1 BRE: Behaviour of thermal rehabilitated façades in case of fire Octavian Lalu PhD Fire Safety Group Part of the BRE Trust
2 Presentation structure Types of façade systems Examples of fires involving combustible insulation materials Design recommendations Experimental research medium scale, large scale and modelling Conclusions
3 Types of façade systems Ventilated façade composite systems Execution detail Reduced time of execution Aesthetic system, which does not bring considerable load to on the structure
4 Types of façade systems External Thermal Insulation Composite System (ETICS) Execution detail Over 5000 building rehabilitated in Bucharest No studies on fire behaviour
5 Examples of fire involving combustible insulation materials
6 Examples of fires involving combustible façades Office Building, Bucharest 2009 Millennium Business Centre 72 m height
7 Examples of fires involving combustible façades Block of flats, Romania 2012 Vertical fire spread Burning droplets Façade system after fire
8 Examples of fires involving combustible façades Block of flats, Hungary 2009 Façade system after fire
9 Fire examples Block of flats, South Korea 2015
10 Fire examples High rise buildings Tamweel Tower 2012 Al Tayer Tower 2012 Address Downtown Hotel 2016
11 Fire examples Residential building, Russia 2014 Experimental work
12 Design recommendations
13 Design recommendations Design recommendations in Romania Horizontal barriers A2-s1,d0 Barriers around windows A2-s1,d0
14 Design recommendations Design recommendations in Germany
15 Design recommendations Design recommendations proposed by VTT Finland Installation on facades Experimental research
16 Large Scale Standard Testing LEPIR II Large Scale test BS 8414 Large Scale test
17 Experimental research medium scale, large scale and modelling
18 Experimental Research - Medium Scale Tests System I ETICS, no fire barrier System II ETICS with fire barrier, d = 30 cm d = 30 cm
19 Experimental Research - Medium Scale Tests System III ETICS, with fire barrier, d = 50 cm System IV ETICS with fire barrier, d = 30 cm d = 50 cm d = 30 cm
20 Experimental Research - Medium Scale Tests System V ETICS, with System VI ETICS with composite composite fire barrier, d = 50 cm fire barrier, d = 50 cm d = 50 cm d = 50 cm
21 Experimental Research Medium Scale Tests System I System II System III
22 Experimental Research Medium Scale Tests System IV System V System VI
23 Experimental Research Medium Scale Tests System I System III System IV System II 35 cm 35 cm 50 cm 50 cm 35 cm 38 cm
24 Experimental Research Medium Scale Tests System V System VI 100cm Composite fire barrier Composite fire barrier System II 50cm 50cm 50cm 50cm 37cm 35cm
25 Experimental Research Large Scale Test Compartment layout
26 Experimental Research Large Scale Test ETICS with composite fire barriers
27 Experimental Research Large Scale Test Fire load distribution
28 Experimental Research Large Scale Test The fire is limited by the oxygen level min 16,5 / t=990s Ventilation procedure development phase min 23,5 / t=1410s
29 Large Scale Experimental Research Flashover at min 29 / t=1740s Fully developed phase min 32,5 / t=1950s
30 Large Scale Experimental Research Cooling phase min 70,5 / t=4320s Modele parametrice de temperatura-timp Temperatura [ o C] EC1 Ma&Makelainen Lie BFD Barnett Experimental Ma&Makelainen adaptat Timp [min]
31 Large Scale Experimental Research Cooling phase min 57,5 / t=3450s Cooling phase min 70,5 / t=4320s
32 Large Scale Experimental Research
33 Large Scale Experimental Research - results 1200 Modele parametrice de temperatura-timp 1000 Temperatura [ o C] EC1 Ma&Makelainen Lie BFD Barnett Experimental Ma&Makelainen adaptat Timp [min] min 38 / t=2280s min 42,5 / t=2550s
34 Large Scale Experimental Research Post-fire analysis
35 Large Scale Experimental Research Post-fire analysis Second floor First floor
36 Conclusions
37 Conclusions The use of combustible materials in the façades systems of tall building represents an increase risk of fire spread Real behaviour of façades can be determined only through large-scale testing There is a need of harmonised European large-scale testing method for façade systems The risk of vertical fire spread on façades can be reduced by appropriate design solutions fire barriers A new design composite fire barrier has been tested and the results shown that it has the potential to reduce vertical fire spread
38 Thank you for your attention! Part of the BRE Trust QUESTIONS
6/16/2016. A FORENSIC EXAMINATION OF TALL BUILDING FACADE FIRES l Building Envelope Fires in Dubai Skyscrapers. Martin Edwards. The Address (Atkins)
A FORENSIC EXAMINATION OF TALL BUILDING FACADE FIRES l Building Envelope Fires in Dubai Skyscrapers Martin Edwards The Address (Atkins) 2016 - Probyn Miers 2010 Ltd ProbhynMiers Ltd 1 The Address Downtown
More informationExecutive summary. Fire Hazards of Exterior Wall Assemblies Containing Combustible Components v
Executive summary It is recognized from past experience that fire spread from floor to floor and over the façade in buildings can be a catastrophic event. The regulatory and test based methodology to address
More informationCombustible materials in façades should they be banned?
