Enviroline 375 Application Guidelines

Size: px
Start display at page:

Download "Enviroline 375 Application Guidelines"

Transcription

1 Enviroline 375 Page 1 of 17 Enviroline 375 Application Guidelines Prepared by: International Paint Ltd. The information in this guideline is not intended to be exhaustive; any person using the product for any purpose other than that specifically recommended in this guideline without first obtaining written confirmation from us as to the suitability of the product for the intended purpose does so at their own risk. All advice given or statements made about the product (whether in this guideline or otherwise) is correct to the best of our knowledge but we have no control over the quality or the condition of the substrate or the many factors affecting the use and application of the product. THEREFORE, UNLESS WE SPECIFICALLY AGREE IN WRITING TO DO SO, WE DO NOT ACCEPT ANY LIABILITY AT ALL FOR THE PERFORMANCE OF THE PRODUCT OR FOR (SUBJECT TO THE MAXIMUM EXTENT PERMITTED BY LAW) ANY LOSS OR DAMAGE ARISING OUT OF THE USE OF THE PRODUCT. WE HEREBY DISCLAIM ANY WARRANTIES OR REPRESENTATIONS, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, INCLUDING WITHOUT LIMITATION, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. All products supplied and technical advice given are subject to our Conditions of Sale. You should request a copy of this document and review it carefully. The information contained in this guideline is liable to modification from time to time in the light of experience and our policy of continuous development. It is the user s responsibility to check with their local International Paint representative that this guideline is current prior to using the product.

2 Enviroline 375 Page 2 of 17 SCOPE AND PURPOSE The International Paint Application Guidelines have been produced and revised in line with the Worldwide Product Range. The purpose of the guidelines is to ensure that a lining system, as applied, provides adequate protection against corrosion. Successful in-service performance of a lining system depends upon both the correct choice of lining and the adoption of the correct guidelines for surface preparation and paint application. The responsibilities for achieving the specific standards outlined, and for carrying out surface preparation and paint application, rest with the Contracting Company. Under no circumstances do these responsibilities rest with International Paint. We will generally provide for the presence of a Technical Service Representative at key stages during the performance of the contract. The role of the International Paint Technical Service Representative is advisory only unless otherwise specified in the terms and conditions of the contract. The information contained herein presents guidelines for the application of Enviroline 375 to both new and existing steel and/or concrete CONTENTS 1. LINING SPECIFICATION 2. ENVIRONMENTAL CONDITIONS FOR APPLICATION 3. APPLICATION PROCEDURE 4. APPLICATION TECHNIQUES 5. TECHNICAL INSPECTION AND PROJECT CONTROL 6. GENERAL NOTES 6.1. Steel Condition 6.2. Steelwork Preparation 6.3. Ventilation 6.4. Heating 6.5. Lighting 6.6. Storage of Product at Point of Application 6.7. Weather Shelters 6.8. Abrasive Grit Blasting 6.9. Cleaning Mixing Stripe Coating Pit Filling 7. REPAIR PROCEDURES 8. HEALTH & SAFETY APPENDIX FABRICATION RECTIFICATION

3 Enviroline 375 Page 3 of LINING SPECIFICATION 1.1 Surface Preparation In common with most protective coatings schemes, the performance level of Enviroline 375 is ultimately determined by degree of surface preparation. The higher the degree of surface preparation achieved, the greater the long-term performance. For optimum performance, all surfaces to be coated should be clean, dry and free from contamination including dirt, salts, oil and grease. Steel Prior to paint application all surfaces should be assessed and treated in accordance with ISO 8504:2000. Where necessary, remove weld spatter and smooth weld seams and sharp edges (see Appendix 1). In cases where the substrate is corroded or pitted, it may be necessary to fresh water wash the areas after abrasive blasting, then reblast, in order to ensure complete removal of soluble corrosion products. The allowable total soluble salt contamination on the steel before application of the Enviroline 375 is as follows: Chlorides : Less than 3µg/cm 2 Sulphates : Less than or equal to 5µg/cm 2 Nitrates : Less than or equal to 5µg/cm 2 The total of all 3 soluble salt types must not exceed 10µg/cm 2 See section 3 for more details regarding measurement. All steel surfaces to be coated should be correctly prepared prior to application of the coating system. Abrasive grit blast the steel to be coated to a minimum of ISO Standard (2007) Sa2½ or SSPC SP10. A sharp and angular surface profile of between 62 and 88 microns ( mils) is required. In certain aggressive service conditions, it may be required to blast to Sa3 or SSPC SP5. Contact International for specific advice. Concrete New concrete shall be properly cured prior to the application of Enviroline 375. Laitance and efflorescence shall be removed. Moisture content must also be checked to make sure it is below 7% prior to coating application. The tensile strength of the concrete should be minimum 2MPa (300psi). The presence of oil, grease and release agents in concrete may cause loss of coating adhesion. Although the surface may appear free of any oil, solvents in the coating material can draw the oil from within the concrete to the coating/concrete interface. Surface preparation of concrete should be done in accordance to SSPC-SP13/NACE 6. All chemical contamination must be removed prior to the application of Enviroline coating systems. Contamination includes efflorescence, laitance, oils, chemicals, acids, salts, alkalis, curing compounds, form release agents, and microorganisms.

4 Enviroline 375 Page 4 of 17 All existing coatings and sealers must be removed to insure proper bond between the concrete substrate and lining. Concrete structures that have mechanical or chemical damage, or rebar corrosion must be restored to provide a uniform substrate for the coating. The presence of severe hydrostatic forces may disbond the coating. The concrete substrate should have a vapor barrier on the soil side to prevent hydrostatic forces. Consult a qualified engineer to determine if these forces are present. If so, it is recommended a test patch be applied to test the bond strength and evaluated over a reasonable period of time. A good blast profile is required to ensure the adhesion of coatings. Depending on condition of the concrete, a combination of chemical cleaning and/or abrasive blasting may be required. Previously applied coating will require abrasive blasting for removal. Dry blasting is recommended. Blasting will remove loose and powdery concrete and surface laitance. The resulting surface must be hard, with surface voids open and with a profile that is satisfactory for coating adhesion. The blast nozzle must be kept at a distance that will provide good results without gouging the concrete. The resulting surface should be at least as rough as grit sandpaper or refer to ICRI profile standards. All dust and debris must be removed after abrasive blasting. Dry, oil-free air must be used for the blasting operation. Use ASTM Method D4285 for determination of oil and water in compressed air sources. Final cleaning methods must ensure that the surface is free of any cleaning agents or other surface contaminants. This may be accomplished by a compressed air blow down, vacuuming, dry wipe down or other appropriate final cleaning methods. The surface must be allowed to dry adequately for compatibility with the coating material. Impact tools (scabblers and scarifiers), vacuum grit blasting, and power grinding may also be used for roughening concrete, opening holes and voids, and to remove loose matter from the surface of poured concrete and precast slabs. These methods may be used instead of blasting but are slower. An appropriate primer is required to effectively seal the concrete substrate. Consult International Protective Coatings for specific advice on primer choice. When working outside or in direct sunlight, concrete gassing or breathing can occur, when the surface temperature rises due to exposure to sunlight or increasing ambient temperatures. This can cause bubbles or holes in the applied coating. When this problem occurs, it is necessary to shade the surface from the sun and/or apply the material in the evening or at night, so that initial cure can take place in cooler temperatures, without air escaping from the concrete. A detailed concrete surface preparation guideline document is available upon request

5 Enviroline 375 Page 5 of Typical Specification Coat Product Dft (microns) Dft (mils) Spec Min Max Spec Min Max Stripe** Enviroline Full* Enviroline * Enviroline 375 can be applied as a one or two coat system to the recommend film thickness as long as the second coat does not exceed the recoat ability window published on the most recent product information bulletin. **All areas itemised in Section 6.11 are to receive a stripe coat. 1.3 Notes The detailed project coating specification provided by International must be followed at all times. This will include specific details with regard to surface preparation and dry film thickness requirements. Specific project requirements will be dependent upon the service end use and operating conditions of the tank or vessel. Always consult International to confirm that Enviroline 375 is suitable for contact with the product to be stored. Refer to the Enviroline 375 datasheet for precise overcoating intervals, pot life and curing requirements. 2. ENVIRONMENTAL CONDITIONS FOR APPLICATION Enviroline 375 will not cure at ambient temperatures below 13 C (55 F). For maximum performance, the temperature should be greater than 13 C (55 F). Humidity control is required during application of Enviroline 375. The climatic conditions should be controlled to maintain a maximum relative humidity of 80% and a minimum temperature of 13 C (55 F). Maximum steel temperature should be no more than 49ºC (120ºF). Application should not take place when relative humidity is more than 80% or the surface temperature is less than 3ºC (5ºF) above the dew point. Dehumidification, air conditioning and/or heating equipment may be necessary to control environmental conditions but care should be taken when choosing heating methods, as some heaters can increase the local relative humidity. For higher temperatures, for example those found in the Middle East and tropical areas consult your regional International Paint Technical Department. 3. LINING APPLICATION PROCEDURE Defective steelwork, prior to contract commencement, should be repaired in line with the guidance notes given in the Appendix of this document. Microclimate should be monitored in between applications. Changes in microclimate may affect overcoating intervals.

