THE EFFECT OF DUCT CLEANING ON INDOOR AIR QUALITY IN OFFICE BUILDINGS

Similar documents
CLEANLINESS REQUIREMENTS FOR VENTILATION DUCTS IN THE NEW FINNISH LABELING SYSTEM: PRACTICAL CONSEQUENCES

INDOOR AIR QUALITY AND THE ADEQUACY OF CLEANING IN 25 FINNISH SCHOOLS

OIL RESIDUES ON HVAC COMPONENTS

MVOC EMISSIONS FROM FUNGI IN HVAC SYSTEM

MAINTENANCE OF HVAC-SYSTEMS AND COMPONENTS, DEFINITION OF CLEANLINESS!

ASSESSMENT OF BIOAEROSOL DISTRIBUTIONS IN MUNICIPAL SOLID WASTE TRANSFER STATION

Classification of Indoor Climate, Construction, and Finishing Materials

Variables affecting indoor air quality in newly finished buildings- a multivariate evaluation

Trends and drivers in the Finnish ventilation and AC market

According to our research and study most occupant complaints relating to IAQ are attributable to the following factors:

MICROBIAL MEASUREMENTS AT VENTILATION SYSTEMS SUPPLY VENTS

INTERPRETING MICROBIAL MEASUREMENT AND ANALYSIS

MICROBIO BIOAEROSOL SAMPLING

UBC Social Ecological Economic Development Studies (SEEDS) Student Report

AIR POLLUTANT EXPOSURE OF ADULT POPULATION IN MILAN (EXPOLIS STUDY)

AIR QUALITY ASSESSMENT FOR TAYLOR STANLEY MARKETING PTE LTD 71, TANNERY LANE #-7-07, CITY INDUSTRIAL BUILDING SINGAPORE

AN INVESTIGATION ON THE OCCURRENCE OF FUNGI AND BACTERIA IN THE MVAC SYSTEM IN AN OFFICE PREMISE

Measuring Indoor Air Quality presented to AAFAME Members Nov. 14, 2017

Comfortable and Healthy Indoor Climate EEN-E4001

INDOOR AIR QUALITY AND MATERIAL EMISSIONS IN NEW BUILDINGS

A FIELD COMPARISON OF METHODS FOR ENUMERATING AIRBORNE FUNGAL BIOAEROSOLS

UNDER SECRETARY FOR HEALTH S INFORMATION LETTER MICROBIOLOGICAL ASSESSMENT OF PHARMACEUTICAL CLEANROOMS

INDOOR AIR QUALITY TESTING AT CARLISLE COUNTY ELEMENTARY SCHOOL

Good (4 points each) > mg/m Bq m Bq m Bq m -3 < ,000 1,000-10,000 10, ,000

HYGIENIC AND MICROBIOLOGICAL (HYGMIC) EVALUATION OF AIR INTAKE AND PLANTS TEN-YEARS-EXPERIENCE

Indoor Air Quality Assessment Report

What s in the Air - Truths, Myths & Simple Strategies

BIOAEROSOL PRODUCTION FROM INDOOR AIR BIOFILTERS

EXPERIENCES FROM THE EMISSION CLASSIFICATION OF BUILDING MATERIALS IN FINLAND

CONCENTRATIONS OF PARTICULATE MATTERS(TSP, PM 10, PM 2.5, AND PM 1 ) AND BIOAEROSOL IN THE ABOVE- AND UNDER-GROUND SUBWAY OFFICES IN SEOUL

Web Seminar. Indoor Air Quality. Indoor Air Quality and Air Cleaning 19 November Peter DYMENT Camfil Ltd

PRINCIPLES AND NEW DEVELOPMENTS OF THE EMISSION CLASSIFICATION OF BUILDING MATERIALS IN FINLAND

Notes on Indoor Air Quality

Indoor Air Quality Solutions

MODELLING THE COST EFFECTS OF THE INDOOR ENVIRONMENT

Department of Environmental and Occupational Health, Faculty of Medicine and Health Sciences, Universiti Putra Malaysia, Selangor, Malaysia.

