Laboratory Report T R1

Size: px
Start display at page:

Download "Laboratory Report T R1"

Transcription

1 Simulated Wind Uplift Testing of LeakBarrier Self-Adhering Roof Systems in accordance with FM Standard 4470 and TAS 114 Prepared for: 2403 Taylors Valley Road Belton, TX Date of Issuance: June 26, 2007 Revision 1: October 9, 2007 EXTERIOR RESEARCH & DESIGN, LLC. MAIN: 80 Yesler Way Suite 200 Seattle, WA P: (206) F: (206) EAST: 353 Christian Street, Unit 13 Oxford, CT P: (203) F: (203) LAB 1: 600 W. Nickerson Street Seattle, WA P: (206) F: (206) LAB 2: 10 Mauney Court Columbia, SC P: (862) F: (803) TL-199 Certified

2 Page 2 of 8 Client Information: Client Reference: ERD Reference: Samples: Sample Delivery: 2403 Taylors Valley Road Belton, TX c/o: Shaik Mohseen Wind Uplift, Wood Decks Project # SC LeakBarrier HPP Asphalt Saturated Underlayment is a mechanically attached, polyester reinforced, asphalt-saturated base sheet. LeakBarrier Base Sheet is a self-adhered, fiberglass-reinforced, smooth-surfaced SBS modified bitumen base ply membrane. LeakBarrier Cap Sheet is a self-adhered, polyesterreinforced, granule-surfaced SBS modified bitumen cap ply membrane. Samples for base sheet rupture (pull-through) testing and wind uplift testing were delivered to the Trinity ERD laboratory located in Seattle, WA and Columbia SC, respectively. Test Date(s): May 1, 2007 and June 26, 2007 M-D Notification: TRINITY ERD Staff: Witnesses: Properties: ERD06049 Jeremy DeWitt, Todd Fritz, Michael Bloom, Robert Nieminen Shaik Mohseen, Base sheet pull-through (rupture) Simulated Wind Uplift Resistance Standards: FM Standard 4470, Class 1 Roof Covers, FM Global, 1986 (1992) TAS 114, Appendix J Test Procedure for 12 x24 Simulated Uplift Pressure Resistance of Roof System Assemblies, 1995, Miami-Dade BCCO. TAS 117(B) Test Procedure for Dynamic Pull-Through Performance of Roofing Membranes over Fastener Heads or Fasteners with Metal Bearing Plates, 1995, Miami-Dade BCCO. Equipment: Pull-Through Resistance: ComTen Wind Uplift Resistance: ERD 12 x24 Wind Uplift Chamber

3 Page 3 of 8 1. Rupture Performance Base Sheet and Coverboard Material 1.1 Samples of and 3/8-inch thick Securock were tested for rupture performance to determine the critical combination for use in full-scale test specimens and to assist with the design of full-scale specimens. 1.2 Specimen Preparation: Four 18 x 18 in. specimens of each combination was pierced with the reference fastening device, centered within each specimen. A cap sheet of was self-adhered to the top of each combination. 1.3 Procedure: The specimen is then clamped into the test apparatus, with the fastener shank pointing up. A grip is placed on the shank and pulled at a rate of 2 inches per minute. The maximum load incurred on the specimen is recorded. 1.4 Results: Specimen No. Table 1: Rupture (Pull-Through) Results (lbf) FBC HVHZ Nails & Tin Caps OMG 3 Galvalume Steel Plate TruFast MP-3 3/8-inch Securock OMG 3 Galvalume Steel Plate TruFast MP Average: Std. Deviation: Coefficient of Variation: 8% 2% 4% 5% 7% 1.5 Observations: The OMG 3 Galvalume Steel Plate is the critical stress plate for attachment of and Securock. Test results from full-scale testing using this critical plate are also applicable to use of the TruFast MP-3 plate.

4 Page 4 of 8 2. Simulated Wind Uplift Resistance 12 x 24 ft Pressure Differential 2.1 Specimen Preparation: One specimen measuring 13 x 26 ft was constructed for each of the following sample descriptions. The simulated wind uplift pressure tests utilize a 24 ft (7.3 m) long by 12 ft (3.7 m) wide steel vacuum pressure vessel arranged to apply vacuum air pressure at pre-established standard rates to the topside of the test panel, which forms the bottom of the pressure vessel Specimens were allowed to cure 7-days in outdoor, ambient conditions prior to testing. Sample ID System Type 1. F 2A. E 2B. E 3. C 4. D Table 2A: Summary of 12 x 24 ft Specimen Construction Coverboard or Substrate Attachment Attachment Base Ply Cap Ply Base Sheet 19/32 Plywood at 24 spans 19/32 Plywood at 24 spans 19/32 Plywood at 24 spans 19/32 Plywood at 24 spans 19/32 Plywood at 24 spans 8d ring shank nails 6-in o.c. 8d common nails 6-in o.c. 8d ring shank nails 6-in o.c. 8d common nails 6-in o.c. 8d common nails 6-in o.c. N/A N/A 3/8-in Securock Securock loose laid followed by FBC HVHZ prescribed nails & tin-caps 7-inch o.c. in 4 laps, with 3 rows 7-inch o.c. equally spaced in field. FBC HVHZ prescribed nails & tin-caps 7-inch o.c. in 4 laps, with 3 rows 7-inch o.c. equally spaced in field. OMG #12 Fasteners & OMG 3 Galvalume Steel Plates at 1 per 1 ft 2 OMG #12 Fasteners & OMG 3 Galvalume Steel Plates. 10-inch o.c. in laps and 10- inch o.c. in 2 equally spaced staggered rows 2.2 Procedure: A net pressure of 30 psf (1.4 kpa) is applied to the test sample and maintained for 1 minute. The pressure is increased to 45 psf (2.2 kpa), then to 60 psf (2.9 kpa) and held for 1 min. after each increment. The pressure is increased in increments of 15 psf (0.7 kpa) every min. until failure occurs. 2.3 Results: See Tables 2B through 2E, below.