6 Enviroline 375 Page 6 of 17 For steel surfaces, grit blast the steel to be coated to a minimum of ISO Standard (2007) Sa2½ or SSPC SP10. A sharp and angular surface profile of between 62 and 88 microns ( mils) is required. In certain aggressive service conditions, it may be required to blast to Sa3 or SSPC SP5. Contact International Protective Coatings for specific advice. For concrete surfaces, carry out appropriate preparation as described in Section 1. Upon completion of the surface preparation process, and following inspection by the Contractor Quality Control Department, an International Paint Technical Service Representative may also inspect the whole area and mark up any substandard areas if agreed as part of the contract. Before coating of the blasted surfaces commences, the amount of residual salt should be measured using an appropriate method such as the Bresle Patch (ISO ), Chlor*Test CSN Salts test kit or similar. The number of tests to be carried out is dependent upon the size of the tank. If the residual salt level is greater than that agreed, the entire area to be coated should be fresh water washed and retested. All marked areas shall be brought up to the required standard. The whole blasted area is to be blown down/vacuum cleaned to remove all dust and contamination. Ensure, prior to application, that the minimum environmental conditions specified in Section 2 are achieved. Provision should be made to ensure these conditions are maintained throughout the painting program. All areas itemised in Section 6.11 are to receive a stripe coat. The stripe coat should be applied within the overcoating intervals specified in the Enviroline 375 technical datasheet. All the areas are to receive a full coat of Enviroline 375 to the specified dry film thickness. When fully hard dry, and accepted by the Contractor Quality Control Department, an International Paint Technical Service Representative may confirm the dry film thickness if agreed as part of the contract. Any areas of under thickness are to be brought up to the minimum thickness specified. This must be carried out within the overcoating intervals specified for the product. If the overcoating interval has been exceeded then the area should be abraded and cleaned prior to application of touch up. Unless otherwise advised, all damages are to be either vacublasted to Sa2½ (ISO (2007)) or SSPC SP10 or Power tool clean to SSPC SP11 with a profile of 62 and 88 microns ( mils). All damages are to be touched up with Enviroline 375 to the specified minimum dry film thickness as per the project specification. Upon completion of installation, the final coating should be inspected using a suitable non-destructive magnetic gauge to verify average lining thickness. Holiday testing and Shore D hardness testing should also be carried out. Following testing, any defective area should be repaired in accordance with the recommendations of the International Paint Technical Service Representative. These recommendations will be based upon those outlined in Section 7. Ensure that fresh containers are used after each unit is sprayed do not refill the old containers.

7 Enviroline 375 Page 7 of APPLICATION TECHNIQUES Enviroline 375 can be applied by either Single Leg Airless Spray (Hot Potting Method) or Plural Component Airless Spray Enviroline 375 should be applied via either method except for stripe coats where brush or a combination of airless spray and brush can be generally used. Available air pressure and capacity for spray equipment should be at least 7kg/cm2 and 7.0m3/min (100 psi and 250 cfm free air volume). All spray equipment must be in good working order. For both airless and heated plural component application, in cold and/or windy weather, insulate the exposed pumping equipment using pipe insulation or similar insulating material to reduce unit heat loss. Single Leg Airless Application (Hot Potting) The single leg airless spray method requires constant attention to temperature and pot life as the material is mixed prior to passing through the pump. It is important to remember that the higher the mixing temperature the shorter the pot life. It is recommended that airless spray pump ratios of 45:1 or greater should be used. Smaller pumps may not be able to physically push the material through the lines and spray gun at an adequate rate. Teflon packings are recommended. Remove suction tube and all filters from the spray unit and airless spray guns Reversible tips should be the size range thou. Tips must not be in a worn condition. Paint line (hose) should be of 3/8 inch diameter, a maximum length of 45m (148ft), with a 1/4 inch diameter and 3m (10ft) whip-end. Both line and whip-end should be rated at 5000psi (351 kg/cm2) Recommendations for the paint crew for single leg airless spray application are as follows: The application crew should consist of a minimum of four (4) trained crew members. The crew should thoroughly understand the basics of the equipment, the material and the application techniques. The contractor may require fewer personnel on smaller projects. Recommendations for distribution of personnel are - two (2) inside of the tank and two (2) on the outside of the tank. The personnel inside of the tank being responsible for proper spraying, wet film thickness readings, and paint line (hose) movement. The outside personnel being responsible for the proper preheating, mixing of material, temperature monitoring once product is mixed, and dispensing of material to the pump. It is recommended that periodic flushing of the pump, hose, and spray gun with Enviroline 71C is carried out. If material reaches 54 C (130ºF) during any part of the application process it is recommended that application be halted and the pump cleaned out immediately to reduce the risk of hardening in the pump, lines and gun

8 Enviroline 375 Page 8 of 17 Plural Component Airless Application Heated plural component spray application is the most practical and preferred method when working with fast curing, short pot life materials, especially when lining large areas and applying at lower temperatures. A pump capable of accurately delivering a 2:1 mix ratio is essential (Graco 45:1 or greater power ratio is recommended). Remove all filters from the spray unit and airless spray guns Two (2) 51 mm (½ inch) x 304 mm (12 inch) elemental in-line static mixers are required these are located in line after the mixer manifold on the plural component equipment. Heated tanks and heated lines up to 55 C (130 F) may be necessary for long runs during cold weather application where the equipment is outside the tank or equipment being sprayed. The resin (Part A) fluid line should be 13mm (½ ) internal diameter minimum The hardener (Part B) fluid line should be 13mm, (½ ) internal diameter, although 10mm, (3/8 ) internal diameter minimum is also possible. The high pressure solvent fluid line should be 6mm, (¼ ), internal diameter minimum. Tips should be the size range thou tip reversible tips are suggested Paint line (hose) should be a diameter or 10 mm (3/8 inch), maximum length 75 meter (246 feet), with a 6 mm (1/4 inch) diameter, 3m (10ft) whip-end. Both line and whip-end should be rated at 5000psi (351 kg/cm2) Plural component application requires volumetric check of the mix ratio (utilizing a ratio monitoring system) before and during the application process, although any variation in product colour during application will also indicate that the plural pump is off ratio. The plural component unit should have facility for heating of the base and curing agent components. The base component (part A) should be heated to a maximum of 55 C (130 F) and the hardener to a maximum of 40 C (105 F) under agitation in the plural component equipment. The use of trace heated lines or an inline heater may be required to maintain the temperature required for application. Recommendations for the paint crew for plural component airless spray application are as follows: The application crew should consist of a minimum of four (4) trained crew members. The crew must thoroughly understand the basics of the equipment, the material and the application techniques. The application crew should consist of an equipment operator, one person to load preheated material into pump, a mixing manifold operator (who can take wet film thickness readings and move the paint line), and a gun operator. Equipment operator should monitor operation of equipment at all times to ensure proper performance. The mixing manifold operator should monitor the manifold gauges to ensure proper mix ratio and continuous pressure delivery. The gun operator should continuously monitor spray fan and material colour for consistency. Arrange equipment and all possible work to allow the gun operator to spray continuously.

9 Enviroline 375 Page 9 of 17 Important Note: A pressure drop is associated with paint lines. This pressure drop needs to be considered and depends upon the following factors. The viscosity of the paint. Higher viscosity paints produce greater pressure drops than low viscosity paints. The length of the paint line. Longer lines produce greater pressure drops The internal diameter of the paint line. Flow rate of paint through the line. 5. TECHNICAL INSPECTION Project control via regular inspection and agreement on any future action is vital to a successful coating project, and in maximising the potential of a lining system. All parties involved in the coating work must agree an inspection procedure prior to work commencing, this should outline how and when both work and inspection will be undertaken. Prior to commencing the project, the contractor(s) must be provided with copies of the relevant product data sheets. Attention should be drawn to pack sizes, mix ratios, thinning restrictions, required application conditions etc. Inspection equipment for measurement of profile depth, humidity, wet and dry film thickness, etc should be of suitable type and should be within calibration limits. NOTE: When measuring the dry film thickness of coatings, the d.f.t. gauge must be calibrated prior to use as follows: 1. Check that the probe is clean. 2. Place the probe on a sample of millscale-free smooth steel of thickness greater than 1mm. 3. Calibrate the instrument to zero. 4. Select a certified shim of similar thickness to that expected for the coating under test. 5. Calibrate the gauge to the shim thickness. 6. Check that the gauge reads zero when replaced on the smooth steel sample. Measurement of dry film thickness is described in ISO Standard 2808: Method 6A. or SSPC PA2 Holiday testing should be carried out to ensure the coating is free from voids according to ASTM D A final inspection should be carried out with a low voltage detector using the wet sponge method. The method of operation is to draw the moistened sponge over the surface. Where the defect has occurred a small current will flow and activate an audible alarm. Excessive wetting of the sponge should be avoided. Hardness Conduct a Shore D Hardness test in accordance to ASTM D to verify that Enviroline 375 has cured to the appropriate hardness. Shore D Hardness readings should be a minimum of 75 to indicate full cure. The fully cured lining system should be uniform in colour and gloss and be relatively free of any runs, sags, porosity, pinholes, fisheyes, soft spots and debris

