy Standard for Buildings Except Low-Rise Residential Buildings.

PAPER-1: GENERAL ASPECTS OF ENERGY MANAGEMENT AND ENERGY AUDIT

1 Project Information. 2 Building Type. 3 Trade Ally/Contractor Information. HVAC Rebate Worksheet. Retrofit New Construction

NATURAL REFRIGERANTS

Condenser Water Heat Recovery"

Central Heating Ventilation Air Conditioning (HVAC) System Optimization For Reduction Of Energy Consumption

AAON. Energy and Economics

EnergyPro Building Energy Analysis. Single-story School Building

A HYBRID MONITORING-MODELING PROCEDURE FOR ANALYZING THE PERFORMANCE OF LARGE CENTRAL CHILLING PLANTS

PERFORMANCE CORRELATIONS FOR COUNTERFLOW COOLING TOWER

Transcription:

Engineering, 2013, 5, 141-145 http://dx.doi.org/10.4236/eng.2013.51a020 Published Online January 2013 (http://www.scirp.org/journal/eng) Verification of Chiller Performance Promotion and Energy Saving Yung-Chung Chang, Chao-Yuan Chen, Jyun-Ting Lu, Jin-Kwei Lee, Tian-Shuen Jan, Ching-Liang Chen National Taipei University of Technology, Taipei, Taiwan Email: rasheed0701@hotmail.com Received October 11, 2012; revised November 12, 2012; accepted November 23, 2012 ABSTRACT In this paper, the model of chiller power consumption is built by using the regression analysis. While taking the parameters from the operation data of chiller into consideration simultaneously, i.e. Partial Load Ratio (PLR), chilled water supply temperature and cooling water return temperature, the prediction results are quite accurate, and its accuracy reaches over 99% in short-term prediction when compared with the actual power consumption. This method can be used to validate the benefits of the chiller s energy saving method. The validation items include: the effect of water flow change on chiller s performance while multiple chillers operate in parallel; the power consumption analysis of centrifugal chiller operating with or without frequency conversion; as well as the discussion on whether the cleaning of condenser coil can improve the Coefficient of Performance (COP) of chiller or not. The case study results show that, while multiple chillers operate in parallel, the water flow change has limited effect on the performance of chiller. However, about 36% electricity can be saved averagely when the chiller controls the frequency of electric power source at partial load, and the cleaning of condenser coil can increase the COP by 3.08%. Keywords: Chiller; PLR; COP; Regression Analysis 1. Introduction Since the industrial revolution, the mankind has been relying on the energy. In recent years, with the vigorous development at home and abroad, the refining industry successfully expands the overseas oil market, and the import volume of industrial coal, electricity-generating natural gas and crude oil required by petrifaction are increased to a large degree, as a result, our energy supply has been growing obviously. As for the energy source, Taiwan s energy supply still mainly relies on import, which accounts for 98.2%, and the self-supplied energy only occupies 1.8% [1]. Currently, more than 75% power generation in Taiwan is thermal power generation, of which most fuel source is fossil oil. Since the domestic economy grows stably, the energy consumption in Industry and commerce will also grows continuously in the future. According to the experts statistics, with the present mining rate, we can carry on for another 40 years at most with oil and 200 years with coal. In the future, the energy shortage will definitely appear. To solve the energy shortage, we only have two measures, i.e. source development and energy conservation. However, source development is very difficult, so we only have the solution of energy conservation. Located at subtropical regions, Taiwan is hot and wet in summer, which causes a big increase in the demand of air conditioners. Air conditioners include window-type, box type, indoor blower, central air conditioning system, etc. Those air conditioners consumes about 30% of electricity in summer [2], which even reaches about 40% at peak load [2]. In the central air conditioning system, the most important equipment is the chiller, which consumes more than 60% of the total power consumption in the system. Therefore, how to reduce the power consumption cost of air conditioners to improve the energy efficiency of chiller will be an important issue on reducing the power consumption and warming. There are quite a lot of methods for energy conservation of air conditioning system. This study builds the power consumption model with linear regression to forecast the chiller s power consumption, so as to discuss the effect of water flow change on the chiller s performance and analyze the energy consumption of drive chiller in either variable frequency or invariable frequency mode. Finally, it validates the performance improvement before and after cleaning the condenser of chiller and the discussion of energy saving potential.

