SECTION GYPSUM CEMENTITIOUS UNDERLAYMENT
|
|
- Maud Black
- 6 years ago
- Views:
Transcription
1 SECTION GYPSUM CEMENTITIOUS UNDERLAYMENT PART 1 GENERAL 1.01 SUMMARY A. This is the recommended specification for Gyp-Crete Floor Underlayment. A. Gyp-Crete gypsum cement B. Maxxon Floor Primer C. Maxxon Overspray 1.03 QUALITY ASSURANCE A. Installer's Qualifications: Installation of Gyp-Crete shall be by an applicator authorized by the Maxxon Corporation using Maxxon approved mixing and pumping equipment DELIVERY, STORAGE AND HANDLING A. General Requirements: Materials shall be delivered in their original, unopened packages, and protected from exposure to the elements. Damaged or deteriorated materials shall be removed from the premises SITE CONDITIONS A. Environmental Requirements: Before, during and after installation of Gyp-Crete, building interior shall be enclosed and maintained at a temperature above 50 degrees F (10 degrees C). PART 2 PRODUCTS 2.01 MATERIALS A. Gypsum Cement: Floor underlayment Gyp-Crete gypsum cement as manufactured by the Maxxon Corporation, Hamel, MN. All others must receive prior approval. B. Sand Aggregate: Sand shall be 1/8 inch (3 mm) or less, washed masonry or plaster sand, meeting requirements of Maxxon Corporation Sand Specifications 101. C. Mix Water: Potable, free from impurities. D. Subfloor Primer: Maxxon Floor Primer E. Sealer: Maxxon Overspray 2.02 MIX DESIGNS A. General Requirements: Mix proportions and methods shall be in strict accordance with product manufacturer recommendations. Elderly Apartment
2 PART 3 EXECUTION 3.01 PREPARATION A. Condition and Cleaning of Subfloor: Subfloor shall be structurally sound. General Contractor shall clean subfloor to remove mud, oil, grease, and other contaminating factors before the arrival of the Gyp-Crete underlayment crew. B. Leak Prevention: Fill cracks and voids with a quick setting patching or caulking material where leakage of Gyp-Crete could occur. C. Priming Subfloor: Prime the subfloor using the Maxxon Floor Primer. Priming instructions may vary according to the type of substrate, multiple coats may be necessary. D. Expansion Joints: Allow joints to continue through the Gyp-Crete at the same width APPLICATION OF CEMENTITIOUS FLOORING A. Scheduling: Application of Gyp-Crete shall not begin until the building is enclosed, including roof, windows, doors and other fenestration. Install after drywall installation unless tenant finish requirements identify partitioning after the pour. B. Application: Place Gyp-Crete at 3/4 inch (19 mm) minimum over wood frame, 1/2 inch (13 mm) minimum over plank or poured in place concrete. Spread and screed Gyp-Crete to a smooth surface. Except at authorized joints, place Gyp-Crete as continuously as possible until application is complete so that no Gyp- Crete product slurry is placed against Gyp-Crete product that has obtained its initial set. C. Drying: General Contractor shall provide continuous ventilation and adequate heat to rapidly remove moisture from the area until the Gyp-Crete is dry. General Contractor shall provide mechanical ventilation if necessary. Under the above conditions, for 3/4 inch (19 mm) thick i. Gyp-Crete, 5-7 days is usually adequate drying time. To test for dryness, tape a 24 inch by 24 inch (609 mm by 609 mm) section of plastic or high density rubber mat to the surface of the underlayment. After hours, if no condensation occurs, the underlayment shall be considered dry. Perform dryness test 5-7 days after pour PREPARATION FOR INSTALLATION OF GLUE DOWN FLOOR GOODS A. Sealing: Seal all areas that receive glue down floor goods with Maxxon Overspray according to the Maxxon Corporation's specifications. Any floor areas where the surface has been damaged shall be cleaned and sealed regardless of floor covering to be used. Where floor goods manufacturers require special adhesive or installation systems, their requirements supersede these recommendations. B. Floor Goods Procedures: See the Maxxon Corporation's "Procedures for Attaching Finished Floor Goods to Maxxon Underlayments" brochure for guidelines for installing finished floor goods. This procedure is not a warranty and is to be used as a guideline only FIELD QUALITY CONTROL Elderly Apartment
3 A. Slump Test: Gyp-Crete mix shall be tested for slump as it's being pumped using a 2 inch by 4 inch (50 mm by 101 mm) cylinder resulting in a patty size of 8 inches (203 mm) plus or minus 1 inch (25 mm) diameter. B. Field Samples: At least one set of 3 molded cube samples shall be taken from each day's pour during the Gyp-Crete application. Cubes shall be tested as recommended by the Maxxon Corporation in accordance with modified ASTM C 472. Test results shall be available to architect and/or contractor upon request from applicator PROTECTION A. Protection From Heavy Loads: During construction, place temporary wood planking over Gyp-Crete wherever it will be subject to heavy wheeled or concentrated loads. END OF SECTION Elderly Apartment
4 SECTION MASONRY ANCHORS AND ACCESSORIES PART 1 GENERAL 1.1 SECTION INCLUDES A. Masonry veneer anchors and ties. B. Stone veneer anchors and ties. C. Masonry accessories. 1.2 RELATED SECTIONS A. Section Unit Masonry Assemblies. B. Section Cut Stone Veneer. C. Section Stone Masonry Veneer. 1.3 REFERENCES A. ASCE/ACI Specifications for Masonry Structures; B. ASTM A 153/A 153M - Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware; C. ASTM A Standard Specification for Stainless and Heat-Resisting Chromium- Nickel Steel Plate, Sheet, and Strip; D. ASTM A 240/A 240M - Standard Specification for Heat-Resisting Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels; 1998b. E. ASTM A Standard Specification for Stainless Steel Bars and Shapes; 1998b. F. ASTM A 479/A 479M - Standard Specification for Stainless and Heat-Resisting Steel Bars and Shapes for Use in Boilers and Other Pressure Vessels; 1997a. G. ASTM A 580/A 580M - Standard Specification for Stainless Steel Wire; H. ASTM A 653/A 653M - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process; 1998.
5 I. ASTM B 633 Standard Specification for Electrodeposited Coatings of Zinc on Iron and Steel; (Reapproved 1994). 1.4 SUBMITTALS A. Submit under provisions of Section B. Product Data: Manufacturer's data on each type of product furnished. PART 2 PRODUCTS 2.1 MANUFACTURERS A. Acceptable Manufacturer: Heckmann Building Products Inc., 1501 N. 31st Avenue Melrose Park, IL Tel: (708) Fax: Heckmann@worldnet.att.net. Website: B. Requests for substitutions will be considered in accordance with provisions of Section C. Substitutions: Not permitted. 2.2 APPLICATIONS A. Provide anchoring systems that comply with ACI 530.1/ASCE 6/TMS MATERIALS A. Steel Types 1. Stainless Steel: Type 304. a. Sheet Metal: ASTM A 167 or ASTM A 240/A 240M. b. Wire: ASTM A 580/A 580M. c. Bars: ASTM A 479/A 479M, annealed and ground.
