Composite Insulator Design for New U.K. Transmission Lines

Size: px
Start display at page:

Download "Composite Insulator Design for New U.K. Transmission Lines"

Transcription

1 Composite Insulator Design for New U.K. Transmission Lines Abstract:Changes to generation over the next decade mean that there will be substantial investment in expanding and upgrading the U.K. s transmission network. National Grid has embraced the need to harness innovation to build new and upgrade existing transmission assets in order to operate a more flexible network, facilitating connection of its customers including an increasing proportion of lower carbon generation to meet Government environmental targets. This INMR article, based on a contribution by Mike Fairhurst of the National Grid provides insight into development of unique 400 kv double circuit transmission lines across the U.K. Lattice steel structures have been deployed in the U.K. for the last 90 years, with the first design selected based on a design competition and evolving over time. In 2011, the Department of Energy & Climate Change as well as National Grid called on architects, designers, engineers and students to come up with innovative transmission tower designs that balance energy needs and visual impact, again carried out on a competitive basis. The competition attracted 250 entries with scale models of the finalists going on public display at the Victoria and Albert Museum as part of the London Design Festival. The winning design the T Pylon submitted by Danish company Bystrup was the overall winner. The basic loading criteria for the design is based on an existing lattice design consisting of a double circuit 400 kv line with a maximum demand transfer of 3800 MVA on a 3-phase, triple bundled, 500 mm spaced, 700 mm 2 AAAC conductors (Araucaria) National Grid subsequently engaged Bystrup to take the design from concept to full engineering compliance, having established that they had the necessary experience and capability in transmission tower design. The design team also engaged a number of composite insulator manufacturers to develop the insulator array. As the T Pylon moved from concept to detailed design, National Grid worked closely with the design team to develop a tower family, based on the original concept, so that it could become a viable alternative to traditional lattice designs for transmission routes of the future.

2 In moving from concept to full design, a great deal of effort was put into the mechanical performance and manufacturing processes. This involved producing full-scale prototypes and developing procedures to fully test mechanical performance under a number of extreme conditions. The diamond shaped design has to withstand high compression and torsional forces under broken wire conditions as well as extreme wind and ice. In parallel with this developmental work, the electrical performance needed to be fully understood since this was a completely new insulator arrangement that incorporates composite line insulators along with substation composite post insulators both solid and hollow core. No international standards yet exist for this arrangement and National Grid therefore engaged two domestic universities to carry out electrical performance studies. In addition, European-accredited test institutions were engaged in association with National Grid and the designer in compiling a robust test protocol to prove the electrical performance of the insulator array. National Grid also has responsibility to ensure that the erection, maintenance and repair of this novel design of transmission line can be carried out safely and efficiently. To that end, a full-scale training facility was constructed that incorporates the entire T Pylon suite of towers. The National Training Centre at Eakring in Nottingham allows development of erection and stringing techniques as well as maintenance and repair procedures in advance of any new build. A plan and photo of this facility is shown below in Appendix 1. Tower Types At the project s onset, the team looked at existing tower structures and their capability to determine what tower types would be required to design and construct a new line. In the U.K. a family of towers is typically designed with a selection of standard height suspension towers with an array of extensions, a range of tension towers with various maximum angles of deviation (typically 10, 30, 60 and 90 ). In addition, there are two types of terminal (end) towers, double and single circuit. In many cases, a double circuit junction tower was also designed to enable existing lines to be tied in to create a 3-ended circuit. Since the winning entry in the competition was a suspension tower, the team had to produce similar tension

3 tower designs. The aim was to keep the same conductor geometry by staying with the diamond shaped configuration while producing a design capable of restraining the mechanical loads and forces imposed when deviating from a straight line. Outline designs were produced for 30, 60 and 90 deviations; however it soon became apparent that for monopole designs with angles above 30, towers would have to be extremely strong, large and wide to meet conductor loading criteria. The resulting structures, compared to the suspension tower that has a slender, light and uplifting visual appearance, looked heavy, wide, cumbersome and less aesthetic. In order to retain the original visual concept, further development on early tension tower designs greater than 30 was frozen and the team looked to design a suspension tower with a maximum deviation of 10. This tower, in combination with the D30 tension tower, allows the line to deviate in sweeping bends rather than the traditional method of turning corners. The deployment of this combination has the effect that the T Pylon follows through the landscape rather than crossing it in a number of sharp turns. By adopting this principle, the number of tower types was reduced to just 5, with 360 m span standard and height being 35 m. T Pylon Tower Types Suspension (Straight Line) Tower Flying Angle F10: Suspension tower with a maximum deviation of 10 degrees Tension D30: Angle tower with a maximum deviation of 30 degrees Double Diamond Terminal Tower: Two independent diamond-shaped structures Single Circuit Gantry Terminal Tower: Low level goal post gantry tower Outline drawings and images of these are shown in Appendix 2 Insulation Type Suspension (Straight Line) Tower Insulation Array consists of two 600 kn standard design suspension long rod composite insulators to form the top section of the array and two 300 kn extra creepage suspension long-rod composite insulators to form the bottom section; composite hollow core or solid core

4 composite compression insulator to provide phase to phase insulation between the points of the diamond. Flying Angle F10 Suspension Tower with Maximum Deviation of 10 Insulation Array consists of two 1100 kn solid core composite standard post insulators to form the top section of the array, two 1100 kn extra creepage solid core composite standard post insulators to form the bottom section; composite hollow core or solid core composite compression insulator to provide phase-to-phase insulation between the points in the diamond. Tension D30 Angle Tower with Maximum Deviation of 30 Insulator Array consists of a standard 300 kn, 400kV composite long rods in a triple formation one for each sub-conductor with standard sag adjuster fittings. Fitted with solid core composite insulators on the inner and outer phases to ensure jumper connections maintain 400 kv phase-to-earth (ground) clearance. Double Diamond Terminal Tower Two Independent Diamond-Shaped Structures Insulator Array same as D30 Single Circuit Gantry Insulator Array As D30 See Appendix 3 Outline insulator drawings Construction During development of the T Pylon, a number of workshops took place with all OHL contractors and National Grid maintenance teams (including Eakring OHL training staff), with respect to build issues and repair techniques. These workshops highlighted the main areas of concern, that in the main were concentrated on the suspension and flying angle towers and associated insulator arrays. Main issues arising from the construction and line repair workshops associated with the Eakring Need Case included: 1. Tower construction & assembly; 2. Tower access & egress;