142 Y.-C. CHANG ET AL. 2. Case Discussion and Analysis 2.1. Effect of Water Flow Change on Chiller s Performance Based on the analysis on power consumption of some buildings, the power consumption of air conditioning systems in general commercial buildings occupies about 50% of the total consumption. The chiller, as the core of the central air conditioning system, consumes about 60% of the total power of the central air condition system. Therefore, if the power usage effectiveness of chiller can be improved, it will do a great help to promoting the central air conditioning system to save the energy and reduce the electricity consumption. Generally, the air conditioning load required by the middle and large office buildings is big, so most of them adopt the design of multiple-chiller system. Moreover, the one-to-one allocation is adopted by the primary side water pump and chiller. In such mode, the water flow is fixed if the primary side water pump isn t collocated with the variable frequency control. This study is exemplified by one public organ, which is equipped with three centrifugal chillers, i.e. one 250-ton and two 400-ton chillers collocated with three 20 Hp water pumps. If the 250-ton chiller operates with one water pump, the water flow is 157 m 3 /h; if it operates with three water pumps, the water flow is 116 m 3 /h. Based on these parameters. This study is to discuss the chiller s performance change with the water flow change. In this paper, the power consumption model of chiller collocated with a water pump is established through the regression analysis, and then the data measured by three water pumps are substituted into the model to analyze its performance change. The operation data measured on field are applied on the statistics software to get a regression analysis equation, by which the power consumption model of chiller is built as bellows [3]: kw a a X a X a Y a Y a XY (1) 2 2 0 1 2 3 4 5 a 0, a 1, a 2, a 3, a 4, a 5 : regression coefficient X: Difference between cooling water return temperature and chilled water supply temperature; Y: Partial Load Ratio (PLR). Table 1 shows the regression coefficient, in which the accuracy of chiller power consumption mode is so high (R 2 = 0.99002) that it can be adopted. Table 2 shows the operation data range, in which the data range of chiller collocated with three water pumps are within that of chiller collocated with one water pump, i.e., the data can be substituted into the model to discuss the performance change. The chiller occupies 60% of the power consumption of central air conditioning system, the water pump 11%, the cooling water pump 13%, the cooling tower 3%, and the Table 1. Regression coefficient of 250-ton chiller operating with one water pump. a 0 62.4307 a 1 0.49409 a 2 0.11425 a 3 1.55136 a 4 61.337 a 5 0.5535 R 2 0.99002 Table 2. Data ranges of chiller collocated with one or three water pumps. One chiller water pump Three chiller water pumps TchwST 7.8 C 7.8 C TcwRT 16.66 C - 31.28 C 20.8 C - 21.75 C PLR 0.285-0.947 0.658-0.734 air handling unit and indoor blower 13% [4], which indicate the chiller occupies the highest power consumption. For this reason, it deserves people s attention to improve the chiller s efficiency. Figure 1 shows the change of chiller s COP when collocated with one or three water pumps and it can be known that the effect of water flow change on the chiller s COP is slight, about 1%. 2.2. Variable-Frequency Chiller In general, there are three types of chillers, namely, centrifugal, screw and reciprocal chillers, in which the centrifugal or screw chillers are adopted by most air conditioning systems with large load. Design of general air conditioners calculates the peak load based on the climatic condition of the highest external air temperature and the indoor load to decide the capacity, so that the chiller mostly operates with partial load. However, the screw chiller can use the slide valve to realize continuous change. Therefore, it still keeps a good efficiency under partial load operation. The traditional centrifugal chiller adjusts the refrigerating ability through the guide vanes. Although the power consumption of compressor might drop when operating under partial load, the operation efficiency will decrease to a large degree, which causes a big waste of energy. The Variable Speed Drives (VSD) of the centrifugal chiller provides the chiller with a good efficiency by adjusting the rotation speed of motor and optimizing the location of guide vanes of compressor under various loads, especially when it operates under partial load. Therefore, this study analyzes the power conservation benefits of the inverter centrifugal chiller [5].

