1 Contents 1. Introduction 2. Earthing and bonding 3. Supporting of electrical cables 4. Final connection to luminaires 5. Thermoplastic luminaire diffusers 6. Fire-protecting suspended ceilings 1. Introduction ceilings are often provided in commercial and similar premises. They generally consist of a grid of light metal bars, usually having an inverted T section, into which ceiling tiles, recessed luminaires (light fittings) and ventilation grilles etc are installed (see Fig 1). Surface-mounted luminaires, smoke detectors and similar items are sometimes installed to the underside of the ceiling. The void above a suspended ceiling, which accommodates the tension wires or other means by which the grid is suspended from the building structure, is commonly used for the routing of wiring systems and non-electrical services, such as pipework and ductwork. An example of a suspended ceiling, incorporating a ventilation grille and recessed luminaires Fig 1 NICEIC NICEIC TECHNICAL MANUAL 27 SEP 01 1 of 5

2 C49-13 C CEILING(S) 2. Earthing and bonding In practice, unless there are very exceptional circumstances (which would need to be taken into account by the electrical designer), the conductive parts of a suspended ceiling will be neither exposed-conductive-parts nor extraneous-conductive-parts. Consequently, in normal circumstances, suspended ceilings need neither to be earthed nor equipotentially bonded. Electrical equipment such as luminaires, lighting track, overhead busbars, air conditioning units and the like incorporated in a suspended ceiling will normally be of either Class I or Class II construction. The exposed-conductive-parts of Class I equipment are required to be connected to the main earthing terminal of the installation by a circuit protective conductor designed to conduct earth fault current. Class II equipment is designed such that any insulation fault in the equipment cannot result in fault current flowing into any conductive parts with which the equipment may be in contact. The conductive parts of a suspended ceiling incorporating Class I and/or Class II equipment are therefore not intended to conduct earth fault current, and so such parts need not be intentionally earthed. (Some conductive parts of a suspended ceiling may be earthed, however, by virtue of fortuitous contact with exposed-conductive-parts, including those of Class I equipment.) Unless there are exceptional circumstances, the conductive parts of a suspended ceiling will not introduce a potential that does not already exist in the space in which the ceiling is installed. In normal circumstances, therefore, there is no need to arrange for the conductive parts of the ceiling to be connected to either a main bonding conductor or to any supplementary bonding conductor. 3. Supporting of electrical cables Some of the requirements applicable to cables in suspended ceilings are embodied in Regulation Groups , and of BS In particular, Regulations and call for cables to be supported, either continuously or at appropriate intervals, such that no damage or undue strain will occur to the cables themselves or to their terminations. It is inadvisable for cables, including insulated and sheathed cables to BS 6004, to be laid directly on a suspended ceiling grid for a number of reasons, including: The cables are liable to be damaged, both during installation and later, by the sharp edges of the grid (Regulations and ). For example, a cable may come into contact with the cut edges of the grid at a notch where sections of grid intersect, or may become trapped between a ceiling tile and the grid, possibly when other trades are carrying out work in connection with the ceiling or other services routed above. The suspended ceiling grid may not have been designed to take the additional weight of cables, and may deform or collapse as a result. 2 of 5 27 SEP 01 NICEIC TECHNICAL MANUAL NICEIC

3 Adequate support for cables for fixed wiring within a suspended ceiling void can be achieved in a number of ways to ensure that the cables are kept well away from the grid and from other services. For example, the designer may consider: Providing a conduit or trunking system, or cable tray (metallic or non-metallic), fixed at suitable spacings to the building structure above the ceiling, or to walls or other structural elements. Providing a catenary system as shown in Fig 2, to which the wiring system may be attached using proprietary clips, cable-ties or cable-hangers at appropriate intervals. Attaching the cables by suitable clips or cable ties to ceiling support rods. Cross-section through a suspended ceiling void, showing cables supported by a catenary system Building structure Catenary wire Cable support (eg tiewrap) Cable(s) Luminaire suspension Final connection device (see item 4) Surface mounted luminaire ceiling grid ceiling tile Switches Note: ceiling supports omitted for clarity Fig 2 4. Final connection to luminaires All connections, including extra-low voltage connections, are required to be made in a suitable accessory or enclosure (Regulation ). NICEIC NICEIC TECHNICAL MANUAL 27 SEP 01 3 of 5