5 3. Conductor stringing; 4. Performance of suspension tower insulator array imbalance when using traditional, one phase at a time, tension string techniques; 5. Erection of insulator array; 6. Earth wire (ground wire) stringing and induced currents; 7. Conductor running blocks; 8. Clipping in new conductor; 9. Raising and lowering of insulator array; 10. Changing defective suspension insulators. Working on tension towers and terminal towers will, in principle, use current techniques and practices since tower attachment points are fixed and will carry conventional composite insulators string arrangements. Since there is no requirement to climb T Pylon structures, access methods will deploy Mobile Elevated Working Platforms (MEWP s) and techniques will therefore be developed at the training facility. Technical Specification Development Initial electrical specification was developed on the basis of existing National Grid s technical specifications, which are derived and adhere to IEC. However National Grid sought verification and input from an independent, internationally accredited test institution to carry out a review and make further recommendations as well as to develop a suite of mechanical and electrical test protocols. Three suppliers were engaged to produce insulators and fittings to meet mechanical and electrical performance criteria. All 3 suspension insulator designs were then subjected to the test regime. Once all the results are compiled, the information and findings will then form the basis for the insulator technical specification and the type test protocol. This will enable National Grid go out to the global market on a commercial basis. Keywords: UK, Insulator, Composite, Design, Transmission line.

Chapter 2. Current Design Practice

Chapter 2. Current Design Practice Chapter 2 Current Design Practice This chapter reviews current South African practices for the design of power line towers (SABS 0280: 2001 - Overhead power lines for conditions prevailing in Southern

More information

NEW 275 kv OVERHEAD LINE SUPPORT SERIES (RESEARCH AND DEVELOPMENT) STAGE 3 FINAL REPORT

NEW 275 kv OVERHEAD LINE SUPPORT SERIES (RESEARCH AND DEVELOPMENT) STAGE 3 FINAL REPORT NEW 275 kv OVERHEAD LINE SUPPORT SERIES (RESEARCH AND DEVELOPMENT) STAGE 3 FINAL REPORT 90SS545-REP-003. This document has been prepared for a specific commission and should not be used in whole or part

More information

RIBA Overhead Line Structures Competition Questions and Answers

RIBA Overhead Line Structures Competition Questions and Answers RIBA Overhead Line Structures Competition Questions and Answers Q1. Should we be proposing solutions for both single mast cantilever solutions and also portal frame gantries? The sample drawings show both,

More information

I. CLARIFICATIONS. This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows:

I. CLARIFICATIONS. This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS 2 294 Evaluation and Qualification criteria: Experience

More information

BASES OF DESIGN OF OVERHEAD ELECTRICAL LINES ACCORDING TO GENERAL REQUIREMENTS OF EUROPEAN STANDARD EN : 2001

BASES OF DESIGN OF OVERHEAD ELECTRICAL LINES ACCORDING TO GENERAL REQUIREMENTS OF EUROPEAN STANDARD EN : 2001 Advanced Steel Construction Vol. 3, No. 2, pp. 553-564 (2007) 553 BASES OF DESIGN OF OVERHEAD ELECTRICAL LINES ACCORDING TO GENERAL REQUIREMENTS OF EUROPEAN STANDARD EN 50341-1: 2001 Z. K. Mendera Professor,

More information

INTERNATIONAL JOURNAL OF CIVIL ENGINEERING AND TECHNOLOGY (IJCIET)

INTERNATIONAL JOURNAL OF CIVIL ENGINEERING AND TECHNOLOGY (IJCIET) INTERNATIONAL JOURNAL OF CIVIL ENGINEERING AND TECHNOLOGY (IJCIET) International Journal of Civil Engineering and Technology (IJCIET), ISSN 0976 6308 ISSN 0976 6308 (Print) ISSN 0976 6316(Online) Volume

More information

Dynamic Analysis of Transmission Tower

Dynamic Analysis of Transmission Tower Dynamic Analysis of Transmission Tower Sk.Musthafa Department of Civil Engineering, Amara Institute of Engineering and Technology. Sk.Yusuf Basha Department of Civil Engineering, Amara Institute of Engineering

More information

Series IEEE 1070 ERS

Series IEEE 1070 ERS Series IEEE 1070 ERS Quality and innovations in Q UESTION: WHY DO TRANSMISSION ASSET OWNERS NEED AN EMERGENCY RESTORATION SYSTEM (ERS)? A NSWER: Transmission line emergencies do occur. Whether caused by

More information

Construction of overhead lines in environmentally sensitive areas

Construction of overhead lines in environmentally sensitive areas Construction of overhead lines in environmentally sensitive areas by A Burger, J Diez Serrano, P Marais and B Jacobs, Trans Africa Projects With the strengthening of major networks currently taking place

More information

ACCR. More Amps. More Confidence. Glenmar E. Cambri, REE Senior Applications Engineer

ACCR. More Amps. More Confidence. Glenmar E. Cambri, REE Senior Applications Engineer TM ACCR More Amps More Confidence Glenmar E. Cambri, REE Senior Applications Engineer What is 3M ACCR? A high voltage, overhead transmission conductor designed as a drop-in replacement for ACSR and other

