PART-II SPECIFICATION OF 22KV PIN INSULATORS. This specification covers 22KV Pin Type Insulators for 22KV H.T. over head power lines.

Similar documents
SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS:

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: -

MGVCL/MM/1043/13-14/11 KV Disc Insulators (Porcelain)

Date: TECHNICAL SPECIFICATION FOR (LT,11KV, 33KV) PORCELAIN PIN INSULATORS

SPECIFICATION FOR HT-LT STAY (GUY) INSULATORS:

Maharashtra State Electricity Distribution Co. Ltd.

SPECIFICATION OF HT-LT STAY (GUY) INSULATORS:

Maharashtra State Electricity Distribution Co. Ltd.

11KV PORCELAIN INSULATORS AND FITTINGS

Specification No. CSC- XXIX/DH/UH/P&D/

Maharashtra State Electricity Distribution Co. Ltd.

MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO. Ltd. (MUMBAI) SCHEDULE 'A' TECHNICAL SPECIFICATION FOR. 11 kv, 22 kv & 33 kv HORN GAP FUSES FOR

TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA

093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA

SPECIFICATION FOR DISC INSULATORS (Standard Type)

SPECIFICATION FOR STAY INSULATORS (PORCELAIN)

ANNEXURE - ' D ' TECHNICAL SPECIFICATION FOR INSULATOR PINS ( PINS FOR 11,22 AND 33 kv INSULATORS )

TECHNICAL SPECIFICATION FOR CONDUCTOR HARDWARE FITTING FOR 11/22/33 kv OVERHEAD POWER LINES

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATION FOR 11 POST INSULATORS, 11 KV & 33 KV PIN INSULATORS AND 11 KV, B&S TYPE 45 KN & 70 KN DISC INSULATORS.

TECHNICAL SPECIFICATION FOR 11 KV & 33 KV POST INSULATORS, 11 KV & 33 KV PIN INSULATORS AND 11 KV, B&S TYPE 45 KN & 70 KN DISC INSULATORS.

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS Insulators & Lightening Arrestor GROUP K & L

TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1

TECHNICAL SPECIFICATION OF UNARMOURED FLAT 1100 VOLTS L.T. PVC INSULATED TWIN CORE 4.0mm² CABLE WITH ROUND ALUMINIUM CONDUCTOR BLACK SHEATHED.

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS. Insulators & Lightening Arrestors GROUP A

TECHNICAL SPECIFICATION

SEAL & SIGNATURE OF THE TENDERER

CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA

No: PUR/IMP/JPL/UVIT/ISO/39 July 29, 2008

2. RATED VOLTAGE: The rated voltage of the AB cables shall be 1100 volts

SPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type

TECHNICAL SPECIFICATION FOR 3-PH SMC BOXES MADE FROM THERMOSETTING PLASTIC FOR 3-PH ENERGY METER.

TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1

Technical Specification for 11 KV, 5KN, 340 Creepage Distance Pin type Composite (Polymer) Insulator with rod

TURKISH ELECTRICITY DISTRIBUTION CO. TECHNICAL SPECIFICATION FOR POST (SUPPORT) INSULATORS FOR MEDIUM VOLTAGE SYSTEMS

Specification No. CSC-70/DH/UH/P&D/

a) Temperature Variation : 5ºC to 55ºC b) Relative humidity : Upto 95% c) Altitude : 0 to 1000 Mtrs. d) No.of tropical monsoon months : 3 (Three)

SPECIFICATION OF LT AERIAL BUNCHED (AB) CABLES (Size: 3C x 35mm² +1C x mm²) FOR LT LINES (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY)

Standard. Extra High Voltage (EHV) Post Insulators Standard R Version 1.0, June Tasmanian Networks Pty Ltd (ABN )

TECHNICAL SPECIFICATION FOR RATE CONTRACT OF INSULATING MATS

APDRP SCHEME, WESCO. Technical Specification for 33KV Air Break Switch PART 1: SCOPE AND CONDITIONS

TECHNICAL SPECIFICATION OF LONG ROD PORCELAIN INSULATORS FOR TRANSMISSION LINES

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT

PART-II. TECHNICAL SPECIFICATIONS FOR 11 KV, 45KN, 320 Creepage Distance, Long rod (B&S) type Composite (Polymer) Insulator.