5 Page 5 of 8 Table 2B: Test Results, Sample 1 Plywood (with 8d ring shank nails, 6 o.c.) / / Sample ID: 1 Failure Pressure 165 Failure Time (sec): During increase Failure Mode: Passing Pressure Plywood nail withdrawal 150 2:1 Margin of Safety 75 Table 2C: Test Results, Samples 2A & 2B Plywood / with nails & tin caps at 7, 7, 7, 7 / Sample ID: 2A (Plywood attached with 8d common nails) 2B (Plywood attached with 8d ring shank nails) Failure Pressure Failure Time (sec): On Rise On Rise Failure Mode: Plywood nail withdrawal Base sheet nail withdrawal Passing Pressure 2:1 Margin of Safety

6 Page 6 of 8 Table 2D: Test Results, Sample 3 Plywood (with 8d common nails, 6 o.c.) / 3/8-in. Securock with OMG parts at 1 per 1 ft2 / Sample ID: 3 Failure Pressure 120 Failure Time (sec): 20 Failure Mode: Passing Pressure Plywood nail withdrawal 105 2:1 Margin of Safety 52.5 Table 2E: Test Results, Sample 4 Plywood (with 8d common nails, 6 o.c.) / Securock, loose laid / with OMG parts at 10, 10, 10 / Sample ID: 4 Failure Pressure 135 Failure Time (sec): 10 Failure Mode: Passing Pressure Plywood nail withdrawal 120 2:1 Margin of Safety 60

7 Page 7 of 8 3. Observations: 3.1 Deck construction consisted of 19/32 thick plywood attached to structural supports of Southern Yelllow Pine spaced 24-inch o.c Panels 2A, 3 and 4 utilized 8d common nails spaced 6 o.c. for plywood securement, and displayed withdrawal of said nails from structural supports at 105, 120 and 135 psf (passing 90, 105 and 120 psf), respectively Panels 1 and 2B utilized 8d ring shank nails spaced 6 o.c. for plywood securement. Panel 1 displayed withdrawal of said nails from structural supports at 165 psf (passing 150 psf), while Panel 2B displayed withdrawal of the base sheet nails from the plywood deck at 135 psf (passing 120 psf) At no point during any of the tests did or display a loss of adhesion from its substrate. 3.2 Samples 3 and 4 were constructed using critical OMG stress plates. 3.3 The use of optional insulation between the coverboard and the deck in Sample 3 would have no bearing on system performance, as the insulation would carry no uplift load. 3.4 The use of alternate type of insulation and/or coverboard between the deck and the base sheet in Sample 4 would have no bearing on system performance, as the insulation and/or coverboard would carry no uplift load. 4. Conclusions: 4.1 TRINITY ERD has tested the specimens outlined in Table 2A, for wind uplift resistance in accordance with FM Standard 4470, Appendix K and FBC TAS 114, Appendix J resulting in the data outlined in Tables 2B -1E. Observations are outlined in Section A summary of systems and maximum design pressures with a 2 to 1 margin of safety are provided in Appendix 1 of this report.

8 Page 8 of 8 Please contact our offices with any questions. Sincerely, TRINITY ERD Jeremy DeWitt Codes / Product Development Manager Todd Fritz Laboratory Quality Manager Reviewed by: Robert Nieminen, P.E. Vice President Florida Reg. No This report and the data contained therein is the sole property of Trinity ERD and the named client. This report shall not be reproduced outside Trinity ERD except by the named client without written permission by the named client, in which case the report shall be reproduced in its entirety. Attached: Appendix 1, Summary of Systems and MDP s