NCCEH Mould Investigation Toolkit

AIRBORNE PARTICULATE MATTER WITHIN 100 RANDOMLY SELECTED OFFICE BUILDINGS IN THE UNITED STATES (BASE)

HVAC. Hygiene. abstract. Mr Jeremy Stamkos

INDOOR AIR QUALITY IN SCHOOLS: THE IMPACT OF VENTILATION CONDITIONS AND INDOOR ACTIVITIES

BREATHE A LITTLE EASIER WITH TSI

The microbiological environment in specific rooms of a university campus

Indoor Air Quality Improvement in a School Building in Delhi

THE LEADER IN PERFORMANCE INDOOR AIR QUALITY MEASUREMENTS

Fire insulations of ventilation equipment and shafts as a source of man-made mineral fibres

AIR QUALITY IN SWINE-FINISHING BARNS 1

AIVC #12,964 ABSTRACT INTRODUCTION THE PACT OF H.V.A.C. SYSTEM CLEANING ON LEVELS OF SURFACE DUST AND VIABLE FUNGI IN DUCTWORK

INDOOR AIR QUALITY ASSESSMENT. Department of Developmental Services & Department of Mental Health Service Center 35 Nagog Park Acton, Massachusetts

SECTION 14 INDOOR AIR QUALITY (IAQ)

A Study of Indoor Environmental Quality Parameters in a South Central Kentucky Daycare Facility

MULTI-CRITERIA ANALYSIS OF HEALTH, COMFORT AND ENERGY-EFFICIENCY OF BUILDINGS

Indoor Air Quality. Basic Management for Healthy Office Environments. Peter A Shelling CSP CIEC

SICK BUILDING SYNDROME SYMPTOMS AND PERFORMANCE IN A FIELD LABORATORY STUDY AT DIFFERENT LEVELS OF TEMPERATURE AND HUMIDITY

The opinion on risk assessment on indoor air quality by SCHER

MEP's Letter of Assurance

April 21, Dear Mike,

DRAFT. UNR Fungi Assessment & Remediation Program

INDOOR CHEMICAL POLLUTION AND EMISSION RATES INVESTIGATED IN A REAL SIZED MODEL ROOM

The Field Comparison of Three Measuring Techniques for Evaluation of the Surface Dust Level in Ventilation Ducts

MICROBIO BIOAEROSOL SAMPLING

Field Performance of Portable Impactors when Enumerating Viable Bioaerosols

International Perspective on Clean Air and Energy Efficiency in Buildings. Morad R. Atif, PhD. Director, Architectural Engineering

Indoor Air Quality Assessment Morell Consolidated School Morell, PEI

Indoor Air Quality Program

The attached report is the result of a mold and bacterial assessment conducted at th Street, Franklin, Ohio on April 24 and 25, 2008.

AIR AND SURFACE SAMPLING MEASUREMENTS OF FUNGAL CONTAMINANTS IN INDOOR ENVIRONMENTS

Premise Microbial Testing

INDOOR AIR QUALITY ASSESSMENT

Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms

ASHRAE s. Indoor Air Quality Procedure. in Ventilation Design

A measurement on chemicals emitted from computers and printers using test chamber method

INDOOR AIR QUALITY OF AIR-CONDITIONED FOOD COURTS: PRELIMINARY FINDINGS IN A TROPICAL CITY STATE

DETERMINATION OF VOLATILE ORGANIC COMPOUNDS IN THE BUILDING OF PRINTING COMPANY

PRACTICAL EXPERIENCES WITH MVOC AS AN INDICATOR FOR MICROBIAL GROWTH

MEP Engineer's Letter of Assurance

Indoor Air Quality Monitoring. Aerosol Particle Counter used in Mold Investigation at Local School

Your family are threatened by harmful and hidden pollutants. Indoor air pollutant sources. WS907 NCCO Air Sanitizing System

Comparison of indoor air quality on a passenger ship and a chemical ship

Scope of application. Definitions. Translation from Finnish Legally binding only in Finnish and Swedish Ministry of Social Affairs and Health

THE ROLE OF VENTILATION AND HVAC SYSTEMS FOR HUMAN HEALTH IN NONINDUSTRIAL INDOOR ENVIRONMENTS. A SUPPLEMENTARY REVIEW BY EUROVEN GROUP

EN ISO A more precise filter standard helps ensure air quality

MOLD REMEDIATION PROCEDURES AT A NEW JERSEY ELEMENTARY SCHOOL

Environmental Monitoring of Aseptic Processing Areas - 2

The indoor climate and energy consumption of educational buildings

Indoor Air Quality Monthly Testing Services, Corcoran Gallery of Art, th Street NW, Washington, DC December 2017

ISO INTERNATIONAL STANDARD. Indoor air Part 16: Detection and enumeration of moulds Sampling by filtration

Do European standards for indoor air quality take into account outdoor air quality? Professor Bjarne W. Olesen, PhD, Department of Civil Engineering

A SURVEY OF INDOOR AIR QUALITY PROBLEMS IN AIR-CONDITIONED BUILDINGS IN INDIA

Effect of Different Ventilation Conditions on Indoor CO2 Levels

Visible emissions were not observed in the school in the vicinity of the construction containment.

