1 Professional Engineer Authenticated TELUS Residential Service Conduit Requirements For Stand-Alone Homes and Duplexes in Fibre Only Communities Beginning in January 2010 TELUS began designing new subdivisions within the Top 48 population centres in Alberta and British Columbia using only fibre optic cable. This document explains the new conduit only servicing model that is used in fibre only communities, and it summarizes what the TELUS and builder responsibilities are within that model. For more information please contact the following TELUS personnel: 780 Area Code / Red Deer North Rick Fedirko rick.fedirko@telus.com 403 Area Code / Red Deer South Tony Walker tony.walker@telus.com General Entrance Requirements TELUS extends the 20mm (3/4 ) HDPE conduit which is stubbed at the property line to the service connection point on the side of the home. TELUS will use this HDPE or PVC conduit and the builder provided PVC conduit and LB to install fibre optic cable when a customer orders service. Note that TELUS no longer pre-installs cables to homes in fibre only communities, and that we are requesting an empty conduit within the house. If a coiled drop of cable is located at the property line then please follow the information included in the P630 located at: Page 1 of 10

2 Fibre Only Conduit Service Diagram: TELUS Responsibility After the builder contacts Ledcor (see Builder Responsibilities below), a continuous section of 20mm (3/4 ) HDPE (high density polyethylene) SDR 13.5 orange or PVC service conduit will be extended from the property line to the side of the house at TELUS expense. At the base of the foundation wall the HDPE or PVC conduit will be fed through a TELUS supplied rigid sweeping 90 degree bend (to prevent HDPE kinking) and extended up the wall through the builder provided PVC conduit and LB. The HDPE conduit will be capped off within the LB. Builder Responsibilities TELUS requests the builder do the following in order to accommodate the HDPE or PVC conduit: 1. TRENCH: Provide a suitable trench from the property line to the service location at the side of the house as follows: Trench must be free of construction materials, rocks or stones. Trench must be sloped for grade changes. Stepped grade changes are not acceptable as this can cause pinching or constriction of the HDPE conduit. Page 2 of 10

3 Where communications services and power services share a common trench, Canadian Electrical Code rule must be followed. 2. PVC CONDUIT & LB: Supply and install a 32mm (1-1/4 ) LB and a 32mm (1-1/4 ) schedule 40 PVC conduit along the outside of the house from the LB to a minimum of 300mm below the finished grade. The TELUS provided HDPE or PVC conduit pathway will be installed inside the PVC conduit and LB, and. *Note that if the HDPE is installed before the builder supplied PVC conduit, then the builder should slide the schedule 40 PVC conduit over the TELUS supplied HDPE leaving the top of the HDPE conduit accessible inside the LB. Provide the following separations between services on the outside of the house: Between Electrical service and TELUS service: 200mm (8 ) minimum separation Between Cable TV service and TELUS service: 250mm (10 ) minimum separation 3. ARRANGE TELUS CONDUIT: After excavation of the trench and installation of the schedule 40 PVC conduit and LB, the builder shall contact the TELUS contractor (Ledcor Technical Services, LTS) to arrange for extension of the HDPE conduit from the property line to the side of the house at TELUS expense. Note that LTS will arrange to install the HDPE or PVC conduit with 72 hours of being contacted, so do not back-fill the trench until the conduit extension has been completed. LTS contact information as follows: Phone (toll free, no area code required) to ltsconduitextension@ledcor.com and provide address and contact information 4. INTERNAL CONDUIT PATHWAY: Supply and install a 25mm (1 ) non-metallic conduit from the LB to the central wiring location inside the home, to provide TELUS with a continuous pathway from our pedestal to the central wiring point within the house. This conduit should have a maximum of four sweeping 90 degree bends, and should have a pull string installed. Providing an internal conduit pathway means that no external splice box is required which makes the external installation more visually appealing and matches the typical installation method of other service providers. *Note that this empty conduit is instead of the previously supplied 4 pair 24 gauge telephone wire and the 6 gauge insulated ground conductor. 5. BACKFILL: Backfill the service trench after the TELUS HDPE or PVC service conduit is installed. Ensure the trench is free of construction material and the service conduit is placed so that kinking or pinching will be avoided. Use only native loose packed fill directly on the service conduit and avoid large rocks or frozen soil which could damage the conduit. Ensure there is 500mm (20 ) of fill coverage on top of the service conduit before tamping. 6. NO INTERNAL CONDUIT PATHWAY: If the builder decides not to provide a non-metallic conduit between the LB and the central wiring point inside the home, then TELUS requires the builder to supply and install a bend insensitive fibre (ITU-T-G657 compliant, indoor or outdoor rated) a 4 pair 24 gauge telephone wire and the 6 gauge insulated ground conductor between the external LB and the internal central wiring point leaving 2m of slack at each end. This will result in an additional splice box installed on the LB on the outside of the house. This wiring is required because TELUS cannot guarantee that fibre could be installed between the LB and the central wiring point through a finished basement at some time in the future. Page 3 of 10