9 Systems Summary: The following notes apply to the systems outlined herein: 1. Roof decks shall be in accordance with FBC requirements to the satisfaction of the AHJ, but not less than that noted herein. 2. For mechanically attached components, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 16, and Zones 2 and 3 shall employ a tighter attachment density designed by a qualified design professional to resist the elevated pressure criteria. 3. For insulations not specifically called-out by tradename, the insulation may be any polyisocyanurate, polystyrene, fiberboard or perlite insulation board that meets the quality assurance requirements of F.A.C. Rule 9B-72 and is documented as meeting FBC and, for foam plastic, FBC or , when installed with the roof cover. 4. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysis shall be in accordance with TAS 105. TABLE 1: WOOD DECKS NEW CONSTRUCTION, REROOF (Tear-Off) or RECOVER SYSTEM TYPE C: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System No. Roof Deck Base Insulation Top Insulation Layer Roof Cover Layer Type Fasteners Attach Base Ply Cap Max. Design Pressure W-1 Min. 19/32 plywood at max. 24 spans attached with 8d common or ring shank nails, 6 o.c. (Optional) One or more layers, any combination, loose laid Min. 3/8-inch Securock Roof Board OMG #12 or #14 Heavy Duty with OMG 3 in. Galvalume Steel Plate or Trufast DP or HD with Trufast MP-3 1 per 1 ft 2 (Optional) psf System No. W-2 Roof Deck Min. 19/32 plywood at max. 24 spans attached with 8d common or ring shank nails, 6 o.c. TABLE 2: WOOD DECKS NEW CONSTRUCTION, REROOF (Tear-Off) or RECOVER SYSTEM TYPE D: LOOSE LAID INSULATION, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER Insulation Layer Base Sheet Roof Cover Type Attach Type Fasteners Attach Ply Cap Any type, thickness or combination Loose laid OMG #12 or #14 Heavy Duty with OMG 3 in. Galvalume Steel Plate or Trufast DP or HD with Trufast MP-3 10-inch o.c. in the min. 4-inch lap and 10-inch o.c. in two, equally spaced, staggered center rows Max. Design Pressure psf Exterior Research and Design, LLC. d/b/a Trinity ERD Laboratory Report T R1 Certificate of Authorization #9503 Date of Issuance: 06/26/2007 Appendix 1, Page 1 of 2

10 TABLE 3: WOOD DECKS NEW CONSTRUCTION or REROOF (Tear-Off) SYSTEM TYPE E: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System No. Roof Deck Base Sheet Roof Cover Type Fasteners Attach Ply Cap Max. Design Pressure W-3 Min. 19/32 plywood at max. 24 spans attached with 8d common nails, 6 o.c. 12 ga. annular ring shank nails and min. 32 ga., 1-5/8 diameter tincaps. (Ref: FBC ) 7-inch o.c. in the 4-inch lap and 7- inch o.c. in three, equally spaced, staggered center rows psf W-4 Min. 19/32 plywood at max. 24 spans attached with 8d ring shank nails, 6 o.c. 12 ga. annular ring shank nails and min. 32 ga., 1-5/8 diameter tincaps. (Ref: FBC ) 7-inch o.c. in the 4-inch lap and 7- inch o.c. in three, equally spaced, staggered center rows psf W-5 Min. 19/32 plywood at max. 24 spans attached with 8d common or ring shank nails, 6 o.c. OMG #12 or #14 Heavy Duty with OMG 3 in. Galvalume Steel Plate or Trufast DP or HD with Trufast MP-3 10-inch o.c. in the min. 4-inch lap and 10-inch o.c. in two, equally spaced, staggered center rows psf System No. W-6 Roof Deck Min. 19/32 plywood at max. 24 spans attached with 8d ring shank nails, 6 o.c. TABLE 4: WOOD DECKS NEW CONSTRUCTION or REROOF (Tear-Off) SYSTEM TYPE F: BONDED ROOF COVER Roof Cover Max. Design Pressure Base Ply Cap (Optional) psf Exterior Research and Design, LLC. d/b/a Trinity ERD Laboratory Report T R1 Certificate of Authorization #9503 Date of Issuance: 06/26/2007 Appendix 1, Page 2 of 2

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants Exterior Research & Design, L.L.C. Building Science and Envelope Consultants Certificate of Evaluation Report 3520.03.04-R2 Evaluation of Roof s for Florida Product Approval #FL2533-R2 Prepared for: CertainTeed

More information

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants Exterior Research &, L.L.C. Building Science and Envelope Consultants Certificate of Authorization #9503 Evaluation Report 00256.09.06 Evaluation of Roofing s for Florida Product Approval #FL7508 Prepared

More information

EVALUATION REPORT ICP Adhesives and Sealants, Inc NW 44 th Street Coral Springs, FL 33065

EVALUATION REPORT ICP Adhesives and Sealants, Inc NW 44 th Street Coral Springs, FL 33065 EVALUATION REPORT ICP Adhesives and Sealants, Inc. 12505 NW 44 th Street Coral Springs, FL 33065 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 CHRISTIAN STREET, UNIT 13 OXFORD,

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203)

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203) EVALUATION REPORT Carlisle SynTec Systems P.O. Box 7000 Carlisle, PA 17013 (717) 245-7264 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 Christian Street Oxford, CT 06478 PHONE:

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786)315-2590

More information

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203)

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203) EVALUATION REPORT Johns Manville Corporation P.O. Box 5108 Denver, CO 80217 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 Christian Street Oxford, CT 06478 PHONE: (203) 262-9245

More information

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street, Unit 13 Oxford, CT (203)

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street, Unit 13 Oxford, CT (203) EVALUATION REPORT Duro-Last Roofing, Inc. 525 Morley Drive Saginaw, MI 48601 (800) 248-0280 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 Christian Street, Unit 13 Oxford, CT

More information

EVALUATION REPORT Boral Roofing 7575 Irvine Center Drive Suite 100 Irvine, CA

EVALUATION REPORT Boral Roofing 7575 Irvine Center Drive Suite 100 Irvine, CA EVALUATION REPORT Boral Roofing 7575 Irvine Center Drive Suite 100 Irvine, CA. 92618 EXTERIOR RESEARCH & DESIGN, LLC. 353 CHRISTIAN STREET, UNIT #13 OXFORD, CT 06478 PHONE: (203) 262-9245 FAX: (203) 262-9243

