Document Number FD & DFD 150X MODELS Hour Curtain Fire Dampers Vertical or Horizontal Mount

Size: px
Start display at page:

Download "Document Number FD & DFD 150X MODELS Hour Curtain Fire Dampers Vertical or Horizontal Mount"

Transcription

1 Document Number FD & DFD 150X MODELS Hour Curtain Fire s Vertical or Horizontal Mount Installation, Operation and Maintenance Instructions FD and DFD 150X Series models are intended for installation in accordance with fire damper requirements established by: National Fire Protection Association NFPA Standard 80, 90A, & 101 IBC International Building Codes CSFM California State Fire Marshal Fire Listing (# :102) New York City (BSA/MEA listing # M) L S TATE S I S T STATE OF CALIFORNIA FIR E MAR S HALL E R V I N G E I C INSTALLATION SUPPLEMENTS Refer to the appropriate Greenheck installation supplements for special requirements: Support Mullions Shaftwall Supplement Drywall Supplement Grille Installation Supplement Drive Slip Supplement Sealant Supplement Extension Supplement Single side Angles Supplement Note: Refer to Greenheck IOM, Part #4615, for CFSD models to be installed in corridor ceiling applications. Refer to Greenheck IOM, Part # for standard DFD and FD models. UL CLASSIFIED (see complete marking on product) UL CLASSIFIED to Canadian safety standards (see complete marking on product) UL Standard 555 (Listing #R117) SAFETY WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment. RECEIVING AND HANDLING Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for. s must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100 F. WARRANTY Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization. This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete. Due to continuing research, Greenheck reserves the right to change specifications without notice.

2 Table of Contents Pre-Installation Guidelines... 2 Installation...-5 Breakaway Connections... 6 Installation for Steel Stud Connection Option... 7 Maintenance... 8 Troubleshooting... 8 Pre-Installation Guidelines The basic intent of a proper installation is to secure the fire damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner. 1. Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the fusible link is in place or has not separated. If fusible link is not present or has separated, replace link. Never install a fire damper without the proper UL approved fusible link in place. (Fusible link is standard control option. An electric link may have been provided.) 2. Lift or handle damper using sleeve or frame.. Install damper accordingly to comply with manufacturer s appropriate UL procedure file number. 4. must be installed into duct or opening square and free of twist or other misalignment. must not be squeezed or stretched into duct or opening. 5. must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include, but are not limited to: a. Mortar dust b. Drywall dust c. Firesafing materials d. Wall texture e. Paint overspray 6. should be sufficiently covered as to prevent overspray of spray-on insulating, wall texturing, or spray painting when performed within 5 feet of the damper. Excessive dirt or foreign material deposits can cause damper to bind and not operate properly. 7. Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles. 8. ACCESS: Suitable access (such that fusible links can be changed) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A). 9. The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary. 2

3 Installation - Failure to follow these instructions will void all warranties. These instructions apply to 11/2 hour rated fire dampers mounted in masonry, block or stud walls and concrete floors. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL 555. Installation shall comply with the requirements of NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems. U.L. listing R117, California State Fire Marshal listings :102, and New York City BSA/MEA listing M as they apply to these dampers. Note: Fire dampers are manufactured and labelled for either vertical or horizontal installation. The dampers must be installed in accordance with the labelling. Angle 2 in. Max. Min. 1 in. Overlap* Wall or Floor Angle Max. 1. NO ADDITIONAL SLEEVES ARE REQUIRED The fire damper extended frame is an approved sleeve and can be properly installed without the need for a supplemental field installed sleeve. frame shall extend a maximum of (152mm) beyond the wall or floor opening on each side. 2. CLEARANCES REQUIRED BETWEEN FIRE DAMPER SLEEVES AND WALL/FLOOR OPENINGS Fire damper assemblies expand during periods of intense heat. Therefore, it is essential that openings in walls or floors be larger than the fire damper assembly to allow for this expansion. Minimum clearances required between the outside of fire damper sleeve assemblies and wall/floor openings are: Galvanized steel fire dampers and sleeves: 1/8 in. (mm) per linear foot of damper width and height with a minimum clearance of 1/4 in. (6mm).Recommended clearances, for width and/or height dimensions of: 1) 48 in. (1219mm) or less: 1/2 in. (1mm) clearance 2) More than 48 in. (1219mm) and 9 (248mm) or less: 1 in. (25mm) clearance ) More than 9 (248mm): 11/2 in. (8mm) clearance These are total clearances (ignoring fastener heads) and do not need to be equally spaced around the damper. Refer to Section and Figure 1 for additional installation considerations. Example: A 12 in. x 12 in. (05mm x 05mm) damper would require a minimum clearance of 1/4 in. (6mm). A 48 in. x 12 in. (1219mm x 05mm) damper would require a minimum clearance of 1/2 in. (1mm) on width and 1/4 in. (6mm) on height. Max. 2 in. Max. *only applicable for damper sizes above x Figure 1: angle installation.. SECURING THE FIRE DAMPER TO WALL AND FLOOR OPENINGS Fire damper assemblies must be installed in wall and floor openings using retaining angles on each side of the wall or floor as described below: angles for 11/2 hour rated dampers with a width and height 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). angles for all hour rated dampers and all dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 gauge (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 11/4 in. (2mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by a minimum of 1 in. (25mm). angles must be attached to the damper using one or more of the following methods of attachment: tack or spot welds #10 sheetmetal screws 1/4 in. (6mm) bolts and nuts /1 (4.7mm) steel pop rivets Attachments must be spaced a maximum of (152mm) on center and a maximum of 2 in. (51mm) from corners. The angles must be attached to all 4 sides of the sleeve with butt joints at each corner. A minimum of two attachments are required on each side, top and bottom. The angles need not be attached to each other at the corners. angles should not be fastened to the wall/ floor material. The angles should only sandwich the wall/floor and allow for damper expansion during periods of intense heat.