4 Normal Conduit Routing to Central Wiring Location: TELUS' primary requirement is to have a clear and unobstructed raceway from the outside wall to the panel location. TELUS' conduit must come above grade at the side of the house and cannot be placed as a continuous underground run with direct entry into the basement for two specific reasons: In the event that the street or pedestal location was too flooded the conduit could act as a direct route for the water to enter into the house. In the event the duct is damaged on private property TELUS would have no direct access into the house to provide temporary services. Internal Conduit Routing Options for a Centralized Panel Extend conduit through the basement floor: Alternative Routing for Centralized Panel Builder Supplied: 1 ¼ Schedule 40 Rigid Conduit to 300mm below grade 6 x 6 or Approximate Transition Box with Cover in place of STB 1 Schedule 40 Rigid duct to sweeping 90 extended through footing to Centralized Panel Location Minimum 900mm Coverage To Property Line Line of Grade 1 ¼ Sched 40 Rigid Conduit Min 300mm Below grade Extend Pull rope 1 Sched 40 Rigid Conduit To Centralized Panel Foundation Wall TELUS Supplied: Continuous 20mm HDPE SDR 13.5 Conduit 2 Sweeping 90 PVC Schedule 40 *Note all bends must be Sweeping* Page 4 of 10

5 Extend conduit through the floor joists: Builder Supplied: 1 ¼ LB 1 ¼ Schedule 40 Rigid Conduit 1 Conduit with Pull Rope to Central Panel location Alternative Routing for Centralized Panel Extend Pull Rope *Note all bends must be Sweeping* Joist To Centralized Panel 1 ¼ LB Joist 1 ¼ Sched 40 Rigid Conduit Line of Grade 1 Sched 40 Rigid or Flexible Non-metallic Conduit Minimum 900mm Coverage Min 300mm Below grade Foundation Wall TELUS Supplied: Continuous 20mm HDPE SDR 13.5 Conduit 2 Sweeping 90 PVC Schedule 40 Page 5 of 10

6 Outside To Inside Transition Pre-Wire and Panel/Backboard Area Central Wiring Requirements The inside wiring should be done in a star configuration where the individual set runs from each telephone jack and TV location collect at a common location within the home (see Figure 2). The centre of the star is to be in a heated environment where there is no risk of the ambient air temperature falling below 0º (zero) Celsius. A garage is NOT a suitable location Builder/Owner will provide One (1) duplex 15A non-switched power receptacle dedicated to home networking, communication and entertainment equipment, installed in a multi media enclosure at this location (the use of a Multi Media enclosure or Smart Panel is not mandatory although it is recommended). Total space required for the mounting of the Fibre Equipment and Multi Media enclosure will be a minimum of 600mm (24 ) x 900mm (36 ). Owner/Builder will provide patch panels for Voice / DATA / Coax. Refer to Figure 2 and Figure 3 for more information Page 6 of 10

7 Figure 2 1 Inch Rigid or Flex Conduit LB Grade Central Wiring Location Space of 24 x 36 inches Required for mounting of Equipment Detailed View see Figure 3 Page 7 of 10

8 Inside Wiring and Equipment Layout (Figure 3) 24 X 36 area of wall space required to accommodate all equipment. If a Multimedia enclosure is not used the same layout will apply on a securely fastened ¾ plywood backboard. Page 8 of 10

9 Inside Wiring Instructions The builder/owner shall supply telephone cabling and terminate as follows: Voice, Data and Coax Patch Panel Style Termination strips at the backboard location. All CAT5e inside wire to each location where the Home Builder/Owner would like Voice, DATA and TV (i.e.: if all 3 services are required in one location, then 3 CAT5e would be required at this location). Voice set runs to have W/BL, W/O AND W/GR terminated on RJ11 wall outlets and all 4 pairs terminated at the backboard location on the voice module. Data & TV runs to be terminated on RJ45 wall outlets and all 4 pairs terminated at the backboard location on the Data module according to the TIA-568A standard and labeled at both ends. Verification testing to be completed on all set runs. TELUS prefers using CAT5e cable for TV but can use coax cables. Please call for more information about products and services offered by TELUS or visit telus.com/bics Page 9 of 10

10 Professional Engineer Authenticated Title: TOPPS Documentation Engineering Review Process Original date of issue: Reviewed by: Tony Walker APEGGA APEGBC Title: Professional Engineer Signed Document history: Date of Revision Description of Revision Revised by Reviewed by Certified by Original Rick Fedirko Tony Walker Changed wording on picture on page 2 from STB to LB Rick Fedirko Eddie Alfonso Changed wording on picture on page 2 and added verbiage on page 6 Rick Fedirko Eddie Alfonso Added PVC and removed pull string from pedestal to LB Rick Fedirko Eddie Alfonso 5 This document is the property of TELUS and contains proprietary and confidential information which must not be duplicated, used or disclosed without prior consent of TELUS. To verify and certify signature please add the certificate to your list of trusted identities by To verify and certify signature please add the certificate to your list of trusted identities by Page 10 of 10

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL 8.01 GENERAL This material is not intended to cover service from OPPD s network in the downtown Omaha area. See Chapter 12 for details