6 B. Products d. Plates, Bars, and Shapes: ASTM A 167 or ASTM A Hot-Dip Galvanized Steel: Hot-dip galvanized after fabrication in accordance with ASTM A 153/A 153M, Class B Electro-Galvanized Steel: Electro-galvanized after fabrication in accordance with ASTM B 633, Service Condition 1. a. Wire: Minimum 3/16 inch (4.76 mm) diameter. 4. Mill Galvanized Steel: a. Sheet Metal: ASTM A 653/A 653M, G60 coating. b. Wire: ASTM A 641, regular coating; minimum 3/16 inch (4.76 mm) diameter. 1. NO. 374 STEEL-WICHÔ TELESCOPING REBAR POSITIONER [Small for [1/2 inch (13 mm)][5/8 inch (16 mm)] rebar][large for 3/4 inch (19 mm)][7/8 inch (22 mm)][1 inch (25 mm) rebar] 2. NO. 375 BARLOC REBAR CONNECTOR 24 gage x 7 inches (178 mm) long x [1/2 inch (13 mm) for 1/2 inch (13 mm) rebar][3/4 inch (19 mm) for 5/8 inch (16 mm) or 3/4 inch (19 mm) rebar] 3. NO. 376 REBAR POSITIONER 1/8 inch diameter for [8 inch (203 mm) walls][12 inch (305 mm) walls)] with 1 inch (25 mm) diameter eyes. PART 3 EXECUTION 3.1 INSTALLATION A. Install as specified in applicable masonry section(s) and in accordance with manufacturer's instructions. END OF SECTION
7 SECTION WELDED WIRE FABRIC PART 1 GENERAL 1.01 SECTION INCLUDES A. The work specified in this Section consists of furnishing and installing reinforcement for concrete structures RELATED SECTIONS A. Cast-In- Place Concrete: Section REFERENCES A. American Concrete Institute: 1. ACI 315; Details and Detailing of Concrete Reinforcement. 2. ACI 318; Building Code Requirements for Reinforced Concrete. B. American Society for Testing and Materials 1. ASTM A 82; Specification for Cold-Drawn Steel Wire for Concrete Reinforcement. 2. ASTM A 185; Specification for smooth Welded Steel Wire Fabric for Concrete Reinforcement C. Concrete Reinforcing Steel Institute: CRSI, Manual of Standard Practice for Reinforcing Concrete Construction SUBMITTALS A. Shop Drawings and Product Data: 1. Prepare shop drawings of concrete reinforcement in accordance with American Concrete Institute s ACI Product Data: Submit manufacturer s descriptive product data and current specification for each product specified herein, include installation instructions DELIVERY, STORAGE, AND HANDLING A. Storage of Materials: 1. Store reinforcing materials in a manner to prevent excessive rusting and fouling with dirt, grease and other bond-breaking coatings Elderly Apartment Welded Wire Fabric
8 1.06 PROJECT CONDITIONS A. Protection: Protect in-place from excessive construction traffic and other work. PART 2 PRODUCTS 2.01 MATERIALS A. Reinforcing Steel 1. Wire: ASTM A82 2. Welded Wire Fabric: ASTM A Metal Accessories: CRSI Manual of Standard Practice for Reinforcing Concrete FABRIFICATION A. Fabricate reinforcement to the dimensions indicated on the Drawings and within the tolerances given in ACI 315, PART 3 EXECUTION 3.01 INSPECTION A. Notify Construction Manager 48 hours before placing concrete so he can inspect placement of metal reinforcement INSTALLATION A. Install welded wire fabric as indicated, lapping joints eight inches and wiring securely. Extend welded wire fabric to within two inches of sides and ends of slabs. B. Cleaning: Clean or otherwise protect metal reinforcement so that at the time concrete is placed, reinforcement is free of rust, scale or other coatings that will destroy or reduce bond. END OF SECTION Welded Wire Fabric Elderly Apartment
9 CEMENTITIOUS WOOD FIBER SYSTEMS SECTION OSB PART 1: GENERAL 1.01 RELATED DOCUMENTS A. Conditions of the Contract and portions of Division One of this Project Manual apply to this Section as though repeated herein WORK INCLUDED A. Cementitious Wood Fiber Deck. B. Structural Purlins. C. Accessories required for a complete installation RELATED WORK A. Paint: Section Field painting of exposed to view surfaces of cementitious wood fiber deck surfaces SUBMITTALS A. Submit the following: 1. Set of 12 inch square samples for each wood fiber deck unit required, showing full range of exposed texture to be expected in completed work. 2. Set of labeled 12 inch long samples of each exposed structural purlins. 3. Labeled set of all accessories required for a complete installation. 4. Manufacturer's product specifications and installation instructions for each cementitious wood fiber deck and Elderly Apartments/ 10/23/ OSB
10 purlin system required, including certified laboratory test reports DELIVERY, STORAGE AND HANDLING A. Deliver materials in original, unopened, protective packaging, with manufacturer's labels indicating brand name, deck style, size, and thickness, legible and intact. B. Store materials in original protective packaging to prevent soiling, physical damage or wetting. C. Store cartons open at each end to stabilize moisture content and temperature QUALITY ASSURANCE A. Deck units shall be formed and cured in a continuous process using gas fired heat for curing. B. Moisture content of units shall not exceed 12 percent at the time of delivery. 1. The Owner's Representative shall have the option to test up to 5 percent of delivered for moisture content REGULATORY REQUIREMENTS A. Underwriter's Laboratories Fire Rated Assembly: [P253 {1} {1-/2} hour {restrained} {unrestrained}] [P262 {restrained} {unrestrained}] [P262 1 hour {restrained} {unrestrained}] [P402 2 hour {restrained} {unrestrained}] [P403 2 hour {restrained} {unrestrained}] [P675 1 hour {restrained} {unrestrained}] [P678 1 hour {restrained} {unrestrained}] PART 2: PRODUCTS 2.01 DECK TYPE 1 A. Tectum I Roof Deck System as produced by Tectum Inc.; Newark, Ohio B. Characteristics: 1. Thickness: [1-1/2] [2] [2-1/2] [3] inches. Elderly Apartments/ 10/23/ OSB
11 2. Form: [Plank with tongue and groove edges and square ends] [Tile with rabbeted edges and {square} {tongue and groove} ends]. 3. Finish: [Natural] [Painted White]. 4. Width and Length: Refer to [structural] drawings DECK TYPE 2 NOTE: This is a Tectum and urethane composite panel. A. Tectum II Roof Deck System as produced by Tectum Inc.; Newark, Ohio B. Characteristics: NOTE: Select one of the options below as structural load design and insulating factor dictates. {1. Substrate Thickness: 2 inches. a. Foam Thickness: [3/4] [1] [1-1/2] [2] [2-1/2] [3] inch(es).} {2. Substrate Thickness: 2-1/2 inches. a. Foam Thickness: [3/4] [1] [1-1/2] [2] [2-1/2] inch(es).} Elderly Apartments/ 10/23/ OSB
12 {3. Substrate Thickness: 3 inches. a. Foam Thickness: [3/4] [1] [1-1/2] [2] inch(es).} 4. Width and Length: Refer to [structural] drawings. 5. Finish: [Natural] [Painted White] DECK TYPE 3 NOTE: This is a Tectum and 7/16 inch oriented strand board (OSB) nailbase composite panel. A. Tectum NS Roof Deck System as produced by Tectum Inc.; Newark, Ohio B. Characteristics: 1. Total Thickness: [2] [2-1/2] [3] [3-1/2] inches. 2. Width and Length: Refer to [structural] drawings. 3. Finish: [Natural] [Painted White] DECK TYPE 4 NOTE: This is a Tectum, expanded polystyrene and 7/16 inch oriented strand board (OSB) nailbase composite panel. Elderly Apartments/ 10/23/ OSB
13 A. Tectum "E" Roof Deck System as produced by Tectum Inc.; Newark, Ohio B. Characteristics: 1. Substrate Thickness: 1-1/2 inches. 2. Foam Total Thickness: [3/4 2-3/4] [1 3] [1-1/2 3-1/2] [2 4] [3 5] [4 6] [5 7] [6 8] [6-1/2 8-1/2] inches. 3. Width and Length: Refer to [structural] drawings. 4. Finish: [Natural] Painted White] DECK TYPE 5 NOTE: This is an extruded polystyrene and 7/16 inch oriented strand board composite panel. (OSB) nailbase Tectum A. Tectum III Roof Deck System as produced by Tectum Inc.; Newark, Ohio B. Characteristics: 1. Substrate Thickness: 1-1/2 inches. 2. Foam Total Thickness: [1-1/2 3-1/2] [2 4] [3 5] [4 6] [5 7] [6 8] inches. 3. Width and Length: Refer to [structural] drawings. Elderly Apartments/ 10/23/ OSB
14 4. Finish: [Natural] Painted White] DECK TYPE 6 NOTE: This is a Tectum Roof Deck Plank with tongue and groove edges and is available in all Tectum Roof Deck Systems. Tectum Long Span Roof Deck Plank is available in Tectum I and Tectum II Systems. A. Tectum ["Roof Deck Plank"] [ "Long Span Plank"] Roof Deck System as produced by Tectum Inc.; Newark, Ohio NOTE: Select option "B." or "C." below as the Project dictates. {B. Roof Deck Plank Characteristics: 1. Thickness: [1-1/2] [2] [2-1/2] [3] inches. 2. Form: Plank with tongue and groove edges and square ends. 3. Finish: [Natural] [Painted White]. 4. Width and Length: Refer to [structural] drawings.} {{C. Long Span Roof Deck Plank Characteristics: Elderly Apartments/ 10/23/ OSB
15 NOTE: Select one of the options below as structural load design and insulating factor dictates. {1. Substrate Thickness: 2 inches. a. Foam Thickness: [3/4] [1] [1-1/2] [2] [2-1/2] [3] inch(es).} {2. Substrate Thickness: 2-1/2 inches. a. Foam Thickness: [3/4] [1] [1-1/2] [2] [2-1/2] inch(es).} {3. Substrate Thickness: 3 inches. a. Foam Thickness: [3/4] [1] [1-1/2] [2] inch(es).} 4. Width and Length: Refer to [structural] drawings. 5. Finish: [Natural] [Painted White].}} 2.07 DECK TYPE 7 NOTE: This is an adaption of any of the Tectum Deck System panels to make them suitable for use on tees or concrete joists. A. Tectum "Roof Deck Tile" Roof Deck System as produced by Tectum Inc.; Newark, Ohio Elderly Apartments/ 10/23/ OSB