More information

NZQA registered unit standard version 3 Page 1 of 5. Install high voltage (HV) electricity network overhead conductors

NZQA registered unit standard version 3 Page 1 of 5. Install high voltage (HV) electricity network overhead conductors Page 1 of 5 Title Install high voltage (HV) electricity network overhead conductors Level 4 Credits 8 Purpose People credited with this unit standard are able to: interpret scope of work for installing

More information

STANDARD TECHNIQUE: OH4K/1

STANDARD TECHNIQUE: OH4K/1 Company Directive STANDARD TECHNIQUE: OH4K/1 Relating to the Design of Insulated Aerial Bundle Conductor For LV Overhead Distribution Systems ST:OH4K/1 13 September 2007-1 of 35 - Document Revision & Review

More information

First South East European Regional CIGRÉ Conference, Portoroz Minimising visual impact of 400 kv support structures

First South East European Regional CIGRÉ Conference, Portoroz Minimising visual impact of 400 kv support structures First South East European Regional CIGRÉ Conference, Portoroz 2016 SEERC 4-10 Minimising visual impact of 400 kv support structures J. DOYLE 1 (ESB Networks), P. VILLA (SAE Power Lines) C. HUGHES, P. ENNIS

More information

Why do Transmission Asset Owners Need a Transmission Restoration System (ERS)? Transmission Line Emergencies Do Occur

Why do Transmission Asset Owners Need a Transmission Restoration System (ERS)? Transmission Line Emergencies Do Occur Sabotage of a critical 500 kv DC transmission line necessitated the erection of this Lindsey Emergency Restoration Structure. Total erection time was 5-1/2 hours. Why do Transmission Asset Owners Need

More information

Various Transmission Tower Analysis & Design Using Professional Software

Various Transmission Tower Analysis & Design Using Professional Software ISSN 2278 0211 (Online) Various Transmission Tower Analysis & Design Using Professional Software Dr. D. R. Panchal Applied Mechanics Department, Faculty of Technical & Engineering M. S. University of Baroda,

More information

V. Design, Application, Maintenance & Operation Technical Requirements

V. Design, Application, Maintenance & Operation Technical Requirements V. Design, Application, Maintenance & Operation Technical Requirements V.A PJM Design & Application of Overhead Transmission Lines 69 kv & Above These design criteria have been established to assure acceptable

More information

STANDARD DRAWINGS. September 2013 UPDATED FEBRUARY 2016

STANDARD DRAWINGS. September 2013 UPDATED FEBRUARY 2016 STANDARD DRAWINGS September 2013 UPDATED FEBRUARY 2016 CONSTRUCTION STANDARD DRAWINGS DIVISION 15 LIST OF DRAWINGS: 1. 01 2004-1 Rev. A - Concrete Standards General Outline and Reinforcement Notes 2. 01

More information

B2-00. SPECIAL REPORT FOR SC B2 (Overhead Lines) V. NAIDOO J. IGLESIAS S. ANSORGE. Special Reporters

B2-00. SPECIAL REPORT FOR SC B2 (Overhead Lines) V. NAIDOO J. IGLESIAS S. ANSORGE. Special Reporters CIGRE 2016 B2-00 SPECIAL REPORT FOR SC B2 (Overhead Lines) V. NAIDOO J. IGLESIAS S. ANSORGE Special Reporters Introduction Study Committee B2 covers the design, construction and operation of overhead lines.

More information

Addendum No.1 (SUMMARY SHEET) Modifications to Tender Documents S.No. Document In Place of Please read as Remarks

Addendum No.1 (SUMMARY SHEET) Modifications to Tender Documents S.No. Document In Place of Please read as Remarks Contract: DMRC-MU-LINE2A-AEUD-03R TURNKEY PROJECT OF DESIGN, SUPPLY, ERECTION, TESTING &COMMISSIONING FOR MODIFICATION & RAISING OF +HEIGHT OF 110KV TRANSMISSION LINE (BORIVALI- MALAD) SPAN 41 AND 42 &(MALAD-ESSELWORLD)

More information

ENGINEERING SPECIFICATION EE SPEC

ENGINEERING SPECIFICATION EE SPEC /. Company Directive ENGINEERING SPECIFICATION EE SPEC : 84/1 Relating to Surge Arresters EE SPEC : 84/1 20 December 2013-1 of 7 - IMPLEMENTATION PLAN Introduction This document defines the surge arresters

More information

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators Version:- 3.1 Date of Issue:- June 2014 Page 1 of 13 NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators 1. Purpose This document is the technical specification for 33kV, 66kV

More information

Revamped High Ampacity Low Sag Stranded Carbon Fiber Composite Core Aluminium Conductor Fiber Reinforced Conductor (ACFR)

Revamped High Ampacity Low Sag Stranded Carbon Fiber Composite Core Aluminium Conductor Fiber Reinforced Conductor (ACFR) 21, rue d Artois, F-75008 PARIS TR/01/18 CIGRE 2018 http : //www.cigre.org Revamped High Ampacity Low Sag Stranded Carbon Fiber Composite Core Aluminium Conductor Fiber Reinforced Conductor (ACFR) OGOSHI

More information

MIPSYCON Duane Phillips Stanley Consultants, Inc.

MIPSYCON Duane Phillips Stanley Consultants, Inc. MIPSYCON 2014 Duane Phillips Stanley Consultants, Inc. Presentation of process and design considerations associated with design & engineering of long spans on transmission lines. Basis: 2700 ft crossing

More information

Optimization of Transmission Line Towers: P-Delta Analysis

Optimization of Transmission Line Towers: P-Delta Analysis Optimization of Transmission Line Towers: P-Delta Analysis Vinay R.B 1, Ranjith.A 2, Bharath.A 3 P.G. Student, Department of Civil Engineering, AIT, Chikmagalur, Karnataka, India 1 Assistant Professor,

More information

TABLE OF CONTENTS 1 GENERAL PROJECT DESCRIPTION Introduction Scope of Construction Work Post Construction Period...