More information

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets. ALLIANT ENERGY CENTER PAVILIONS Project No. 2013 027 SECTION 27 05 28 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Huntsville Utilities Underground Residential Service Requirements

Huntsville Utilities Underground Residential Service Requirements Huntsville Utilities Underground Residential Service Requirements Sections: Scope General Conduit Installation Conduit Termination at Riser Pole Conduit Termination at Padmount Transformer or Secondary

More information

Addendum 1.0. For Lagrange Library Specification 1.0. Technology Consultants Fort Wayne, Indiana

Addendum 1.0. For Lagrange Library Specification 1.0. Technology Consultants Fort Wayne, Indiana Addendum 1.0 For Lagrange Library Specification 1.0 Technology Consultants Fort Wayne, Indiana TECHNICAL SPECIFICATIONS FOR TELECOMMUNICATION DISTRIBUTION FACILITIES AND INSTALLATION PROCEDURES For Lagrange

More information

Local Government District of Pinawa P.O. Box 100 PH: Pinawa, MB R0E 1L0 FX:

Local Government District of Pinawa P.O. Box 100 PH: Pinawa, MB R0E 1L0 FX: Local Government District of Pinawa P.O. Box 100 PH: 204-753-5100 Pinawa, MB R0E 1L0 FX: 204-753-2770 G. Smith B.C. Skinner Resident Administrator Mayor 204-753-5105 204-753-2199 REQUEST FOR QUOTATION

More information

legend. #1 is a gas relief valve? If so does Enbridge supply with station?

legend. #1 is a gas relief valve? If so does Enbridge supply with station? Michael Pacholok, Director Purchasing and Materials Management Division City Hall, 8 th Floor, West Tower 00 Queen Street West Toronto, Ontario M5H N Joanne Kehoe Manager Construction Services May 4, 06

More information

The following sections are included in Division 27: Section : Underground Ducts and Raceways for Communication SysteMS 283

The following sections are included in Division 27: Section : Underground Ducts and Raceways for Communication SysteMS 283 P a r t IV: De s i g n St a n d a r d s 279 Division 27: Communications Ge n e ra l Professionals shall verify that all applicable portions of these standards are incorporated into the final construction

More information

1 data PIC location (with 2 ports) typically asf for multiple staff members

1 data PIC location (with 2 ports) typically asf for multiple staff members 1 Introduction 1.1 In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a utility. It should be assumed that all new

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin February 2019 Page 1 of 5 2018 CANADIAN ELECTRICAL CODE SUBJECT: Section 6 Services and service equipment Rule 6-102 Number of supply services permitted Row housing

More information

Communications Page 1 of 9

Communications Page 1 of 9 Page 1 of 9 Last Update: April 23 rd, 2014 Introduction Design In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a

More information

STREET LIGHTING. Springville City Power standard street lights will be installed in accordance with Springville City Power's Line Extension Policy.

STREET LIGHTING. Springville City Power standard street lights will be installed in accordance with Springville City Power's Line Extension Policy. General The following general requirements shall apply to street lights installed in new underground residential subdivisions or developments located within the service area of Springville City Power (within

More information

INDEX. Page SECTION 1.0: SCOPE Toronto Hydro Requirements Ontario Electrical Safety Code 1 SECTION 2.0: PURPOSE 1

INDEX. Page SECTION 1.0: SCOPE Toronto Hydro Requirements Ontario Electrical Safety Code 1 SECTION 2.0: PURPOSE 1 INDEX Page SECTION 1.0: SCOPE 1 1.1 Toronto Hydro Requirements 1 1.2 Ontario Electrical Safety Code 1 SECTION 2.0: PURPOSE 1 SECTION 3.0: DEFINITIONS AND THE INTERNATIONAL SYSTEM OF UNITS 1 3.1 Definitions

More information

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 41 UNDERGROUND ELECTRICAL CONSTRUCTION A. This section specifies the furnishing, installation, and connection of precast manholes and pullboxes with ducts

More information

Section 2: Underground

Section 2: Underground Section 2: Underground GENERAL INSTALLATION REQUIREMENTS FOR UNDERGROUND FACILITIES Underground electric service and meter location will be established by NHEC upon site visit. In some instances the type,

More information

UBC Technical Guidelines Section Edition Audio-Video Infrastructure Page 1 of 5

UBC Technical Guidelines Section Edition Audio-Video Infrastructure Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 UBC Learning Space Acoustical Guidelines.2 UBC Learning Space Design Guidelines 1.2 Coordination Requirements.1 UBC IT Audio Visual 1.3 Description.1

More information

UNDERGROUND SERVICES SECONDARY

UNDERGROUND SERVICES SECONDARY Reference UNDERGROUND SERVICES SECONDARY Underground services secondary... U- 1 General requirements for underground service... U- 2 Name of parts for underground service... U- 3 Conduit layouts... U-

More information

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS 1 Introduction 1.1 In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a utility. It should be assumed that all new

More information

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0528 Pathways. Page 1 of 6

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0528 Pathways. Page 1 of 6 1 General 1.1 Scope of work 1.1.1 The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the completion of

More information

Basic Service. This Section provides information regarding a. Introduction

Basic Service. This Section provides information regarding a. Introduction Basic Service Introduction This Section provides information regarding a new electric Basic Service for a single phase service less than or equal to 400 amps, and a three phase service less than 50kW.