16 B. Tile Characteristics: NOTE: Choose Tectum [I] [II] [III] substrate thickness as the Project dictates. {{1. Tectum I Substrate Thickness: [1-1/2] [2] [2-1/2] [3] inches.}} {{2. Tectum II Substrate Thickness: 2 inches. a. Foam Thickness: [3/4] [1] [1-1/2] [2] [2-1/2] [3] inch(es).} {3. Tectum II Substrate Thickness: 2-1/2 inches. a. Foam Thickness: [3/4] [1] [1-1/2] [2] [2-1/2] inch(es).} {4. Tectum II Substrate Thickness: 3 inches. a. Foam Thickness: [3/4] [1] [1-1/2] [2] inch(es).}} {{5. Tectum III Substrate Thickness: 1-1/2 inches. a. Foam Total Thickness: [1-1/2 3-1/2] [2 4] [3 5] [4 6] [5 7] [6 8] inches.}} 6. Width and Length: Refer to [structural] drawings. 7. Finish: [Natural] [Painted White]. C. Subpurlins: Designed to carry a load of PSF with a deflection not to exceed [l/180] [i/240]. D. Grout: Tectum Brand Premixed Grout. Elderly Apartments/ 10/23/ OSB
17 2.08 DECK TYPE 8 NOTE: Tectum Form Plank and Tectum Form Tile consist of the Tectum I roof or Tectum II panel adapted for formwork. A. Tectum "Roof Form [Plank] [Tile]" Roof Deck System as produced by Tectum Inc.; Newark, Ohio B. Characteristics: {{1. Tectum I Substrate Thickness: [1-1/2] [2] [2-1/2] [3] inches.}} {{2. Tectum II Substrate Thickness: 2 inches. a. Foam Thickness: [3/4] [1] [1-1/2] [2] [2-1/2] [3] inch(es).} {3. Tectum II Substrate Thickness: 2-1/2 inches. a. Foam Thickness: [3/4] [1] [1-1/2] [2] [2-1/2] inch(es).} {4. Tectum II Substrate Thickness: 3 inches. a. Foam Thickness: [3/4] [1] [1-1/2] [2] inch(es).}} 5. Width and Length: Refer to [structural] drawings. 6. Finish: [Natural] [Painted White]. Elderly Apartments/ 10/23/ OSB
18 C. Subpurlins: Designed to carry a load of PSF with a deflection not to exceed [l/180] [i/240]. D. Grout: Tectum Brand Premixed Grout. NOTE: The following should be deck type as recommended by Tectum for proper diaphragm design ADHESIVE A. Adhesive shall be of the type to meet American Plywood Association (APA) Standard AFG-01 and shall be of the type recommended for the material being attached and for the material the deck is attached to. B. Adhesive: Miracle Brand SFA66. PART 3: EXECUTION 3.01 EXAMINATION A. Examine surfaces scheduled to receive units for unevenness, irregularities, and dampness that would affect quality and execution of work. Do not proceed with work until unsatisfactory conditions have been corrected INSTALLATION, GENERAL A. Install materials in accordance with manufacturer's printed instructions, governing regulations, fire Elderly Apartments/ 10/23/ OSB
19 resistance rating requirements, and industry standards applicable to work. NOTE: Select "3.03", "3.04", "3.05", "3.06", "3.07" accordingly as deck units were selected in PART 2 above TILE A. Position subpurlins to within plus or minus 1/16 inch of the manufacturer's recommended spacing and securely positioned by means of templates during welding. B. Weld tees at every crossing point over support members with a 3/4 inch long fillet weld on alternate sides of the flange. Weld both sides of the flange at all tee ends. C. Subpurlins shall be funished in lengths to span three purlins. D. Mix and place grout in accord with manufacturer's printed instructions. Remove excess grout once initial set has been achieved. Avoid walking on the tile panels PLANK A. Place planks on joists with square cut ends butted tightly together. Stagger end joints. End joints shall occur over joists with a minimum 1 inch bearing. B. Secure planks to joists with galvanized steel clips of type, size and spacing as recommended by the plank manufacturer. Install clips prior to allowing any construction traffic on planks. NOTE: The following should be deck type as recommended by Tectum for Elderly Apartments/ 10/23/ OSB
20 proper diaphragm design. C. Apply adhesive as recommended by Tectum for proper diaphragm design LONG SPAN PLANK A. Install in strict accord with manufacturer's printed instructions. B. Cut plank neatly to abut parapets, around openings and penentrations. NOTE: The following should be deck type as recommended by Tectum for proper diaphragm design. C. Apply adhesive as recommended by Tectum for proper diaphragm design FORMBOARD A. Install in strict accord with manufacturer's printed instructions. B. Cut plank neatly to abut parapets, around openings and penentrations. NOTE: The following should be deck type as recommended by Tectum for proper diaphragm design. C. Apply adhesive as recommended by Tectum for proper diaphragm design. Elderly Apartments/ 10/23/ OSB
21 3.07 COMPOSITE PLANK A. Install in strict accord with manufacturer's printed instructions. B. Cut plank neatly to abut parapets, around openings and penentrations. NOTE: The following should be deck type as recommended by Tectum for proper diaphragm design. C. Apply adhesive as recommended by Tectum for proper diaphragm design CLEANING A. Clean exposed surfaces of all deck surfaces. B. Remove work which cannot be successfully cleaned and repaired to permanently eliminate evidence of damage PROTECTION A. Provide required protection for the deck units so that the work will be without damage and deterioration at the time of acceptance by the Owner. END OF SECTION Elderly Apartments/ 10/23/ OSB
22 Section Precast Concrete 1.0 General 1.1 Description A. The General conditions of the Contract and Supplementary General Conditions apply to this Division, except as qualified herein and/or excluded. B. Refer to drawings and specifications. 1.2 Work Included A. Design, supply, delivery and installation of: 1. Spec Note: This section includes structural precast concrete units including the following: Double tee slab units Parking structures Structural framing units Structural precast concrete B. Supply information required for the installation of bracing, supports, inserts and similar accessories required for the work under this contract supplied and to be installed by others. 1.3 Reference Standards A. CSA A , Methods of Test for Concrete B. CSA A , Design of Concrete Structures 1.4 Qualifications of Manufacturer Elderly Apartment Precast Concrete
23 Fabricate precast/prestressed concrete elements certified by the Canadian Standards Association in the appropriate category(ies) according to CSA Standard A "Precast Concrete - Materials and Construction". The precast concrete manufacturer shall be certified in accordance with the CSA Certification program for Structural Precast/Prestressed Concrete prior to submitting a tender and must specifically verify as part of his tender that he is currently certified in the appropriate category(ies): 1.5 Allowable Tolerances A. Conform to the requirements of CSA A23.4-Section 10. B. Refer to related Sections of this Specification and fabricate work to accommodate the specified tolerances. 1.6 Finishes of Formed Surfaces A. Finishes shall be (a) Commercial Grade, (b) Standard Grade, (c) Finish Grade B, or (d) Finish Grade A in accordance with clause 24 of CSA A23.4 as shown on the contract drawings. B. Finishes shall be (a) Commercial Grade, or (b) Standard Grade unless otherwise noted. 1.7 Delivery, Storage and Protection A. Accept full responsibility for delivery, handling and storage of units. B. Deliver, handle and store precast/prestressed units using methods approved by the manufacturer. Do not permit units to contact earth or staining influences or to rest on corners. 1.8 Design A. Requirements: Design and fabricate precast structural concrete elements, brackets and anchorage devices so that when installed they will: a..1 Compensate for allowable construction tolerances in the structure to which they are secured. b..2 Tolerate a structural deflection of span/360 due to live load. c..3 Adequately sustain themselves, and superimposed loads, specified by the engineer, without exceeding deflection of 1/360. Elderly Apartment Precast Concrete
24 d..4 Design loads shall be as specified by the (Provincial) Building Code. 2.0 Products 2.1 Materials B..1 Forms: to CSA3-A23.4. C..2 Hardware and miscellaneous materials: to CSA-A23.1. D..3 Air entrainment admixture: to CSA-A E..8 Bearing pads: neoprene, [60] durometer hardness to ASTM D2240, and [17] MPa minimum tensile strength to ASTM D412, molded to size or cut from molded sheet. (Random oriented fiber-reinforced neoprene.) F..4 Surface retardant: to CSA-A G..5 Zinc-rich primer: to CGSB 1-GP-181M. 2.2 Concrete Mixes A..1 Unless otherwise noted or specified, use concrete mix designed to produce a minimum of 35 MPa compressive cylinder strength at 28 days, with a maximum water/cement ratio to CSA A23.4. B..2 Use cement and supplementary cementing materials which conform to CSA A23.1. C..3 Air Entrainment of Concrete Mix: Refer to CSA-A23.1 D..4 Use of calcium chloride not permitted. 2.3 Finishes A..1Finish units to [commercial grade] [standard grade] [finish grade A] [finish grade B] to CSA A23.4 Clause 2.4 Double Tee Slab Units Elderly Apartment Precast Concrete
25 B..1 Precast floor and roof units shall be double tee components with prestressed reinforcement as required by design. The finish of the underside of the double tees shall be a standard form finish. C..2 Prestressing tendons shall be uncoated 7 wire strands conforming to CSA Standard A Structural Framing Units A..1 Type: Precast concrete structural framing units. B..2 Furnish units free of voids or honeycombs. C..3 Provide standard finish to precast units. D..4 Where ends of strands will not be enclosed or covered, cut flush and cover with a highstrength mortar bonded to unit with an epoxy-resin bonding agent. E..5 Reinforce units to resist transportation and erection stresses. F..6 Include cast-in weld plates where required. G..7 Coordinate with other trades for installation of cast-in items. 3.0 Execution 3.1 General A..1 Erect precast work in accordance with CSA-A23.4. Spec Note: It is not the Precast Manufacturer's responsibility to confirm and correlate dimensions at the job site. Precast concrete is a prefabricated material. Site dimensioning would require the structure to be complete before fabrication could commence. 3.2 Installation B..1 Set precast concrete units, straight, level and square. C..2 Do welding in accordance with CSA-W59, for welding to steel structures and CSA W186, for welding of reinforcement. Elderly Apartment Precast Concrete
