INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS

Size: px
Start display at page:

Download "INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS"

Transcription

1 INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s) FD, DFD, SSFD & KFD Models FD & DFD 150X Models DFDR-XXX, SSDFDR-XXX, FDR-XXX, and SSFDR-XXX Models OFSD-XXX, ODFD-XXX, OFD-XXX and OSSFD-XXX Series Single Side KIT # CURTAIN FIRE DAMPERS DFD/FD/OFD/ODFD/DFDR/FDR

2 Document Number FD, DFD, SSFD, SSDFD, & KFD Models 11/2 and 3 Hour Curtain Fire s Vertical and Horizontal Mount Installation, Operation and Maintenance Instructions FD, DFD, SSFD, & KFD models are intended for installation in accordance with fire damper requirements established by: National Fire Protection Association NFPA Standard 80, 90A, & 101 IBC International Building Code CSFM California State Fire Marshal Fire Listing (# :102) New York City (BSA/MEA listing # M) UL CLASSIFIED (see complete marking on product) UL CLASSIFIED to Canadian safety standards (see complete marking on product) UL Standard 555 (Listing #R13317) SAFETY WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment. WARRANTY Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization. RECEIVING AND HANDLING Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for. s must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100 F (38 C). Installation Supplements Refer to the appropriate Greenheck installation supplements for special requirements: Close Indicator Switch Concrete Floor with Steel Deck Drive Slip Breakaway Connection Fire Resistant Ventilated Assembly Firestop Material Greenheck Test Switch Grille Installation Metal Stud in Shaftwall Quick Connect Breakaway Connections Sealant Supplement Single Side Single 3-Sided - Vertical Mount Extension Support Mullions Note: Refer to Greenheck IOM, Part #461335, for CFSD models to be installed in corridor ceiling applications. These instructions apply to 11/2 and 3 hour rated fire dampers mounted (blades must be horizontal) in masonry, block or stud walls and concrete floors. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL 555. Installation shall comply with the requirements of NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems. UL listing R13317, California State Fire Marshal listings :102, and New York City BSA/MEA listing M apply to these dampers. Note: Fire dampers are manufactured and labelled for either vertical or horizontal installation. The dampers must be installed in accordance with the labelling. Due to continuing research, Greenheck reserves the right to change specifications without notice. This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete. 2

3 Table of Contents Pre-Installation Guidelines...3 Installation Clearances Required Between Fire s and Wall/Floor Openings...3 Length and Wall Thickness to Connections Securing the / Assembly to Wall and Floor Openings Installing Multiple Section Assemblies...7 Recommended Preparation of Openings in Wood and Metal Stud Walls Breakaway Connections Pre-Installation Guidelines The basic intent of a proper installation is to secure the fire damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner. 1) Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the fusible link is in place or has not activated. Never install a fire damper without the proper UL approved fusible link in place. If damper is furnished with fusible link, visually inspect the link to verify its not missing or broken. Replace link as necessary. 2) Lift or handle damper using sleeve or frame. Do not lift damper using blades. 3) has label on outside of sleeve indicating a No Screw area. Do not install screws into this area as screws may interfere with unexposed blade linkage and prevent damper blades from opening and/or closing. 4) has label indicating position of damper and sleeve assembly in the wall. Install accordingly to comply with manufacturer s appropriate UL Classification file number. 5) must be installed into duct or opening square and free of twist or other misalignment. must not be squeezed or stretched into duct or opening. Out of square, racked, twisted or misaligned installations can cause excessive leakage and/or torque requirements to exceed damper/actuator design. 6) must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to: a) Mortar dust b) Drywall dust c) Firesafing materials d) Wall texture e) Paint overspray 7) should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause excessive leakage and/or torque requirements to exceed damper/actuator design. 8) Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles. 9) ACCESS: Suitable access (such that fusible links can be maintained, etc.) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A). 10) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary. 1. CLEARANCES REQUIRED BETWEEN FIRE DAMPER SLEEVES AND WALL/FLOOR OPENINGS Fire damper and sleeve assemblies expand during periods of intense heat. Therefore it is essential that openings in walls or floors be larger than the fire damper and sleeve assembly to allow for this expansion. Minimum clearances required between the outside of fire damper sleeve assemblies and wall/floor openings are: Galvanized steel fire dampers and sleeves: 1/8 in. (3mm) per foot of damper width and 1/8 in. (3mm) per foot height with a minimum clearance of 1/4 in. (6mm) Recommended clearances, for width and/or height dimensions of: 1) 48 in. (1219mm) or less: 1/2 in. (13mm) clearance 2) More than 48 in. (1219mm) and 96 in. (2438mm) or less: 1 in. (25mm) clearance 3) More than 96 in. (2438mm): 1 1/2 in. (38mm) clearance Stainless steel fire dampers and stainless steel or galvanized sleeves: 3/16 in. (4.8mm) per foot of damper width and height with a minimum clearance of 1/4 in. (6mm), of 2 in. (51mm). Recommended clearances, for width and/or height dimensions of: 1) 48 in. (1219mm) or less: 3/4 in. (19mm) clearance 2) More than 48 in. (1219mm) and 96 in. (2438mm) or less: 1 1/2 in. (38mm) clearance 3) More than 96 in. (2438mm): 2 in. (51mm) clearance These are total clearances (ignoring fastener heads) and do not need to be equally spaced around the damper. Refer to Section 4 and Figure 6 for additional installation considerations. 3

4 Example: A 12 in. x 12 in. (305mm x 305mm) damper would require a minimum clearance of 1/4 in. (6mm) on width and 1/4 in. (6mm) on height A 48 in. x 12 in. (1219mm x 305mm) damper would require a minimum clearance of 1/2 in. (13mm) on width and 1/4 in. (6mm) on height. Vertical mount without factory mounted sleeve 1/4 in. minimum total clearance (See Section 1) 2. GAUGES AND LENGTHS OF FIRE DAMPER SLEEVES All fire dampers must be installed in a steel sleeve of the required gauge and length. See Table 1 for required minimum sleeve gauges. sleeve thickness is 10 gauge (3.5mm). inside dimensions must equal damper outside dimensions. s shall extend a of 6 in. (152mm) beyond the wall or floor opening on each side (see Figure 1). When an access door is incorporated as a part of sleeve, the sleeve may extend a of 16 in. (406mm) beyond the wall or floor opening on the access door side. See Section 2 s (See Section 4) Wall or floor See Section 2 (See Sections 2 & 3) Type A Gauge 14 ga. (0.075 in.) - 10 ga. (0.138 in.) [2mm - 3.5mm] Dimension All duct sizes Type of to Connection Permitted Rigid or Breakaway angle leg shall not exceed 7 in. (178mm) Wall or floor 16 ga. (0.060 in.) [1.5mm] 36 in. (914mm) max. width 24 in. (610mm) max. width 24 in. (610mm) diameter Rigid or Breakaway 16 ga. (0.060 in.) [1.5mm] All duct sizes 18 ga. (0.048 in.) [1.2mm] 20 ga. (0.036 in.) [0.9mm] 22 ga. (.030 in.) [0.76mm] 24 ga. (0.024) [0.6mm] 85 in. (2159mm) wide and over 55 in in. wide (1397mm mm) 31 in in. wide (787mm mm) 13 in in. wide (330mm - 762mm) Breakaway only On types R & CR factory furnished duct collar qualifies as breakaway conneciton (See Section 5) Type B Wall or floor 26 ga. (0.018 in.) [0.46mm] 12 in. wide and under (305mm) thickness must not be less than the gauge of the connecting duct. UL Standard 555 requires all ducts to terminate at fire damper sleeves. Table 1: Minimum sleeve thickness for fire dampers. Type C, CO, CR & R When dampers installed vertically, the blade stack must be on the top.. 4 Figure 1

5 Horizontal mount without factory mounted sleeve 1/4mount in. minimum Vertical with factory total clearance mounted sleeve Horizontal mount with factory mounted sleeve 1/4 in. minimum total clearance Wall or Floor 6 in. s (See Section 4) 6 in. See Section 2 K side See Section 2 in.floor Wall6or s (See Section 4) 6 in. See Section 2 K side Wall or Floor (see sections 2 & 3) See Section 2 1/4 in. minimum total clearance Wall or Floor (see sections 2 & 3) s s (See (See Section 3) 3) Section Type A Type AA Type Type A Wall or Floor Wall or Floor Wall or Floor 6 in. s (See Section 4) 6 in. See Section 2 K side Wall or Floor angles (See Section 4) See Section 2 K side (see sections 2 & 3) Wall or Floor See Section 2 (See Sections 2 & 3) See Section 2 Type B s (See Section 3) Type B Type A On types R, CO & CR factory Type furnished duct collar qualifies as breakaway connection. Type B B Wall or Floor Wall or Floor On types R, CO & CR factory furnished duct collar qualifies as breakaway connection. Type B Type B2 Wall or floor Wall or floor Type B2 Type C, CO, CR, & R K side Wall or Floor Type B2 Wall or floor Wall or floor Wall or floor Type B2 On types R, CO & CR factory furnished duct collar qualifies as breakaway Wall or Floor connection. Type C, CO, CR, & R K side On types R & CR factory furnished duct collar qualifies as breakaway connection, see Section 5 Type C, CO, CR, & R On types R & CR factory furnished duct collar qualifies as breakaway connection, see Section 5 When dampers installed horizontally, the ramp must be positioned up as shown in above drawings. Figure 1 Wall or floor Type C, CO, CR, & R Type C, CO, CR, & R When dampers installed vertically, the blade stack must be on the top. 5 When dampers installed horizontally, the ramp must be positioned up as shown in above drawings.

6 3. ATTACHING FIRE DAMPERS TO SLEEVES Fire dampers must be attached to sleeves as shown in Figure 3. All four sides of the damper frame must be attached to the sleeve with one row of attachments on each side of the blade channel. Attachments must be spaced a of 6 in. (152mm) on centers and a of 2 in. (51mm) from corners. A minimum of 4 attachments (2 on each side of the blade channel ) per side (16 per damper) are required. One of the methods of attachment shown below must be used. tack or spot welds #10 sheet metal screws 1 /4 in. (6mm) bolts and nuts 3 /16 in. (4.7mm) steel pop rivets 4. SECURING FIRE DAMPER AND SLEEVES TO WALL AND FLOOR OPENINGS. The fire damper must be installed such that the centerline of the blades are mounted in the plane of the wall or floor. Fire damper and sleeve assemblies must be installed in wall and floor openings using retaining angles on each side of the wall or floor as described below: angles for 11/2 hour rated dampers with a width and height 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). angles for all 3 hour rated dampers and all dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 gauge (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 11/4 in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by a minimum of 1 in. (25mm). (See Figure 4). angle legs may be reversed with leg of retaining angle with annular space of opening so angle and sleeve is flush against barrier. angles must be attached to the sleeve using the procedures and methods described in Section 3. The angles must be attached to all 4 sides of the sleeve with butt joints at each corner. A minimum of two attachments are required on each side, top and bottom. The angles need not be attached to each other at the corners. angles should not be fastened to the wall/ floor material. The angles should only sandwich the wall/floor and allow for damper/sleeve expansion during periods of intense heat. For single retaining angle applications, see Single Side Supplement (#474015). No Connecting or Transfer Opening Openings where duct does not attach on either side will not require a breakaway connection. Transfer openings are typical of a non-ducted installation (see Figure 2). may end flush with the rated wall/floor on both sides Refer to Section 4 for securing retaining angles to sleeves. 5. CONNECTING DUCTS TO FIRE DAMPER SLEEVE Any duct connection other than breakaway is considered rigid. The connections shown on this page are considered breakaway. Factory furnished duct collars on type R and CR fire dampers are also considered breakaway (see Figure 1). 6 Figure 2 Transfer opening or no connecting duct Attachments--Do not place attachments between blade channels Blade Channel 2 in. Max. 6 in. Max. NOTE: Attachments must not enter blade channel or they may cause interference with blade closure. Narrow Line and Ultra Thin dampers do not have flange for attachments and must be welded to sleeve. Attachments can be staggered or evenly spaced. Figure 3: Field attachment of fire dampers to sleeves. 2 in. Max. 6 in. Max. 6 in. Max. 2 in. Max. Figure 4: angle installation. Min. 1 in. overlay* Wall or Floor angle