More information

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203)

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203) EVALUATION REPORT Mule-Hide Products Co., Inc. 1195 Prince Hall Drive Beloit, WI 53511 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 Christian Street Oxford, CT 06478 PHONE: (203)

More information

EVALUATION REPORT Tarco Roofing One Information Way, Suite 225 Little Rock, AR DESCRIPTION: Tarco Roof Underlayments

EVALUATION REPORT Tarco Roofing One Information Way, Suite 225 Little Rock, AR DESCRIPTION: Tarco Roof Underlayments EVALUATION REPORT Tarco Roofing One Information Way, Suite 225 Little Rock, AR 72202 EXTERIOR RESEARCH & DESIGN, LLC. 353 CHRISTIAN STREET, UNIT #13 OXFORD, CT 06478 PHONE: (203) 262-9245 FAX: (203) 262-9243

More information

DESCRIPTION: Firestone SBS and APP Modified Bitumen Roof Systems

DESCRIPTION: Firestone SBS and APP Modified Bitumen Roof Systems EVALUATION REPORT Firestone Building Products Company, LLC. 250 West 96 th treet Indianapolis, IN 46260 (800) 443-4272 EXTERIOR REEARCH & DEIGN, LLC. Certificate of Authorization #9503 353 Christian treet

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

Florida Building Code Online Page 1 of 2 BCIS Home Log In User Registration Hot Topics Submit Surcharge Stats & Facts Publications FBC Staff BCIS Site Map Links Search Product Approval USER: Public User

More information

technical bulletin ROOFING CORPORATION

technical bulletin ROOFING CORPORATION ROOFING CORPORATION technical bulletin TO: All Region Managers, Plant Managers, National Account Managers, Sales Representatives, Account Executives, and Atlanta Sales FROM: Ed Todd, Director, Product

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 NOTICE OF ACCEPTANCE

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3909 Issued 07/2017 This report is subject to renewal 07/2018. DIVISION: 07 00 00

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

UL Evaluation Report UL ER Issued: December 19, 2014 Revised: August 14, UL Category Code: ULFB. CSI MasterFormat

UL Evaluation Report UL ER Issued: December 19, 2014 Revised: August 14, UL Category Code: ULFB. CSI MasterFormat UL Evaluation Report UL ER9516-02 Issued: December 19, 2014 Revised: August 14, 2015 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code:

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

UL Evaluation Report UL ER Issued: July 25, UL Category Code: ULFB. CSI MasterFormat

UL Evaluation Report UL ER Issued: July 25, UL Category Code: ULFB. CSI MasterFormat UL Evaluation Report UL ER10167-01 Issued: July 25, 2014 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code: ULFB CSI MasterFormat DIVISION:

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY AFFAIRS (PERA) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786)315-2590

More information

technical bulletin ROOFING CORPORATION

technical bulletin ROOFING CORPORATION ROOFING CORPORATION technical bulletin TO: All Region Managers, Plant Managers, National Account Managers, Sales Representatives, Account Executives, and Atlanta Sales FROM: Ed Todd, Director, Product

More information

UL Evaluation Report UL ER Issued: December 9, Revised: September 29, UL Category Code: ULFB. CSI MasterFormat

UL Evaluation Report UL ER Issued: December 9, Revised: September 29, UL Category Code: ULFB. CSI MasterFormat UL Evaluation Report UL ER9516-01 Issued: December 9, 2013 Revised: September 29, 2017 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code:

More information

2010 FLORIDA BUILDING CODE TEST PROTOCOLS HVHZ (TAS)

2010 FLORIDA BUILDING CODE TEST PROTOCOLS HVHZ (TAS) TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE FOR FIELD UPLIFT RESISTANCE OF EXISTING MEMBRANE ROOF SYSTEMS AND IN SITU TESTING FOR REROOF AND NEW CONSTRUCTION APPLICATIONS 1. Scope: 1.1 This

More information

statement: "Miami-Dade County Product Control Approved", unless otherwise noted herein.

statement: Miami-Dade County Product Control Approved, unless otherwise noted herein. MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786)315-2590

More information

DESCRIPTION: Eagle Roof Tiles

DESCRIPTION: Eagle Roof Tiles EVALUATION REPORT Eagle Roofing Products Florida LLC. 1575 East Country Road 470 Sumterville, FL 33585 (800) 400-3245 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 CHRISTIAN STREET,

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590

More information

Addendum No. 1. ITB for Emergency Management/Utilities Administration Building Renovation Addendum Release Date April 06, 2017

Addendum No. 1. ITB for Emergency Management/Utilities Administration Building Renovation Addendum Release Date April 06, 2017 City of Wilton Manors Finance Department 2020 Wilton Drive Wilton Manors, FL 33305 Phone (954) 390-2171 Fax (954)390-2199 www.wiltonmanors.com Addendum No. 1 ITB # 2016-16 ITB for Emergency Management/Utilities

More information

EVALUATION REPORT Soprema, Inc. 310 Quadral Drive Wadsworth, OH 44281

EVALUATION REPORT Soprema, Inc. 310 Quadral Drive Wadsworth, OH 44281 EVALUATION REPORT Soprema, Inc. 310 Quadral Drive Wadsworth, OH 44281 EXTERIOR RESEARCH & DESIGN, LLC. 353 CHRISTIAN STREET OXFORD, CT 06478 PHONE: (203) 262-9245 FAX: (203) 262-9243 Date of Issuance:

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590

More information

ANSI/FM Approvals March FM Approvals LLC. All rights reserved.