TABLE OF CONTENTS 1 GENERAL PROJECT DESCRIPTION Introduction Scope of Construction Work Post Construction Period... TABLE OF CONTENTS 1 GENERAL PROJECT DESCRIPTION... 1 1.1 Introduction... 1 1.2 Scope of Construction Work... 1 1.3 Post Construction Period... 3 1.4 General Conditions... 3 2 DESIGN CRITERIA... 5 2.1 Design

More information

Specification for Transport and Erection of Tower Structures

Specification for Transport and Erection of Tower Structures Ergon Energy Corporation Limited Specification for Transport and Erection of Tower Structures This material is made available on the basis that it may be necessary for a Registered Professional Engineer

More information

Bridge articulation No. 1.04

Bridge articulation No. 1.04 Bridge articulation Scope This Guidance Note gives advice on the selection of the articulation arrangements, the choice of bearing types and dispositions of bearings, for bridges where relative movement

More information

Overhead Power Lines

Overhead Power Lines F. Kiessling P. Nefzger J.F. Nolasco U. Kaintzyk Overhead Power Lines Planning, Design, Construction With 402 Figures and 193 Tables Springer Contents 1 Overall planning 1 1.0 Symbols 1 1.1 Development

More information

Transmission Line General Requirements Including Typical Overhead Line Structures. Document Number: 1-03-FR-09

Transmission Line General Requirements Including Typical Overhead Line Structures. Document Number: 1-03-FR-09 Transmission Line General Requirements Including Typical Overhead Line Structures Document Number: 1-03-FR-09 VERSION 1.0 June 2018 This functional requirements document is in line with the organisation's

More information

LINDSEY EMERGENCY RESTORATION SYSTEM

LINDSEY EMERGENCY RESTORATION SYSTEM LINDSEY EMERGENCY RESTORATION SYSTEM Technical Feasibility Study Information and Data Worksheet After completely filling out this 6-page information and data worksheet, return this by E-mail or facsimile

More information

4. POINTS ON SWITCH AND CIRCUIT BREAKER PLATFORM GROUNDING.

4. POINTS ON SWITCH AND CIRCUIT BREAKER PLATFORM GROUNDING. 4. POINTS ON SWITCH AND CIRCUIT BREAKER PLATFORM GROUNDING. 4.1 All equipment (i.e., switches, breakers, control cabinets, etc.) inside switchyards or substations which require operations by workers must

More information

A Study on Analysis of Transmission Line Tower and Design of Foundation

A Study on Analysis of Transmission Line Tower and Design of Foundation A Study on Analysis of Transmission Line Tower and Design of Foundation 1 B. Bharath Kumar Reddy, 2 K. Rasagnya, 3 V. Sanjay Gokul 1,2 Under Graduates, 3 Assistant Professor Abstract - The Transmission

More information

International Journal of Advance Engineering and Research Development

International Journal of Advance Engineering and Research Development Scientific Journal of Impact Factor (SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 12,December -2015 E-ISSN (O): 2348-4470 P-ISSN (P): 2348-6406 COMPARITIVE

More information

Pre-Qualification Certificate

Pre-Qualification Certificate Nordic Utility Pre-Qualification System Pre-Qualification Certificate Awarded to Registration number: 984 277 032 Sellihca Id: Sellihca Qualification hereby confirms that is now fully registered as a supplier

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 220, 132 & 66 COMPOSITE SOLIDCORE STATION POST INSULATORS GETCO/E/2,1,6

More information

Analysis and Design of Vertical and Horizontal Configurations of Cross-arms in A Transmission Line Tower.

Analysis and Design of Vertical and Horizontal Configurations of Cross-arms in A Transmission Line Tower. Analysis and of Vertical and Horizontal Configurations of Cross-arms in A Transmission Line Tower. 1 Kamil. M. Shaikh 2 Prof. B. A.Vyas 1 P.G. Student, Applied Mechanics Dept. 2 Associate Professor, Applied

More information

QUALITY AND INNOVATION IN TR

QUALITY AND INNOVATION IN TR QUALITY AND INNOVATION IN TRANSMISSION AND DISTRIBUTION SINCE 1947 ERS Emergency Restoration System 600H-Series 600H Series Emergency Restoration System Structures Strong, dependable modular transmission

More information

Certificate in Electrical Power Engineering - Overhead Lines at SCQF Level 5 ( )

Certificate in Electrical Power Engineering - Overhead Lines at SCQF Level 5 ( ) Certificate in Electrical Power Engineering - Overhead Lines at SCQF Level 5 (2343-53) Unit handbook www.cityandguilds.com July 2016 Version 1.1 Contents 1 About this document 3 Unit 001 Working safely

More information

MSME Testing Centre, 65/1, G. S. T. Road, Guindy, Chennai, Tamil Nadu. Discipline Electrical Testing Issue Date

MSME Testing Centre, 65/1, G. S. T. Road, Guindy, Chennai, Tamil Nadu. Discipline Electrical Testing Issue Date Last Amended on - Page 1 of 7 I. TRANSMISSION LINE EQUIPMENT & ACCESSORIES ]] 1 Stockbridge Vibration dampers for Power lines Examination & IS 9708:1993 Cl. 7.2 Cl. 7.3 Mass pull off (Slip) Cl. 7.6 120

More information

How 3M Aluminum Conductor Composite Reinforced can help improve sustainability for electrical utilities.