4 4. CONNECTING DUCTS TO THE FIRE DAMPER All duct connections to FD & DFD 150X series extended frame dampers must be breakaway type connections. All connections shown 1/4 on in. minimum page 5 & 6 are considered breakaway. Factory furnished duct collars on types R & CR fire total clearance dampers are also considered breakaway(see Figure 2 & ). 1/4 in. minimum total clearance 1/4 in. minimum total clearance Angles (See Section 4) See Section 2 K side (see sections 2 & ) See Section 2 Angles Angles (See Section Angles ) (See Section ) (See Section ) Type A Type A Wall or Floor Type A Angles (See Section 4) See Section 2 K side Wall or Floor See Section 2 (see sections 2 & ) Type B On types R & CR factory furnished duct collar qualifies as breakaway connection. On types R & CR factory On types furnished R & duct CR factory collar furnished qualifies duct as breakaway collar qualifies connection. as breakaway connection. Type B Type B Type B K side Wall or floor Type C, CO, CR, & R Type C, CO, CR, & R On types R & CR factory furnished duct collar qualifies as breakaway connection, see Section 5 Type C, CO, CR, & R Figure 2: Vertical Mount Type A, Type B, and Type C, CO, CR, R damper installation diagrams. Type C, CO, CR, & R Figure : Horizontal Mount Type A, Type B, and Type C, CO, CR, R damper installation diagrams. When dampers installed horizontally, the ramp must be positioned up as shown in above drawings. 4 Table 1 Model Sizes for Single Section s* in. (mm) FD-150X (H or V) 48 x 48 (1219 x 1219) DFD-150X (V) 6 x 6 (914 x 914) DFD-150X (H) 0 x 0 (762 x 762) Note: V = Vertical mount & H = Horizontal * Sizes are based on damper with no transitions.

5 Preparation of Openings in Wood and Metal Stud Walls Frame wall openings as shown in Figure 4 and 4A. Gypsum wall board must be fastened 12 in. on center to all stud and runner flanges surrounding opening (see Figure 4 and 4A). Prepare opening between studs and sleeve assembly as shown below (see Figure 5). All construction and fasteners must meet then requirements of the appropriate wall design. (See UL Fire Resistance Directory) Second set of studs are required on openings x (914mm x 914mm) or smaller. 24 in. o.c. (metal studs) 24 in. o.c. (metal studs) Ceiling Runner 12 in. 24 in. o.c. 2 Panhead Screws 2 in. (51mm) 2 in. (51mm) 1 o.c. (wood studs) 1 o.c. (wood studs) Figure 4: Preparation detail for opening in stud wall. Second set of studs are not required on openings x (914mm x 914mm) or smaller. Figure 4A Metal Stud Construction Metal stud only Wooden Stud Construction Gypsum Wallboard Gypsum Wa llboard Stud or Runner Stud or Runner Angle Angl e 1 in. Min. 1 in. Min. In metal stud construction, exposed steel surfaces need not be covered with gypsum wallboard. In wood stud construction, gypsum wallboard must cover all wood stud surfaces. Figure 5: Detail of retaining angles and gypsum board application for metal and wooden stud construction. 5

6 - Connections Traditional Breakaway Style Transverse Joints Transverse joints illustrated in Figure 6 have always been approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway connections. The breakaway connections shown to the right can be applied with maximum of (2) #10 sheet metal screws on each side and on the bottom located in the center of the slip pocket and penetrating both sides of the slip pocket. Transverse joints illustrated can be applied as top and bottom joints with Drive Slip - side Drive Slip Joint joints in duct heights up to 20 in. (508mm). Round and Oval Breakaway Connections Round or flat oval ducts connected to factory supplied Type R, CR, or CO damper collars may use #10 sheet metal screws as follows: s 22 in. (559mm) wide (or dia.) and smaller may use screws. s larger than 22 in. (559mm) wide (or dia.) may use 5 screws. Proprietary Flange System Breakaway Connections (mate, Ward, Nexus) Flanged connection systems manufactured by mate, DuroDyne, Ward, and Nexus are approved as breakaway connections when installed as illustrated in Figure 7. (TDC by Lockformer, TDF by Engle) TDC and TDF systems are approved as breakaway connections when installed as described in the SMACNA Construction Standards. Standard metal clips may be used with spacing (see Figure 8). Three-eighth in. metal bolts and nuts may be used to fasten together corner pieces (see Figure 9). Plain S Slip Hemmed S Slip Double S Slip Inside Slip Joint Standing S Standing S (Alt.) Standing S (Alt.) Standing S Standing S (Bar Reinforced) (Angle Reinforced) Figure 6: Traditional breakaway style transverse joints. NOTE: All breakaway connections described may have duct sealant, PA2084T duct sealant adhesive manufactured by Precision, DP1010 water base duct sealant by Design Polymetrics, Grey Pookie, mate PROseal, or CL Ward S Seal applied in accordance with SMACNA recommendations. (Attach per manufacturer s instructions) Figure 7: long metal cleat or 1/1 max. thickness plastic cleat; 12 in. c-c (min. 1 per side) Flanged system angles Neoprene gasket between all angles Detail of manufactured flanged system breakaway connections. Fire Do not bolt corners 60 in. 4 Req d. Clip Spacing 7 in. Std. Clip Length 9 in. 7 in. End Flange Corner Piece Typical TDC/TDF joint 48 in. Req d. Req d. 24 in. 2 Req d. 18 in. & Smaller 1 Req d. 5 in. 5 in. 5 in. CL 5 in. /8 in. bolt (optional) Figure 8: 6 Detail of proprietary flanged system breakaway connections. Figure 9: Detail of bolted corner.