ANSI/FM Approvals March FM Approvals LLC. All rights reserved. American National Standard for Evaluating the Simulated Wind Uplift Resistance of Roof Assemblies Using Static Positive and/or Negative Differential Pressures ANSI/FM Approvals 4474 March 2004 2004 FM

More information

TESTING APPLICATION STANDARD (TAS) No TEST PROCEDURE FOR STATIC UPLIFT RESISTANCE OF MORTAR OR ADHESIVE SET TILE SYSTEMS

TESTING APPLICATION STANDARD (TAS) No TEST PROCEDURE FOR STATIC UPLIFT RESISTANCE OF MORTAR OR ADHESIVE SET TILE SYSTEMS TESTING APPLICATION STANDARD (TAS) No. 101-95 TEST PROCEDURE FOR STATIC UPLIFT RESISTANCE OF MORTAR OR ADHESIVE SET TILE SYSTEMS 1. Scope 2. Referenced Documents 1.1 This Protocol covers the determination

More information

EVALUATION REPORT GAF 1361 Alps Road, Building 7-3 Wayne, NJ 07470

EVALUATION REPORT GAF 1361 Alps Road, Building 7-3 Wayne, NJ 07470 EVALUATION REPORT GAF 1361 Alps Road, Building 7-3 Wayne, NJ 07470 EXTERIOR RESEARCH & DESIGN, LLC. 353 CHRISTIAN STREET, UNIT #13 OXFORD, CT 06478 PHONE: (203) 262-9245 FAX: (203) 262-9243 Date of Issuance:

More information

Re-Roof Permit Checklist

Re-Roof Permit Checklist Re-Roof Permit Checklist The following items are required with submission of your building permit application: 2 copies of completed Re-Roof permit application Roof Pressure Sheet completed as applicable

More information

SECTION LIGHTWEIGHT INSULATING CONCRETE

SECTION LIGHTWEIGHT INSULATING CONCRETE SECTION 03342 LIGHTWEIGHT INSULATING CONCRETE PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 03300 - Cast-In-Place Concrete. 2. 05310 - Steel Deck. 3. 07511 - Multi-Ply Mineral Surfaced Built-Up Roofing

More information

MILLENNIUM METALS, INC TEST REPORT

MILLENNIUM METALS, INC TEST REPORT MILLENNIUM METALS, INC TEST REPORT SCOPE OF WORK WIND DRIVEN RAIN RESISTANCE TESTING OF MMI 26 GA OFF RIDGE VENT WITH DETACHABLE BAFFLE REPORT NUMBER H7685.03-450-18 R1 TEST DATE 11/29/17 ISSUE DATE 12/18/17

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: POLYGLASS USA, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: POLYGLASS USA, INC. 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2018 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 07 00

More information

TEST PROCEDURE FOR AIR PERMEABILITY TESTING OF RIGID, DISCONTINUOUS ROOF SYSTEMS

TEST PROCEDURE FOR AIR PERMEABILITY TESTING OF RIGID, DISCONTINUOUS ROOF SYSTEMS TESTING APPLICATION STANDARD (TAS) 116-95 TEST PROCEDURE FOR AIR PERMEABILITY TESTING OF RIGID, DISCONTINUOUS ROOF SYSTEMS Scope 1.1 This Protocol covers the determination of the air permeability characteristics

More information

ROOF MITIGATION STRUCTURE EVALUATION FORM. For Single Family Residential Re-Roof Effective October 1, 2007 (Revised February 2, 2018)

ROOF MITIGATION STRUCTURE EVALUATION FORM. For Single Family Residential Re-Roof Effective October 1, 2007 (Revised February 2, 2018) ROOF MITIGATION STRUCTURE EVALUATION FORM For Single Family Residential Re-Roof Effective October 1, 2007 (Revised February 2, 2018) Check One Value of home does not exceed $300,000 based on insured value

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

Wood Decks Testing Reveals Best Wood Roof Deck Systems to Resist Wind-Uplift by Fulton Desler, senior engineer, APA The Engineered Wood Association

Wood Decks Testing Reveals Best Wood Roof Deck Systems to Resist Wind-Uplift by Fulton Desler, senior engineer, APA The Engineered Wood Association This article was originally published in Western Roofing January/February 2007 Wood Decks Testing Reveals Best Wood Roof Deck Systems to Resist Wind-Uplift by Fulton Desler, senior engineer, APA The Engineered

More information

Roof Replacement. Notes: T-1 (Title Sheet) Roof Key Plan Russell House Student Union 1400 Greene Street Columbia, South Carolina 29208

Roof Replacement. Notes: T-1 (Title Sheet) Roof Key Plan Russell House Student Union 1400 Greene Street Columbia, South Carolina 29208 Notes: Drawing Index T-1 Title R-1 Roof Plan - Existing Conditions R-2 Roof Plan - New D-1 Roof Details D-2 Roof Details D-3 Roof Details M-1 Mechanical - Roof Plan M-2 Mechanical - Details Roof Key Plan