26 D..3 Erect precast elements within allowable tolerances as [indicated] [specified]. E..4 Non-cumulative erection tolerances to be in accordance with CSA3-A23-4, Section [10]. Spec Note: Where bearing pads are required, specify locations if not clearly indicated on drawings. F..5 Set elevations and alignment between units to within allowable tolerances before connecting units. G. Spec Note: Check if required. Do not grout under elastomeric pads. H..6 Grout underside of precast units with shrinkage compensating grout where indicated. I..7 Secure with bolts using [lockwashers] [or] [tack-weld nut to bolt]. J..8 Do not weld or secure bearing plates at sliding joints. K..9 Use grout to align elevations at surface of joints in situations where allowable tolerances have been exceeded or as noted on consultant's drawings in critical locations. L..10 Clean field welds with wire brush and touch-up [shop primer with primer] [galvanized finish with zinc-rich primer]. M..11 Fasten units in place as per approved connection detail shop drawings. Protect work from damage by weld splatter. N..12 Clean field welds with wire brush and touch up with galvafroid paint or zinc rich primer. 3.3 Handling and Erection A..1 Precast components shall be handled and erected in accordance with CSA Standard A23.4 and as per the manufacturer's instructions. B..2 Precast components shall be delivered and handled in such a manner as to avoid warpage. C..3 Holes and reglets shall be protected from forming of ice during freezing weather. D..4 Lifting devices shall be protected from rusting at all times. Elderly Apartment Precast Concrete
27 E..5 All precast components shall be erected by experienced workmen under the supervision of a qualified superintendent with a minimum of five (5) years' experience. F..6 Welding of the precast units shall be performed by certified welders in accordance with CSA Standard A23.4, Clause 32. G..7 Units shall be set plumb and true with joints parallel and uniform. H..8 All necessary precautions shall be taken to prevent weld burn or splatter on to exposed surfaces. I..9 Patch damaged, or chipped components as required. 3.4 Cleaning A..1 If required, clean exposed face work by washing and brushing only, as precast is erected. Use approved masonry cleaner if washing and brushing fails to achieve required finish. Remove immediately materials that may set up or harden. This section is not responsible for soiling or damage by others. END OF SECTION Elderly Apartment Precast Concrete
28 SECTION MASONRY ANCHORS PART 1 GENERAL 1.01 SECTION INCLUDES A. Masonry veneer anchors and ties. B. Stone veneer anchors and ties. C. Masonry accessories RELATED SECTIONS A. Section Unit Masonry Assemblies. B. Section Cut Stone Veneer. C. Section Stone Masonry Veneer REFERENCES A. ASCE/ACI Specifications for Masonry Structures; B. ASTM A 153/A 153M - Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware; C. ASTM A Standard Specification for Stainless and Heat-Resisting Chromium- Nickel Steel Plate, Sheet, and Strip; D. ASTM A 240/A 240M - Standard Specification for Heat-Resisting Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels; 1998b. E. ASTM A Standard Specification for Stainless Steel Bars and Shapes; 1998b. F. ASTM A 479/A 479M - Standard Specification for Stainless and Heat-Resisting Steel Bars and Shapes for Use in Boilers and Other Pressure Vessels; 1997a. G. ASTM A 580/A 580M - Standard Specification for Stainless Steel Wire; H. ASTM A 653/A 653M - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process; I. ASTM B 633 Standard Specification for Electrodepositied Coatings of Zinc on Iron and Steel; (Reapproved 1994). Elderly Apartments Masonry Anchors
29 1.04 SUBMITTALS A. Submit under provisions of Section B. Product Data: Manufacturer's data on each type of product furnished. PART 2 PRODUCTS 2.01 MANUFACTURERS Acceptable Manufacturer: Heckmann Building Products Inc., 1501 N. 31 st Avenue, Melrose Park, IL or FAX: Heckmann@worldnet.att.net. Website: A. Requests for substitutions will be considered in accordance with provisions of Section B. Substitutions: Not permitted APPLICATIONS A. Provide anchoring systems that comply with ACI 530.1/ASCE 6/TMS 602. ***************************************************************** NOTE: The following anchors are one part of a two-part system - the part that attaches to the backup or structure. These anchors are suitable for masonry veneer, stone, and other claddings. Be sure, if any of these are used, that the second part - the tie or other attachment to the cladding - is also specified. Delete the types not required. If more that one type for a particular application is required, be sure to indicate where each is to be used. ***************************************************************** B. Masonry Anchors: 1. Anchors to Concrete: Channel slots screwed to face. 132 SCREW-ON CHANNEL SLOT [11 gage][16 gage] x 12 (305 mm) long 133 LONG CHANNEL SLOT 16 gage x [5 ft (1.524 m)][10 ft (3.048 m)] 2. Anchors to Masonry Backup: Channel slots screwed to face. 131 MASONRY TYPE CHANNEL SLOT [16 gage][11 gage] x 1-3/8 inches (35 mm) wide x 8 inches (203 mm) long with welded Z-Anchors [Length (1/2 of block thickness] and 1-1/2 inch (38 mm) bends 132 SCREW-ON CHANNEL SLOT [11 gage][16 gage] x 12 inches (305 mm) long Elderly Apartments Masonry Anchors
30 133 LONG CHANNEL SLOT 16 gage x [5 feet (1.524 m)][10 feet (3.048 m)] 3.Anchors welded to Structural Steel: 130 CHANNEL SLOT [16 gage][11 gage] x 1-3/8 inches (35 mm) wide x 8 inches (203 mm) long 133 LONG CHANNEL SLOT 16 gage x [5 feet (1.524 m)][10 feet (3.048 m)] ***************************************************************** NOTE: The following masonry ties must be used with one or more of the anchor types listed above. ***************************************************************** C. Masonry Veneer Seismic Ties: Continuous wire in mortar joint, anchored to 362 CHANNEL SLOT SEISMIC ANCHOR [gage] x 1-1/4 inches (32 mm) wide x [length from face of channel]. D. Masonry Veneer Ties: Provide minimum 2 inches (50 mm) embedment in mortar. 1. For Use with channel slots: 122 CHANNEL SLOT PARTITION ANCHOR [gage] x 1-1/4 inches (32 mm) x 12 inches (305 mm) from face of channel. 123 CHANNEL SLOT HORIZONTAL TRIANGLE ANCHOR [gage] x 1-1/4 inches (32 mm) x 12 inches (305 mm) from face of channel. 124 CHANNEL SLOT CAVITY WALL ANCHOR [gage] x 1-1/4 inches (32 mm) x 5 inches (127 mm) from face of channel. 125 CHANNEL SLOT FURRING ANCHOR [gage] x 1-1/4 inches (32 mm) x 1-1/2 inches (38 mm) from face of channel. 129 CHANNEL SLOT TRIANGULAR WIRE TIE 12 gage clip factory assembled to a 3/16 inch (4.76 mm) diameter x [tie length] 134 CHANNEL SLOT CORRUGATED ANCHORS [gage] x 1-1/4 inches (32 mm) x [length] from face of channel. 135 CHANNEL SLOT STONE ANCHOR [gage] x 1-1/4 inches (32 mm) x [length] from face of channel x [i.d. length of bend]. 136 CHANNEL SLOT SPLIT BEND ANCHOR [gage] x 1-1/4 inches (32 mm) x [length] from face of channel x [i.d. length of split bend]. 137 CHANNEL SLOT PIN ANCHOR [gage] x 1-1/4 inches (32 mm) x [length] from face of channel with [welded][fixed][loose] pin [diameter] x [length] centered [length] from end of anchor 138 CHANNEL SLOT FLAT ANCHOR [gage] x 1-1/4 inches (32 mm) x [length] from face of channel 138-R CHANNEL SLOT THREADED ROD ANCHOR [gage] x 1-1/4 inches (32 mm) x [length] from face of channel x [rod diameter] 2. Other Applications: Where details or installation conditions require, provide ties Elderly Apartments Masonry Anchors
31 fabricated of shape and size to suit conditions and provide adequate anchorage. E. Stone Ties: Custom strap ties, fabricated to suit details and installation requirements. 1. For Anchoring Into Edge of Dimension Stone Panels: Use dowel pin type 137 CHANNEL SLOT PIN ANCHOR [gage] x 1-1/4 inches (32 mm) x [length] from face of channel with [welded][fixed][loose] pin [diameter] x [length] centered [length] from end of anchor 2. For Anchoring Into edge of dimension Stone Panels: Use Anchor type 135 CHANNEL SLOT STONE ANCHOR [gage] x 1-1/4 inches (32 mm) x [length] from face of channel x [i.d. length of bend]. 136 CHANNEL SLOT SPLIT BEND ANCHOR [gage] x 1-1/4 inches (32 mm) x [length] from face of channel x [i.d. length of split bend]. 137 CHANNEL SLOT PIN ANCHOR [gage] x 1-1/4 inches (32 mm) x [length] from face of channel with [welded][fixed][loose] pin [diameter] x [length] centered [length] from end of anchor 3. Where not otherwise indicated, use anchoring method specified above. ***************************************************************** Note: Select one of the following 3 combinations of materials: all stainless steel, all hot-dip galvanized, or hot-dip galvanized except for items completely embedded in mortar. Delete the inappropriate choices. ***************************************************************** F. Material for Anchors and Ties in Exterior Walls: Stainless steel. 1. Exception: Structural Plates, Angles, and Bars: Hot-dip galvanized. G. Material for Anchors and Ties in Exterior Walls: Hot-dip galvanized. H. Material for Anchors and Ties Exposed to Air in Exterior Walls: Hot-dip galvanized. I. Material for Ties Completely Embedded in Mortar Joints: Mill galvanized MATERIALS A. Stainless Steel: Type Sheet Metal: ASTM A 167 or ASTM A 240/A 240M. 2. Wire: ASTM A 580/A 580M. 3. Bars: ASTM A 479/A 479M, annealed and ground. 4. Plates, Bars, and Shapes: ASTM A 167 or ASTM A 276. B. Hot-Dip Galvanized Steel: Hot-dip galvanized after fabrication in accordance with Elderly Apartments Masonry Anchors