4 C49-13 C CEILING(S) Final connection of a luminaire can be achieved by the use of a luminaire supporting coupler (LSC) mounted immediately adjacent to the luminaire (for example mounted on a conduit box above it), keeping the final flex connection as short as practicable. Alternatively, a suitable plug and socket-outlet (correctly mounted) may be used. Both of these options will provide a suitable means of isolation for the connected luminaire. These and other methods of final connection are discussed in Topic L An advantage of the use of LSCs or socket-outlets is that it facilitates the completion of the fixed installation without the need to have prior knowledge of the exact locations of the luminaires. Moreover, the plug-in arrangement makes the final connection and testing, and subsequent maintenance or replacement of luminaires, particularly easy and quick to carry out. However, the ease with which final connections can be made may be an invitation to the lighting engineer to relocate the luminaires within the suspended ceiling in order to achieve a different lighting effect or intensity. From the contractor s point of view, such changes can result in longer lengths of flexible cords, which are often left to lie on the suspended ceiling for at least part of their length. In order to ensure compliance with Regulations , and , the following points should all be observed: Flexible cord connections to luminaires should be as short as possible (ideally, a vertical drop from the fixed connection to the luminaire). Flexible cords should not be allowed to rest on top of, or come into contact with the sharp edges of the inverted T section of the ceiling grid, for the reasons mentioned in item 3. Suitable cord grips should be provided to securely retain the sheath of the flexible cord if strain is likely to occur on terminations within a luminaire. For some types of luminaire, a cord grip may need to be purchased separately. Where the first and/or the second of the foregoing points cannot be observed, the contractor should consider the use of a type of flexible cord with a suitably reinforced sheath, or so-called curly flex, cut to the appropriate length. 5. Thermoplastic luminaire diffusers The use of thermoplastic lighting diffusers is subject to certain provisions concerning prevention of the spread of fire in buildings. These provisions, which are laid down in Approved Document B, relating to the statutory requirements of The Building Regulations, are the subject of Topic L Fire-protecting suspended ceilings Precautions that need to be considered where a recessed luminaire or other electrical equipment penetrates a suspended ceiling that is intended to contribute to the overall fire resistance of the floor/ceiling assembly are covered in Topic C of 5 27 SEP 01 NICEIC TECHNICAL MANUAL NICEIC

5 Topics referred to in this text: C49-15 CEILING(S):, fire-protecting, precautions in L105-1 LUMINAIRE(S): Connection of L LUMINAIRE(S): Thermoplastic diffusers in suspended ceilings Topics not referred to in this text, which are related and may be of interest: C93-5 CLASSES OF EQUIPMENT: Classes 0, I, II, III for the purposes of shock protection C165-1 CONNECTIONS, JOINTS AND TERMINATIONS: General L LUMINAIRE(S): Supporting couplers (LSC) S309-1 SUPPORTS: for cables Requirements for electrical installations (BS 7671): Some of the most important requirements are found in: Protection against indirect contact Section 413 Protection against thermal effects Chapter 42 Selection and erection in relation to external influences Section 522 Electrical connections Section 526 NICEIC NICEIC TECHNICAL MANUAL 27 SEP 01 5 of 5

IET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 705 AGRICULTURAL AND HORTICULTURAL PREMISES

IET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 705 AGRICULTURAL AND HORTICULTURAL PREMISES IET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 705 AGRICULTURAL AND HORTICULTURAL PREMISES 705.1 Scope The particular requirements of this section apply to fixed electrical installations indoors

More information

GN7 Amendment 3-5 Agricultural and horticultural premises

GN7 Amendment 3-5 Agricultural and horticultural premises GN7 Amendment 3-5 Agricultural and horticultural premises 5.1Introduction Amendment No. 3 to the 17th Edition Sect 705 There are no significant changes introduced in Section 705by Amendment No. 3 to the

More information

SECTION EARTHING AND EARTH FAULT PROTECTION

SECTION EARTHING AND EARTH FAULT PROTECTION SECTION 16660 PART 1 - GENERAL 1.01 DESCRIPTION A. The work to be performed includes, but is not necessarily limited to, all work involved with the construction and assembly of a complete electrical earthing

More information

The definition of an extraneous-conductive-part, as given in Part 2 of BS 7671 is:

The definition of an extraneous-conductive-part, as given in Part 2 of BS 7671 is: Contents 1. Introduction 2. 3. Summary 1. Introduction Extraneous-conductive-parts are referred to extensively in BS 7671, mostly in relation to equipotential bonding, but also with regard to electric

More information

10 THE INTEGRATION O.F SERVICES INTO BUILDINGS

10 THE INTEGRATION O.F SERVICES INTO BUILDINGS 10 THE INTEGRATION O.F SERVICES INTO BUILDINGS INTRODUCTION Buildings of different use will contain varying amounts of electrical, mechanical and sanitary services, and this will generally be reflected

More information

Temporary Wiring. Low-Voltage Electrical Safety Orders

Temporary Wiring. Low-Voltage Electrical Safety Orders Temporary Wiring Low-Voltage Electrical Safety Orders 2405.1. Scope. Except as specifically modified in this Article, all other requirements of this Order for permanent wiring shall also apply to temporary