General Requirements. Technical Specifications for Insulators of Transmission Lines

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara:

5.2 The phase conductors shall be provided with one, two & three ridges for easy identification.

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv)

11 KV, 45KN, 320 Creepage Distance, Long rod (B&S) type Composite (Polymer) Insulator

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

1. 8mtr 200Kg PSC Pole 2. 9mtr 300Kg PSC Pole

SECTION-II (VOLUME-II) PAGE 1

TECHNICAL SPECIFICATION OF MS TOR BARS FOR TRANSMISSION LINES

SPECIFICATION OF NEOPRENE RUBBER SEALS

TECHNICAL SPECIFICATION OF 70KN & 45KNDISC INSULATOR (B & S)

TECHNICAL SPECIFICATION FOR CONDUCTORS

COMPOSITE INSULATORS

TECHNICAL SPECIFICATION FOR 11KV COMPOSITE INSULATORS (SILICON RUBBER HOUSED)

Technical Specifications for 11 KV, 45KN, 320 mm. Creepage Distance, Long rod, (B&S) type Composite (Polymer) Insulator

SPECIFICATION FOR POLYMER DISC INSULATOR

TECHNICAL SPECIFICATION FOR OUTDOOR TYPE DISTRIBUTION PLOT & SERVICE JUNCTION BOX

TECHNICAL SPECIFICATION FOR MS BEAMS 116X100 11MTR LONG FOR SUB-STATIONS

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS

6C-001 High-Voltage Pin-Type Insulator

POST AND DISC INSULATOR

MGVCL/MM/ 3Cx240 mm 2 XLPE Cables/2077 TECHNICAL SPECIFICATION FOR 11 KV XLPE POWER CABLE (CROSS LINKED POLYTHELENE DRY GAS CURED) SECTION I

TECHNICAL SPECIFICATION OF ACCESSORIES SUITABLE FOR 7/3.15 mm G.I. EARTH WIRE

Specification for Polymer Disc Insulator

Bharat Heavy Electricals Limited. Ceramic Business Unit. ollow. An ISO 9001, & Certified Company

TECHNICAL SPECIFICATION FOR SMC LT AMR METER BOXES MANUFACTURED FROM THERMOSETTING PLASTIC 1.0 SCOPE:

P.V.C. INSULATED UNARMOURED COPPER CABLES

Technical Specification for Insulated Low Voltage Single Core Copper Cable

TENDER NO. PGVCL/PROC/HT SMC Meter Box/872

2.1 Similar parts of any equipment supplies shall be interchangeable.

Technical Specification for Low Voltage Aerial Bundled HDPE Insulated Cables

TECHNICAL SPECIFICATION OF SILICON RUBBER HOUSED COMPOSITE INSULATORS FOR TRANSMISSION LINES

SPECIFICATION FOR FRLS POWER CABLES

ASSAM POWER DISTRIBUTION COMPANY LIMITED. OFFICE OF THE CHIEF GENERAL MANAGER (HQ),APDCL BIJULEE BHAWAN, PALTANBAZAR, GUWAHATI

TECHNICAL SPECIFICATION OF SILICON RUBBER HOUSED COMPOSITE INSULATORS FOR TRANSMISSION LINES

TECHNICAL SPECIFICATIONS FOR. 11 KV, 45 KN, 320 mm. Creepage Distance, Long rod (B&S) type Composite (Polymer) Insulators

1.1 All testing apparatus shall be periodically checked and calibrated records of such checks/calibration shall be maintained.

TECHNICAL SPECIFICATION FOR G.I. BARBED WIRE. (SPECIFICATION NO.MM/I/G.I.BARBED WIRE/2006) (Dt )

SECTION 07 TECHNICAL SPECIFICATIONS 11KV OUTDOOR TYPE SINGLE PHASE METAL OXIDE (ZNO) GAPLESS LIGHTNING ARRESTER (LA)

660 Volts 630 & 800AMP

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION

8. Hydrophobicity classification guide STRI guide 1.92/1 9. Radio interference characteristics of overhead power lines and high-voltage equipment

TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATION FOR FRP FENCING AROUND DISTRIBUTION TRANSFORMER STATIONS

NEPAL ELECTRICITY AUTHORITY (An Undertaking of Government of Nepal) Distribution and Consumer Services Butwal Regional Office