Combustible materials in façades should they be banned? Dr Kate Nguyen & Prof. Priyan Mendis Innovative Fire Engineering Group The University of Melbourne Façade fires Hotel building - Rostov-on-Don, Russia
More informationeuropean fire standards and national legislation
1 european fire standards and national legislation An Introduction Current testing and standards In the past, manufacturers, designers and specifiers in the Internal Market had to cope with a lack of meaningful
More informationBRE Global Test Report
BRE Global Test Report BS 8414-1:2015 + A1:2017 test on ventilated façade system with Kingspan (K15) thermal insulation and ACM panels Prepared for: Date: 18 January 2017 Mitsubishi Chemical Corporation
More informationEvaluating Fire Performance of Facade Assemblies Using ANSI/FM 4880
Evaluating Fire Performance of Facade Assemblies Using ANSI/FM 4880 Yi Wang FM Global 5 th International Tall Building Fire Safety Conference, June 2018 Recent Façade Fires ACM fire catastrophes Accelerated
More informationFIRE MITIGATION IN FACADE DESIGN & MATERIAL CHOICE
FIRE MITIGATION IN FACADE DESIGN & MATERIAL CHOICE By Satria Ramadhana 1. MECHANISM OF FIRE SPREAD IN FACADES AND EXAMPLE OF FIRES INVOLVING BUILDING ENVELOPES 2. PERIMETER CURTAIN WALL FIRE PROTECTION
More informationFire Behaviour in Different Building Types
^ Fire Behaviour in Different Building Types Agenda Single Storey Steel Frame High Rise Purpose Built Domestic Modern Construction Materials / Methods Converted Buildings Evacuations Building design shapes
More informationFIRE STOP & SMOKE SEAL
Fire Protection in Curtain Wall and Façade Systems Ir Dr. Dominic YU Principal Structural Fire and Façade Alpha Consulting Limited Email: dominic@alpha-c.com.hk FIRE STOP & SMOKE SEAL Spread of Fire and
More informationPRODUCT SUSPENDED. Rainscreen Cladding Compliance Guide When specifying Celotex RS5000 in buildings above 18 metres
01473 820850 celotex.co.uk Update - IMPORTANT: On 23 June 2017, in view of the focus on components of rainscreen cladding systems, Celotex stopped the supply of Celotex RS5000, pending further clarity.
More informationTitle: ETICS Fire Performance Test. Authors: Ivana Banjad Pečur 1) Dubravka Bjegović 1) Lars Boström 2) Bojan Milovanović 1) Milan Hajduković 3)
Cover page Title: ETICS Fire Performance Test Authors: Ivana Banjad Pečur 1) Dubravka Bjegović 1) Lars Boström 2) Bojan Milovanović 1) Milan Hajduković 3) (FIRST PAGE OF ARTICLE) ABSTRACT With the increasing
More informationThis was followed by a Part 2 experimental scoping study focusing on the issue of external fire spread, to be covered in next month s issue.