More information

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING 2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING E3305.3: now reads The space equal to the width and depth of the panelboard and extending

More information

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL WARNING Before digging or trenching... Call Indiana Underground Protection Service 1-800-382-5544 AVOID BURIED POWER CABLES CONTENTS Page # 100-200 OR 400 AMP

More information

CHAPTER 11 CONDUITS AND FITTINGS

CHAPTER 11 CONDUITS AND FITTINGS CONDUITS AND FITTINGS CHAPTER 11 CONDUITS AND FITTINGS The standards and requirements for conduits and fittings used for traffic control signal and lighting systems are presented in this chapter. 11.1

More information

Please check with your local inspection authority for any additional requirements before installation.

Please check with your local inspection authority for any additional requirements before installation. Specifications for Residential Underground Electric Service Installation This brochure addresses most typical residential underground service installations. Variances for the following specifications must

More information

TYPICAL INSTALLATION INSTRUCTIONS

TYPICAL INSTALLATION INSTRUCTIONS TYPICAL INSTALLATION INSTRUCTIONS Environment One Grinder Pump Feature Identification 1. Grinder Pump Basin High density polyethylene (HDPE) 2. Accessway Cover Painted Steel 3. Electrical Quick Disconnect

More information

CONDUITS AND FITTINGS

CONDUITS AND FITTINGS CONDUIT AND FITTINGS Rigid Steel Conduit 3801 Rigid PVC Conduit 3803 HDPE Conduit 3803 Flexible Non Metallic Liquid Tight Conduit Type LFNC-B 3804 PVC Coated Urethane Lined Galvanized Rigid Steel Conduit

More information

1. Approved Manufacturers: Carlon Electrical Products, Cantex, or approved equal.

1. Approved Manufacturers: Carlon Electrical Products, Cantex, or approved equal. PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University for for Electrical System. B. Texas State University recognizes

More information

a) Line and load compartments must be separated by a stable barrier.

a) Line and load compartments must be separated by a stable barrier. 1.00 GENERAL 1.01 The electric utility shall furnish and connect all meters, instrument transformers, test switches, and meter control wiring necessary to complete the meter installation. 1.02 The customer

More information

SECTION PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY

SECTION PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY SECTION 280528 - PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Metal conduits, tubing, and fittings. 2. Nonmetallic conduits, tubing, and fittings. 3.

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 26 ELECTRICAL SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 26 ELECTRICAL SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS SECTION 260533 - RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes raceways, fittings, boxes, enclosures, and cabinets for electrical wiring. B. See Division

More information

TS 803 DUCTS DUCT INSTALLATION, PROTECTION AND MARKING WITHIN A TRENCH OPEN TRENCH DUCT INSTALLATION PROFILE

TS 803 DUCTS DUCT INSTALLATION, PROTECTION AND MARKING WITHIN A TRENCH OPEN TRENCH DUCT INSTALLATION PROFILE TORONTO TRANSPORTATION March 2012 TS 803 DUCTS TABLE OF CONTENTS 1. DRAWINGS TTD 803.001 TTD 803.010 DUCT INSTALLATION, PROTECTION AND MARKING WITHIN A TRENCH OPEN TRENCH DUCT INSTALLATION PROFILE 2. CONSTRUCTION

More information

FORMAT Technical specifications content and numbering system shall be based on 2004 CSI MasterFormat.

FORMAT Technical specifications content and numbering system shall be based on 2004 CSI MasterFormat. DIVISION 27 00 00 COMMUNICATIONS FORMAT Technical specifications content and numbering system shall be based on 2004 CSI MasterFormat. BASIS OF DESIGN Design guidelines supplement building, fire, and other

More information

[Type text] Heber Light & Power. Developers & Excavators. Electrical Service Requirements Manual

[Type text] Heber Light & Power. Developers & Excavators. Electrical Service Requirements Manual [Type text] Heber Light & Power Developers & Excavators Electrical Service Requirements Manual May 2017 E.1.1 - GENERAL REQUIREMENTS PURPOSE This section was prepared to aid developers, contractors, engineers

More information

Residential Electric Policy

Residential Electric Policy Residential Electric Policy 7/19/16 1 Table of Contents General Information..3 Construction.3 Ownership....3 Underground Service...3 Apartments/Multi-Unit Dwellings..3 Modular and Manufactured Homes...3

More information

Homeowner electrical wiring guide. Including the 2015 Canadian Electrical Code amendments

Homeowner electrical wiring guide. Including the 2015 Canadian Electrical Code amendments Homeowner electrical wiring guide Including the 2015 Canadian Electrical Code amendments Table of Contents Homeowner electrical wiring guide... 1 Required inspections... 2 Rough inspections (prior to any

More information

Design Guidelines for Facilities Construction:

Design Guidelines for Facilities Construction: Western Michigan University Office of Information Technology & Campus Planning, Design & Construction Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG17-1 Outside / Inter-building Systems

More information

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC).