7 Installation for Steel Stud Connection (SSC) Option These instructions apply to 11/2 hour rated fire dampers mounted in steel stud walls. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL555. Installation shall comply with the requirements of NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems. U.L. listings R117 and R174, California State Fire Marshal listings :102 and :101, and New York City BSA/ MEA listing M as they apply to these dampers. 1. NO ADDITIONAL SLEEVES OR ANGLES ARE REQUIRED The fire damper extended frame is an approved sleeve and the Steel Stud Connection (SSC) Option allows fastening of the fire damper sleeve directly to the wall's steel stud framing. frame shall extend a maximum of (152mm) beyond the wall opening on either side. size fire damper that may be installed using this SSC option is W x H (914mm x 914mm). 2. INSTALLATION Fire damper with SSC option must be in place before the wall is constructed or it can be installed as the wall is being constructed. Wall opening is framed around the fire damper before sheet rock or other wall board material is applied to the steel studs. This installation provides appropriate protection for duct penetrations in fire resistant wall construction using steel studs with a fire resistance rating less than hours. The following wall design numbers (as detailed in the UL Fire Resistance Directory) are appropriate for fire damper installations using this SSC option: 1 Hour Design: U405, U406, U422, U44, U448, U451, U456, U457, U465, U468, U469, U485, U494 11/2 Hour Design: U449, U452, U470, U471 2 Hour Design: U40, U411, U412, U421, U425, U428, U429, U44, U45, U474, U475, U477, U484, U491, U495. FRAMING OF WALL OPENING Form a wall opening 1/8 in. (mm) to 1/4 in. (6mm) larger than the OD of the fire damper's extended frame (sleeve) using the same metal studs and techniques required by the wall design per the UL Fire Resistance Directory. Open side of the steel stud channels shall face the fire damper and encompass the damper's retaining bar. 4. APPLY WALLBOARD AFTER DAMPER INSTALLATION After damper is installed, wallboard shall be applied to steel stud framework in the manner required by the wall design per the UL Fire Resistance Directory listing. Around the damper perimeter use a minimum of 2 connections per side, spaced 12 in. (05mm) maximum and located a maximum of 2 in. (51mm) from each corner. No additional retaining angles are required to complete the installation. 5. CONNECTING DUCTS TO THE FIRE DAMPER All duct connections to FD & DFD 150X series extended frame dampers must be breakaway type connections. All connections shown on page 5 & 6 are considered breakaway. Factory furnished duct collars on types R, CR, & CO fire dampers are also considered breakaway. Item Description 1 FD150X fire damper with SSC option 2 Steel stud wall (see UL Fire Resistance Directory for specific details) Steel stud frame around opening in wall 4 connection (see section 6) 5 Wallboard (see UL Fire Resistance Directory for specific details) 6 Fasteners (see UL Fire Resistance Directory and Section 5) Bar 1 4 Top Cross-section View 4 2 Side Cross-Section View of in Wall 7

8 Maintenance s shall be maintained, cycled, and tested in intervals as stated in the latest editions of NFPA 90A, 92A, and UL 864 unless local codes require more frequent inspections. s do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired, do not use oil-based lubricants or any other lubricants that attract contaminant s such as dust. Trouble Shooting The following is a cause and correction list for common concerns with the dampers. Symptom Possible Cause Corrective Action does not fully open and/or fully close Frame is 'racked' causing blades to bind on jamb Screws in damper linkage Contaminant's on damper Link separated Heat Replace link Adjust frame such that it is square and plumb Locate screws and remove Clean with a non-oil based solvent (see Maintenance) Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. Phone: (715) Fax: (715) gfcinfo@greenheck.com Website: DFD & FD 150X Series Rev. 18, February 2015 Copyright 2015 Greenheck Fan Corporation 8

Document Number FD, DFD, SSFD, SSDFD, & KFD Models 11/2 and 3 Hour Curtain Fire Dampers Vertical and Horizontal Mount

Document Number FD, DFD, SSFD, SSDFD, & KFD Models 11/2 and 3 Hour Curtain Fire Dampers Vertical and Horizontal Mount Document Number 452763 FD, DFD, SSFD, SSDFD, & KFD Models 11/2 and 3 Hour Curtain Fire s Vertical and Horizontal Mount Installation, Operation and Maintenance Instructions FD, DFD, SSFD, & KFD models are

More information

Document number CURTAIN FIRE DAMPERS

Document number CURTAIN FIRE DAMPERS Document number 481324 CURTAIN FIRE DAMPERS DFD, DFD-150X, FD, FD-150X, SSDFD, SSFD, AND KFD Series 1 1 2 and 3 Hour Curtain Fire s Vertical and Horizontal Mount Installation, Operation and Maintenance

More information

INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS

INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS INSTALLATION INSTRUCTION BOOKLET FOR CURTAIN FIRE DAMPERS Instructions included in this booklet: IOM # Description Page(s) 452763 FD, DFD, SSFD & KFD Models 2 9 453946 FD & DFD 150X Models 10 17 462721

More information

Document GRILLE ACCESS OUT OF WALL OR OUT OF FLOOR COMBINATION FIRE SMOKE DAMPERS

Document GRILLE ACCESS OUT OF WALL OR OUT OF FLOOR COMBINATION FIRE SMOKE DAMPERS Document 472477 GRILLE ACCESS OUT OF WALL OR OUT OF FLOOR COMBINATION FIRE SMOKE DAMPERS GFSD-XXX SERIES 1 1 2 Hour Combination Fire Smoke Dampers Vertical and Horizontal Mount Installation, Operation

More information

Document OUT OF WALL FIRE AND COMBINATION FIRE SMOKE DAMPERS

Document OUT OF WALL FIRE AND COMBINATION FIRE SMOKE DAMPERS Document 461337 OUT OF WALL FIRE AND COMBINATION FIRE SMOKE DAMPERS ODFD-XXX, OFD-XXX, OFSD-XXX SERIES 1 1 2 Hour Fire & Combination Fire Smoke Dampers Out of Wall or Out of Floor Vertical and Horizontal

More information

RECEIVING AND HANDLING INSTALLATION SUPPLEMENTS WARRANTY SAFETY WARNING:

RECEIVING AND HANDLING INSTALLATION SUPPLEMENTS WARRANTY SAFETY WARNING: Typical Actuator RRL Control Device Standard Part #461336 Installation, Operation and Maintenance Instructions for FSD-XXX, DFD-XXX, CFSD-XXX, SSFSD-XXX SERIES 1 1 2 and 3 Hour Fire & Combination Fire