10 Enviroline 375 Page 10 of GENERAL NOTES 6.1 Steel Condition Prior to commencement of gritblasting it is essential that the steel is clean, dry, and in a condition suitable for surface preparation and application of the coating scheme. All grease and oil must be removed from all surfaces and all hot work must be complete. Defective steelwork, prior to contract commencement, should be repaired in line with the guidance notes given in Appendix Steelwork Preparation Preparation grades of welds, cut edges and surface imperfections are described in ISO Preparation to P3 grade of this standard will provide surfaces which will ensure optimum paint performance. International Paint recommends the following methods and minimum levels of preparation on any new steelwork. Please see Appendix concerning rectification of fabrication faults. 6.3 Ventilation During and after coating application the ventilation system and trunking must be so arranged such that dead spaces do not exist. As solvent vapours are heavier than air, and will tend to accumulate in the lower areas and it is important that they are extracted from those areas. The extracted air must be balanced with fresh air being introduced into the encapsulated area. Equipment used must not re-introduce abrasive dust, solvent vapour etc. into the area where the coated articles are stored. The level of ventilation employed must take account of the Lower Explosive Limit (LEL) of the product being applied and comply with local legislative requirements. International Paint recommends that this is such that vapour concentrations do not exceed 10% of the LEL. Venting to 10% of the LEL is considered to provide a reasonable margin of safety to allow for possible higher local concentrations. Care should be taken when setting up ventilation/extraction systems, to ensure that 10% figure is not exceeded. Responsibility rests with the contractor to ensure that the requisite equipment is available and operated in such a way that these requirements are met. International Paint will provide all of the information needed to allow the contractor to calculate ventilation requirements. However, International Paint does not accept responsibility for the equipment, its operation, or the monitoring necessary to ensure that the requisite ventilation requirements are met. All equipment used after the commencement of paint application must be electrically safe in operation.

11 Enviroline 375 Page 11 of Heating If heating is necessary to satisfy the painting specification, it should be by means of a heat exchange system, i.e. air admitted to the encapsulated area should not pass directly through a combustion chamber. 6.5 Lighting Lighting during painting must be electrically safe and provide suitable illumination for all work. As a general guide, lighting may be considered suitable if this text can be read at a distance of 30 centimeters from the eye. Ideally, the lighting should be powerful mains supplied spotlight with background lighting on at all times in the interests of safety. Powerful mains spotlighting must be provided when inspection work is being carried out. 6.6 Storage of materials (at point of application) Provision must be made for heated storage of the Enviroline 375 to ensure a temperature of 35 C (95 F) is achieved for the part A and 30 C (86 F) for the part B prior to application. 6.7 Weather Shelters Weather shelters should be made available to cover application equipment during mixing and application of material. This should also prevent contamination from entering the area where application is underway. 6.8 Abrasive Grit Blasting The steel surface should be grit blasted to a minimum standard ISO (2007) Sa2½ or SSPC SP10. In certain aggressive service conditions, it may be required to blast to Sa3 or SSPC SP5. Contact International Protective Coatings for specific advice. In cases where the substrate is corroded or pitted, it may be necessary to fresh water wash the areas after abrasive blasting, then re-blast, in order to ensure complete removal of soluble corrosion products. The maximum allowed total soluble salt contamination on the steel before application of the Enviroline 375 scheme is 100mg/m-2 (10µg/cm2) Air used for blasting must be clean, oil free and dry. The pressure should be at least 7kgcm-² at the nozzle. Abrasives used for blasting must be dry and free from dirt, oil, and grease and suitable for producing the standard of cleanliness and profile specified. The abrasive must therefore be in accordance with the specifications given in ISO Parts 1 to 8 and each delivery should carry a certificate of conformity to this specification. If blasting abrasive is supplied on site without a certificate of conformity, the material should be tested by the yard or contractor in accordance with the methods given in ISO Parts 1 to 7.

12 Enviroline 375 Page 12 of 17 Particular attention should be given to ISO Part 6, where the level of water soluble contaminants must not give a conductivity value greater than 25mS/m, and ISO Part 7, where the level of water soluble chlorides must not exceed % by weight. Iron or steel abrasives can be used for in-situ open blasting. Specifications for metallic abrasives are given in ISO Parts 1 to 4 and the corresponding test methods in ISO Parts 1 to 7. If used, careful and thorough cleaning must be carried out at all stages of the operation to ensure that no abrasive remains on the steel as this may subsequently corrode. The required amplitude of the blast profile depends upon the type of coating to be applied. Measurement on site should be by profile gauge or other mutually agreed instruments. Measurement of surface profile using comparators is described in ISO using comparators detailed in ISO A medium 'G' type comparator should be used and a value of microns (2.2 to 3.8 mils) is acceptable when measured by: ISO : Focusing microscope ISO : Stylus When using a needle gauge such as the Elcometer 123, a value of 62 and 88 microns ( mils), taking a maximum of 10 determinations, is ideal. 6.9 Cleaning Prior to initial blasting inspection, the bulk of spent grit should be removed. Any substandard areas should be identified and should be brought up to the specified standard. Following provisional approval of the blast standard, ALL remaining traces of grit and dust should be removed from all areas. Final approval of a substrate for coating application should be confirmed after final cleaning Mixing Efficient mechanical stirrers for the correct mixing of paint must be used. For single leg airless spray application (Hot Potting Method) the mixed paint must be between 27 C (80 F) and 30 C (85 F) upon completion of mixing. This is best achieved by heating of the individual components to between 27 C (80 F) and 30 C (85 F) in a thermostatically controlled storage facility. The material (Part A, Resin, and Part B, Hardener) should first be pre-mixed in its own container to ensure proper dispersion of contents. Scraping the sides and bottom of the container is required. The hardener component, Part B should then be combined with the resin component Part A. This can be carried out in the 20 litre or 5-gallon container provided as part of the standard Enviroline unit, or in a separate hopper. The combined components should then be agitated until thoroughly mixed with one another, at rpm's, checking to see if the combined component color is uniform and complete. Excessive rpm s will induce air into the mixture and is not recommended. The equipment recommended for mixing consists of a 13mm, (½ ), drive reversible variable speed drill, an Enviroline mixing paddle or equivalent, and a thermometer. The temperature of the material should be monitored during mixing.

13 Enviroline 375 Page 13 of 17 For plural component application the individual components should be heated to 30 C (86 F) and fully pre-mixed in its own container to ensure proper dispersion of contents prior to loading into the appropriate hoppers on the spray unit (this is to facilitate the circulation and heating required for application). Facility for continued mixing will assist in maintaining uniform temperature during application Stripe Coats Stripe coating is an essential part of good painting practice. Typical areas where stripe coats must be applied include behind bars, plate edges, cut outs, e,g, scallops, manholes, etc, welds, chimes and seam areas, areas of difficult access, small fitments of difficult configuration and areas of pitting. Note: The above list is not comprehensive, all areas must be included. The following diagrams indicate key areas requiring stripe coating: In general, stripe coats should be applied by brush. Application by roller should be limited to the inside of scallops. In exceptional circumstances it may be acceptable to apply a stripe coat to the backs of angle bars by narrow angle spray. The use of spray applied stripe coats however, must be discussed and agreed with the International Paint representative on site. The stripe coat may be overcoated immediately wet on wet with Enviroline 375.