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC). SECTION 16111 CONDUITS PART 1 - GENERAL 1.01 DESCRIPTION A. General: Provide conduits, complete, as shown, specified or required per Contract Documents. Principal items include: 1. Rigid aluminum conduit.

More information

Student Services & Classroom Addition

Student Services & Classroom Addition SECTION 260533 - RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes raceways, fittings, boxes, enclosures, cabinets, and track busway for electrical wiring.

More information

SECTION HORIZONTAL CABLING

SECTION HORIZONTAL CABLING PART 1 - GENERAL 1.1 SUMMARY SCOPE OF WORK SECTION 25160 HORIZONTAL CABLING 1. Horizontal cabling is the portion of the cabling system that extends from the work area to the Telecommunications Room or

More information

WIRING METHODS CHAPTER 38

WIRING METHODS CHAPTER 38 CHAPTER 38 WIRING METHODS SECTION E3801 GENERAL REQUIREMENTS E3801.1 Scope. This chapter covers the wiring methods for services, feeders and branch circuits for electrical power and distribution. E3801.2

More information

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding.

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding. ALLIANT ENERGY CENTER PAVILIONS Project No. 2013 027 SECTION 27 11 00 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Electric Service Handbook

Electric Service Handbook R E S I D E N T I A L Electric Service Handbook 2015 Building or remodeling a home in Clark County? This handbook provides information regarding current Clark Public Utilities standards and requirements

More information

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6.2 OVERHEAD SERVICES Wiring of any premises for connection

More information

Post Office Box 500 Carson, WA Phone (509) Fax (509) Toll Free (800)

Post Office Box 500 Carson, WA Phone (509) Fax (509) Toll Free (800) Public Utility District No. 1 of Skamania County Post Office Box 500 Carson, WA 98610 Phone (509) 427-5126 Fax (509) 427-8416 Toll Free (800) 922-5329 ELECTRIC LINE EXTENSION If you are purchasing property

More information

New Conduit Specification

New Conduit Specification New Conduit Specification Combines Portions of Sections 715, 783 & 992 into New Section 630. Coordinated Effort Between Traffic Operations, ITS, Lighting, Construction, and Industry New Conduit Specification

More information

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11 Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11 Underground Residential Distribution (URD) Index General Discussion... 1-2 Description... 3-7 Drawings (Available

More information

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6.2 OVERHEAD SERVICES Wiring of any premises for connection

More information

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

CONSTRUCTION SPECIFICATION FOR GROUNDING

CONSTRUCTION SPECIFICATION FOR GROUNDING ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 609 NOVEMBER 2001 CONSTRUCTION SPECIFICATION FOR GROUNDING TABLE OF CONTENTS 609.01 SCOPE 609.02 REFERENCES 609.03 DEFINITIONS - Not Used 609.04 DESIGN

More information

nbn Lead-in Trenching Requirements

nbn Lead-in Trenching Requirements nbn Lead-in Trenching Requirements Engineering Document number F0002-31-11578 Document category Guide Author Engineering Status Approved Issue date 15 JULY 2016 Revision number 2.1 Classification Public

More information

B. Provide a complete conduit system with associated couplings, connectors, and fittings.

B. Provide a complete conduit system with associated couplings, connectors, and fittings. SECTION 26 05 33 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 260500. B. Provide a complete conduit system with associated couplings, connectors, and fittings. 1.02 RELATED

More information

.2 The maximum length of horizontal cable shall not exceed 90 meters in any 360 degree direction.

.2 The maximum length of horizontal cable shall not exceed 90 meters in any 360 degree direction. 1.0 GENERAL 1.1 DOCUMENTS.1 This section of the Specification forms part of the Contract Documents and is to be read, interpreted, and coordinated with all other parts. 1.2 SUMMARY.1 Section Includes:

More information

TS 804 CABLES TABLE OF CONTENTS TRAFFIC SIGNAL EQUIPMENT POLE WIRING DIAGRAM LOCATIONS WITH CENTRE MEDIANS

TS 804 CABLES TABLE OF CONTENTS TRAFFIC SIGNAL EQUIPMENT POLE WIRING DIAGRAM LOCATIONS WITH CENTRE MEDIANS TORONTO TRANSPORTATION January 2012 TS 804 CABLES TABLE OF CONTENTS 1. DRAWINGS TTD 804.001 TTD 804.002 TTD 804.003 TTD 804.005 TTD 804.006 TTD 804.007 TTD 804.010 TTD 804.015 TTD 804.020 TTD 804.025 TTD

More information

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE ONTARIO PROVINCIAL STANDARD SPECIFICATION OPSS.PROV 604 NOVEMBER 2017 CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

Building Design Standards December 2009 SECTION COMMUNICATIONS HISTORY DRAWINGS

Building Design Standards December 2009 SECTION COMMUNICATIONS HISTORY DRAWINGS SECTION 27 00 00 COMMUNICATIONS HISTORY The University Technology Services (UTS) Building Design Specification is a collection of requirements which architects and engineering consultants must adhere to

More information

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp,

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp, TITLE 14 CHAPTER 10 PART 4 HOUSING AND CONSTRUCTION ELECTRICAL CODES 2011 NEW MEXICO ELECTRICAL CODE 14.10.4.1 ISSUING AGENCY: The Construction Industries Division of the Regulation and Licensing Department.