More information

C&G 2382 BS7671: th Edition IEE Wiring Regulations. 25 Questions

C&G 2382 BS7671: th Edition IEE Wiring Regulations. 25 Questions C&G 2382 BS7671:2008 17 th Edition IEE Wiring Regulations 25 Questions 1. BS7671 states that installation design must take into account a. current copper prices b. the effects of climate change c. a comparison

More information

DOMESTIC ELECTRICAL INSTALLATION PERIODIC INSPECTION REPORT (FOR A SINGLE DWELLING) B ADDRESS AND DETAILS OF THE INSTALLATION Address: SPECIMEN

DOMESTIC ELECTRICAL INSTALLATION PERIODIC INSPECTION REPORT (FOR A SINGLE DWELLING) B ADDRESS AND DETAILS OF THE INSTALLATION Address: SPECIMEN A DETAILS OF THE CLIENT Client / Address: C PURPOSE OF THE REPORT Purpose for which this report is required: E PARTICULARS OF THE CONTRACTOR Trading Title: Address: DOMESTIC ELECTRICAL INSTALLATION PERIODIC

More information

AS/NZS 3000: 2018 Changes to Wiring Rules Standard

AS/NZS 3000: 2018 Changes to Wiring Rules Standard BUILDING SERVICES Ref: BCA 19-01 Current at January 2019 AS/NZS 3000: 2018 Changes to Wiring Rules Standard The new edition of AS/NZS 3000 Wiring Rules Standard (Electrical Installations) was published

More information

Electrical Services Standard Specification Cable Tray Installation. May For ROYAL HOLLOWAY UNIVERSITY OF LONDON

Electrical Services Standard Specification Cable Tray Installation. May For ROYAL HOLLOWAY UNIVERSITY OF LONDON Electrical Services Standard Specification 4.0 - Cable Tray Installation May 2010 For ROYAL HOLLOWAY UNIVERSITY OF LONDON Prepared For The Estates Division By: Hulley & Kirkwood Consulting Engineers Ltd

More information

Same as Client Address. 40, Havelock Close. India Way. London. Postcode: W12 7NQ

Same as Client Address. 40, Havelock Close. India Way. London. Postcode: W12 7NQ DOMESTIC ELECTRICAL INSTALLATION CONDITION REPORT Issued in accordance with British Standard BS 7671 - Requirements for Electrical Installations Certificate Reference: 1 DETAILS OF THE CLIENT 2 ADDRESS

More information

Installation, Inspection and Maintenance of Dry Type Transformers

Installation, Inspection and Maintenance of Dry Type Transformers Dry Type TX 1 of 8 Installation, Inspection and Maintenance of Dry Type Page 1 of 8 Dry Type TX 2 of 8 Table Of Contents Page Number 1. General... 3 2. Installation... 3 3. Safety Inspections... 4 4. Safety

More information

Same As Client Address SPECIMEN. operational limitations. of the inspection and. agreed with):

Same As Client Address SPECIMEN. operational limitations. of the inspection and. agreed with): DOMESTIC ELECTRICAL INSTALLATION CONDITION REPORT Issued in accordance with British Standard BS 7671 - Requirements for Electrical Installations Certificate Reference: DEICR000021652 1 DETAILS OF THE CLIENT

More information

Inspection Guide for PV Systems in One- and Two- Family Dwellings (For Rooftop Photovoltaic Systems meeting the Standard Plan)

Inspection Guide for PV Systems in One- and Two- Family Dwellings (For Rooftop Photovoltaic Systems meeting the Standard Plan) TOOLKIT DOCUMENT #7 Inspection Guide for PV Systems in One- and Two- Family Dwellings (For Rooftop Photovoltaic Systems meeting the Standard Plan) This document has two sections. Neither section is all-inclusive

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin February 2019 Page 1 of 5 2018 CANADIAN ELECTRICAL CODE SUBJECT: Section 6 Services and service equipment Rule 6-102 Number of supply services permitted Row housing

More information

SECTION ENCLOSED BUS ASSEMBLIES

SECTION ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

To bond or not to bond: domestic swimming pools

To bond or not to bond: domestic swimming pools To bond or not to bond: domestic swimming pools With the summer sun warming our skin and tempting us into plans for weekends spent poolside, Paul Harris BEng (Hons) CEng FIHEEM MIEE MCIBSE, of Harris Associates

More information

CHAPTER 13 GROUNDING AND BONDING

CHAPTER 13 GROUNDING AND BONDING GROUNDING AND BONDING CHAPTER 13 GROUNDING AND BONDING Grounding and bonding must be in accordance with Article 250 of the National Electrical Code (NEC). Bonding is defined in the NEC as the permanent

More information

SECTION ENCLOSED BUS ASSEMBLIES

SECTION ENCLOSED BUS ASSEMBLIES SECTION 262500 ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

1. Hangers and supports for electrical equipment and systems.

1. Hangers and supports for electrical equipment and systems. PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 DEFINITIONS... 1 1.4 PERFORMANCE REQUIREMENTS... 1 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 2 1.7 COORDINATION... 2 PART 2 - PRODUCTS...