More information

11/2 HOUR UL CLASSIFIED CURTAIN TYPE (D)IBD2, (D)IBD2SS AND IBDT FIRE DAMPERS

11/2 HOUR UL CLASSIFIED CURTAIN TYPE (D)IBD2, (D)IBD2SS AND IBDT FIRE DAMPERS 3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 INSTALLATION INSTRUCTIONS 11/2 HOUR UL CLASSIFIED CURTAIN TYPE (D)IBD2, (D)IBD2SS AND IBDT FIRE DAMPERS APPLICATION The fire

More information

Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19

Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19 Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19 Page 1 or 8 APPLICATION This fi re damper is intended to restrict the passage of fl ame. The standard installation requires that the

More information

FC /2 Hour Curtain Fire Dampers

FC /2 Hour Curtain Fire Dampers FC-2000 1-1/2 Hour Curtain Fire Dampers Installation Instructions 44-3521- 0, Rev. B Part No. 44-3521-0, Rev. B Issued March 2016 Applications Johnson Controls provides a 1-1/2 hour curtain fire damper

More information

Insulated Fire-Rated Access Door Model(s): BIT/BIW/BIP

Insulated Fire-Rated Access Door Model(s): BIT/BIW/BIP Insulated Fire-Rated Access Door INSTALLATION, OPERATION & MAINTENANCE MANUAL Table of Contents Insulated Fire-Rated Access Door Table of Contents General Description...3 Installation...4-7 Operation...8

More information

RF-2000 Round Fire Damper

RF-2000 Round Fire Damper RF-2000 Round Fire Damper Installation Instructions 44-1121- 32, Rev. C Part No. 44-1121-32, Rev. C Issued March 2016 Applications The RF-2000 round fire damper is designed to operate with blade running

More information

UL Design System HW-D-1012 continued

UL Design System HW-D-1012 continued UL System No. HW-D-1012 Assembly Ratings 1, 2 and 3 Hr (See Item 2) Nominal Joint Width 3 in. Class II and III Movement Capabilities 100% Compression or Extension Page 1 of 5 1. Floor Assembly The fire-rated

More information

Shaftwall and Area Separation Wall Systems.

Shaftwall and Area Separation Wall Systems. Shaftwall and Area Separation Wall Systems www.marinoware.com Marino\WARE S Fire Rated Wall Systems Quality that takes you to the top. Marino\WARE created its CT Shaftwall System, to be a flexible shaftwall

More information

PRESTON HEALTH SERVICES ARCHITECT'S NO. 2700

PRESTON HEALTH SERVICES ARCHITECT'S NO. 2700 SECTION 09 5113 - ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

A. This Section includes ceiling- and wall-mounted diffusers, registers, grilles and louvers.

A. This Section includes ceiling- and wall-mounted diffusers, registers, grilles and louvers. SECTION 23 37 13 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

I-STUD Shaftwall System

I-STUD Shaftwall System I-STUD Shaftwall System Summit Tower I-Stud and CertainTeed Shaftliner TM MILL CERTIFIED Steel-Con 00% GALVANIZED Steel Construction Systems UL Evaluation Report No. ER3660-02 Intertek The I-Stud is approved

More information

NATIONAL GYPSUM COMPANY Wood Frame Walls And Ceilings Single- And Double-Layer Construction

NATIONAL GYPSUM COMPANY Wood Frame Walls And Ceilings Single- And Double-Layer Construction Walls And Ceilings Single- And Double-Layer Construction 09 9 00/NGC Single-Layer Construction The single-layer construction system consists of a single layer of Gold Bond brand Gypsum Board applied to

More information

6032 SH 3P Residential Shower Installation Instructions Gelcoat & Solid Surface Bathware

6032 SH 3P Residential Shower Installation Instructions Gelcoat & Solid Surface Bathware Tools/materials you might need for proper installation 6D galvanized screws 100% silicone caulking caulking gun acrylic latex caulk shims tape measure 1/8 drill bit Phillips screw driver cardboard china

More information

SHOWER & TUB/SHOWER INSTALLATION

SHOWER & TUB/SHOWER INSTALLATION SHOWER & TUB/SHOWER INSTALLATION Suggested Tools Please consult all local and state building codes and read the entire installation instructions prior to beginning the installation of this unit to ensure

More information

B. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other work.

B. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other work. SECTION 10 5113 - METAL LOCKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Façade Architectural Wall Panel System - Guide Specification 3/11/2017 SECTION FRAMED DECORATIVE PANEL SYSTEMS PART 1 - GENERAL 1.

Façade Architectural Wall Panel System - Guide Specification 3/11/2017 SECTION FRAMED DECORATIVE PANEL SYSTEMS PART 1 - GENERAL 1. SECTION 09 7710 FRAMED DECORATIVE PANEL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: Decorative ½ / ¾ (13mm/19mm) thick prefinished panel with preengineered attachment clip along with hardware

More information

FORM HEADWALL. FORM HEADWALL (floating) (floating) Installation Manual

FORM HEADWALL. FORM HEADWALL (floating) (floating) Installation Manual FORM HEADWALL (floating) Installation Manual FORM HEADWALL (floating) OVERVIEW The Form is a UL-listed configurable headwall system. This system includes multiple horizontal equipment channels integrated

More information

Installation Guide and Safety Manual

Installation Guide and Safety Manual Installation Guide and Safety Manual Resilmount A237R (Resilient Sound Isolation Clips) REQUIRED FURRING CHANNEL REQUIRED FURRING CHANNEL* 1 4" 2 2" Minimum f" Gauge:...25 Gauge With Hemmed Edge (Do Not

More information

2012 & 2015 International Building Code. Section Section Section Section Section Section 713.4

2012 & 2015 International Building Code. Section Section Section Section Section Section 713.4 Pei Evaluation Service is an accredited ISO Standard 17065 Product Certifier, accredited by the IAS. This Assembly Evaluation Report represents a product that Pei ES has Evaluated and has an Assembly Evaluation

More information

SECTION ACOUSTICAL PANEL CEILINGS

SECTION ACOUSTICAL PANEL CEILINGS SECTION 095113 ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

I-STUD Shaftwall System

I-STUD Shaftwall System I-STUD Shaftwall System Summit Tower Spokane, WA I-Stud and CertainTeed Shaftliner MILL CERTIFIED 00% GALVANIZED UL Evaluation Report No. ER3660-02 Intertek SCAFCO I-Stud is approved with the following