32 ASTM A 153/A 153M, Class B Wire: Minimum 3/16 inch (4.76 mm) diameter. C. Electro-Galvanized Steel: Electro-galvanized after fabrication in accordance with ASTM B 633, Service Condition Wire: Minimum 3/16 inch (4.76 mm) diameter. D. Mill Galvanized Steel: 1. Sheet Metal: ASTM A 653/A 653M, G60 coating. 2. Wire: ASTM A 641, regular coating; minimum 3/16 inch (4.76 mm) diameter. E. Channel Slots: 7-3/8 inch (187 mm) slots with 3/4 inch (19 mm) between slots. Type for Welding On: 130 CHANNEL SLOTS [16 gage][11 gage] x 1-3/8 inches (35 mm) wide x 8 inches (203 mm) long 1. Type for building into masonry: 131 MASONRY TYPE CHANNEL SLOT [16 gage][11 gage] x 1-3/8 inches (35 mm) wide x 8 inches (203 mm) long with welded Z-Anchors [Length (1/2 of block thickness] and 1-1/2 inch (38 mm) bends 2. Metal Thickness: 11 gage (3 mm) I. Strap Ties and Stone Anchors: Maximum thickness for channel slot ties stainless steel 1/8 ; for galvanized, 3/16 inch. 1. Metal Thickness: 3/16 inch (4.7 mm). 2. Metal Thickness: 1/8 inch (3.175 mm). 3. Metal Thickness: 12 gage (2.6 mm). 4. Metal Thickness: 16 gage (1.5 mm). PART 3 EXECUTION 3.01 INSTALLATION A. Install as specified in applicable masonry section(s) and in accordance with manufacturer's instructions. 1. Anchors A. 130 CHANNEL SLOTS: - Weld 1-1/2 inches (38.1 mm) on both sides at the top and the bottom of the anchor. B. 131 MASONRY TYPE CHANNEL SLOT: Place Z-Anchors in the core of the CMU. Push the Channel Slot back until it is flush with the face of the CMU. Grout core. C. 132 SCREW-ON CHANNEL SLOT: Use an acceptable fastener for the backup system. Use two fasteners per anchor. D. 133 LONG CHANNEL SLOT: Elderly Apartments Masonry Anchors
33 1. Welded to Structural: Weld 1-1/2" (38.1 mm) on both sides at distances recommended by structural engineer. 2. Attached to Existing wall: Use Heckmann No. 133-P Bridge Plates along with acceptable fastener for the backup system. Fasten minimum of every 16 inches. 2. Ties: Insert tie into channel and rotate 90 degrees. END OF SECTION Elderly Apartments Masonry Anchors
34 SECTION PART 1 - GENERAL 1.1 SUMMARY A. Section includes: Self-adhering waterproofing membrane and primer to provide moisture protection within masonry wall cavities. 1.2 REFERENCES A. ASTM D146 - Sampling and Testing Bitumen-Saturated Felts and Woven Fabrics for Roofing and Waterproofing. B. ASTM D412 - Test Methods for Vulcanized Rubber and Thermoplastic Rubbers and Thermoplastic Elastomers - Tension. C. ASTM D903 - Peel or Stripping Strength of Adhesive Bonds. D. ASTM D Asphalt Roof Cement. E. ASTM E154 - Water Vapor Retarders Used in Contact with Earth Under Concrete Slabs, or Walls, or as Ground Cover. 1.3 SUBMITTALS A. Provide in accordance with Section Submittal Procedures: 1. Product data and installation instructions. 2. Material safety data sheets (MSDS). 3. [2 by 2] [51 by 51 mm] minimum sample of membrane. 1.4 PRODUCT HANDLING 2002 Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine TEL: ; FAX: ; WEBSITE: A. Protect products from excessive heat, freezing temperatures, and direct sunlight during delivery, storage, and application. B. Store in clean, dry area away from open flame, sparks, or welding. PARTS 2 - PRODUCTS Elderly Apartment
35 2.1 ACCEPTABLE MANUFACTURERS A. Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine 04083; ; B. Manufacturers of equivalent products submitted and approved in accordance with Section Product Substitutions Procedures. 2.2 PRODUCTS A. Self-adhering, waterproof membrane with siliconized release liner; Peel-N-Seal as manufactured by Advanced Building Products, Inc. 1. Total thickness: 40 mils. 2. Composition: 32 mils rubberized asphalt laminated to 8 mils high density polyethylene film. 3. Width: [12inches.] [305mm.] 4. Tensile strength: 1,200 PSI minimum tested in accordance with ASTM D Elongation: 200 percent tested in accordance with ASTM D Pliability: Pass 1/4 inch mandrel test at minus 24 degrees tested in accordance with ASTM D Peel adhesion: 5 pounds per inch minimum tested in accordance with ASTM D Puncture resistance: 40 pounds minimum tested in accordance with ASTM E154. B. Primer: As recommended by membrane manufacturer for substrate Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine TEL: ; FAX: ; WEBSITE: PART 3 - EXECUTION 3.3 INSPECTION ***** Include the following paragraph if membrane is applied to concrete substrate. ***** A. Verify concrete substrates to receive membrane are fully cured. Cure concrete walls 7 days minimum. Elderly Apartment
36 B. Verify substrates are solid, free of oil, form release agents, curing compounds, frozen matter, loose particles, cracks, pits, rough projections, and foreign matter detrimental to adhesion and application of waterproofing. C. Verify air and surface temperatures are above 40 degrees F. 3.4 PREPARATION A. Clean and prepare surfaces to receive waterproofing in accordance with manufacturer's instructions. ***** for best results concrete, masonry, and some gypsum substrates require priming. Contact Advanced Building Products, Inc. for recommendations. ***** B. Primer application: 1. Provide adequate ventilation. 2. Apply by spray, brush, or roller at 250 to 350 square feet per gallon. 3. Only prime areas to be waterproofed same day. 4. At 75 degrees F allow primer to dry 1 hour minimum. 5. Re-prime prior to application of waterproofing if contaminated by dust or curing time is exceeded. 3.5 MEMBRANE APPLICATION A. Apply membrane in accordance with manufacturer's instructions to masonry cavities as indicated and detailed on Drawings. B. Pre-cut membrane to fit each location in [8 feet] [2438 mm] maximum lengths. C. Remove release liner and carefully position membrane before pressing in place. D. Lap adjoining pieces [2 inches] [51 mm] Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine TEL: ; FAX: ; WEBSITE: E. Roll membrane with steel hand roller to ensure full adhesion. Avoid air pockets and wrinkles. F. At terminations, press membrane firmly to wall with hardwood tool exerting heavy pressure. [Provide termination bars and flashings as detailed on Drawings.] G. At horizontal terminations, turn up membrane [2 inches] [51 mm] to form end dam. Elderly Apartment END OF SECTION
37 SECTION Brick Masonry PART 1 GENERAL 1.01 SECTION INCLUDES A. System Description: Work described in this section covers requirements for Brick Unit Masonry and its installation and maintenance RELATED SECTIONS A. Section Mortar B. Section Masonry Accessories 1.03 REFERENCES A. ACI Building Code Requirements for Masonry Structures & Specifications for Masonry Structures. B. ASTM C 67 Standard Test Methods for Sampling and Testing Brick and Structural Clay Tile. C. Underwriters' laboratories, Inc. (UL) D. Brick Industry Association (BIA) 1.04 DELIVERY, STORAGE, AND HANDLING A. Deliver Brick to Project Site as packaged by manufacturer. Offload Brick packages using equipment that will not damage the Brick face(s). No Brick is allowed to be in direct contact with the ground. Do not double stack pallets of Brick. B. Cover Brick with non-staining waterproof membrane covering. Keep units dry. Allow air circulation around stacked units. Installation of wet or stained Brick is prohibited ENVIRONMENTAL REQUIREMENTS A. Do not lay Brick and mortar when ambient temperatures are below 40 degrees F (4.4 degrees C), unless properly protected in a heated enclosure and accepted means are provided to heat units and mortar, with specific written approval from Architect. B. Maintain air temperature above 40 degrees F (4.4 degrees C) on both sides of masonry for at least 72 hours after erection of walls. C. Protect masonry construction from direct exposure to wind and sun then erected in ambient air temperatures of 95(or higher) degrees F (35 degrees C) in shade with relative humidity less than 50%. Elderly Apartment Brick Masonry