7 6. MULTIPLE SECTION FIRE DAMPERS When multiple sections are shipped unassembled, installer shall fasten dampers together as described in Section 3. Table 2 shows sizes for multiple section dampers. s that are two or more sections tall must be factory assembled. Model Mounting Single Section Sizes* Note: All dimensions shown are in inches (W x H). * Sizes listed is the damper size not transition size. Table 2: section sizes and overall sizes for multiple section dampers (W x H). Multi-Section Sizes* FD-100, FD-300, FD-310, SSFD-350 Vertical 48 X 48 (1219mm x 1219mm) - FD-150 Vertical or Horizontal 48 X 48 (1219mm x 1219mm) 96 x 48 (2438mm x 1219mm) or 120 x 40 (3048mm x 1016mm) FD-110 Vertical or Horizontal 48 x 48 (1219mm x 1219mm) 96 x 48 (2438mm x 1219mm) 96 X 48 (2438mm x 1219mm) or Vertical 48 X 48 (1219mm x 1219mm) 120 X 40 (3048mm x 1016mm) SSFD-150 Horizontal 36 x 36 (914mm x 914mm) - FD-350 Vertical 48 x 48 (1219mm x 1219mm) - Horizontal 40 x 40 (1016mm x 1016mm) 80 x 40 (2032mm x 1016mm) KFD-150 Vertical or Horizontal 36 x 16 (914mm x 406mm) 96 x 48 (2438mm x 1219mm) or 120 x 40 (3048mm x 1016mm) KFD-110 Vertical or Horizontal 36 x 16 (914mm x 406mm) 96 x 48 (2438mm x 1219mm) SSKFD-150 Vertical 36 x 16 (914mm x 406mm) 96 X 48 (2438mm x 1219mm) or 120 X 40 (3048mm x 1016mm) KFD-350 Vertical 36 x 16 (914mm x 406mm) - Horizontal 36 x 16 (914mm x 406mm) 80 x 40 (2032mm x 1016mm) SSKFD-350 Vertical 36 x 16 (914mm x 406mm) - DFD-150, DFD-110 Vertical 36 x 36 (914mm x 914mm) 72 x 48 (1828mm x 1219mm) or 60 x 60 (1524mm x 1524mm) or 120 x 30 (3048mm x 762mm) Horizontal 24 x 18 (610mm x 457mm) 48 x 36 (1217mm x 914mm) 30 x 30 (762mm x 762mm) - Vertical 36 x 36 (914mm x 914mm) - DFD x 18 (610mm x 457mm) 48 x 36 (1217mm x 914mm) Horizontal 30 x 30 (762mm x 762mm) DFD-310 Vertical 36 x 36 (914mm x 914mm) - Horizontal 30 x 30 (762mm x 762mm) - SSDFD-110, SSDFD-150. SSDFD-350 Vertical 30 x 30 (762mm x 762mm) - DUCT-SLEEVE CONNECTIONS Traditional Breakaway Style Transverse Joints Transverse joints illustrated in Figure 5 have always been approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway connections. The breakaway connections shown to the right can be applied with of (2) #10 sheet metal screws on each side and on the bottom located in the center of the slip pocket and penetrating both sides of the slip pocket. Transverse joints illustrated can be applied as top and bottom joints with Drive Slip - side joints in duct heights up to 20 inches (508mm). Drive Slip Joint Plain S Slip Hemmed S Slip Double S Slip Inside Slip Joint Standing S Standing S (Alt.) Standing S (Alt.) Standing S Standing S (Bar Reinforced) ( Reinforced) Figure 5: Traditional breakaway style transverse joints. 7

8 Round and Oval Breakaway Connections Round ducts connected to factory supplied Type R or CR damper collars may use #10 sheet metal screws as follows: s 22 in. (559mm) wide (or dia.) and smaller may use 3 screws. s larger than 22 in. (559mm) wide (or dia.) may use 5 screws. NOTE: All breakaway connections described may have duct sealant applied, PA2084T duct sealant adhesive manufactured by Precision or DP1010 water base duct sealant by Design Polymetrics, Grey Pookie, or mate PROseal, or CL Ward S Seal in accordance with SMACNA recommendations. Manufactured Flanged System Breakaway Connections Flanged connection systems manufactured by mate, Ward, and Nexus are approved as breakaway connections when installed as illustrated in Figure 6. DUCT-SLEEVE CONNECTIONS cont... (Attach per manufacturer's instructions) 6 in. long 1 /16 in. max. thickness plastic cleats; 12 in. c-c (min. 1 per side) Flanged system angles Neoprene gasket between all angles Fire Do not bolt corners Figure 6: Detail of manufactured flanged system breakaway connections. Proprietary Flange System Breakaway Connections (TDC by Lockformer, TDF by Engle) TDC and TDF systems are approved as breakaway connections when installed as described in the SMACNA Construction Standards. Standard 6 in. (152mm) metal clip may be used with spacing as shown in Figure 7. Threeeighths in. (9.5mm) metal bolts and nuts may be used to fasten together corner pieces. 60 in. 4 Req d. Clip Spacing 48 in. 3 Req d. 6 in. 36 in. 3 Req d. 24 in. 2 Req d. 7 in. Std. Clip Length 9 in. 6 in. 6 in. 5 in. 5 in. 5 in. 5 in. 7 in. Typical TDC/TDF joint 18 in. & Smaller 1 Req d. C L Figure 7: Detail of proprietary flanged system breakaway connections. Recommended Preparation of Openings in Wood and Metal Stud Walls Frame wall openings as shown in Figure 8 & 8A. Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening (see Figure 8 & 8A). Prepare opening between studs and sleeve assembly as shown (see. Figure 9). All construction and fasteners must meet the requirements of the appropriate wall design. (See UL Fire Resistance Directory) Metal Stud Construction Wooden Stud Construction Gypsum Wallboard Gypsum Wallboard Stud or Runner Stud or Runner 1in. (25mm) minimum 1in. (25mm) minimum In metal stud construction, exposed steel surfaces need not be covered with gypsum wallboard. In wood stud construction, gypsum wallboard must cover all wood stud surfaces. Figure 9: Detail of retaining angles and gypsum board application for metal and wooden stud construction. 8

9 Second set of studs are not required on openings 36 in. x 36 in. (914mm x 914mm) or smaller. 24 in. o.c. (metal studs) 24 in. o.c. (metal studs) Ceiling Runner 12 in. 24 in. o.c. 2 in. (51mm) 2 Panhead Screws 2 in. (51mm) 16 in. o.c. (wood studs) 16 in. o.c. (wood studs) Floor Runner Metal stud only Figure 8: Preparation detail for opening in stud wall. Figure 8A Maintenance s shall be maintained, cycled, and tested in intervals as stated in the latest editions of NFPA 90A, 92A, and UL 864 unless local codes require more frequent inspections. s do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired, do not use oil-based lubricants or any other lubricants that attract contaminant s such as dust. Trouble Shooting The following is a cause and correction list for common concerns with the dampers. Symptom Possible Cause Corrective Action does not fully open and/or fully close Frame is 'racked' causing blades to bind on jamb Screws in damper linkage Contaminant's on damper Link separated Heat Replace link Adjust frame such that it is square and plumb Locate screws and remove Clean with a non-oil based solvent (see Maintenance) Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. Phone: (715) Fax: (715) gfcinfo@greenheck.com Website: DFD, FD, SSDFD Series Rev. 17, August 2013 Copyright 2013 Greenheck Fan Corporation 9

10 Document Number FD & DFD 150X MODELS Hour Curtain Fire s Vertical or Horizontal Mount Installation, Operation and Maintenance Instructions FD and DFD 150X Series models are intended for installation in accordance with fire damper requirements established by: National Fire Protection Association NFPA Standard 80, 90A, & 101 IBC International Building Codes CSFM California State Fire Marshal Fire Listing (# :102) New York City (BSA/MEA listing # M) L S TATE S I S T STATE OF CALIFORNIA FIR E MAR S HALL E R V I N G E I C INSTALLATION SUPPLEMENTS Refer to the appropriate Greenheck installation supplements for special requirements: Support Mullions Shaftwall Supplement Drywall Supplement Grille Installation Supplement Drive Slip Supplement Sealant Supplement Extension Supplement Single side s Supplement Note: Refer to Greenheck IOM, Part #461335, for CFSD models to be installed in corridor ceiling applications. Refer to Greenheck IOM, Part # for standard DFD and FD models. UL CLASSIFIED (see complete marking on product) UL CLASSIFIED to Canadian safety standards (see complete marking on product) UL Standard 555 (Listing #R13317) SAFETY WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment. RECEIVING AND HANDLING Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for. s must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100 F. WARRANTY Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization. This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete. Due to continuing research, Greenheck reserves the right to change specifications without notice. 10

11 Table of Contents Pre-Installation Guidelines...11 Installation Breakaway Connections...15 Installation for Steel Stud Connection Option...16 Maintenance...17 Troubleshooting...17 Pre-Installation Guidelines The basic intent of a proper installation is to secure the fire damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner. 1. Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the fusible link is in place or has not separated. If fusible link is not present or has separated, replace link. Never install a fire damper without the proper UL approved fusible link in place. (Fusible link is standard control option. An electric link may have been provided.) 2. Lift or handle damper using sleeve or frame. 3. Install damper accordingly to comply with manufacturer s appropriate UL procedure file number. 4. must be installed into duct or opening square and free of twist or other misalignment. must not be squeezed or stretched into duct or opening. 5. must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include, but are not limited to: a. Mortar dust b. Drywall dust c. Firesafing materials d. Wall texture e. Paint overspray 6. should be sufficiently covered as to prevent overspray of spray-on insulating, wall texturing, or spray painting when performed within 5 feet of the damper. Excessive dirt or foreign material deposits can cause damper to bind and not operate properly. 7. Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles. 8. ACCESS: Suitable access (such that fusible links can be changed) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A). 9. The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary. 11

12 Installation - Failure to follow these instructions will void all warranties. These instructions apply to 11/2 hour rated fire dampers mounted in masonry, block or stud walls and concrete floors. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL 555. Installation shall comply with the requirements of NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems. U.L. listing R13317, California State Fire Marshal listings :102, and New York City BSA/MEA listing M as they apply to these dampers. Note: Fire dampers are manufactured and labelled for either vertical or horizontal installation. The dampers must be installed in accordance with the labelling. 2 in. Max. Min. 1 in. Overlap* Wall or Floor 6 in. Max. 1. NO ADDITIONAL SLEEVES ARE REQUIRED The fire damper extended frame is an approved sleeve and can be properly installed without the need for a supplemental field installed sleeve. frame shall extend a of 6 in. (152mm) beyond the wall or floor opening on each side. 2. CLEARANCES REQUIRED BETWEEN FIRE DAMPER SLEEVES AND WALL/FLOOR OPENINGS Fire damper assemblies expand during periods of intense heat. Therefore, it is essential that openings in walls or floors be larger than the fire damper assembly to allow for this expansion. Minimum clearances required between the outside of fire damper sleeve assemblies and wall/floor openings are: Galvanized steel fire dampers and sleeves: 1/8 in. (3mm) per linear foot of damper width and height with a minimum clearance of 1/4 in. (6mm).Recommended clearances, for width and/or height dimensions of: 1) 48 in. (1219mm) or less: 1/2 in. (13mm) clearance 2) More than 48 in. (1219mm) and 96 in. (2438mm) or less: 1 in. (25mm) clearance 3) More than 96 in. (2438mm): 11/2 in. (38mm) clearance These are total clearances (ignoring fastener heads) and do not need to be equally spaced around the damper. Refer to Section 3 and Figure 1 for additional installation considerations. Example: A 12 in. x 12 in. (305mm x 305mm) damper would require a minimum clearance of 1/4 in. (6mm). A 48 in. x 12 in. (1219mm x 305mm) damper would require a minimum clearance of 1/2 in. (13mm) on width and 1/4 in. (6mm) on height. 6 in. Max. 2 in. Max. *only applicable for damper sizes above 36 in. x 36 in. Figure 1: angle installation. 3. SECURING THE FIRE DAMPER TO WALL AND FLOOR OPENINGS Fire damper assemblies must be installed in wall and floor openings using retaining angles on each side of the wall or floor as described below: angles for 11/2 hour rated dampers with a width and height 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). angles for all 3 hour rated dampers and all dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 gauge (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 11/4 in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by a minimum of 1 in. (25mm). angles must be attached to the damper using one or more of the following methods of attachment: tack or spot welds #10 sheetmetal screws 1/4 in. (6mm) bolts and nuts 3/16 in. (4.7mm) steel pop rivets Attachments must be spaced a of 6 in. (152mm) on center and a of 2 in. (51mm) from corners. The angles must be attached to all 4 sides of the sleeve with butt joints at each corner. A minimum of two attachments are required on each side, top and bottom. The angles need not be attached to each other at the corners. angles should not be fastened to the wall/ floor material. The angles should only sandwich the wall/floor and allow for damper expansion during periods of intense heat. 12