How 3M Aluminum Conductor Composite Reinforced can help improve sustainability for electrical utilities. How 3M Aluminum Conductor Composite Reinforced can help improve sustainability for electrical utilities. George Fofeldea Power Engineer, 3M Canada December 2018 Introduction Canada, like every developed

More information

STANDARD TECHNIQUE : OH4L/1

STANDARD TECHNIQUE : OH4L/1 Company Directive STANDARD TECHNIQUE : OH4L/1 Relating to Stay Strands and Fittings for Overhead Lines ST:OH4L/1 March 2012-1 of 21 - Document Revision & Review Table Date Comments Author 06/06/13 Note

More information

CLARIFICATION NO 4. by bid drawings, that is, the protection of shield angle of 18 degrees.

CLARIFICATION NO 4. by bid drawings, that is, the protection of shield angle of 18 degrees. 1 SCHEDULES OF TECHNICAL INFORMATION9.6 Earth conductor maximum shielding angle from vertical at tower attachment point over outer line conductors SCHEDULES OF TECHNICAL INFORMATION 9.6 terms require maximum

More information

Building on Our Growth Opportunities May 27 30, 2015 Miser sur nos opportunités de croissance REGINA, SK

Building on Our Growth Opportunities May 27 30, 2015 Miser sur nos opportunités de croissance REGINA, SK EFFECT OF THE DESIGN RESISTANCE OF STRUCTURES ON THE EXTENT OF TRANSMISSION LINE CASCADING FAILURES Oussama Lamine Naouali 1, Sébastien Langlois 1, Eng., Ph.D and Frédéric Légeron 2, Eng., Ph.D 1 Department

More information

ISO Rules Part 500, Facilities Division 502, Technical Requirements Section Bulk Transmission Technical Requirements

ISO Rules Part 500, Facilities Division 502, Technical Requirements Section Bulk Transmission Technical Requirements Part 500, Facilities Division 502, Technical Requirements Section 502.2 Bulk Transmission Technical Requirements Applicability 1 This section 502.2 applies to: Requirements the legal owner of any bulk

More information

Nip / Tuck Method A Solution to Providing Additional Conductor-to-Ground Clearances for Transmission Lines

Nip / Tuck Method A Solution to Providing Additional Conductor-to-Ground Clearances for Transmission Lines Nip / Tuck Method A Solution to Providing Additional Conductor-to-Ground Clearances for Transmission Lines Michael E Belanger, P.E., M.ASCE Garrett E Luszczki, E.I., A.M.ASCE TRC Augusta, Maine Presented

More information

Power Systems 2 ELE3015. Lecture 1: Transmission Lines

Power Systems 2 ELE3015. Lecture 1: Transmission Lines Power Systems 2 ELE3015 Lecture 1: Transmission Lines Transmission Lines: Introduction Use to carry electrical power from point of generation to the point of use. Usually over large distances. Made with

More information

P.G student, Civil Engineering department, Saraswati College of Engineering, Maharashtra, India 1

P.G student, Civil Engineering department, Saraswati College of Engineering, Maharashtra, India 1 International Journal of Scientific & Engineering Research, Volume 6, Issue 1, December-15 145 Analysis and Design of kv transmission line tower with hot rolled and cold formed section Supriya Khedkar1,

More information

Introduction to Substation Design TADP 542

Introduction to Substation Design TADP 542 Introduction to Substation Design TADP 542 Substation Structures- Introduction Instructor: Dr. Yenumula Prasad Transmission & Distribution Program Substation Structures Reference Substation Structure Design

More information

Contents. 1 Introduction Background Aim of this document The Network in Dumfries and Galloway Asset Replacement...

Contents. 1 Introduction Background Aim of this document The Network in Dumfries and Galloway Asset Replacement... Contents 1 Introduction... 2 2 Background... 2 3 Aim of this document... 3 4 The Network in Dumfries and Galloway... 3 5 Asset Replacement... 5 6 Connection of Renewable Generation... 6 7 Interconnector

More information

CHAPTER 4 STEEL LATTICE TOWERS

CHAPTER 4 STEEL LATTICE TOWERS 70 CHAPTER 4 STEEL LATTICE TOWERS 4.1 TRANSMISSION LINE TOWERS In the power industry, steel lattice towers are commonly used for transmission of power through electrical conductors from the place of power

More information

Update on ASCE and NESC Codes and Standards

Update on ASCE and NESC Codes and Standards Power Line Systems IT S ALL ABOUT YOUR POWER LINES 2017 PLS-CADD Advanced Training and User Group Update on ASCE and NESC Codes and Standards by Otto J. Lynch, P.E. Power Line Systems, Inc. 6/12/2017 IT

More information

ENGINEERING STANDARD FOR OVERHEAD TRANSMISSION AND DISTRIBUTION LINES ORIGINAL EDITION

ENGINEERING STANDARD FOR OVERHEAD TRANSMISSION AND DISTRIBUTION LINES ORIGINAL EDITION ENGINEERING STANDARD FOR OVERHEAD TRANSMISSION AND DISTRIBUTION LINES ORIGINAL EDITION MAY 1997 1 CONTENTS : PAGE No. 0. INTRODUCTION... 4 1. SCOPE... 5 2. GENERAL... 5 3. STANDARDS... 5 4. PLANNING OF

More information

Innovative New Live Line Tool and Framing Designs Facilitating Safe and Efficient Cross-arm Replacement

Innovative New Live Line Tool and Framing Designs Facilitating Safe and Efficient Cross-arm Replacement Innovative New Live Line Tool and Framing Designs Facilitating Safe and Efficient Cross-arm Replacement A.J. Carreira, P.Eng., SMIEEE President Toronto, Canada carreira@k-line.net ISSUES WITH CURRENT CROSS

More information

STANDARDIZED STRUCTURES

STANDARDIZED STRUCTURES Q, QH & QL TOWERS 16.1 Q, QH, and QL Towers General Description The series includes three and four leg angle towers, which are suited for a variety of antenna mounting positions and load conditions. The