Y.-C. CHANG ET AL. 143 Table 3. Regression coefficient in invariable frequency control mode. a 0 171.85 a 1 18.08 a 2 2.096 a 3 735.04 a 4 90.57 a 5 72.07 R 2 0.9958 Figure 1. Effect of flow change on chiller s performance (one data/10 min). This study adopts the actually measured data of the air conditioning system in one hypermarket, uses the linear regression to build the chiller power consumption model and discusses the power consumption analysis with variable frequency control and invariable frequency control. The data must be analyzed and compared within the same load range, and the measuring duration was from April 28 to May 6, 2008. We took records per minute of the chiller power, chilled water supply temperature, cooling water return temperature and water flow. Since the data was sampled instantly, we sorted the data by 10 minutes on average and then analyzed them by the quadratic regression to avoid error. On April 29 and 30, the chiller was set as invariable frequency control mode, the chilled water supply temperature was 10 C, the cooling water return temperature range was between 22.3 C - 25 C, and partial load ratio varied between 0.473-0.704. In the rest days, the data were measured when the chiller operated in variable frequency mode, the chilled water supply temperature was 10 C, the cooling water return temperature range was between 22.31 C - 24.25 C and partial load ratio varied between 0.476-0.703. This study establishes the power consumption model of chiller in invariable frequency mode with the regression analysis, and then substitutes the data measured in variable frequency mode into the model to analyze its power saving potential. The operation data measured are applied to the statistics software to get a regression analysis equation, by which the power consumption model of chiller is built, and the regression coefficient is shown in Table 3. In Table 4, the invariable frequency data are substituted into the built model, which gets the simulated total invariable frequency power of 12294.97 kw, and the actually measured value is of 12294.95 kw. Thus, the error ratio between the two is 0.00021%, very close to zero. As for the single error, the maximum error is 1.19% and the minimum error is 0.0076%, the average error is Table 4. Error ratio between total actual power and simulated power in invariable frequency control mode. Total actual power in invariable frequency Total simulated in invariable frequency Error (%) The average error (%) 12294.95 12294.97 0.00021% 0.389% 0.389%. Therefore, it can be seen that the model has a quite high accuracy. Figure 2 shows the comparison between actual invariable frequency control power and simulated one, in which the actual invariable frequency control power curve is very close to that of the simulated one. Thus, it can be proven that the model has a high accuracy. The measured data of the chiller collocated with the inverter is classified per 10 minutes, 416 data in total. 193 data under the same load of the model are substituted into the model to validate the power saving effectiveness. Table 5 shows the power saved by the inverter chiller, the actual power of chiller in variable frequency control mode is 17187.4 kw and the simulated invariable frequency control power is 27059.6 kw under the same load. Thus, the variable frequency control can save about 36% of the power consumption. It can be known from Figure 3, under the same conditions, the variable frequency control and invariable frequency control show great difference in the power consumption. In an energy conservation and carbon reduction era, the variable frequency control deserves to be promoted. 2.3. Improvement of Chiller s Performance by Cleaning the Condenser Coil Ordinary air conditioning systems mainly have two big water circuits. The water circuit design is generally based on the flexible usage of actual requirements, which tends to the concept of primary and secondary side. Thus, the main function of water circuit is to bring the indoor heat back to the chilled plant to exchange with the cooling water circuit. While the main function of the cooling water circuit is to take away the indoor heat of water circuit and the heat produced by the compressor. When the

144 Y.-C. CHANG ET AL. Figure 2. Comparison between actual invariable frequency Figure 3. Comparison between actual variable frequency Table 5. Power conservation of actual variable frequency Actual variable frequency control Simulated invariable frequency control Power saving Power saving percent (%) 17187.4 27059.6 9872.2 36.4% heat exchange rate of condenser reduces, it will result in over-high voltage of the compressor, which will increase the power consumption of the compressor so as to reduce the entire COP of the system. Since the cooling water circuit is an open water system, the contact between water and air will cause water pollution in addition to the pollution source in the air. Generally, the cooling water is within the warm temperature range, which easily causes the generation of moss and scale, thus it is suggested cleaning and maintaining the condenser of air conditioning system every three months or half a year in order to keep a high heat exchange rate. This study mainly focuses on the evaluation of system benefit improvement before and after cleaning the chiller s condenser of one hypermarket. Both the discussion of the method and the power consumption prediction are to validate the energy conservation, and it can act as a method to validate the evaluation on the technology of improving the performance of various system functions by the industry in the future [6]. This study adopts the actually measured data of the air conditioning system and uses the linear regression to build the chiller power consumption model so as to discuss the improvement of chiller s performance by cleaning the condenser coil. The data must be analyzed and compared within the same load range, and the measuring duration were from May 28 to June 24, 2008 (The condenser coil was cleaned on June 10). We took records per minute of the chiller power, chilled water supply temperature, cooling water return temperature and water flow, and then got the average data per hour. The data got from May 28 to June 9 were before cleaning, during which the chilled water supply temperature was 10.4 C, the cooling water return temperature range was between 28.973 C - 31.328 C and partial load ration varied between 0.3794-0.5927. The data got from June 11 to June 24 were after cleaning, during which the chilled water supply temperature was 10.4 C, the cooling water return temperature range was between 28.9 C - 32.913 C and partial load ratio varied between 0.3494-0.629. This study establishes the power consumption model of chiller after cleaning the condenser coil, and then substitutes the data measured before cleaning into the model to analyze its performance improvement. The regression coefficient of chiller power consumption model is shown in Table 6. Generally, when the evaluation coefficient R 2 reaches 0.95, it indicates the method has quite high accuracy and reliability. It can be seen from Table 6 that, the regression coefficient has a high accuracy when its R 2 is above 0.95. In Table 7, the data are substituted into the model, which gets the simulated total power of 19066.732 kw, and the actually measured one is of 19045.532 kw. Thus the error ratio between the two is 0.111%. The single error is 0.713%. Therefore, it can be seen that the built model has a high accuracy. Table 6. Regression coefficient after cleaning the condenser coil. a 0 172.165 a 1 13.547 a 2 0.4355 a 3 116.648 a 4 23.474 a 5 0.498 R 2 0.956