14 Enviroline 375 Page 14 of REPAIR PROCEDURE These repair guidelines are recommended for damages either at the initial coating stage or where breakdown of coating has occurred during service. The repair procedure recommended will depend upon the extent of damage involved but can be split into major and minor areas. 7.1 Major Repairs A major repair should essentially be dealt with as if the project were beginning. The recommendations given earlier for steel preparation, coating application, etc. must all be adhered to. 7.2 Minor Repairs Under this heading are repairs to areas damaged either at the initial coating stage or caused during service. The principle requirements are: The area to be repaired must be fresh water washed and dry. Remove any corrosion by means of either: - vacuum blasting (to achieve a minimum profile of 75µm, (3 mils) - hand tools, i.e. disc sander and grinder to effectively roughen the coating surface Any pitting which does not need re-welding should be prepared by needle gun and/or cone shaped grinder. Abrade the area immediately surrounding the repair to provide key for subsequent paint application. Apply the paint system in accordance with the guidelines. If small areas are involved and application is by brush, several coats may be required to achieve the correct dry film thickness. To repair an area of a tank that does not meet minimum thickness, brush blast, abrade (coarse grit), or grind the affected area to remove gloss and obtain a suitable surface roughness profile. Feather edges of repair site to achieve a smooth transition between repair and surrounding coating. Clean to remove any dust or debris prior to recoating and solvent wipe with MEK. Allow solvent to evaporate. Spray or brush apply Enviroline 375 depending upon the size of the affected area, to obtain the proper thickness or to cover any discontinuities. Holiday testing should be carried out to ensure the coating is free from voids according to ASTM D A final inspection should be carried out with a low voltage detector using the wet sponge method. The method of operation is to draw the moistened sponge over the surface. Where the defect has occurred a small current will flow and activate an audible alarm. Excessive wetting of the sponge should be avoided. Disposable solvent resistant brushes 2.5 to 10cm (1 to 4 inches) in width should be used for touch-ups and hard to reach areas only.

15 Enviroline 375 Page 15 of HEALTH & SAFETY 8.1 Introduction Whilst Enviroline 375 is high volume solids, the aerosol droplets/particulates produced during airless spray of this material may form an explosive mixture with air and additionally may contain materials which may necessitate personal protection against potential health hazards. A summary of the main precautions to be taken includes: Danger of explosion or fire Provision of a suitable breathing environment for workers. Prevention of skin irritation problems. Use of paints which have been specially formulated for use in tanks. 8.2 Danger of Explosion or Fire The key factors in preventing an explosion or fire are: Adequate ventilation. Elimination of naked flames, sparks and any ignition sources. 8.3 Ventilation Ventilation is necessary during abrasive blasting operations to ensure adequate visibility. Flexible trunking should be used to allow the point of extraction to be reasonably close to the personnel carrying out the blasting. During and after coating application it is essential that solvent vapours are removed to ensure that the level present in the atmosphere does not rise above that recommended in the section (6.2) dealing with Danger of Explosion and Fire. This means that the ventilation system must be arranged such that dead spaces do not exist and the ventilation must be continued both during the time that application is proceeding and also whilst solvent is released from the paint film during the drying process. Particular care must be taken to ensure that solvent vapour, which is heavier than air, does not accumulate in the lower areas of the tanks. The amount of air per minute for ventilating to 10% of the LEL (lower explosive limit) can be regarded as the required air quantity multiplied by rate of application per minute. The required air quantity is the amount of air needed for each litre of paint to ventilate to the required level. RAQ = Required Air Quantity LEL = Low Explosive Limit International Paint should be contacted for RAQ and LEL values, which are also given on the Material Safety Data Sheets for the appropriate products. Ventilation required (m3/minute) = RAQ x the application rate (litres/minute). The likely approximate application rate can be calculated from figures available from the application equipment supplier and will depend on the airless spray pump pressure and the orifice size of the tip used. In the event of a failure of the extraction/ventilation system paint application must be stopped and the area evacuated of personnel immediately.

16 Enviroline 375 Page 16 of Elimination of Ignition Sources Safety is the overriding consideration with this type of coating work, and the Site Safety Department must be made fully aware of all aspects of the operation. Welding, cutting or grinding in the immediate vicinity should be forbidden until paint fumes are totally dispersed. Lights, including hand torches, must be certified by the manufacturer as flash proof and suitable for use in solvent laden atmospheres. Smoking must be prohibited in the area or near to extraction systems. No electrical junction boxes should be allowed in the area where application is carried out. Airless spray equipment must be earthed (because of the danger of static electricity build-up). Mobile telephones, electrical cameras, and any equipment that is not intrinsically safe, must not be used in the area or near to extraction systems. 8.5 Solvent Vapour and Paint Mists - Protection of Painting Personnel No ventilation system can reduce solvent vapour levels to below the Occupational Exposure Limit for solvents whilst coating is in operation. Painters should, therefore, wear air fed hoods or pressure fed masks with additional eye protection. (Please note: air fed hoods which provide a curtain of air across the visor are available. These help to prevent settlement of spray mist on the visor). Normal protective clothing must be worn, e.g. overalls, gloves, and suitable footwear of non-spark type. 8.6 Skin Irritation If proper protective clothing has been worn, e.g. overalls, gloves, air fed hood etc, no discomfort should be experienced from skin irritation. Any small areas not protected by clothing, e.g. wrists or neck, can be treated with a non-greasy barrier cream. (Petroleum jelly is not recommended as this can assist the transport of solvents into the skin). Any areas of skin accidentally contaminated with paint must be thoroughly washed with soap and water. A skin conditioner that is designed to replace the natural oils in the skin can be used. Note 1. The preceding safety information is given for guidance only. 2. It is imperative that, prior to the commencement of any tank coating project, local Regulations regarding Health and Safety be consulted.

17 Enviroline 375 Page 17 of 17 APPENDIX FABRICATION RECTIFICATION ITEM PROBLEM/SOLUTION Sharp Edge Remove sharp edges or gas cutting edges with grinder or disc sander to achieve a radius of 1.5mm-2.0mm Weld Spatter Remove spatter observed before blasting by grinder, chipping hammer etc. For spatter observed after blasting: Remove with chipping hammer /scraper etc. Where spatter is sharp, use disc sander or grinder until obtuse Obtuse spatter no treatment required (a) (b) (c) Plate Lamination Any lamination to be removed by grinder or disc sander Undercut Where undercut is to a depth exceeding 1mm and a width smaller than the depth, repair by welding or grinding may be necessary Manual Weld For welding bead with surface irregularity or with excessive sharp edges, remove by disc sander or grinder Gas Surface Cut For surfaces of excessive irregularity, remove by disc sander or grinder

APPLICATION GUIDELINES EXTERIOR DECK SYSTEM

APPLICATION GUIDELINES EXTERIOR DECK SYSTEM APPLICATION GUIDELINES EXTERIOR DECK SYSTEM Revision 6 Issue Date: 15 th September 2015 Registered Office The AkzoNobel Building, Wexham Road, Slough, SL2 5DS Page 1 CONTENTS Page 1. SCOPE AND PURPOSE

More information

APPLICATION GUIDELINES RAPID REPAIR EXTERIOR DECK SYSTEM

APPLICATION GUIDELINES RAPID REPAIR EXTERIOR DECK SYSTEM APPLICATION GUIDELINES RAPID REPAIR EXTERIOR DECK SYSTEM Revision 6 Issue Date: 15 th September 2015 Registered Office The AkzoNobel Building, Wexham Road, Slough, SL2 5DS Page 1 CONTENTS Page 1. SCOPE

More information

Interline 850 Working Procedures

Interline 850 Working Procedures INTRODUCTION: GENERAL REQUIREMENTS FOR TANK LINING: NEW CONSTRUCTION: TANK CONDITION PRE-CONTRACT: Installation of a lining system is the most effective method of protecting steel tanks and vessels from

More information

APPLICATION SPECIFICATION SHEET GENERAL INDUSTRIAL EFFECTIVE: 01/09/12

APPLICATION SPECIFICATION SHEET GENERAL INDUSTRIAL EFFECTIVE: 01/09/12 I. Scope A. This specification defines application requirements of SpectraGarde NSF-61 plural-component 100% solids, 3:1 volumetric mix ratio polyurethane to concrete, ferrous and non-ferrous substrates

More information

DURASHIELD 110 &

DURASHIELD 110 & DURASHIELD 110 & 110-61 EFFECTIVE: 3/01/19 I. Scope A. This specification defines application requirements of DuraShield 110/110-61 plural-component, 100% solids, 1:1 volumetric mix ratio polyurethane

More information

DURASHIELD 210 &

DURASHIELD 210 & DURASHIELD 210 & 210-61 I. Scope A. This specification defines application requirements of DuraShield 210 & DuraShield 210-61 plural-component 100% solids, 2:1 volumetric mix ratio polyurethane to steel

More information

APPLICATION GUIDELINES OUTER HULL

APPLICATION GUIDELINES OUTER HULL APPLICATION GUIDELINES OUTER HULL Revision 10 Issue Date: 19 th July 2017 Registered Office The AkzoNobel Building, Wexham Road, Slough, SL2 5DS Page 1 Revision 10 Date 19 th July 2017 CONTENTS Page 1.