1 External fire spread: new research In a two-part feature, BRE Global reports on the latest findings to come out of its work on the Investigation of Real Fires for the Department for Communities and Local
More informationRainscreen Cladding Compliance Guide When specifying Celotex RS5000 in buildings above 18 metres
01473 820850 celotex.co.uk Rainscreen Cladding Compliance Guide When specifying Celotex RS5000 in buildings above 18 metres 1 Rainscreen Cladding Compliance Guide Compliance Guide This document provides
More informationBUS5 Building structures 5: Fire safety
Czech Technical University in Prague FACULTY OF CIVIL ENGINEERING Deptarment of Building Structures BUS5 Building structures 5: Fire safety Excercise 3 Fire Resistance of Building materials Petr Hejtmánek
More informationDesign guide to separating distances during construction, Part 4
TRUCTURAL TIMBER ASSOCIATION Building solutions in timber Design guide to separating distances during construction, Part 4 For CLT type frame buildings Version. - November 204 Thanks to KLH and Binderholz
More informationMulti-storey timber construction in the UK IRCC workshop, Vienna 7 June 2013 Dr Julie Bregulla Dipl-Ing, PhD, CEng, FICE
Multi-storey timber construction in the UK IRCC workshop, Vienna 7 June 2013 Dr Julie Bregulla Dipl-Ing, PhD, CEng, FICE Scope- Inhalt Timber construction UK: Some figures UK market and its drivers: Applications
More informationFire Engineering and Structures a Fire Service View
Fire Engineering and Structures a Fire Service View Eur Ing Dr Jim Marsden CEng CFFireE MEI What are the sprits of the Code? Cost Malta April 2012 Fire Safety Principles Fire Starts Alarm Sounds Evacuation
More informationChanges to the built environment through sustainability and some implications for fire safety
Changes to the built environment through sustainability and some implications for fire safety Prof David Charters, PhD, CEng, FIFireE. MIMechE Director of Fire Engineering Visiting professor of fire risk
More informationHigh Rise Buildings with a Floor Level Above 18m. Meeting the guidance within the Requirements of Approved Document B Volume 2
High Rise Buildings with a Floor Level Above 18m Meeting the guidance within the Requirements of Approved Document B Volume 2 Contents 4 Introduction Introduction... 4 Requirement: Part B of Building Regulations...
More informationBS :2005 test on a Kingspan Benchmark External Wall Insulation System
BS 8414-2:2005 test on a Kingspan Benchmark External Wall Insulation Prepared for: Kingspan Ltd. Carrickmacross Road Kingscourt County Cavan Ireland 7 September 2011 0578 Page 1 of 30 Prepared on behalf
More informationWHOLE BUILDING BEHAVIOUR RESULTS FROM A SERIES OF LARGE SCALE TESTS
Proceedings of the CIB-CTBUH International Conference on Tall Buildings, 8-10 May 2003, Malaysia WHOLE BUILDING BEHAVIOUR RESULTS FROM A SERIES OF LARGE SCALE TESTS T. LENNON Principal Consultant, FRS,
More informationInsights into the behavior of structures in fire and the implication on practice
HKIE Fire Division 9 th Annual Symposium 2017 Insights into the behavior of structures in fire and the implication on practice Asif Usmani Department of Building Services Engineering, Faculty of Construction
More informationBRE Global Classification Report
BRE Global Classification Report Kingspan Ltd. BENCHMARK Engineered Façade system - Metallic Hook on Cassette. Classification of fire performance in accordance with BR 135: 2013 Annex B Prepared for: Kingspan
More informationcombustibility behaviour of insulation products
1 combustibility behaviour of insulation products Smouldering and continuous glowing Smouldering and continuous glowing are slow internal combustion processes that can lead to fires breaking out some distance
More informationAn Applied Engineering Research Project to Evaluate Radiant Heat Exposure of Exterior Walls
An Applied Engineering Research Project to Evaluate Radiant Heat Exposure of Exterior Walls by Fred L. Fisher, P. E., Charles M. Fleischmann, and Donald W. Belles, P.E. The exterior walls of a building
More informationPARAMETRIC HIGH RISE OPTIMIZATION Josh T Mauro B Sandeep A
PARAMETRIC HIGH RISE OPTIMIZATION Josh T Mauro B Sandeep A LOCATION LOCATION SKYLINE SITE FLOW OF WORK OVERVIEW UNDERSTAND OBJECTIVES SINGLE OBJECTIVE OPTIMIZIA TION MULTI OBJECTIVE OPTIMIATION AQUIRING
More informationA Comparative Analysis of the Use of Different External Fire Spread Calculation Methods
A Comparative Analysis of the Use of Different External Fire Spread Calculation Methods (1)Declan Thomson, (2)Paul Currie, and (2)Jianqiang Mai (1)Hoare Lea and Partners (6th Floor Royal Exchange, Manchester,
More informationBRE Global Test Report
BRE Global Test Report BS 8414-2 : 2005 Test on a Gebrik Rainscreen Cladding System Prepared for: Isosystems and Aquarian Cladding Systems Date: 21 September 2015 Report Number: P100838-1000 Issue 2 BRE
More informationBRE Global Classification Report
BRE Global Classification Report Classification of fire performance in accordance with BR 135: 2013 Annex A for a ventilated façade system with Kingspan Kooltherm K15 insulation and Alpolic/fr panels.