38 D. Take all precautions necessary to protect units from damage. 1. Handle and store in protective cartons or trays until actual installation in the wall. PART 2 PRODUCTS 2.01 STRUCTURAL BRICK A. Pattern or Type: 2. Damaged units will not be accepted in the wall. 1. As detailed and required (running bond or stack bond). B. Brick as manufactured by Elgin Butler Company, or other approved equal, shall meet ASTM C-1405, Class Exterior (or Interior), Grade S (Select), and the size(s) shall be: (Thickness x Height x Length) 1. Modular, 4S Series 3-5/8 (92) x 2-1/4 (57) x 7-5/8 (194), Division Solid, Type I & II 2. Standard, SS Series 3-5/8 (92) x 2-1/4 (57) x 8 (203), Division Solid, Type I & II 3. Jumbo, JX Series 3-5/8 (92) x 2-3/4 (70) x 8 (203), Division Solid, Type I & II 4. Closure, EN-4P Series 3-5/8 (92) x 3-5/8 (92) x 7-5/8 (194), Division H40V or Solid (option of manufacturer), Type I & II 5. Utility, EN-6P 3-5/8 (92) x 3-5/8 (92) x 11-5/8 (295), Division H40V or Solid (option of manufacturer), Type I & II 6. Norman, 6S Series 3-5/8 (92) x 2-1/4 (57) x 11-5/8 (295), Division H40V or Solid (option of manufacturer), Type I & II 2.02 ACCESSORIES 7. 8-Square, 4W Series 3-5/8 (92) (thickness of 1-5/8 (41), 5-5/8 (143), 7-5/8 (194) also available) x 7-5/8 (194) x 7-5/8 (194), Division H40V or Solid (option of manufacturer), Type I & II Square, 6Y Series, 3-5/8 (92) x 11-5/8 (295) x 11-5/8 (295), Division H40V, Type I A. Mortar: As specified in mortar section Brick Masonry Elderly Apartments
39 B. Joint Reinforcing: Masonry joint reinforcing as specified in Masonry Accessories section. C. Wall Ties: Installed as per BIA recommendations, such as with a 4"(101mm) or less width cavity, use corrosion resistant metal ties, minimum of one 3/16"(5mm) diameter steel wall tie in every 3-sq. ft.(27.87 sq. dm); Ties for veneer brick over steel stud back-up systems should be two-piece adjustable, corrosion resistant spaced per every 1.67 sq. ft.(15.5 sq. dm) of wall area; for vertical-cell hollow masonry units the tie shall be rectangular or U-shaped, or for horizontal-cell, hollow masonry units or solid masonry units shall be Z-shaped (Reference BIA Tech Note 21 series and ACI 530). D. Lateral support as required. PART 3 EXECUTION 3.01 PREPERATION A. Protect the surfaces of the installed Brick. Cover freshly laid weather exposed masonry at the end of each day or the start of each shut down period, with nonstaining waterproof material in such a manner which will ensure that the covering will overhang the masonry not less than 2' (6.1dm) on each side of the masonry. Anchor on each side of wall. Finished walls to be covered with 15# (6.8kg) felt paper and erect wooden barriers to protect walls at areas that are subject to large amounts of construction traffic or material movement. Protect face from exposure to welding burns, stains, etc INSTALLATION A. Workmanship: 1. Lay only dry masonry units. 2. Lay masonry plumb, level and true to line. 3. Lay units in bonding pattern as specified. 4. Cut units with masonry saw using a wet diamond blade. No not use units less than 4"(101mm) in length. B. Build in work of other trades indicated to be built-in with Glazed Brick as work progresses. C. Brick wall construction recommendations (Reference: BIA Technical Note 13, revised December 2005). 1. Vented cavity wall construction. 2. Install flashing, vents (weep holes), and vapor barrier. Elderly Apartment Brick Masonry
40 3. Provide flexible anchorage to columns and beams. D. Mortar Joints: 1. Lay joints of each first course in full width bed of mortar. 2. Vertically cored units: 3. Remove and replace mortar with fresh mortar where adjustment must be made after mortar has started to set. 4. Keep bed and head joints uniform in width, except for minor variations required to maintain bond and locate returns. 5. Both bed and head mortar joints standard thickness: a. Use 3/8"(10mm), +/- 1/16"(1.6mm). E. Joint Treatment 3.03 APPLICATION A. Walls must be straight in plane CLEANING 1. Tool or strike mortar joints on exposed face when they are thumb print hard. 2. Tool all Glazed Brick joints concave using a non-metallic tool 1"(25mm) in diameter or larger unless otherwise noted. B. Maximum variation from plumb: 1/4"(6mm) in 10' 0"(3.05m); not exceeding 3/8"(10mm) in 20' 0"(6.1m). C. Maximum variation from level: 1/4(6mm) in 20' 0"(6.1m); not exceeding 1/2"(13mm) in 40' 0"(12.2m) or more. D. Maximum variation in linear building line from location indicated: 1/4"(6mm) in 20' 0"(6.1m). A. It is intended that with careful adherence to this specification that extensive cleaning will not be necessary. During construction, wipe surface clean after tooling of joints or within 30 minutes after laying, with course rag. Keep wall clean as work progresses to avoid more difficult cleanup. Use no metal scrapers, abrasive powders or unauthorized cleaning agents. Use wooden paddles or scrapers to clean away mortar residue or lumps. Wash with clean water. A mild Brick Masonry Elderly Apartments
SECTION COLD-FORMED METAL FRAMING
SECTION 05400 PART I - GENERAL 1.01 DESCRIPTION A. Scope: Work of this Section shall include all materials and installation necessary to provide all cold formed metal framing. B. This Section includes:
More informationSECTION GYPSUM CEMENT UNDERLAYMENT RECOMMENDED SPECIFICATION FOR DURA-CAP FLOOR UNDERLAYMENT OVER EXTRUDED OR EXPANDED POLYSTYRENE FOAM
SECTION 03 54 00 1 GYPSUM CEMENT UNDERLAYMENT RECOMMENDED SPECIFICATION FOR DURA-CAP FLOOR UNDERLAYMENT OVER EXTRUDED OR EXPANDED POLYSTYRENE FOAM PART 1 GENERAL 1.01 SUMMARY A. This is the recommended
More informationBEARING METAL STUD FRAMING
L-1 Section 05410 Long Form Specification LOAD BEARING METAL STUD FRAMING This section includes axially loaded steel studs, with unique slotted top channels, usually of 0.91, 1.2 and 1.5 mm (16, 18, or
More information1.2 Reference Standard: NOFMA - National Oak Flooring Manufacturers Association Grading Standards.
WOOD FLOORING GENERAL INFORMATION 1.1 This section applies to factory finished wood strip flooring. 1.2 Reference Standard: NOFMA - National Oak Flooring Manufacturers Association Grading Standards. 1.3
More informationINSULATED CONCRETE MASONRY UNITS Section 04220
INSULATED CONCRETE MASONRY UNITS Section 04220 PART 1 GENERAL 1.01 Summary A. Section Includes 1. Insulated masonry wall units (CMU's) 2. Decorative insulated masonry wall units 1.02 SUBMITTALS A. Samples:
More information1.02 STANDARD REFERENCES: The following standard specifications shall apply to the Work of this Section as indicated:
SECTION 04220 CONCRETE UNIT MASONRY PART 1 - GENERAL 1.01 SCOPE: A. The CONTRACTOR shall furnish all labor, materials and equipment necessary for the masonry construction as shown on the drawings or as
More information1. Cast-in-place concrete is specified in Section
SECTION 03 38 00 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section describes the requirements for furnishing and installing post-tensioned slabs, jacks, jacking and anchors at Parking Structure, and record
More informationSECTION MASONRY ACCESSORIES
PART 1 GENERAL 1.01 SCOPE OF WORK A. Contractor shall furnish all labor, materials, equipment and incidentals required to provide masonry accessories as shown on the Contract Drawings and specified herein.
More informationSECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection
SECTION 13090 RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13090-1 LOW INTENSITY RADIATION PROTECTION
More informationSECTION STRUCTURAL PRECAST HOLLOW CORE SLABS
PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish all labor, materials, equipment and incidentals to provide a complete structural precast hollow core slab system as shown on the Contract
More informationCorium Brick Rainscreen System Specifications
CORIUM BRICK RAINSCREEN SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Work Included: The Work of this Section shall include but not be limited to the following: 1. Corium brick plates 2. Galvanized and coated
More informationA. Coordinate concrete unit masonry (also termed CMU and block ) work with work before and after, especially:
04222 CONCRETE UNIT MASONRY (UNREINFORCED ONLY) SPECIFIER: Use this section only for UNREINFORCED concrete masonry. Its only reinforcement is in the horizontal joints. It covers ONLY plain blockwork (no
More informationAnchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi
STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel
More informationGUIDE SPECIFICATIONS For STRUCTURAL PRECAST HOLLOW CORE SLABS SECTION 03410
GUIDE SPECIFICATIONS For STRUCTURAL PRECAST HOLLOW CORE SLABS SECTION 03410 Note to user: These guide specifications are provided by Mid- States Concrete Products as a service to you; they are NOT specific
More information1. Section , Concrete Reinforcement and Embedded Assemblies. B. ACI 530/ASCE 5 - Building Code Requirements for Masonry Structures
SECTION 04 22 00 CONCRETE MASONRY UNIT PART 1 - GENERAL 1.1 SUMMARY A. Work Includes: This Section includes the furnishing and installation of concrete masonry units, reinforcing steel, miscellaneous masonry
More informationSECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM
Page 1 of 6 SECTION 08 32 20 LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS SLIDING DOORS. SECTION INCLUDES OVERHEAD SLIDING TUBE ASSEMBLY, MOUNTING
More informationSpecifiers: Click on the icon in the WORD toolbar to reveal detailed instructions
Specifiers: Click on the icon in the WORD toolbar to reveal detailed instructions (Specifier Note: The purpose of this guide specification is to assist the specifier in correctly specifying perforated
More informationSECTION STAY-IN-PLACE INSULATED CONCRETE FORMING SYSTEM
ARCHITECTURAL SPECIFICATIONS MANUFACTURER: InterBlock LLC PO Box 1123, Sheboygan, WI 53082 Phone Number 920-207-7234 SECTION 03100 STAY-IN-PLACE INSULATED CONCRETE FORMING SYSTEM PART 1 GENERAL 1.01 Summary
More information1. Rubberized asphalt waterproofing membrane, reinforced. 2. Molded sheet drainage panels. 3. Insulation. 4. Plaza deck pavers.