More information

FORM HEADWALL. FORM HEADWALL (floor mount) (floor mount) Installation Manual

FORM HEADWALL. FORM HEADWALL (floor mount) (floor mount) Installation Manual FORM HEADWALL (floor mount) Installation Manual FORM HEADWALL (floor mount) OVERVIEW The Form is a UL-listed configurable headwall system. This system includes multiple horizontal equipment channels integrated

More information

ROOF MOUNT KIT OWNERS MANUAL

ROOF MOUNT KIT OWNERS MANUAL ROOF MOUNT KIT OWNERS MANUAL Made in the USA by: Primus Wind Power, Inc. 938 Quail St. Lakewood, CO 80215 Phone: (303) 242-5820 www.primuswindpower.com AIR is a trademark of Primus Wind Power, Inc. ROOF

More information

A. Types of lightgauge metal framing units include the following: 1. C-shaped structural steel studs Uniform Building Code.

A. Types of lightgauge metal framing units include the following: 1. C-shaped structural steel studs Uniform Building Code. SECTION 05400 COLD-FORMED METAL FRAMING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

B. Qualification Data: For installers specified in Quality Assurance article.

B. Qualification Data: For installers specified in Quality Assurance article. SECTION 233113 METAL DUCTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Cavity ShAftwall System

Cavity ShAftwall System 09 9 00/NGC Cavity shaftwall systems are non-load-bearing, -hour to -hour, fire-rated partitions constructed from one side used to enclose elevator shafts, stairs and mechanical shafts where the design

More information

SECTION HVAC GRAVITY VENTILATORS

SECTION HVAC GRAVITY VENTILATORS SECTION 23 37 23 HVAC GRAVITY VENTILATORS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Fire Barrier Duct Wrap 615+

Fire Barrier Duct Wrap 615+ Fire Barrier Duct Wrap 615+ Duct Wrap Fire Protection System for Commercial Kitchen Grease and Ventilation Air Ducts Product Data Batts and blankets for use in fire resistive duct assemblies see UL fire

More information

SECTION GYPSUM BOARD ASSEMBLIES

SECTION GYPSUM BOARD ASSEMBLIES SECTION 09 21 16 GYPSUM BOARD ASSEMBLIES PART 1 GENERAL 1.1 SECTION INCLUDES A. Metal stud wall and ceiling framing, 20 gauge. B. Metal channel suspended ceiling framing. C. Gypsum board. D. Gypsum sheathing.

More information

COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100

COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100 COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100 Part 1 General 1.01 Work Included A. The work under this section shall include the furnishing of all items shown on the drawings and as specified,

More information

SECTION COLD-FORMED METAL FRAMING

SECTION COLD-FORMED METAL FRAMING SECTION 05400 PART I - GENERAL 1.01 DESCRIPTION A. Scope: Work of this Section shall include all materials and installation necessary to provide all cold formed metal framing. B. This Section includes:

More information

Price Egg Crate Grille

Price Egg Crate Grille Price Egg Crate Grille Division 23 Heating, Ventilating, and Air Conditioning Section 23 37 13 Diffusers, Registers, and Grilles The following specification is for a defined application. Price would be

More information

ESD-435X. Florida Product Approved Drainable Blade Louver. Application and Design. Standard Construction. Qualified Shapes

ESD-435X. Florida Product Approved Drainable Blade Louver. Application and Design. Standard Construction. Qualified Shapes Application and Design Florida Product Approved Drainable Blade Louver is a Florida Product Approved stationary drainable blade extruded aluminum louver designed to protect air intake and exhaust openings

More information

Introduction. Before you begin. Structure installation

Introduction. Before you begin. Structure installation Installation Manual Introduction Thank you for choosing a Valley product! This installation manual provides you with general information on the proper installation of our bath products. IMPORTANT NOTE:

More information

UL, KUL, WG-KUL, ARK, ARK-1

UL, KUL, WG-KUL, ARK, ARK-1 Installation manual GB/en Non-return dampers Types UL, KUL, WG-KUL, ARK, ARK-1 TROX GmbH Heinrich-Trox-Platz 47504 Neukirchen-Vluyn Germany Phone: +49 (0) 2845 2020 Fax: +49 (0) 2845 202265 E-mail: trox@trox.de

More information

INSTALLATION PROCEDURE

INSTALLATION PROCEDURE INSTALLATION PROCEDURE VOLU-probe/1, /3, /4 for Round Ducts INSPECTION & HANDLING. VOLU-probes should be carefully inspected for damage prior to installation. Report damage to your Freight Department,

More information

To Contact PS DOORS:

To Contact PS DOORS: Rev. 091416 MODEL FP- 530 TABLE OF CONTENTS PAGE Warranty Information 2 Flood Plank Barrier Safety & Product Info.. 3 Flood Barrier Installation Information. 5 Installation & Maintenance. 7 Inspection

More information

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board. 1.2 RELATED WORK A. Installation of steel framing members for walls, partitions,

More information

The GlasRoc Shaftliner Type X advantage...

The GlasRoc Shaftliner Type X advantage... C e r t a i n T e e d SHAFTLINER F o r A r e a S e p a r a t i o n F i r e w a l l s Shaftliner S Type X for Area Separation GlasRoc Shaftliner is a specially formulated product for applications where

More information

Pre-Fabricated Roof Curbs

Pre-Fabricated Roof Curbs Knock Down Curb Assembly Instructions These roof curb assembly instructions are to be used as general guidelines only. Included with shipment are as-built drawings for proper location of sections and channels.

More information

Installation Instructions/Operation and Maintenance Manual. Models PLG-60 PLG-72. PS DOORS Contact Information. Website psdoors.