More informationFire Hazards of Exterior Wall Assemblies Containing Combustible Components. Final Draft Report
Fire Hazards of Exterior Wall Assemblies Containing Combustible Components Final Draft Report Prepared by: Nathan White CSIRO Highett, VIC, Australia Michael Delichatsios FireSERT, University of Ulster
More informationCavity Barriers: Final Factual Report of the Experimental Programme
Cavity Barriers: Final Factual Report of the Experimental Programme The authors of this report are employed by BRE. The work reported herein was carried out under a Contract placed by the ODPM. Any views
More informationFaçade Particulars of the UAE Code Windows, Doors & Facades Conf. 2017
Façade Particulars of the UAE Code Windows, Doors & Facades Conf. 2017 Andy Dean FCIOB, FSFE Head of Façades Learning objectives 1. Overview of the new code layout 2. Awareness of some of the particulars
More informationFIRE PERFORMANCE OF ARCHAIC MATERIALS. prof. Papaioannou Kyriakos ARISTOTLE UNIVERSITY
FIRE PERFORMANCE OF ARCHAIC MATERIALS prof. Papaioannou Kyriakos ARISTOTLE UNIVERSITY 139 Summary The term archaic material is Greek- American orientated and means a construction or a material of an earlier
More informationBRE Global Test Report
BRE Global Test Report BS 8414-2: 2005 Test on a Kingspan BENCHMARK 220mm QuadCore TM Wall liner panel with a Corium brick system. Prepared for: Kingspan Ltd Date: 7 th November 2016 Report Number: P102340-1000
More informationFire performance of curtain walls and rainscreens
Technical Note No. 73 Fire performance of curtain walls and rainscreens Curtain walls are normally used for areas of the building envelope that are not required to be fire resisting but they still require
More informationWOOD USE IN NONCOMBUSTIBLE BUILDINGS
INTRODUCTION The National Building Code of Canada (NBCC) 1 requires that some buildings be of noncombustible construction under its prescriptive requirements. Its use in certain types of buildings such
More informationWHITE PAPER. Fire Safety of Insulated Metal Wall Panels. by Marcelo Hirschler, GBH International. Introduction
Introduction WHITE PAPER Fire Safety of Insulated Metal Wall Panels by Marcelo Hirschler, GBH International Insulated Metal Panels (IMPs) are lightweight composite exterior wall and roof panels with two
More informationEfficient and smart climate shell. refurbishment of residential buildings PART OF SMART SOLUTION 1: EFFICIENT AND SMART CLIMATE SHELL REFURBISHMENT
6 Efficient and smart climate shell FACTSHEET refurbishment of residential buildings PART OF SMART SOLUTION 1: EFFICIENT AND SMART CLIMATE SHELL REFURBISHMENT Fig. 1: Image: www.idae.es LOW ENERGY DISTRICT
More informationDuco s intrusion-resistant solutions
(en) Duco s intrusion-resistant solutions Ventilation louvres, continuous louvre walls and louvre doors of resistance class Complete range of louvres Complies with European regulation Louvres, continuous
More informationDuco s intrusion-resistant solutions
(en) Duco s intrusion-resistant solutions Ventilation louvres, continuous louvre walls and louvre doors of resistance class Complete range of louvres Complies with European regulation Louvres, continuous
More informationFire Engineering, the BCA (NCC) & Bushfire Calculator. Keith Nicholls - Manager Product Testing and Assessments (Australia) Exova Group Limited
Fire Engineering, the BCA (NCC) & Bushfire Calculator Keith Nicholls - Manager Product Testing and Assessments (Australia) Exova Group Limited Presentation Topics Current Building Code (fire safety) design
More informationModule 8: Ontario Building Code Fire and Spatial Separations