13 4. CONNECTING DUCTS TO THE FIRE DAMPER All duct connections to FD & DFD 150X series extended frame dampers must be breakaway type connections. All connections shown 1/4 are in. minimum considered breakaway. Factory furnished duct collars on types R & CR fire total clearance dampers are also considered breakaway(see Figure 2 & 3). 1/4 in. minimum total clearance 1/4 in. minimum total clearance s (See Section 4) Wall or Floor See Section 2 6 in. 6 in. 6 in. Wall or Floor 6 in. Wall or Floor 6 in. 6 in. K side Wall or Floor (see sections 2 & 3) See Section 2 s s (See Section s 3) (See Section 3) (See Section 3) Type A Type A Wall Wall or Floor or Floor Wall or Floor Type A s (See Section 4) See Section 2 K side Wall or Floor See Section 2 (see sections 2 & 3) Type B Wall or Floor On types R & CR factory furnished duct collar qualifies as breakaway connection. On types R & CR factory On types furnished R & duct CR factory collar furnished qualifies duct as breakaway collar qualifies connection. as breakaway connection. Type B Type B Wall or Floor Wall or Floor Type B K side Wall or floor Type C, CO, CR, & R Type C, CO, CR, & R On types R & CR factory furnished duct collar qualifies as breakaway connection, see Section 5 Type C, CO, CR, & R Figure 2: Vertical Mount Type A, Type B, and Type C, CO, CR, R damper installation diagrams. Type C, CO, CR, & R Figure 3: Horizontal Mount Type A, Type B, and Type C, CO, CR, R damper installation diagrams. When dampers installed horizontally, the ramp must be positioned up as shown in above drawings. Table 1 Model Sizes for Single Section s* in. (mm) FD-150X (H or V) 48 x 48 (1219 x 1219) DFD-150X (V) 36 x 36 (914 x 914) DFD-150X (H) 30 x 30 (762 x 762) Note: V = Vertical mount & H = Horizontal * Sizes are based on damper with no transitions. 13

14 Recommended Preparation of Openings in Wood and Metal Stud Walls Frame wall openings as shown in Figure 4 and 4A. Gypsum wall board must be fastened 12 in. on center to all stud and runner flanges surrounding opening (see Figure 4 and 4A). Prepare opening between studs and sleeve assembly as shown below (see Figure 5). All construction and fasteners must meet then requirements of the appropriate wall design. (See UL Fire Resistance Directory) 24 in. o.c. (metal studs) 24 in. o.c. (metal studs) Ceiling Runner 12 in. 24 in. o.c. 2 Panhead Screws 2 in. (51mm) 2 in. (51mm) 16 in. o.c. (wood studs) 16 in. o.c. (wood studs) Floor Runner Figure 4: Preparation detail for opening in stud wall. Second set of studs are not required on openings 36 in. x 36 in. (914mm x 914mm) or smaller. Figure 4A Metal Stud Construction Metal stud only Wooden Stud Construction Gypsum Wallboard Gypsum Wa llboard Stud or Runner Stud or Runner Angl e 1 in. Min. 1 in. Min. In metal stud construction, exposed steel surfaces need not be covered with gypsum wallboard. In wood stud construction, gypsum wallboard must cover all wood stud surfaces. Figure 5: Detail of retaining angles and gypsum board application for metal and wooden stud construction. 14

15 - Connections Traditional Breakaway Style Transverse Joints Transverse joints illustrated in Figure 6 have always been approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway connections. The breakaway connections shown to the right can be applied with of (2) #10 sheet metal screws on each side and on the bottom located in the center of the slip pocket and penetrating both sides of the slip pocket. Transverse joints illustrated can be applied as top and bottom joints with Drive Slip - side Drive Slip Joint joints in duct heights up to 20 in. (508mm). Round and Oval Breakaway Connections Round or flat oval ducts connected to factory supplied Type R, CR, or CO damper collars may use #10 sheet metal screws as follows: s 22 in. (559mm) wide (or dia.) and smaller may use 3 screws. s larger than 22 in. (559mm) wide (or dia.) may use 5 screws. Plain S Slip Hemmed S Slip Double S Slip Inside Slip Joint Standing S Standing S (Alt.) Standing S (Alt.) Standing S Standing S (Bar Reinforced) ( Reinforced) Figure 6: Traditional breakaway style transverse joints. NOTE: All breakaway connections described may have duct sealant, PA2084T duct sealant adhesive manufactured by Precision, DP1010 water base duct sealant by Design Polymetrics, Grey Pookie, mate PROseal, or CL Ward S Seal applied in accordance with SMACNA recommendations. Proprietary Flange System Breakaway Connections (mate, Ward, Nexus) Flanged connection systems manufactured by mate, Ward, and Nexus are approved as breakaway connections when installed as illustrated in Figure 7. 6 in. long 1/16 in. max. thickness plastic cleats; 12 in. c-c (min. 1 per side) Flanged system angles Fire (TDC by Lockformer, TDF by Engle) TDC and TDF systems are approved as breakaway connections when installed as described in the SMACNA Construction Standards. Standard 6 in. metal clips may be used with spacing (see Figure 8). Three-eighth in. metal bolts and nuts may be used to fasten together corner pieces (see Figure 9). (Attach per manufacturer s instructions) Figure 7: Neoprene gasket between all angles Detail of manufactured flanged system breakaway connections. Do not bolt corners 60 in. 4 Req d. Clip Spacing 6 in. 7 in. Std. Clip Length 9 in. 6 in. 6 in. 7 in. End Flange Corner Piece Typical TDC/TDF joint 48 in. 3 Req d. 36 in. 3 Req d. 24 in. 2 Req d. 18 in. & Smaller 1 Req d. 5 in. 5 in. 5 in. CL 5 in. 3/8 in. bolt (optional) Figure 8: Detail of proprietary flanged system breakaway connections. Figure 9: Detail of bolted corner. 15

16 Installation for Steel Stud Connection (SSC) Option These instructions apply to 11/2 hour rated fire dampers mounted in steel stud walls. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL555. Installation shall comply with the requirements of NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems. U.L. listings R13317 and R13743, California State Fire Marshal listings :102 and :101, and New York City BSA/ MEA listing M as they apply to these dampers. 1. NO ADDITIONAL SLEEVES OR ANGLES ARE REQUIRED The fire damper extended frame is an approved sleeve and the Steel Stud Connection (SSC) Option allows fastening of the fire damper sleeve directly to the wall's steel stud framing. frame shall extend a of 6 in. (152mm) beyond the wall opening on either side. size fire damper that may be installed using this SSC option is 36 in. W x 36 in. H (914mm x 914mm). 2. INSTALLATION Fire damper with SSC option must be in place before the wall is constructed or it can be installed as the wall is being constructed. Wall opening is framed around the fire damper before sheet rock or other wall board material is applied to the steel studs. This installation provides appropriate protection for duct penetrations in fire resistant wall construction using steel studs with a fire resistance rating less than 3 hours. The following wall design numbers (as detailed in the UL Fire Resistance Directory) are appropriate for fire damper installations using this SSC option: 1 Hour Design: U405, U406, U422, U434, U448, U451, U456, U457, U465, U468, U469, U485, U494 11/2 Hour Design: U449, U452, U470, U471 2 Hour Design: U403, U411, U412, U421, U425, U428, U429, U443, U453, U474, U475, U477, U484, U491, U FRAMING OF WALL OPENING Form a wall opening 1/8 in. (3mm) to 1/4 in. (6mm) larger than the OD of the fire damper's extended frame (sleeve) using the same metal studs and techniques required by the wall design per the UL Fire Resistance Directory. Open side of the steel stud channels shall face the fire damper and encompass the damper's retaining bar. 4. APPLY WALLBOARD AFTER DAMPER INSTALLATION After damper is installed, wallboard shall be applied to steel stud framework in the manner required by the wall design per the UL Fire Resistance Directory listing. Around the damper perimeter use a minimum of 2 connections per side, spaced 12 in. (305mm) and located a of 2 in. (51mm) from each corner. No additional retaining angles are required to complete the installation. 5. CONNECTING DUCTS TO THE FIRE DAMPER All duct connections to FD & DFD 150X series extended frame dampers must be breakaway type connections. All connections shown on page 5 & 6 are considered breakaway. Factory furnished duct collars on types R, CR, & CO fire dampers are also considered breakaway. Item Description 1 FD150X fire damper with SSC option 2 Steel stud wall (see UL Fire Resistance Directory for specific details) 3 Steel stud frame around opening in wall 4 connection (see section 6) 5 Wallboard (see UL Fire Resistance Directory for specific details) 6 Fasteners (see UL Fire Resistance Directory and Section 5) Bar 1 4 Top Cross-section View Side Cross-Section View of in Wall

17 Maintenance s shall be maintained, cycled, and tested in intervals as stated in the latest editions of NFPA 90A, 92A, and UL 864 unless local codes require more frequent inspections. s do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired, do not use oil-based lubricants or any other lubricants that attract contaminant s such as dust. Trouble Shooting The following is a cause and correction list for common concerns with the dampers. Symptom Possible Cause Corrective Action does not fully open and/or fully close Frame is 'racked' causing blades to bind on jamb Screws in damper linkage Contaminant's on damper Link separated Heat Replace link Adjust frame such that it is square and plumb Locate screws and remove Clean with a non-oil based solvent (see Maintenance) Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. Phone: (715) Fax: (715) gfcinfo@greenheck.com Website: DFD & FD 150X Series Rev. 15, August 2013 Copyright 2013 Greenheck Fan Corporation 17

18 DOCUMENT NUMBER DFDR-XXX, SEDFDR-XXX, SSDFDR-XXX, FDR-XXX, and SSFDR-XXX MODELS Hour Round Fire s Vertical and Horizontal Mount Installation, Operation and Maintenance Instructions DFDR-XXX, SSDFDR-XXX, FDR-XXX, and SSFDR- XXX Model s are intended for installation in accordance with fire damper requirements established by: National Fire Protection Association NFPA Standards 80, 90A, 101 and 105 IBC International Building Codes New York City (MEA listing # M) California State Fire Marshal (CSFM) Fire Listing ( :0112) UL CLASSIFIED (see complete marking on product) UL CLASSIFIED to Canadian safety standards (see complete marking on product) UL Standard 555 (Classification #R13317) RECEIVING AND HANDLING Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for. s must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100 F (37 C). INSTALLATION SUPPLEMENTS Refer to the appropriate Greenheck installation supplements for special requirements: Steel Deck Supplement SAFETY WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment. WARRANTY Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization. Due to continuing research, Greenheck reserves the right to change specifications without notice. This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete. 18

19 Table of Contents Pre-Installation Guidelines...19 Installation Maintenance...19 Troubleshooting...19 Pre-Installation Guidelines The basic intent of a proper installation is to secure the fire damper in the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner. 1) Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the fusible link is in place or has not separated. s will be supplied with a temperature responsive fusible link device. If fusible link is not present or has separated, replace link. Never install a fire damper without the proper UL approved fusible link in place. 2) Lift or handle damper using the frame. Do not lift damper using blades. 3) Do not install screws into the main body area of the damper frame as screws may interfere with and prevent damper blade from opening and/or closing. 4) must be installed into duct or opening free of distortion or other misalignment. must not be squeezed or stretched into duct or opening. Out of round, racked, twisted or misaligned installations can cause torque requirements to exceed damper design. 5) must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to: 1) Mortar dust 2) Drywall dust 3) Firesafing materials 4) Wall texture and 5) Paint overspray. 6) should be sufficiently covered to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause torque requirements to exceed damper design. 7) Caulking is not allowed between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining plates and a field-applied sealant may be required for the damper sleeve and transitions to meet certain duct leakage standards. 8) ACCESS: Suitable access (such that fusible links can be maintained) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A). 9) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary. Installation - Failure to follow these instructions will void all warranties. These instructions apply to 1 1/2 hour rated fire dampers mounted (blades must be horizontal) in: 1) masonry, block or stud walls and 2) concrete floors or ceilings. Specific requirements in these instructions are mandatory. s must be installed in accordance with these instructions to meet the requirements of UL 555. The installation of the damper and all duct connections to the damper sleeve shall conform to the latest editions of NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems, and the SMACNA Fire, Smoke and Radiation Installation Guide, and UL Classifications R