More information

PRIMARY LINE EXTENSION

PRIMARY LINE EXTENSION PRIMARY LINE EXTENSION Installation of new electric service to an empty parcel/lot or extending a transformer to within 150' of proposed meter location. This includes installing a permanent branch, addition,

More information

GV 001 Equipment Bases and Enclosures General Information

GV 001 Equipment Bases and Enclosures General Information Eq u ip me n tba s e s a n d En c lo s u re s Ge n e ra lin fo rma tio n E n g in e e r :R.An th o n GV0 0 1 Ap p r o v e r :Jo s h u a Jo n e s Ap r 1 7 2 0 Ap r1 7 GV 001 Equipment Bases and Enclosures

More information

SECTION ELECTRICAL CABLE. 1. Trench excavation, backfill, and compaction; Section

SECTION ELECTRICAL CABLE. 1. Trench excavation, backfill, and compaction; Section 02735-1 of 5 SECTION 02735 ELECTRICAL CABLE 02735.01 GENERAL A. Description Electrical cable installation shall include, but not necessarily be limited to, furnishing and placing electrical cable as shown

More information

OVERHEAD SERVICES - SECONDARY

OVERHEAD SERVICES - SECONDARY OVERHEAD SERVICES - SECONDARY Contents - Overhead Services... O-1 General Requirements for Overhead Service... O-2 Names of Parts for Overhead Service... O-3 Service Attachment on an Unguyed Service Mast...

More information

The University of Texas at Austin September 30, 2011

The University of Texas at Austin September 30, 2011 SECTION 27 11 00 COMMUNICATIONS EQUIPMENT ROOM FITTINGS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes basic communications room requirements. Refer to T series drawings for specific communication

More information

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 604 NOVEMBER 2004 CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

CITY OF UNION, OREGON TECHNICAL SPECIFICATIONS SECTION 9 UNDERGROUND UTILITIES

CITY OF UNION, OREGON TECHNICAL SPECIFICATIONS SECTION 9 UNDERGROUND UTILITIES A. GENERAL 1. Scope. These specifications cover the installation of the utility systems and appurtenances for the electrical power, telephone, gas, and television as shown in the Drawings. The Work includes,

More information

Procurement Services SVC East Fowler Avenue Tampa, Florida (813)

Procurement Services SVC East Fowler Avenue Tampa, Florida (813) Procurement Services SVC 1073 4202 East Fowler Avenue Tampa, Florida 33620 (813) 974-2481 Web Address: https://www.usf.edu/business-finance/purchasing/public-bids/rfi.aspx October 12, 2018 Invitation to

More information

UNM IT/Telecommunications Guide Specification Communications Underground Ducts, Raceways and Structures /27/06

UNM IT/Telecommunications Guide Specification Communications Underground Ducts, Raceways and Structures /27/06 Communications Underground Ducts, Structures and Raceways PART 1: GENERAL The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification

More information

Request for Proposal. I. Background. Objectives. Summary Scope of Work. Park City Fire Service District Fiber Upgrade Duct Installation

Request for Proposal. I. Background. Objectives. Summary Scope of Work. Park City Fire Service District Fiber Upgrade Duct Installation Request for Proposal Park City Fire Service District Fiber Upgrade Duct Installation I. Background The Park City Fire Service District (PCFSD) provides emergency services and prevention programs to protect

More information

UMass Amherst Information Technology. Design and Construction Guidelines

UMass Amherst Information Technology. Design and Construction Guidelines UMass Amherst Information Technology Design and Construction Guidelines December 2018 2.13 INFORMATION TECHNOLOGY AND COMMUNICATIONS 2.13.1. General A. UMass IT/ Cable Engineering Services (CES) is here

More information

EFFECTIVE DATE: July 1, 2008, unless a later date is cited at the end of a section. [ NMAC - Rp,

EFFECTIVE DATE: July 1, 2008, unless a later date is cited at the end of a section. [ NMAC - Rp, TITLE 14 CHAPTER 10 PART 4 HOUSING AND CONSTRUCTION ELECTRICAL CODES 2008 NEW MEXICO ELECTRICAL CODE 14.10.4.1 ISSUING AGENCY: The Construction Industries Division of the Regulation and Licensing Department.

More information

EXTERIOR ASSIST PHONES REVISIONS Summary of Change Date 4/11/11 Blue Light Updated Manufacturer Information

EXTERIOR ASSIST PHONES REVISIONS Summary of Change Date 4/11/11 Blue Light Updated Manufacturer Information EXTERIOR ASSIST PHONES REVISIONS Revision Section Summary of Change Date 4/11/11 Blue Light Updated Manufacturer Information UNIVERSITY CONTACT: Network Services (302) 831-3722 EXTERIOR ASSIST PHONES Table

More information

DIVISION STRUCTURED CABLE

DIVISION STRUCTURED CABLE FORMAT 1. Technical specifications content and numbering system shall be based on the most current CSI Master Format. BASIS OF DESIGN 1. Design guidelines supplement building, fire, and other health, safety

More information

A/E Design Guide for Drawings and Spec Section Communications Infrastructure.