Installation Instructions/Operation and Maintenance Manual. Models PLG-60 PLG-72. PS DOORS Contact Information. Website psdoors. Rev. 091416 Pallet Gate Installation Instructions/Operation and Maintenance Manual Models PLG-60 PLG-72 Table of Contents Product Information...2 Installation Instructions...3 Operation...6 Inspection

More information

Shaftwall & Stairwell Systems Fire protection & sound isolation for shafts & stairwells

Shaftwall & Stairwell Systems Fire protection & sound isolation for shafts & stairwells Shaftwall & Stairwell Systems Fire protection & sound isolation f shafts & stairwells what the job demands Shaftwall & Stairwell Systems Fire protection & sound isolation systems f elevat shafts, stairwells

More information

ONE SCHOOL STREET SEPTEMBER 18, 2008 GOWANDA, NEW YORK ARCH PROJECT NO

ONE SCHOOL STREET SEPTEMBER 18, 2008 GOWANDA, NEW YORK ARCH PROJECT NO SECTION 09265 - GYPSUM BOARD SHAFT-WALL ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers. SECTION 230529 - HANGERS AND SUPPORTS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Sleeves. 6. Mechanical sleeve seals. 7. Firestopping

More information

SECTION GYPSUM BOARD

SECTION GYPSUM BOARD SECTION 09250 GYPSUM BOARD PART 1GENERAL 1.1 SUMMARY A. Related Documents: General and Supplementary Conditions of the Contract, Division 1 - General Requirements, and Drawings are collectively applicable

More information

Central Dartmouth Section Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Dartmouth, NS

Central Dartmouth Section Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Dartmouth, NS Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Part 1 General 1. RELATED SECTIONS 1. Section 07 92 10 Joint Sealing 2. Section 08 71 00 Door Hardware 2. REFERENCES 1. American Society

More information

Bottom Hinged Flood Barrier Operation & Maintenance Manual

Bottom Hinged Flood Barrier Operation & Maintenance Manual Rev. 091416 Bottom Hinged Flood Barrier Operation & Maintenance Manual Model BH-590 Table of Contents Product Information...2 Inspection & Maintenance...5 Inspection & Maintenance Log...8 Warranty Information...9

More information

SECTION HVAC DUCTS AND CASINGS

SECTION HVAC DUCTS AND CASINGS SECTION 23 31 00 HVAC DUCTS AND CASINGS PART 1 -GENERAL 1.1 SUMMARY A. Section includes metal ductwork, nonmetallic ductwork, casing and plenums, buried ductwork, kitchen hood ductwork, duct cleaning.

More information

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection SECTION 13090 RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13090-1 LOW INTENSITY RADIATION PROTECTION

More information

Pedestrian Flood Door

Pedestrian Flood Door Pedestrian Flood Door Operations & Maintenance Manual Models PD-520 PD-522FFR Table of Contents Product Information...2 Inspection & Maintenance...6 Inspection & Maintenance Log...7 Warranty Information...8

More information

Wall Louvers (10200)

Wall Louvers (10200) Wall Louvers 08 90 00 (10200) PART 1 GENERAL SECTION INCLUDES A. Fixed, extruded-aluminum horizontal storm resistant louver RELATED SECTIONS A. Section 05120 - Structural Steel: Supports for penthouses.

More information

SKIRTED BATHTUB INSTALLATION MANUAL

SKIRTED BATHTUB INSTALLATION MANUAL SKIRTED BATHTUB INSTALLATION MANUAL 33778 North Railway Ave Mission, BC, V2V 1H6 Canada Toll free: 1-877 - 398-8827 Email: purchasing@valleyacrylic.com www.valleyacrylic.com INTRODUCTION products. Thank

More information

SECTION NON-STRUCTURAL METAL FRAMING

SECTION NON-STRUCTURAL METAL FRAMING PART 1 - GENERAL 1.1 DESCRIPTION SECTION 09 22 16 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

WHY I SHOULD SPECIFY AND USE FAS TRACK 1000?

WHY I SHOULD SPECIFY AND USE FAS TRACK 1000? TRACK 1000 FIRE MANAGEMENT PRODUCTS TECHNICAL PRODUCT GUIDE www.cemcosteel.com WHY I SHOULD SPECIFY AND USE FAS TRACK 1000? SOUND BENEFITS: Whether the protection you need is Fire, Air (Smoke), or Sound

More information

RSIC-1 SOUND ISOLATION SYSTEMS RSIC-1 INSTALLATION GUIDE

RSIC-1 SOUND ISOLATION SYSTEMS RSIC-1 INSTALLATION GUIDE RSIC-1 INSTALLATION GUIDE PAC International, Inc. Tel: (866) 774-2100 Technical: (866) 649-2710 Web Site: www.pac-intl.com RSIC is a registered Trade Mark of PAC International, Inc. Page 1 Drywall Furring

More information

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance Pei Evaluation Service is an accredited ISO Standard 17065 Product Certifier, accredited by the IAS. This Assembly Evaluation Report represents a product that Pei ES has Evaluated. This Assembly Evaluation

More information

Product Guide Specification

Product Guide Specification PAC International, Inc. December 2007 Las Vegas, NV 89128 Toll Free (866) RSIC-100 (866) 774-2100 Fax (866) 649-2710 Web Site www.pac-intl.com E-Mail info@pac-intl.com Product Guide Specification Specifier

More information

INSTALLATION INSTRUCTIONS for MP-RC1 TWO PIECE CONSTRUCTION TO BE INSTALLED ON COMPLETED ROOF DECK

INSTALLATION INSTRUCTIONS for MP-RC1 TWO PIECE CONSTRUCTION TO BE INSTALLED ON COMPLETED ROOF DECK INSTALLATION INSTRUCTIONS for MP-RC1 TWO PIECE CONSTRUCTION TO BE INSTALLED ON COMPLETED ROOF DECK A. 1. Using curb ribs as a guide, layout and mark roof openings on completed roof deck as outside curb

More information

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017 SECTION 10505 - METAL STUDENT LOCKERS PART 1 - GENERAL 1.01 SCOPE OF WORK A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

A M E R I C A N A R C H I T E C T U R A L M A N U F A C T U R E R S A S S O C I A T I O N

A M E R I C A N A R C H I T E C T U R A L M A N U F A C T U R E R S A S S O C I A T I O N A M E R I C A N A R C H I T E C T U R A L AAMA 2410-13 Standard Practice for Installation of Windows with an Exterior Flush Fin Over an Existing Window Frame M A N U F A C T U R E R S A S S O C I A T I