More information

INDIA S LARGEST TOWER TESTING FACILITY L&T TRANSMISSION LINE TESTING & RESEARCH STATION

INDIA S LARGEST TOWER TESTING FACILITY L&T TRANSMISSION LINE TESTING & RESEARCH STATION INDIA S LARGEST TOWER TESTING FACILITY L&T TRANSMISSION LINE TESTING & RESEARCH STATION (An ISO/IEC 17025:2005 NABL Accredited Laboratory) 765 kv Sipat Seoni transmission line Larsen & Toubro (L&T), a

More information

Basic Suspension Systems

Basic Suspension Systems CEILING & WALL SYSTEMS Commercial Ceilings and Walls Solutions Guide Installing Armstrong Suspended Ceilings The ceiling system is made up of Armstrong panels which are supported by a suspension system

More information

ELE-LPT-E-2004 Electrical Project Engineer Consultant PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS

ELE-LPT-E-2004 Electrical Project Engineer Consultant PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS 104073-ELE-LPT-E-2004 Electrical Project Engineer Consultant Holds a B. Sc. in Electrical Engineering and has over 12 years hands-on experience working in protection, testing, commissioning and OHTL. PERSONAL

More information

Electric Field and Potential Distribution in a 420 kv Novel Unibody Composite Cross-Arm

Electric Field and Potential Distribution in a 420 kv Novel Unibody Composite Cross-Arm 4 th Nordic Insulation Symposium on Materials, Components and Diagnostics Electric Field and Potential Distribution in a 4 kv Novel Unibody Composite Cross-Arm Jahangiri, Tohid ; Bak, Claus Leth ; Faria

More information

New Construction Units. a. Includes the furnishing of all labor and equipment for the installation of new construction units.

New Construction Units. a. Includes the furnishing of all labor and equipment for the installation of new construction units. 1 All construction is to follow design and construction documents approved by the Engineer and marked approved for construction. All construction shall also follow the National Electrical Safety Code,

More information

Optimization of Transmission Line Tower

Optimization of Transmission Line Tower Optimization of Transmission Line Tower S. Karthick 1, M.Venkatesh 2 Assistant Professor, Department of Civil Engineering, Valliammai Engineering College, Chennai, India 1 Assistant Professor, Department

More information

Inveraray to Crossaig Overhead Line Reinforcement

Inveraray to Crossaig Overhead Line Reinforcement About Scottish Hydro Electric (SHE) Transmission plc Scottish and Southern Energy Power Distribution is part of the SSE plc group of companies. We own, maintain and invest in the electricity networks in

More information

TECHNICAL SPECIFICATION OF ACCESSORIES SUITABLE FOR 7/3.15 mm G.I. EARTH WIRE

TECHNICAL SPECIFICATION OF ACCESSORIES SUITABLE FOR 7/3.15 mm G.I. EARTH WIRE GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION OF ACCESSORIES SUITABLE FOR 7/3.15 mm G.I. EARTH WIRE GETCO/E/TS EAC020/R0

More information

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv)

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv) Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators

More information

STRESS-RIBBON BRIDGES STIFFENED BY ARCHES OR CABLES

STRESS-RIBBON BRIDGES STIFFENED BY ARCHES OR CABLES 2nd Int. PhD Symposium in Civil Engineering 1998 Budapest STRESS-RIBBON BRIDGES STIFFENED BY ARCHES OR CABLES Tomas Kulhavy Technical University of Brno, Department of Concrete and Masonry Structures Udolni

More information

Ontario ENGINEERING STANDARD SPECIFICATION 1/10 REV. ELECTRICAL DISTRIBUTION HIGH VOLTAGE SUBSTATION GROUNDING AND BONDING. Approved by.

Ontario ENGINEERING STANDARD SPECIFICATION 1/10 REV. ELECTRICAL DISTRIBUTION HIGH VOLTAGE SUBSTATION GROUNDING AND BONDING. Approved by. /0 Rev Description Revision by Approved by Issue Date YYYY/MM/DD New Format Replaces 5322-0.0. T.C. 206/02/09 T.C. 206/03/02 206/03/02 2/0.0 PURPOSE This specification describes the minimum requirements

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LIMITED TRANSMISSION CIRCL, SURENDRANAGAR. CONSTRUCTION DIVISION,LIMBDI

GUJARAT ENERGY TRANSMISSION CORPORATION LIMITED TRANSMISSION CIRCL, SURENDRANAGAR. CONSTRUCTION DIVISION,LIMBDI GUJARAT ENERGY TRANSMISSION CORPORATION LIMITED TRANSMISSION CIRCL, SURENDRANAGAR. CONSTRUCTION DIVISION,LIMBDI. PART - II TECHNICAL SPECIFICATION FOR ERECTION FOR 66KV LINE H FRAME STRUCTURES 1. GENERAL

More information

SECURING A CONNECTION ANYWHERE RAPID DEPLOYMENT SOLUTIONS RAPID DEPLOYMENT TOWER (RDT)

SECURING A CONNECTION ANYWHERE RAPID DEPLOYMENT SOLUTIONS RAPID DEPLOYMENT TOWER (RDT) SECURING A CONNECTION ANYWHERE RAPID DEPLOYMENT SOLUTIONS RAPID DEPLOYMENT TOWER (RDT) RAPID DEPLOYMENT SOLUTIONS RAPID DEPLOYMENT TOWER (RDT) Rapid Deployment Tower (RDT) is a compact Greenfield site

More information

AS/NZS 7000:2010 AS/NZS

AS/NZS 7000:2010 AS/NZS AS/NZS 7000:2016 Australian/New Zealand Standard Overhead line design Superseding AS/NZS 7000:2010 AS/NZS 7000:2016 AS/NZS 7000:2016 This joint Australian/New Zealand standard was prepared by joint Technical

More information

APDRP SCHEME, WESCO. Technical Specification for 33KV Air Break Switch PART 1: SCOPE AND CONDITIONS

APDRP SCHEME, WESCO. Technical Specification for 33KV Air Break Switch PART 1: SCOPE AND CONDITIONS PART 1: SCOPE AND CONDITIONS 1. SCOPE This specification covers the design, engineering, manufacture, testing, supply, delivery, off-loading and performance requirements of 33kV, 200 amp, triple pole Gang

More information

TEESTAVALLEY POWER TRANSMISSION LTD.