The Leader in Performance Indoor Air Quality Measurements

The Leader in Performance Indoor Air Quality Measurements

VENTILATION RATES AND IAQ IN EUROPEAN STANDARDS AND NATIONAL REGULATIONS

Personal Ventilation: from research to practical use

DETECTION OF LEGIONELLA PNEUMOPHILA IN ENVIRONMENTAL AEROSOLS OF COOLING TOWERS BY IMPACT SAMPLING METHODS

HAZARD EVALUATION AND TECHNICAL ASSISTANCE REPORT HETA SOCIAL SECURITY ADMINISTRATION SAN JUAN, PUERTO RICO AUGUST 1991

Visible emissions were not observed in the school in the vicinity of the construction containment.

Health & Public Safety Management

Transcription:

THE EFFECT OF DUCT CLEANING ON INDOOR AIR QUALITY IN OFFICE BUILDINGS S Kolari 1*, M Luoma 1, M Ikäheimo 2 and P Pasanen 2 1 VTT Technical Research Centre of Finland, Espoo, Finland 2 University of Kuopio, Department of Environmental Sciences, Kuopio, Finland ABSTRACT The effect of duct cleaning on supply air quality, duct cleanliness, air exchange and working environment was studied in 15 non-problem office buildings. Mass and number concentrations of particles, concentrations of microbes, volatile organic compounds and CO 2 were measured in outdoor, supply and indoor air. Samples of accumulated dust were taken from the inner duct surfaces and supply and exhaust air flows were measured. An Indoor Climate Questionnaire was delivered to over 900 employees before and after the duct cleaning. Duct cleaning had no measurable effect on supply air quality. The results showed that the average amount of dust on the inner duct surfaces decreased from 8.4±9.1 to 1.9±2.1 g/m 2. The employees perceived the working environment better after the cleaning than before it. INDEX TERMS Cleaning, Ventilation system, Office building, Supply air, Working environment INTRODUCTION Most office buildings in Finland have balanced supply and exhaust ventilation system and the material used for ventilation ducts is sheet metal. According to national recommendations, inspection and cleaning of the ventilation system in office buildings is recommended every fifth year (FiSIAQ 2001). Although inspection and cleaning originally concerned the exhaust ducts for fire safety reasons, in recent years cleaning of supply air ducts have became more frequent as the awareness of the connection between ventilation system maintenance and indoor air quality (IAQ) has increased. The most common cleaning technique of air ducts in Finland consists of mechanical loosening the dust with rotating brushes and suction of removed particles from the ductwork to a filtration unit with sufficient air velocity. However, the effects of mechanical duct cleaning on ventilation system hygiene and IAQ are not well known. The aim of this study was to investigate the effect of mechanical duct cleaning on ventilation system hygiene and IAQ in office buildings. The results of the seven first measured offices were presented in Indoor Air 99 (Luoma et al. 1999) and Healthy Buildings 2000 (Ikäheimo et al. 2000) conferences. METHODS Case study buildings Field measurements were carried out at 15 non-problem office buildings during years 1997-2000. Eight of these buildings located in the central part of Finland and the rest in the southern part of Finland. All study buildings were provided with a mechanical supply and * Contact author email: sirpa.kolari@vtt.fi 694