More information

DRAFT NOTICE OF ACCEPTANCE (NOA)

DRAFT NOTICE OF ACCEPTANCE (NOA) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590

More information

Residential, 26 Ga. Roof Panel over 15/32 Plywood. Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D

Residential, 26 Ga. Roof Panel over 15/32 Plywood. Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Product Evaluation Report REED S METAL, INC. Residential, 26 Ga. Roof Panel over 15/32 Plywood Florida Product Approval # 12725.2 R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Category: Roofing

More information

SPECIFICATION SUBMITTAL

SPECIFICATION SUBMITTAL 101C AWAPLAN PREMIUM INSULATED DECK TAMKO BASE PLY INSULATION 1/2 m = 50 cm = 19-11/16 inches 1 m = 100 cm = 39-3/8 inches Material Requirements TAMKO GLASS-BASE, TAM-GLASS PREMIUM, TAM- PLY IV, or BASE-N-PLY

More information

CREEK Technical Services, LLC

CREEK Technical Services, LLC a CREEK Certificate of Authization 29824 17520 Edinburgh Drive Tampa, FL 33647 (813) 480-3421 EVALUATION REPORT FLORIDA BUILDING CODE 5 TH EDITION (2014) Manufacturer: JOHNS MANVILLE CORPORATION Issued

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: POLYVINYL CHLORIDE ROOFING REPORT HOLDER: IB ROOF SYSTEMS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: POLYVINYL CHLORIDE ROOFING REPORT HOLDER: IB ROOF SYSTEMS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 28 Reissued 02/2018 This report is subject to renewal 02/2019. DIVISION: 07 00 00

More information

REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC 250 WEST 96 TH STREET INDIANAPOLIS, INDIANA EVALUATION SUBJECT:

REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC 250 WEST 96 TH STREET INDIANAPOLIS, INDIANA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2831 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00

More information

Subject: NRCA MRCA Joint Technical Bulletin. Date: January 2008 NOT COMPROMISE.

Subject: NRCA MRCA Joint Technical Bulletin. Date: January 2008 NOT COMPROMISE. Roofing No. 3001 NRCA MRCA Joint Technical Bulletin Attached is a copy of the NRCA/MRCA Joint Technical Bulletin which was presented at the 1987 MRCA Convention. This document is entitled, In-Service R-Values

More information

Uniform Mitigation Verification Inspection Form Maintain a copy of this form and any documentation provided with the insurance policy

Uniform Mitigation Verification Inspection Form Maintain a copy of this form and any documentation provided with the insurance policy Uniform Mitigation Verification Inspection Form Maintain a copy of this form and any documentation provided with the insurance policy Inspection Date: 04/01/2015 Owner Information Owner Name: JACK AND

More information

Recommended Fastening Patterns for Rmax Insulation in Low Slope Roofing Applications

Recommended Fastening Patterns for Rmax Insulation in Low Slope Roofing Applications Recommended Fastening Patterns for Rmax Insulation in Low Slope Roofing Applications INTRODUCTION Rmax recommends that any insulation which is laid over a steel or wood roof deck be attached with mechanical

More information

Thermoplastic Single Ply & Multi-Ply Roofing Systems

Thermoplastic Single Ply & Multi-Ply Roofing Systems Thermoplastic Single Ply & Multi-Ply Roofing Systems COMMERCIAL INDUSTRIAL INSTITUTIONAL RESIDENTIAL Specializing in Roof Solutions for over 25 years FlexRoofingSystems.com Thermoplastic Single Ply Roof

More information

ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95

ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95 ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95 TEST PROCEDURE FOR STATIC UPLIFT RESISTANCE OF MECHANICALLY ATTACHED, CLIPPED, RIGID, ROOF SYSTEMS (For Methods of Mechanical Attachment Excluding Clips,

More information

Sure-Weld (TPO) Adhered Roofing Systems Code Approval Guide January, Table of Contents

Sure-Weld (TPO) Adhered Roofing Systems Code Approval Guide January, Table of Contents (TPO) Adhered Roofing Systems Code Approval Guide January, 2017 Introduction... ii Guidelines... Mechanically Fastened or Induction Welding Roofing Systems UL Approvals NonCombustible ANSI UL Class A...

More information

RESIDENTIAL RE-ROOFING PERMIT APPLICATION

RESIDENTIAL RE-ROOFING PERMIT APPLICATION RESIDENTIAL RE-ROOFING PERMIT APPLICATION Effective date: October 1, 2007. Note: These requirements apply to residential structures built prior to implementation of the FBC on March 1, 2002. I. LEGAL DESCRIPTION:

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ETHYLENE PROPYLENE DIENE MONOMER ROOFING REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ETHYLENE PROPYLENE DIENE MONOMER ROOFING REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Rept ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.g ESR 3026 Reissued 04/207 This rept is subject to renewal 04/208. DIVISION: 07 00 00 THERMAL

More information

EMPIRE SHAKE, EMPIRE PLUS SHAKE, AND EMPIRE SLATE POLYOLEFIN COMPOSITE TILES

EMPIRE SHAKE, EMPIRE PLUS SHAKE, AND EMPIRE SLATE POLYOLEFIN COMPOSITE TILES UL Evaluation Report UL ER18920-01 Issued: August 15, 2014 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code: ULEX CSI MasterFormat DIVISION:

More information

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC.