TEESTAVALLEY POWER TRANSMISSION LTD. TEESTAVALLEY POWER TRANSMISSION LTD. TECHNICAL SPECIFICATION FOR TRANSMISSION LINE TOWER PACKAGES A1 & A2 VOLUME-II SPECIFICATION NO.: TOWER PACKAGE- A1 & A2 (This document is meant for the exclusive purpose

More information

General Description of the Project and Extent of Works (GTS-1)

General Description of the Project and Extent of Works (GTS-1) General Description of the Project and Extent of Works (GTS-1) KENYA - UGANDA INTERCONNECTION 400 kv DOUBLE CIRCUIT LINE (OPERATED INITIALLY AS A 220 kv OHTL) Table of Contents 1.1 Introduction... 1 1.2

More information

Draft Kenya Standard for Balloting Not to be Cited as Kenya Standard

Draft Kenya Standard for Balloting Not to be Cited as Kenya Standard KENYA STANDARD KS 1876-1:2010 ICS 29.240.20 Electrical power transmission and distribution Overhead power lines for conditions prevailing in Kenya Part 1: Code of practice BALLOT DRAFT, MAY 2010 KEBS 2010

More information

Duke Energy Carolinas Distribution Construction Standards Reference Guide

Duke Energy Carolinas Distribution Construction Standards Reference Guide Duke Energy Carolinas Distribution Construction Standards Reference Guide The Duke Energy Carolinas (DEC) Distribution Construction Standards are available on the My Duke Energy Contractor Portal. Access

More information

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008 Revisions Notes Changed note Date 1 (A) Changed template 09 / 07 / 2008 2 Changed template. Clause 12.5.4.1 hot-rolled steel added. Clause 12.5.4.2, 12.5.2.4, 12.5.3.4, 12.5.4.4, 12.5.5.4, 12.5.6.4, 12.5.7.4

More information

Walk through the associated design considerations associated with transmission line design

Walk through the associated design considerations associated with transmission line design Walk through the associated design considerations associated with transmission line design Follow-up to Transmission Design 101 (2012) & Transmission Design 102 (2013) Additional design considerations

More information

Test Report on 3M ACCR 477-T16 Conductor Returned from Xcel Riverside Line after 13 Years of Service in Minneapolis, MN

Test Report on 3M ACCR 477-T16 Conductor Returned from Xcel Riverside Line after 13 Years of Service in Minneapolis, MN Test Report on 3M ACCR 477-T16 Conductor Returned from Xcel Riverside Line after 13 Years of Service in Minneapolis, MN 3M HCC Testing Laboratory November 3, 2015 Phu Trac Quality Quality Specialist: Phu

More information

Title Transmission Line Base Safety and Operating Standards. Reference Number POS 01 - (RIC Standard: EP SP)

Title Transmission Line Base Safety and Operating Standards. Reference Number POS 01 - (RIC Standard: EP SP) Discipline Engineering Standard - NSW Category Electrical Title Transmission Line Base Safety and Operating Standards Reference Number POS 01 - (RIC Standard: EP 10 01 00 03 SP) Document Control Status

More information

C C CEILING(S) Suspended. Contents. 1. Introduction. 2. Earthing and bonding. 3. Supporting of electrical cables

C C CEILING(S) Suspended. Contents. 1. Introduction. 2. Earthing and bonding. 3. Supporting of electrical cables Contents 1. Introduction 2. Earthing and bonding 3. Supporting of electrical cables 4. Final connection to luminaires 5. Thermoplastic luminaire diffusers 6. Fire-protecting suspended ceilings 1. Introduction

More information

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH SPECIFICATIONS FOR LOAD BREAK SWITCH This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE CODES

More information

SECTION-I TECHNICAL SPECIFICATIONS

SECTION-I TECHNICAL SPECIFICATIONS SECTION-I TECHNICAL SPECIFICATIONS 1. General Information and Scope 1.1 Scope 1.1.1 The following 400 kv double circuit transmission lines are included in the scope of the Contractor for various packages.

More information

Structural Analysis of the Bow Gantry of Dredge No.4

Structural Analysis of the Bow Gantry of Dredge No.4 Structural Analysis of the Bow Gantry of Dredge No.4 van Rijn, Gerard 1 ABSTRACT Dredge No.4 is a National Historical Site administered by Parks Canada. This paper was based on a report on the structural

More information

SECTION CHAIN LINK FENCING

SECTION CHAIN LINK FENCING SECTION 02835 - CHAIN LINK FENCING 1.0 GENERAL 1.1 Furnish and install chain link fencing complete in place with gates and accessories as specified herein and as shown on the Contract Drawings. 1.2 Reference

More information

IEC Oil Filled & SF 6 Gas Current Transformers

IEC Oil Filled & SF 6 Gas Current Transformers g IEC Oil Filled & SF 6 Gas Current Transformers 72.5kV - 550kV (325kV - 1550kV BIL) with Primary Plus TM Pre-engineered solution set that digitizes XD GE primary equipment and provides factory installed

More information

BEST PRACTICE GUIDANCE THE SAFE OFF-LOADING OF REINFORCEMENT FABRIC.