Y.-C. CHANG ET AL. 145 Table 7. Error ratio between actual total power and simulated total power after cleaning. After cleaning actual total power After cleaning simulated total power Error ratio (%) Single error (%) 19045.532 19066.732 0.111% 0.713% Table 8. Energy conservation calculation of cleaning the condenser coil (kw h). Power consumption mode before improvement (A) Power consumption mode after improvement (B) Saving ratio Power saving 9385 9093 3.11% 292 kw h (Note: Power consumption before improvement is the cumulated amount of chiller after 72 hours of operation). Figure 4. Comparison of COP before and after cleaning the condenser coil. The measured data before cleaning the condenser coil were recorded per hour, 72 data in total. The data under the same load of the model are substituted into the model to validate the power saving effectiveness. Table 8 shows the energy conservation calculation of cleaning the condenser coil. Before the improvement, the power consumption is 9385 kw h. After the improvement, the power consumption is 9093 kw h. Thus, the saving rate is 3.11% (292 kw h). Figure 4 shows the comparison of COP before and after cleaning the condenser coil. 3. Conclusion In this study, the above three different cases are analyzed by the power conservation validation method, by which the following results are obtained: Partial Load Ratio (PLR), chilled water supply temperature and cooling water return temperature, the prediction results are quite accurate, and its accuracy reaches over 99% in short-term prediction when compared with the actual power consumption. We evaluate the power conservation of chiller with or without variable frequency control under the same load. It is shown from the study results that, the total power consumption of chiller with variable frequency control is 17187.4 kw during the test period, and that of the simulated invariable frequency control chiller is 27059.6 kw, thus the power consumption of the chiller with variable frequency save 36.4% than the chiller without variable frequency. Cleaning the condenser coil improves chiller s performance and power consumption. It is shown from the study results that, the power consumption before the improvement is 9385 kw h and that after improvement is 9093 kw h, thus the saving ratio is 3.11%. REFERENCES [1] Bureau of Energy, Ministry of Economic Affairs. http://www.moeaboe.gov.tw/ [2] C.-Y. Chu, Application of Grey System Theory to Predict Chiller Power Consumption, Master s Thesis, National Taipei University of Technology, Taipei, 2007. [3] ASHRAE Handbook, Supervisory Control Strategies and Optimization, CH.40, Atlanta, 1999. [4] C.-C. Liu, Application of Energy-Saving Technology and Management for Air Conditioning, The Industrial Technology Research Institute (ITRI), 2003. [5] C.-K. Chou and Y.-Y. Lin, A Study of an Automated Fault Detection and Diagnosis (FDD) Strategy for Centrifugal Chillers, Energy Conservation Center, Taiwan Green Productivity Foundation, Taipei, 2006. [6] M. Leung, G. Lai, W. H. Chan, J. Y. Qin and S. Y. Lee, Sponge-Ball Automatic Tube Cleaning Device for Saving Energy in a Chiller, International Energy Journal, Vol. 3, No. 1, 2002, pp. 35-43.