SECTION 1 SCOPE, SPECIFIC TECHNICAL REQUIREMENTS AND QUANTITIES

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

TECHNICAL SPECIFICATION FOR SUPPLY OF WEDGE CONNECTOR TO BE USED IN POWER DISTRIBUTION SYSTEM

BIDDING DOCUMENT FOR. Supply of Galvanized Steel Tubular Poles, 11KV Polymer Insulators and ACSR Conductors under Saubhagya Scheme

Transcription:

1. SCOPE: PART-II SPECIFICATION OF 22KV PIN INSULATORS This specification covers 22KV Pin Type Insulators for 22KV H.T. over head power lines. 2. APPLICABLE STANDARDS: Except when they conflict with specific requirement in this specification, the insulators shall comply with the Indian Standard specification, IS- 731/1971and the latest version thereof. The insulators fittings shall comply with the Indian Standard specification IS-2486/Part-I/1993, IS- 2486/Part.II/1989 or the latest version thereof. 3. DESCRIPTION: 22KV Brown Glazed pin insulators confirming to IS-731/1971 and subsequent amendment No.1 to 5 to give rigid support to an over-head line and intended to be mounted vertically on supporting structure by GI Pin passing up inside this insulator with minimum failing loads 10 KN. 4. GENERAL REQUIREMENT: i) The porcelain shall be sound and free from defects, thoroughly vitrified and smoothly glazed. ii) The glaze shall be brown in colour. The glaze shall cover all the porcelain parts of the insulator except those areas which serve as support during fixing or are left unglazed for the Purpose of assembly. iii) The design of the insulators shall be such that stresses due to expansion and contraction in any part of the insulator shall not lead to deterioration. The porcelain shall not engage directly with hard metal. iv) Cement used in the construction of the insulators shall not cause fracture by expansion or lossen by contraction and proper care shall be taken to locate the individual parts correctly during cementing. The cement shall not give rise to chemical reaction with metal fitting and its thickness shall be as uniform as possible. 5. ELECTRICAL AND MECHANICAL CHARACTERISTICS: The electrical and mechanical particulars of 22KV Pin insulators shall be as per the Guaranteed Technical Particulars shown in Annexure - A & B attached herewith, measured at the following standard atmospheric conditions. [DGVCL/SP/8004/ 22KV Pin Insulators/Doc Page 1 of 5]

1. Ambient temperature 20 Deg. C 2. Barometric pressure 1013 millibars 11 Grams of water per cubic mtrs. 3. Absolute Humidity Corresponding to 63% relative humidity at 20 Deg.C. 6. BASIC INSULATION LEVELS: 6.1 The test voltage of Pin insulators shall be as per the values given in Guaranteed Technical Particulars shown in Annexure A & attached. 6.2 In this specification power frequency voltages are expressed as peak values divided by 2 and impulse voltages are expressed as peak values. 6.3 The withstand flashover voltages are referred to the reference atmospheric conditions. 7. As the insulators are to be used any where in Gujarat State including the coastal area, the Creepage distances of specified in GTP are minimum. However, the firm may offer insulators of higher creepage distance, but the mechanical and electrical parameters of their product shall be as per the mechanical and electrical requirement given in Appendix-A & B attached. 8. TESTS: i) All the bidders must submit copies of type test certificates alongwith laboratory approved drawings for the products offered by them. The Certificates shall be from CPRI, ERDA, and Indian Institute of Science, Bangalore or any other Govt. recognized laboratory, but not more than 5 years old as on date of opening the tender. ii) Copy of type test certificate of each type offered must be submitted. iii) The type test certificate shall be final and complete for all the tests as per the list of type tests given in specification Cl.No.8.1 of the specification. iv) Failure to submit the type test certificates as described above shall be liable for rejection of tender offer. v) Routine test shall be carried out on every insulator as specified in IS-731/71 with amendment No.1 to 5 and certificate issued with each batch. Details of test result on each of the insulator supplied, has to be submitted to inspector for his perusal and verification. vi) The insulators shall comply with the type tests as per IS-731/1971 with latest amendment 1 to 5 and as mentioned in Cl.No.8.1 below. [DGVCL/SP/8004/ 22KV Pin Insulators/Doc Page 2 of 5]