More information

DEVICES AND LUMINAIRES

DEVICES AND LUMINAIRES CHAPTER 40 DEVICES AND LUMINAIRES SECTION E4001 SWITCHES E4001.1 Rating and application of snap switches. General-use snap switches shall be used within their ratings and shall control only the following

More information

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES Guidelines effective March 5, 2007 NES is committed to providing safe, reliable electric service at a reasonable price for all of our customers. These guidelines offer direction for activities relating

More information

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0528 Pathways. Page 1 of 6

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0528 Pathways. Page 1 of 6 1 General 1.1 Scope of work 1.1.1 The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the completion of

More information

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp,

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp, TITLE 14 CHAPTER 10 PART 4 HOUSING AND CONSTRUCTION ELECTRICAL CODES 2011 NEW MEXICO ELECTRICAL CODE 14.10.4.1 ISSUING AGENCY: The Construction Industries Division of the Regulation and Licensing Department.

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 5/12/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 5/12/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 5/12/10 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. Is it illegal to install a wet-niche luminaire face-up

More information

DEVICES AND LUMINAIRES

DEVICES AND LUMINAIRES CHAPTER 39 DEVICES AND LUMINAIRES SECTION E3901 SWITCHES E3901.1 Rating and application of snap switches [404.14(A)]. General-use snap switches shall be used within their ratings and shall control only

More information

Kaf-Tech Product Specification

Kaf-Tech Product Specification Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519.13 METAL CLAD CABLE-LUMINARY CABLE

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519 METAL CLAD CABLE - MC-PLUS Neutral

More information

Installation Address. Postcode. Purpose of the report This form to be used only for reporting on the condition of an existing installation.

Installation Address. Postcode. Purpose of the report This form to be used only for reporting on the condition of an existing installation. A B C Details of the installation Owner*/Occupier*/Customer*/ (*Delete as necessary) Only for the reporting on the condition of an existing installation Purpose for which this report is required Installation

More information

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 CANADIAN ELECTRICAL CODE 1 The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 Repealed by Chapter E-6.3 Reg 8 (effective June 24, 2003). Formerly Chapter E-6.3 Reg 6 (effective March

More information

CI/SfB. October RockLink 15. Installation system

CI/SfB. October RockLink 15. Installation system CI/SfB (5) Xh2 October 2008 RockLink 15 Installation system RockLink 15 Rockfon tiles with A15 and E15 edge 1 6 2 details are suit able for installation using this system. 5 6 2 6 4 The following ceiling

More information

Technical Services Information Bureau

Technical Services Information Bureau Technical Services Information Bureau INSTALLING ACOUSTICAL LAY-IN TYPE CEILINGS IN SEISMIC REGIONS AUGUST 2009 UPDATED MAY 2017 TECHNICAL BULLETIN This document covers the installation practices recognized

More information

ELECTRICAL INSTALLATION DESIGN Three Day Course with option to achieve BTEC Advanced Award

ELECTRICAL INSTALLATION DESIGN Three Day Course with option to achieve BTEC Advanced Award ELECTRICAL INSTALLATION DESIGN Three Day Course with option to achieve BTEC Advanced Award INTRODUCTION This course is aimed at the needs of designers, specifiers and others involved in the design and

More information

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

Terminating and connecting conductors, cables and flexible cords in electrical systems (ELTP05)

Terminating and connecting conductors, cables and flexible cords in electrical systems (ELTP05) Level: 3 Credit value: 4 UAN: H/602/2828 Unit aim This unit is designed to enable the learner to develop the skills required, and apply the associated knowledge, in order that they are able to demonstrate

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. AFC Cable Systems, Inc. Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519.13 METAL CLAD CABLE-MC

More information

SECTION LIGHTNING PROTECTION SYSTEM

SECTION LIGHTNING PROTECTION SYSTEM SECTION 16670 - LIGHTNING PROTECTION SYSTEM PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Candidate Self-Assessment Checklist

Candidate Self-Assessment Checklist Candidate Information You are about to undertake the AM2 Assessment of Occupational Competence. The AM2 Electrotechnical Assessment of Occupational Competence is designed for individuals who wish to practise

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT ACTIVE COMPOSITE MILLS LTD. Dewan Idris Road, Zirabo, Ashulia, Savar, Dhaka, Bangladesh Factory List: 1. Active Composite Mills Ltd. Inspected by: Hemlal Report Generated

More information

CI/SfB. June RockLink 24 Monolith. Installation system

CI/SfB. June RockLink 24 Monolith. Installation system I/SfB (35) Xh2 June 2008 RockLink 24 Monolith Installation system RockLink 24 Monolith Gypsum / MF plasterboard border Rockfon s with edge detail D in module size x are suit able for installation using