More information

DURASHIELD 310 &

DURASHIELD 310 & DURASHIELD 310 & 310-61 I. Scope A. This specification defines application requirements of DuraShield 310 & DuraShield 310-61 plural-component 100% solids, 3:1 volumetric mix ratio polyurethane to concrete,

More information

APPLICATION GUIDELINES EXTERIOR DECK SYSTEM

APPLICATION GUIDELINES EXTERIOR DECK SYSTEM APPLICATION GUIDELINES EXTERIOR DECK SYSTEM Revision 5 Issue Date: 12 th February 216 Registered Office The AkzoNobel Building, Wexham Road, Slough, SL2 5DS Page 1 CONTENTS Page 1. SCOPE AND PURPOSE 3

More information

DURASHIELD 210 &

DURASHIELD 210 & DURASHIELD 210 & 210-61 I. Scope A. This specification defines application requirements of DuraShield 210 & DuraShield 210-61 plural-component 100% solids, 2:1 volumetric mix ratio polyurethane to steel

More information

Polibrid 705E Application Guidelines

Polibrid 705E Application Guidelines International Paint Ltd Protective Coatings Technical Support Polibrid 705E Application Guidelines Prepared by: PC Technical Support International Paint Ltd. www.international-pc.com The information in

More information

APPLICATION GUIDELINES EXTERNAL DECK SYSTEM

APPLICATION GUIDELINES EXTERNAL DECK SYSTEM APPLICATION GUIDELINES EXTERNAL DECK SYSTEM Intershield 71LWT Revision 3 Issue Date: 1 th September 1 Registered in England No. 3 Registered Office The AkzoNobel Building, Wexham Road, Slough, SL DS Page

More information

DURASHIELD JARS APPLICATION SPECIFICATION SHEET FIELD-APPLIED JOINT & REPAIR SYSTEM (JARS) EFFECTIVE: 6/2/15

DURASHIELD JARS APPLICATION SPECIFICATION SHEET FIELD-APPLIED JOINT & REPAIR SYSTEM (JARS) EFFECTIVE: 6/2/15 DURASHIELD 310-61 JARS FIELD-APPLIED JOINT & REPAIR SYSTEM (JARS) I. Scope A. This specification defines application requirements of DuraShield 310-61 Joint and Repair System (JARS) plural-component 100%

More information

Intertherm 751CSA Application Guidelines

Intertherm 751CSA Application Guidelines International Paint Ltd Protective Coatings Technical Support Intertherm 751CSA Application Guidelines Prepared by: PC Technical Support International Paint Ltd. www.international-pc.com The information

More information

Intercure 99NA Application Guidelines

Intercure 99NA Application Guidelines International Paint Ltd Protective Coatings Technical Operations Intercure 99NA Application Guidelines Prepared by: PC Technical Support International Paint Ltd. www.international-pc.com The information

More information

Elastocoat Protective Coatings APPLICATION GUIDE

Elastocoat Protective Coatings APPLICATION GUIDE Elastocoat Protective Coatings DESCRIPTION Elastocoat polyurea and polyurethane coatings are two-component, 100% solids elastomer systems. The coatings systems are designed for processing through plural

More information

APPLICATION GUIDELINES CARGO HOLDS

APPLICATION GUIDELINES CARGO HOLDS APPLICATION GUIDELINES CARGO HOLDS Revision 11 Issue Date: 14 th September 2015 Registered Office The AkzoNobel Building, Wexham Road, Slough, SL2 5DS Page 1 CONTENTS Page 1. SCOPE AND PURPOSE 3 2. PRODUCT

More information

HEMPEL S GALVOSIL 15780

HEMPEL S GALVOSIL 15780 For product description refer to product data sheet Scope: This application instruction covers surface preparation, application equipment and application of. For optimum performance, the following is recommended:

More information

Interline 910 Working Procedures

Interline 910 Working Procedures INTRODUCTION GENERAL REQUIREMENTS FOR TANK LINING NEW CONSTRUCTION TANK CONDITION PRE-CONTRACT Installation of a lining system is the most effective method of protecting steel tanks and vessels from corrosion

More information

APPLICATION GUIDELINES CARGO TANKS

APPLICATION GUIDELINES CARGO TANKS APPLICATION GUIDELINES CARGO TANKS Revision 18 Issue Date: 18 th March 2016 Registered Office The AkzoNobel Building, Wexham Road, Slough, SL2 5DS Page 1 CONTENTS Page 1. SCOPE AND PURPOSE 3 2. PRODUCT

More information

3M Scotchkote Liquid Epoxy Coating 323+

3M Scotchkote Liquid Epoxy Coating 323+ Product Description 3M TM Scotchkote TM Liquid Epoxy Coating 323+ is a two part liquid epoxy coating designed to protect steel pipe and other metal surfaces from corrosion. 3M TM Scotchkote TM Liquid Epoxy

More information

Product Information CHEMGLAZE B 9942 A/B. Coating for Casting Pits. Easy Application Chemglaze B 9942 A/B will bond to damp and wet surfaces.

Product Information CHEMGLAZE B 9942 A/B. Coating for Casting Pits. Easy Application Chemglaze B 9942 A/B will bond to damp and wet surfaces. Product Information Chemical Products Division CHEMGLAZE B 9942 A/B Coating for Casting Pits. FEATURES BENEFITS. Easy Application Chemglaze B 9942 A/B will bond to damp and wet surfaces. Will build to

More information

AMERLOCK 2 AL. PRODUCT DATA SHEET September 12, 2018 (Revision of May 2, 2018) DESCRIPTION. Fast Dry Aluminum Epoxy Mastic Coating

AMERLOCK 2 AL. PRODUCT DATA SHEET September 12, 2018 (Revision of May 2, 2018) DESCRIPTION. Fast Dry Aluminum Epoxy Mastic Coating DESCRIPTION Fast Dry Aluminum Epoxy Mastic Coating PRINCIPAL CHARACTERISTICS Fast drying properties Good drying properties even at low temperatures Low VOC High performance coating for new or old steel

More information

APPLICATION GUIDELINES CARGO TANKS

APPLICATION GUIDELINES CARGO TANKS APPLICATION GUIDELINES CARGO TANKS Revision 16 Issue Date: 9 th February 2018 All products supplied and technical advice or recommendations given are subject to our standard Conditions of Sale. Page 1

More information

SIGMAZINC 160. Revision of March 2007 DESCRIPTION. two component moisture curing inorganic zinc (ethyl) silicate primer PRINCIPAL CHARACTERISTICS

SIGMAZINC 160. Revision of March 2007 DESCRIPTION. two component moisture curing inorganic zinc (ethyl) silicate primer PRINCIPAL CHARACTERISTICS 5 pages Revision of March 2007 DESCRIPTION PRINCIPAL CHARACTERISTICS COLOURS AND GLOSS BASIC DATA AT 20 C Mass density Volume solids VOC (supplied) Recommended dry film thickness Theoretical spreading

More information

POLYURETHANE COATINGS ON STEEL OR DUCTILE IRON PIPE

POLYURETHANE COATINGS ON STEEL OR DUCTILE IRON PIPE Section 02527 PART 1 G E N E R A L 1.01 SECTION INCLUDES A. Two-component polyurethane coating system for use as external coating for steel or ductile iron pipe. 1.02 MEASUREMENT AND PAYMENT A. Unit Prices.

More information

APPLICATION GUIDELINE FOR

APPLICATION GUIDELINE FOR APPLICATION GUIDELINE FOR Company Name M/V SEA-SPEED V 10 X (100 % solids) (Hard film siloxane hybrid foul release coating) SCOPE This specification, together with the Product Data Sheet, defines the minimum

More information

APPLICATION GUIDELINE FOR

APPLICATION GUIDELINE FOR APPLICATION GUIDELINE FOR Company Name M/V SEA-SPEED V 10 X (100 % solids) (Hard film siloxane hybrid foul release coating) SCOPE This specification, together with the Product Data Sheet, defines the minimum

More information

A/D Firefilm III PRODUCT DATA SHEET

A/D Firefilm III PRODUCT DATA SHEET SELECTION & SPECIFICATION DATA Generic Type Description Features Color Finish Primer A single package, water based intumescent coating designed for the fire protection of interior structural steel. A/D

More information

Solventless, two-component, cross-linked epoxy. Epoxies lose gloss, discolour and eventually chalk in sunlight exposure.