20 Installation - Continued 1. CLEARANCES REQUIRED BETWEEN FIRE DAMPER SLEEVES AND WALL/FLOOR OPENINGS Fire damper assemblies expand during periods of intense heat. Therefore, it is essential that openings in walls or floors be larger than the fire damper assembly to allow for this expansion. The wall/floor opening must be a minimum of 7 /8 in. (22mm) larger than the outside diameter of the damper. Refer to Section 4 for additional installation considerations. RETAINER PLATE (OPTIONAL) DUCT CONNECTION AREA 2 in. AIRFLOW CLEARANCE FOR EXPANSION RETAINER PLATE BLADE LATCH ACCESS DOOR TO BE ON SAME SIDE AS BLADE LATCH 2 in. DUCT CONNECTION AREA and can be installed without the need for additional field installed sleeves. Gauge of factory furnished sleeve determines the type of duct to sleeve connections required (see table below). Any duct connection other than the breakaway connections are considered rigid. Gauge (mm) Dimension Inches (mm) Type of to Connection Permitted 10 ga. (3.5) 14 ga. (2) 16 ga. (1.5) 20 ga. (1mm) 24 (610) 24 (610) Rigid or Breakaway Breakaway only thickness must not be less than the gauge of the connecting duct. UL Standard 555 requires all ducts to terminate at fire damper sleeves. Fig. 1 6 in. max. TW SLEEVE LENGTH DO NOT PLACE RETAINER PLATE IN THIS GROOVE 6 in. max. 2. SLEEVE LENGTH AND WALL/FLOOR THICKNESS Insert the damper assembly into the prepared opening, to appropriate depth (see Fig. 1). Recommended and minimum insertion depth can be exceeded as long as the C L of the damper blade remains within the plane of the wall/ floor. IMPORTANT SAFETY DANGER! To avoid causing death or serious bodily harm to building occupants, do not insert screws into the damper frame unless used for duct connection within 2 in. (51mm) of the frame end. The sleeve may extend a of 6 in. (152mm) beyond both sides of the wall or floor. Recommended standard sleeve lengths for various wall/floor thicknesses are: Wall/Floor Thickness Dimension (T w ) Inches (mm) Length Dimension (L) Inches (mm) Up to 61/2 (165) 13 5/8 (346) 61/2-81/2 ( ) 15 5/8 (397) 81/2-101/2 ( ) 17 5/8 (448) 3. DUCT TO SLEEVE CONNECTIONS s are supplied with sleeves from the factory SECURING THE DAMPER/SLEEVE ASSEMBLY TO WALL AND FLOOR OPENINGS assemblies must be installed in wall/ floor openings using a single retaining plate on either side of the wall/floor or by using a retaining plate on both sides of the wall/floor. The use of a second retaining plate is allowed, but is not necessary. A single retaining plate is provided with the dampers. A second retaining plate can be ordered as an option. The retaining plate(s) will open up for easy installation when the clamping screw is loosened. If necessary, remove the clamping screw and nut (see Fig. 2). (IMPORTANT: The clamping mechanism should face away from the wall/floor). Retainer plate(s) are designed to mount flush to the wall/floor and hold the damper in the wall/floor opening. Place the damper and attached retainer plate into the wall/floor opening. If a second retaining plate is being used, secure it on the opposite side of the wall/floor DO NOT POSITION RETAINER PLATE(S) IN FRAME GROOVE Verify position, blade orientation, and actuator clearance then tighten the retainer plate clamping screws. The retainer plate(s) must overlap the wall/floor opening a minimum of 1 inch (25mm). Secure the retainer plate(s) to the wall using appropriate fasteners (minimum #8 sheet metal screws) at the four corners of each retainer plate when two retainer plates are used and also within 3/4 in. (19mm) of the center of each plate when one retainer plate is used.

21 Opening + 2 in. Min. 24 in. o.c. (metal studs) 24 in. o.c. (metal studs) Ceiling Runner 12 in. Wall/Floor Opening = Nominal Size + 7/8 in. Min. Clamping Screw 1.00 in. Typ. Fasteners 24 in. o.c. Nut 2 Panhead Screws 2 in. 2 in. 16 in. o.c. (wood studs) 16 in. o.c. (wood studs) Plate Assembly Fig. 4 Floor Runner Fig. 2 Clamping Screw 5. Recommended Preparation of Openings in Wood and Metal Stud Walls Frame wall openings as shown below. (see Fig. 4 & 4A). Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening. (see Fig. 4 & 4A). Prepare opening between studs and sleeve assembly as shown below (see Fig. 3). All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance Directory) and/or local codes. Second set of studs are not required on openings 36 in. x 36 in. (914mm x 914mm) or smaller. DAMPER FRAME METAL STUD 1.00 MIN Fig. 4A Metal stud only Fig. 3 DO NOT PLACE RETAINER PLATE IN THIS GROOVE. DAMPER FRAME WOOD STUD DO NOT PLACE RETAINER PLATE IN THIS GROOVE MIN 6. Round Connections Round duct connections shall be attached with #8 sheet metal screws as follows: s 22 in. (559mm) dia. and smaller shall have three screws. s larger than 22 in. (559mm) dia. and up to including 24 in. dia. shall have five screws. NOTE: All breakaway connections described may have duct sealant, PA2084T Sealant Adhesive manufactured by Precision or DP1010 Water Base Sealant manufactured by Design Polymetrics, Grey Pookie, mate PROseal, or CL Ward S Seal applied in accordance with SMACNA recommendations. 21

22 DFDR-XXX Blade Orientation Axle Off Horizontal () 30 Axle 30 Off Horizontal () Axle Normal Maintenance s do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, do not use oilbased lubricants or any other lubricants that attract contaminants such as dust. s and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with: The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA and local codes. Actuator manufacturer recommendations. Troubleshooting The following is a possible cause and correction list for common concerns with the dampers. Symptom Possible Cause Corrective Action Frame is out of round causing blades Adjust frame such that it is round to interfere with frame does not fully open and/or fully close Screws interfere with blade Locate screws and remove Contaminants on damper Clean with a non-oil based solvent (see Maintenance) Link separated Heat Replace link Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. Phone: (715) Fax: (715) gfcinfo@greenheck.com Website: DFDR, FDR Series Rev. 9, August 2013 Copyright 2013 Greenheck Fan Corporation 22

23 Document Number OFSD-XXX, ODFD-XXX, OFD-XXX, and OSSFD-XXX Series 11/2 Hour Combination Fire Smoke or Curtain Fire s Out of Wall or Out of Floor Vertical or Horizontal Mount Installation, Operation, and Maintenance Instructions OFSD-XXX, ODFD-XXX, OFD-XXX, and OSSFD-XXX series dampers are intended for installation in accordance with combination fire smoke dampers requirements established by: NFPA National Fire Protection Association NFPA Standards 80, 90A, 92A, 92B, 101, & 105 IBC International Building Codes New York City (MEA listing # M) California State Fire Marshal Listing # :103 & :104 UL Classified (see complete marking on product) UL Classified to Canadian safety standards (see complete marking on product) UL Standard 555 & 555S (Classification R13317) Receiving and Handling Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for. s must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100 F (38 C). Warranty Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the purchase date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization. Electrical Guidelines All wiring shall be done in accordance with the National Electrical Code ANSI/NFPA-70 latest edition, any local codes that may apply, and wiring diagrams developed in compliance with the job or project design and specifications. Safety Warning: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment. Safety Caution! Electrical input may be needed for this equipment. This work should be performed by a qualified electrician. Verify power before wiring actuator. Greenheck is not responsible for any damage to, or failure of the unit caused by incorrect field wiring. To avoid causing death or serious bodily harm to building occupants, follow all instructions carefully. s must close completely to preserve the integrity of the fire smoke separation. Due to continuing research, Greenheck reserves the right to change specifications without notice. This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete. 23

24 Table of Contents Pre-Installation Guidelines Installation Clearances Requirements to Connections Securing the / Assembly to Wall and Floor Openings Actuator Connections Recommended Preparation of Openings in Wood and Metal Stud Walls Breakaway Connections Maintenance...34 Troubleshooting...34 Pre-Installation Guidelines The basic intent of a proper installation is to secure the fire or fire smoke damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire or fire smoke damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner. 1) Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the Reusable Resettable Link (RRL) is in place or has not activated. Never install a fire damper without the proper UL approved RRL in place. (RRL is standard control option. These electric links have a button for resetting.) If damper is furnished with fusible link, visually inspect the link to verify its not missing or broken. Replace link as necessary. 2) Lift or handle damper using sleeve or frame. Do not lift damper using blades or actuators. 3) has label on outside of sleeve indicating a No Screw area. Do not install screws into this area as screws may interfere with unexposed blade linkage and prevent damper blades from opening and/or closing. 4) has label indicating position of damper and sleeve assembly in the wall. Install accordingly to comply with manufacturer s appropriate UL Classification file number. 5) must be installed into duct or opening square and free of twist or other misalignment. must not be squeezed or stretched into duct or opening. Out of square, racked, twisted or misaligned installations can cause excessive leakage and/or torque requirements to exceed damper/actuator design. 6) and actuator must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to: a) Mortar dust b) Drywall dust c) Firesafing materials d) Wall texture e) Paint overspray 7) should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause excessive leakage and/or torque requirements to exceed damper/actuator design. 8) Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles. 9) ACCESS: Suitable access (such that RRL s and actuators can be maintained, etc.) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A). 10) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary. Installation - Failure to follow these instructions will void all warranties. These instructions apply to 11/2 hour rated combination fire smoke dampers and curtain fire dampers mounted in masonry, block, wood or metal stud walls, or concrete floors. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL555. Installation shall comply with the requirements of NFPA 90A (Installation of Air Conditioning and Ventilating Systems) and UL listing R

25 1. DAMPER IS INSTALLED OUTSIDE OF WALL PLANE OFSD-XXX Figure 1 shows two approved installations for combination fire smoke dampers: 1) Through the grille access and 2) installation in continuing duct. To provide through the grille access to the damper actuator, the damper is located toward the back of the sleeve and the actuator is installed between the damper and grille. Actuator and damper can be accessed and serviced by removing the grille. To provide access to the damper actuator for continuing ductwork, refer to the requirements of NFPA 90A. 7 1/2 in. Max. Masonry floor Continues Horizontal or Vertical Mount Steel stud Gypsum Wallboard Stud or Runner In wood stud construction, gypsum wallboard must cover all wood stud surfaces. Wooden Stud Construction Flange #10 2 1/2 in. long sheet metal screws spaced 6 in. on center and of 2 in. from the corners (minimum of 2 screws per side) through the sleeve into the header, sill and jamb framing members. Screw into rear portion of the studs so as to avoid space conflicts with the grille assembly. (Refer to section 4) #10 sheet metal screws, 2 1/2 inches long, spaced 6 in. on center and of 2 in. from corners (minimum of 2 screws per side). Screw into rear portion of the studs so as to avoid space conflicts with the grille assembly. Grille (Supplied by others) Grille (Supplied by others) 7 1/2 in. Max. Terminates Metal Stud 6 1/2 in. Max. Fire damper or combination fire smoke damper Terminates Wood Stud Note: Both installations for vertical mount. Figure 1: Installation configurations for Out of Wall combination fire smoke dampers. ODFD-XXX, OFD-XXX, and OSSFD-XXX: Figure 2 shows installations that are also approved for curtain fire dampers. For access to inspect the damper and fusible link, refer to the requirements of NFPA 90A. 2. CLEARANCE REQUIREMENTS There is no minimum clearance requirement between the wall/floor opening and the sleeve exterior (with thermal blanket attached). However, to facilitate installation, clearances between the wall/floor opening and the damper sleeve are recommended. although there is no allowable clearance, the minimum overlap requirements between the wall/floor and the flange/retaining angle must be met. On grill mount installations the flange must overlap the wall/floor by 1 2 in. (13mm). On continuous duct installations, the retaining angles must overlap the wall/floor by 1 in. (25mm). Because no clearances are required between the wall/floor opening and the sleeve, dampers may not be installed in the plane of the wall using this installation method. 25

26 Figure 2 Masonry Wall Wood Stud Masonry Wall Wood Stud 7 1/2 in. (191mm) max. Steel Stud Flange Flange Flange Steel Stud Alternate Location Factory Supplied Thermal Blanket Type A- Vertical Mount, Terminates Single Method Type A- Vertical Mount, Terminates Flange Method max. Flange Masonry Floor Masonry or Concrete Floor max. Type A - Horizontal Mount Above Floor/Wall, Terminates Single Method Masonry Floor Type A - Horizontal Mount Below Floor/Wall, Terminates Flange Method max. 26 Type A - Horizontal Mount Below Floor/Wall, Terminates Single Method

27 Figure 2 cont... Masonry or Concrete Wall Wood Stud Masonry Wall Wood Stud max. Metal Stud Alternate Location Type A- Vertical Mount, Thru with Two s Type A- Vertical Mount, Thru with Single max. Masonry or Concrete Floor Masonry Floor Type A - Horizontal Mount Above Floor/Wall, Thru with Two s Type A - Horizontal Mount Above Floor/Wall, Thru with Single Masonry or Concrete Floor Masonry Floor max. Type A - Horizontal Mount Below Floor/Wall, Thru with Two s 27 Type A - Horizontal Mount Below Floor/Wall, Thru with Single