More information

CERTIFICATE OF ACCREDITATION

CERTIFICATE OF ACCREDITATION CERTIFICATE OF ACCREDITATION In terms of section 22(2)(b) of the Accreditation for Conformity Assessment, Calibration and Good Laboratory Practice Act, 2006 (Act 19 of 2006), read with sections 23(1),

More information

NEC 2014 Code Changes

NEC 2014 Code Changes NEC 2014 Code Changes Articles 280.21-300.50 CHANGES FROM 2011 TO 2014 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 280 Surge Arresters, Over 1000 volts II. Instillation III. Connecting Surge

More information

7. For items classified in Section K as C1 ( Danger

7. For items classified in Section K as C1 ( Danger NAPIT Electrical Installation Condition Report Guidance for recipients This report is an important and valuable document which should be retained for future reference.. The purpose this condition report

More information

BRANZ FACTS RESILIENT NON-STRUCTURAL ELEMENTS SEISMICALLY RESILIENT NON-STRUCTURAL ELEMENTS # 3. Restraint systems

BRANZ FACTS RESILIENT NON-STRUCTURAL ELEMENTS SEISMICALLY RESILIENT NON-STRUCTURAL ELEMENTS # 3. Restraint systems SEISMICALLY BRANZ FACTS RESILIENT NON-STRUCTURAL ELEMENTS SEISMICALLY RESILIENT DESIGN CRITERIA # 2 NON-STRUCTURAL ELEMENTS # 3 Restraint systems The next step in the non-specific design pathway in NZS

More information

Temporary Wiring Practices And Guidelines For NECA. National Electrical Contractors Association Omaha, Nebraska

Temporary Wiring Practices And Guidelines For NECA. National Electrical Contractors Association Omaha, Nebraska Temporary Wiring Practices And Guidelines For NECA National Electrical Contractors Association Omaha, Nebraska Table of Contents I. Planning II. Lighting and Power III. Maintenance IV. Inspections V. Routing

More information

PARTICULAR SPECIFICATION E11: GENERAL ELECTRICAL EARTHING AND LIGHTNING PROTECTION

PARTICULAR SPECIFICATION E11: GENERAL ELECTRICAL EARTHING AND LIGHTNING PROTECTION E11 : General Electrical Earthing and LIGHTNING Protection PARTICULAR SPECIFICATION E11: GENERAL ELECTRICAL EARTHING AND LIGHTNING PROTECTION 1 2009-05-12 Review of Mechanical / Electrical and Control

More information

Candidate Self-Assessment Checklist

Candidate Self-Assessment Checklist General Information This compulsory document must be completed by all candidates due to undertake the AM2 Assessment of Occupational Competence and provided to the assessment centre prior to assessment.

More information

Guidance note Electrical Wiring Installations in Churches

Guidance note Electrical Wiring Installations in Churches Guidance note Electrical Wiring Installations in Churches Those responsible for the care of a church building need to understand the procedures for the maintenance and testing of electrical systems and

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin March 2014 CEC-12 [rev-6] Page 1 of 6 CANADIAN ELECTRICAL CODE SUBJECT: Section 12 Wiring Methods Conductors General Insulation Thickness on Conductors Used in Ungrounded

More information

Nortrax Section David Manchester Road, Ottawa NON-STRUCTURAL METAL FRAMING 16 May 2014 Page 1

Nortrax Section David Manchester Road, Ottawa NON-STRUCTURAL METAL FRAMING 16 May 2014 Page 1 16 May 2014 Page 1 PART 1 GENERAL 1.1 DESCRIPTION This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories

More information

SECTION NON-STRUCTURAL SEISMIC DESIGN CRITERIA PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION NON-STRUCTURAL SEISMIC DESIGN CRITERIA PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 014100 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

METAL SUSPENSION SYSTEMS FOR LAY-IN PANEL CEILINGS: 2001 CBC IR

METAL SUSPENSION SYSTEMS FOR LAY-IN PANEL CEILINGS: 2001 CBC IR California Department of General Services. Division of the State Architect. Interpretation of Regulations Document METAL SUSPENSION SYSTEMS FOR LAY-IN PANEL CEILINGS: 2001 CBC IR 25-2.01 References: 2001

More information

Reference Information:

Reference Information: Solar PV Simplified Standard Permit Application Requirements For: Central/String Inverter(s) & Micro-Inverter(s) Systems for One and Two Family Dwellings SCOPE: Use this application only for utility-interactive

More information

EFFECTIVE DATE: July 1, 2008, unless a later date is cited at the end of a section. [ NMAC - Rp,

EFFECTIVE DATE: July 1, 2008, unless a later date is cited at the end of a section. [ NMAC - Rp, TITLE 14 CHAPTER 10 PART 4 HOUSING AND CONSTRUCTION ELECTRICAL CODES 2008 NEW MEXICO ELECTRICAL CODE 14.10.4.1 ISSUING AGENCY: The Construction Industries Division of the Regulation and Licensing Department.