SECTION 071413 HOT FLUID APPLIED RUBBERIZED ASPHALT WATERPROOFING PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Rubberized asphalt waterproofing membrane, reinforced. 2. Molded sheet drainage panels.
More informationSECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the
More information***********************************************************************************
AQUAFIN-2K/M Two-Component Cement-based Acrylic-based Waterproofing GUIDE AQUAFIN, Inc. SPECIFICATION PART 1 - GENERAL 1.1 SECTION INCLUDES SECTION 07 16 14 ACRYLIC MODIFIED (FLEXIBLE) CEMENTITIOUS WATERPROOFING
More informationSECTION PRE-ENGINEERED BUILDING INSULATION
PART 1 GENERAL SECTION 07213 PRE-ENGINEERED BUILDING INSULATION Microsoft Word Instructions: Display hidden notes to specifier by using "Tools"/"Options"/"View"/"Hidden Text". 1.1 SECTION INCLUDES A. Pre-Engineered
More informationSECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING
P.O. Box 599 - Mars, PA 16046 800-321-3337 SECTION 07555 COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including
More informationARCHITECTURAL GUIDE SPECIFICATIONS - DESCRIPTIVE
ARCHITECTURAL GUIDE SPECIFICATIONS - DESCRIPTIVE MANNINGTON COLORFIELDS SHEET RUBBER FLOORING Section 09 65 16 Sheet rubber Flooring (Thermoset Rubber) Created May 2012 Mannington Mills, Inc. P. O. Box
More informationSECTION COMMON WORK RESULTS FOR CONCRETE SSPECIALTY COATINGS
SECTION 03 05 00 COMMON WORK RESULTS FOR CONCRETE 09 97 00 SSPECIALTY COATINGS Weld Crete ************************************************************************************************************************
More informationStructural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)
Inspection of Fabricators (1704.2) Furnish inspection reports (1704.2.1) - Fabricators that have not been approved Provide a Certificate of Compliance (1704.2.2) - Approved Fabricators Steel Construction
More informationSPECIFICATION GUIDELINE
SPECIFICATION GUIDELINE Environmental Stoneworks Corporate Office 6300 East Stapleton Drive South Denver, CO 80216 Phone (303) 309-3040 Fax (303) 309-3059 www.estoneworks.com Environmental Stoneworks specification
More informationPERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960
STUC-O-FLEX PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960 PART 1 - GENERAL 1.01 DESCRIPTION Provide all labor, materials and equipment necessary
More informationSECTION PLATE CONNECTED WOOD TRUSSES
SECTION 06173 PLATE CONNECTED WOOD TRUSSES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Shop fabricated wood trusses for roof and floor framing. 2. Bridging, bracing, and anchorage. B. Related Sections:
More informationSECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS
SECTION 075423 - THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Division 00 Bidding Requirements and other Division
More informationSECTION TERRAZZO FLOOR TILE
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 09 66 16 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // ----- // if not applicable to project. Also delete any other item or
More informationNorthpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017
SECTION 055213 - PIPE AND TUBE RAILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationMay 8, 2017 ADDENDUM #1. IFB Resin Floor System For Highway Department Central District Building
May 8, 2017 ADDENDUM #1 IFB 17-082 Resin Floor System For Highway Department Central District Building Addendum #1 is being issued to offer an alternate resin flooring system. 096700 FLUID-APPLIED FLOORING
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-03 11 13.00 10 (May 2014) --------------------------------- Preparing Activity: USACE Superseding UFGS-03 11 13.00 10 (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationSECTION mil thickness COLD FLUID-APPLIED WATERPROOFING
SECTION 07 14 16 CCW-MIRASEAL @ 120 mil thickness COLD FLUID-APPLIED WATERPROOFING PART 1 - GENERAL 1.1 SECTION INCLUDES: Installation of waterproofing membrane on surfaces indicated on drawings, consisting
More informationLouis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1
Louis Armstrong New Orleans International Airport NOAB Project # 8910-01233 PART 1 - GENERAL SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS 1.1 RELATED DOCUMENTS A. Drawings and general provisions
More informationColphene BSW Training and Application Guide. Colphene BSW Waterproofing Membrane. 1. Prepare substrate
Colphene BSW Training and Application Guide Colphene BSW Waterproofing Membrane. 1. Prepare substrate Substrate must be structurally sound. Surface must be free of voids, spalled areas, loose aggregate,
More informationPage 1 of 5
SPECIFICATIONS COMPOSITE MATERIAL PANEL SYSTEM ESTOLGA 1000 DRY SEAL SYSTEM PART 1 GENERAL 1.01 SECTION INCLUDES A. Exterior cladding consisting of formed metal composite material (MCM) sheet, secondary
More informationFLUID APPLIED WATERPROOFING
SECTION 07120 FLUID APPLIED WATERPROOFING PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 03300 - Cast-In-Place Concrete. 2. 09200 - Metal Studs, Metal Lath, Suspension Ceilings, Plaster, and Stucco.
More informationSECTION EXPANSION CONTROL
SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationNOVABRIK MORTARLESS CONCRETE BRICK VENEER SPECIFICATION. MASTERFORMAT SECTION (Mortarless Concrete Brick Veneer)
NOVABRIK MORTARLESS CONCRETE BRICK VENEER SPECIFICATION MASTERFORMAT SECTION 04818 (Mortarless Concrete Brick Veneer) Spec_USA_En_18102005.doc 12/1/2005 Novabrik Page 2 Section 04818 NOVABRIK MORTARLESS
More informationA. Submittal Procedures: See Article 13 of the General Conditions.
SECTION 321313 - CONCRETE PAVING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Driveways. 2. Roadways. 3. Parking lots. 4. Curbs and gutters. 5. Walks. B. Proposed Substitutions: See Article 2,
More informationSECTION MODIFIED BITUMINOUS SHEET WATERPROOFING
SECTION 07 13 52 MODIFIED BITUMINOUS SHEET WATERPROOFING SPEC WRITER NOTE: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section
More informationSECTION DIMENSION STONE CLADDING
SECTION 04851 DIMENSION STONE CLADDING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes dimension stone panels set with individual anchors,. B. Related Sections include the following: 1. Division
More informationSECTION EPOXY TERRAZZO
SECTION 09402 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to
More informationSPECIFICATIONS FOR BRIDGE CONSTRUCTION SECTION 5 REINFORCING STEEL. 5.1 General Certification Fabrication...
SPECIFICATIONS FOR BRIDGE CONSTRUCTION SECTION 5 REINFORCING STEEL TABLE OF CONTENTS 5.1 General...5-1 5.2 Certification...5-1 5.3 Fabrication...5-1 5.4 Handling and Storage...5-1 5.5 Field Repair of Epoxy
More informationBy CTS Cement Manufacturing Corp.
CSI SECTION 03 60 00 GROUTING 03 62 00 NON-SHRINK GROUTING 03 62 13 NON-METALLIC NON-SHRINK GROUTING High Flow, Non-Metallic, Multi-Purpose, Cementitious, Non-Shrink Grout EDITOR NOTE: The following guideline
More informationRetain "Preinstallation Conference" Paragraph below if Work of this Section is extensive or complex enough to justify a conference.
SECTION 05 40 00 - COLD-FORMED METAL FRAMING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION UNIT MASONRY SYSTEM
SECTION 04320 UNIT MASONRY SYSTEM PART 1 GENERAL 1.01 SECTION INCLUDES A. Concrete masonry and face brick units. B. Reinforcement, anchorage, and accessories. 1.03 SUBMITTALS A. Submit product data under
More informationSECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 [08 33 13] COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Metal Counter
More informationSECTION METAL BUILDING SYSTEMS
SECTION 13 3419 PART 1 GENERAL 1.01 SECTION INCLUDES A. Manufacturer-engineered, shop-fabricated structural steel building frame. B. Insulated Metal wall and roof panels including gutters and downspouts.
More informationSECTION 07530CP EPDM MEMBRANE ROOFING
PART 1 GENERAL 1.1 SUMMARY SECTION 07530CP EPDM MEMBRANE ROOFING A. Section includes: 1. Adhered membrane roofing and flashing 2. Mechanically fastened roof insulation 3. Walkway pads 1.2 ARCHITECTURAL
More informationTechnical Notes 28 - Anchored Brick Veneer, Wood Frame Construction Rev August 2002
Technical Notes 28 - Anchored Brick Veneer, Wood Frame Construction Rev August 2002 Abstract: This Technical Notes deals with the prescriptive design of brick veneer with wood frame construction in buildings
More information1. Division 09 Section "Rough Carpentry."