exhaust ventilation system and none of these buildings used recirculated air. The efficiency of the supply air filters varied from EU4 to EU8. Ventilation systems of the 15 office buildings were cleaned for the first time and the reason for the duct cleaning was the national recommendation to inspect and clean the ventilation system at regular intervals. The cleaning included both supply and exhaust ventilation systems. The section of ductwork to be cleaned was first under pressured and then cleaned with rotating brushes. The terminal devices were removed and washed. In most of the buildings, new supply air filters were installed and air flows were balanced after the cleaning. Study design and field measurements In each building, two to five rooms were selected to represent IAQ of the whole building. Field measurements were performed few days prior to duct cleaning and at least one month after the cleaning. Air quality parameters were measured in supply, indoor and outdoor air. The average time period between the IAQ measurements before and after the cleaning was 5.4 months. Thus, the measurements were carried out at different seasons. Particle mass concentrations were measured gravimetrically by collecting samples on 37 mm diameter polycarbonate filters (0.8 µm pore size) using open face filter cassettes. Sampling time was 5-6 hours and flow rate was 20±5 L/min. The filters were stabilized 24 hours in a constant humidity room before the weighing (precision 1 µg). Laboratory and field blanks were used for quality control of sampling. Particle number concentrations of supply air were measured with a portable optical particle counter (Climet-500) in size ranges 0.3-0.5, 0.5-1.0, 1.0-5.0, 5.0-10 and 10-25 µm. Ten successive 1 min samples were collected at the supply air terminal devices in each location. Airborne bioaerosol samples were collected with N6- or 6- stage Andersen samplers for 5 to 10 min using 28.3 L/min flow rate. Fungi were collected to malt extract agar (M2) and dichloran glycerol agar (DG18) and tryptone glucose yeast agar (THG) was used for bacteria. Agar plates were incubated for 7 days for fungi and 5 to14 days for bacteria at 25 C and colony forming units (cfu) were determined. Volatile organic compounds were collected on Tenax absorption tubes using 0.1 L/min flow rate and 60-90 min sampling time. Samples were analyzed with thermodesorption gas chromatograph, equipped with mass selective detector. The TVOC concentration was determined as toluene equivalents from range C 6 -C 16. CO 2 concentrations were determined with IR-analyzer (Vaisala, Finland) by using 5 min sampling time. Samples of accumulated dust were taken from the inner duct surfaces using a vacuum pump and pre-weighted filter cassettes (37 mm mixed cellulose ester filter, pore size 0.8µm). Filters were weighted together with cassettes (precision 100 µg). For consistency of the sampling area in ducts with various diameter, dust samples in spiral ducts were collected from an area which was rejected with a specimen between the bottom line and the line on the widest level of duct (Pasanen et al. 1992). Sampling areas used were 100-200 cm 2. The cleanliness of the ducts was inspected also visually before the cleaning and afterwards. In seven buildings, the bioaerosol content of the accumulated dust was detected from the collected dust suspending the weighted dust to dilution water and cultivating on agar plates. In eight buildings, samples for microbial analysis were collected from the inner duct surfaces by sterile swab and cultivated. Agars, incubation time and temperature were similar to air samples of microbes. Supply and exhaust air flow rates were measured with velocity or pressure difference measurements from the terminal devices in each study rooms. Ventilation rates were 695

determined using the measured exhaust air flow rates and volumes of the room. Temperature and relative humidity were measured from outdoor and indoor air. Temperature of outdoor air ranged from 14 C to 30 C before and from 16 C to 26 C after the cleaning. The ranges of relative humidity were 18-85% and 25-90 %, correspondingly. Indoor Climate Questionnaire A self administrated Indoor Climate Questionnaire (MM-Questionnaire) was delivered to 931 employees few days before the duct cleaning and at least one month after the cleaning process. Employees background factors, working conditions and workplace related symptoms were asked in the questionnaire. The recall period for the questionnaire was three months before the cleaning and one month after the cleaning. RESULTS Thermal environment, ventilation and supply air quality Means, standard deviations and numbers of observations of thermal environment, ventilation, supply air quality and duct hygiene parameters are listed in Table 1. No statistical analysis is performed for the results of measurements or questionnaire data. The measured mean indoor air temperatures were, in general, quite high with an average of 22.7 C before cleaning and 22.6 C after cleaning. Indoor air RH was at normal level. The mean air flows per person exceeded 20 L/s per person before and after cleaning. The mean ventilation rate at studied offices was 1.7±0.9 1/h before and 2.3±2.1 1/h after the cleaning. Mean airborne dust concentration in supply air was below 7 µg/m 3 before and after cleaning and it was lower than concentrations in indoor air (12.0±6.2 µg/m 3 before cleaning, 11.8±6.0 µg/m 3 after cleaning) and outdoor air (18.9±14.2 µg/m 3 before cleaning, 29.8±30.4 µg/m 3 after cleaning). Particle mass concentration in supply air was about 34% of that in the outdoor air before cleaning and about 23% after the cleaning. Number concentration of particles <1µm increased with 88% from levels observed before cleaning. Also, the outdoor air concentration of particles <1µm increased with 144% from levels before cleaning. The average TVOC concentration in supply air before duct cleaning was 71±75 µg/m 3, which was lower than concentrations in indoor air (117±105 µg/m 3 ) and outdoor air (100±124 µg/m 3 ). After the cleaning, TVOC concentrations in outdoor air (52±50 µg/m 3 ) and supply air (52±61µg/m 3 ) were similar but indoor air concentration was higher (74±71µg/m 3 ). Average indoor air CO 2 concentrations were higher than corresponding outdoor air concentrations, which were below 350 ppm. Concentrations of viable fungal spores and bacteria in supply air were low in general and average fungal spores and bacteria concentrations measured before and after cleaning were below 60 cfu/m 3. Fungal spores and bacteria concentrations outdoors ranged between 140-320 cfu/m 3. Duct hygiene Surface dust levels of supply air ducts ranged from 0.7 to 47.0 g/m 2 before cleaning and from <0.1 to 8.8 g/m 2 after cleaning. Duct cleaning decreased the average surface dust load from 8.4±9.1 to 1.9±2.1 g/m 2 (Table 1). Thus, the reduction of dust load was 77%. At four buildings, the average dust load was after cleaning higher than presented limit value (2.0 g/m 2 ) for accumulated dust in office building ventilation systems (FiSIAQ 2001). The average microbe concentrations on the inner duct surfaces were lower after the cleaning than before the cleaning. Fungal concentration on M2 agar decreased about 70% and on DG18 agar about 90%. 696