Solventless, two-component, cross-linked epoxy. Epoxies lose gloss, discolour and eventually chalk in sunlight exposure. SELECTION & SPECIFICATION DATA Generic Type Description Features Colour Finish Primer Solventless, two-component, cross-linked epoxy. is a solventless epoxy lining for a variety of cargos including water,

More information

Intercrete 4802 Application Guidelines

Intercrete 4802 Application Guidelines 4802_UK Intercrete 4802 Page 1 of 5 Intercrete 4802 Application Guidelines Prepared by: M&PC Technical Operations International Paint Ltd. www.international-pc.com These guidance notes are intended to

More information

APPLICATION GUIDELINES CARGO OIL TANKS

APPLICATION GUIDELINES CARGO OIL TANKS APPLICATION GUIDELINES CARGO OIL TANKS Revision 11 Issue Date: 4 th July 2017 For compliance with IMO PSPC MSC.288(87) for Cargo Oil Tanks of Crude Oil Tankers at Newbuilding only. Registered Office The

More information

Hardener: at least 24 months when stored cool and dry

Hardener: at least 24 months when stored cool and dry DESCRIPTION Two-component, engineered siloxane coating PRINCIPAL CHARACTERISTICS Unique, high gloss, engineered siloxane Virtually HAPs free, ultra-low VOC High durability in challenging environments Tough

More information

NSP SPECIALTY PRODUCTS Technical Data Sheet. NSP 120 High Performance Epoxy Coating

NSP SPECIALTY PRODUCTS Technical Data Sheet. NSP 120 High Performance Epoxy Coating Description: NSP 120, a two component, 100% solids, high build epoxy coating, offers excellent chemical, corrosion and abrasion resistance in severe industrial environments. This extremely versatile product

More information

SIGMAZINC 158. Revision of September 2008 DESCRIPTION. two component moisture curing zinc (ethyl) silicate primer PRINCIPAL CHARACTERISTICS

SIGMAZINC 158. Revision of September 2008 DESCRIPTION. two component moisture curing zinc (ethyl) silicate primer PRINCIPAL CHARACTERISTICS 5 pages Revision of September 2008 DESCRIPTION PRINCIPAL CHARACTERISTICS COLOURS AND GLOSS BASIC DATA AT 20 C Mass density Volume solids VOC (supplied) Recommended dry film thickness Theoretical spreading

More information

TL-225-NS Teflon Filled, Vinyl Ester Coating & Lining

TL-225-NS Teflon Filled, Vinyl Ester Coating & Lining TL-225-NS Teflon Filled, Vinyl Ester Coating & Lining PRODUCT DESCRIPTION TYPICAL USES APPLICATION METHODS Blome TL-225-NS is a Teflon filled, sprayable vinyl ester tank lining system. TL-225-NS offers

More information

TL-280 Sprayable Flake Glass Vinyl Ester Lining System

TL-280 Sprayable Flake Glass Vinyl Ester Lining System TL-280 Sprayable Flake Glass Vinyl Ester Lining System PRODUCT DESCRIPTION TL-280 is a high performance, flake glass vinyl ester lining system, utilizing carefully selected and sized glass flake reinforcement

More information

TL-250 Glass Flake Filled, Vinyl Ester Tank Lining System

TL-250 Glass Flake Filled, Vinyl Ester Tank Lining System TL-250 Glass Flake Filled, Vinyl Ester Tank Lining System PRODUCT DESCRIPTION TL-250 is a Vinyl Ester Tank Lining system based on a glass flake filled, trowel-on base coat and a spray applied glass flake

More information

two component polyamide cured epoxy primer yellow/green - eggshell

two component polyamide cured epoxy primer yellow/green - eggshell 6 pages Revision of December 006 DESCRIPTION PRINCIPAL CHARACTERISTICS COLOURS AND GLOSS BASIC DATA AT 0 C Mass density Volume solids VOC (supplied) Recommended dry film thickness Theoretical spreading

More information

two component high build amine adduct cured phenolic epoxy primer

two component high build amine adduct cured phenolic epoxy primer 5 pages Revision of January 2003 DESCRIPTION two component high build amine adduct cured phenolic epoxy primer PRINCIPAL CHARACTERISTICS primer coat in the Sigma Phenguard tank coating system excellent

More information

Matte Volume Solids 80 ± 2% (ISO 3233:1998) VOC. Overcoating Data 10ºC 25ºC 35ºC Min. 10 hours 4 hours 3 hours Max. 6 months 6 months 6 months

Matte Volume Solids 80 ± 2% (ISO 3233:1998) VOC. Overcoating Data 10ºC 25ºC 35ºC Min. 10 hours 4 hours 3 hours Max. 6 months 6 months 6 months W-POXI ERP 322 PRODUCT DESCRIPTION: Bicomponent epoxy polyamide primer, high solids and anticorrosive pigment based on zinc phosphate, fast dry and good applicability. Excellent adherence on carbon steel

More information

Note: Epoxies will chalk and change color with exterior exposure. Colors are approximately and will tend to change over time.

Note: Epoxies will chalk and change color with exterior exposure. Colors are approximately and will tend to change over time. DESCRIPTION Solvent Free Cycloaliphatic Amine Tank Lining PRINCIPAL CHARACTERISTICS Excellent chemical, solvent, and water immersion resistance Meets NSF/ANSI Standard 61 for potable water when applied

More information

NAVSEA REVIEWED ASTM F-718. Interline 783 Finish, Ultra High Solids Two-Pack Fast Cure Solvent-Free Coating

NAVSEA REVIEWED ASTM F-718. Interline 783 Finish, Ultra High Solids Two-Pack Fast Cure Solvent-Free Coating ASTM F-71 International Paint, LLC Interline 73 Finish, Ultra High Solids Two-Pack Fast Cure Solvent-Free Coating PRODUCT DESIGNATIONS Part A: THA72/THA73/THA7/THA79/THA Series Part B: THA75 MIL-PRF-23236

More information

PERFORMANCE, 100% SOLIDS,

PERFORMANCE, 100% SOLIDS, FEATURES Meets all VOC Requirements Can Saturate 1 Ounce Fiberglass Mat Can be Filled with EA-1 Aggregate and Troweled at 1/4. Can be Seeded with Sand or Aluminum Oxide for Anti- Skid. RECOMMENDED APPLICATIONS

More information

SIGMAZINC 158. PRODUCT DATA SHEET January 7, 2015 (Revision of December 15, 2014) DESCRIPTION

SIGMAZINC 158. PRODUCT DATA SHEET January 7, 2015 (Revision of December 15, 2014) DESCRIPTION DESCRIPTION Two-component, moisture-curing zinc (ethyl) silicate primer PRINCIPAL CHARACTERISTICS Certificate for ASTM A-490 class 'B' for slip coefficient Complies with the compositional requirements

More information

two component polyamide cured epoxy primer yellow/green (redbrown on request) - eggshell

two component polyamide cured epoxy primer yellow/green (redbrown on request) - eggshell 5 pages Revision of September 2009 DESCRIPTION PRINCIPAL CHARACTERISTICS COLOURS AND GLOSS BASIC DATA AT 20 C Mass density Volume solids VOC (supplied) Recommended dry film thickness Theoretical spreading

More information

TECHNICAL INFORMATION. 331 and PENNCOAT 340 LINING INSTALLATION. CES /01 Supersedes 04/00 PAGE 1 of 7 1. SURFACE PREPARATION. 1.

TECHNICAL INFORMATION. 331 and PENNCOAT 340 LINING INSTALLATION. CES /01 Supersedes 04/00 PAGE 1 of 7 1. SURFACE PREPARATION. 1. AN ERGONARMOR COMPANY TECHNICAL INFORMATION 08/01 Supersedes 04/00 PAGE 1 of 7 CORROSION ENGINEERING SPECIFICATION FOR INSTALLATION PENNCOAT 331 and PENNCOAT 340 LINING 1. SURFACE PREPARATION 1.1 Steel:

More information

Property Test/Standard Description

Property Test/Standard Description Other Technical Data Sheet 24100;24120;26200 1 24100 VValidationDate). 1 Product description This is a two component, anticorrosive water borne epoxy coating. It is a versatile, fast drying product containing

More information

Rust-Oleum Industrial Brands Specification

Rust-Oleum Industrial Brands Specification Rust-Oleum Industrial Brands Specification Coating Specification for Rust-Oleum Virtual Solutions Coating Solution 23 A solvent based coating system High Performance 4315 High Heat Aluminum For service

More information

Airblast Tech Tips Surface Preparation in General

Airblast Tech Tips Surface Preparation in General Introduction Proper surface preparation is essential for the success of any protective coating scheme. The importance of removing oil, grease, old coatings and surface contaminants (such as mill scale

More information

Protective Industrial Polymers - USA Manufacturer s Specification February 11, 2015

Protective Industrial Polymers - USA Manufacturer s Specification February 11, 2015 This specification covers InhibiChem SR-GF-L Enhanced Chemical and Solvent-Resistant Glass-Flake Reinforced Steel Tank Lining System. This system consists of a vinyl ester primer, and two troweled coats

More information

PU Anti Graffiti Polyurethane Finish

PU Anti Graffiti Polyurethane Finish PRODUCT DESCRIPTION A two pack, aliphatic anti graffiti acrylic polyurethane INTENDED USES Used as a highly durable finish coat with excellent obliteration properties for exterior of tanks, equipment,

More information

FOR COATING TANK INTERIORS

FOR COATING TANK INTERIORS Effective: December 11, 2013 Rev. 1 SP-9888 TF APPLICATION SPECIFICATION FOR COATING TANK INTERIORS I. GENERAL 1.1 SP-9888 TF is a 100% solids, epoxy manufactured and marketed by Specialty Polymer Coatings,