Ontario Building Code (OBC) 1. Fire Separations 2. Fire Resistance Ratings By Classification 3. Fire Resistance Ratings By Adjacent Use 4. Fire Resistance Ratings By Specific Space 5. Fire Resistance Ratings
More informationPOLYCITY Innovation Energy and environmental concepts of the POLYCITY project in Cerdanyola del Vallès CONCERTO POLYCITY
POLYCITY Innovation Energy and environmental concepts of the POLYCITY project in Cerdanyola del Vallès CONCERTO POLYCITY The POLYCITY project 5 Energy supply in the Directional Centre 6 The Cerdanyola
More informationWatermist State of the Art Technology
Watermist State of the Art Technology IWMA Seminar 19 th January 2014 Dubai, UAE By Alex Palle, VID Fire-Kill, Denmark Agenda: 1) Introduction to VID Fire-Kill. 2) What is a fire. 3) What is Watermist
More informationEfficient cooling in a natural and energy-saving way. Large volume flows of outside air provide cooling. Intelligent control
Ventilative cooling NEW Efficient cooling in a natural and energy-saving way Large volume flows of outside air provide cooling Intelligent control No artificial interventions needed (such as air conditioning)
More informationFire safety issues with balconies
Fire safety issues with balconies By Ciara Holland, Martin Shipp and David Crowder of BRE Global Introduction BRE Global carries out fire investigation activities on behalf of the Department for Communities
More informationBRE Global Classification Report
BRE Global Classification Report Classification of fire performance in accordance with BR135:2013 Annex B on a Kingspan BENCHMARK 80mm QuadCore TM Karrier & Dri Design Cassette system. Prepared for: Kingspan
More informationPAROC FIRE PROTECTION SOLUTIONS FOR PIPE PENETRATIONS
PAROC FIRE PROTECTION SOLUTIONS FOR PIPE PENETRATIONS APPROVED FIRE SAFETY WITH PAROC STONE WOOL EN 1366-3 is a harmonized European standard for fire resistance tests for penetration seals. The test method
More informationGood Morning everybody
Good Morning everybody A discussion of fire scenarios and models for steel framed enclosed multi-storey balconies. Gordon Cooke International Fire Safety Consultant ( Formerly Visiting Professor, School
More informationCyprus Energy Agency. Nearly Zero Energy Buildings
Cyprus Energy Agency Nearly Zero Energy Buildings 2009 Energy efficiency of buildings - status 33% of all energy in EU is used for transport 26% of all energy in EU is used by industry 41% of all energy
More informationExterior System installation instructions
Exterior System installation instructions 11/20/14 WPS ES-400 & 500 INSTALLATION INSTRUCTION. The WPS ES-400 & 500 systems Façade panels are designed for use as an external wall cladding in conjunction
More informationOIL POOL FIRE IN A LARGE TURBINE HALL CFD simulation
STUK-YTO-TR 193 / OCTOBER 2002 OIL POOL FIRE IN A LARGE TURBINE HALL CFD simulation Risto Huhtanen (VTT Processes) In STUK this study was supervised by Jouko Marttila STUK SÄTEILYTURVAKESKUS STRÅLSÄKERHETSCENTRALEN
More informationDr.-Ing. Kai Schild. Chair of building physics and building services Univ.-Prof. Dr.-Ing. habil. Wolfgang M. Willems. technische universität dortmund
Current calculation rules for thermal bridges and resulting problems for the practical use Dr.-Ing. Kai Schild 9 th Nordic Symposium on Building Physics, Tampere, Finland, 2011 1 Main topics and questions
More informationConcepts. Products. Service. Providence Tower, London
Concepts Products Service Providence Tower, London 1 Project Report Providence Tower, London New Providence is a luxurious residental tower in the London Docklands on the north end of Blackwall Tunnel.