GREENSPOINT AND LAUDER RD. EC/PRE-KlK PAGE 1 SECTION 096400 - WOOD FLOORING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary
More informationSECTION REFLECTIVE-FACED, MASONRY CAVITY WALL INSULATION
MANUFACTURER S GUIDE SPECIFICATIONS SECTION 04 27 23 REFLECTIVE-FACED, MASONRY CAVITY WALL INSULATION 900 Hensley Lane Wylie TX 75098 800-527-7092 www.carlisleccw.com 07.09.13 Carlisle and R2+ are trademarks
More informationSuggested Specification for Tri-Patch Versatile Concrete Patching Compound
Suggested Specification for Tri-Patch Versatile Concrete Patching Compound SURFACE PREPARATION for Interior and Exterior Floor-Covering Installations. (Vinyl Composition Tiles, Sheet Vinyl, Rubber, Indoor
More informationGigaCrete Specification PlasterMax. PlasterMax : Fire Rated Plaster for Direct Application over Cement Masonry Units (CMU) Interior Walls
GigaCrete Inc. 6775 Speedway Blvd. Suite M105 Las Vegas, NV 89115 Ph (702) 643-6363 Fax (702) 643 1453 www.gigacrete.com GigaCrete Specification PlasterMax PlasterMax : Fire Rated Plaster for Direct Application
More informationEDGEWATER, FLORIDA JUNE 14, 2010
SECTION 09 2400 - PORTLAND CEMENT PLASTER PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION CAST-IN-PLACE CONCRETE
SECTION 03300 CAST-IN-PLACE CONCRETE PART 1 GENERAL 1.01 SECTION INCLUDES A. The Contractor shall furnish all work and materials, including cement, sand and coarse aggregate, water, admixtures, curing
More informationSPECIFICATIONS PRECAST PRESTRESSED CONCRETE PART 1 GENERAL 1.6.2.5 Openings, inserts and related reinforcement 1.6.3 Each drawing submitted to bear stamp of 1.1 Related Work qualified Professional Engineer
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 055113 - METAL PAN STAIRS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationNCMA TEK TEK 19-5A FLASHING DETAILS FOR CONCRETE MASONRY WALLS
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology FLASHING DETAILS FOR CONCRETE MASONRY WALLS TEK 19-5A Water Penetration Resistance
More informationSECTION METAL FLOOR PLATE STAIRS
SECTION 05513 - METAL FLOOR PLATE STAIRS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationTILE TILE
09300 - TILE 09300-1 PART ONE: GENERAL 1.1 Description TILE 1.1.1 Work of this Section, as shown or specified, shall be provided by the Interior Contractor and shall be in accordance with the requirements
More informationMASTER GUIDE SPECIFICATION
TOTALJOIST (TJ) GUIDE NOTE: This master specification section includes TOTALJOIST GUIDE NOTEs identified as TJ GUIDE NOTE for information purposes and to assist the specification writer in making appropriate
More informationSECTION ACOUSTICAL PANEL CEILINGS
SECTION 095113 ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationDIVISION 04 MASONRY CAST STONE. A. Design Considerations. 1. Cast stone shall comply with ASTM C1364, Standard Specification for Cast Stone.
DIVISION 04 MASONRY 04720 CAST STONE A. Design Considerations 1. Cast stone shall comply with ASTM C1364, Standard Specification for Cast Stone. 2. Care must be taken in the design of individual units
More informationSECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products.
SECTION 05720 ORNAMENTAL ALUMINUM RAILING ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products. This section is based on the products of Superior Aluminum Products,
More informationST. JOHNS COUNTY ARCH. PROJ. NO SECTION PREFABRICATED ALUMINUM CANOPIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS
SECTION 10530 PREFABRICATED ALUMINUM CANOPIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.
SECTION 06 12 00 STRUCTURAL INSULATED PANELS ------------------------------------------------------------------------------------------------------------ PART 1- GENERAL ----------------------------- 1.1
More informationA. Access doors and frames are part of an access door and frame allowance.
SECTION 08 31 13 ACCESS DOORS AND FRAMES PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationHANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
13686.00 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529-1 SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 1.1 SUMMARY A. Section Includes: 1. Metal pipe hangers and supports.
More informationEditing notes to assist users are separated from specification text by rows of asterisks. Delete these notes prior to final printing.
SECTION 09635 LIMESTONE FLOORING This guide specification has been prepared by TexaStone Quarries LLC to assist design professionals in the preparation of a specification section covering cut limestone
More information1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards
SECTION 07185 TRAFFIC MEMBRANE PART 1 GENERAL 1.1 SECTION INCLUDES A. Traffic membrane, consisting of welded seam PVC waterproofing, over f following surfaces: 1. Decks, balconies, and sun porches 2. Walkways,
More informationSECTION UNIT MASONRY
PART 1 GENERAL 1.01 SECTION INCLUDES A. Concrete Masonry Units. B. Mortar and Grout. C. Accessories. 1.02 RELATED REQUIREMENTS 1.03 REFERENCE STANDARDS SECTION 042000 UNIT MASONRY A. Unless otherwise noted
More informationSECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT
SECTION 220529 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationCEMENTITIOUS CRYSTALLIZING WATERPROOFING PART 1 GENERAL
CEMENTITIOUS CRYSTALLIZING WATERPROOFING PART 1 GENERAL 1.1 SECTION INCLUDES A. Cementitious crystallizing waterproofing for interior/exterior walls and floor slabs with nonactive leaks. B. Cementitious
More informationSECTION MANUFACTURED ROOF EXPANSION JOINTS
SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationPRESTON HEALTH SERVICES ARCHITECT'S NO. 2700
SECTION 09 5113 - ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More information***************************************************************************************************************
03365 POST-TENSIONED CONCRETE *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 03 38 00. ***************************************************************************************************************
More informationFloor Insulation Underlayment Section Sound Control Matting
Floor Insulation Underlayment Section 09618 Sound Control Matting Part I General 1.1 Summary A. Section includes a sound control material for achieving an STC and IIC rating in excess of 50 to meet building
More informationSECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT
SECTION 220529 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Steel pipe hangers and supports. 2. Metal framing systems. 3. Thermal-hanger shield inserts. 4. Fastener systems.
More informationSECTION FIBERGLASS REINFORCED POLYMER (FRP) PANELS
SECTION 07 44 50 FIBERGLASS REINFORCED POLYMER (FRP) PANELS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Design, Engineering, manufacturing and erection of fiberglass reinforced panels. Delegated Design of
More informationSECTION CONCRETE PAVING SLABS SET IN MORTAR
SECTION 32 14 13.16 CONCRETE PAVING SLABS SET IN MORTAR (1995 MasterFormat Section 02784) Note: This guide specification for the U.S. is for paving slabs mortared to a concrete base and grouted joints
More informationITEM 458 WATERPROOFING FOR STRUCTURES
ITEM 458 WATERPROOFING FOR STRUCTURES 458.1. Description. This Item shall govern for the furnishing and placing of waterproofing on concrete and steel bridge decks of railroad structures and on other structures
More informationSECTION HANGERS AND SUPPORTS FOR PLUMBING
SECTION 22 05 29 HANGERS AND SUPPORTS FOR PLUMBING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationPIPE AND TUBE RAILINGS
SECTION 05521 - PIPE AND TUBE RAILINGS PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION CEMENT BOARD SUPPORTED ADHERED MASONRY VENEER. 2. Installation materials including adhesives, mortars, and pointing mortars.
(Specifier Note: The purpose of this guide specification is to assist the Specifier in correctly specifying cement board supported adhered masonry. The Specifier needs to edit these guide specifications
More informationA. Product Data: For each type of deck, accessory, and product indicated.
SECTION 053100 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Roof deck. 2. Composite floor deck. 3. Noncomposite form deck. 1.2 SUBMITTALS A. Product Data: For each type of deck, accessory, and
More informationA. Section includes hydraulic-cement-based, polymer-modified, self-leveling underlayment for application below interior floor coverings.
SECTION 03 54 16 - HYDRAULIC CEMENT UNDERLAYMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationDaytona Beach Pier Building Renovation Jun 2010
SECTION 15060 - HANGERS AND SUPPORTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationA. ASTM C190 - Test Method for Tensile Strength of Hydraulic Cement Mortars
SECTION 04850 (04 40 00) MSI PRECAST STONE VENEER SYSTEM PART 1 GENERAL 1.1 SECTION INCLUDES A. MSI Precast Stone Veneer for exterior and interior vertical surfaces. 1.2 RELATED SECTIONS Specifier Notes:
More informationTECHNICAL SPECIAL PROVISION FOR CONCRETE REPAIRS. Financial Project ID , &
TECHNICAL SPECIAL PROVISION FOR CONCRETE REPAIRS Financial Project ID 429140-1-52-01, 429140-2-52-01 & 428267-1-52-01 The official record of this Technical Special Provision is the electronic file signed
More informationCSI SECTION MAINTENANCE OF CONCRETE Repair & Resurfacing with Rapid Hardening, High Strength, Low-Shrink, Non-Metallic Cementitious Materials
CSI SECTION 03 01 00 MAINTENANCE OF CONCRETE Repair & Resurfacing with Rapid Hardening, High Strength, Low-Shrink, Non-Metallic Cementitious Materials EDITOR NOTE: The following guideline specification
More informationSECTION LIGHT DUTY SLIDING AND STACKING GLASS DOOR SYSTEMS
Page 1 of 9 SECTION 10 2238.13 LIGHT DUTY SLIDING AND STACKING GLASS DOOR SYSTEMS USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED FOLDING GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,
More informationENKASONIC FLOOR UNDERLAYMENT 9110
ENKASONIC FLOOR UNDERLAYMENT 9110 GS1197 Section 13080 SECTION 09618 SOUND CONTROL MATTING Part I General 1.1 Summary A. Section includes a sound control material for achieving an STC and IIC rating in
More informationB. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.
SECTION 230529 - HANGERS AND SUPPORTS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Sleeves. 6. Mechanical sleeve seals. 7. Firestopping
More informationGUIDE SPECIFICATION
GUIDE SPECIFICATION 09 64 33.01 940 Centre Circle, Suite 1000 Altamonte Springs, FL 32714 Telephone: 407-260-9910 Fax: 407-260-9933 Toll Free: 800-800-5247 Web Site: http://www.kahrs.com This Guide Specification
More information