More information

Application Guidelines

Application Guidelines Page 1 of 18 Application Guidelines Prepared by: International Paint Ltd. www.international-pc.com These guidelines are not relevant to Interchar Water Borne coatings placed on the North American Market

More information

max g/l (approx. 1.9 lb/gal) (aluminum) 31.2 m²/l for 25 µm (1251 ft²/us gal for 1.0 mils)

max g/l (approx. 1.9 lb/gal) (aluminum) 31.2 m²/l for 25 µm (1251 ft²/us gal for 1.0 mils) DESCRIPTION Two-component, engineered polysiloxane clearcoat PRINCIPAL CHARACTERISTICS Universal clear finish compatible with primed steel, clean metals and concrete High durability in challenging environments

More information

Carboguard 890 PRODUCT DATA SHEET SELECTION & SPECIFICATION DATA. Generic Type. Cycloaliphatic Amine Epoxy

Carboguard 890 PRODUCT DATA SHEET SELECTION & SPECIFICATION DATA. Generic Type. Cycloaliphatic Amine Epoxy SELECTION & SPECIFICATION DATA Generic Type Description Features Color Finish Primer Cycloaliphatic Amine Epoxy Highly chemical resistant epoxy mastic coating with exceptionally versatile uses in all industrial

More information

DIMETCOTE 9 / SIGMAZINC 9

DIMETCOTE 9 / SIGMAZINC 9 DESCRIPTION Two-component, moisture-curing zinc (ethyl) silicate coating PRINCIPAL CHARACTERISTICS Anticorrosive primer for structural steel High zinc content resulting in excellent corrosion protection

More information

20-30 mils ( microns) per coat mils ( microns) in two or more coats

20-30 mils ( microns) per coat mils ( microns) in two or more coats SELECTION & SPECIFICATION DATA Generic Type Description Features Color Primer Dry Film Thickness Coverage Rate VOC Values Dry Temp. Resistance Topcoats Density Vinyl ester Plasite 4310 is a vinyl ester

More information

The Application Guide offers product details and recommended practices for the use of the product.

The Application Guide offers product details and recommended practices for the use of the product. Technical Data Sheet Application Guide Approved 345 1,2 345 alkyd ^(ValidationDate) 1 Product description This is a one component styrene modified oxidatively drying alkyd coating. It is heat resistant

More information

1.04 REFERENCES STANDARDS.1 For reference standards tests & results refer to Manufactures Product Data Sheets

1.04 REFERENCES STANDARDS.1 For reference standards tests & results refer to Manufactures Product Data Sheets This specification covers InhibiChem CR-GF-L Chemical-Resistant Glass Flake-Reinforced Steel Tank Lining System. This system consists of a vinyl ester primer, and two troweled coats of glass flake filled

More information

Note: Epoxies will characteristically chalk and fade with exposure to sunlight. Light colors are prone to ambering

Note: Epoxies will characteristically chalk and fade with exposure to sunlight. Light colors are prone to ambering DESCRIPTION Two-component, penetrating epoxy primer sealer PRINCIPAL CHARACTERISTICS Solvent-free Compatible with damp surfaces Wicking action penetrates rusted steel and concrete surfaces Surface tolerant

More information

PPG HI-TEMP PRODUCT DATA SHEET April 16, 2018 (Revision of September 5, 2017) DESCRIPTION

PPG HI-TEMP PRODUCT DATA SHEET April 16, 2018 (Revision of September 5, 2017) DESCRIPTION DESCRIPTION One-component, high-build heat-resistant inert multipolymeric matrix / inorganic ceramic coating PRINCIPAL CHARACTERISTICS Designed to prevent corrosion under insulation (CUI) of carbon steel

More information

SigmaZinc 9 Technical Data Sheet

SigmaZinc 9 Technical Data Sheet SigmaZinc 9 Technical Data Sheet Description PRINCIPAL CHARACTERISTICS COLOURS AND GLOSS two component moisture curing zinc (ethyl) silicate coating anticorrosive primer for structural steel high zinc

More information

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Tunnel Painting

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Tunnel Painting 1993 Specifications CSJ 8075-18-005 SPECIAL SPECIFICATION ITEM 4514 Tunnel Painting 1. Description. This Item shall govern for the painting of the walls and ceiling of a tunnel. The intent is to provide

More information

Technical Data Jotamastic 80 MIO

Technical Data Jotamastic 80 MIO Technical Data Jotamastic 80 MIO Product description Jotamastic 80 MIO is a high solids two-pack micaceous iron oxide pigmented, surface-tolerant epoxy mastic coating which can be applied in low film thickness.

More information

SURFACE PREPARATION FOR SYNTHETIC ROPES

SURFACE PREPARATION FOR SYNTHETIC ROPES Published date: June 30, 2005 SURFACE PREPARATION FOR SYNTHETIC ROPES Rust damaged chock typical of crude tankers. The following recommendations can be applied at the shipyard or during vessel operations.

More information

POLYMER CONCRETE 800 NON-SHRINK VINYL ESTER POLYMER CONCRETE, CONCENTRATED HYDROFLUORIC ACID RESISTANCE

POLYMER CONCRETE 800 NON-SHRINK VINYL ESTER POLYMER CONCRETE, CONCENTRATED HYDROFLUORIC ACID RESISTANCE RECOMMENDED APPLICATIONS Polymer Concrete 800 is a three-component, vinyl ester polymer concrete used for the construction of chemical resistant floors, pads, curbing, trenches and sumps. Polymer Concrete

More information

Technical Data Chemflake Special

Technical Data Chemflake Special Technical Data Chemflake Special Product description A high build glass flake reinforced vinyl ester coating, specially designed for high temperature service. Recommended use Steel in aggressive environments.

More information

Sea~Barrier is the registered trademark of Altex Coatings Limited

Sea~Barrier is the registered trademark of Altex Coatings Limited SELECTION & SPECIFICATION DATA Generic Type Description Carboguard 640 is a high performance, two-component, modified phenalkamine, chemically cured, immersion grade epoxy barrier coating. Carboguard 640

More information

Note: This specification was written for Clarabelle Mill's flotation cells but may have other applications.

Note: This specification was written for Clarabelle Mill's flotation cells but may have other applications. 017/03/3 1/7 1.0 PURPOSE This specification describes the minimum application and performance requirements for a field-applied, elastomer spray coating either polyurethane or polyurea type. Note: This

More information

IMTECH ADHESIVE SYSTEMS

IMTECH ADHESIVE SYSTEMS IMTECH STR-2100 IMTECH STR-2100 is a two-part chloroprene rubber adhesive system, specially formulated to provide outstanding performance characteristics when used in the following applications: Rubber

More information

DIMETCOTE 9 VOC. PRODUCT DATA SHEET July 12, 2016 (Revision of August 7, 2015) DESCRIPTION. Inorganic Zinc Silicate Primer PRINCIPAL CHARACTERISTICS

DIMETCOTE 9 VOC. PRODUCT DATA SHEET July 12, 2016 (Revision of August 7, 2015) DESCRIPTION. Inorganic Zinc Silicate Primer PRINCIPAL CHARACTERISTICS DESCRIPTION Inorganic Zinc Silicate Primer PRINCIPAL CHARACTERISTICS High level of zinc in dry film VOC compliant for

More information

TL-250AR Abrasion Resistant, Glass Flake Filled, Vinyl Ester Tank Lining System

TL-250AR Abrasion Resistant, Glass Flake Filled, Vinyl Ester Tank Lining System TL-250AR Abrasion Resistant, Glass Flake Filled, Vinyl Ester Tank Lining System PRODUCT DESCRIPTION TL-250AR is a Vinyl Ester Tank Lining system based on a glass flake filled, trowel-on base coat and a

More information

Property Test/Standard Description. US EPA method 24 (tested) (CARB(SCM)2007, SCAQMD rule 1113, Hong Kong)

Property Test/Standard Description. US EPA method 24 (tested) (CARB(SCM)2007, SCAQMD rule 1113, Hong Kong) Approved 16561;16840;18880 1,2 18880 epoxy mastic ^(ValidationDate) 1 Product description This is a two component polyamine cured epoxy mastic coating. It is a surface tolerant, abrasion resistance, high

More information

Rust-Oleum Industrial Brands Specification

Rust-Oleum Industrial Brands Specification Rust-Oleum Industrial Brands Specification Coating Specification for Rust-Oleum Virtual Solutions Coating Solution 65 A solvent based coating system High Performance 9100 System 100 VOC DTM Epoxy Mastic

More information

Solventless two-component crosslinked epoxy

Solventless two-component crosslinked epoxy SELECTION & SPECIFICATION DATA Generic Type Description Features Color Finish Primer Dry Film Thickness Solventless two-component crosslinked epoxy Solventless, clear, epoxy lining that can be applied

More information

SP-100 Equipment Wash SP-110 Tool Cleaner SP-120 Internal Storage Lubricant

SP-100 Equipment Wash SP-110 Tool Cleaner SP-120 Internal Storage Lubricant DESCRIPTION: SP-9888 Pipe Lining is based on the latest Zero VOC Novolac Technology. The product cures to a highly cross-linked coating with excellent chemical, solvent and water immersion resistance.