More informationBRE Global Client Report
BRE Global Client Report BS 8414-1:2015 + A1:2017 test referred to as DCLG test 1. Prepared for: DCLG Date: 27th July 2017 Report Number: B137611-1037 (DCLG test 1) Issue: 1.0 BRE Global Ltd Watford, Herts
More informationKNAUF Therm ETIXX façade λ 31
KNAUF Therm ETIXX façade λ 31 KNAUF Therm ETIXX façade λ 31 polystyrene panels are designated by the following code according to PN-EN standard EN 13163:2012+A1:2015 EPS EN 13163 T(2)-L(2)-W(2)-S(5)-P(5)-BS100-DS(N)5-DS(70,-)2-TR100
More informationNUMERICAL-SIMULATION RESEARCH ON BUILDING-FACADE GEOMETRY AND ITS EFFECT ON FIRE PROPAGATION IN WOODEN FACADES
NUMERICAL-SIMULATION RESEARCH ON BUILDING-FACADE GEOMETRY AND ITS EFFECT ON FIRE PROPAGATION IN WOODEN FACADES María Pilar Giraldo 1, Jaume Avellaneda 2, Ana Lacasta 3, Camila Burgos 4. ABSTRACT: Fire
More informationValue Benefits of Modular Construction in Building Extensions
Value Benefits of Modular Construction in Building Extensions SPEED OF INSTALLATION Extensions to existing buildings using modular units can be constructed in less than 50% of the time required for conventional
More information447 - Thermal Performance of Residential Buildings in Lisbon with Large Glazing Areas
447 - Thermal Performance of Residential Buildings in Lisbon with Large Glazing Areas M. Tavares *, H. Gonçalves and J. Bastos INETI, Department of Renewable Energies, Campus do Lumiar do INETI, 649-38
More informationPrecast Concrete Hollow Core Slabs in Fire. By Tom Lennon, Principal Consultant, BRE
Precast Concrete Hollow Core Slabs in Fire By Tom Lennon, Principal Consultant, BRE Synopsis Following concerns expressed in the media in relation to the performance of hollow core slabs in fire two full-scale
More information8414-1: A1:2017
www..co.uk RE Global Client Report BS 8414-1:2015 + A1:2017 Test referred to as DCLG test 7. Prepared for: Date: Report Number: DCLG 18th August 2017 B137611-1037 (DCLG test 7) Issue: 2.0 BRE Global Ltd
More informationREQUESTED BY : Atlas Roofing and Flooring PO Box Queenswood CONTRACT No : FTC12/088. AUTHOR(S) : K. van Dyk. DATE : 13 September 2012
TITLE : Report on the small-scale fire properties of a Structural Insulated Panel System (SIPS) product when used as a roofing material and exposed to a fire originating inside the structure REQUESTED
More informationExterior Wall Systems NFPA 285
Exterior Wall Systems NFPA 285 Presented by: David Hintz Senior Project Engineer UL and the UL logo are trademarks of UL LLC 2014 Exterior Wall Systems Why Do We Test? A broad range of components that
More informationEngineering Analysis of NFPA 285 Tested Assemblies
Engineering Analysis of NFPA 285 Tested Assemblies Introduction Foam plastics used in buildings of Types I-IV construction require an assessment of their ability to resist vertical and lateral flame spread
More informationNearly zero energy building renovation, the EU-GUGLE project Javier Llorente Yoldi
Nearly zero energy building renovation, the EU-GUGLE project Javier Llorente Yoldi jllorente@cener.com In a nutshell European cities serving as Green Urban Gate towards Leadership in sustainable Energy
More informationDesign guide to separating distances during construction
Design guide to separating distances during construction For timber frame buildings and projects above 600m 2 total floor area Part 3 - Timber frame build methods to reduce the separating distances Version
More informationThe experimental programme for this stage of the project has been undertaken in three phases:
Annex A Floor Voids General In order to investigate the potential for unseen fire spread to occur through voids in suspended floor systems, a series of experiments have been undertaken utilising a commercially
More informationAn Adaptable Façade Concept for Sustainable Office Refurbishment
Session B-4: Developments of Activation Technologies An Adaptable Façade Concept for Sustainable Office Refurbishment Thiemo EBBERT, Ph. D. 1 Ulrich KNAACK² 1 2 Delft University of Technology, Faculty
More informationDELIVERING THE FUTURE OF COMPOSITE SOLUTIONS CIVIL & ARCHITECTURAL FIRE REQUIREMENTS APPLIED TO COMPOSITE STRUCTURES.