28 Figure 2 cont /2 in.(191mm) Wood Stud Metal Stud Wood Stud Masonry or Concrete Steel Stud Flange Type B2- Vertical Mount, Thru with Two s Masonry or Concrete Type B2- Vertical Mount, Terminates Flange Method Flange Masonry or Concrete Masonry or Concrete Type B2 - Horizontal Mount Above Floor/Wall, Thru with Two s Masonry or Concrete Type B2 - Horizontal Mount Below Floor/Wall, Terminates Flange Method 28 Type B2 - Horizontal Mount Below Floor/Wall, Thru with Two s

29 Figure 2 cont... Masonry Metal Stud Wood Stud Masonry Alternate Location Alternate Location Type B2- Vertical Mount, Terminates Single Method Type B2- Vertical Mount, Thru with Single Masonry Masonry Type B2 - Horizontal Mount Above Floor/Wall, Terminates Single Method Type B2 - Horizontal Mount Above Floor/Wall, Thru with Single Masonry Masonry Type B2 - Horizontal Mount Below Floor/Wall, Terminates Single Method 29 Type B2 - Horizontal Mount Below Floor/Wall, Thru with Single

30 Figure 2 cont... Wood Stud Metal Stud Wood Stud Flange Masonry Masonry Metal Stud Type C2- Vertical Mount, Terminates Flange Method Type C2- Vertical Mount, Thru with Two s Masonry Masonry Flange Type C2 - Horizontal Mount Above Floor/ Wall, Terminates Flange Method Type C2 - Horizontal Mount Above Floor/Wall, Thru with Two s Flange Masonry Masonry Type C2 - Horizontal Mount Below Floor/Wall, Terminates Flange Method Type C2 - Horizontal Mount Below Floor/Wall, Thru with Two s 30

31 Figure 2 cont... Metal Stud Wood Stud Masonry 3. DUCT TO SLEEVE CONNECTIONS s are supplied with actuators (on applicable models) and sleeves from the factory and can be installed without the need for additional field installed sleeves. gauges of (.9mm - 2mm) are to be used. UL Standard 555 requires all ducts to terminate at fire damper sleeves. thickness must not be less than the gauge of the connecting duct. to sleeve breakaway connections must be of the type described on page 33. Factory furnished round duct collars on type R and CR dampers are also considered to be breakaway connections and may be used. Alternate Location Type C2- Vertical Mount, Thru with Single Flange (installed around entire outside surface of sleeve) Wall Masonry Figure 3: d damper with Thermal Blanket (duct termination). Type C2 - Horizontal Mount Above Floor/Wall, Thru with Single Masonry Type C2 - Horizontal Mount Below Floor/Wall, Thru with Single 4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO WALL OPENINGS. /sleeve assemblies must be installed in wall openings using flanges and sheet metal screws as illustrated and described below. Flange on front (grille end) of sleeve must be a minimum of 16 gauge (1.5mm) steel and have a 5 8 in. (16mm) minimum flange leg (refer to Figure 3). Using #10 (19mm) sheet metal screws, screw from inside of sleeve through the rear portion of the studs (as shown in Figure 1). Space screws a of 6 in. (152mm) on center and a of 2 in. (51mm) from the corners (minimum of 2 screws per side). No retaining angles are required on the side of wall opposite from the grille. angles for 11/2 hour rated dampers with a width and height 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). angles for all 3 hour rated dampers and all dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 gauge (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 11/4 in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by a minimum of 1 in. (25mm)(see Figure 4). 31

32 4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO WALL OPENINGS continued... angles must be attached to the sleeve using one or more of the following methods of attachment: Tack or spot welds #10 (19mm) sheet metal screws 1 4 in. (6mm) bolts and nuts 3 16 in. (4.7mm) steel pop rivets Attachments must be spaced a minimum of 6 in. (152mm) on center and a of 2 in. (51mm) from corners. The angles must be attached to all 4 sides of the sleeve. A minimum of two attachments are required on each side, top and bottom. The angles need not be attached to each other at the corners. Caution! Do not tear the thermal blanket during installation. s are tested for correct operation and are square and straight before shipment from the factory. s must be installed square and straight and must not be twisted or racked. Failure to install the damper square and straight may prevent the damper blades from operating open and closed. 5. ACTUATOR CONNECTIONS Electrical and/or pneumatic connections to damper actuators should be made in accordance with wiring and piping diagrams developed in compliance with applicable codes, ordinances and regulations (see Electrical Guidelines). 6 Recommended Preparation of Openings in Wood and Metal Stud Walls Frame wall openings as shown (see Figure 5 & 5A) Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening (see Figure 5 & 5A). Prepare opening between studs and sleeve assembly as shown (Figure 6 & 7). All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance Directory) and/or local codes. Wall 2 in. Max. 6 in. Max. 6 in. Max. 2 in. Max. (installed around entire outside surface of sleeve) Figure 4: d damper with Thermal Blanket (duct continuation). Note: Thermal blanket is riveted to the damper sleeve and the seam is taped with acrylic adhesive tape, FSK facing tape 152 5CWnt, manufactured by Venture Tape Company. 24 in. o.c. 12 in. 24 in. o.c. (metal studs) 16 in. o.c. (wood studs) 24 in. o.c. (metal studs) 2 Panhead Screws 16 in. o.c. (wood studs) 2 in. (51mm) 2 in. (51mm) Ceiling Runner Second set of studs are not required on openings 36 in. x 36 in. (914mm x 914mm) or smaller. Floor Runner Figure 5 Figure 5A Metal stud only 32

33 Metal Stud Construction Gypsum Wallboard Wooden Stud Construction Gypsum Wallboard Stud or Runner Stud or Runner 1 in. Min. 1 in. Min. Figure 6 In metal stud construction, exposed steel surfaces need not be covered with gypsum wallboard. Figure 7 In wood stud construction, gypsum wallboard must cover all wood stud surfaces. Breakaway Connections Traditional Breakaway Style Transverse Joints Transverse joints illustrated at right have always been approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway connections. The breakaway connections shown (Figure 8) can be applied with of two #10 (19mm) sheet metal screws on each side and on Drive Slip Joint the bottom located in the center of the slip pocket and Figure 7 penetrating both sides of the slip pocket. Transverse joints illustrated can be applied as top and bottom joints with Drive Slip - side joints in duct heights up to 20 inches (508mm) See Figure 7. Round and Oval Breakaway Connections Round or flat oval ducts connected to Type R or O damper collars shall be attached with #10 (19mm) sheet metal screws as follows: s to 22 in. (558mm) wide (or dia.) and smaller shall have three screws. s larger than 22 in. (558mm) wide (or dia.) up to and including 36 in. (914mm) wide (or dia.) shall have five screws. NOTE: All breakaway connections described may have duct sealant applied, PA2084T duct sealant adhesive manufactured by Precision, DP1010 water base duct sealant manufactured by Design Polymetrics, Grey Pookie, mate PROseal, or CL Ward S Seal in accordance with SMACNA recommendations. Manufactured Flanged System Breakaway Connections Flanged connection systems manufactured by mate, Ward, and Nexus are approved as breakaway connections when installed as illustrated (Figure 9). Figure 8 (Attach per manufacturer's instructions) Plain S Slip Hemmed S Slip Double S Slip Inside Slip Joint Standing S Standing S (Alt.) Standing S (Alt.) Standing S Standing S (Bar Reinforced) ( Reinforced) 6 in. long 1/16 in. max. thickness plastic cleats; 12 in. c-c (min. 1 per side) Flanged system angles Figure 9 Neoprene gasket between all angles Fire Do not bolt corners Proprietary Flange System Breakaway Connections (TDC by Lockformer, TDF by Engle) TDC and TDF systems are approved as breakaway connections when installed as described in the TDC or TDF addendum to the SMACNA Construction Standards except the corners may not be bolted. Standard 6 in. (152mm) metal clip may be used with spacing as shown in Figure 10. 3/8 in. (9.5mm) metal bolts and nuts may be used to fasten together corner pieces (see Figure 11). Typical TDC/TDF joint 33

34 60 in. 4 Req d. Clip Spacing 6 in. 7 in. Std. Clip Length 9 in. 6 in. 6 in. 7 in. End Flange Corner Piece 48 in. 3 Req d. 36 in. 3 Req d. 24 in. 2 Req d. 5 in. 5 in. 5 in. 5 in. 3/8 in. bolt (optional) 18 in. & Smaller 1 Req d. C L Figure 10: Detail of proprietary flanged system breakaway connections. Maintenance s do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust. s and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with: The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA and local codes. Actuator manufacturer recommendations. Troubleshooting Figure 11 The following is a possible cause and correction list for common concerns with the dampers. Symptom Possible Cause Corrective Action Frame is 'racked' causing blades Adjust frame such that it is square and plumb to bind on jamb seals Actuator linkage loose Close damper, disconnect power, adjust and tighten linkage does not fully open and/or close RRL or TOR sensor tripped does not operate Our Commitment Defective motor Screws in damper linkage Contaminants on damper Heat No power supplied to the actuator Replace installed too far into wall. Move out to line as designated on damper label Clean with a non-oil based solvent (see Maintenance) Push reset button located on backside of RRL or TOR Add power supply As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. Phone: (715) Fax: (715) gfcinfo@greenheck.com Website: ODFD OFD Rev. 14, August 2013 Copyright 2013 Greenheck Fan Corporation 34

35 Refer to: Installation Instructions for FD, DFD, SSFD, & KFD Models (Part #452763) or Installation Instructions for FSD-XXX, DFD-XXX, SSFSD- XXX & CFSD-XXX Series Fire & Combination Fire Smoke s (Part #461336) or Installation Instructions for FD & DFD 150X Series Curtain Fire s (Part #453946) for additional details. Document number Single Side Installation Instructions Supplement FD & DFD Series 1 1 /2 Hour Fire s and FSD Series 1 1 /2 Hour Combination Fire Smoke s UL CLASSIFIED (see complete marking on product) UL CLASSIFIED to Canadian safety standards (see complete marking on product) Standards UL 555 & 555S Classifications Filed at UL under Listing #R13317 These instructions apply to 11/2 hour rated combination fire smoke dampers and curtain fire dampers mounted in masonry or block walls, metal stud walls, wood stud walls or concrete floors. Specific requirement in these instructions are mandatory. These instructions meet the requirements of NFPA 90A (Standard for the Installation of Air Conditioning and Ventilating Systems). Vertical mount dampers up to a size of 80 in. W x 50 in. H (2032mm x 1270mm), 50 in. W x 80 in. H (1270mm x 2032mm), or 40 in. W x 100 in. H (1016mm x 2540mm) or horizontal mount dampers up to a size of 144 in. W x 96 in. H (3658mm x 2438mm) may be installed as illustrated below. Larger damper assemblies require retaining angles on both sides of the partition. Note: Model specific size limits can be found in the base installation instruction documents noted above. 1. Clearance Requirements On vertical mount single side angle installations there are no minimum clearance requirements between the wall opening and the damper sleeve. However, to facilitate installation, clearances between the wall opening and the damper sleeve are recommended. On horizontal mount single side angle installations a minimum clearance is required between the outside of the damper sleeve and the floor opening of 1/8 in. per foot (3mm per.3m) of damper width and 1/8 in. per foot (3mm per.3m) height with a minimum clearance of 1/4 in. (6mm). The overall clearance is 1 1/2 in. (38mm), 2. Securing the / Assembly to Wall/ Floor Opening angles must be attached to both the sleeve and the partition (see figures 1-8). angles for dampers with a width and height of 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). angles for Single side retaining angle dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 ga. (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 1 1/4 in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by at least 1 in. (25mm). For metal stud partitions only, the single-side mounting angle may be directly attached to the metal stud prior to the installation of the drywall. angles must be attached to the sleeve using one of the methods shown below: tack or spot welds #10 sheet metal screws 1/4 in. (6mm) nuts and bolts angles must be attached to the partition using one of the methods shown below: Drywall screws of a length such that the screw engages the steel stud/track by 1/2 in. (13mm) (steel framing). 35