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. 26 Ga. GulfRib Roof Panel over 15/32 Plywood Florida Product Approval #11651.22 R3 Florida Building Code 2017 Per Rule 61G20-3 Method:

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786)315-2590

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: CERTAINTEED CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: CERTAINTEED CORPORATION 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1388 Reissued 05/2017 This report is subject to renewal 05/2018. DIVISION: 07 00 00 THERMAL

More information

Florida Building Code Product Approval

Florida Building Code Product Approval Florida Building Code Product Approval Updated 4/7/10 Your Best and Safest Choice Quality You Can Trust Since 1886! Florida Building Code Online http://floridabuilding.org/pr/pr_app_dtl.aspx?param=wgevxqwtdquqvxydmpwxq0d...

More information

Understanding Wind Uplift Ratings

Understanding Wind Uplift Ratings Page 1 of 5 Home Understanding Wind Uplift Ratings By Stan Choiniere September 1, 2006 What is an FM Approvals wind test, and what do the various wind uplift ratings mean? This question is frequently asked,

More information

HALIFAX HUMANE SOCIETY BOARDING AND GROOMING FACILITY SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS

HALIFAX HUMANE SOCIETY BOARDING AND GROOMING FACILITY SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS SECTION 075216 - PART 1 - GENERAL 1.1 SUMMARY A. Section includes styrene-butadiene-styrene (SBS) modified bituminous membrane roofing. 1.2 DEFINITIONS A. Hot Roofing Asphalt: Roofing asphalt heated to

More information

ROOFING APPLICATION STANDARD (RAS) No. 109

ROOFING APPLICATION STANDARD (RAS) No. 109 ROOFING APPLICATION STANDARD (RAS) No. 109 Scope 1.1 This Roofing Application Standard sets the requirements to determine whether a substrate and surrounding environmental conditions are appropriate for

More information

FM APPROVALS Boston Providence Turnpike, Norwood, MA Phone: (781) Fax: (781) E mail:

FM APPROVALS Boston Providence Turnpike, Norwood, MA Phone: (781) Fax: (781) E mail: THE DEVELOPMENT OF FM APPROVAL STANDARDS FOR CLASS ONE STEEP ROOF COVERS, FLEXIBLE PHOTOVOLTAIC MODULES, AND VEGETATIVE ROOF SYSTEMS BY DAVID L. ALVES FM APPROVALS 1151 Boston Providence Turnpike, Norwood,

More information

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC.

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. 26 Ga. GulfRib Roof Panel over 15/32 Plywood Florida Product Approval #11651.23 R3 Florida Building Code 2017 Per Rule 61G20-3 Method:

More information

Firestone Polyiso Boards

Firestone Polyiso Boards Firestone Polyiso Boards Superior energy efficiency. Superior protection. Firestone Polyiso Boards POLISOBROUK10.indd 1 1/04/10 14:26 Firestone Polyiso Boards Firestone total roofing systems Since Firestone

More information

1. SUBJECT: DURO-LAST, DURO-TUFF, DURO-FLEECE, and DURO-FLEECE PLUS ROOFING MEMBRANES

1. SUBJECT: DURO-LAST, DURO-TUFF, DURO-FLEECE, and DURO-FLEECE PLUS ROOFING MEMBRANES UL Evaluation Report UL ER10128-01 Issued: January 22, 2016 Revised: September 30, 2017 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code:

More information

CBUCK Engineering. Product: Zee-Lock Roof Panel Material: Steel Panel Thickness: 24 gauge Panel Width: 16 Support: Wood Deck

CBUCK Engineering. Product: Zee-Lock Roof Panel Material: Steel Panel Thickness: 24 gauge Panel Width: 16 Support: Wood Deck Evaluation Report Zee-Lock With Continous Zee-Rib Clip Metal Roof Assembly Manufacturer: 1720 Maury Road Houston, TX 77026 (800) 231-8127 2333 for Florida Product Approval HVHZ # FL 15471.1 Florida Building

More information

PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY

PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY MIAMI DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY 11805 SW 26 Street, Room 208 AFFAIRS (PERA) Miami, Florida 33175 2474 BOARD AND CODE ADMINISTRATION DIVISION

More information

COMMERCIAL WINDSTORM MITIGATION INSPECTION REPORT Prepared for: Boca Vista Condominium Association, Inc th Avenue Madeira Beach, FL 33708

COMMERCIAL WINDSTORM MITIGATION INSPECTION REPORT Prepared for: Boca Vista Condominium Association, Inc th Avenue Madeira Beach, FL 33708 Insurance Appraisals Reserve Studies Wind Mitigation COMMERCIAL WINDSTORM MITIGATION INSPECTION REPORT Prepared for: Boca Vista Condominium Association, Inc. 401 150th Avenue Madeira Beach, FL 33708 As

More information

LEGACY REPORT DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FLUID APPLIED ROOFING REPORT HOLDER: CONKLIN COMPANY INC.