More information

SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM

SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM Page 1 of 6 SECTION 08 32 20 LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS SLIDING DOORS. SECTION INCLUDES OVERHEAD SLIDING TUBE ASSEMBLY, MOUNTING

More information

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS PART 1 GENERAL 1.01 SUMMARY Section 15140 PIPE HANGERS, This Section includes the furnishing and subsequent installation of: A. Pipe and equipment hangers, supports, and associated anchors B. Equipment

More information

Drag Chain Conveyor Installation and Operation Manual

Drag Chain Conveyor Installation and Operation Manual Drag Chain Conveyor Installation and Operation Manual Material Handling Equipment Sales, Incorporated 310 S. Section Line Rd Delaware, OH 43015 Phone: (989) 430-4005 Fax: (740) 363-9004 WARRANTY MATERIAL

More information

LISTING INFORMATION OF ClarkDietrich Steel 'H' Stud and 'U' Track Fire-resistance-rated Area Separation Wall Assemblies SPEC ID: 26662

LISTING INFORMATION OF ClarkDietrich Steel 'H' Stud and 'U' Track Fire-resistance-rated Area Separation Wall Assemblies SPEC ID: 26662 LISTING INFORMATION OF ClarkDietrich Steel 'H' Stud and 'U' Track Fire-resistance-rated Area Separation Wall Assemblies SPEC ID: 26662 ClarkDietrich Building Systems 9100 Centre Pointe Drive, Suite 210

More information

Light-Metal Roof Edge, Raised

Light-Metal Roof Edge, Raised NAIL WOOD CANT TO BLOCKING 2 ROWS STAGGERED EACH ROW 24 O.C. 1/2 MIN. 10 0 MAX. FASTEN 18 O.C. WITH NEOPRENE GASKETED FASTENERS 3-1/2 MIN. 4 6 JOINT COVER PLATE SET IN TWO BEADS OF SEALANT 4 MIN. SPECIFIED

More information

Container Installation Guide

Container Installation Guide Continuous Insulation Container Installation Guide Panels and InSerts The InSoFast CX Container panel and the InSerts are designed to fit most shipping containers. Containers have three types of corrugations:

More information

SECTION MODULAR GALVANIZED RF SHIELDING SYSTEM SPECIFICATIONS

SECTION MODULAR GALVANIZED RF SHIELDING SYSTEM SPECIFICATIONS SECTION 13096 MODULAR GALVANIZED RF SHIELDING SYSTEM SPECIFICATIONS Prepared by: NELCO 125 Chenoweth Lane, Ste. 206 Louisville, KY 40207 (502) 899-3726 13096-1 MODULAR GALVANIZED RF SHIELDING SYSTEM PART

More information

138 H-STUD AREA SEPARATION WALL SYSTEM

138 H-STUD AREA SEPARATION WALL SYSTEM H-STUD AREA SEPARATION WALL SYSTEM The fire-protection of gypsum-based Area Separation Walls is demonstrated in dramatic fashion by the results of this actual townhouse fire in which the two-hour fire-rated

More information

Model # BARK-358-RDP

Model # BARK-358-RDP Model # BARK-358-RDP 1675 Locust Street Red Bud, IL 62278 Phone: 618-282-8200 Fax: 618-282-8202 WARRANTY & TERMS WARRANTY: 5 Year Limited Warranty on Thermoplastic/Canine coated elements. guarantees all

More information

application instructions

application instructions application instructions FOUNDATIONS 76 & 120 SERIES PRIMED PANEL SIDING ARCHITECTURAL COLLECTION REVERSE BOARD & BATTEN AND STUCCO PANEL SIDING General At the time of manufacture, siding meets or exceeds

More information

3M Fire Barrier Moldable Putty Pads MPP+ Product Data Sheet

3M Fire Barrier Moldable Putty Pads MPP+ Product Data Sheet 3M Fire Barrier Moldable Putty Pads MPP+ Product Data Sheet 1. Product Description 4 in. x 8 in. (101.6 mm x 203.3 mm), 7 in. x 7 in. (177.8 mm x 177.8 mm) and 9.5 in. x 9.5 in. (241.2 mm x 241.3 mm) pad

More information

DIVISION OF PITTCON CUSTOM CORPORATION. Series Plastic Laminate or Veneer clad Column Covers CC-7

DIVISION OF PITTCON CUSTOM CORPORATION. Series Plastic Laminate or Veneer clad Column Covers CC-7 DIVISION OF PITTCON CUSTOM CORPORATION Series 8500 Plastic Laminate or Veneer clad s CC-7 Series 8500-Details Quarter Round (Wall Mount) Half Round (Wall Mount) Three-Quarter & Partial Column Covers Post

More information

Model # 238HS-P8. 4/27/2011 Page 1 of 11

Model # 238HS-P8. 4/27/2011 Page 1 of 11 Model # 238HS-P8 4/27/2011 Page 1 of 11 4/27/2011 Page 2 of 11 1675 Locust Street Red Bud, IL 62278 Phone: 618-282-8200 Fax: 618-282-8202 WARRANTY & TERMS WARRANTY: 5 Year Limited Warranty on Thermoplastic

More information

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466 BUSWAY LOW VOLTAGE (POW-R-WAY III) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein

More information

SECTION SOUND ISOLATION

SECTION SOUND ISOLATION SECTION 13085 SOUND ISOLATION PART 1 GENERAL 1.1 SECTION INCLUDES A. Resilient sound isolation clips installed with drywall furring channels for support of gypsum board for noise control (de-coupling)

More information

DIVISION: FINISHES SECTION: SUSPENSION SYSTEMS SECTION: ACOUSTICAL CEILING SUSPENSION ASSEMBLIES REPORT HOLDER:

DIVISION: FINISHES SECTION: SUSPENSION SYSTEMS SECTION: ACOUSTICAL CEILING SUSPENSION ASSEMBLIES REPORT HOLDER: 0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-3336 Reissued 01/2015 This report is subject to renewal 01/2017. DIVISION: 09 00 00 FINISHES