Table 1. Statistics of thermal environment and ventilation parameters, supply air concentrations, and duct hygiene parameters measured before and after duct cleaning in 15 non-problem office buildings. Measured Unit Before duct cleaning After duct cleaning parameter Mean Stdev n Mean Stdev n Air temperature 1 C 22.7 1.7 45 22.6 1.3 44 Relative humidity 1 % 31 15 45 26 14 44 Air flow L/s person 22.9 13.8 40 27.1 13.2 40 Ventilation rate 1/h 1.7 0.9 40 2.3 1.2 41 Airborne dust µg/m 3 6.4 5.7 34 6.8 4.6 30 Dust particles: 1/L 0.3-0.5 µm 69,800 78,900 14 133,000 146,700 14 0.5-1.0 µm 6,000 6,700 14 9,200 10,000 14 1.0-5.0 µm 500 700 14 700 800 14 5.0-10 µm 41 47 14 70 97 14 10-25 µm 12 17 14 12 18 14 Airborne microbes: cfu/m 3 M2 36 61 45 20 23 45 DG18 22 55 44 17 26 43 THG 21 30 44 57 105 44 TVOC µg/m 3 71 75 45 52 61 43 1 CO 2 ppm 504 84 45 475 71 44 Surface dust 2 g/m 2 8.4 9.1 61 1.9 2.1 51 Microbe load on cfu/cm 2 duct surface: M2 7 13 56 2 3 55 DG18 13 58 56 1 2 54 THG 830 3660 52 610 2230 52 1 Measured from indoor air, 2 Measured from inner duct surface Questionnaire The response rate in questionnaire was 63% before and 59% after cleaning. The background factors of the respondents were similar before and after cleaning (Table 2). The number of respondents ever suffered from hayfever or eczema was lower after cleaning. This can be explained by the fact that partly different people answered to the questionnaire before and after cleaning. Prevalence of respondents ever suffered from asthmatic symptoms or eczema was similar compared to other studies (Bluyssen et al. 1996), but the prevalence of hayfever was higher in this study. Complaints concerning draft and too high room temperature were similar before and after cleaning. Instead of this, complaining about stuffy bad air, dry air and dust and dirt reduced after cleaning. The highest improvement in these parameters was detected with stuffy air. Prevalence of work related symptoms was also slightly lower after cleaning. 697