DELIVERING THE FUTURE OF COMPOSITE SOLUTIONS CIVIL & ARCHITECTURAL FIRE REQUIREMENTS APPLIED TO COMPOSITE STRUCTURES gurit@gurit.com www.gurit.com INTRODUCTION Building regulations ensure that, in case
More informationCERTIFICATE No VTT-C Date of issue
NAME OF PRODUCT CERTIFICATE No VTT-C-9190-12 Date of issue 3.12.2012 CERTIFICATE HOLDER ACTIS SA Avenue de Catalogne 11300 Limoux France MANUFACTURER ACTIS SA PRODUCT DESCRIPTION is a vapour control multifoil
More informationEffect of energy renovation on thermal sensation and comfort
Effect of energy renovation on thermal sensation and comfort 9th Nordic Symposium on Building Physics Riikka Holopainen VTT Technical Research Centre of Finland 2 Human Thermal Model (HTM) developed for
More informationBuilding Envelope Systems AE 544 Course Notes
Building Envelope Systems AE 544 Course Notes By Dr. Ahmad A. Hamid, Ph.D., P.E. Professor Department of Civil, Architectural and Environmental Engineering Drexel University, Philadelphia, PA 251 895 2342
More informationAPPENDIX 3C DOMINION HOTEL SPECIFICATIONS
APPENDIX 3C DOMINION HOTEL SPECIFICATIONS 1. GENERAL 1.1 Refer to Section 2.1 of Schedule 3 [Design and Construction Specifications] regarding compliance with Schedule 3 and this Building Specification.
More informationFIRST ROMANIAN PUBLIC NZEB PROPOSAL FOR A FUTURE EU PROJECT
11:41 FIRST ROMANIAN PUBLIC NZEB PROPOSAL FOR A FUTURE EU PROJECT Associate Professor Cătălin LUNGU PhD, FII-UTCB & AIIR SOURCE: REHVA NZEB TC 1 11:41 SUMMARY 1. GENERAL CONTEXT & RO-NZEB CONSORTIUM 2.
More information- The Essential Elements. Andy Dean on OFFICIAL PUBLICATION OF THE FIRE & SECURITY ASSOCIATION OF INDIA (FSAI) Special Issue
www.fsai.in Special Issue www.fsaijournal.in ` 90 Andy Dean on And - The Essential Elements OFFICIAL PUBLICATION OF THE FIRE & SECURITY ASSOCIATION OF INDIA (FSAI) Fire and Façades The Essential Elements
More informationIntegrity of Compartmentation in Buildings During a Fire. Tom Lennon 30 th September 2004, BRE, Garston
Integrity of Compartmentation in Buildings During a Fire Tom Lennon 3 th September 24, BRE, Garston Background Review of Approved Document B Use of structural fire engineering New forms of construction
More informationCombustible Exterior Wall Cladding Systems: An ICC Perspective
Combustible Exterior Wall Cladding Systems: An ICC Perspective The tragic Grenfell Tower fire in London brought extensive public focus on combustible exterior wall systems, often called cladding, prompting
More informationSPECIFICATIONS:
GREEN PLANET SUSPENDED CEILING INSULATION SYSTEM SPECIFICATIONS: 18.7.2014 This insulation system is comprised of two separate items: 1) Green Planet Encapsulated Insulation Pads. 2) Green Planet Radiant
More informationESR-1061 Reissued May 1, 2011 This report is subject to renewal in two years.
ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION Section: 07 21 00 Thermal Insulation Section: 07 25 00 Water-Resistive Barriers/Weather
More informationStructural failure and the Twin Towers. Dr Barbara Lane CEng
Structural failure and the Twin Towers Dr Barbara Lane CEng What lessons from the WTC event apply to other more typical building forms? Everyone loves a good conspiracy theory.. Is there any scientific
More informationWildland Fire Physics 01-1-S190-EP
Wildland Fire Physics 01-1-S190-EP Introduction Control Line: Comprehensive term used for all the constructed or natural fire barriers and treated fire edges used to control the fire. Fireline: Any cleared
More informationREPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:
0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3089 Reissued 07/2016 This report is subject to renewal 07/2018. DIVISION: 07 00
More informationCOMPUTER-SIMULATION RESEARCH ON BUILDING-FACADE GEOMETRY FOR FIRE SPREAD CONTROL IN BUILDINGS WITH WOOD CLADDINGS.