A/E Design Guide for Drawings and Spec Section Communications Infrastructure. Instructions to A/E: Communications Infrastructure specification 27 17 51 shall be included and coordinated with the master specifications unless directed otherwise by the University Project Manager. All

More information

A WORK PROCESS SCHEDULE

A WORK PROCESS SCHEDULE Appendix A WORK PROCESS SCHEDULE AND RELATED INSTRUCTION OUTLINE Appendix A WORK PROCESS SCHEDULE OCCUPATION TITLE: ELECTRICIAN O*NET-SOC CODE: 47-2111.00 RAPIDS CODE: 0159 This schedule is attached to

More information

1993 SPECIFICATIONS CSJ SPECIAL SPECIFICATION ITEM 4110 CONCRETE ENCASED DUCT BANK

1993 SPECIFICATIONS CSJ SPECIAL SPECIFICATION ITEM 4110 CONCRETE ENCASED DUCT BANK 1993 SPECIFICATIONS CSJ 581-1-95 SPECIAL SPECIFICATION ITEM 4110 CONCRETE ENCASED DUCT BANK 1. DESCRIPTION. This Item shall govern for the furnishing and installation of all materials and equipment for

More information

Primary Contact: Owner Customer Electrician Builder

Primary Contact: Owner Customer Electrician Builder EL PASO ELECTRIC COMPANY RESIDENTIAL REQUEST FOR SERVICE FORM Responsible Party: Property Owner Name: Phone: Email: Customer Name: Phone: Email: Electrician Name: Phone: Email: Builder/Contractor: Phone:

More information

UNIVERSITY OF ALABAMA AT BIRMINGHAM DEPARTMENT OF FACILITIES PLANNING. NAME: Communications Equipment Room ORIGINAL DATE:

UNIVERSITY OF ALABAMA AT BIRMINGHAM DEPARTMENT OF FACILITIES PLANNING. NAME: Communications Equipment Room ORIGINAL DATE: UNIVERSITY OF ALABAMA AT BIRMINGHAM DEPARTMENT OF FACILITIES PLANNING FACILITIES STANDARD PURPOSE: 1. The general purpose of each Facilities Standard is to provide minimal criteria for construction materials

More information

Telecommunications Design Guidelines University of Alberta Cabling Standards (version 2.1)

Telecommunications Design Guidelines University of Alberta Cabling Standards (version 2.1) February 7, 2008 Telecommunications Design Guidelines University of Alberta Cabling Standards (version 2.1) Introduction: For all planned building projects on the U of A campus, Facilities Management,

More information

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 604 NOVEMBER 2008 CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 7/14/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 7/14/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 7/14/10 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. We were turned down for an underground installation of

More information

A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails.

A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails. SECTION 27 11 00 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

c. Army Reserve Design Process Submittal Requirements (DPSR) d. USARC G-2/6 IT Design Criteria Updates, 17 October 2013 ( ENCLOSURE 1)

c. Army Reserve Design Process Submittal Requirements (DPSR) d. USARC G-2/6 IT Design Criteria Updates, 17 October 2013 ( ENCLOSURE 1) CELRL-PM-R October ARCOS BULLETIN - SUBJECT: IT Design Criteria Updates. REFERENCE: a. UFC --0, Army Reserve Facilities b. Army Reserve IT Manual, Change c. Army Reserve Design Process Submittal Requirements

More information

OREGON UNIVERSITY SYSTEM STANDARD PUBLIC IMPROVEMENT CONTRACT BID FORM. FROM: Name of Contractor

OREGON UNIVERSITY SYSTEM STANDARD PUBLIC IMPROVEMENT CONTRACT BID FORM. FROM: Name of Contractor OREGON UNIVERSITY SYSTEM STANDARD PUBLIC IMPROVEMENT CONTRACT BID FORM OUS CAMPUS: PROJECT: BID CLOSING: University of Oregon Chiles Hall 3 rd Floor Business Technology Center Improvements Project June

More information

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS Greenbook Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 08-15-17 Rev. #06:

More information

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property 2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical

More information

ZG Scope. 2 Applicable Documents. 3 General. 4 Stock Item Numbers. Padvault Single-Phase Residential, 2.1 PacifiCorp Material Specifications

ZG Scope. 2 Applicable Documents. 3 General. 4 Stock Item Numbers. Padvault Single-Phase Residential, 2.1 PacifiCorp Material Specifications 1 Scope This specification outlines the minimum requirements for a 48 48 padvault for single-phase primary service. Single-phase transformers and sectionalizers (elbow switched cabinets) can be mounted

More information

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL WARNING Before digging or trenching... Call 811 Indiana Underground Protection Service 1-800-382-5544 AVOID BURIED POWER CABLES 4901 East Park 30 Drive P.O.