36 2. Securing the / Assembly to the Wall/Floor opening cont... Drywall screws of a length such that the screw engages the wood stud by 13/4 in. (44mm) (wood framing). Steel anchors or self tapping concrete screws penetrating masonry or block 11/4 in. (31mm). A minimum of two connections per side are required. Additional connections must be made at a of 12 in. (305mm) O.C. (on center) for openings of 48 in. W x 36 in. H (1219mm x 914mm) and less, and 6 in. (152mm) O.C. (on center) for openings 80 in. W x 50 in. H (2032mm x 1270mm), 50 in. W x 80 in. H (1270mm x 2032mm), and 40 in. W x 100 in. H (1016mm x 2540mm) or less. 2 1/2 in. Min. Stud or Runner 1/2 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details) 2 1/2 in. min. Stud or Runner Two layers of 1/2 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details) Fastener (see Section 2) Figure 1: 1 Hour Wall Rating Fastener (See Section 2) Figure 2: 2 Hour Wall Rating 2 1/2 in. Min. Metal Stud or Runner 1/2 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details) 2 1/2 in. min. Metal Stud or Runner Two layers of 1/2 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details) Fastener (see Section 2) Figure 3: 1 Hour Wall Rating Figure 4: 2 Hour Wall Rating Fastener (See Section 2) 2 1/2 in. Min. Stud or Runner 1/2 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details) 2 1 /2 in. Min. Stud or Runner 1/2 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details) Fastener (see Section 2) Figure 5: 1 Hour Wall Rating Fastener (see Section 2) Figure 6: 2 Hour Wall Rating 36

37 2. Securing the / Assembly to the Wall/Floor opening cont... Top Side Masonry or Concrete Wall Fastener (see Section 2) Masonry or Concrete Floor Fastener (see Section 2) Figure 7: Masonry or Concrete Wall Figure 8: Concrete Floor Note: For horizontal installations, retaining angles must be mounted on top side of partition. Grille Installations (s up to 36 in. x 36 in. [914mm x 914mm] ) legs may be reversed and one leg inserted into the wall/floor opening. angles used in conjunction with grille installations must be a minimum of 20 gauge (1mm) steel and have a minimum of 5/8 in. x 1 in. (15mm x 25mm) 20 gauge (1mm) steel. Space screws a of 6 in. (152mm) on center and a of 2 in. (51mm) from the corners (minimum of 2 screws per side). See Figure 9 and Figure 10. Note: Screws used to attach grille are allowed to penetrate reversed angle leg. #10 sheet metal screws spaced 6 in. on center and a of 2 in. from the corners (minimum of 2 screws per side). Screw into studs so as to avoid space conflicts with the grille Fastener (see Note 2) 2 1 /2 in. Min. Stud or Runner 1/2 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details) #10 sheet metal screws spaced 6 in. on center and a of 2 in. from the corners (minimum of 2 screws per side). Screw into studs so as to avoid space conflicts with the grille Fastener (see Note 2) 2 1/2 in. Min. Stud or Runner Two layers of 1/2 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details) Grille (supplied by others) (See Section 2) Grille (supplied by others) (See Section 2) Figure 9: 1 Hour Wall Rating Figure 10: 2 Hour Wall Rating Copyright 2013 Greenheck Corporation Single Side Suppl Rev. 3 Jan

38 DATE NOTES 38

39 DATE NOTES 39

40 Copyright 2013 Greenheck Fan Corporation Curtain Packet August 2013

This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.

This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete. Part Number 452763 FD, DFD, SSFD, SSDFD, & KFD Models 11/2 and 3 Hour Curtain Fire s Vertical and Horizontal Mount Installation, Operation and Maintenance Instructions FD, DFD, SSFD, & KFD models are intended

More information

Document Number FD & DFD 150X MODELS Hour Curtain Fire Dampers Vertical or Horizontal Mount

Document Number FD & DFD 150X MODELS Hour Curtain Fire Dampers Vertical or Horizontal Mount Document Number 45946 FD & DFD 150X MODELS 1 1 2 Hour Curtain Fire s Vertical or Horizontal Mount Installation, Operation and Maintenance Instructions FD and DFD 150X Series models are intended for installation

More information

RECEIVING AND HANDLING

RECEIVING AND HANDLING FD and DFD 150X Series models are intended for installation in accordance with fire damper requirements established by: National Fire Protection Association NFPA Standard 90A BOCA National Building Codes

More information

Document Number FD, DFD, SSFD, SSDFD, & KFD Models 11/2 and 3 Hour Curtain Fire Dampers Vertical and Horizontal Mount

Document Number FD, DFD, SSFD, SSDFD, & KFD Models 11/2 and 3 Hour Curtain Fire Dampers Vertical and Horizontal Mount Document Number 452763 FD, DFD, SSFD, SSDFD, & KFD Models 11/2 and 3 Hour Curtain Fire s Vertical and Horizontal Mount Installation, Operation and Maintenance Instructions FD, DFD, SSFD, & KFD models are

More information

for FD & DFD 150X MODELS

for FD & DFD 150X MODELS Part #45946 Installation, Operation and Maintenance Instructions FD and DFD 150X Series models are intended for installation in accordance with fire damper requirements established by: National Fire Protection

More information

Document number CURTAIN FIRE DAMPERS

Document number CURTAIN FIRE DAMPERS Document number 481324 CURTAIN FIRE DAMPERS DFD, DFD-150X, FD, FD-150X, SSDFD, SSFD, AND KFD Series 1 1 2 and 3 Hour Curtain Fire s Vertical and Horizontal Mount Installation, Operation and Maintenance

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 483517 Curtain Fire s DFD-XXX and FD-XXX 1 1 2 and 3 Hour Curtain Fire s Vertical and Horizontal Mount Installation, Operation and Maintenance Manual Please read and save these instructions for

More information

Installation, Operation, and Maintenance Instructions

Installation, Operation, and Maintenance Instructions Part Number 461337 OFSD-XXX, ODFD-XXX, OFD-XXX, and OSSFD-XXX Series 11/2 Hour Combination Fire Smoke or Curtain Fire s Out of Wall or Out of Floor Vertical or Horizontal Mount Installation, Operation,

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 481319 Fire and Combination Fire Smoke Dampers DFDR-XXX, FDR-XXX, FSDR-XXX, SEDFDR-XXX, SEFSDR- XXX, SSDFDR-XXX, SSFDR-XXX SSFSDR-XXX Series 1 1 2 Hour Vertical and Horizontal Mount Installation,

More information

installation instructions Combination Fire & Smoke Damper

installation instructions Combination Fire & Smoke Damper Combination Fire & Smoke Damper Sleeve Fire Rated Partition Retaining Angle Combination Fire & Smoke Damper Actuator General Notes: Combination Fire & Smoke Dampers are approved for use in static or dynamic

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 461335 Corridor Ceiling Dampers CFSD-xxx SERIES (with factory installed sleeve and actuator) Installation, Operation and Maintenance Manual Please read and save these instructions for future reference.

More information

Typical Actuator. RRL Control Device Standard

Typical Actuator. RRL Control Device Standard Part Number 461336 FSD-XXX, DFD-XXX, DFDTF-XXX CFSD-XXX, SEDFD-XXX, SEFSD-XXX, IMO-XXX, and SSFSD-XXX Series 1 1 2 and 3 Hour Fire & Combination Fire Smoke s (with factory installed sleeve and actuator)

More information

Document OUT OF WALL FIRE AND COMBINATION FIRE SMOKE DAMPERS

Document OUT OF WALL FIRE AND COMBINATION FIRE SMOKE DAMPERS Document 461337 OUT OF WALL FIRE AND COMBINATION FIRE SMOKE DAMPERS ODFD-XXX, OFD-XXX, OFSD-XXX SERIES 1 1 2 Hour Fire & Combination Fire Smoke Dampers Out of Wall or Out of Floor Vertical and Horizontal

More information

LLOYD INDUSTRIES INC. DAMPER INSTALLATION INSTRUCTIONS

LLOYD INDUSTRIES INC.   DAMPER INSTALLATION INSTRUCTIONS Installation and Maintenance Instructions 1-1/2 Hour Rated, UL Classified model 75 fire dampers For use in fire barriers with ratings of less than 3 hours INSPECTION 1. Inspect for shipping damage. 2.

More information

Document GRILLE ACCESS OUT OF WALL OR OUT OF FLOOR COMBINATION FIRE SMOKE DAMPERS

Document GRILLE ACCESS OUT OF WALL OR OUT OF FLOOR COMBINATION FIRE SMOKE DAMPERS Document 472477 GRILLE ACCESS OUT OF WALL OR OUT OF FLOOR COMBINATION FIRE SMOKE DAMPERS GFSD-XXX SERIES 1 1 2 Hour Combination Fire Smoke Dampers Vertical and Horizontal Mount Installation, Operation

More information

RATING: Consult factory for availability Consult factory for availability

RATING: Consult factory for availability Consult factory for availability DYNAMIC FIRE DAMPER MODELS: 75A-DY (1-1/2 HR rating) APPLICATION The model 75A-DY is constructed with standard constructiongalvanized steel. 75A-DY is 1-1/2 hour UL rated dynamic damper for use in HVAC

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 483519 MULTI-BLADE FIRE AND COMBINATION FIRE SMOKE DAMPERS DFD-XXX and FSD-XXX 1 1 2 Hour Fire & Combination Fire Smoke s (with factory installed sleeve and actuator) Vertical and Horizontal Mount

More information

2.5" Min. Stud or Runner. 1.5" Mineral Fiber Blanket in Cavity, If Required. Wallboard. Retaining Angle. 1" Min. Damper Sleeve on 10" centers.

2.5 Min. Stud or Runner. 1.5 Mineral Fiber Blanket in Cavity, If Required. Wallboard. Retaining Angle. 1 Min. Damper Sleeve on 10 centers. General Notes: When UL is referred to in this document, it represents UL/ULC. This installation instruction applies to Fire s (static, dynamic, curtain, single and multi-blade types) mounted in the plane

More information

RECEIVING AND HANDLING INSTALLATION SUPPLEMENTS WARRANTY SAFETY WARNING:

RECEIVING AND HANDLING INSTALLATION SUPPLEMENTS WARRANTY SAFETY WARNING: Typical Actuator RRL Control Device Standard Part #461336 Installation, Operation and Maintenance Instructions for FSD-XXX, DFD-XXX, CFSD-XXX, SSFSD-XXX SERIES 1 1 2 and 3 Hour Fire & Combination Fire

More information

Document MULTI-BLADE FIRE AND COMBINATION FIRE SMOKE DAMPERS

Document MULTI-BLADE FIRE AND COMBINATION FIRE SMOKE DAMPERS Document 481318 MULTI-BLADE FIRE AND COMBINATION FIRE SMOKE DAMPERS DFD-XXX, DFDAF-XXX, FSD-XXX, FSD-XXXV, IMO-XXX,SEDFD-XXX, SEFSD-XXX, AND SSFSD-XXX 1 1 2 and 3 Hour Fire & Combination Fire Smoke s (with

More information

Application & General Notes: Installation Supplements: Safety Warning: Other Installation References: Receiving & Handling: Electrical Guidelines:

Application & General Notes: Installation Supplements: Safety Warning: Other Installation References: Receiving & Handling: Electrical Guidelines: TRUE ROUND FIRE & FIRE/SMOKE DAMPER INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS R8218 FSD-RD FD(D)-RD UL/ULC File: R8218 New York BSA/MEA Listing: 79-03-M California State Fire Marshall Listing:

More information

3 HOUR UL CLASSIFIED CURTAIN TYPE (D)IBD230, (D)IBD430, and (D)IBD630 FIRE DAMPERS WITH INTEGRAL SLEEVES

3 HOUR UL CLASSIFIED CURTAIN TYPE (D)IBD230, (D)IBD430, and (D)IBD630 FIRE DAMPERS WITH INTEGRAL SLEEVES 3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 INSTALLATION INSTRUCTIONS 3 HOUR UL CLASSIFIED CURTAIN TYPE (D)IBD230, (D)IBD430, and (D)IBD630 FIRE DAMPERS WITH INTEGRAL SLEEVES

More information

Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19

Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19 Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19 Page 1 or 8 APPLICATION This fi re damper is intended to restrict the passage of fl ame. The standard installation requires that the

More information

11/2 HOUR UL CLASSIFIED CURTAIN TYPE (D)IBD2, (D)IBD2SS AND IBDT FIRE DAMPERS

11/2 HOUR UL CLASSIFIED CURTAIN TYPE (D)IBD2, (D)IBD2SS AND IBDT FIRE DAMPERS 3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 INSTALLATION INSTRUCTIONS 11/2 HOUR UL CLASSIFIED CURTAIN TYPE (D)IBD2, (D)IBD2SS AND IBDT FIRE DAMPERS APPLICATION The fire

More information

11/2 HOUR UL CLASSIFIED DAMPERS WITH GRILLE MOUNTING ANGLES

11/2 HOUR UL CLASSIFIED DAMPERS WITH GRILLE MOUNTING ANGLES 3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 INSTALLATION INSTRUCTIONS SUPPLEMENT 11/2 HOUR UL CLASSIFIED DAMPERS WITH GRILLE MOUNTING ANGLES FOR RUSKIN (D)IBD, FD AND FSD