More information

Code of practice for protective earthing of electrical installations

Code of practice for protective earthing of electrical installations BS 7430:2011 Incorporating corrigendum No. 1 BSI Standards Publication Code of practice for protective earthing of electrical installations NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT

More information

Part I. Design of Electrical Installation Systems

Part I. Design of Electrical Installation Systems Part I Design of Electrical Installation Systems Chapter 1 Regulations Governing Electrical Installations Whatever type of electrical equipment is installed, it has to be connected by means of cables and

More information

CHAPTER LOCAL AMENDMENTS TO THE NATIONAL ELECTRICAL CODE 2011 EDITION

CHAPTER LOCAL AMENDMENTS TO THE NATIONAL ELECTRICAL CODE 2011 EDITION CHAPTER 23.30 LOCAL AMENDMENTS TO THE NATIONAL ELECTRICAL CODE 2011 EDITION Sections 23.30.010 Local amendments to the National Electrical Code 2011 Edition.... 1 23.30.020 Certificate of fitness - right

More information

IMPORTANT CODE UPDATE ENFORCEMENT DATE FOR NEW NATIONAL ELECTRIC CODE IS SET FOR MAY 1, 2013

IMPORTANT CODE UPDATE ENFORCEMENT DATE FOR NEW NATIONAL ELECTRIC CODE IS SET FOR MAY 1, 2013 IMPORTANT CODE UPDATE ENFORCEMENT DATE FOR NEW NATIONAL ELECTRIC CODE IS SET FOR MAY 1, 2013 2011 National Electrical Code (NEC) Update Statement The National Electrical Code, 2011 Edition, with Appendices,

More information

AtlasSound.com 1/5 FAP82T. Strategy Series II 8" In-Ceiling Speaker System FAP82T. FAP82T (Pendulum Eyebolt & Phoenix / Euro Style Connector) Features

AtlasSound.com 1/5 FAP82T. Strategy Series II 8 In-Ceiling Speaker System FAP82T. FAP82T (Pendulum Eyebolt & Phoenix / Euro Style Connector) Features Strategy Series II 8" In-Ceiling Speaker System Specifications Woofer Size 8" (203mm) Woofer Impedance 8Ω Direct Coupled (Nominal) Transformer Taps 1.9, 3.8, 7.5, 15, 30, & 60 Watts & 8Ω Bypass Power Handling

More information

SECTION AIR-TO-AIR ENERGY RECOVERY EQUIPMENT

SECTION AIR-TO-AIR ENERGY RECOVERY EQUIPMENT SECTION 23 72 00 AIR-TO-AIR ENERGY RECOVERY EQUIPMENT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

TABLE OF CONTENTS Public Safety Building

TABLE OF CONTENTS Public Safety Building DOCUMENT 00 01 10 - TABLE OF CONTENTS VOLUME I DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS 00 01 10 Table of Contents 00 31 32 Geotechnical Data DIVISION 01 GENERAL REQUIREMENTS 01 10 00 Summary

More information

A. This Section includes steel cable trays and accessories.

A. This Section includes steel cable trays and accessories. SECTION 26 05 36 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1.

.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1. PAGE 1 PART 1 GENERAL 1.1 REFERENCE.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1. 1.2 RELATED WORK SPECIFIED ELSEWHERE.1 Cast

More information

EAL Assessment Route Summary

EAL Assessment Route Summary Performing Engineering Operations QPEO2/034N Credit Value: 13 QCF Level: 2 GLH: 65 Forming and assembling electrical cable enclosure Learner Name: EAL Assessment Route Summary This EAL assessment route

More information

City of Rohnert Park Building Department Inspection Descriptions

City of Rohnert Park Building Department Inspection Descriptions 200 SITE REVIEW: Prior to a permit being issued the Fire / Building Department is authorized to examine existing buildings, structures, and site for which an application has been filed. 201 PRECONSTRUCTION

More information

UBC Technical Guidelines Section Edition Thermal Insulation for Piping Page 1 of 5

UBC Technical Guidelines Section Edition Thermal Insulation for Piping Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Refer to Division 33 and Division 23 - Underground Steam and Condensate Piping.2 Refer to Division 23 - Steam and Condensate Piping Above Grade 1.2

More information

ROCKFON SYSTEM T24 X

ROCKFON SYSTEM T24 X System description ROCKFON SYSTEM T24 X Concealed ceiling system Continuous expression GRP SYSTE E asy integration of services X EDGE WAR YEARS IT LIM ED Quick and easy to install M NT Y L ow installation

More information

Rockfon System Maxispan T24 A, E

Rockfon System Maxispan T24 A, E System description Rockfon System Maxispan T24 A, E Ceiling systems for special applications Corridor A-EDGE GRP SYSTE M WAR YEARS NT Y U p to 3 m span due to the strength of the profiles N o need for

More information

SECTION BASIC ELECTRICAL REQUIREMENTS

SECTION BASIC ELECTRICAL REQUIREMENTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions, apply to work of this section. 1.2 SUMMARY A. This section specifies

More information

DIVISION 5 METALS SECTION COLD-FORMED METAL FRAMING

DIVISION 5 METALS SECTION COLD-FORMED METAL FRAMING DIVISION 5 METALS SECTION 05 40 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

.4 United States of America, Federal Communications Commission (FCC).1 FCC (CFR47) EM and RF Interference Suppression.