More information

Specifications for Electrical Underground Residential Distribution Systems

Specifications for Electrical Underground Residential Distribution Systems Specifications for Electrical Underground Residential Distribution Systems Specification DDS-2 Revision 13, February 2010 ONCOR ELECTRIC DELIVERY COMPANY SPECIFICATIONS FOR ELECTRICAL UNDERGROUND RESIDENTIAL

More information

SECTION GROUNDING

SECTION GROUNDING SECTION 16450 GROUNDING PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies general grounding and bonding requirements of electrical and telecommunication installations for personnel safety, equipment

More information

UNDERGROUND DROP CABLE CONDUIT INSTALLATION AND SPECIFICATION GUIDELINES FOR SINGLE DWELLING RESIDENTIAL APPLICATIONS

UNDERGROUND DROP CABLE CONDUIT INSTALLATION AND SPECIFICATION GUIDELINES FOR SINGLE DWELLING RESIDENTIAL APPLICATIONS UNDERGROUND DROP CABLE CONDUIT INSTALLATION AND SPECIFICATION GUIDELINES FOR SINGLE DWELLING RESIDENTIAL APPLICATIONS 1. SPECIFICATIONS This document details the specifications for the installation of

More information

c. Army Reserve Design Process Submittal Requirements (DPSR) d. USARC G-2/6 IT Design Criteria Updates, 26 March 2013 ( ENCLOSURE 1)

c. Army Reserve Design Process Submittal Requirements (DPSR) d. USARC G-2/6 IT Design Criteria Updates, 26 March 2013 ( ENCLOSURE 1) CELRL-PM-R March ARCOS BULLETIN - SUBJECT: IT Design. REFERENCE: a. UFC --0, Army Reserve Facilities b. Army Reserve IT Manual, Change c. Army Reserve Design Process Submittal Requirements (DPSR) d. USARC

More information

RESEARCH AND TECHNOLOGY BUILDING RENOVATION MAY 18, 2009 SECTION COMMUNICATIONS

RESEARCH AND TECHNOLOGY BUILDING RENOVATION MAY 18, 2009 SECTION COMMUNICATIONS SECTION 27 00 00 PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following items for wiring systems used as signal pathways for voice and highspeed data transmission: 1. Communication outlets.

More information

PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION

PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION Permit No. 175 Beaver Drive, P.O. Box 486 DuBois, PA 15801 Phone: 814-375-1111 Fax: 814-375-1117 Toll Free: 855-PENNSAF LOCATION OF PROPOSED

More information

SPECIAL SPECIFICATION 6623 Multi-Duct Conduit System

SPECIAL SPECIFICATION 6623 Multi-Duct Conduit System 2004 Specifications Houston District SPECIAL SPECIFICATION 6623 Multi-Duct Conduit System 1. Description. Furnish and place a Multi-Duct Conduit (MDC) system that is suitable for installation in an outdoor

More information

The Medical Center Company Electrical System Installation Requirements

The Medical Center Company Electrical System Installation Requirements The Medical Center Company Electrical System Installation Requirements Introduction System Description Approvals Scheduling of Power Shutdowns and Power Transfers 5. Service Entrance 6. Feeder Systems

More information

Central Lincoln PUD Single-Family Residential Guidelines & Standards April 21, 2017

Central Lincoln PUD Single-Family Residential Guidelines & Standards April 21, 2017 Central Lincoln PUD Single-Family Residential Guidelines & Standards April 21, 2017 Overview of Hook-Up Procedures: The following is a general outline of how you get a new electrical service for a single-family

More information

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION SECTION 74 AIRPORT OBSTRUCTION LIGHTS (FAA L-119) 74-1 GENERAL The Contractor shall perform all work required by the plans and specifications for construction of obstruction lights in accordance with the

More information

Electric Service Standards

Electric Service Standards V: 1 of 6 A. Padmounted Requirements Complete requirements are contained in FPL specifications given to Customers for individual projects. Typical pad mounted transformer requirements include, but are

More information

Telecommunication Spaces

Telecommunication Spaces Telecommunication Spaces October 19, 2016 Page 1 Revision History Telecommunication Spaces Standard Effective Date Email Version Contact Phone OIT-TS strevena@csustan.edu 1.0 Stan Trevena 209.667.3137

More information

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents DIVISION 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN Contents 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION 13 00 60 LIST OF FIGURES... 6 Page 1 of 6 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN 1. General

More information

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section Data System Page 1 of 7

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section Data System Page 1 of 7 Issued 2006/08/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment

More information

Merrimac Municipal Light Department. Commercial Developments Policy

Merrimac Municipal Light Department. Commercial Developments Policy Merrimac Municipal Light Department Commercial Developments Policy General: This document provides specific instructions for the provision of underground electrical facilities associated with the construction

More information

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS SECTION 16711-27 05 28.33 PART 1 - GENERAL 1.01 SUMMARY A. This section includes Labor, materials and equipment necessary to complete the installation required for the items specified under this Section,

More information