COMPUTER-SIMULATION RESEARCH ON BUILDING-FACADE GEOMETRY FOR FIRE SPREAD CONTROL IN BUILDINGS WITH WOOD CLADDINGS. M. Pilar Giraldo 1, Jaume Avellaneda 2, Ana M. Lacasta 3, Vladimir Rodríguez 4. ABSTRACT:
More informationKoniklecová 4, Brno-Nový Lískovec
Koniklecová 4, Brno-Nový Lískovec Project summary Energy concept: Renovation to low-energy / passive house standard Background for the renovation reasons: Intention for the renovation: Overall modernization
More informationFEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF
FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF Oliver Baumann 1, and Claudius Reiser 1/2 1 Ebert & Baumann Consulting Engineers, Washington, D.C. 2 Ebert-Ingenieure GmbH &Co. KG, Munich,
More informationKnowledge Objectives (3 of 3)
Building Systems Knowledge Objectives (1 of 3) Identify construction types in commercial and residential structures. Explain fire behavior as it relates to the method of construction. Discuss the structural
More informationApril Section Cladded Walls
April 2012 Section Cladded Walls Cladded Walls Cladded walls Rainscreen cladding and curtain wall systems Rainscreen cladding systems There are a wide variety of proprietary rainscreen cladding systems
More informationEnergy study of a non-residential and historic building in transient conditions
Energy and Sustainability VI 511 Energy study of a non-residential and historic building in transient conditions S. Grignaffini, M. Romagna & A. Vallati Department of Astronautical, Electrical and Energetic
More informationOPEN COMPETITION Energy Design of High Performance Buildings Organised by EC-JRC and ESRU
OPEN COMPETITION Energy Design of High Performance Buildings Organised by EC-JRC and ESRU Target group: under-graduate, postdoc, PhD students and researchers level SUMMARY The objective is to assess for
More informationBUILDING CODE COMMISSION
Ruling No. 02-04-859 Application No. 2001-81 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentences 3.2.3.7.(7)
More informationI Prophets energy services
CIBSE LOW CARBON CONSULTANTS REGISTER SESSION 7 BUILDING REGULATIONS APPROVED DOCUMENT L2B I Prophets energy services 03012013 Key Features Slide 4 ADL2B Details Slide 13 Controlled Fittings Slide 20 Controlled
More information(904) FAX (904) The Intermodal Hardware Specialists. Therm-Cool
(904) 696-0010 FAX (904) 696-0019 e-mail sales@buffersusa.com The Intermodal Hardware Specialists BUFFERS USA, INC. 10180 New Berlin Rd. Jacksonville, FL. 32226 Therm-Cool Thermal Insulated Bulkhead Product
More informationGeneral Commercial Energy Provisions
PART II General Commercial Energy Provisions Section 3: General Commercial Energy Provisions Section 4: Administration and Enforcement Mmaxer/www.Shutterstock.com 19 Section 3 General Commercial Energy
More informationCouncil on Tall Buildings and Urban Habitat
Advanced Super Tall Building Design with the Hot-summer and Cold-winter Climate Jianqiang Li, PhD, LEED AP Shanghai Institute of Architectural Design & Research (Co.Ltd.) Contents 1. Introduction 2. Climate
More informationMid-rise Timber Buildings Proposal for Change. Colin MacKenzie Technical Consultant
Mid-rise Timber Buildings Proposal for Change Colin MacKenzie Technical Consultant FWPA programs Mid-rise Timber Buildings Background New engineered timber products and building systems are now being used.
More informationVENTILATED FIRE BARRIERS FOR EXTERNAL CLADDING AND RAINSCREEN SYSTEMS
VENTILATED FIRE BARRIERS FOR EXTERNAL CLADDING AND RAINSCREEN SYSTEMS TENMAT is a leading manufacturer of unique, high performance intumescent materials and solutions with over 30 years of passive fire
More informationLEEDS : LEEDS UNIVERSITY
STAGE @ LEEDS : LEEDS UNIVERSITY Client : Leeds University Project Manager : Leeds University Structural Engineer : Bland and Swift Services Consultant : Preston Lee Chambers Contractor : Brenville Construction
More informationPost Tower Bonn, Germany
Winner 10 Year Award Post Tower Bonn, Germany The design single-handedly changed the way we look at façade and office design to date. It has become an exemplar sustainable icon in contemporary architecture.
More informationBRE Global Ltd Watford, Herts WD25 9XX. d+b facades (UK) Ltd. The Packway, Larkhill, Salisbury, SP4 8PY. Customer Services
BRE Global Test Report BS 8414-1:2015 + A1:2017 test on d+b facades rain screen cladding system with 100mm-thick Rockwool insulation and aluminium cassette panels. Prepared for: d+b facades (UK) Ltd. Date:
More information