More information

3900 Dr. Greaves Rd. Kansas City, MO (816) FAX (816)

3900 Dr. Greaves Rd. Kansas City, MO (816) FAX (816) 3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 INSTALLATION INSTRUCTIONS FSD60-3 and FSD60-3M COMBINATION FIRE AND SMOKE DAMPER 3 HOUR UL555 RATED UL555S LEAKAGE CLASS 1 RATED

More information

abi air balance INSTALLATION INSTRUCTIONS FIRE/LEAKAGE RATED CORRIDOR DAMPERS MODEL FS2C250 APPLICATION INSTALLATION Wiring Diagram II-FS2C-04.

abi air balance INSTALLATION INSTRUCTIONS FIRE/LEAKAGE RATED CORRIDOR DAMPERS MODEL FS2C250 APPLICATION INSTALLATION Wiring Diagram II-FS2C-04. INSTALLATION INSTRUCTIONS FIRE/LEAKAGE RATED CORRIDOR DAMPERS MODEL FS2C250 II-FS2C-04.8 APPLICATION This Corridor Damper is Classified by Underwriters Laboratories for One Hour Fire Resistance and as

More information

Fire Dampers (Static & Dynamic)

Fire Dampers (Static & Dynamic) Fire Dampers (Static & Dynamic) Important General Notes: When UL is referred to in this document, it represents UL/ULC. This installation instruction applies to Fire Dampers (static, dynamic, curtain,

More information

Standard Installation Combination Fire/Smoke Damper Models: FS1(SS), FS2(SS) Fire Damper Models: MD19(SS)

Standard Installation Combination Fire/Smoke Damper Models: FS1(SS), FS2(SS) Fire Damper Models: MD19(SS) Standard Installation Combination Fire/Smoke Damper Models: FS1(SS), FS2(SS) Fire Damper Models: MD19(SS) Page 1 of 6 APPLICATION These dynamically rated fire/smoke and fire s are intended to restrict

More information

FC /2 Hour Curtain Fire Dampers

FC /2 Hour Curtain Fire Dampers FC-2000 1-1/2 Hour Curtain Fire Dampers Installation Instructions 44-3521- 0, Rev. B Part No. 44-3521-0, Rev. B Issued March 2016 Applications Johnson Controls provides a 1-1/2 hour curtain fire damper

More information

BASIC LOUVER INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

BASIC LOUVER INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS BASIC LOUVER INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS The following installation instructions apply to all regular stationary and operable louvers fabricated out of extruded aluminum or steel.

More information

Standard Installation

Standard Installation APPLICATION Damper Models RC and RF are round, single blade, dynamically rated combination fire/smoke and fire dampers are intended to restrict the passage of flame and smoke (Model RC) or flame only (Model

More information

Louvers and Dampers April Product Guide Specification SECTION SMOKE DAMPERS

Louvers and Dampers April Product Guide Specification SECTION SMOKE DAMPERS Louvers and Dampers April 2008 P.O. Box 606 7435 Industrial Road Florence, Kentucky, 41042 Phone: (859) 647-2299 Fax: (859) 647-7810 Web Site: www.louvers-dampers.com Product Guide Specification SECTION

More information

SAUDI AIR CONTROL SYSTEM INDUSTRIAL REGISTRATION NO.353 FIRE DAMPERS

SAUDI AIR CONTROL SYSTEM INDUSTRIAL REGISTRATION NO.353 FIRE DAMPERS SAUDI AIR CONTROL SYSTEM INDUSTRIAL REGISTRATION NO.353 FIRE DAMPERS FIRE DAMPERS OUTSTANDING FEATURES: Gravity operated for vertical installation and with closure springs and latches for horizontal installation.

More information

Duct Wrap Flexible Wraps

Duct Wrap Flexible Wraps Design No. 3MU/ 60-01 December 23, 2010 VENTILATION DUCT PROTECTION 3M Company 3M Fire Barrier Duct Wraps: 615 and 615+ 3M Fire Barrier Sealants: Water-Tight 1000-NS Silicone, Water-Tight 1003-SL Silicone

More information

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 17

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 17 07 21 16 Blanket Insulation Page 1 of 17 Design Number UNI/BI 120-03 FIRE RESISTANT GREASE DUCT Unifrax I LLC FyreWrap Elite 1.5 Duct Insulation CAN/ULC S144 Fire Resistance Rating 2 hours Fire Inside

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 092216 - NON-STRUCTURAL METAL FRAMING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

2500 Series Fire Smoke Dampers

2500 Series Fire Smoke Dampers General Description The model 2550 is designed to prevent the spread of fire and smoke through ventilation ductwork in walls and floors. From receiving an alarm the power to the damper actuator is removed

More information

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 11

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 11 07 21 16 Blanket Insulation Page 1 of 11 Unifrax I LLC Design No. UNI/BI 120-14 FIRE RESISTANT GREASE DUCT FyreWrap Elite 1.5 Duct Insulation ASTM E 2336-16 and ICC-ES Acceptance Criteria for Grease Duct

More information

4-PIECE SHOWER WITH E-Z Pin INSTALLATION

4-PIECE SHOWER WITH E-Z Pin INSTALLATION 4-PIECE SHOWER WITH E-Z Pin INSTALLATION Suggested Tools Please consult all local and state building codes and read the entire installation instructions prior to beginning the installation of this unit

More information

0160 Series Curtain Fire Dampers

0160 Series Curtain Fire Dampers Burrell Way, General Description The 0160 series curtain fire dampers are designed to stop the spread of fire through ductwork, walls and floors in ventilation systems. When the fusible link reaches elevated

More information

Standard Installation Ceiling Radiation Dampers Models: 289, RCU, L89, A89, 291, RCI, L91, A91, 293, RC4, L93, A93, 295, RDU, L95, A95, 297, RDI,

Standard Installation Ceiling Radiation Dampers Models: 289, RCU, L89, A89, 291, RCI, L91, A91, 293, RC4, L93, A93, 295, RDU, L95, A95, 297, RDI, Page of 6 Standard Installation Ceiling Radiation Dampers Models: 289, RCU, L89, A89, 29, RCI, L9, A9, 293, RC4, L93, A93, 295, RDU, L95, A95, 297, RDI, APPLICATION These ceiling radiation dampers provide

More information

SECTION ACCESS DOORS AND FRAMES

SECTION ACCESS DOORS AND FRAMES 11303, 26 th avenue Montreal, Quebec Canada H1E 6N6 Phone: (800) 479-1489 Fax: (800) 297-1489 PRODUCT GUIDE SPECIFICATION SECTION 08 31 00 S PART 1 - GENERAL 1.1 SUMMARY A. Provide access doors, frames

More information

Insulated Fire-Rated Access Door Model(s): BIT/BIW/BIP

Insulated Fire-Rated Access Door Model(s): BIT/BIW/BIP Insulated Fire-Rated Access Door INSTALLATION, OPERATION & MAINTENANCE MANUAL Table of Contents Insulated Fire-Rated Access Door Table of Contents General Description...3 Installation...4-7 Operation...8

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 474644 EHH-601D Channel Installation with VCD-40 Damper Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting

More information

1 Exam Prep Application and Finishing of Gypsum Board GA Tabs and Highlights

1 Exam Prep Application and Finishing of Gypsum Board GA Tabs and Highlights 1 Exam Prep Application and Finishing of Gypsum Board GA-216-2013 Tabs and s These 1 Exam Prep Tabs are based on the Gypsum Association GA-216-2013 Application and Finishing of Gypsum Panel Products. Each

More information

1 Exam Prep Application and Finishing of Gypsum Board GA Tabs and Highlights

1 Exam Prep Application and Finishing of Gypsum Board GA Tabs and Highlights 1 Exam Prep Application and Finishing of Gypsum Board GA-216-2016 Tabs and s These 1 Exam Prep Tabs are based on the Gypsum Association GA-216-2016 Application and Finishing of Gypsum Panel Products. Each

More information

Home Depot Page 1 of 5 HDPB Humacao, PR 10/19/09

Home Depot Page 1 of 5 HDPB Humacao, PR 10/19/09 PART 1 - GENERAL 1.01 SUMMARY A. Types of cold-formed metal framing units include the following: 1. C-shaped steel studs B. Related work specified elsewhere includes but may not be limited to: 1. Section

More information

1. Non-load-bearing steel framing systems for interior gypsum board assemblies. 2. Suspension systems for interior gypsum ceilings and soffits.

1. Non-load-bearing steel framing systems for interior gypsum board assemblies. 2. Suspension systems for interior gypsum ceilings and soffits. SECTION 09 2216 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Non-load-bearing steel framing systems for interior gypsum board assemblies. 2. Suspension systems for interior gypsum ceilings and

More information

LVH-A Series Intumescent Fire Dampers Alternative Mounted Systems 1, 2 & 4 hour Fire Rating

LVH-A Series Intumescent Fire Dampers Alternative Mounted Systems 1, 2 & 4 hour Fire Rating LVH-A Series Intumescent Fire Dampers Alternative Mounted Systems 1, 2 & 4 hour Fire Rating For use in vertical and horizontal fire barriers COMPLETE DESIGN FREEDOM KEY FEATURES General Lorient LVH-A series

More information

DIVISION 15-MECHANICAL PN SECTION DUCTWORK SYSTEMS PART 1 - GENERAL 1.01 SECTION INCLUDES. A. Low, medium and high pressure ductwork.

DIVISION 15-MECHANICAL PN SECTION DUCTWORK SYSTEMS PART 1 - GENERAL 1.01 SECTION INCLUDES. A. Low, medium and high pressure ductwork. PART 1 - GENERAL 1.01 SECTION INCLUDES A. Low, medium and high pressure ductwork. 1.02 DEFINITIONS A. Duct Sizes: Inside clear dimensions. B. Low Pressure: 1/2 inch, 1 inch and 2 inch wg, positive or negative.

More information

5-1/2 inch Vinyl Handrail Model(s): BHRVE55C-P

5-1/2 inch Vinyl Handrail Model(s): BHRVE55C-P 5-1/2 inch Vinyl Handrail INSTALLATION, OPERATION & MAINTENANCE MANUAL Table of Contents 5-1/2 inch Vinyl Handrail Table of Contents General Description...3 Installation...4-7 Parts List...8 Maintenance...9

More information

PRESTON HEALTH SERVICES ARCHITECT'S NO. 2700

PRESTON HEALTH SERVICES ARCHITECT'S NO. 2700 SECTION 09 5113 - ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

LISTING INFORMATION OF International Fireproof Technology Inc. - Joint Systems SPEC ID: 43848

LISTING INFORMATION OF International Fireproof Technology Inc. - Joint Systems SPEC ID: 43848 LISTING INFORMATION OF International Fireproof Technology Inc. - Joint Systems SPEC ID: 43848 International Fireproof Technology Inc. 17528 Von Karman Avenue Irvine, CA 92614 This report is for the exclusive

More information

DIVISION 10 SPECIALTIES SECTION METAL LOCKERS

DIVISION 10 SPECIALTIES SECTION METAL LOCKERS DIVISION 10 SPECIALTIES SECTION 10 51 13 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

RF-2000 Round Fire Damper

RF-2000 Round Fire Damper RF-2000 Round Fire Damper Installation Instructions 44-1121- 32, Rev. C Part No. 44-1121-32, Rev. C Issued March 2016 Applications The RF-2000 round fire damper is designed to operate with blade running

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 092216 - COLD FORMED STEEL FRAMING - NON-STRUCTURAL (CFSF-NS) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 ACTION

More information

Shaftwall and Area Separation Wall Systems.