BEST PRACTICE GUIDANCE THE SAFE OFF-LOADING OF REINFORCEMENT FABRIC. BEST PRACTICE GUIDANCE THE SAFE OFF-LOADING OF REINFORCEMENT FABRIC www.uk-bar.org CONTENTS Introduction.... 3 Hazards.... 4 Accidents... 5 Working at Height... 6 Dunnage.... 7 Planning for a Safe Delivery....

More information

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Objectives and Task Analysis for a Professional Small Wind Energy System Installer

Objectives and Task Analysis for a Professional Small Wind Energy System Installer North American Board of Certified Energy Practitioners Objectives and Task Analysis for a Professional Small Wind Energy System Installer Introduction This document presents an in-depth task analysis for

More information

Study Committee B2 Technical Advisory Group B2-AG-06

Study Committee B2 Technical Advisory Group B2-AG-06 Study Committee B2 Technical Advisory Group B2-AG-06 Cigré AG06 Seminar Bangkok Types and Uses of High Brian Wareing Brian Wareing.Tech Ltd Chester, UK Convenor Cigré AG06 WG48 Experience with the Mechanical

More information

NPS/003/033 Technical Specification for Substation Support Structures

NPS/003/033 Technical Specification for Substation Support Structures Version:- 2.0 Date of Issue:- April 2015 Page 1 of 21 NPS/003/033 Technical Specification for Substation Support Structures 1. Purpose The purpose of this document is to specify the technical requirements

More information

Colorado River Aqueduct Pumping Plants 230 kv Disconnect Switches Replacement

Colorado River Aqueduct Pumping Plants 230 kv Disconnect Switches Replacement DATE: July 15, 2011 ADDENDUM NUMBER: 2 MODIFYING: Specifications No. 1698 PROJECT: Colorado River Aqueduct Pumping Plants 230 kv Disconnect Switches Replacement BID TIME AND DATE: 2:00 p.m., July 19, 2011

More information

TECHNICAL SPECIFICATION A.B. CABLE

TECHNICAL SPECIFICATION A.B. CABLE TECHNICAL SPECIFICATION A.B. CABLE 1.0 NATURE OF WORK The work covered by this Specification is for L.T lines in A.B cable as specified herein and in the attached Schedules. The overhead distribution lines

More information

Design and Optimization of Overhead Transmission Lines using PLS- CADD and PLS-Tower Software

Design and Optimization of Overhead Transmission Lines using PLS- CADD and PLS-Tower Software Design and Optimization of Overhead Transmission Lines using PLS- CADD and PLS-Tower Software Theoretical and Practical PLS-CADD training Course General information and registration form 1 Date of course

More information

Guidelines for Increased Utilization of Existing Overhead Transmission Lines

Guidelines for Increased Utilization of Existing Overhead Transmission Lines Guidelines for Increased Utilization of Existing Overhead Transmission Lines Electra - August 2008 WG 13 Management of Existing Overhead Lines Keith Lindsey 1of 24 what are we going to talk about background

More information

Network of offshore wind farms connected by gas insulated transmission lines?

Network of offshore wind farms connected by gas insulated transmission lines? Network of offshore wind farms connected by gas insulated transmission lines? Anja Drews, ForWind, Carl von Ossietzky Universität Oldenburg, Institute of Physics, Carl-von- Ossietzky Str. 9-11, 29129 Oldenburg,

More information

Certificate of Acceptance

Certificate of Acceptance Class II FSP Switchgear Assembly (Type: FSP03) Product Description Product Image Class II FSP Switchgear Assembly (Type: FSP03) for Signalling Power Supplies Scope of Acceptance Full acceptance as per

More information

ATTACHMENT 13 NORTHEAST-POCONO RELIABILITY PROJECT PPL DESIGN CRITERIA AND SAFETY PRACTICES

ATTACHMENT 13 NORTHEAST-POCONO RELIABILITY PROJECT PPL DESIGN CRITERIA AND SAFETY PRACTICES ATTACHMENT 13 NORTHEAST-POCONO RELIABILITY PROJECT PPL DESIGN CRITERIA AND SAFETY PRACTICES The National Electrical Safety Code (NESC) is a set of rules to safeguard people during the installation, operation,

More information

SPECIFICATION SS-20 / 4 STEEL STRUCTURES FOR SUBSTATION AND SWITCHING STATION MATERIAL

SPECIFICATION SS-20 / 4 STEEL STRUCTURES FOR SUBSTATION AND SWITCHING STATION MATERIAL 1 JULY 2009 SPECIFICATION SS-20 / 4 STEEL STRUCTURES FOR SUBSTATION AND SWITCHING STATION MATERIAL I. SCOPE This Specification covers the technical characteristics, the manufacturing and testing of steel

More information

End-to-end electrical solutions for the biggest challenges involved with connecting wind energy to the grid. Solutions for Wind Energy Integration

End-to-end electrical solutions for the biggest challenges involved with connecting wind energy to the grid. Solutions for Wind Energy Integration End-to-end electrical solutions for the biggest challenges involved with connecting wind energy to the grid Solutions for Wind Energy Integration There are lots of challenges involved in harnessing the

More information

EFFECT OF MEDIUM WIND INTENSITY ON 21M 132kV TRANSMISSION TOWER

EFFECT OF MEDIUM WIND INTENSITY ON 21M 132kV TRANSMISSION TOWER EFFECT OF MEDIUM WIND INTENSITY ON 21M 132kV TRANSMISSION TOWER V. Lakshmi 1, A. Rajagopala Rao 2 1 Assistant Professor, Civil Engineering, JNT University Kakinada, Andhra Pradesh, India, lveerni@yahoo.com

More information

Alternating Current and Three-Phase Systems Annotated Instructor s Guide

Alternating Current and Three-Phase Systems Annotated Instructor s Guide Alternating Current and Three-Phase Systems Annotated Instructor s Guide Module 80201-11 Module Overview This module provides an introduction to the theory of alternating current, along with AC circuits,

More information