Table 2. Characteristics of respondents, perceived indoor climate and symptoms of 931 employees of 15 office buildings before and after the duct cleaning. Background factors Unit Reference Before duct value 2,3 cleaning Average age year 44 44 Portion of women % 56 57 Portion of smokers % 17 18 Respondents suffered ever from Asthmatic symptoms % 10 10 11 Hayfever % 25 42 36 Eczema % 27 29 21 Environmental factors 1 Draft % 4 12 11 Too high room temperature % 5 9 9 Stuffy bad air % 10 29 15 Dry air % 20 23 19 Dust and dirt % 10 17 14 Workplace related symptoms 1 Itching, burning or irritation of the eyes % 6 15 12 Irritated, stuffy or runny nose % 9 21 18 Hoarse, dry throat % 5 13 11 1 Bothered every week, 2 Andersson 1999, 3 Bluyssen et al. 1996 After duct cleaning DISCUSSION Particle mass, TVOC and CO 2 concentrations of supply air were low and consistent with previous office studies (Bluyssen et al.1996). Also airborne microbe concentrations were low. Number concentration of particles <1µm was higher after cleaning, but this can be explained by the fact that outdoor concentration of particles <1 µm was also higher after the cleaning. Higher concentration after cleaning could be also result of the changing the new supply air filters. New filters are not so efficient than used ones (Ottney 1993). Thus, duct cleaning had no measurable effect on supply air quality. Instead of this, the average amount of dust on the inner surfaces decreased from 8.4±9.1 to 1.9±2.1 g/m 2. Correspondingly, mean microbe load on inner duct surface decreased due to cleaning and this finding was consistent with a previous study (Collet et al. 1999). The improvement of duct cleanliness was also noticed visually. The average air flows exceeded 20 L/s person before and after cleaning and duct cleaning and rebalancing the ventilation system mainly increased air flows in the investigated rooms. Even though the ventilation rates on average were above 20 L/s person, variation of the air flows were high among the investigated rooms, even inside the same building. Air flows were below 20 L/s person in 50% of the measured rooms before the cleaning. After cleaning and rebalancing the ventilation systems the proportion decreased to 33%. According to employee s answers to the questionnaire, nearly all factors concerning the working environment were improved. Also, the prevalence of work related symptoms was slightly reduced after the cleaning. Andersson (1998) has presented the reference values for this questionnaire for non-problem office buildings in the Nordic countries (Table 2). In our study the mean percentage of selected environmental factors and workplace related symptoms were from 2 to 3 times higher than those reference values. The highest difference was 698

detected with stuffy air. A high prevalence of stuffy air complaints before cleaning refers to insufficient ventilation. This contradicts with the measured air flow rates per person which were at levels suggested by Seppänen et al. (1999). One possible explanation could be insufficient air flows in the several rooms not measured in this study. CONCLUSIONS AND IMPLICATIONS This study proved that the effects of duct cleaning on IAQ are difficult to measure in nonproblem buildings. On the other hand, employees perceived improvement of IAQ and reduced prevalence of work related symptoms. Duct cleaning is important part of ventilation system maintenance, because simultaneously with duct cleaning the possible technical failures can be detected and air flows rebalanced. Thus, if maintenance is neglected, IAQ problems might occur, leading to complaints by personnel and extra costs for building management. ACKNOWLEDGEMENTS The study was funded by the Finnish Work Environment Fund and the State Treasury. The authors thank the owners, maintenance personnel and employees of the study buildings and the duct cleaning companies for the co-operation in this study. REFERENCES Andersson K. 1998. Epidemiological approach to indoor air problems. Indoor Air. Suppl. 4, pp 32-39. Bluyssen PM, de Oliveira Fernandes E, Groes L, et al. 1996. European Indoor Air Quality Audit Project in 56 office buildings. Indoor Air. Vol 6, pp 221-238. Collett CW, Nathanson T, Scott JA, et al. 1999. The impact of H.V.A.C system cleaning on levels of surface dust and viable fungi in ductwork, Proceedings of the 8 th International Conference on Indoor Air Quality and Climate - Indoor Air 99, Vol 3, pp 56-61. Edinburgh: Indoor Air 99. FiSIAQ Publication 5. 2001. Classification of Indoor Climate 2000, Target values, design, guidance and product requirements, Espoo: Finnish Society of Indoor Air Quality and Climate (in Finnish). Ikäheimo M, Luoma M, and Pasanen P. 2000. The effect of duct cleaning and rebalancing of the ventilation system on air flow rates and particle concentrations in office buildings, Proceedings of Healthy Buildings 2000, Vol 2, pp. 205-210. Espoo: Healthy Buildings 2000. Luoma M, Pasanen P and Ikäheimo M. 1999. The effect of duct cleaning on indoor air quality in office buildings, Proceedings of the 8 th International Conference on Indoor Air Quality and Climate - Indoor Air 99, Vol 3, pp 91-96. Edinburgh: Indoor Air 99. Ottney TC. 1993. Particle management for HVAC systems. ASHRAE Journal. Vol 35, pp 26-34. Pasanen P, Nevalainen A, Ruuskanen J, et al. 1992. The composition and location of dust settled supply air ducts, Proceedings of 13 th AIVC Conference, Ventilation for Energy Efficiency and optimum Indoor air Quality, pp 481-488. Nice: AIVC Conference 1992. Seppänen OA, Fisk WJ, and Mendell MJ. 1999. Association of ventilation rates and CO 2 concentrations with health and other responses in commercial and institutional buildings. Indoor Air. Vol 9, pp 226-252. 699