More information

SLOTTED STUD WIND-LOAD & NON-LOAD BEARING DEFLECTION WALL SYSTEM. U.L. FIRE RATED Head-of-Wall Joint Systems

SLOTTED STUD WIND-LOAD & NON-LOAD BEARING DEFLECTION WALL SYSTEM. U.L. FIRE RATED Head-of-Wall Joint Systems SLOTTED STUD WIND-LOAD & NON-LOAD BEARING DEFLECTION WALL SYSTEM U.L. FIRE RATED Head-of-Wall Joint Systems 1-800-275-2279 STEELER INC. SLOTTED STUD 1-800-275-2279 The STEELER SLOTTED STUD is an innovative

More information

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION SUPPORTS AND ANCHORS

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION SUPPORTS AND ANCHORS OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 WORK INCLUDED A. Supports and anchors for piping systems and equipment. 1.2 RELATED WORK SPECIFIED ELSEWHERE A. The provisions of Section 15050, Basic

More information

RAY-CORE Structural Insulated Roof and Wall Panels

RAY-CORE Structural Insulated Roof and Wall Panels SUBMITTAL 20180101 RAY-CORE Structural Insulated Roof and Wall Panels Closed Cell Polyurethane Foam Insulation Douglas Fir Studs STANDARD FEATURES Insulation, Framing and Wrap in a 4 wide panel Available

More information

B. Polyethylene samples shall be submitted for Owner approval of color and quality.

B. Polyethylene samples shall be submitted for Owner approval of color and quality. Glass Rail ENGINEERED DASHERBOARD SPECIFICATIONS PART 1 - GENERAL 1.01 PROJECT SCOPE A. Contractor shall furnish and install one complete set of steel framed dasherboards as indicated on the drawings and

More information

SECTION METAL DUCTS

SECTION METAL DUCTS SECTION 15815 METAL DUCTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Rev. 07 8/15 Please Read Disclaimers:

Rev. 07 8/15 Please Read Disclaimers: FiberCorr panels Guidelines 6005.FC Rev. 07 8/15 Please Read Disclaimers: PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION!! These guidelines are provided in good faith to help prevent any problems

More information

SECTION EXTERIOR GRILLS AND SCREENS

SECTION EXTERIOR GRILLS AND SCREENS SECTION 10 82 13 PART 1 GENERAL PART 1 1 SUMMARY A. Section Includes: 1. Exterior perforated aluminum screen wall system with Ombrae TM Optical Tile imaging technology. 2. Accessories including attachments,

More information

Model # 800SM-PS3. 8/3/2016 Page 1 of 8

Model # 800SM-PS3. 8/3/2016 Page 1 of 8 Model # 800SM-PS3 8/3/2016 Page 1 of 8 /3/2016 Page 2 of 8 1675 Locust Street Red Bud, IL 62278 Phone: 618-282-8200 Fax: 618-282-8202 WARRANTY & TERMS WARRANTY: 5 Year Limited Warranty on Thermoplastic

More information

SECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products.

SECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products. SECTION 05720 ORNAMENTAL ALUMINUM RAILING ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products. This section is based on the products of Superior Aluminum Products,

More information

Series 3000 Pocket Doors

Series 3000 Pocket Doors Series 3000 Pocket Doors Introduction: The following three (3) part specification offers the Standard and Optional features for the Series 3000 Pocket Doors. The yellow highlighted areas in the specification

More information

SECTION GYPSUM WALLBOARD. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION GYPSUM WALLBOARD. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 092116 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS CHIMNEY CONNECTOR WALL THIMBLE MODEL IWT INSTALLATION INSTRUCTIONS Warnock Hersey C US LISTED ULC-S641/UL103 IT IS OF THE UTMOST IMPORTANCE THAT THIS WALL THIMBLE BE INSTALLED ONLY Y IN ACCORD CCORDANCE

More information

DIVISION 10 SPECIALTIES SECTION OPERABLE PARTITIONS

DIVISION 10 SPECIALTIES SECTION OPERABLE PARTITIONS DIVISION 10 SPECIALTIES SECTION 10 22 26 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Area Separation Walls

Area Separation Walls Area Separation Walls G-P Gypsum Your Complete Resource for Innovative Gypsum Products Overview When tested, as manufactured, in accordance with ASTM D 3273, DensGlass Ultra Shaftliner TM panels scored

More information

RSIC-1. RSIC-1, the Low Cost, High Performance, Noise control Solution. RSIC-1 specifications:

RSIC-1. RSIC-1, the Low Cost, High Performance, Noise control Solution. RSIC-1 specifications: RSIC-1 The RSIC-1 is designed for use with any wood framed, steel framed, CMU, or concrete wall and ceiling system where noise control is needed. The RSIC-1 assembly decouples and isolates the gypsum board

More information

GYPSUM BOARD SECTION GYPSUM BOARD PART 1 - GENERAL

GYPSUM BOARD SECTION GYPSUM BOARD PART 1 - GENERAL 13686.00 GYPSUM BOARD 092116-1 1.1 RELATED DOCUMENTS: SECTION 092116 - GYPSUM BOARD PART 1 - GENERAL A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division

More information

Repair Maintenance Hangar Phase II August 2010

Repair Maintenance Hangar Phase II August 2010 SECTION 08800 GLASS AND GLAZING PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Monolithic glass. 2. Insulating glass. 3. Mirror glass. 4. Glazing accessories. B. Types of work in this section include

More information

Suspension Systems for Acoustical Lay-in Ceilings Seismic Design Categories D, E & F

Suspension Systems for Acoustical Lay-in Ceilings Seismic Design Categories D, E & F NWCB Technical Document SUSPENDED CEILINGS 401 Suspension Systems for Acoustical Lay-in Ceilings Seismic Design Categories D, E & F 10/09 This document has been revised based on current Building Code standards.

More information

SECTION ROOF SPECIALTIES

SECTION ROOF SPECIALTIES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 71 00 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information