More information

SP-100 Equipment Wash SP-110 Tool Cleaner SP-120 Internal Storage Lubricant

SP-100 Equipment Wash SP-110 Tool Cleaner SP-120 Internal Storage Lubricant DESCRIPTION: SP-9888 Tank Lining is based on the latest Zero VOC Novolac Technology. The product cures to a highly cross-linked coating with excellent chemical, solvent and water immersion resistance.

More information

Refer to Substrates & Surface Preparation.

Refer to Substrates & Surface Preparation. SELECTION & SPECIFICATION DATA Generic Type Description Features Aliphatic Acrylic Polyurethane High gloss finish with exceptional weathering performance characteristics. Used extensively in virtually

More information

(1 g/cm³ = 8.35 lb/us gal; 1 m²/l = 40.7 ft²/us gal) (data for mixed product)

(1 g/cm³ = 8.35 lb/us gal; 1 m²/l = 40.7 ft²/us gal) (data for mixed product) 5 pages Revision of April 2010 Description PRINCIPAL CHARACTERISTICS COLOURS AND GLOSS two component solvent free amine cured phenolic epoxy coating one coat system direct to metal for pipe externals suitable

More information

Technical Data Sheet PaveCoat Product Description

Technical Data Sheet PaveCoat Product Description Technical Data Sheet PaveCoat Product Description PaveCoat Features: Safety Precautions: PaveCoat is manufactured from high performance acrylic resins, is recommended for a wide variety of functional,

More information

PROTECTO-COAT 900/905

PROTECTO-COAT 900/905 FEATURES Excellent Chemical Resistance Conductive Version Available Low Permeability RECOMMENDED APPLICATIONS Structural Steel Water Storage Towers Plating Lines, Exterior Pickling Lines, Exterior Underground

More information

vinyl ester Property Test/Standard Description semi gloss (35-70) Flash point ISO 3679 Method 1 34 C calculated IED (2010/75/EU) (theoretical)

vinyl ester Property Test/Standard Description semi gloss (35-70) Flash point ISO 3679 Method 1 34 C calculated IED (2010/75/EU) (theoretical) Approved 408;21800;21820;21740;21760;21840 1,2 408 ^(ValidationDate) 1 Product description This is a glass flake reinforced coating. It is an ultra high build, extremely chemical resistant and fast curing

More information

SECONDARY CONTAINMENT COATING SPECIFICATION

SECONDARY CONTAINMENT COATING SPECIFICATION SECONDARY CONTAINMENT COATING SPECIFICATION 1.0 GENERAL PROVISIONS Applicable to the following areas: Typical concrete secondary containment structure with occasional exposure acidic and alkaline compounds

More information

PPG HI-TEMP 1000 VS. PRODUCT DATA SHEET December 10, 2014 (Revision of June 30, 2014) DESCRIPTION

PPG HI-TEMP 1000 VS. PRODUCT DATA SHEET December 10, 2014 (Revision of June 30, 2014) DESCRIPTION DESCRIPTION One-component, heat-resistant silicone topcoat for use in an elevated temperature coating system, primarily for application over PPG HI-TEMP 1027 primer PRINCIPAL CHARACTERISTICS Heat-resistant

More information

PPG HI-TEMP 1000 V (AMERCOAT 873) PRODUCT DATA SHEET December 10, 2014 (Revision of June 30, 2014) DESCRIPTION

PPG HI-TEMP 1000 V (AMERCOAT 873) PRODUCT DATA SHEET December 10, 2014 (Revision of June 30, 2014) DESCRIPTION DESCRIPTION One-component, heat-resistant silicone topcoat for use in an elevated temperature coating system PRINCIPAL CHARACTERISTICS Heat-resistant topcoat with highly engineered silicone resin; able

More information

TECHNICAL DATA SHEET

TECHNICAL DATA SHEET Page 1of 5 PRODUCT DESCRIPTION PROPERTIES COLOUR GLOSS LEVEL WEATHERING UT100 2-Pack topcoat is an unmodified acrylic polyurethane designed to maintain maximum appearance for the maximum length of time.

More information

HAMMERITE NO. 1 RUST BEATER PRIMER

HAMMERITE NO. 1 RUST BEATER PRIMER TECHNICAL DATA SHEET Version 2 2018 June THIS ISSUE SUPERSEDES ALL PREVIOUS PUBLICATIONS PRODUCT DESCRIPTION Hammerite No.1 Rust Beater provides a high build finish to heavily pitted areas of rust and

More information

NC Sanding Sealer Clear Clear Nitrocellulose Sanding Sealer

NC Sanding Sealer Clear Clear Nitrocellulose Sanding Sealer PRODUCT DESCRIPTION A one component, high solids, high viscosity modified nitrocellulose, transparent, Sanding/isolation sealer INTENDED USES A clear, high viscosity, fast drying sanding sealer for solid

More information

Property Test/Standard Description. US EPA method 24 (tested) (CARB(SCM)2007, SCAQMD rule 1113, Hong Kong)

Property Test/Standard Description. US EPA method 24 (tested) (CARB(SCM)2007, SCAQMD rule 1113, Hong Kong) Approved 402;2522 1,2 2522 zinc epoxy ^(ValidationDate) 1 Product description This is a two component polyamide cured zinc rich epoxy coating. It is a high zinc dust containing product. It conforms to

More information

Protective: Recommended as an internal lining for offshore, onshore and buried tanks and pipes. Refer to Protective Product Resistance List.

Protective: Recommended as an internal lining for offshore, onshore and buried tanks and pipes. Refer to Protective Product Resistance List. Approved 30382;30383 1,2 30382 ^(ValidationDate) 1 Product description This is a two component polyamine cured coating. It has good chemical resistance. Can be used as primer, mid coat or finish coat in

More information

POLYMER CONCRETE 100 EPOXY POLYMER CONCRETE DILUTE ACIDS RESISTANCE

POLYMER CONCRETE 100 EPOXY POLYMER CONCRETE DILUTE ACIDS RESISTANCE RECOMMENDED APPLICATIONS Polymer Concrete 100 is a three-component, epoxy polymer concrete used for the construction of chemical resistant floors, pads, curbing, trenches and sumps. Polymer Concrete 100

More information

Measured in accordance with ASTM D 2697.

Measured in accordance with ASTM D 2697. SELECTION & SPECIFICATION DATA Generic Type Description Features Color Finish Primer Service Temperature Solvent Based Inorganic Zinc Ultra-low VOC member of the Carbozinc family with extraordinary corrosion

More information

The Application Guide offers product details and recommended practices for the use of the product.

The Application Guide offers product details and recommended practices for the use of the product. Technical Data Sheet Application Guide Approved 345 1,2 345 alkyd ^(ValidationDate) 1 Product description This is a one component styrene modified oxidatively drying alkyd coating. It is heat resistant

More information

Hardener: at least 24 months when stored cool and dry

Hardener: at least 24 months when stored cool and dry DESCRIPTION Two-component, high-build polyamide cured zinc phosphate epoxy primer/coating PRINCIPAL CHARACTERISTICS Good anticorrosive properties under atmospheric conditions Forms durable coating systems

More information

Measured in accordance with ASTM D 2697.

Measured in accordance with ASTM D 2697. SELECTION & SPECIFICATION DATA Generic Type Description Features Color Finish Primer Service Temperature Solvent Based Inorganic Zinc Ultra-low VOC member of the Carbozinc family with extraordinary corrosion

More information

PROTECTO-COAT EPG EPOXY PHENOLIC GLASS FLAKE COATING

PROTECTO-COAT EPG EPOXY PHENOLIC GLASS FLAKE COATING FEATURES Self Priming RECOMMENDED APPLICATIONS PHYSICAL PROPERTIES Volume Solids 65% VOC-Thinned 5% 2.95 lbs./gal. VOC-Un-thinned 2.70 lbs./gal. Interior tank lining Acid areas for maximum protection from

More information

Ganicin 2.8 ZR-E Zinc-Rich Epoxy Primer

Ganicin 2.8 ZR-E Zinc-Rich Epoxy Primer Ganicin 2.8 ZR-E Zinc-Rich Epoxy Primer GENERAL DESCRIPTION A three-package, VOC conforming (2.8 lbs/gal) low HAPS, zinc-rich epoxy primer based on Axalta epoxy amine technology. The resulting organic

More information

Product Data Barmastic EMH-375

Product Data Barmastic EMH-375 Product Data Barmastic EMH-375 PRODUCTS Barmastic EMH-375 EMH-9057 Hardener Thinners 375-Pack A 375-9057, 375-9238 FAST only recommended at Ambient temperatures below 15 C. R202-Normal conditions, R270-Hot

More information