Shaftwall and Area Separation Wall Systems. Shaftwall and Area Separation Wall Systems www.marinoware.com Marino\WARE S Fire Rated Wall Systems Quality that takes you to the top. Marino\WARE created its CT Shaftwall System, to be a flexible shaftwall

More information

DIVISION 5 METALS SECTION COLD-FORMED METAL FRAMING

DIVISION 5 METALS SECTION COLD-FORMED METAL FRAMING DIVISION 5 METALS SECTION 05 40 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION ACOUSTICAL PANEL CEILINGS

SECTION ACOUSTICAL PANEL CEILINGS SECTION 095113 ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION NON-STRUCTURAL METAL FRAMING

SECTION NON-STRUCTURAL METAL FRAMING SECTION 09 22 16 PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories

More information

ROOF MOUNT KIT OWNERS MANUAL

ROOF MOUNT KIT OWNERS MANUAL ROOF MOUNT KIT OWNERS MANUAL Made in the USA by: Southwest Windpower, Inc. 1801 W. Route 66 Flagstaff, Arizona 86001 Phone: (928) 779-9463 Fax: (928) 779-1485 E-mail: info@windenergy.com Web: www.windenergy.com

More information

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1 FIRESTOP JOINT SPRAY CFS-SP WB SILICONE JOINT SPRAY CFS-SP SIL F-RATING 2-HR. 2-HR. T-RATING -HR. -HR. APPLICATION THICKNESS PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table /8" WET FILM (/6"

More information

SECTION NON--STRUCTURAL METAL FRAMING

SECTION NON--STRUCTURAL METAL FRAMING The Collective Voice of America s Steel Framing Industry The Steel Framing Industry Association (SFIA) is dedicated to expanding the market for cold-formed steel in construction through programs and initiatives

More information

Pre-Fabricated Roof Curbs

Pre-Fabricated Roof Curbs TC-1, TC-2, TC-3, TC-5 Table of Contents General Information 4-5 Specifications 6-9 Assembly Instructions 10-16 Pitch Information 17 Submittal 18-21 54 years of excellence... www.thybar.com 3 Insulated

More information

4-PIECE SHOWER & TUB/SHOWER w/ E-Z Pin INSTALLATION

4-PIECE SHOWER & TUB/SHOWER w/ E-Z Pin INSTALLATION 4-PIECE SHOWER & TUB/SHOWER w/ E-Z Pin INSTALLATION Suggested Tools Please consult all local and state building codes and read the entire installation instructions prior to beginning the installation of

More information

ROOF MOUNT KIT OWNERS MANUAL

ROOF MOUNT KIT OWNERS MANUAL ROOF MOUNT KIT OWNERS MANUAL Made in the USA by: Primus Wind Power, Inc. 938 Quail St. Lakewood, CO 80215 Phone: (303) 242-5820 www.primuswindpower.com AIR is a trademark of Primus Wind Power, Inc. ROOF

More information

AMBICO Limited 7\2018 Section and OVERSIZED METAL DOORS AND FRAMES Page 1

AMBICO Limited 7\2018 Section and OVERSIZED METAL DOORS AND FRAMES Page 1 Page 1 This section includes Oversize Steel Doors and Frames and relies on the Canadian Steel Door Manufacturers Association (CSDMA.org) industry standard, as well as on the Hollow Metal Manufacturers

More information

SECTION WALL AND DOOR PROTECTION

SECTION WALL AND DOOR PROTECTION PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 10 26 00 WALL AND DOOR PROTECTION SPEC WRITER NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable to

More information

Nortrax Section David Manchester Road, Ottawa NON-STRUCTURAL METAL FRAMING 16 May 2014 Page 1

Nortrax Section David Manchester Road, Ottawa NON-STRUCTURAL METAL FRAMING 16 May 2014 Page 1 16 May 2014 Page 1 PART 1 GENERAL 1.1 DESCRIPTION This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories

More information

SINGLE SWING DOOR PAIRED SWING DOOR

SINGLE SWING DOOR PAIRED SWING DOOR Rev. 091416 SINGLE SWING DOOR PAIRED SWING DOOR Drawing No.: Revision: Date: If you need to contact Customer Service Please complete the following information and retain for future reference: Serial Number:

More information

Banyan Air Service November 18, 2011 AVE Aviation and Commerce Center Building 1 Miami, FL

Banyan Air Service November 18, 2011 AVE Aviation and Commerce Center Building 1 Miami, FL SECTION 09511 - ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Construction Standards PAGE

Construction Standards PAGE Construction Standards PAGE 095113-1 SECTION 095113 - PART 1 - GENERAL 1.1 M.S.U. ISSUES 1. It the intent of MSU that all joint sealants used on its projects will comply with LEED NC 3 Credit Requirements

More information

FD Damper Installation, Operating and Maintenance Instructions

FD Damper Installation, Operating and Maintenance Instructions FD Damper Installation, Operating and Maintenance Instructions 1 Health and Safety 1.1 Only competent personnel may carry out the work outlined within this document. 1.2 The wearing of appropriate Personal

More information

Intumescent Fire Dampers

Intumescent Fire Dampers Fire tested and for up to 2 hours fire integrity in plasterboard, concrete or masonry and in steel duct spigots walls and floors Approved to AS1530.4 Technical Data Sheet KEY BENEFITS - 2 hours fire rating

More information

B. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other work.

B. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other work. SECTION 10 5113 - METAL LOCKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Fire Barrier Duct Wrap 615+

Fire Barrier Duct Wrap 615+ Fire Barrier Duct Wrap 615+ Duct Wrap Fire Protection System for Commercial Kitchen Grease and Ventilation Air Ducts Product Data Batts and blankets for use in fire resistive duct assemblies see UL fire

More information

Product Information Sheet

Product Information Sheet Product Information Sheet FyreWrap Elite 1.5 Duct Insulation Air Distribution System (ADS Ducts) Introduction Unifrax s FyreWrap Elite 1.5 Duct Insulation is a singlelayer flexible duct wrap enclosure

More information

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Pan System

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Pan System SECTION 13096 RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Pan System Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13096-1 RF MODULAR PAN SYSTEM PART 1 GENERAL 1.1

More information

SECTION NON-STRUCTURAL METAL FRAMING

SECTION NON-STRUCTURAL METAL FRAMING PART 1 - GENERAL 1.1 DESCRIPTION SECTION 09 22 16 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

B. Qualification Data: For installers specified in Quality Assurance article.

B. Qualification Data: For installers specified in Quality Assurance article. SECTION 233113 METAL DUCTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Installation Guide Document No BioSafe Cleanroom Windows Copyright 2017 Terra Universal Inc. All rights reserved. Revised December 2017

Installation Guide Document No BioSafe Cleanroom Windows Copyright 2017 Terra Universal Inc. All rights reserved. Revised December 2017 Document No. 1788-20 Copyright 2017 Terra Universal Inc. All rights reserved. Revised December 2017 Terra Universal, Inc. TerraUniversal.com 800 S. Raymond Ave. Fullerton, CA 92831 TEL: (714) 578-6000

More information

SECTION MANUAL FOUR FOLD DOORS MODEL 38 DECORATIVE PANEL DESIGN

SECTION MANUAL FOUR FOLD DOORS MODEL 38 DECORATIVE PANEL DESIGN SECTION 08350 MANUAL FOUR FOLD DOORS MODEL 38 DECORATIVE PANEL DESIGN PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION GYPSUM BOARD

SECTION GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Gypsum board screw attached to wood framing and furring members, joint treatment, and accessories. 2. Installation of

More information

WEIGHT PER PIECE (LBS.)

WEIGHT PER PIECE (LBS.) PRODUCT DESCRIPTION DATA SHEET 04 73 19-US BASIC USE ProGUARD DP is intended to be installed over sheathing and waterproofing over steel or wood studs or over concrete masonry units or poured concrete

More information

Façade Architectural Wall Panel System - Guide Specification 3/11/2017 SECTION FRAMED DECORATIVE PANEL SYSTEMS PART 1 - GENERAL 1.

Façade Architectural Wall Panel System - Guide Specification 3/11/2017 SECTION FRAMED DECORATIVE PANEL SYSTEMS PART 1 - GENERAL 1. SECTION 09 7710 FRAMED DECORATIVE PANEL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: Decorative ½ / ¾ (13mm/19mm) thick prefinished panel with preengineered attachment clip along with hardware

More information

Instruction and Safety Manual Resilient Sound Isolation Clips (SIC Clips)

Instruction and Safety Manual Resilient Sound Isolation Clips (SIC Clips) SOUND ISOLATION CLIPS Installation Manual Instruction and Safety Manual Resilient Sound Isolation Clips (SIC Clips) SOUND ISOLATION CLIP SPECIFICATIONS Width...1.00 inch Height...1.06 inch Length...3.86

More information

SECTION ACCESS DOORS AND FRAMES

SECTION ACCESS DOORS AND FRAMES SECTION 08310 ACCESS DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. [Fire rated] [and] [Non-fire rated] wall access panels. 2. [Fire rated] [and] [Non-fire rated] ceiling access

More information

Manufacturer of Coolers, Freezers, Step-Ins, Refrigeration Trailers and Sliding Doors COOLER AND FREEZER INSTALLATION MANUAL

Manufacturer of Coolers, Freezers, Step-Ins, Refrigeration Trailers and Sliding Doors COOLER AND FREEZER INSTALLATION MANUAL Manufacturer of Coolers, Freezers, Step-Ins, Refrigeration Trailers and Sliding Doors COOLER AND FREEZER INSTALLATION MANUAL http://www.walkincoolersandfreezers.com 786-286-2926 1 BEFORE INSTALLATION Please

More information

FyreWrap Elite 1.5 Duct Insulation Air Distribution System (ADS Ducts)

FyreWrap Elite 1.5 Duct Insulation Air Distribution System (ADS Ducts) Product Information Sheet FyreWrap Elite 1.5 Duct Insulation Air Distribution System (ADS Ducts) Introduction Unifrax s FyreWrap Elite 1.5 Duct Insulation is a singlelayer flexible duct wrap enclosure

More information

UL Design System HW-D-1012 continued

UL Design System HW-D-1012 continued UL System No. HW-D-1012 Assembly Ratings 1, 2 and 3 Hr (See Item 2) Nominal Joint Width 3 in. Class II and III Movement Capabilities 100% Compression or Extension Page 1 of 5 1. Floor Assembly The fire-rated

More information

I-STUD Shaftwall System

I-STUD Shaftwall System I-STUD Shaftwall System Summit Tower I-Stud and CertainTeed Shaftliner TM MILL CERTIFIED Steel-Con 00% GALVANIZED Steel Construction Systems UL Evaluation Report No. ER3660-02 Intertek The I-Stud is approved

More information

INSTALLATION MANUAL. FOOTWALL/SINKWALL (floor mount)

INSTALLATION MANUAL. FOOTWALL/SINKWALL (floor mount) INSTALLATION MANUAL FOOTWALL/SINKWALL (floor mount) OVERVIEW The Form is a UL-listed configurable footwall/sinkwall system. This system can include any combination of base cabinets, upper cabinets, wardrobes,

More information

Installation Guide and Safety Manual Resilient Sound Isolation Clips (SIC Clips)

Installation Guide and Safety Manual Resilient Sound Isolation Clips (SIC Clips) Installation Guide and Safety Manual Resilient Sound Isolation Clips (SIC Clips) SOUND ISOLATION CLIP SPECIFICATIONS Width...1.00 inch Height...1.06 inch Length...3.86 inch Weight....025 lbs Max Spacing...48

More information

FIRESTOPPING & SMOKE SEALS

FIRESTOPPING & SMOKE SEALS FIRESTOPPING & SMOKE SEALS SPECIFICATION SECTION 07860 1 General 1.1 SECTION INCLUDES.1 Comply with Division 1, General Requirements and Documents referred to therein..2 It is the intent of this section

More information

Price Egg Crate Grille

Price Egg Crate Grille Price Egg Crate Grille Division 23 Heating, Ventilating, and Air Conditioning Section 23 37 13 Diffusers, Registers, and Grilles The following specification is for a defined application. Price would be

More information

INSTALLATION MANUAL SURFACE-MOUNTED HEADWALL

INSTALLATION MANUAL SURFACE-MOUNTED HEADWALL INSTALLATION MANUAL SURFACE-MOUNTED HEADWALL Model # Series 7200-S Top Mounting Plate Electrical Junction Box Located Behind Removable Upper Panel Medical Gas Connections Lower Mounting Plate OVERVIEW

More information

SECTION MISCELLANEOUS METALS THIS SECTION TO BE INCLUDED IN SUB BID FOR SECTION MISCELLANEOUS AND ORNAMENTAL IRON

SECTION MISCELLANEOUS METALS THIS SECTION TO BE INCLUDED IN SUB BID FOR SECTION MISCELLANEOUS AND ORNAMENTAL IRON SECTION 055000 THIS SECTION TO BE INCLUDED IN SUB BID FOR SECTION 050001 MISCELLANEOUS AND ORNAMENTAL IRON PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a

More information

Cavity ShAftwall System

Cavity ShAftwall System 09 9 00/NGC Cavity shaftwall systems are non-load-bearing, -hour to -hour, fire-rated partitions constructed from one side used to enclose elevator shafts, stairs and mechanical shafts where the design

More information

INSTALLATION PROCEDURE

INSTALLATION PROCEDURE INSTALLATION PROCEDURE VOLU-probe/1, /3, /4 for Round Ducts INSPECTION & HANDLING. VOLU-probes should be carefully inspected for damage prior to installation. Report damage to your Freight Department,

More information