.4 United States of America, Federal Communications Commission (FCC).1 FCC (CFR47) EM and RF Interference Suppression. Page 1 1 General 1.1 REFERENCES.1 American National Standards Institute (ANSI).1 ANSI C82.1-1995, Specifications For Fluorescent Lamp Ballasts..2 ANSI C82.4-1992, Ballasts for High-Intensity-Discharge

More information

DPN6C/ CRN/ Original (To the person ordering the work) A. DETAILS OF THE CLIENT

DPN6C/ CRN/ Original (To the person ordering the work) A. DETAILS OF THE CLIENT Contractor s Reference Number CRN/ A. DETAILS OF THE CLIENT Client: Address: B. PURPOSE OF THE REPORT Purpose for which this report is required: MR M REYNARD The Old Rectory Rectory Lane Barham Canterbury

More information

SECTION GROUNDING

SECTION GROUNDING SECTION 16450 GROUNDING PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies general grounding and bonding requirements of electrical and telecommunication installations for personnel safety, equipment

More information

PROJECT MANUAL FOR: HUMPHREYS CO. SHERRILL BUILDING RENOVATIONS: NEW URGENT CARE CLINIC & EXTENSION SERVICE OFFICE

PROJECT MANUAL FOR: HUMPHREYS CO. SHERRILL BUILDING RENOVATIONS: NEW URGENT CARE CLINIC & EXTENSION SERVICE OFFICE PROJECT MANUAL FOR: HUMPHREYS CO. SHERRILL BUILDING RENOVATIONS: NEW URGENT CARE CLINIC & EXTENSION SERVICE OFFICE HUMPHREYS COUNTY BOARD OF SUPERVISOR BELZONI, MISSISSIPPI APRIL 20, 2016 EMILY POOLE ARCHITECTURE,

More information

SECTION NON-STRUCTURAL METAL FRAMING

SECTION NON-STRUCTURAL METAL FRAMING SECTION 09 22 16 PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories

More information

Installation guide. ROCKFON System Z mm. 600 mm

Installation guide. ROCKFON System Z mm. 600 mm Installation guide 600 mm ROCKFON tiles with the D edge detail are suitable for installation using this system. The following ceiling tile module sizes (mm) can be used with : 1500 x 600 1800 X 600 100

More information

DATA SHEET Single Core 2HR Fire Rated Cable

DATA SHEET Single Core 2HR Fire Rated Cable Features: 2HR Fire Rated 0.6/1kV Insulation Rating 110 o C Continuous Operation AS/NZS 3013 WS52W AS/NZS 5000.1 AS/ACIF S008 RCM Certified Low Smoke Zero Halogen Flame Retardant Flexible Class 6 Conductors

More information

City of Santa Monica Building and Safety Division

City of Santa Monica Building and Safety Division This is to be used as a general checklist; it is not inclusive of all code requirements and inspection criteria. General requirements Verify that address on permit matched Address, Description and Approvals:

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Notice to Bidders

More information

FIRE PROTECTION. GTEC Shaftwall systems 244 GTEC Shaftwall Stairwell systems 248 GTEC Horizontal Shaftwall systems 249 GTEC Encasement systems 250

FIRE PROTECTION. GTEC Shaftwall systems 244 GTEC Shaftwall Stairwell systems 248 GTEC Horizontal Shaftwall systems 249 GTEC Encasement systems 250 FIRE PROTECTION GTEC Shaftwall range uses a specially designed system to protect voids and shafts in buildings. It resists pressure changes and enables installation from one side of the shaft only. GTEC

More information

Sections through of Chapter 5 of the Victoria City Code are amended to read as follows: ARTICLE IX. NATIONAL ELECTRICAL CODE

Sections through of Chapter 5 of the Victoria City Code are amended to read as follows: ARTICLE IX. NATIONAL ELECTRICAL CODE Sections 5-100 through 5-105 of Chapter 5 of the Victoria City Code are amended to read as follows: ARTICLE IX. NATIONAL ELECTRICAL CODE Sec. 5-100. Adoption of published code. There is hereby adopted

More information

Wind Power Solutions. Company Registration No: Vat Registration No.:

Wind Power Solutions. Company Registration No: Vat Registration No.: Wind Power Solutions Foundation Grounding and Construction, Bonding, Power Connections, Surge Protection, and Lightning Protection ERICO offers a complete range of foundation grounding and construction,

More information

The Passive Fire Protection Handbook

The Passive Fire Protection Handbook The Passive Fire Protection Handbook The UK s comprehensive guide to passive fire protection Chapter Ceilings, Floors and Roofs AUGUST 0 The Passive Fire Protection Handbook Contents Chapter : Introduction

More information

RESIDENTIAL QUICK REFERENCE

RESIDENTIAL QUICK REFERENCE RESIDENTIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR

More information

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL 8.01 GENERAL This material is not intended to cover service from OPPD s network in the downtown Omaha area. See Chapter 12 for details

More information

Knauf C-Form Suspended Ceilings

Knauf C-Form Suspended Ceilings Knauf C-Form Suspended Ceilings The Knauf C-Form Suspended Ceiling system uses the minimum number of different components and is extremely easy and quick to install. The system is very strong and perfect

More information

SEMPEO SQA Unit Code FP3G 04 Forming and assembling electrical cable enclosure and support systems

SEMPEO SQA Unit Code FP3G 04 Forming and assembling electrical cable enclosure and support systems Forming and assembling electrical cable enclosure and support Overview This standard covers a broad range of basic competences that you need to form and assemble electrical cable enclosure and support

More information

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS SECTION 270528 PATHWAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Communications equipment coordination and installation. 2. Sleeves for pathways and cables. 3. Raceway

More information

SECTION ACOUSTICAL CEILINGS (CEMENTITIOUS WOOD FIBER CEILINGS)

SECTION ACOUSTICAL CEILINGS (CEMENTITIOUS WOOD FIBER CEILINGS) Tectum Inc. 105 South Sixth Street Newark, OH 43055 Phone: (888) 977-9691 Phone: (740) 345-9691 Fax: (800) 832-8869 E-mail: info@tectum.com www.tectum.com This MANU-SPEC utilizes the Construction Specifications

More information

PT. Swd Engineering Consultant

PT. Swd Engineering Consultant Spec.No.1525017/E/JICT LEVEL 2ND & HELPDESK LEVEL GROUND/V/2015 Page 1 CONTENTS SECTION DESCRIPTION Page No. SECTION : 1 - GENERAL 2 SECTION : 2 - TESTING AND COMMISSIONING 5 SECTION : 3 - MAINTENANCE

More information

2015 Fourth Quarter. (Base Year 2013) Detailed by: Main building materials and. services groups. Construction Cost Index

2015 Fourth Quarter. (Base Year 2013) Detailed by: Main building materials and. services groups. Construction Cost Index To w e r b u i l d i n g s p r o j e c t s 2015 Fourth Quarter (Base Year 2013) Detailed by: Main building materials and Release Date: March Construction Cost2016 Index 1 services groups Table of Contents

More information

PAGE 415. Part 9. External works. 9.1 Garages. 9.2 Drives, paths and landscaping

PAGE 415. Part 9. External works. 9.1 Garages. 9.2 Drives, paths and landscaping PAGE 415 Part 9 External works 9.2 Drives, paths and landscaping Part 9 External works Chapter CONTENTS SCOPE Clause DESIGN Design standards D1 1 Statutory requirements D2 1 Garage foundations D3 1 Garage

More information

DIRECTORATE OF ESTATES

DIRECTORATE OF ESTATES DIRECTORATE OF ESTATES PROCEDURE AND INFORMATION MANUAL EPM PM8 Standard Electrical Specification Document Originated: January 2006 By: Mike Bailey Issue Number: 2 Number of pages: 28 Approved by EMG:

More information

Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD.

Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD. Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD. Included are selected sections of codes taken directly from: 1997 Uniform

More information

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL). 16450 GROUNDING ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 26 An optional keynote to the

More information

SECTION COMPOSITE CORE ACOUSTICAL PANEL CEILINGS. Sound-Rite Inc. #9, rd Avenue NE Calgary, AB T2A 7P3

SECTION COMPOSITE CORE ACOUSTICAL PANEL CEILINGS. Sound-Rite Inc. #9, rd Avenue NE Calgary, AB T2A 7P3 SECTION 09510 COMPOSITE CORE ACOUSTICAL PANEL CEILINGS Sound-Rite Inc. #9, 2821 3rd Avenue NE Calgary, AB T2A 7P3 Tel 403-296-0505 Fax 403-296-0511 Email info@sound-rite.com Web www.sound-rite.com Techstyle

More information

Forming and assembling electrical cable enclosure and support systems

Forming and assembling electrical cable enclosure and support systems Unit 034 Forming and assembling electrical cable Level: 2 Credit value: 13 NDAQ number: 500/9514/6 Unit aim This unit covers the skills and knowledge needed to prove the competences required to form and

More information