8.1 TYPE TESTS: The following shall constitute the type tests (Cl.No.10.1.1 of IS- 731/1971).However; the test voltage value shall be as per GTP enclosed. a) Visual examination. b) Verification of dimensions. c) Visible discharge test. d) Impulse voltage withstand test (+ve wave & -ve wave) e) Impulse voltage flashover test (+ve wave & -ve wave) f) Dry and wet power frequency voltage withstands test. g) Dry and wet power frequency flashover voltage test. h) Temperature Cycle test. i) Mechanical failing load test j) Puncture test. k) Porosity test. The tests shall be carried out on the two samples in the order mentioned in the Cl.10.1.1 of IS-731/1971. All the tests shall be carried out in the same laboratory. 8.2 ACCEPTANCE TESTS: From the offered lot, samples shall be drawn randomly as per the criteria given. The firm has to arrange for carrying out all following acceptance tests at firms works only at firm's cost in presence of inspector deputed by DGVCL Corporate SURAT. a) Verification of dimensions and Visual examination. b) Temperature cycle tests. e) Mechanical failing load test f) Puncture test. g) Porosity test. 8.3 ROUTINE TESTS:- The following tests shall be carried out as routine tests by firm on each insulator before offering the lot for inspection. a) Visual examination. b) Mechanical routine test (for type 'B' string insulators units only) c) Electrical routine test (for type 'B' string insulators and rigid insulators). 9 DRAWING AND CATALOGUES: The tenderer shall furnish catalogues, literature and detailed dimensional drawing of insulators offered showing section of the insulators to show the method of construction connecting arrangement, length and type of threads etc. [DGVCL/SP/8004/ 22KV Pin Insulators/Doc Page 3 of 5]

The drawing shall be got approved by the User Department prior to commencing the bulk supply. 10. MARKING: 10.1. Each insulator shall be legibly and indelibly marked to show the following. a) Name or trade mark of the manufacturer. b) Month and year of manufacturer. c) Minimum failing load. d) Country of manufacture. e) ISI Certification mark, if any. f) Word 'DGVCL' marked stickers to be provided on each insulator. 10.2. Marking on porcelain shall be printed and shall be applied before firing. 11. PACKING: i) All insulators (without fittings) shall be packed in wooden crates suitable for easy but rough handling suitable for rail/road transport. Where more than one insulator is packed in a crate, wooden separators shall be fixed between the insulators to keep individual insulator in position, without movement within the crates. Disc. Insulators however, may be assembled in a string and then packed inside a crate, in above fashion. ii) The wooden crates shall be provided with steel hoop and bends for strength and durability to withstand rough handling. The bends shall have descriptive marking of the firm thereon. iii) The firm shall provide at his cost, lead seal and wire on each wooden crate to facilitate sealing by the inspector of DGVCL after acceptance of the lot. 12. INSPECTION: Party has to offer the materials for inspection duly packed in crates as mentioned in GTP. The inspection approval is valid for a period of 15 days from the date of inspection to enable the firm to despatch the materials by arranging transportation at destination allotted thereof within the said period. After this period of 15 days, the validity of the inspection will lapse. Thereafter, the inspection approval will be revalidated by competent authority on furnishing written application explaining therein the valid reasons for delay in affecting dispatches. 13. The firm shall not despatch the offered lot unless the same is inspected by the inspector of DGVCL - SURAT & accepted by him after [DGVCL/SP/8004/ 22KV Pin Insulators/Doc Page 4 of 5]

passing in all acceptance tests, and/or receipt of waival of inspection in writing from competent authority of DGVCL Corporate SURAT. 14. Type Test: 1. The offers without type test certificate and certified drawing by Government approved laboratory will not be considered. 2. Party should submit his own design drawing with all dimensional details to be supported by type test certificate and attested drawings. Sr. No. 1 Description of materials 22KV Pin Insulators Brown Glazed porcelain Pin Insulator confirming to IS-731/1971 Amendment 1 to 5 Type-B with 560mm minimum creepage distance and with lead/zinc thimble suitable for use with G.I. Forged pin having large steel head as per IS-2486 (P.I)/1993 & IS-2486 (P.II)/1989 second revision and conforming REC specification. Quantity required. 20,000 nos. [DGVCL/SP/8004/ 22KV Pin Insulators/Doc Page 5 of 5]