LEGACY REPORT DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FLUID APPLIED ROOFING REPORT HOLDER: CONKLIN COMPANY INC. 0 Most Widely Accepted and Trusted ICC ES Legacy Report ICC ES 000 (800) 42 6587 (562) 699 054 www.icc es.org ER 520 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 07 00 00 THERMAL

More information

Christopher North Builders, INC.

Christopher North Builders, INC. Christopher North Builders, INC. 239-825-9155 Naples, Florida 34108 chrisnorthnaples@gmail.com Inspection Date: Uniform Mitigation Verification Inspection Form Maintain a copy of this form and any documentation

More information

CBUCK Engineering. Evaluation Report Englert Series 500 Metal Roof Assembly Manufacturer: Englert, Inc Amboy Avenue Perth Amboy, NJ

CBUCK Engineering. Evaluation Report Englert Series 500 Metal Roof Assembly Manufacturer: Englert, Inc Amboy Avenue Perth Amboy, NJ Evaluation Report Englert Series 500 Metal Roof Assembly Manufacturer: 1200 Amboy Avenue Perth Amboy, NJ 08862 for Florida Product Approval # FL 11698.2 R3 Florida Building Code 5th Edition (2014) Method:

More information

Impact Resistance What the Hail Is Happening?

Impact Resistance What the Hail Is Happening? Impact Resistance What the Hail Is Happening? Thomas J. Taylor GAF 1 Campus Drive Parsippany, NJ 07054 1 April 11 th 2016 Wylie, TX Hail Storm Hail can be very destructive! How can we manage the risk?

More information

CBUCK Engineering. Florida Product Approval # FL R2

CBUCK Engineering. Florida Product Approval # FL R2 Specialty Structural Engineering CBUCK, Inc. Certificate of Authorization #8064 Prepared by: James L. Buckner, P.E., SECB Florida Professional Engineer # 31242 Florida Evaluation ANE ID: 1916 Project Manager:

More information

Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D

Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Product Evaluation Report REED S METALS, INC. Perma-Lok, 26 Ga. 16 Coverage Roof Panel over 15/32 Plywood Florida Product Approval # 12725.1 R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Category:

More information

SHEET METAL ROOF TEST REPORT

SHEET METAL ROOF TEST REPORT SHEET METAL ROOF TEST REPORT Introduction The time tested performance of the double lock standing seam and batten seam metal roofing is demonstrated by thousands of squares successfully installed by SMACNA

More information

Quality You Can Trust Since From North America s Largest Roofing Manufacturer

Quality You Can Trust Since From North America s Largest Roofing Manufacturer Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer Florida Building Code Online http://floridabuilding.org/pr/pr_app_dtl.aspx?param=wgevxqwtdqsxyieb4opodtnwo... Page

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

JM PVC Fleece Backed 50 mil, JM PVC Fleece Backed 60 mil, JM PVC Fleece Backed 80 mil

JM PVC Fleece Backed 50 mil, JM PVC Fleece Backed 60 mil, JM PVC Fleece Backed 80 mil UL Evaluation Report UL ER10167-02 Issued: August 8, 2016 Revised: November 3, 2016 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code: ULFB

More information

CONSTRUCTION MATERIALS

CONSTRUCTION MATERIALS CONSTRUCTION MATERIALS T E C H N O L O G I E S WATER PONDING EVALUATION OF THE EDGE TM VENT (PROJECT NO. AVIG-004-02-01) For AIR VENT, INC. 4117 PINNACLE POINT DRIVE, SUITE 200 DALLAS, TX 75211 JUNE 20,

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

CBUCK Engineering. Evaluation Report Cee Lock Panel Metal Roof Assembly

CBUCK Engineering. Evaluation Report Cee Lock Panel Metal Roof Assembly Specialty Structural Engineering CBUCK, Inc. Certificate of Authorization #8064 Prepared by: James L. Buckner, P.E., S.E.C.B. Florida Professional Engineer # 31242 Florida Evaluation ANE ID: 1916 Project

More information

American National Standard Standard Field Test Procedure for Determining the Withdrawal Resistance of Roofing Fasteners

American National Standard Standard Field Test Procedure for Determining the Withdrawal Resistance of Roofing Fasteners ANSI/SPRI FX-1 American National Standard Standard Field Test Procedure for Determining the Withdrawal Resistance of Roofing Fasteners Table of Contents 1.0 Purpose................................................

More information

PRP-108 Performance Standards and Policies for Structural-Use Panels

PRP-108 Performance Standards and Policies for Structural-Use Panels A P A S T A N D A R D PRP-108 Performance Standards and Policies for Structural-Use Panels Published by APA The Engineered Wood Association February 1994 A P A The Engineered Wood Association 1997 APA

More information

SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS MEMBRANE ROOFING

SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS MEMBRANE ROOFING SECTION 075216 - STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS MEMBRANE ROOFING PART 1 - GENERAL 1.1 SUMMARY A. Section includes styrene-butadiene-styrene (SBS) modified bituminous membrane roofing.

More information

Uniform Mitigation Verification Inspection Form Maintain a copy of this form with insurance policy

Uniform Mitigation Verification Inspection Form Maintain a copy of this form with insurance policy Uniform Mitigation Verification Inspection Form Maintain a copy of this form with insurance policy Inspection Date: 08/12/2011 Owner Information Owner Name: Steve Owner Contact Person: Joe Contact Address:

More information